JILA ADDITION
F: 303.421.0331
303 EAST 17TH AVENUE SUITE 1000 DENVER, COLORADO 80203 303.764.1520
MECHANICAL LEGEND
M−101
PUMP SCHEDULEMAX. TOTAL VIBRATION SUCTION DISCHARGE
DESIG. MFR. MODEL PUMP TYPE SERVICE OPER. TEMP. GPM DYNAMIC EFF. MIN. RPM ISOLATOR SIZE SIZE CONTROL REMARKS°F HEAD (FT.) % HP TYPE (IN.) (IN.)
CWP-1A B & G END SUCTION MAIN CHILLED WATER DISTRIBUTION 600 60 25
CWP-1B B & G END SUCTION MAIN CHILLED WATER DISTRIBUTION 600 60 25 1
CWP-2A B & G INLINE PROCESS CHILLED WATER PUMP 180 30 5
CWP-2B B & G INLINE PROCESS CHILLED WATER PUMP 180 30 5 1
HWP-1A B & G INLINE GLYCOL HEATING WATER PUMP 115 50 5
HWP-1B B & G INLINE GLYCOL HEATING WATER PUMP 115 50 5 1
HWP-2A B & G INLINE HEATING WATER PUMP 70 70 5
HWP-2B B & G INLINE HEATING WATER PUMP 70 70 5 1
CP-1A B & G INLINE AHU-1 CW COIL PUMP 1
CP-1B B & G INLINE AHU-1 HW COIL PUMP 1
CP-2A B & G INLINE AHU-2 CW COIL PUMP 2
CP-2B B & G INLINE AHU-2 HW COIL PUMP 2
CP-3A B & G INLINE MAU-1 CW COIL PUMP 1/2
CP-3B B & G INLINE MAU-1 HW COIL PUMP 1/2
NOTES:
1. 100% REDUNDANT PUMP
1/11/2010 16:44 P:\CU\Boulder\2008-124 JILA Addition\Cad\Acad2004\Mech\Mschedules\[M-2008-124.xls]S540-1 Pump
FAN COIL UNIT SCHEDULEFAN DATA COIL DATA
CFM MOTOR EAT LAT WATERDESIG. MFR. MODEL ARRANG. TOTAL ESP WATTS SERVICE °F °F °F °F MBH GPM CONTROL REMARKS
AT 5400' DB WB DB WB FT.W.C.
FCU-1 TRANE NOTES 1-6
FCU-2 TRANE NOTES 1-6
FCU-3 TRANE NOTES 1-5, 7
FCU-4 TRANE NOTES 1-5, 7
FCU-5 TRANE NOTES 1-5, 7
FCU-6 TRANE NOTES 1-5, 8
FCU-7 TRANE NOTES 1-5, 8
FCU-8 TRANE NOTES 1-5, 9
NOTES:1. EXTERNAL STATIC PRESSURE DOES NOT INCLUDE UNIT CASING, FILTERS OR COILS.2. HEATING COIL CAPACITY BASED ON 160°F EWT, 140°F LWT.3. CHILLED WATER COOLING COIL CAPACITY BASED ON 50°F EWT, 60°F LWT .4. PROVIDE FLOAT SWITCH IN DRAIN PAN TO DISABLE UNIT WHEN WATER LEVEL IS ABOVE DRAIN5. UNIT CFM/COIL CAPACITIES BASED ON (MEDIUM) SPEED OPERATION.6. PROVIDE UNIT CAPABLE OF BEING CEILING FLUSH MOUNTED W/ BOTTOM RETURN AND DUCTED SUPPLY IN LABS, AND PLENUM RETURN AND DUCTED SUPPLY - LOCATED ABOVECEILING IN ALL OTHER AREAS.7. PROVIDE UNIT W/ DUCTED SUPPLY AND PLENUM RETURN - LOCATED ABOVE CEILING.8. PROVIDE CEILING FLUSH MOUNTED UNIT W/ BOTTOM SUPPLY AND RETURN.9. PROVIDE UNIT W/ DUCTED SUPPLY AND BOTTOM RETURN MOUNTED FLUSH IN CEILING W/ REMOVEABLE ACCESS PANEL/RETURN GRILLE.1/11/2010 16:53
CONVECTOR SCHEDULEDESIG. MFR. MODEL SERVICE ARRANG. RECESS LENGTH HEIGHT DEPTH MBH GPM DAMPER REMARKS
DEPTH REQUIRED
CV-1 TRANE OFFICE VERTICAL 1.5
1/11/2010 16:54 P:\CU\Boulder\2008-124 JILA Addition\Cad\Acad2004\Mech\Mschedules\[M-2008-124.xls]S830-7 Convector
DUCT PRESSURE CLASSIFICATION SCHEDULEDUCT TYPE PRESSURE CLASS REMARKS
MEDIUM PRESSURE SUPPLY BETWEEN FAN & TERMINAL BOX 4"
LOW PRESSURE SUPPLY BETWEEN TERMINAL BOX & ROOM 2"
MEDIUM PRESSURE EXHAUST BETWEEN FAN & TERMINAL BOX 4"
LOW PRESSURE EXHAUST BETWEEN TERMINAL BOX & ROOM 2"
EXHAUST STACK (VERTICAL) 4"
RETURN AIR DUCTWORK 2"
OUTSIDE AIR DUCTWORK 2"
FUME HOOD EXHAUST 4"
1/11/2010 16:47
FAN SCHEDULEWHEEL CFM S.P. TOTAL TIP OUTLET VIBRATION MAX MIN. APPROX. ARRANGE.
DESIG. MFR. MODEL FAN TYPE SERVICE DIA. AT IN. W.C. CFM APPROX. SPEED VELOCITY MIN. ISOLATOR DRIVE DB(A) PLUME DAMPER THROAT & CONTROL REMARKS(INCHES) 5400' AT 5400' AT 5400' RPM (FPM) (FPM) HP TYPE TYPE AT 10' HT. (FT) TYPE DIM. MOUNTING
EF-1 CENTRIFUGAL DOWNBLAST
GENERAL BLDG EXH. 5,000 0.75 5,000 2 BELT
EF-2A HIGH PLUME DILUTION CORROSIVE LAB EXH. 24.5 6,000 3.0 13,800 1,411 9,050 3,896 7.5 1" SPRING BELT 67 24.0 1,3
EF-2B HIGH PLUME DILUTION CORROSIVE LAB EXH. 24.5 6,000 3.0 13,800 1,411 9,050 3,896 7.5 1" SPRING BELT 67 24.0 1,3,4
EF-3A HIGH PLUME DILUTION CORROSIVE C/R EXH. 19.3 4,000 4.0 9,200 2,318 11,718 4,819 5 1" SPRING BELT 71 21.5 2,3
EF-3B HIGH PLUME DILUTION CORROSIVE C/R EXH. 19.3 4,000 4.0 9,200 2,318 11,718 4,819 5 1" SPRING BELT 71 21.5 2,3,4
NOTES:1. FAN SHALL BE FRP CASING AND EPOXY COATED STEEL WHEEL. PROVIDE FRP PLENUM, ANODIZED ALUMINUM ISOLATION DAMPERS AND BYPASS DAMPER.2. FAN SHALL BE FRP CASING AND FRP WHEEL. PROVIDE FRP PLENUM, FRP ISOLATION DAMPER AND ANODIZED ALUMINUM BYPASS DAMPER. ALL AIR STREAM COMPONENTS TO BE FRP WITH SYNTHETIC VEIL LINER.3. FAN AND DILUTION NOZZLE AS A SYSTEM SHALL BE LICENSED TO BEAR THE AMCA 211 AND 311 SEALS.4. 100% REDUNDANT FAN.
1/12/2010 11:42 P:\CU\Boulder\2008-124 JILA Addition\Cad\Acad2004\Mech\Mschedules\[M-2008-124.xls]S850-1 Fan
SHELL AND TUBE HEAT EXCHANGER SCHEDULESHELL TUBE TUBE SIDE SHELL SIDE HEATING
DESIG. MFR. MODEL SERVICE DIA. LENGTH NO. EWT LWT ÄP FT. EWT LWT STEAM LBS/ SURFACE REMARKS(IN.) (FT.) PASSES °F °F GPM W.C. MBH °F °F GPM INLET PSIG HR (SF)
HX-1A, 1B B&G SU 8 3-2 GLYCOL HEATING WATER 2 150 180 115 1.0 1,600 320 320 -- 75 1,800
HX-2A, 2B B&G SU 6 3-2 HEATING WATER 2 150 180 70 1.0 1,000 320 320 -- 75 1,150
HX-3 B&G PROCESS CHILLED WATER 2
1/11/2010 16:47 P:\CU\Boulder\2008-124 JILA Addition\Cad\Acad2004\Mech\Mschedules\[M-2008-124.xls]S755-3 Hx Sh & Tb
UNIT HEATER SCHEDULE (HOT WATER)DESIG. MFR. MODEL LOCATION ARRANG. MBH GPM CFM RPM MOTOR CONTROL REMARKS
AT 5400' AT 5400' HP
UH-1 TRANE SEE PLANS FOR LOCATION AND QUANTITY HORIZONTAL 34.2 3.4 1400 1050 1/12 T-STAT
UH-2 TRANE SEE PLANS FOR LOCATION AND QUANTITY HORIZONTAL 131.1 13.1 5000 1140 1/3 T-STAT
CUH-1 TRANE SEE PLANS FOR LOCATION AND QUANTITY VERTICAL CABINET 25.8 2.8 430 1050 1/8 T-STAT
NOTES:
1. THE HOT WATER SUPPLY TEMPERATURE = 140 °F. 2. FOR UNIT HEATERS, THE MAXIMUM MOUNTING HEIGHT = 10 FT.
P:\CU\Boulder\2008-124 JILA Addition\Cad\Acad2004\Mech\Mschedules\[M-2008-124.xls]S830-4 CUH
CUSTOM AIR HANDLING UNIT SCHEDULESUPPLY FAN DATA RETURN FAN DATA COIL DATA FILTER DATA DIMENSIONS
CFM CFM TSP ESP NO. FAN VIBRATION CFM TSP NO. FAN VIBRATION MAX FACE COIL AIR ÄP EAT LAT WATER OPER.DESIG. MFR. MODEL SERVICE TOTAL O.A. IN. W.C. IN. W.C. FAN WHEEL RPM MIN. ISOLATOR TOTAL IN. W.C. FAN WHEEL RPM MIN. ISOLATOR SERVICE FACE AREA CFM AT IN W.C. °F °F MBH GPM ÄP FT. TYPE AREA % L" W" H" WEIGHT CONTROL REMARKS
AT 5400' AT 5400' AT 5400' AT 5400' WHEELS DIA. TYPE HP TYPE 5400' AT 5400' WHEELS DIA. TYPE HP TYPE VEL SF 5400' AT 5400' DB WB DB WB W.C. SF EFF. LBS.
AHU-1 OFFICE 28,000 8,000 5.5 2.0 4 PLENUM (4) 15 SPRING 20,000 2.0 4 PLENUM (4) 5 SPRINGHEATING 450 28,000 420 28 PRE FILTER 30
492 128 108 SEE NOTESCOOLING 450 28,000 670 105 FINAL FILTER 80
AHU-2 LAB 36,000 9,000 6.5 3.0 4 PLENUM (4) 25 SPRING 36,000 3.0 4 PLENUM (4) 7.5 SPRINGHEATING 450 36,000 550 36 PRE FILTER 30
492 158 108 SEE NOTESCOOLING 450 36,000 960 150 FINAL FILTER 95
AHU-3 EBEAM 4,000 -- 6.0 3.0 2 PLENUM (2) 7.5 SPRING -- -- -- -- -- -- --HEATING - - - - - - - - - - - PRE FILTER 30
316 48 78 SEE NOTESCOOLING 450 4,000 60 10 FINAL FILTER 95
AHU-4 LITHOGRAPHY 10,200 -- 5.0 3.0 2 PLENUM (2) 20 SPRING -- -- -- -- -- -- --HEATING - - - - - - - - - - - PRE FILTER 30
316 72 96 SEE NOTESCOOLING 450 10,200 180 30 FINAL FILTER 95
AHU-5 DRY ETCH 10,500 -- 5.0 3.0 2 PLENUM (2) 20 SPRING -- -- -- -- -- -- --HEATING - - - - - - - - - - - PRE FILTER 30
316 72 96 SEE NOTESCOOLING 450 10,500 125 20 FINAL FILTER 95
NOTES:1. MINIMUM 2 ROW HEATING COIL. COIL SIZED FOR 150 DEG F. TO 120 DEG F. WATER TEMPERATURE, 30% ETHYLENE GLYCOL.2. MINIMUM 6 ROW COOLING COIL. COIL SIZED FOR 48 DEG F. TO 60 DEG F. WATER TEMPERATURE.3. PROVIDE AHU-1 AND AHU-2 WITH MEEFOG HUMIDIFIER/EVAPORATIVE COOLER, COOLING COIL, HEATING COIL. MEEFOG HUMIDIFIER WILL REQUIRE RO WATER GENERATOR, TO BE PROVIDED WITH EQUIPMENT. RO WATER SHALL BE PROVIDED FOR AHU-1, AHU-2, MAU-1, AHU-3, AHU-4 AND AHU-5.4. AHU-3, AHU-4 AND AHU-5 SHALL BE PROVIDED WITH SPRING ISOLATORS UNDER UNIT, CONNECTED TO 24" HIGH CURB. CURB SHALL BE UTILIZED FOR RETURN AIR PLENUM.5. PROVIDE AHU-3, AHU-4 AND AHU-5 WITH MEEFOG HUMIDIFIER, COOLING COIL.6. SUPPLY AND RETURN FANS FOR AHU-1 AND AHU-2 SHALL HAVE 3 +1 REDUNDANCY.7. SUPPLY FANS FOR AHU-3, AHU-4 AND AHU-5 SHALL HAVE 1 + 1 REDUNDANCY.8. PROVIDE A 48" TALL STAINLESS STEEL SECTION FOR THE MEEFOG HUMIDIFIER/EVAPORATIVE COOLING SYSTEM. SECTION TO HAVE AN ACCESS DOOR AND DRAIN PAN FOR THE ENTIRE SECTION LENGTH.
1/12/2010 11:42 P:\CU\Boulder\2008-124 JILA Addition\Cad\Acad2004\Mech\Mschedules\[M-2008-124.xls]S855-5 AHU Cust
CUSTOM MAKEUP AIR HANDLING UNIT SCHEDULESUPPLY FAN DATA COIL DATA DESSICANT DATA REGEN COIL DATA REGEN FAN DATA FILTER DATA DIMENSIONS
CFM CFM TSP ESP NO. FAN VIBRATION MAX FACE COIL AIR ÄP EAT LAT WATER ROTOR COIL AIR DP EAT LAT MAX COIL AIR DP EAT LAT STEAM CFM TSP ESP NO. FAN VIBRATION OPER.DESIG. MFR. MODEL TOTAL O.A. IN. W.C. IN. W.C. FAN WHEEL RPM MIN. ISOLATOR SERVICE FACE AREA CFM AT IN W.C. °F °F MBH ÄP FT. RECIRC SERVICE DEPTH CFM AT IN W.C. DEG F. DEG F. FAC CFM AT IN W.C. DEG F. DEG. F PRESS. MBH LB/HR TOTAL IN. W.C. IN. W.C. FAN WHEEL RPM MIN. ISOLATOR TYPE AREA % L" W" H" WEIGHT CONTROL REMARKS
AT 5400' AT 5400' AT 5400' AT 5400' WHEELS DIA. TYPE HP TYPE VEL. SF 5400' AT 5400' DB WB DB WB W.C. GPM MM 5400' AT 5400' DB GR/LB DB GR/LB VEL 5400' AT 5400' DB WB DB WB PSIG. AT 5400' AT 5400' AT 5400' WHEELS DIA. TYPE HP TYPE SF EFF. LBS.
MAU-1 6,500 6,500 6.25 0.75 2 PLENUM (2) 15 HP SPRINGHEATING 450 6,500 -20 -- 550 PROCESS INLET 200 4,000 1.15 53.9 76.9 101.2 22.8 1,271 75
1,271 3 0.75 1 SPRINGPRE FILTER 30
276 72 96 SEE NOTESPRE-COOL 450 6,500 68 66 250 REGEN OUTLET 200 1,271 1.5 68.0 116.3 135.0 286.6 FINAL FILTER 65
NOTES:
1. MINIMUM 2 ROW HEATING COIL. COIL SIZED FOR 150 DEG F. TO 120 DEG F. WATER TEMPERATURE, 30% ETHYLENE GLYCOL.2. MINIMUM 6 ROW COOLING COIL. COIL SIZED FOR 48 DEG F. TO 60 DEG F. WATER TEMPERATURE.3. PROVIDE MAU-1 WITH DESSICANT DEHUMIDIFICATION WHEEL, PRE-COOLING COIL, HOT WATER HEATING COIL, POST-COOLING COIL, AND STEAM HEAT REACTIVATION COIL FOR DESSICANT WHEEL.4. MAKEUP AIR UNIT SHALL BE STACKED CONFIGURATION, WITH RELIEF FAN ON SIDE OF UNIT.5. PROVIDE MAU-1 WITH (2) PLUG FANS, SIZED FOR 100% REDUNDANCY.6. PROVIDE UNIT WITH SPRING ISOLATORS, MOUNTED ON HOUSEKEEPING PAD.
1/12/2010 13:30 P:\CU\Boulder\2008-124 JILA Addition\Cad\Acad2004\Mech\Mschedules\[M-2008-124.xls]S810-1 Humidifier
JILA ADDITION
F: 303.421.0331
303 EAST 17TH AVENUE SUITE 1000 DENVER, COLORADO 80203 303.764.1520
MECHANICAL SCHEDULES
M−102
AIR DEVICE SCHEDULEDESIG. MFR. TYPE MODEL FRAME MATERIAL FINISH DAMPER REMARKS
TYPE
A TITUS CEILING SUPPLY MCD LAY-IN OR SURFACE MTD STEEL WHITE N/A 24"x24" MODULE
B TITUS CEILING RETURN / EXHAUST PAR LAY-IN OR SURFACE MTD STEEL WHITE N/A 24"x24" MODULE
C TITUS CEILING RETURN / EXHAUST PAR LAY-IN OR SURFACE MTD STEEL WHITE N/A 24"x12" MODULE
D TITUS HEPA FILTER LAMINAR FLOW DIFFUSER TLF LAY-IN WHITE N/A 48"x24" MODULE
E GUTH COMB. LIGHT AND FLOW-THRU TROFFER AIRFLOW LAY-IN WHITE 48"x24" MODULE
F TITUS SIDEWALL SUPPLY 300RL SURFACE MTD STEEL WHITE N/A
G TITUS SIDEWALL RETURN / EXHAUST 350ZRL SURFACE MTD STEEL WHITE N/A
NOTES:1. SEE PLANS FOR NECK SIZE2. PROVIDE W/ OBD WHEN LOCATED ABOVE HARD CEILING.3. PROVIDE TYPE D AND TYPE E WITH HEPA FILTER MODULE WITH DUCT INLET CONNECTION AS INDICATED ON DRAWINGS.
TERMINAL BOX SCHEDULEMAX. MAX. MIN. MIN. HEATING COIL DATA
MODEL INLET DESIGN PRIMARY HEATING PRIMARY INLET S.P. WATERDESIG. SERVICE MFR. (HIGH DIA. CFM CFM CFM CFM IN W.C. EAT LAT MBH GPM P FT. EWT CONTROL REMARKS
RANGE) (IN.) AT 5280' AT 5280' AT 5280' AT 5280' AT S.L. °F °F W.C. °F
TB- OFFICE SUPPLY TITUS DESV 8 8 900 0 0.57 55 0.0 0.0 0.50 180 SEE SPEC. 1
REMARKS: 1. PROVIDE BOX SELECTION TO MEET LAT, DESIGN CFM, AND MBH. GPM ESTIMATES ARE FOR REFERENCE ONLY.
1/11/2010 16:47 P:\CU\Boulder\2008-124 JILA Addition\Cad\Acad2004\Mech\Mschedules\[M-2008-124.xls]S855-4 MAU Cust
PHOENIX VALVE SCHEDULEMAX. MAX. MIN. MIN. HEATING COIL DATA
MODEL INLET DESIGN PRIMARY HEATING PRIMARY INLET S.P. WATERDESIG. SERVICE MFR. (HIGH DIA. CFM CFM CFM CFM IN W.C. EAT LAT MBH GPM P FT. EWT CONTROL REMARKS
RANGE) (IN.) AT 5280' AT 5280' AT 5280' AT 5280' AT S.L. °F °F W.C. °F
SA- SUPPLY TITUS DESV 8 8 900 0 0.57 55 0.0 0.0 0.50 180 SEE SPEC. 1
EA- EXHAUST TITUS DESV 8 8 900 0 0.57 55 0.0 0.0 0.50 180 SEE SPEC. 1
REMARKS: 1. PROVIDE BOX SELECTION TO MEET LAT, DESIGN CFM, AND MBH. GPM ESTIMATES ARE FOR REFERENCE ONLY.
1/11/2010 16:48 P:\CU\Boulder\2008-124 JILA Addition\Cad\Acad2004\Mech\Mschedules\[M-2008-124.xls]S855-4 MAU Cust
FINTUBE RADIATION SCHEDULEBTUH/LF GPM/ UNIT
DESIG. MFR. MODEL NO. LF LF LENGTH REMARKSPANELS ELEMENT ELEMENT FT.
FTR-1A RUNTAL RF-4 4 760 0.05 SEE PLANS FLOOR MOUNTED, CIRCUIT #1
NOTES:
1. PROVIDE FLOOR MOUNTING KIT.2. HEATING COIL CAPACITY IS BASED ON 180 F TO 150 F WATER TEMPERATURE, 30% PROPYLENE GLYCOL.3. PROVIDE CONTINUOUS CURVED FIN TUBE TO MATCH ARCHITECTURAL WALL CURVE.4. COLOR FOR FIN TUBE SHALL BE RUNTAL STEEL (#9007).1/12/2010 8:18 P:\CU\Boulder\2008-124 JILA Addition\Cad\Acad2004\Mech\Mschedules\[M-2008-124.xls]S830-12 FinTube
HUMIDIFIER SCHEDULEENTERING ENTERING LEAVING RO WATER MAX. VAPOR TRAIL
DESIG. MFR. MODEL AREA/UNIT CFM AT ROOM ROOM AIR TEMP. RELATIVE RELATIVE LOAD INPUT ABSORBTION REMARKSSERVED 5400' DB RH °F HUMIDITY % HUMIDITY % LB/HR GPM DISTANCE (IN.)
H-1 OFFICES / AHU-1 70 30% 203 0.41 SEE NOTES
H-2 LABS / AHU-2 70 30% 225 0.45 SEE NOTES
H-3 E-BEAM CR /AHU-3 68 40% 32 0.06 SEE NOTES
H-4 LITHOGRAPHY CR / AHU-4 68 40% 144 0.29 SEE NOTES
H-5 DRY ETCH CR / AHU-5 68 40% 33 0.07 SEE NOTES
NOTES:1. MEEFOG PUMP IS __ HP, WITH VFD. PROVIDE 100% REDUNDANT PUMP WITH SYSTEM.2. RO SYSTEM IS 1HP AND RE-PRESSURIZATION PUMPS ARE (2) 3/4HP. PROVIDE 100% REDUNDANT RO UNIT AND UV FILTER.3. THE AHU MANUFACTURER SHALL BE PROVIDED WITH A 4' STAINLESS STEEL SECTION AND CONTINUOUS DRAIN PAN IN THE AHU. ACCESS DOOR SHALL BE IN THE MIDDLE OF THE 4' SECTION.4. H-1 & H-2 ARE DUAL PURPOSE HUMIDIFICATION AND EVAPORATIVE COOLING CONTROL. UNITS HAVE 100% AIR SIDE ECONOMIZERS.
1/12/2010 13:29 P:\CU\Boulder\2008-124 JILA Addition\Cad\Acad2004\Mech\Mschedules\[M-2008-124.xls]S810-1 Humidifier
JILA ADDITION
F: 303.421.0331
303 EAST 17TH AVENUE SUITE 1000 DENVER, COLORADO 80203 303.764.1520
MECHANICAL SCHEDULES
M−103
PLUMBING FIXTURE & EQUIPMENT SCHEDULEELECTRICAL
FIXTURE FITTINGS ACCESORY CONNECTIONSSYMBOL REQUIREMENTS
I.R. / BATTERY REMARKSFIXTURE NAME MANUFACTURER MODEL TYPE SIZE MANUFACTURER MODEL SUPPLY HP WASTE VENT CW HW
WC-1(ADA)
WATER CLOSET(MEN/UNISEX) AMERICAN STANDARD 3351.160
WALL HUNG,SIPHON JET,
1.6 GPF
ELONGATEDBOWL SLOAN, ROYAL 111-YO N/A 4" 2" 1" N/A
RE: ARCH. DWGS FOR MTG. HT. & LOCATION. PROVIDE W/CHURCH MODEL 295SSC SEAT, COLOR TO BE BLACK
WC-2(ADA)
WATER CLOSET(PUBLIC) AMERICAN STANDARD 3351.160
WALL HUNG,SIPHON JET,
1.6 GPF
ELONGATEDBOWL SLOAN, ROYAL SOLIS
8111 N/A SOLAR/BATTERY 4" 2" 1" N/ARE: ARCH. DWGS FOR MTG. HT. & LOCATION. PROVIDE W/CHURCH MODEL 295SSC SEAT, COLOR TO BE BLACK
WC-3(ADA)
WATER CLOSET(WOMENS) AMERICAN STANDARD 3351.160
WALL HUNG,SIPHON JET,
1.6 GPF
ELONGATEDBOWL SLOAN, ROYAL DUAL FLUSH MODEL WES-111 N/A 4" 2" 1" N/A
RE: ARCH. DWGS FOR MTG. HT. & LOCATION. PROVIDE W/CHURCH MODEL 295SSC SEAT, COLOR TO BE BLACK
UR-1(ADA) URINAL ZURN Z5738.205.00 PINT URINAL SYSTEM
.125 GPF14" X 18 1/2" X
43 3/8" ZURN INTREGAL N/A 2" 1 1/2" 3/4" N/A RE: ARCH. DWGS FOR MTG. HT. & LOCATION.
L-1(ADA) ORNON-ADA
LAVATORY AMERICAN STANDARD 0491.019 COUNTER MOUNTED 19" DIA. CHICAGO FAUCET 895-317GN2AE3XK RE: SPEC 2" 1 1/2" 1/2" 1/2" RE: ARCH. DWGS FOR MTG. HT. & LOCATION.
L-2(ADA) ORNON-ADA
LAVATORY AMERICAN STANDARD 0954.000 WALL MOUNTED 22" X 21" CHICAGO FAUCET 895-317GN2AE3XK RE: SPEC 2" 1 1/2" 1/2" 1/2" RE: ARCH. DWGS FOR MTG. HT. & LOCATION.
MSB-1 TERRAZOMOP SERVICE BASIN
FLORESTONEFIAT 81 WALL INSTALLATION 36"X 36"
X12" CHICAGO FAUCET 897-CP N/A 3" 2" 1/2" 1/2" JANITOR CLOSET
DF-1(ADA) 2 POSITION DRINKING FOUNTAIN ELKAY EHWM217C WALL HUNG - N/A N/A N/A 2" 1 1/2" 1/2" N/A RE: ARCH. DWGS FOR MTG. HT. & LOCATION.
SH-1(ADA) SHOWER TILED SHOWER BY
ARCHITECT - ADA TRANSFER SHOWER 36"X 36"X 77" DELTA FAUCET T17230 W/060124A HANDSHOWER AND
T11630 DIVERTER N/A 2" 1 1/2" 1/2" 1/2" RE: ARCH. DWGS FOR MTG. HT. & LOCATION.
FD-1 FLOOR/ SHOWER DRAIN JAY R. SMITH 2005 CAST IRON DRAIN RE: ROUNDOR SQUARE N/A N/A N/A RE:
PLANS2"
MIN. 5" MINIMUM STRAINER SIZE, ROUND GRATE
FS-1 FLOOR SINK JAY R. SMITH 3101 CAST IRON FLOOR SINK W/ BUCKET STRAINER
8 1/2"SQ. N/A N/A N/A RE:
PLANS2"
MIN. - - ACID RESISTANT ENAMEL COATED, 1/2 GRATE
RD/OD-1 COMBINATION ROOF DRAIN/OVERFLOW DRAIN JOSAM 22200-23 CAST IRON DRAIN W/ ROUGH BRONZE
DOME STRAINER12"DIA. N/A N/A N/A 3"
MIN. - - - PROVIDE DECK CLAMP ASSEMBLY & DRAIN RECEIVER ASSEMBLY AS REQ'D
GD-1 GARBAGE DISPOSER IN-SINK-ERATOR EVOLUTION SOUND INSULATED N/A N/A N/A N/A HARD WIRED1.0 HP 2" - - -
PROVIDE WITH WALL SWITCH, REFERENCE ELECTRICAL DRAWINGS (BREAK RM. A1B76)
HB-1 HOSE BIB CHICAGOFAUCET CO. 952-CP SIDE VALVE N/A N/A N/A N/A N/A N/A 3/4" N/A
HB-2 HOSE BIB CHICAGOFAUCET CO. 293-E27 FRONT VALVE N/A N/A N/A N/A N/A N/A 3/4" N/A
GWWB-1 GLASS WASHERWALL BOX GUY GRAY, IPS CORP. SSWB1
WALL MT.,STAINLESS STEEL WALL BOX WITH A CHROME
QUARTER TURN 1/2"HW VALVE - SWEAT CONNECTION
10 7/8"X 8 3/8" SPEARS
PROVIDE A SPEARS 1/2" LXT BALL VALVE ON THE CW SIDE OF THE BOX WITH A 1/2" LXT 90 DEG. ELBOW AND
A 1 1/4" X 1/2" LXT REDUCER.
N/A 2" 1 1/2" 1/2" 1/2"SECURE THE LXT BALL VALVE ASS'Y TO THE WALL BOX AS REQUIRED FOR A QUALITY/STABLE INSTALLATION
WH-1 EXTERIOR WALL HYDRANT WOODFORD B67-PB WALL MTD. FREEZELESS 7 1/2" X6 1/2" N/A N/A N/A - - - 3/4" - POLISHED BRASS FINISH
ESHR-1 EMERGENCY SHWR. & EYE/ FACE WASH HAWS 8356WC WALL MOUNTED - SEE EMV-1 - N/A 2"
FD 1 1/2" - - RE: ARCH. DWGS FOR MTG. LOC.
EMV-1 EMERGENCY MIXING VALVE LEONARD TM-5125 - - - - N/A - - 1 1/4" 1 1/4"
1. REFER TO GENERAL SPECIFICATIONS FOR WATER CLOSETS, URINALS, LAVATORYS, SINKS AND MISC. FIXTURE REQUIREMENTS.2. GRAB BARS BY ARCHITECT.3. THIS SCHEDULE INCLUDES ITEMS THAT MAY NOT BE INCLUDED IN THE DRAWING DOCUMENTS
S440-1
PLUMBING PUMP SCHEDULEMAX. SUCTION DISCHARGE
DESIG. MFR. MODEL PUMP TYPE SERVICE OPER. TEMP. GPM MIN. RPM SIZE SIZE CONTROL REMARKS°F HEAD (FT.) HP (IN.) (IN.)
DCP-1 GRUNDFOS UPS 32-80 IN-LINE DOMESTIC HOT WATER CIRC 230 10 18 1/2 - 3/4 3/4 WALL SWITCH
DCP-2 GRUNDFOS UPS 32-80 IN-LINE IND. HOT WATER CIRC - 10 18 1/2 - 3/4 3/4 WALL SWITCH
SP-1 DUPLEX WEIL 1601 SUMP BLDG
UNDERDRAIN - 50 35 (2) 1 1750 2" 2" FLOAT SWITCHS W/CONTROL PANEL SEE NOTES 1
SP-2DUPLEX WEIL 2436 SUMP SEWAGE
EJECTOR - 30 32 (2) 1.5 3450 2" 2" FLOAT SWITCHS W/CONTROL PANEL SEE NOTES 1
SP-3DUPLEX STANCOR SE50 SUMP ELEVATOR SUMP - 35 25 1/2 3600 2" 2" FLOAT SWITCHS
W/CONTROL PANEL SEE NOTES 1
NOTES:1. PROVIDE WITH CONTROL PANEL, FLOAT SWITCHES, MOTOR STARTERS AND ALL COMPONENTS NECESSARY FOR A COMPLETELY FUNCTIONING DUPLEX PUMP SYSTEM.2. PROVIDE HIGH WATER LEVEL ALARM CONNECTION TO THE BUILDING AUTOMATION SYSTEM.1/12/2010 15:32 P:\CU\Boulder\2008-124 JILA Addition\Cad\Acad2004\Plbg\Pschedules\[P-2008-124-JILA.xls]S440-1 Plmb Fxt
DOMESTIC/INDUSTRIAL WATER HEATER SCHEDULERECOVERY WATER
DESIG. MANUFACTURER MODEL MBH GPM RATE TEMP. RISE STEAM LBS/HR REMARKSINPUT (GPH) °F PRESSURE
HW-1 LESLIE E1500L .7 15 1020 80 15 720 NOTE 1 (DOM. WATER)
HW-2 LESLIE E1500L .7 15 1020 80 15 720 NOTE 1 (IND. WATER)
NOTES: 1. PROVIDE SKID MOUNTED WITH STEAM PRESSURE REGULATOR AND STEAM POWERED CONDENSATE PUMP.
1/12/2010 15:33 P:\CU\Boulder\2008-124 JILA Addition\Cad\Acad2004\Plbg\Pschedules\[P-2008-124-JILA.xls]S458-1 Dom HW
EXPANSION TANK SCHEDULECAPACITY PRE-CHARGE OPER.
DESIGNATION MANUFACTURER MODEL Tank Type ACCEPT. TANK SERVICE PRESSURE WEIGHT REMARKSVOL. VOL. (PSIG) (LBS)
DET-1 THERM-X-TROL ST-12 - 2.4 4.7 DOMESTIC HOT 55 73
1/12/2010 15:33 P:\CU\Boulder\2008-124 JILA Addition\Cad\Acad2004\Plbg\Pschedules\[P-2008-124-JILA.xls]S120-1 Exp Tank
RO/DI WATER SYSTEM SCHEDULEDESIG. MFR. MODEL SERVICE STORAGE TANK CAPACITY CONTROL REMARKS
DI-1 SIEMENS PROTEGRA CS 260 LAB 250 GAL. INTEGRAL SEE NOTE 1, 2, 3
NOTES:1. TYPE II DI WATER REQUIRED. PROVIDE W/ WATER SOFTENERS, 250 GALLON STORAGE TANK AND 10 GPM RECIRCULATING PUMP.2. PROVIDE WITH ALL REQUIRED ACCESSORIES/COMPONENTS FOR A FULLY FUNCTIONAL DI TYPE II WATER SYSTEM.3. PROVIDE SPARE PARTS FOR ALL CRITICAL COMPONENTS AND LONG LEAD TIME COMPONENTS.1/12/2010 15:34 P:\CU\Boulder\2008-124 JILA Addition\Cad\Acad2004\Plbg\Pschedules\[P-2008-124-JILA.xls]RO-DI Water System
VACUUM PUMP SCHEDULERECEIVER
DESIG. MFR. MODEL SERVICE SCFM AT 19"HG MINIMUM GALLON REMARKSHP CAPACITY
VAC-1(DUPLEX) POWEREX VTD0303 LAB 17 (2) 3 80 (HORIZ. TANK) SEE NOTE 1 AND 2
NOTES:1. PROVIDE WITH OIL LEVEL PROTECTION SWITCH AND EXHAUST HIGH TEMPERATURE SWITCH.2. VAC-1 IS TO MEET NFPA LEVEL 3 LAB REQUIREMENTS.
1/12/2010 15:35 P:\CU\Boulder\2008-124 JILA Addition\Cad\Acad2004\Plbg\Pschedules\[P-2008-124-JILA.xls]S540-2 Pump (VAC)
LAB AIR COMPRESSOR (AC) SCHEDULESCFM SCFM RECEIVER DIMENSIONS
DESIG. MFR. MODEL # DUTY AT AT CAPACITY REMARKS100 PSI 145 PSI (GAL) HP LENGTH WIDTH HEIGHT
LA-1(DUPLEX)
STD050 (W/80 GAL. TANK)POWEREX LAB AIR 30 -- -- (2) 5 64" 26" 40" SEE NOTES 1, 2 & 3
NOTES:1. PROVIDE WITH DESICCANT AIR DRYER (30 SCFM) AND DEW POINT MONITOR.2. PROVIDE WITH ELECTRIC TANK DRAIN.3. LA-1 TO MEET NFPA LEVEL 3 LAB REQUIREMENTS.
S481-1
JILA ADDITION
F: 303.421.0331
303 EAST 17TH AVENUE SUITE 1000 DENVER, COLORADO 80203 303.764.1520
MECHANICAL SCHEDULES
M−104
TEMPERATURE CONTROL MATRIXPOINT TYPE ANALOG IND. ALARM
POINTS LIST: NO
. OF
UN
ITS
DIG
ITA
L IN
PUT
DIG
ITA
L O
UTP
UT
AN
ALO
G IN
PUT
AN
ALO
G O
UTP
UT
TEM
PER
ATU
RE
REL
. HU
MID
ITY
POSI
TIO
N/S
PEED
/LEV
EL
PRES
SUR
E
STA
TUS
HIG
H
LOW
MA
INTE
NA
NC
E
PAC
KA
GED
EQ
UIP
. ALA
RM
EMS
PRO
GR
AM
S
REMARKS
Cooling Coil Circ Pump Start/Stop X
Cooling Coil Circ Pump Status X X
Cooling Coil Air Temperature X X
Evap. Cooling Pump Status X X
Evap. Cooling Pump Start/Stop X
Evap. Cooling Fill/Drain X
Evap. Cooling Make Up Water Meter X X
Discharge Air Relative Humidity X X Multiple per Unit - See Diagram
Supply Damper Position X
Supply Damper Control X
Outside Air CO2 X PPM
Minimum Outside Air Damper Position X
Minimum Outside Air Damper Control X
Outside Air Damper Position X
Outside Air Damper Control X
System Static Pressure X X X
Low Temp Limit X X
Return Air Damper Position X X
Return Air Damper Control X
Relief Air Damper Position X X
Relief Air Damper Control X
Mixed Air Temperature X X
Return Air Temperature X X
Return Air CO2 X PPM
Return Fan Start/Stop X
Return Fan Status X
Return Fan Measuring Station X
Return Fan VFD Fault X X
Return Fan VFD Alarm
Return Fan VFD Speed X
Return Duct Smoke Detector X
Supply Duct Smoke Detector X
Supply Air CO2 X PPM
Building Pressure X
Outside Air Flow Measuring Station X
Return Air Flow Measuring Station X
CLEANROOM AHU'S (AHU-3, AHU-4, AHU-5) 1
Supply Fan Start/Stop X
Supply Fan Status X X
Supply Fan Measuring Station X
Start Fan VFD Speed X X
Supply Fan VFD Fault X X
Supply Fan VFD Alarm
High Discharge Static Pressure X X
Final Filter Delta-P Transmitter X X X
Supply Air Temperature X X X X Multiple per Unit - See Diagram
Pre-Filter Delt-P Transmitter X X X
Cooling Coil Valve X
Cooling Coil Valve Differential Pressure X X
Chilled Water Supply Temperature X X
Chilled Water Return Temperature X X
Cooling Coil Circ Pump Start/Stop X
Cooling Coil Circ Pump Status X X
Cooling Coil Air Temperature X X
Evap. Cooling Pump Status X X
Evap. Cooling Pump Start/Stop X
Evap. Cooling Fill/Drain X
Evap. Cooling Make Up Water Meter X X
Discharge Air Relative Humidity X X Multiple per Unit - See Diagram
Supply Damper Position X
Supply Damper Control X
Outside Air Damper Position X
Outside Air Damper Control X
System Static Pressure X X X
Low Temp Limit X X
Return Air Damper Position X X
Return Air Damper Control X
Relief Air Damper Position X X
Relief Air Damper Control X
Mixed Air Temperature X X
NOTES:
1. The Temperature Control Matrix, Control Diagrams, and the Sequence of Operation are all binding. If there is a discrepancy between them, the worst case scenario shall be used for bidding purposes. Additional costs will not be allowed for discrepancies between the specifications and the drawings.2. Not Used3. See plans for quantity.4.Coordinate with the Fire Alarm Vendor/Contractor for Smoke and Fire/Smoke damper closure when fan fails. Monitor modules should be wired to the VFD contacts.
NOTES:
1. The Temperature Control Matrix, Control Diagrams, and the Sequence of Operation are all binding. If there is a discrepancy between them, the worst case scenario shall be used for bidding purposes. Additional costs will not be allowed for discrepancies between the specifications and the drawings.2. Not Used3. See plans for quantity.4.Coordinate with the Fire Alarm Vendor/Contractor for Smoke and Fire/Smoke damper closure when fan fails. Monitor modules should be wired to the VFD contacts.
TEMPERATURE CONTROL MATRIXPOINT TYPE ANALOG IND. ALARM
POINTS LIST: NO
. OF
UN
ITS
DIG
ITA
L IN
PUT
DIG
ITA
L O
UTP
UT
AN
ALO
G IN
PUT
AN
ALO
G O
UTP
UT
TEM
PER
ATU
RE
REL
. HU
MID
ITY
POSI
TIO
N/S
PEED
/LEV
EL
PRES
SUR
E
STA
TUS
HIG
H
LOW
MA
INTE
NA
NC
E
PAC
KA
GED
EQ
UIP
. ALA
RM
EMS
PRO
GR
AM
S
REMARKS
Outside Air Temperature 1 X X
Outside Air Relative Humidity 1 X X
Outside Air Pressure 1 X X
MAKEUP AIR UNIT MAU-1 (100% OA) 1
Fan Start/Stop X
Fan Status X X
Fan VFD Speed X X
Fan VFD Alarm X X
Fan VFD Fault X X
High Discharge Static Pressure X X
Final Filter Delta-P X X X
Discharge Supply Air Temperature X X X X Multiple per Unit - See Diagram
Pre-Filter Delta-P X X X
Heating Coil Circ Pump Start/Stop X
Heating Coil Circ Pump Status X X
Heating Coil Valve X
Heating Water Supply Temperature X X
Heating Water Return Temperature X X
Cooling Coil Valve X X
Cooling Coil Valve Differential Pressure X X
Cooling Coil Circ Pump Start/Stop X
Cooling Coil Circ Pump Status X X
Chilled Water Supply Temperature X X
Chilled Water Return Temperature X X
Cooling Coil Air Temperature X X
Meefog Humidifier Status X X
Discharge Air Relative Humidity X X Multiple per Unit - See Diagram
Supply Damper Position X
Supply Damper Control X
Outside Air Damper Position X
Outside Air Damper Control X
Supply Duct Smoke Detector X
System Static Pressure X X X
Low Temp Limit X X
TYPICAL EXHAUST FANS (Partial Redundant Laboratory Fans or Fully Redundant Fans)
Quantity of Fan Sets NOTE 3
Status NOTE 3 X X
Start/Stop NOTE 3 X
Damper Position NOTE 3 X
Damper Control NOTE 3 X
System Static Pressure NOTE 3 X X
VFD Speed NOTE 3 X X
VFD Fault NOTE 3 X X
VFD Alarm NOTE 3 X X
Exhaust Fans: (constant volume fans)
Status NOTE 3 X X
Start/Stop NOTE 3 X
Exhaust Fans: (Single fans with VFD's)
Status NOTE 3 X X
Start/Stop NOTE 3 X
System Static Pressure NOTE 3 X X
VFD Speed NOTE 3 X X
VFD Fault NOTE 3 X X
VFD Alarm NOTE 3 X X
OFFICE AND LAB AHU (AHU-1, AHU-2) 1
Supply Fan Start/Stop X
Supply Fan Status X X
Supply Fan Measuring Station X
Start Fan VFD Speed X X
Supply Fan VFD Fault X X
Supply Fan VFD Alarm
High Discharge Static Pressure X X
Final Filter Delta-P Transmitter X X X
Supply Air Temperature X X X X Multiple per Unit - See Diagram
Pre-Filter Delt-P Transmitter X X X
Heating Coil Circ Pump Start/Stop X
Heating Coil Circ Pump Status X X
Heating Coil Valve X
Heating Water Supply Temperature X X
Heating Water Return Temperature X X
Cooling Coil Valve X
Cooling Coil Valve Differential Pressure X X
Chilled Water Supply Temperature X X
Chilled Water Return Temperature X X
JILA ADDITION
F: 303.421.0331
303 EAST 17TH AVENUE SUITE 1000 DENVER, COLORADO 80203 303.764.1520
MECHANICAL SCHEDULES
M−105
TEMPERATURE CONTROL MATRIXPOINT TYPE ANALOG IND. ALARM
POINTS LIST: NO
. OF
UN
ITS
DIG
ITA
L IN
PUT
DIG
ITA
L O
UTP
UT
AN
ALO
G IN
PUT
AN
ALO
G O
UTP
UT
TEM
PER
ATU
RE
REL
. HU
MID
ITY
POSI
TIO
N/S
PEED
/LEV
EL
PRES
SUR
E
STA
TUS
HIG
H
LOW
MA
INTE
NA
NC
E
PAC
KA
GED
EQ
UIP
. ALA
RM
EMS
PRO
GR
AM
S
REMARKS
Runtel/Baseboard Control Valve Note 3 X X
Fan Coil Units Status Note 3 X X
Fan Coil Unit Chilled Water Valve Note 3 X X
FCU Chilled water valve Diff Pressure Note 3 X X
Fan Coil Unit Hot Water Valve Note 3
Fan Coil Units Discharge Air Temp. Note 3 X Ducted units only
Water Heater Alarms (Domestic and Industrial) 2 X X
Hot Water Circ Pump Status 4 X X
Hot Water Circ Pump Start/Stop 4 X X
Steam Flow Meter 1 X Flow
Chilled Water Flow Meter 1 X Flow
Water Meter 1 X Flow (Gallons)
Electrical Meter 1 X Coordinate available input with Electrical contractor
Elevator Sump Pumps Status Current Sensor
Oil Minder Elevator Sump Pump Status 1 X X
Oil Minder Elevator Sump Pump Alarm 1 X X
Generator Status 1 X X
Generator Load Shed 1 X
Chilled Water System
Chilled Water System Delta-P 2 X X 1 in Penthouse
Chilled Water Pump Start/Stop 2 X
Chilled Water Pump Status 2 X
Chilled Water Pump Speed (VFD) 2 X
Chilled Water Pump VFD Alarm 2 X X
Chilled Water Pump VFD Fault 2 X X
Chilled Water Bypass Valve 1 X X
Process Cooling Pump Start/Stop 1 X
Process Cooling Pump Status 1 X X
Process Cooling Pump Speed (VFD) 1 X
Process Cooling Pump VFD Alarm 1 X
Process Cooling Pump VFD Fault 1 X X
Process Cooling HX Control Valve 1 X X X
Process Cooling Supply Temperature 1 X X
Process Cooling Return Temperature 1 X X
Process Cooling System Supply Pressure 1 X X
Process Cooling System Return Pressure 1 X X
NOTES:
1. The Temperature Control Matrix, Control Diagrams, and the Sequence of Operation are all binding. If there is a discrepancy between them, the worst case scenario shall be used for bidding purposes. Additional costs will not be allowed for discrepancies between the specifications and the drawings.2. Not Used3. See plans for quantity.4.Coordinate with the Fire Alarm Vendor/Contractor for Smoke and Fire/Smoke damper closure when fan fails. Monitor modules should be wired to the VFD contacts.
NOTES:
1. The Temperature Control Matrix, Control Diagrams, and the Sequence of Operation are all binding. If there is a discrepancy between them, the worst case scenario shall be used for bidding purposes. Additional costs will not be allowed for discrepancies between the specifications and the drawings.2. Not Used3. See plans for quantity.4.Coordinate with the Fire Alarm Vendor/Contractor for Smoke and Fire/Smoke damper closure when fan fails. Monitor modules should be wired to the VFD contacts.
Return Air Temperature X X
Return Air CO2 X PPM
Return Duct Smoke Detector X
Supply Duct Smoke Detector X
Supply Air CO2 X PPM
Building Pressure X
Return Air Flow Measuring Station X
Steam Supply System 1
Steam Header Pressure 1 X X X
Bldg Water Heating System
Hot Water Supply Temp. 1 X X
Hot Water Return Temp. 1 X X
Heating Water Primary Pump Start/Stop 2 X
Heating Water Primary Pump Status 2 X
Heating System Delta-P 6 X X
Heating Water Pump Speed (VFD) 2 X
Heating Water Pump VFD Alarm 2 X X
Heating Water Pump VFD Fault 2 X X
Duct Heating Coils (Phoenix Valves for Labs)
Space Temperature Note 3 X X
HW Coil Valve Note 3 X
HW Coil Discharge Air Temperature Note 3 X
Heat Reclaim System
Heat Reclaim Exhaust Air Filter Status 1 X X
Heat Reclaim Pump Status 1 X X
Heat Reclaim Pump Start/Stop 1 X
Heat Reclaim Supply Water Temperature 1 X X
Heat Reclaim Return Water Temperature 1 X X
Heat Reclaim Glycol Feeder Alarm 1 X
Heat Exchangers (Preheat)
Glycol HWS Temp. 1 X X
Glycol HWR Temp 1 X X
HX Control Valve 2 X
Glycol Heating Pump Start/Stop 2 X
Glycol Heating Pump Status 2 X
Glycol Heating Pump Speed (VFD) 2 X
Glycol Heating Pump VFD Alarm 2 X X
Glycol Heating Pump VFD Fault 2 X X
Glycol Heating System Pressure 1 X X
Glycol Heating System DP 1 X X
Heat Exchangers (Space Heat)
HWS Temp. 1 X X
HWR Temp 1 X X
HX Control Valve 2 X
Heating Pump Start/Stop 2 X
Heating Pump Status 2 X
Heating Pump Speed (VFD) 2 X
Heating Pump VFD Alarm 2 X X
Heating Pump VFD Fault 2 X X
Heating System Pressure 1 X X
Heating System DP 1 X X
General
Room Pressure Monitor Status Note 3 X X
Room CO2 monitors Note 3
Air Compressor Alarm 1 X X
Compressed Air Pressure 1 X X
Vacuum Pump Alarm 1 X X
Vacuum Pressure 1 X X
Glycol Feeder Alarms 2 X
Terminal Box Damper Position Note 3 X
Terminal Box Airflow Note 3 X X
Terminal Box HW Coil Valve Note 3 X
Terminal Box Discharge Air Temperature Note 3 X
Space Thermostats for Terminal Box Control Note 3 X X
Convector Control Valve Note 3 X X
TEMPERATURE CONTROL MATRIXPOINT TYPE ANALOG IND. ALARM
POINTS LIST: NO
. OF
UN
ITS
DIG
ITA
L IN
PUT
DIG
ITA
L O
UTP
UT
AN
ALO
G IN
PUT
AN
ALO
G O
UTP
UT
TEM
PER
ATU
RE
REL
. HU
MID
ITY
POSI
TIO
N/S
PEED
/LEV
EL
PRES
SUR
E
STA
TUS
HIG
H
LOW
MA
INTE
NA
NC
E
PAC
KA
GED
EQ
UIP
. ALA
RM
EMS
PRO
GR
AM
S
REMARKS
JILA ADDITION
F: 303.421.0331
303 EAST 17TH AVENUE SUITE 1000 DENVER, COLORADO 80203 303.764.1520
MECHANICAL SCHEDULES
M−106
JILA ADDITION
F: 303.421.0331
303 EAST 17TH AVENUE SUITE 1000 DENVER, COLORADO 80203 303.764.1520
MECHANICALSITE PLAN
M−201
WATER SERVICE SLEEVE DETAIL
FIRE SPRINKLER SYSTEMFLOOR CONTROL DETAIL
PIPE IN OUTSIDE WALL DETAILTYPICAL PIPEANCHOR DETAIL
FIRE SERVICESLEEVE DETAIL
SADDLE DETAILINSULATED PIPE
FIRE LINE ENTRY DETAILF.D.C. DETAILFREE STANDING
DRAIN FLASHING DETAILSTALL SHOWER
FLOOR DRAIN FLASHING DETAIL
GLYCOL FEEDER DETAIL FEEDER/COUPON RACK DETAILCHEMICAL POT
LAB PIPING ENTRANCE DETAIL
JILA ADDITION
F: 303.421.0331
303 EAST 17TH AVENUE SUITE 1000 DENVER, COLORADO 80203 303.764.1520
MECHANICAL DETAILS
M−301
CLEANOUT DETAIL
GENERATOR PIPING DETAILDOMESTIC HOT WATER
VENT PIPING DETAILSTEAM SAFETY VALVE
STEAM LINE DRIP DETAILMEDIUM PRESSURE
SYSTEM SCHEMATICDEIONIZED WATER
ELEVATOR SUMP DETAILROOF DRAIN FLASHING DETAIL
TYPICAL RO/DI WATER DROP DETAIL
IN-LINE PUMP PIPING DETAILDOMESTIC HOT WATER CIRC.
END OF STEAMMAIN DRIP DETAIL
DUPLEX SEWAGE EJECTOR DETAIL
LABORATORY AIR COMPRESSOR DETAILVACUUM PUMP DETAIL
JILA ADDITION
F: 303.421.0331
303 EAST 17TH AVENUE SUITE 1000 DENVER, COLORADO 80203 303.764.1520
MECHANICAL DETAILSCONT.
M−302
DETAIL (TYPICAL OF STEAMMAIN STEAM SHUT-OFF VALVE
ISOLATION VALVES IN MECH ROOM)
2-WAY VAV HOT WATERCOIL PIPING DETAIL
COIL UNIT PIPING DETAILHORIZONTAL CEILING FAN
CHILLED WATER COILPIPING DETAIL
FAN COIL UNIT PIPING DETAIL
HEAT EXCHANGER PIPING DETAIL (HX-1A, 1B, 2A, 2B)
PUMPED
PIPING DETAILHOT WATER COIL
PIPING DETAILCONDENSATE DRAIN
IN-LINE PUMP PIPING DETAIL
EXPANSION TANK DETAILHEAT RECLAIM COILPIPING DETAIL
PUMP PIPING DETAILEND SUCTION
MECHANICAL DETAILSCONT.
M−303
JILA ADDITION
F: 303.421.0331
303 EAST 17TH AVENUE SUITE 1000 DENVER, COLORADO 80203 303.764.1520
DUCT TAKE-OFF DETAIL
ROOF EXHAUST FAN DETAIL
TERMINAL BOX DETAIL
INSTALLATION DETAILFIRE DAMPER
ROOF EXHAUST FAN DETAIL
FIRE/SMOKE DAMPERINSTALLATION DETAIL
SPLITTER DUCT DETAIL
AIR DEVICE DETAIL SOUND ELBOW DETAIL
ROUND DUCT / PIPE ROOFPENETRATION DETAIL EXHAUST AIR DETAIL
ENERGY METER DETAILCHILLED WATER
RETURN AIR DUCT DETAIL
JILA ADDITION
F: 303.421.0331
303 EAST 17TH AVENUE SUITE 1000 DENVER, COLORADO 80203 303.764.1520
MECHANICAL DETAILSCONT.
M−304
CLEANOUT DETAIL
WATER SERVICESLEEVE DETAIL
SURFACE CLEANOUT DETAILWATER PRESSURE REDUCINGSTATION DETAIL (IND. WATER)
FOR MANUAL SWITCHOVERTYPICAL LAB GAS MANIFOLD DETAIL
SURFACE 2-WAYCLEANOUT DETAIL
HYDRAULIC ELEVATOR SUMP DETAIL
WATER PRESSURE REDUCINGSTATION DETAIL (DOM. WATER)
3/4" - 1 1/2" HORIZONTAL RPBFP DETAIL
FIRE PROTECTION ROOFMANIFOLD PIPING DETAIL
DOM. & IND. HORIZONTAL REDUNDANT RPBFP'S DETAIL
ISLAND VENT DETAIL
JILA ADDITION
F: 303.421.0331
303 EAST 17TH AVENUE SUITE 1000 DENVER, COLORADO 80203 303.764.1520
MECHANICAL DETAILSCONT.
M−305
CIRC. IN-LINE PUMP PIPING DETAILHEATING AND DOMESTIC HOT WATER
FIRE LINE ENTRY DETAIL
AIR COMPRESSOR DETAIL
STERILIZER/AUTOCLAVE PIPING DETAIL
GLASSWARE WASHER PIPING DET.UNDER-COUNTER
DUPLEX SUMP PUMP (BLDG. UNDERDRAIN) DETAILDUPLEX SEWAGE EJECTOR DETAIL
GENERATOR PIPING DETAILINDUSTRIAL HOT WATER
GENERATOR PIPING DETAILDOMESTIC HOT WATER
JILA ADDITION
F: 303.421.0331
303 EAST 17TH AVENUE SUITE 1000 DENVER, COLORADO 80203 303.764.1520
MECHANICAL DETAILSCONT.
M−306
JILA ADDITION
F: 303.421.0331
303 EAST 17TH AVENUE SUITE 1000 DENVER, COLORADO 80203 303.764.1520
CHILLED WATERPIPING SCHEMATIC
M−401
JILA ADDITION
F: 303.421.0331
303 EAST 17TH AVENUE SUITE 1000 DENVER, COLORADO 80203 303.764.1520
HEATING WATERPIPING SCHEMATIC
M−402
JILA ADDITION
F: 303.421.0331
303 EAST 17TH AVENUE SUITE 1000 DENVER, COLORADO 80203 303.764.1520
BUILDING AIRFLOWSCHEMATIC
M−403
MAINT.
ACCESS
MAINT.
ACCESS
MAINT.ACCESS
MAINT.ACCESS
MAINT.ACCESS
MAINT.ACCESS
MAINT.ACCESS
MAINT.ACCESS
MAINT.
ACCESS
MAINT.ACCESS
MAINT.ACCESS
MAINT.ACCESS
MAINT.ACCESS
MAINT.ACCESS
MAINT.ACCESS
MAINT.ACCESS
MAINT.
ACCESS
MAINT.
ACCESS
MAINT.
ACCESS
MAINT.
ACCESS
MAINT.
ACCESS
MAINT.
ACCESS
MAINT.ACCESS
MAINT.
ACCESS
UP
DN
UP
DN
UP
UP
UP
DN
23
45
67
ACFH BG
LAB A
X1B10
LAB A
X1B20
LAB A
X1B30
LAB A
X1B40
LAB A
X1B11
LAB A
X1B21
LAB A
X1B31
LAB A
X1B41
LAB A
X1B51
M/E
CRX1B30
M/E
CRX1B05
STAIR
STX1B90
D B.1
86.1
5.5
2.5
1
COLLABORATION
X1B52
RAMP
CRX1B01
ELEVATOR
ELX1B90WOMEN
RRWX1B67
MEN
RRMX1B57
JANITOR
X1B77
LAB A
X1B50
E
CIRCULATION
CRX1B25
PUMP ROOM
X1B87
STAIR
STX1B25
LOBBY
CRX1B90
STAIR
STX1B01
RESEARCH LAB
S1B05
RESEARCH LAB
S1B20
RESEARCH LAB
CRS1B79
CIRCULATION
CRS1B84
STUDENT OFFICE
CRS1B81
6.5
LAB MECH.
X1B01
RECYCLING
X1B02
48"x24"
2' - 6"
40"x24"
20"x18"
36"x20"
26"x18"
30"x22"
16"x10"
28"x18"
10"ø
CUH
1
30"x22"
70/32 RA UP(22,000 CFM)
40/24 SA UP(11,000 CFM)
40/24 SA UP(11,000 CFM)
16/10 LAB EA UP(1,000 CFM FUTURECAPACITY)
10/10 EA UP(500 CFM)
10"x10"
1
FCU
#
2
TYPICAL LABLAYOUT
GENERAL NOTES:WORK INCLUDED IN THE CONTRACT IS DENOTED IN BOLD. EXISTING CONDITIONS TOREMAIN ARE DENOTED LIGHTLY.
A DETAILED METHOD OF PROCEDURE IS REQUIRED WHEN A CONSTRUCTIONACTIVITY AFFECTS THE SAFETY OF THE OCCUPANTS, TELEPHONE EQUIPMENT ORVALUABLE CONTENTS OR ANY SYSTEM WHICH SUPPORTS THESE SYSTEMS; ORESSENTIALLY AFFECTS THE BUILDING MANAGEMENT, OPERATIONS OR SECURITY.
CONTRACTOR IS RESPONSIBLE FOR FIELD VERIFICATION OF ALL EXISTINGCONDITIONS PRIOR TO COMMENCEMENT OF ANY WORK AND SHALL NOTIFY THEENGINEER/ARCHITECT OF ANY DISCREPANCIES FOR RESOLUTION.
COORDINATE WORK WITH ALL TRADES.
CONTRACTOR IS RESPONSIBLE FOR SECURING AND WEATHERPROOFING ANYROOF OPENING NOT COMPLETED DURING WORKING HOURS.
COORDINATE ALL DUCTWORK AND PIPING WITH EQUIPMENT, STRUCTURE, ETC.
CONTRACTOR SHALL BE RESPONSIBLE FOR DEACTIVATION OF ROOF-MOUNTEDEQUIPMENT AND ASSOCIATED INDOOR EQUIPMENT. ONLY ONE UNIT SHALL BETAKEN OUT OF SERVICE AT ANY TIME, WITH REMAINDER OF UNITS LEFTOPERATIONAL. COORDINATE WITH GENERAL CONTRACTOR AND ELECTRICALCONTRACTOR.
CONTRACTOR SHALL NOT SHUT DOWN / TAKE OUT OF SERVICE ANY SYSTEMSWITHOUT FIRST COORDINATING WITH OWNER AND PREPARING M.O.P.
1.
2.
3.
4.
5.
6.
7.
8.
HVAC NOTES:ALL LOW PRESSURE RECTANGULAR DUCTWORK DOWNSTREAM OF TERMINALBOX SHALL HAVE 1" THICK INTERNAL DUCT LINER. SIZES SHOWN ARE ACTUALSHEET METAL SIZE AND INCLUDE THICKNESS OF LINER. (UNLESS NOTEDOTHERWISE).
ALL SUPPLY AIR DIFFUSERS ARE 4-WAY AIR PATTERN UNLESS SHOWNOTHERWISE.
DUCT SIZE OF BRANCH DUCT TO AIR DEVICE SHALL BE THE SAME SIZE ASNECK SIZE OF AIR DEVICE UNLESS NOTED OTHERWISE.
BRANCH DUCT SIZE TO INLET OF ALL TERMINAL BOXES SHALL BE THE SAMESIZE AS THE INLET SCHEDULED UNLESS NOTED OTHERWISE.
ALL MEDIUM PRESSURE AND ROUND LOW PRESSURE SUPPLY AIR DUCTWORKSHALL BE EXTERNALLY WRAPPED TO THICKNESS AS STATED INSPECIFICATIONS. RETURN AND EXHAUST DUCTWORK IS NEITHER LINED NORWRAPPED.
PROVIDE ROOM AIR BALANCE TO ACHIEVE POSITIVE (+) OR NEGATIVE (-) ATTHE DIFFERENTIAL PRESSURE INDICATED ON THE DRAWINGS.
1.
2.
3.
4.
5.
6.
FLAG NOTES:
PROVIDE SEPARATE, RATED SHAFT ENCLOSURE FOR LAB EXHAUST DUCT.
DUCTED FAN COIL UNIT, TYPICAL.
1
2
E
D
C
B
A
1 2 3 4 5 6
E
D
C
B
A
1 2 3 4 5 6
SCALE
PROJECT NUMBER
KEY PLAN
X
CD
F
E G
A
S
B
NORTH
IF THIS SHEET IS NOT 30" X 42", IT IS A REDUCEDSIZE PLOT. USE GRAPHIC SCALE ACCORDINGLY.
NOT FOR CO
NSTRUC
TION
PRELIMINARY
JILAUNIVERSITY OF COLORADO440 UCBBOULDER, CO 80309−0440
JILA ADDITION
CATOR RUMA & ASSOCIATES, CO.896 TABOR STREETLAKEWOOD, CO 80401P: 303.232.6200F: 303.233.3701
MARTIN / MARTIN CONSULTING ENGINEERS12499 WEST COLFAX AVENUEPO BOX 151500LAKEWOOD, CO 80215P: 303.431.6100F: 303.431.6866
M−E ENGINEERS, INC.10055 W. 43RD AVENUEWHEAT RIDGE, CO 80033P: 303.421.6655F: 303.421.0331
HDR ARCHITECTURE, INC.303 EAST 17TH AVENUE, SUITE 1000DENVER, CO 80203P: 303.764.1520F: 303.860.7139
ARCHITECT:
MECHANICAL / ELECTRICAL ENGINEER:
STRUCTURAL / CIVIL ENGINEER:
TELECOMMUNICATIONS ENGINEER:
BELT COLLINS WEST, LTD.4909 PEARL EAST CIRCLE, SUITE 300BOULDER, CO 80301P: 303.442.4588F: 303.786.8026
LANDSCAPE ARCHITECT:
CU PROJECT NO. PR 002650
UNIVERSITY OF COLORADOAT BOULDEROFFICE OF FACILITIES PLANNINGRL−2, THIRD FLOOR, ROOM 301BOULDER, CO 80309P: 303.492.1275F: 303.492.4082
OWNER:
GALLUN SNOW1920 MARKET STREET, SUITE 201DENVER, CO 80202P: 303.433.9500F: 303.433.5624
INTERIOR ARCHITECT:
303 EAST 17TH AVENUE SUITE 1000 DENVER, COLORADO 80203 303.764.1520
HDR ARCHITECTURE, INC.
SCHEMATIC DESIGN04/30/2009
01/19/2010 DESIGN DEVELOPMENT TECHNICAL REVIEW
C:\Revit Local Projects\2010\2008-124 JILA Addition\llange_MECH-2008-124 CU JILA.rvt
1/15/2010 8:27:12 AM
As indicated
MH-10B
282-89589
BASEMENT HVACPLAN
DESIGN DEVELOPMENT TECHNICAL REVIEW
SCALE: 1/8" = 1'-0"
BASEMENT HVAC PLAN
MARK DATE DESCRIPTION
MAINT.
ACCESS
MAINT.ACCESS
MAINT.ACCESS
MAINT.
ACCESS
MAINT.
ACCESS
MAINT.ACCESS
MAINT.ACCESS
MAINT.
ACCESS
MAINT.
ACCESS
MAINT.ACCESS
MAINT.ACCESS
MAINT.ACCESS
DN
DN
UP
DN
UP
DN
GENERAL NOTES:WORK INCLUDED IN THE CONTRACT IS DENOTED IN BOLD. EXISTING CONDITIONS TOREMAIN ARE DENOTED LIGHTLY.
A DETAILED METHOD OF PROCEDURE IS REQUIRED WHEN A CONSTRUCTIONACTIVITY AFFECTS THE SAFETY OF THE OCCUPANTS, TELEPHONE EQUIPMENT ORVALUABLE CONTENTS OR ANY SYSTEM WHICH SUPPORTS THESE SYSTEMS; ORESSENTIALLY AFFECTS THE BUILDING MANAGEMENT, OPERATIONS OR SECURITY.
CONTRACTOR IS RESPONSIBLE FOR FIELD VERIFICATION OF ALL EXISTINGCONDITIONS PRIOR TO COMMENCEMENT OF ANY WORK AND SHALL NOTIFY THEENGINEER/ARCHITECT OF ANY DISCREPANCIES FOR RESOLUTION.
COORDINATE WORK WITH ALL TRADES.
CONTRACTOR IS RESPONSIBLE FOR SECURING AND WEATHERPROOFING ANYROOF OPENING NOT COMPLETED DURING WORKING HOURS.
COORDINATE ALL DUCTWORK AND PIPING WITH EQUIPMENT, STRUCTURE, ETC.
CONTRACTOR SHALL BE RESPONSIBLE FOR DEACTIVATION OF ROOF-MOUNTEDEQUIPMENT AND ASSOCIATED INDOOR EQUIPMENT. ONLY ONE UNIT SHALL BETAKEN OUT OF SERVICE AT ANY TIME, WITH REMAINDER OF UNITS LEFTOPERATIONAL. COORDINATE WITH GENERAL CONTRACTOR AND ELECTRICALCONTRACTOR.
CONTRACTOR SHALL NOT SHUT DOWN / TAKE OUT OF SERVICE ANY SYSTEMSWITHOUT FIRST COORDINATING WITH OWNER AND PREPARING M.O.P.
1.
2.
3.
4.
5.
6.
7.
8.
HVAC NOTES:ALL LOW PRESSURE RECTANGULAR DUCTWORK DOWNSTREAM OF TERMINALBOX SHALL HAVE 1" THICK INTERNAL DUCT LINER. SIZES SHOWN ARE ACTUALSHEET METAL SIZE AND INCLUDE THICKNESS OF LINER. (UNLESS NOTEDOTHERWISE).
ALL SUPPLY AIR DIFFUSERS ARE 4-WAY AIR PATTERN UNLESS SHOWNOTHERWISE.
DUCT SIZE OF BRANCH DUCT TO AIR DEVICE SHALL BE THE SAME SIZE ASNECK SIZE OF AIR DEVICE UNLESS NOTED OTHERWISE.
BRANCH DUCT SIZE TO INLET OF ALL TERMINAL BOXES SHALL BE THE SAMESIZE AS THE INLET SCHEDULED UNLESS NOTED OTHERWISE.
ALL MEDIUM PRESSURE AND ROUND LOW PRESSURE SUPPLY AIR DUCTWORKSHALL BE EXTERNALLY WRAPPED TO THICKNESS AS STATED INSPECIFICATIONS. RETURN AND EXHAUST DUCTWORK IS NEITHER LINED NORWRAPPED.
PROVIDE ROOM AIR BALANCE TO ACHIEVE POSITIVE (+) OR NEGATIVE (-) ATTHE DIFFERENTIAL PRESSURE INDICATED ON THE DRAWINGS.
1.
2.
3.
4.
5.
6.
FLAG NOTES:
CONNECT RA CHASES TO RA MAIN UP TO AHU ABOVE. UTILIZE DUCTEDPLENUMS ABOVE CLEANROOM CEILING.
PROVIDE SEPARATE, RATED SHAFT ENCLOSURE FOR LAB EXHAUST DUCT.
1
2
23
45
67
ACFH BG
M/E
CRX130
M/E
X115
UNISEX
RRWX100
B LAB
X110
B LAB
X120
B LAB
X130
B LAB
X140
D
SHAFT 2SHAFT 1
CIRCULATION
CRX125
B.1
86.1
5.5
KECK LAB
X145
LAB MGR
X145A
2.5
1
STAIR
STX101
E
COLLABORATION
X152
STAIR
STX125
RAMP
CRX101
E-BEAM
X131A
LITHOGRAPHY CL
X121D
LITHOGRAPHY
CHASE
X121C
MAIN AISLE CL
X121A
FABRICATION CL
X121B
WIPE DOWN CL
X121
GOWN CL
X131
CIRCULATION
CRX190
CONFERENCE
ROOM
S105
LIBRARY STACKS
S120
STUDY ROOM
S124
OFFICE
S115
CIRCULATION
S102
6.5
ELEVATOR
ELX190
STAIR
STX190
50"x24"
20"x16"
20"x18"
90/36 RA UP,70/32 DN
20"x14"
36"x24"
20"x16"
20/16 C/R EXHAUST UP
40/24 SA DN
50/28 SA UP(15,000 CFM)
18"x14"
20"x18"
50/32 SA UP(19,000 CFM)40/24 SA DN
16/10 LAB EXH.UP AND DN24/20 LAB EXH. UP
40"x20"
10"ø
10/10 EA DN12/12 EA UP(700 CFM)
10"ø
100 CFM
0 / 0
100 CFM
0 / 0
1
1
2
22
60/40 RA UPTO AHU-4
40/40 RA UPTO AHU-3
30/30 SA UPTO AHU-3
60/30 SA UPTO AHU-4
60/30 SA UPTO AHU-5
E
D
C
B
A
1 2 3 4 5 6
E
D
C
B
A
1 2 3 4 5 6
SCALE
PROJECT NUMBER
KEY PLAN
X
CD
F
E G
A
S
B
NORTH
IF THIS SHEET IS NOT 30" X 42", IT IS A REDUCEDSIZE PLOT. USE GRAPHIC SCALE ACCORDINGLY.
NOT FOR CONSTRUCTION
PRELIMINARY
JILAUNIVERSITY OF COLORADO440 UCBBOULDER, CO 80309−0440
JILA ADDITION
CATOR RUMA & ASSOCIATES, CO.896 TABOR STREETLAKEWOOD, CO 80401P: 303.232.6200F: 303.233.3701
MARTIN / MARTIN CONSULTING ENGINEERS12499 WEST COLFAX AVENUEPO BOX 151500LAKEWOOD, CO 80215P: 303.431.6100F: 303.431.6866
M−E ENGINEERS, INC.10055 W. 43RD AVENUEWHEAT RIDGE, CO 80033P: 303.421.6655F: 303.421.0331
HDR ARCHITECTURE, INC.303 EAST 17TH AVENUE, SUITE 1000DENVER, CO 80203P: 303.764.1520F: 303.860.7139
ARCHITECT:
MECHANICAL / ELECTRICAL ENGINEER:
STRUCTURAL / CIVIL ENGINEER:
TELECOMMUNICATIONS ENGINEER:
BELT COLLINS WEST, LTD.4909 PEARL EAST CIRCLE, SUITE 300BOULDER, CO 80301P: 303.442.4588F: 303.786.8026
LANDSCAPE ARCHITECT:
CU PROJECT NO. PR 002650
UNIVERSITY OF COLORADOAT BOULDEROFFICE OF FACILITIES PLANNINGRL−2, THIRD FLOOR, ROOM 301BOULDER, CO 80309P: 303.492.1275F: 303.492.4082
OWNER:
GALLUN SNOW1920 MARKET STREET, SUITE 201DENVER, CO 80202P: 303.433.9500F: 303.433.5624
INTERIOR ARCHITECT:
303 EAST 17TH AVENUE SUITE 1000 DENVER, COLORADO 80203 303.764.1520
HDR ARCHITECTURE, INC.
SCHEMATIC DESIGN04/30/2009
01/19/2010 DESIGN DEVELOPMENT TECHNICAL REVIEW
C:\Revit Local Projects\2010\2008-124 JILA Addition\llange_MECH-2008-124 CU JILA.rvt
1/15/2010 8:47:50 AM
As indicated
MH-101
282-89589
1ST FLOOR HVACPLAN
DESIGN DEVELOPMENT TECHNICAL REVIEW
SCALE: 1/8" = 1'-0"
1ST FLOOR HVAC PLAN
MARK DATE DESCRIPTION
MAINT.ACCESS
MAINT.ACCESS
MAINT.ACCESS
MAINT.ACCESS
MAINT.ACCESS
MAINT.ACCESS
MAINT.
ACCESS
MAINT.
ACCESS
DN
DN
UP
DN
UP
GENERAL NOTES:WORK INCLUDED IN THE CONTRACT IS DENOTED IN BOLD. EXISTING CONDITIONS TOREMAIN ARE DENOTED LIGHTLY.
A DETAILED METHOD OF PROCEDURE IS REQUIRED WHEN A CONSTRUCTIONACTIVITY AFFECTS THE SAFETY OF THE OCCUPANTS, TELEPHONE EQUIPMENT ORVALUABLE CONTENTS OR ANY SYSTEM WHICH SUPPORTS THESE SYSTEMS; ORESSENTIALLY AFFECTS THE BUILDING MANAGEMENT, OPERATIONS OR SECURITY.
CONTRACTOR IS RESPONSIBLE FOR FIELD VERIFICATION OF ALL EXISTINGCONDITIONS PRIOR TO COMMENCEMENT OF ANY WORK AND SHALL NOTIFY THEENGINEER/ARCHITECT OF ANY DISCREPANCIES FOR RESOLUTION.
COORDINATE WORK WITH ALL TRADES.
CONTRACTOR IS RESPONSIBLE FOR SECURING AND WEATHERPROOFING ANYROOF OPENING NOT COMPLETED DURING WORKING HOURS.
COORDINATE ALL DUCTWORK AND PIPING WITH EQUIPMENT, STRUCTURE, ETC.
CONTRACTOR SHALL BE RESPONSIBLE FOR DEACTIVATION OF ROOF-MOUNTEDEQUIPMENT AND ASSOCIATED INDOOR EQUIPMENT. ONLY ONE UNIT SHALL BETAKEN OUT OF SERVICE AT ANY TIME, WITH REMAINDER OF UNITS LEFTOPERATIONAL. COORDINATE WITH GENERAL CONTRACTOR AND ELECTRICALCONTRACTOR.
CONTRACTOR SHALL NOT SHUT DOWN / TAKE OUT OF SERVICE ANY SYSTEMSWITHOUT FIRST COORDINATING WITH OWNER AND PREPARING M.O.P.
1.
2.
3.
4.
5.
6.
7.
8.
HVAC NOTES:ALL LOW PRESSURE RECTANGULAR DUCTWORK DOWNSTREAM OF TERMINALBOX SHALL HAVE 1" THICK INTERNAL DUCT LINER. SIZES SHOWN ARE ACTUALSHEET METAL SIZE AND INCLUDE THICKNESS OF LINER. (UNLESS NOTEDOTHERWISE).
ALL SUPPLY AIR DIFFUSERS ARE 4-WAY AIR PATTERN UNLESS SHOWNOTHERWISE.
DUCT SIZE OF BRANCH DUCT TO AIR DEVICE SHALL BE THE SAME SIZE ASNECK SIZE OF AIR DEVICE UNLESS NOTED OTHERWISE.
BRANCH DUCT SIZE TO INLET OF ALL TERMINAL BOXES SHALL BE THE SAMESIZE AS THE INLET SCHEDULED UNLESS NOTED OTHERWISE.
ALL MEDIUM PRESSURE AND ROUND LOW PRESSURE SUPPLY AIR DUCTWORKSHALL BE EXTERNALLY WRAPPED TO THICKNESS AS STATED INSPECIFICATIONS. RETURN AND EXHAUST DUCTWORK IS NEITHER LINED NORWRAPPED.
PROVIDE ROOM AIR BALANCE TO ACHIEVE POSITIVE (+) OR NEGATIVE (-) ATTHE DIFFERENTIAL PRESSURE INDICATED ON THE DRAWINGS.
1.
2.
3.
4.
5.
6.
FLAG NOTES:
DUCTED FAN COIL UNIT, TYPICAL.
PROVIDE CONVECTOR UNDER WINDOW AS SHOWN. IF SPACE CONTAINSFULL HEIGHT WINDOWS, PROVIDE BASEBOARD AT FULL ROOM LENGTH INLIEU OF CONVECTORS.
COIL PULL CLEARANCE.
ROUTE RA DUCTWORK IN MECHANICAL ROOM, SERVING CLEANROOM RAPLENUM BELOW SLAB.
CONNECT DUCT TO RA PLENUM BELOW AIR HANDLING UNIT. AHU 3, 4, 5 TOHAVE 24" ELEVATED CURB FOR REURN AIR.
TO MAU-1 OA CONNECTION.
PROVIDE SEPARATE, RATED SHAFT ENCLOSURE FOR LAB EXHAUST DUCT.
1
2
3
4
5
6
7
23
45
67
ACFH BG
GRADUATE
OFFICE
X220
ELECT.
X201
MECH
X231
JANITOR
X200
D
SHAFT 1SHAFT 2
TELECOM MAIN
X210
B.1
86.1
5.5
STAIR
STX290
ELECT.
ENTRANCE
X231A
2.5
1
LOWER TERRACE
X245
ELEVATOR
LOBBY
CRX290
E
STORAGE
X240A
CIRCULATION
CRX205
RECYCLE
X205
ELEVATOR
ELX290
STAIR
STX225
CIRCULATION
CRX225
COLLABORATION
X222
COLLABORATION
X242
COLLABORATION
X241
COLLABORATION
X232
CIRCULATION
CRX245
CIRCULATION
CRX240
STAFF OFFICE
S211
STAFF OFFICE
S209 STUDENT OFFICE
S205
STAFF OFFICE
S220
STAFF OFFICE
S222 FACULTY OFFICE
S224
CIRCULATION
CRS200
6.5
ENTRY
CRX295
STORAGE
X215
JANITOR
X255
90/36 LAB RA UP/DN
FCU
#
FCU
#
CUH
2
1
1
FCU
#
1
36"x18"
36/16 RA UP (5,000 CFM)
20"x14"
30"x20"
FCU
#
30/20 SA UP (5,150 CFM)
50/32 SA UP
50/32 SA DN
16/10 LAB EXH. DN
24/20 LAB EXH. DN16/10 LABEXH. UP
24/20 LABEXH. UP
20/16 C/REXH. UP
50/28SA UP
50/28 SA DN(15,000 CFM)
1
FCU
#
1
10"ø
12/12 EA DN
14/12 EA UP(900 CFM)
2
30"x20"
2
2
2
2
2
2
BASEBOARD RADIATONTYPICAL
AHU
3
AHU
5
AHU
4
MAU
1
3
3
7
7
7
2
2
UH
#
UH
#
5
4
RELIEF AIRLOUVER
36"x24"
OA INTAKELOUVER
6
E
D
C
B
A
1 2 3 4 5 6
E
D
C
B
A
1 2 3 4 5 6
SCALE
PROJECT NUMBER
KEY PLAN
X
CD
F
E G
A
S
B
NORTH
IF THIS SHEET IS NOT 30" X 42", IT IS A REDUCEDSIZE PLOT. USE GRAPHIC SCALE ACCORDINGLY.
NOT FOR CONSTRUCTION
PRELIMINARY
JILAUNIVERSITY OF COLORADO440 UCBBOULDER, CO 80309−0440
JILA ADDITION
CATOR RUMA & ASSOCIATES, CO.896 TABOR STREETLAKEWOOD, CO 80401P: 303.232.6200F: 303.233.3701
MARTIN / MARTIN CONSULTING ENGINEERS12499 WEST COLFAX AVENUEPO BOX 151500LAKEWOOD, CO 80215P: 303.431.6100F: 303.431.6866
M−E ENGINEERS, INC.10055 W. 43RD AVENUEWHEAT RIDGE, CO 80033P: 303.421.6655F: 303.421.0331
HDR ARCHITECTURE, INC.303 EAST 17TH AVENUE, SUITE 1000DENVER, CO 80203P: 303.764.1520F: 303.860.7139
ARCHITECT:
MECHANICAL / ELECTRICAL ENGINEER:
STRUCTURAL / CIVIL ENGINEER:
TELECOMMUNICATIONS ENGINEER:
BELT COLLINS WEST, LTD.4909 PEARL EAST CIRCLE, SUITE 300BOULDER, CO 80301P: 303.442.4588F: 303.786.8026
LANDSCAPE ARCHITECT:
CU PROJECT NO. PR 002650
UNIVERSITY OF COLORADOAT BOULDEROFFICE OF FACILITIES PLANNINGRL−2, THIRD FLOOR, ROOM 301BOULDER, CO 80309P: 303.492.1275F: 303.492.4082
OWNER:
GALLUN SNOW1920 MARKET STREET, SUITE 201DENVER, CO 80202P: 303.433.9500F: 303.433.5624
INTERIOR ARCHITECT:
303 EAST 17TH AVENUE SUITE 1000 DENVER, COLORADO 80203 303.764.1520
HDR ARCHITECTURE, INC.
SCHEMATIC DESIGN04/30/2009
01/19/2010 DESIGN DEVELOPMENT TECHNICAL REVIEW
C:\Revit Local Projects\2010\2008-124 JILA Addition\llange_MECH-2008-124 CU JILA.rvt
1/15/2010 8:49:01 AM
As indicated
MH-102
282-89589
2nd FLOOR HVACPLAN
DESIGN DEVELOPMENT TECHNICAL REVIEW
SCALE: 1/8" = 1'-0"
2ND FLOOR HVAC PLAN
MARK DATE DESCRIPTION
MAINT.ACCESS
MAINT.ACCESS
MAINT.
ACCESS
MAINT.ACCESS
MAINT.ACCESS
MAINT.ACCESS
MAINT.ACCESS
MAINT.ACCESS
MAINT.
ACCESS
UPDN
DN
UP
GENERAL NOTES:WORK INCLUDED IN THE CONTRACT IS DENOTED IN BOLD. EXISTING CONDITIONS TOREMAIN ARE DENOTED LIGHTLY.
A DETAILED METHOD OF PROCEDURE IS REQUIRED WHEN A CONSTRUCTIONACTIVITY AFFECTS THE SAFETY OF THE OCCUPANTS, TELEPHONE EQUIPMENT ORVALUABLE CONTENTS OR ANY SYSTEM WHICH SUPPORTS THESE SYSTEMS; ORESSENTIALLY AFFECTS THE BUILDING MANAGEMENT, OPERATIONS OR SECURITY.
CONTRACTOR IS RESPONSIBLE FOR FIELD VERIFICATION OF ALL EXISTINGCONDITIONS PRIOR TO COMMENCEMENT OF ANY WORK AND SHALL NOTIFY THEENGINEER/ARCHITECT OF ANY DISCREPANCIES FOR RESOLUTION.
COORDINATE WORK WITH ALL TRADES.
CONTRACTOR IS RESPONSIBLE FOR SECURING AND WEATHERPROOFING ANYROOF OPENING NOT COMPLETED DURING WORKING HOURS.
COORDINATE ALL DUCTWORK AND PIPING WITH EQUIPMENT, STRUCTURE, ETC.
CONTRACTOR SHALL BE RESPONSIBLE FOR DEACTIVATION OF ROOF-MOUNTEDEQUIPMENT AND ASSOCIATED INDOOR EQUIPMENT. ONLY ONE UNIT SHALL BETAKEN OUT OF SERVICE AT ANY TIME, WITH REMAINDER OF UNITS LEFTOPERATIONAL. COORDINATE WITH GENERAL CONTRACTOR AND ELECTRICALCONTRACTOR.
CONTRACTOR SHALL NOT SHUT DOWN / TAKE OUT OF SERVICE ANY SYSTEMSWITHOUT FIRST COORDINATING WITH OWNER AND PREPARING M.O.P.
1.
2.
3.
4.
5.
6.
7.
8.
HVAC NOTES:ALL LOW PRESSURE RECTANGULAR DUCTWORK DOWNSTREAM OF TERMINALBOX SHALL HAVE 1" THICK INTERNAL DUCT LINER. SIZES SHOWN ARE ACTUALSHEET METAL SIZE AND INCLUDE THICKNESS OF LINER. (UNLESS NOTEDOTHERWISE).
ALL SUPPLY AIR DIFFUSERS ARE 4-WAY AIR PATTERN UNLESS SHOWNOTHERWISE.
DUCT SIZE OF BRANCH DUCT TO AIR DEVICE SHALL BE THE SAME SIZE ASNECK SIZE OF AIR DEVICE UNLESS NOTED OTHERWISE.
BRANCH DUCT SIZE TO INLET OF ALL TERMINAL BOXES SHALL BE THE SAMESIZE AS THE INLET SCHEDULED UNLESS NOTED OTHERWISE.
ALL MEDIUM PRESSURE AND ROUND LOW PRESSURE SUPPLY AIR DUCTWORKSHALL BE EXTERNALLY WRAPPED TO THICKNESS AS STATED INSPECIFICATIONS. RETURN AND EXHAUST DUCTWORK IS NEITHER LINED NORWRAPPED.
PROVIDE ROOM AIR BALANCE TO ACHIEVE POSITIVE (+) OR NEGATIVE (-) ATTHE DIFFERENTIAL PRESSURE INDICATED ON THE DRAWINGS.
1.
2.
3.
4.
5.
6.
FLAG NOTES:
DUCTED FAN COIL UNIT, TYPICAL.
PROVIDE CONVECTOR UNDER WINDOW AS SHOWN. IF SPACE CONTAINSFULL HEIGHT WINDOWS, PROVIDE BASEBOARD AT FULL ROOM LENGTH INLIEU OF CONVECTORS.
PROVIDE SEPARATE, RATED SHAFT ENCLOSURE FOR LAB EXHAUST DUCT.
TYPICAL OFFICE AIR DISTRIBUTION LAYOUT.
1
2
3
4
23
45
67
ACFH BG
STAIR
STX390
ELEC.
X301
JANITOR
X300
D
SHAFT 1 SHAFT 2
B.1
86.1
5.5
UPPER TERRACE
X335
2.5
1
CONFERENCE
X390
GRADUATE
OFFICE
X324
COPIER
X320
CONFERENCE
X340
FELLOWS OFFICE
X350
MEN
X310B
WOMEN
X310A
E
LARGE
CONFERENCE
X315
MEDIUM
CONFERENCE
X325
CIRCULATION
CRX325
STAIR
STX325
COLLABORATION
X355
ELEVATOR
ELX390
STUDENT OFFICE
S315 STUDENT OFFICE
S305
CIRCULATION
CRS300
FACULTY OFFICE
S320
FACULTY OFFICE
S324
CIRCULATION
S350
6.5
CIRCULATION
CRX390
FELLOWS OFFICE
X360
STORAGE
X375
FCU
#
20"x16"
34"x24"
24"x16"
12"ø
20"x16"
48"x24"
FCU
#
FCU
#
1
1
90/36 LAB RA UP/DN54/30 RA UP (15,850 CFM)AND 36/18 DN
34/24 SA UP (8,000 CFM)30/20 SA DN
50/32 LAB SA UP/DN
16/10 LABEXH UP/DN
24/20 LABEXH. UP/DN
50/28 LABSA UP/DN
34/24 SA UP(8,000 CFM)
20/18 C/REXH UP/DN
1
14/12 EA DN18/14 EA UP (1440 CFM)
12"ø
12"ø
8" (TYP)
2
2
2
2
BASEBOARD RADIATIONTYPICAL
3
33
A0 CFM
(TYP. OF 5)
2
2
22
2
2
2
2
E
D
C
B
A
1 2 3 4 5 6
E
D
C
B
A
1 2 3 4 5 6
SCALE
PROJECT NUMBER
KEY PLAN
X
CD
F
E G
A
S
B
NORTH
IF THIS SHEET IS NOT 30" X 42", IT IS A REDUCEDSIZE PLOT. USE GRAPHIC SCALE ACCORDINGLY.
NOT FOR CONSTRUCTION
PRELIMINARY
JILAUNIVERSITY OF COLORADO440 UCBBOULDER, CO 80309−0440
JILA ADDITION
CATOR RUMA & ASSOCIATES, CO.896 TABOR STREETLAKEWOOD, CO 80401P: 303.232.6200F: 303.233.3701
MARTIN / MARTIN CONSULTING ENGINEERS12499 WEST COLFAX AVENUEPO BOX 151500LAKEWOOD, CO 80215P: 303.431.6100F: 303.431.6866
M−E ENGINEERS, INC.10055 W. 43RD AVENUEWHEAT RIDGE, CO 80033P: 303.421.6655F: 303.421.0331
HDR ARCHITECTURE, INC.303 EAST 17TH AVENUE, SUITE 1000DENVER, CO 80203P: 303.764.1520F: 303.860.7139
ARCHITECT:
MECHANICAL / ELECTRICAL ENGINEER:
STRUCTURAL / CIVIL ENGINEER:
TELECOMMUNICATIONS ENGINEER:
BELT COLLINS WEST, LTD.4909 PEARL EAST CIRCLE, SUITE 300BOULDER, CO 80301P: 303.442.4588F: 303.786.8026
LANDSCAPE ARCHITECT:
CU PROJECT NO. PR 002650
UNIVERSITY OF COLORADOAT BOULDEROFFICE OF FACILITIES PLANNINGRL−2, THIRD FLOOR, ROOM 301BOULDER, CO 80309P: 303.492.1275F: 303.492.4082
OWNER:
GALLUN SNOW1920 MARKET STREET, SUITE 201DENVER, CO 80202P: 303.433.9500F: 303.433.5624
INTERIOR ARCHITECT:
303 EAST 17TH AVENUE SUITE 1000 DENVER, COLORADO 80203 303.764.1520
HDR ARCHITECTURE, INC.
SCHEMATIC DESIGN04/30/2009
01/19/2010 DESIGN DEVELOPMENT TECHNICAL REVIEW
C:\Revit Local Projects\2010\2008-124 JILA Addition\llange_MECH-2008-124 CU JILA.rvt
1/15/2010 8:49:42 AM
As indicated
MH-103
282-89589
3rd FLOOR HVACPLAN
DESIGN DEVELOPMENT TECHNICAL REVIEW
SCALE: 1/8" = 1'-0"
3RD FLOOR HVAC PLAN
MARK DATE DESCRIPTION
MAINT.ACCESS
MAINT.ACCESS
MAINT.ACCESS
MAINT.ACCESS
MAINT.ACCESS
MAINT.ACCESSMAINT.ACCESS
MAINT.ACCESS
MAINT.ACCESS
MAINT.ACCESS
MAINT.ACCESS
MAINT.
ACCESS
UPDN
DN
UP
DN
GENERAL NOTES:WORK INCLUDED IN THE CONTRACT IS DENOTED IN BOLD. EXISTING CONDITIONS TOREMAIN ARE DENOTED LIGHTLY.
A DETAILED METHOD OF PROCEDURE IS REQUIRED WHEN A CONSTRUCTIONACTIVITY AFFECTS THE SAFETY OF THE OCCUPANTS, TELEPHONE EQUIPMENT ORVALUABLE CONTENTS OR ANY SYSTEM WHICH SUPPORTS THESE SYSTEMS; ORESSENTIALLY AFFECTS THE BUILDING MANAGEMENT, OPERATIONS OR SECURITY.
CONTRACTOR IS RESPONSIBLE FOR FIELD VERIFICATION OF ALL EXISTINGCONDITIONS PRIOR TO COMMENCEMENT OF ANY WORK AND SHALL NOTIFY THEENGINEER/ARCHITECT OF ANY DISCREPANCIES FOR RESOLUTION.
COORDINATE WORK WITH ALL TRADES.
CONTRACTOR IS RESPONSIBLE FOR SECURING AND WEATHERPROOFING ANYROOF OPENING NOT COMPLETED DURING WORKING HOURS.
COORDINATE ALL DUCTWORK AND PIPING WITH EQUIPMENT, STRUCTURE, ETC.
CONTRACTOR SHALL BE RESPONSIBLE FOR DEACTIVATION OF ROOF-MOUNTEDEQUIPMENT AND ASSOCIATED INDOOR EQUIPMENT. ONLY ONE UNIT SHALL BETAKEN OUT OF SERVICE AT ANY TIME, WITH REMAINDER OF UNITS LEFTOPERATIONAL. COORDINATE WITH GENERAL CONTRACTOR AND ELECTRICALCONTRACTOR.
CONTRACTOR SHALL NOT SHUT DOWN / TAKE OUT OF SERVICE ANY SYSTEMSWITHOUT FIRST COORDINATING WITH OWNER AND PREPARING M.O.P.
1.
2.
3.
4.
5.
6.
7.
8.
HVAC NOTES:ALL LOW PRESSURE RECTANGULAR DUCTWORK DOWNSTREAM OF TERMINALBOX SHALL HAVE 1" THICK INTERNAL DUCT LINER. SIZES SHOWN ARE ACTUALSHEET METAL SIZE AND INCLUDE THICKNESS OF LINER. (UNLESS NOTEDOTHERWISE).
ALL SUPPLY AIR DIFFUSERS ARE 4-WAY AIR PATTERN UNLESS SHOWNOTHERWISE.
DUCT SIZE OF BRANCH DUCT TO AIR DEVICE SHALL BE THE SAME SIZE ASNECK SIZE OF AIR DEVICE UNLESS NOTED OTHERWISE.
BRANCH DUCT SIZE TO INLET OF ALL TERMINAL BOXES SHALL BE THE SAMESIZE AS THE INLET SCHEDULED UNLESS NOTED OTHERWISE.
ALL MEDIUM PRESSURE AND ROUND LOW PRESSURE SUPPLY AIR DUCTWORKSHALL BE EXTERNALLY WRAPPED TO THICKNESS AS STATED INSPECIFICATIONS. RETURN AND EXHAUST DUCTWORK IS NEITHER LINED NORWRAPPED.
PROVIDE ROOM AIR BALANCE TO ACHIEVE POSITIVE (+) OR NEGATIVE (-) ATTHE DIFFERENTIAL PRESSURE INDICATED ON THE DRAWINGS.
1.
2.
3.
4.
5.
6.
FLAG NOTES:
DUCTED FAN COIL UNIT, TYPICAL.
PROVIDE CONVECTOR UNDER WINDOW AS SHOWN. IF SPACE CONTAINSFULL HEIGHT WINDOWS, PROVIDE BASEBOARD AT FULL ROOM LENGTH INLIEU OF CONVECTORS.
PROVIDE SEPARATE, RATED ENCLOSURE FOR LAB EXHAUST DUCT.
1
2
3
23
45
67
ACFH BG
STAIR
STX490
JANITOR
X414
D
CONFERENCE
X490
SHAFT 1 SHAFT 2
B.1
86.1
5.5
ELEC.
X405
2.5
1
E
CONFERENCE
X440
FELLOWS OFFICE
X460
POST DOC
OFFICE
X445
FELLOW OFFICE
X435
FELLOW OFFICE
X425
GRADUATE
OFFICES
X415
WOMEN
X410
MEN
X420
TELECOM
X424
ADMINSTRATIVE
OFFICE
X429
STAIR
STX425
COLLABORATION
X421
STORAGE
X409
COLLABORATION
X441
GRADUATE
OFFICE
X428
STAIR
STX400
ELEVATOR
ELX490
CIRCULATION
CRX425
TELECOM
S420
MECHANICAL
S410
MECHANICAL
S405CIRCULATON
CRS410
6.5
CIRCULATION
CRX490
FELLOWS OFFICE
X450
POST DOC
OFFICE
X455
STORAGE
X465
1
2
2.5
3
4
5
6
7
8
5.5
6.1
ABCDEFGH B.1
EX.E
EX.1 EX.2 EX.3 EX.4 EX.5 EX.6
EX.7
6.5
24"x20"
16"x14"
24"x20"
12"ø
24"x20"
24"x20"
FCU
#
CUH
#
FCU
#
FCU
#
FCU
#
1
1
90/36 LAB RA UP/DN
48"x24"
70/34 RA UP (25,250 CFM)45/30 RA DN
CUH
2
48/24 SA UP (12,900 CFM)34/24 SA DN
50/32 LAB SA UP/DN
16/10 LAB EXH.UP/DN
24/20 LAB EXH.UP/DN
50/28 LAB SA UP/DN20/16 C/R EXH.UP/DN
48/24 SA UP (12,500 CFM)34/24 SA DN
1
2
1
2
2
2
2
BASEBOARD RADIATIONTYPICAL
18/14 EA DN18/16 EA UP(1,840 CFM)
12"ø
8" TYP.
3
3
3
2
2
2
2
2
2
2
2
2
2
E
D
C
B
A
1 2 3 4 5 6
E
D
C
B
A
1 2 3 4 5 6
SCALE
PROJECT NUMBER
KEY PLAN
X
CD
F
E G
A
S
B
NORTH
IF THIS SHEET IS NOT 30" X 42", IT IS A REDUCEDSIZE PLOT. USE GRAPHIC SCALE ACCORDINGLY.
NOT FOR CONSTRUCTION
PRELIMINARY
JILAUNIVERSITY OF COLORADO440 UCBBOULDER, CO 80309−0440
JILA ADDITION
CATOR RUMA & ASSOCIATES, CO.896 TABOR STREETLAKEWOOD, CO 80401P: 303.232.6200F: 303.233.3701
MARTIN / MARTIN CONSULTING ENGINEERS12499 WEST COLFAX AVENUEPO BOX 151500LAKEWOOD, CO 80215P: 303.431.6100F: 303.431.6866
M−E ENGINEERS, INC.10055 W. 43RD AVENUEWHEAT RIDGE, CO 80033P: 303.421.6655F: 303.421.0331
HDR ARCHITECTURE, INC.303 EAST 17TH AVENUE, SUITE 1000DENVER, CO 80203P: 303.764.1520F: 303.860.7139
ARCHITECT:
MECHANICAL / ELECTRICAL ENGINEER:
STRUCTURAL / CIVIL ENGINEER:
TELECOMMUNICATIONS ENGINEER:
BELT COLLINS WEST, LTD.4909 PEARL EAST CIRCLE, SUITE 300BOULDER, CO 80301P: 303.442.4588F: 303.786.8026
LANDSCAPE ARCHITECT:
CU PROJECT NO. PR 002650
UNIVERSITY OF COLORADOAT BOULDEROFFICE OF FACILITIES PLANNINGRL−2, THIRD FLOOR, ROOM 301BOULDER, CO 80309P: 303.492.1275F: 303.492.4082
OWNER:
GALLUN SNOW1920 MARKET STREET, SUITE 201DENVER, CO 80202P: 303.433.9500F: 303.433.5624
INTERIOR ARCHITECT:
303 EAST 17TH AVENUE SUITE 1000 DENVER, COLORADO 80203 303.764.1520
HDR ARCHITECTURE, INC.
SCHEMATIC DESIGN04/30/2009
01/19/2010 DESIGN DEVELOPMENT TECHNICAL REVIEW
C:\Revit Local Projects\2010\2008-124 JILA Addition\llange_MECH-2008-124 CU JILA.rvt
1/15/2010 8:50:14 AM
As indicated
MH-104
282-89589
4th FLOOR HVACPLAN
DESIGN DEVELOPMENT TECHNICAL REVIEW
SCALE: 1/8" = 1'-0"
4TH FLOOR HVAC PLAN
MARK DATE DESCRIPTION
MAINT.
ACCESS
MAINT.
ACCESS
MAINT.
ACCESS
UPDN
UP
DNUP
GENERAL NOTES:WORK INCLUDED IN THE CONTRACT IS DENOTED IN BOLD. EXISTING CONDITIONS TOREMAIN ARE DENOTED LIGHTLY.
A DETAILED METHOD OF PROCEDURE IS REQUIRED WHEN A CONSTRUCTIONACTIVITY AFFECTS THE SAFETY OF THE OCCUPANTS, TELEPHONE EQUIPMENT ORVALUABLE CONTENTS OR ANY SYSTEM WHICH SUPPORTS THESE SYSTEMS; ORESSENTIALLY AFFECTS THE BUILDING MANAGEMENT, OPERATIONS OR SECURITY.
CONTRACTOR IS RESPONSIBLE FOR FIELD VERIFICATION OF ALL EXISTINGCONDITIONS PRIOR TO COMMENCEMENT OF ANY WORK AND SHALL NOTIFY THEENGINEER/ARCHITECT OF ANY DISCREPANCIES FOR RESOLUTION.
COORDINATE WORK WITH ALL TRADES.
CONTRACTOR IS RESPONSIBLE FOR SECURING AND WEATHERPROOFING ANYROOF OPENING NOT COMPLETED DURING WORKING HOURS.
COORDINATE ALL DUCTWORK AND PIPING WITH EQUIPMENT, STRUCTURE, ETC.
CONTRACTOR SHALL BE RESPONSIBLE FOR DEACTIVATION OF ROOF-MOUNTEDEQUIPMENT AND ASSOCIATED INDOOR EQUIPMENT. ONLY ONE UNIT SHALL BETAKEN OUT OF SERVICE AT ANY TIME, WITH REMAINDER OF UNITS LEFTOPERATIONAL. COORDINATE WITH GENERAL CONTRACTOR AND ELECTRICALCONTRACTOR.
CONTRACTOR SHALL NOT SHUT DOWN / TAKE OUT OF SERVICE ANY SYSTEMSWITHOUT FIRST COORDINATING WITH OWNER AND PREPARING M.O.P.
1.
2.
3.
4.
5.
6.
7.
8.
HVAC NOTES:ALL LOW PRESSURE RECTANGULAR DUCTWORK DOWNSTREAM OF TERMINALBOX SHALL HAVE 1" THICK INTERNAL DUCT LINER. SIZES SHOWN ARE ACTUALSHEET METAL SIZE AND INCLUDE THICKNESS OF LINER. (UNLESS NOTEDOTHERWISE).
ALL SUPPLY AIR DIFFUSERS ARE 4-WAY AIR PATTERN UNLESS SHOWNOTHERWISE.
DUCT SIZE OF BRANCH DUCT TO AIR DEVICE SHALL BE THE SAME SIZE ASNECK SIZE OF AIR DEVICE UNLESS NOTED OTHERWISE.
BRANCH DUCT SIZE TO INLET OF ALL TERMINAL BOXES SHALL BE THE SAMESIZE AS THE INLET SCHEDULED UNLESS NOTED OTHERWISE.
ALL MEDIUM PRESSURE AND ROUND LOW PRESSURE SUPPLY AIR DUCTWORKSHALL BE EXTERNALLY WRAPPED TO THICKNESS AS STATED INSPECIFICATIONS. RETURN AND EXHAUST DUCTWORK IS NEITHER LINED NORWRAPPED.
PROVIDE ROOM AIR BALANCE TO ACHIEVE POSITIVE (+) OR NEGATIVE (-) ATTHE DIFFERENTIAL PRESSURE INDICATED ON THE DRAWINGS.
1.
2.
3.
4.
5.
6.
FLAG NOTES:
DUCTED FAN COIL UNIT, TYPICAL.
SUPPORT DUCTWORK FROM PENTHOUSE FLOOR.
PROVIDE 2-HOUR FIRE BLANKET AROUND EXHAUST DUCTWORK, WHEREROUTED THROUGH PENTHOUSE FROM SHAFT TO ROOF EXIT.
ROUTE DUCT TO SHAFT.
SA DUCT TO PROVIDE VENTILATION AIR TO SOUTH TOWER FCU'S.
1
2
3
4
5
23
45
67
ACFH BG
MECHANICAL
X525
D
STAIR
STX500
SHAFT 1 SHAFT 2
B.1
86.1
5.5
2.5
1
CONFERENCE
X590
STAIR
STX590
WOMEN
RRWX542
MEN
RRMX544
SHAFT 4
SHAFT 3
E
CORRIDOR
CRX555
STAIR
STX550
ELEVATOR
ELX590
6.5
VESTIBULE
CRX590
1
2
2.5
3
4
5
6
7
8
5.5
6.1
ABCDEFGH B.1
EX.E
EX.1 EX.2 EX.3 EX.4 EX.5 EX.6
EX.7
6.5
FCU
#
CUH
#
1
AHU
1
48/24 SA DN(12,900 CFM)
50/32 SA DN(19,000 CFM)
16/10 LAB EXH. DN(1,000 CFM)
24/20 LAB EXH. DN(5,000 CFM)
3
3
24" DEEP INTAKE PLENUMTO OA LOUVERS
70"x34"
70/34 RA DN
2
18"x16"
20"x18"
20/18 EA UP TOFAN ON ROOF(2,500 CFM)
18/16 EA DN
20/16 C/R EXH. DN(4,000 CFM)
AHU
2
FCU
#
1
64
24" DEEP INTAKE PLENUMTO OA LOUVERS
4
UH
#
UH
#
UH
#
UH
#
CONVECTOR
E
D
C
B
A
1 2 3 4 5 6
E
D
C
B
A
1 2 3 4 5 6
SCALE
PROJECT NUMBER
KEY PLAN
X
CD
F
E G
A
S
B
NORTH
IF THIS SHEET IS NOT 30" X 42", IT IS A REDUCEDSIZE PLOT. USE GRAPHIC SCALE ACCORDINGLY.
NOT FOR CONSTRUCTION
PRELIMINARY
JILAUNIVERSITY OF COLORADO440 UCBBOULDER, CO 80309−0440
JILA ADDITION
CATOR RUMA & ASSOCIATES, CO.896 TABOR STREETLAKEWOOD, CO 80401P: 303.232.6200F: 303.233.3701
MARTIN / MARTIN CONSULTING ENGINEERS12499 WEST COLFAX AVENUEPO BOX 151500LAKEWOOD, CO 80215P: 303.431.6100F: 303.431.6866
M−E ENGINEERS, INC.10055 W. 43RD AVENUEWHEAT RIDGE, CO 80033P: 303.421.6655F: 303.421.0331
HDR ARCHITECTURE, INC.303 EAST 17TH AVENUE, SUITE 1000DENVER, CO 80203P: 303.764.1520F: 303.860.7139
ARCHITECT:
MECHANICAL / ELECTRICAL ENGINEER:
STRUCTURAL / CIVIL ENGINEER:
TELECOMMUNICATIONS ENGINEER:
BELT COLLINS WEST, LTD.4909 PEARL EAST CIRCLE, SUITE 300BOULDER, CO 80301P: 303.442.4588F: 303.786.8026
LANDSCAPE ARCHITECT:
CU PROJECT NO. PR 002650
UNIVERSITY OF COLORADOAT BOULDEROFFICE OF FACILITIES PLANNINGRL−2, THIRD FLOOR, ROOM 301BOULDER, CO 80309P: 303.492.1275F: 303.492.4082
OWNER:
GALLUN SNOW1920 MARKET STREET, SUITE 201DENVER, CO 80202P: 303.433.9500F: 303.433.5624
INTERIOR ARCHITECT:
303 EAST 17TH AVENUE SUITE 1000 DENVER, COLORADO 80203 303.764.1520
HDR ARCHITECTURE, INC.
SCHEMATIC DESIGN04/30/2009
01/19/2010 DESIGN DEVELOPMENT TECHNICAL REVIEW
C:\Revit Local Projects\2010\2008-124 JILA Addition\llange_MECH-2008-124 CU JILA.rvt
1/15/2010 8:50:43 AM
As indicated
MH-105
282-89589
5th FLOOR HVACPLAN
DESIGN DEVELOPMENT TECHNICAL REVIEW
SCALE: 1/8" = 1'-0"
5TH FLOOR HVAC PLAN
MARK DATE DESCRIPTION
MAINT.ACCESS
MAINT.ACCESS
MAINT.
ACCESS
DN
DN
DN
GENERAL NOTES:WORK INCLUDED IN THE CONTRACT IS DENOTED IN BOLD. EXISTING CONDITIONS TOREMAIN ARE DENOTED LIGHTLY.
A DETAILED METHOD OF PROCEDURE IS REQUIRED WHEN A CONSTRUCTIONACTIVITY AFFECTS THE SAFETY OF THE OCCUPANTS, TELEPHONE EQUIPMENT ORVALUABLE CONTENTS OR ANY SYSTEM WHICH SUPPORTS THESE SYSTEMS; ORESSENTIALLY AFFECTS THE BUILDING MANAGEMENT, OPERATIONS OR SECURITY.
CONTRACTOR IS RESPONSIBLE FOR FIELD VERIFICATION OF ALL EXISTINGCONDITIONS PRIOR TO COMMENCEMENT OF ANY WORK AND SHALL NOTIFY THEENGINEER/ARCHITECT OF ANY DISCREPANCIES FOR RESOLUTION.
COORDINATE WORK WITH ALL TRADES.
CONTRACTOR IS RESPONSIBLE FOR SECURING AND WEATHERPROOFING ANYROOF OPENING NOT COMPLETED DURING WORKING HOURS.
COORDINATE ALL DUCTWORK AND PIPING WITH EQUIPMENT, STRUCTURE, ETC.
CONTRACTOR SHALL BE RESPONSIBLE FOR DEACTIVATION OF ROOF-MOUNTEDEQUIPMENT AND ASSOCIATED INDOOR EQUIPMENT. ONLY ONE UNIT SHALL BETAKEN OUT OF SERVICE AT ANY TIME, WITH REMAINDER OF UNITS LEFTOPERATIONAL. COORDINATE WITH GENERAL CONTRACTOR AND ELECTRICALCONTRACTOR.
CONTRACTOR SHALL NOT SHUT DOWN / TAKE OUT OF SERVICE ANY SYSTEMSWITHOUT FIRST COORDINATING WITH OWNER AND PREPARING M.O.P.
1.
2.
3.
4.
5.
6.
7.
8.
HVAC NOTES:ALL LOW PRESSURE RECTANGULAR DUCTWORK DOWNSTREAM OF TERMINALBOX SHALL HAVE 1" THICK INTERNAL DUCT LINER. SIZES SHOWN ARE ACTUALSHEET METAL SIZE AND INCLUDE THICKNESS OF LINER. (UNLESS NOTEDOTHERWISE).
ALL SUPPLY AIR DIFFUSERS ARE 4-WAY AIR PATTERN UNLESS SHOWNOTHERWISE.
DUCT SIZE OF BRANCH DUCT TO AIR DEVICE SHALL BE THE SAME SIZE ASNECK SIZE OF AIR DEVICE UNLESS NOTED OTHERWISE.
BRANCH DUCT SIZE TO INLET OF ALL TERMINAL BOXES SHALL BE THE SAMESIZE AS THE INLET SCHEDULED UNLESS NOTED OTHERWISE.
ALL MEDIUM PRESSURE AND ROUND LOW PRESSURE SUPPLY AIR DUCTWORKSHALL BE EXTERNALLY WRAPPED TO THICKNESS AS STATED INSPECIFICATIONS. RETURN AND EXHAUST DUCTWORK IS NEITHER LINED NORWRAPPED.
PROVIDE ROOM AIR BALANCE TO ACHIEVE POSITIVE (+) OR NEGATIVE (-) ATTHE DIFFERENTIAL PRESSURE INDICATED ON THE DRAWINGS.
1.
2.
3.
4.
5.
6.
FLAG NOTES:
DUCTED FAN COIL UNIT. TYPICAL.
SA DUCT TO PROVIDE VENTILATION AIR TO SOUTH TOWER FCU'S.
1
2
23
45
67
ACFH BG
D
B.1
86.1
5.5
2.5
1
E
6.5
1
2
2.5
3
4
5
6
7
8
5.5
6.1
ABCDEFGH B.1
EX.E
EX.1 EX.2 EX.3 EX.4 EX.5 EX.6
EX.7
6.5
FCU
#
CUH
#
12" DN
1
2
EF
2A
EF
2B
EF
3A
EF
3B
EF
1
VAV TERMINAL,TYPICAL
E
D
C
B
A
1 2 3 4 5 6
E
D
C
B
A
1 2 3 4 5 6
SCALE
PROJECT NUMBER
KEY PLAN
X
CD
F
E G
A
S
B
NORTH
IF THIS SHEET IS NOT 30" X 42", IT IS A REDUCEDSIZE PLOT. USE GRAPHIC SCALE ACCORDINGLY.
NOT FOR CONSTRUCTION
PRELIMINARY
JILAUNIVERSITY OF COLORADO440 UCBBOULDER, CO 80309−0440
JILA ADDITION
CATOR RUMA & ASSOCIATES, CO.896 TABOR STREETLAKEWOOD, CO 80401P: 303.232.6200F: 303.233.3701
MARTIN / MARTIN CONSULTING ENGINEERS12499 WEST COLFAX AVENUEPO BOX 151500LAKEWOOD, CO 80215P: 303.431.6100F: 303.431.6866
M−E ENGINEERS, INC.10055 W. 43RD AVENUEWHEAT RIDGE, CO 80033P: 303.421.6655F: 303.421.0331
HDR ARCHITECTURE, INC.303 EAST 17TH AVENUE, SUITE 1000DENVER, CO 80203P: 303.764.1520F: 303.860.7139
ARCHITECT:
MECHANICAL / ELECTRICAL ENGINEER:
STRUCTURAL / CIVIL ENGINEER:
TELECOMMUNICATIONS ENGINEER:
BELT COLLINS WEST, LTD.4909 PEARL EAST CIRCLE, SUITE 300BOULDER, CO 80301P: 303.442.4588F: 303.786.8026
LANDSCAPE ARCHITECT:
CU PROJECT NO. PR 002650
UNIVERSITY OF COLORADOAT BOULDEROFFICE OF FACILITIES PLANNINGRL−2, THIRD FLOOR, ROOM 301BOULDER, CO 80309P: 303.492.1275F: 303.492.4082
OWNER:
GALLUN SNOW1920 MARKET STREET, SUITE 201DENVER, CO 80202P: 303.433.9500F: 303.433.5624
INTERIOR ARCHITECT:
303 EAST 17TH AVENUE SUITE 1000 DENVER, COLORADO 80203 303.764.1520
HDR ARCHITECTURE, INC.
SCHEMATIC DESIGN04/30/2009
01/19/2010 DESIGN DEVELOPMENT TECHNICAL REVIEW
C:\Revit Local Projects\2010\2008-124 JILA Addition\llange_MECH-2008-124 CU JILA.rvt
1/15/2010 8:51:09 AM
As indicated
MH-106
282-89589
6th FLOOR HVACPLAN
DESIGN DEVELOPMENT TECHNICAL REVIEW
SCALE: 1/8" = 1'-0"
6TH FLOOR HVAC PLAN
MARK DATE DESCRIPTION
GENERAL NOTES:WORK INCLUDED IN THE CONTRACT IS DENOTED IN BOLD. EXISTING CONDITIONS TOREMAIN ARE DENOTED LIGHTLY.
A DETAILED METHOD OF PROCEDURE IS REQUIRED WHEN A CONSTRUCTIONACTIVITY AFFECTS THE SAFETY OF THE OCCUPANTS, TELEPHONE EQUIPMENT ORVALUABLE CONTENTS OR ANY SYSTEM WHICH SUPPORTS THESE SYSTEMS; ORESSENTIALLY AFFECTS THE BUILDING MANAGEMENT, OPERATIONS OR SECURITY.
CONTRACTOR IS RESPONSIBLE FOR FIELD VERIFICATION OF ALL EXISTINGCONDITIONS PRIOR TO COMMENCEMENT OF ANY WORK AND SHALL NOTIFY THEENGINEER/ARCHITECT OF ANY DISCREPANCIES FOR RESOLUTION.
COORDINATE WORK WITH ALL TRADES.
CONTRACTOR IS RESPONSIBLE FOR SECURING AND WEATHERPROOFING ANYROOF OPENING NOT COMPLETED DURING WORKING HOURS.
COORDINATE ALL DUCTWORK AND PIPING WITH EQUIPMENT, STRUCTURE, ETC.
CONTRACTOR SHALL BE RESPONSIBLE FOR DEACTIVATION OF ROOF-MOUNTEDEQUIPMENT AND ASSOCIATED INDOOR EQUIPMENT. ONLY ONE UNIT SHALL BETAKEN OUT OF SERVICE AT ANY TIME, WITH REMAINDER OF UNITS LEFTOPERATIONAL. COORDINATE WITH GENERAL CONTRACTOR AND ELECTRICALCONTRACTOR.
CONTRACTOR SHALL NOT SHUT DOWN / TAKE OUT OF SERVICE ANY SYSTEMSWITHOUT FIRST COORDINATING WITH OWNER AND PREPARING M.O.P.
1.
2.
3.
4.
5.
6.
7.
8.
HVAC NOTES:ALL LOW PRESSURE RECTANGULAR DUCTWORK DOWNSTREAM OF TERMINALBOX SHALL HAVE 1" THICK INTERNAL DUCT LINER. SIZES SHOWN ARE ACTUALSHEET METAL SIZE AND INCLUDE THICKNESS OF LINER. (UNLESS NOTEDOTHERWISE).
ALL SUPPLY AIR DIFFUSERS ARE 4-WAY AIR PATTERN UNLESS SHOWNOTHERWISE.
DUCT SIZE OF BRANCH DUCT TO AIR DEVICE SHALL BE THE SAME SIZE ASNECK SIZE OF AIR DEVICE UNLESS NOTED OTHERWISE.
BRANCH DUCT SIZE TO INLET OF ALL TERMINAL BOXES SHALL BE THE SAMESIZE AS THE INLET SCHEDULED UNLESS NOTED OTHERWISE.
ALL MEDIUM PRESSURE AND ROUND LOW PRESSURE SUPPLY AIR DUCTWORKSHALL BE EXTERNALLY WRAPPED TO THICKNESS AS STATED INSPECIFICATIONS. RETURN AND EXHAUST DUCTWORK IS NEITHER LINED NORWRAPPED.
PROVIDE ROOM AIR BALANCE TO ACHIEVE POSITIVE (+) OR NEGATIVE (-) ATTHE DIFFERENTIAL PRESSURE INDICATED ON THE DRAWINGS.
1.
2.
3.
4.
5.
6.
23
45
67
ACFH BG D B.1
86.1
5.5
2.5
1
E
6.5
1
2
2.5
3
4
5
6
7
8
5.5
6.1
ABCDEFGH B.1
EX.E
EX.1 EX.2 EX.3 EX.4 EX.5 EX.6
EX.7
6.5
E
D
C
B
A
1 2 3 4 5 6
E
D
C
B
A
1 2 3 4 5 6
SCALE
PROJECT NUMBER
KEY PLAN
X
CD
F
E G
A
S
B
NORTH
IF THIS SHEET IS NOT 30" X 42", IT IS A REDUCEDSIZE PLOT. USE GRAPHIC SCALE ACCORDINGLY.
NOT FOR CONSTRUCTION
PRELIMINARY
JILAUNIVERSITY OF COLORADO440 UCBBOULDER, CO 80309−0440
JILA ADDITION
CATOR RUMA & ASSOCIATES, CO.896 TABOR STREETLAKEWOOD, CO 80401P: 303.232.6200F: 303.233.3701
MARTIN / MARTIN CONSULTING ENGINEERS12499 WEST COLFAX AVENUEPO BOX 151500LAKEWOOD, CO 80215P: 303.431.6100F: 303.431.6866
M−E ENGINEERS, INC.10055 W. 43RD AVENUEWHEAT RIDGE, CO 80033P: 303.421.6655F: 303.421.0331
HDR ARCHITECTURE, INC.303 EAST 17TH AVENUE, SUITE 1000DENVER, CO 80203P: 303.764.1520F: 303.860.7139
ARCHITECT:
MECHANICAL / ELECTRICAL ENGINEER:
STRUCTURAL / CIVIL ENGINEER:
TELECOMMUNICATIONS ENGINEER:
BELT COLLINS WEST, LTD.4909 PEARL EAST CIRCLE, SUITE 300BOULDER, CO 80301P: 303.442.4588F: 303.786.8026
LANDSCAPE ARCHITECT:
CU PROJECT NO. PR 002650
UNIVERSITY OF COLORADOAT BOULDEROFFICE OF FACILITIES PLANNINGRL−2, THIRD FLOOR, ROOM 301BOULDER, CO 80309P: 303.492.1275F: 303.492.4082
OWNER:
GALLUN SNOW1920 MARKET STREET, SUITE 201DENVER, CO 80202P: 303.433.9500F: 303.433.5624
INTERIOR ARCHITECT:
303 EAST 17TH AVENUE SUITE 1000 DENVER, COLORADO 80203 303.764.1520
HDR ARCHITECTURE, INC.
SCHEMATIC DESIGN04/30/2009
01/19/2010 DESIGN DEVELOPMENT TECHNICAL REVIEW
C:\Revit Local Projects\2010\2008-124 JILA Addition\llange_MECH-2008-124 CU JILA.rvt
1/15/2010 8:51:32 AM
1/8" = 1'-0"
MH-107
282-89589
ROOF MECHANICALPLAN
DESIGN DEVELOPMENT TECHNICAL REVIEW
SCALE: 1/8" = 1'-0"
ROOF HVAC PLAN
MARK DATE DESCRIPTION
23
45
67
ACFH BG D B.1
86.
15.
52.
51
E
JILA ADDITION
F: 303.421.0331
303 EAST 17TH AVENUE SUITE 1000 DENVER, COLORADO 80203 303.764.1520
BASEMENTZONING PLAN
MH−20B
23
45
67
ACFH BG D B.1
86.
15.
52.
51
E
JILA ADDITION
F: 303.421.0331
303 EAST 17TH AVENUE SUITE 1000 DENVER, COLORADO 80203 303.764.1520
FIRST FLOORZONING PLAN
MH−201
23
45
67
ACFH BG D B.1
86.
15.
52.
51
E
JILA ADDITION
F: 303.421.0331
303 EAST 17TH AVENUE SUITE 1000 DENVER, COLORADO 80203 303.764.1520
SECOND FLOORZONING PLAN
MH−202
23
45
67
ACFH BG D B.1
86.
15.
52.
51
E
JILA ADDITION
F: 303.421.0331
303 EAST 17TH AVENUE SUITE 1000 DENVER, COLORADO 80203 303.764.1520
THIRD FLOORZONING PLAN
MH−203
23
45
67
ACFH BG D B.1
86.
15.
52.
51
E
JILA ADDITION
F: 303.421.0331
303 EAST 17TH AVENUE SUITE 1000 DENVER, COLORADO 80203 303.764.1520
FOURTH FLOORZONING PLAN
MH−204
23
45
67
ACFH BG D B.1
86.
15.
52.
51
E
23
45
67
ACFH BG D B.1
86.
15.
52.
51
E
JILA ADDITION
F: 303.421.0331
303 EAST 17TH AVENUE SUITE 1000 DENVER, COLORADO 80203 303.764.1520
FIFTH FLOORZONING PLAN
MH−205
23
45
67
ACFH BG D B.1
86.
15.
52.
51
E
342
JILA ADDITION
F: 303.421.0331
303 EAST 17TH AVENUE SUITE 1000 DENVER, COLORADO 80203 303.764.1520
SIXTH FLOOR ZONING PLAN
MH−206
MAINT.
ACCESS
MAINT.
ACCESS
MAINT.ACCESS
MAINT.ACCESS
MAINT.ACCESS
MAINT.ACCESS
MAINT.ACCESS
MAINT.ACCESS
MAINT.
ACCESS
MAINT.ACCESS
MAINT.ACCESS
MAINT.ACCESS
MAINT.ACCESS
MAINT.ACCESS
MAINT.ACCESS
MAINT.ACCESS
MAINT.
ACCESS
MAINT.
ACCESS
MAINT.
ACCESS
MAINT.
ACCESS
MAINT.
ACCESS
MAINT.
ACCESS
MAINT.ACCESS
MAINT.
ACCESS
UP
DN
UP
DN
UP
UP
UP
DN
GENERAL NOTES:WORK INCLUDED IN THE CONTRACT IS DENOTED IN BOLD. EXISTING CONDITIONS TOREMAIN ARE DENOTED LIGHTLY.
A DETAILED METHOD OF PROCEDURE IS REQUIRED WHEN A CONSTRUCTIONACTIVITY AFFECTS THE SAFETY OF THE OCCUPANTS, TELEPHONE EQUIPMENT ORVALUABLE CONTENTS OR ANY SYSTEM WHICH SUPPORTS THESE SYSTEMS; ORESSENTIALLY AFFECTS THE BUILDING MANAGEMENT, OPERATIONS OR SECURITY.
CONTRACTOR IS RESPONSIBLE FOR FIELD VERIFICATION OF ALL EXISTINGCONDITIONS PRIOR TO COMMENCEMENT OF ANY WORK AND SHALL NOTIFY THEENGINEER/ARCHITECT OF ANY DISCREPANCIES FOR RESOLUTION.
COORDINATE WORK WITH ALL TRADES.
CONTRACTOR IS RESPONSIBLE FOR SECURING AND WEATHERPROOFING ANYROOF OPENING NOT COMPLETED DURING WORKING HOURS.
COORDINATE ALL DUCTWORK AND PIPING WITH EQUIPMENT, STRUCTURE, ETC.
CONTRACTOR SHALL BE RESPONSIBLE FOR DEACTIVATION OF ROOF-MOUNTEDEQUIPMENT AND ASSOCIATED INDOOR EQUIPMENT. ONLY ONE UNIT SHALL BETAKEN OUT OF SERVICE AT ANY TIME, WITH REMAINDER OF UNITS LEFTOPERATIONAL. COORDINATE WITH GENERAL CONTRACTOR AND ELECTRICALCONTRACTOR.
CONTRACTOR SHALL NOT SHUT DOWN / TAKE OUT OF SERVICE ANY SYSTEMSWITHOUT FIRST COORDINATING WITH OWNER AND PREPARING M.O.P.
1.
2.
3.
4.
5.
6.
7.
8.
HVAC PIPING NOTES:ALL HEATING WATER SUPPLY AND RETURN BRANCH PIPING TO TERMINALBOXES SHALL BE 3/4" UNLESS NOTED OTHERWISE. ALL PIPING TAKE-OFFSFROM MAINS SHALL BE BOTTOM/TOP TAKE-OFFS WITH SWING JOINTS.
PROVIDE EOMD AT ALL LOW POINTS FOR STEAM SUPPLY PIPING ASREQUIRED WHICH MAY NOT NECESSARILY BE SHOWN.
ALL BRANCH STEAM SUPPLY AND CONDENSATE RETURN PIPING FROMMAINS SHALL BE TOP TAKE-OFFS WHICH SWING JOINTS.
1.
2.
3.
FLAG NOTES:
1"CWS/R TO LAB FAN COIL UNIT.
1"PCWS/R TO LAB PROCESS CHILLED WATER EQUIPMENT.
1
2
23
45
67
ACFH BG
LAB A
X1B10
LAB A
X1B20
LAB A
X1B30
LAB A
X1B40
LAB A
X1B11
LAB A
X1B21
LAB A
X1B31
LAB A
X1B41
LAB A
X1B51
M/E
CRX1B30
M/E
CRX1B05
STAIR
STX1B90
D B.1
86.1
5.5
2.5
1
COLLABORATION
X1B52
RAMP
CRX1B01
ELEVATOR
ELX1B90WOMEN
RRWX1B67
MEN
RRMX1B57
JANITOR
X1B77
LAB A
X1B50
E
CIRCULATION
CRX1B25
PUMP ROOM
X1B87
STAIR
STX1B25
LOBBY
CRX1B90
STAIR
STX1B01
RESEARCH LAB
S1B05
RESEARCH LAB
S1B20
RESEARCH LAB
CRS1B79
CIRCULATION
CRS1B84
STUDENT OFFICE
CRS1B81
6.5
LAB MECH.
X1B01
RECYCLING
X1B02
3"CWS/R UP
3" PROCESS CWS/R(PCWS/R) UP
3"PCWS/R UP(65 GPM)
3"CWS/R UP(65 GPM)
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1 1/4"HWS/R
1 1/4"HWS/R
1 1/4"HWS/R
3"HWS/R UP/DN
PROCESS COOLING WATERTANK, HEAT EXCHANGER,AND PUMP
E
D
C
B
A
1 2 3 4 5 6
E
D
C
B
A
1 2 3 4 5 6
SCALE
PROJECT NUMBER
KEY PLAN
X
CD
F
E G
A
S
B
NORTH
IF THIS SHEET IS NOT 30" X 42", IT IS A REDUCEDSIZE PLOT. USE GRAPHIC SCALE ACCORDINGLY.
NOT FOR CONSTRUCTION
PRELIMINARY
JILAUNIVERSITY OF COLORADO440 UCBBOULDER, CO 80309−0440
JILA ADDITION
CATOR RUMA & ASSOCIATES, CO.896 TABOR STREETLAKEWOOD, CO 80401P: 303.232.6200F: 303.233.3701
MARTIN / MARTIN CONSULTING ENGINEERS12499 WEST COLFAX AVENUEPO BOX 151500LAKEWOOD, CO 80215P: 303.431.6100F: 303.431.6866
M−E ENGINEERS, INC.10055 W. 43RD AVENUEWHEAT RIDGE, CO 80033P: 303.421.6655F: 303.421.0331
HDR ARCHITECTURE, INC.303 EAST 17TH AVENUE, SUITE 1000DENVER, CO 80203P: 303.764.1520F: 303.860.7139
ARCHITECT:
MECHANICAL / ELECTRICAL ENGINEER:
STRUCTURAL / CIVIL ENGINEER:
TELECOMMUNICATIONS ENGINEER:
BELT COLLINS WEST, LTD.4909 PEARL EAST CIRCLE, SUITE 300BOULDER, CO 80301P: 303.442.4588F: 303.786.8026
LANDSCAPE ARCHITECT:
CU PROJECT NO. PR 002650
UNIVERSITY OF COLORADOAT BOULDEROFFICE OF FACILITIES PLANNINGRL−2, THIRD FLOOR, ROOM 301BOULDER, CO 80309P: 303.492.1275F: 303.492.4082
OWNER:
GALLUN SNOW1920 MARKET STREET, SUITE 201DENVER, CO 80202P: 303.433.9500F: 303.433.5624
INTERIOR ARCHITECT:
303 EAST 17TH AVENUE SUITE 1000 DENVER, COLORADO 80203 303.764.1520
HDR ARCHITECTURE, INC.
SCHEMATIC DESIGN04/30/2009
01/19/2010 DESIGN DEVELOPMENT TECHNICAL REVIEW
C:\Revit Local Projects\2010\2008-124 JILA Addition\llange_MECH-2008-124 CU JILA.rvt
1/15/2010 8:52:03 AM
As indicated
MP-10B
282-89589
BASEMENT HVACPIPING PLAN
DESIGN DEVELOPMENT TECHNICAL REVIEW
SCALE: 1/8" = 1'-0"
BASEMENT HVAC PIPING PLAN
MARK DATE DESCRIPTION
MAINT.
ACCESS
MAINT.ACCESS
MAINT.ACCESS
MAINT.
ACCESS
MAINT.
ACCESS
MAINT.ACCESS
MAINT.ACCESS
MAINT.
ACCESS
MAINT.
ACCESS
MAINT.ACCESS
MAINT.ACCESS
MAINT.ACCESS
DN
DN
UP
DN
UP
DN
GENERAL NOTES:WORK INCLUDED IN THE CONTRACT IS DENOTED IN BOLD. EXISTING CONDITIONS TOREMAIN ARE DENOTED LIGHTLY.
A DETAILED METHOD OF PROCEDURE IS REQUIRED WHEN A CONSTRUCTIONACTIVITY AFFECTS THE SAFETY OF THE OCCUPANTS, TELEPHONE EQUIPMENT ORVALUABLE CONTENTS OR ANY SYSTEM WHICH SUPPORTS THESE SYSTEMS; ORESSENTIALLY AFFECTS THE BUILDING MANAGEMENT, OPERATIONS OR SECURITY.
CONTRACTOR IS RESPONSIBLE FOR FIELD VERIFICATION OF ALL EXISTINGCONDITIONS PRIOR TO COMMENCEMENT OF ANY WORK AND SHALL NOTIFY THEENGINEER/ARCHITECT OF ANY DISCREPANCIES FOR RESOLUTION.
COORDINATE WORK WITH ALL TRADES.
CONTRACTOR IS RESPONSIBLE FOR SECURING AND WEATHERPROOFING ANYROOF OPENING NOT COMPLETED DURING WORKING HOURS.
COORDINATE ALL DUCTWORK AND PIPING WITH EQUIPMENT, STRUCTURE, ETC.
CONTRACTOR SHALL BE RESPONSIBLE FOR DEACTIVATION OF ROOF-MOUNTEDEQUIPMENT AND ASSOCIATED INDOOR EQUIPMENT. ONLY ONE UNIT SHALL BETAKEN OUT OF SERVICE AT ANY TIME, WITH REMAINDER OF UNITS LEFTOPERATIONAL. COORDINATE WITH GENERAL CONTRACTOR AND ELECTRICALCONTRACTOR.
CONTRACTOR SHALL NOT SHUT DOWN / TAKE OUT OF SERVICE ANY SYSTEMSWITHOUT FIRST COORDINATING WITH OWNER AND PREPARING M.O.P.
1.
2.
3.
4.
5.
6.
7.
8.
HVAC PIPING NOTES:ALL HEATING WATER SUPPLY AND RETURN BRANCH PIPING TO TERMINALBOXES SHALL BE 3/4" UNLESS NOTED OTHERWISE. ALL PIPING TAKE-OFFSFROM MAINS SHALL BE BOTTOM/TOP TAKE-OFFS WITH SWING JOINTS.
PROVIDE EOMD AT ALL LOW POINTS FOR STEAM SUPPLY PIPING ASREQUIRED WHICH MAY NOT NECESSARILY BE SHOWN.
ALL BRANCH STEAM SUPPLY AND CONDENSATE RETURN PIPING FROMMAINS SHALL BE TOP TAKE-OFFS WHICH SWING JOINTS.
1.
2.
3.
FLAG NOTES:
1"CWS/R TO LAB FAN COIL UNIT.
1"PCWS/R TO LAB PROCESS CHILLED WATER EQUIPMENT.
1
1
23
45
67
ACFH BG
M/E
CRX130
M/E
X115
UNISEX
RRWX100
B LAB
X110
B LAB
X120
B LAB
X130
B LAB
X140
D
SHAFT 2SHAFT 1
CIRCULATION
CRX125
B.1
86.1
5.5
KECK LAB
X145
LAB MGR
X145A
2.5
1
STAIR
STX101
E
COLLABORATION
X152
STAIR
STX125
RAMP
CRX101
E-BEAM
X131A
LITHOGRAPHY CL
X121D
LITHOGRAPHY
CHASE
X121C
MAIN AISLE CL
X121A
FABRICATION CL
X121B
WIPE DOWN CL
X121
GOWN CL
X131
CIRCULATION
CRX190
CONFERENCE
ROOM
S105
LIBRARY STACKS
S120
STUDY ROOM
S124
OFFICE
S115
CIRCULATION
S102
6.5
ELEVATOR
ELX190
STAIR
STX190
3" PCWS/R DN(PROCESS EQUIP.
LOOP - 65 GPM)
2
1
2
1
2
1
2
1
2
1
3"CWS/R DN TOPROCESS COOLING HX,
TANK AND PUMP
3"PCWS/R DN TOPROCESS COOLING HX,
TANK AND PUMP3"CWS/R UP(100 GPM)
CWR
CWS
HPC
HPS
HP STEAMENTRY
6"CWS/R UP(600 GPM)
STEAM PRV140 PSI TO75 PSI STEAM
4"MPS UP
2"LPC UP
3" CWS/R DN(FCU LOOP - 65 GPM)
3" HWS/R UP/DN
1 1/8"HWS/R
3"CWS/R(EQUIP. PROCESS LOOP)
(100 GPM)
3"CWS/R(EQUIP. PROCESS LOOP)
(100 GPM)
E
D
C
B
A
1 2 3 4 5 6
E
D
C
B
A
1 2 3 4 5 6
SCALE
PROJECT NUMBER
KEY PLAN
X
CD
F
E G
A
S
B
NORTH
IF THIS SHEET IS NOT 30" X 42", IT IS A REDUCEDSIZE PLOT. USE GRAPHIC SCALE ACCORDINGLY.
NOT FOR CONSTRUCTION
PRELIMINARY
JILAUNIVERSITY OF COLORADO440 UCBBOULDER, CO 80309−0440
JILA ADDITION
CATOR RUMA & ASSOCIATES, CO.896 TABOR STREETLAKEWOOD, CO 80401P: 303.232.6200F: 303.233.3701
MARTIN / MARTIN CONSULTING ENGINEERS12499 WEST COLFAX AVENUEPO BOX 151500LAKEWOOD, CO 80215P: 303.431.6100F: 303.431.6866
M−E ENGINEERS, INC.10055 W. 43RD AVENUEWHEAT RIDGE, CO 80033P: 303.421.6655F: 303.421.0331
HDR ARCHITECTURE, INC.303 EAST 17TH AVENUE, SUITE 1000DENVER, CO 80203P: 303.764.1520F: 303.860.7139
ARCHITECT:
MECHANICAL / ELECTRICAL ENGINEER:
STRUCTURAL / CIVIL ENGINEER:
TELECOMMUNICATIONS ENGINEER:
BELT COLLINS WEST, LTD.4909 PEARL EAST CIRCLE, SUITE 300BOULDER, CO 80301P: 303.442.4588F: 303.786.8026
LANDSCAPE ARCHITECT:
CU PROJECT NO. PR 002650
UNIVERSITY OF COLORADOAT BOULDEROFFICE OF FACILITIES PLANNINGRL−2, THIRD FLOOR, ROOM 301BOULDER, CO 80309P: 303.492.1275F: 303.492.4082
OWNER:
GALLUN SNOW1920 MARKET STREET, SUITE 201DENVER, CO 80202P: 303.433.9500F: 303.433.5624
INTERIOR ARCHITECT:
303 EAST 17TH AVENUE SUITE 1000 DENVER, COLORADO 80203 303.764.1520
HDR ARCHITECTURE, INC.
SCHEMATIC DESIGN04/30/2009
01/19/2010 DESIGN DEVELOPMENT TECHNICAL REVIEW
C:\Revit Local Projects\2010\2008-124 JILA Addition\llange_MECH-2008-124 CU JILA.rvt
1/15/2010 8:52:28 AM
As indicated
MP-101
282-89589
1ST FLOOR HVACPIPING PLAN
DESIGN DEVELOPMENT TECHNICAL REVIEW
SCALE: 1/8" = 1'-0"
1ST FLOORHVAC PIPING PLAN
MARK DATE DESCRIPTION
MAINT.
ACCESS
MAINT.ACCESS
MAINT.ACCESS
MAINT.ACCESS
MAINT.ACCESS
MAINT.ACCESS
MAINT.ACCESS
MAINT.ACCESS
MAINT.ACCESS
MAINT.ACCESS
MAINT.ACCESS
MAINT.
ACCESSMAINT.
ACCESS
MAINT.
ACCESS
DN
DN
UP
DN
UP
DN
GENERAL NOTES:WORK INCLUDED IN THE CONTRACT IS DENOTED IN BOLD. EXISTING CONDITIONS TOREMAIN ARE DENOTED LIGHTLY.
A DETAILED METHOD OF PROCEDURE IS REQUIRED WHEN A CONSTRUCTIONACTIVITY AFFECTS THE SAFETY OF THE OCCUPANTS, TELEPHONE EQUIPMENT ORVALUABLE CONTENTS OR ANY SYSTEM WHICH SUPPORTS THESE SYSTEMS; ORESSENTIALLY AFFECTS THE BUILDING MANAGEMENT, OPERATIONS OR SECURITY.
CONTRACTOR IS RESPONSIBLE FOR FIELD VERIFICATION OF ALL EXISTINGCONDITIONS PRIOR TO COMMENCEMENT OF ANY WORK AND SHALL NOTIFY THEENGINEER/ARCHITECT OF ANY DISCREPANCIES FOR RESOLUTION.
COORDINATE WORK WITH ALL TRADES.
CONTRACTOR IS RESPONSIBLE FOR SECURING AND WEATHERPROOFING ANYROOF OPENING NOT COMPLETED DURING WORKING HOURS.
COORDINATE ALL DUCTWORK AND PIPING WITH EQUIPMENT, STRUCTURE, ETC.
CONTRACTOR SHALL BE RESPONSIBLE FOR DEACTIVATION OF ROOF-MOUNTEDEQUIPMENT AND ASSOCIATED INDOOR EQUIPMENT. ONLY ONE UNIT SHALL BETAKEN OUT OF SERVICE AT ANY TIME, WITH REMAINDER OF UNITS LEFTOPERATIONAL. COORDINATE WITH GENERAL CONTRACTOR AND ELECTRICALCONTRACTOR.
CONTRACTOR SHALL NOT SHUT DOWN / TAKE OUT OF SERVICE ANY SYSTEMSWITHOUT FIRST COORDINATING WITH OWNER AND PREPARING M.O.P.
1.
2.
3.
4.
5.
6.
7.
8.
HVAC PIPING NOTES:ALL HEATING WATER SUPPLY AND RETURN BRANCH PIPING TO TERMINALBOXES SHALL BE 3/4" UNLESS NOTED OTHERWISE. ALL PIPING TAKE-OFFSFROM MAINS SHALL BE BOTTOM/TOP TAKE-OFFS WITH SWING JOINTS.
PROVIDE EOMD AT ALL LOW POINTS FOR STEAM SUPPLY PIPING ASREQUIRED WHICH MAY NOT NECESSARILY BE SHOWN.
ALL BRANCH STEAM SUPPLY AND CONDENSATE RETURN PIPING FROMMAINS SHALL BE TOP TAKE-OFFS WHICH SWING JOINTS.
1.
2.
3.
FLAG NOTES:
NOT USED.
NOT USED.
ROUTE HWS/R TO FCU'S, CONVECTORS, ETC. ON THIS LEVEL.
1
2
3
23
45
67
ACFH BG
GRADUATE
OFFICE
X220
ELECT.
X201
MECH
X231
JANITOR
X200
D
SHAFT 1SHAFT 2
TELECOM MAIN
X210
B.1
86.1
5.5
STAIR
STX290
ELECT.
ENTRANCE
X231A
2.5
1
LOWER TERRACE
X245
ELEVATOR
LOBBY
CRX290
E
STORAGE
X240A
CIRCULATION
CRX205
RECYCLE
X205
ELEVATOR
ELX290
STAIR
STX225
CIRCULATION
CRX225
COLLABORATION
X222
COLLABORATION
X242
COLLABORATION
X241
COLLABORATION
X232
CIRCULATION
CRX245
CIRCULATION
CRX240
STAFF OFFICE
S211
STAFF OFFICE
S209 STUDENT OFFICE
S205
STAFF OFFICE
S220
STAFF OFFICE
S222 FACULTY OFFICE
S224
CIRCULATION
CRS200
6.5
ENTRY
CRX295
STORAGE
X215
JANITOR
X255
2"LPC UP/DN
4"MPS UP/DN
1"MPS (75 PSI) TO MAU-1
3/4"LPC TO MAU-1
6"CWS/R DN
4"CWS/R(200 GPM)
CWP
1
6"CWS/R UP (300 GPM)3"CWS/R DN (100 GPM)
3"HWS/RUP/DN
1 1/2"HWS/R
2 1/2"HWS/R UP
3
CWP
1
E
D
C
B
A
1 2 3 4 5 6
E
D
C
B
A
1 2 3 4 5 6
SCALE
PROJECT NUMBER
KEY PLAN
X
CD
F
E G
A
S
B
NORTH
IF THIS SHEET IS NOT 30" X 42", IT IS A REDUCEDSIZE PLOT. USE GRAPHIC SCALE ACCORDINGLY.
NOT FOR CONSTRUCTION
PRELIMINARY
JILAUNIVERSITY OF COLORADO440 UCBBOULDER, CO 80309−0440
JILA ADDITION
CATOR RUMA & ASSOCIATES, CO.896 TABOR STREETLAKEWOOD, CO 80401P: 303.232.6200F: 303.233.3701
MARTIN / MARTIN CONSULTING ENGINEERS12499 WEST COLFAX AVENUEPO BOX 151500LAKEWOOD, CO 80215P: 303.431.6100F: 303.431.6866
M−E ENGINEERS, INC.10055 W. 43RD AVENUEWHEAT RIDGE, CO 80033P: 303.421.6655F: 303.421.0331
HDR ARCHITECTURE, INC.303 EAST 17TH AVENUE, SUITE 1000DENVER, CO 80203P: 303.764.1520F: 303.860.7139
ARCHITECT:
MECHANICAL / ELECTRICAL ENGINEER:
STRUCTURAL / CIVIL ENGINEER:
TELECOMMUNICATIONS ENGINEER:
BELT COLLINS WEST, LTD.4909 PEARL EAST CIRCLE, SUITE 300BOULDER, CO 80301P: 303.442.4588F: 303.786.8026
LANDSCAPE ARCHITECT:
CU PROJECT NO. PR 002650
UNIVERSITY OF COLORADOAT BOULDEROFFICE OF FACILITIES PLANNINGRL−2, THIRD FLOOR, ROOM 301BOULDER, CO 80309P: 303.492.1275F: 303.492.4082
OWNER:
GALLUN SNOW1920 MARKET STREET, SUITE 201DENVER, CO 80202P: 303.433.9500F: 303.433.5624
INTERIOR ARCHITECT:
303 EAST 17TH AVENUE SUITE 1000 DENVER, COLORADO 80203 303.764.1520
HDR ARCHITECTURE, INC.
SCHEMATIC DESIGN04/30/2009
01/19/2010 DESIGN DEVELOPMENT TECHNICAL REVIEW
C:\Revit Local Projects\2010\2008-124 JILA Addition\llange_MECH-2008-124 CU JILA.rvt
1/15/2010 8:52:54 AM
As indicated
MP-102
282-89589
2nd FLOOR HVACPIPING PLAN
DESIGN DEVELOPMENT TECHNICAL REVIEW
SCALE: 1/8" = 1'-0"
2ND FLOOR HVAC PIPING PLAN
MARK DATE DESCRIPTION
MAINT.ACCESS
MAINT.ACCESS
MAINT.
ACCESS
MAINT.ACCESS
MAINT.ACCESS
MAINT.ACCESS
MAINT.ACCESS
MAINT.ACCESS
MAINT.
ACCESS
UPDN
DN
UP
GENERAL NOTES:WORK INCLUDED IN THE CONTRACT IS DENOTED IN BOLD. EXISTING CONDITIONS TOREMAIN ARE DENOTED LIGHTLY.
A DETAILED METHOD OF PROCEDURE IS REQUIRED WHEN A CONSTRUCTIONACTIVITY AFFECTS THE SAFETY OF THE OCCUPANTS, TELEPHONE EQUIPMENT ORVALUABLE CONTENTS OR ANY SYSTEM WHICH SUPPORTS THESE SYSTEMS; ORESSENTIALLY AFFECTS THE BUILDING MANAGEMENT, OPERATIONS OR SECURITY.
CONTRACTOR IS RESPONSIBLE FOR FIELD VERIFICATION OF ALL EXISTINGCONDITIONS PRIOR TO COMMENCEMENT OF ANY WORK AND SHALL NOTIFY THEENGINEER/ARCHITECT OF ANY DISCREPANCIES FOR RESOLUTION.
COORDINATE WORK WITH ALL TRADES.
CONTRACTOR IS RESPONSIBLE FOR SECURING AND WEATHERPROOFING ANYROOF OPENING NOT COMPLETED DURING WORKING HOURS.
COORDINATE ALL DUCTWORK AND PIPING WITH EQUIPMENT, STRUCTURE, ETC.
CONTRACTOR SHALL BE RESPONSIBLE FOR DEACTIVATION OF ROOF-MOUNTEDEQUIPMENT AND ASSOCIATED INDOOR EQUIPMENT. ONLY ONE UNIT SHALL BETAKEN OUT OF SERVICE AT ANY TIME, WITH REMAINDER OF UNITS LEFTOPERATIONAL. COORDINATE WITH GENERAL CONTRACTOR AND ELECTRICALCONTRACTOR.
CONTRACTOR SHALL NOT SHUT DOWN / TAKE OUT OF SERVICE ANY SYSTEMSWITHOUT FIRST COORDINATING WITH OWNER AND PREPARING M.O.P.
1.
2.
3.
4.
5.
6.
7.
8.
HVAC PIPING NOTES:ALL HEATING WATER SUPPLY AND RETURN BRANCH PIPING TO TERMINALBOXES SHALL BE 3/4" UNLESS NOTED OTHERWISE. ALL PIPING TAKE-OFFSFROM MAINS SHALL BE BOTTOM/TOP TAKE-OFFS WITH SWING JOINTS.
PROVIDE EOMD AT ALL LOW POINTS FOR STEAM SUPPLY PIPING ASREQUIRED WHICH MAY NOT NECESSARILY BE SHOWN.
ALL BRANCH STEAM SUPPLY AND CONDENSATE RETURN PIPING FROMMAINS SHALL BE TOP TAKE-OFFS WHICH SWING JOINTS.
1.
2.
3.
FLAG NOTES:
NOT USED
NOT USED.
ROUTE HWS/R TO FCU'S, CONVECTORS, ETC. ON THIS LEVEL.
1
2
3
23
45
67
ACFH BG
STAIR
STX390
ELEC.
X301
JANITOR
X300
D
SHAFT 1 SHAFT 2
B.1
86.1
5.5
UPPER TERRACE
X335
2.5
1
CONFERENCE
X390
GRADUATE
OFFICE
X324
COPIER
X320
CONFERENCE
X340
FELLOWS OFFICE
X350
MEN
X310B
WOMEN
X310A
E
LARGE
CONFERENCE
X315
MEDIUM
CONFERENCE
X325
CIRCULATION
CRX325
STAIR
STX325
COLLABORATION
X355
ELEVATOR
ELX390
STUDENT OFFICE
S315 STUDENT OFFICE
S305
CIRCULATION
CRS300
FACULTY OFFICE
S320
FACULTY OFFICE
S324
CIRCULATION
S350
6.5
CIRCULATION
CRX390
FELLOWS OFFICE
X360
STORAGE
X375
6"CWS/R UP/DN
4"MPS UP/DN2"LPC UP/DN
3"HWS/RUP/DN
1 1/2"HWS/R
2 1/2"HWS/R UP/DN
3
E
D
C
B
A
1 2 3 4 5 6
E
D
C
B
A
1 2 3 4 5 6
SCALE
PROJECT NUMBER
KEY PLAN
X
CD
F
E G
A
S
B
NORTH
IF THIS SHEET IS NOT 30" X 42", IT IS A REDUCEDSIZE PLOT. USE GRAPHIC SCALE ACCORDINGLY.
NOT FOR CONSTRUCTION
PRELIMINARY
JILAUNIVERSITY OF COLORADO440 UCBBOULDER, CO 80309−0440
JILA ADDITION
CATOR RUMA & ASSOCIATES, CO.896 TABOR STREETLAKEWOOD, CO 80401P: 303.232.6200F: 303.233.3701
MARTIN / MARTIN CONSULTING ENGINEERS12499 WEST COLFAX AVENUEPO BOX 151500LAKEWOOD, CO 80215P: 303.431.6100F: 303.431.6866
M−E ENGINEERS, INC.10055 W. 43RD AVENUEWHEAT RIDGE, CO 80033P: 303.421.6655F: 303.421.0331
HDR ARCHITECTURE, INC.303 EAST 17TH AVENUE, SUITE 1000DENVER, CO 80203P: 303.764.1520F: 303.860.7139
ARCHITECT:
MECHANICAL / ELECTRICAL ENGINEER:
STRUCTURAL / CIVIL ENGINEER:
TELECOMMUNICATIONS ENGINEER:
BELT COLLINS WEST, LTD.4909 PEARL EAST CIRCLE, SUITE 300BOULDER, CO 80301P: 303.442.4588F: 303.786.8026
LANDSCAPE ARCHITECT:
CU PROJECT NO. PR 002650
UNIVERSITY OF COLORADOAT BOULDEROFFICE OF FACILITIES PLANNINGRL−2, THIRD FLOOR, ROOM 301BOULDER, CO 80309P: 303.492.1275F: 303.492.4082
OWNER:
GALLUN SNOW1920 MARKET STREET, SUITE 201DENVER, CO 80202P: 303.433.9500F: 303.433.5624
INTERIOR ARCHITECT:
303 EAST 17TH AVENUE SUITE 1000 DENVER, COLORADO 80203 303.764.1520
HDR ARCHITECTURE, INC.
SCHEMATIC DESIGN04/30/2009
01/19/2010 DESIGN DEVELOPMENT TECHNICAL REVIEW
C:\Revit Local Projects\2010\2008-124 JILA Addition\llange_MECH-2008-124 CU JILA.rvt
1/15/2010 8:54:08 AM
As indicated
MP-103
282-89589
3rd FLOOR HVACPIPING PLAN
DESIGN DEVELOPMENT TECHNICAL REVIEW
SCALE: 1/8" = 1'-0"
3RD FLOOR HVAC PIPING PLAN
MARK DATE DESCRIPTION
MAINT.ACCESS
MAINT.ACCESS
MAINT.ACCESS
MAINT.ACCESS
MAINT.ACCESS
MAINT.ACCESSMAINT.ACCESS
MAINT.ACCESS
MAINT.ACCESS
MAINT.ACCESS
MAINT.ACCESS
MAINT.
ACCESS
UPDN
DN
UP
DN
GENERAL NOTES:WORK INCLUDED IN THE CONTRACT IS DENOTED IN BOLD. EXISTING CONDITIONS TOREMAIN ARE DENOTED LIGHTLY.
A DETAILED METHOD OF PROCEDURE IS REQUIRED WHEN A CONSTRUCTIONACTIVITY AFFECTS THE SAFETY OF THE OCCUPANTS, TELEPHONE EQUIPMENT ORVALUABLE CONTENTS OR ANY SYSTEM WHICH SUPPORTS THESE SYSTEMS; ORESSENTIALLY AFFECTS THE BUILDING MANAGEMENT, OPERATIONS OR SECURITY.
CONTRACTOR IS RESPONSIBLE FOR FIELD VERIFICATION OF ALL EXISTINGCONDITIONS PRIOR TO COMMENCEMENT OF ANY WORK AND SHALL NOTIFY THEENGINEER/ARCHITECT OF ANY DISCREPANCIES FOR RESOLUTION.
COORDINATE WORK WITH ALL TRADES.
CONTRACTOR IS RESPONSIBLE FOR SECURING AND WEATHERPROOFING ANYROOF OPENING NOT COMPLETED DURING WORKING HOURS.
COORDINATE ALL DUCTWORK AND PIPING WITH EQUIPMENT, STRUCTURE, ETC.
CONTRACTOR SHALL BE RESPONSIBLE FOR DEACTIVATION OF ROOF-MOUNTEDEQUIPMENT AND ASSOCIATED INDOOR EQUIPMENT. ONLY ONE UNIT SHALL BETAKEN OUT OF SERVICE AT ANY TIME, WITH REMAINDER OF UNITS LEFTOPERATIONAL. COORDINATE WITH GENERAL CONTRACTOR AND ELECTRICALCONTRACTOR.
CONTRACTOR SHALL NOT SHUT DOWN / TAKE OUT OF SERVICE ANY SYSTEMSWITHOUT FIRST COORDINATING WITH OWNER AND PREPARING M.O.P.
1.
2.
3.
4.
5.
6.
7.
8.
HVAC PIPING NOTES:ALL HEATING WATER SUPPLY AND RETURN BRANCH PIPING TO TERMINALBOXES SHALL BE 3/4" UNLESS NOTED OTHERWISE. ALL PIPING TAKE-OFFSFROM MAINS SHALL BE BOTTOM/TOP TAKE-OFFS WITH SWING JOINTS.
PROVIDE EOMD AT ALL LOW POINTS FOR STEAM SUPPLY PIPING ASREQUIRED WHICH MAY NOT NECESSARILY BE SHOWN.
ALL BRANCH STEAM SUPPLY AND CONDENSATE RETURN PIPING FROMMAINS SHALL BE TOP TAKE-OFFS WHICH SWING JOINTS.
1.
2.
3.
FLAG NOTES:
NOT USED.
NOT USED.
ROUTE HWS/R TO FCU'S, CONVECTORS, ETS. ON THIS LEVEL.
1
2
3
23
45
67
ACFH BG
STAIR
STX490
JANITOR
X414
D
CONFERENCE
X490
SHAFT 1 SHAFT 2
B.1
86.1
5.5
ELEC.
X405
2.5
1
E
CONFERENCE
X440
FELLOWS OFFICE
X460
POST DOC
OFFICE
X445
FELLOW OFFICE
X435
FELLOW OFFICE
X425
GRADUATE
OFFICES
X415
WOMEN
X410
MEN
X420
TELECOM
X424
ADMINSTRATIVE
OFFICE
X429
STAIR
STX425
COLLABORATION
X421
STORAGE
X409
COLLABORATION
X441
GRADUATE
OFFICE
X428
STAIR
STX400
ELEVATOR
ELX490
CIRCULATION
CRX425
TELECOM
S420
MECHANICAL
S410
MECHANICAL
S405CIRCULATON
CRS410
6.5
CIRCULATION
CRX490
FELLOWS OFFICE
X450
POST DOC
OFFICE
X455
STORAGE
X465
6"CWS/R UP/DN
4"MPS UP/DN2"LPC UP/DN
3"HWS/RUP/DN
1 1/2"HWS/R
2 1/2"HWS/RUP/DN
3
E
D
C
B
A
1 2 3 4 5 6
E
D
C
B
A
1 2 3 4 5 6
SCALE
PROJECT NUMBER
KEY PLAN
X
CD
F
E G
A
S
B
NORTH
IF THIS SHEET IS NOT 30" X 42", IT IS A REDUCEDSIZE PLOT. USE GRAPHIC SCALE ACCORDINGLY.
NOT FOR CONSTRUCTION
PRELIMINARY
JILAUNIVERSITY OF COLORADO440 UCBBOULDER, CO 80309−0440
JILA ADDITION
CATOR RUMA & ASSOCIATES, CO.896 TABOR STREETLAKEWOOD, CO 80401P: 303.232.6200F: 303.233.3701
MARTIN / MARTIN CONSULTING ENGINEERS12499 WEST COLFAX AVENUEPO BOX 151500LAKEWOOD, CO 80215P: 303.431.6100F: 303.431.6866
M−E ENGINEERS, INC.10055 W. 43RD AVENUEWHEAT RIDGE, CO 80033P: 303.421.6655F: 303.421.0331
HDR ARCHITECTURE, INC.303 EAST 17TH AVENUE, SUITE 1000DENVER, CO 80203P: 303.764.1520F: 303.860.7139
ARCHITECT:
MECHANICAL / ELECTRICAL ENGINEER:
STRUCTURAL / CIVIL ENGINEER:
TELECOMMUNICATIONS ENGINEER:
BELT COLLINS WEST, LTD.4909 PEARL EAST CIRCLE, SUITE 300BOULDER, CO 80301P: 303.442.4588F: 303.786.8026
LANDSCAPE ARCHITECT:
CU PROJECT NO. PR 002650
UNIVERSITY OF COLORADOAT BOULDEROFFICE OF FACILITIES PLANNINGRL−2, THIRD FLOOR, ROOM 301BOULDER, CO 80309P: 303.492.1275F: 303.492.4082
OWNER:
GALLUN SNOW1920 MARKET STREET, SUITE 201DENVER, CO 80202P: 303.433.9500F: 303.433.5624
INTERIOR ARCHITECT:
303 EAST 17TH AVENUE SUITE 1000 DENVER, COLORADO 80203 303.764.1520
HDR ARCHITECTURE, INC.
SCHEMATIC DESIGN04/30/2009
01/19/2010 DESIGN DEVELOPMENT TECHNICAL REVIEW
C:\Revit Local Projects\2010\2008-124 JILA Addition\llange_MECH-2008-124 CU JILA.rvt
1/15/2010 8:54:36 AM
As indicated
MP-104
282-89589
4th FLOOR HVACPIPING PLAN
DESIGN DEVELOPMENT TECHNICAL REVIEW
SCALE: 1/8" = 1'-0"
4TH FLOOR HVAC PIPING PLAN
MARK DATE DESCRIPTION
MAINT.
ACCESS
MAINT.
ACCESS
MAINT.
ACCESS
UPDN
UP
DNUP
GENERAL NOTES:WORK INCLUDED IN THE CONTRACT IS DENOTED IN BOLD. EXISTING CONDITIONS TOREMAIN ARE DENOTED LIGHTLY.
A DETAILED METHOD OF PROCEDURE IS REQUIRED WHEN A CONSTRUCTIONACTIVITY AFFECTS THE SAFETY OF THE OCCUPANTS, TELEPHONE EQUIPMENT ORVALUABLE CONTENTS OR ANY SYSTEM WHICH SUPPORTS THESE SYSTEMS; ORESSENTIALLY AFFECTS THE BUILDING MANAGEMENT, OPERATIONS OR SECURITY.
CONTRACTOR IS RESPONSIBLE FOR FIELD VERIFICATION OF ALL EXISTINGCONDITIONS PRIOR TO COMMENCEMENT OF ANY WORK AND SHALL NOTIFY THEENGINEER/ARCHITECT OF ANY DISCREPANCIES FOR RESOLUTION.
COORDINATE WORK WITH ALL TRADES.
CONTRACTOR IS RESPONSIBLE FOR SECURING AND WEATHERPROOFING ANYROOF OPENING NOT COMPLETED DURING WORKING HOURS.
COORDINATE ALL DUCTWORK AND PIPING WITH EQUIPMENT, STRUCTURE, ETC.
CONTRACTOR SHALL BE RESPONSIBLE FOR DEACTIVATION OF ROOF-MOUNTEDEQUIPMENT AND ASSOCIATED INDOOR EQUIPMENT. ONLY ONE UNIT SHALL BETAKEN OUT OF SERVICE AT ANY TIME, WITH REMAINDER OF UNITS LEFTOPERATIONAL. COORDINATE WITH GENERAL CONTRACTOR AND ELECTRICALCONTRACTOR.
CONTRACTOR SHALL NOT SHUT DOWN / TAKE OUT OF SERVICE ANY SYSTEMSWITHOUT FIRST COORDINATING WITH OWNER AND PREPARING M.O.P.
1.
2.
3.
4.
5.
6.
7.
8.
HVAC PIPING NOTES:ALL HEATING WATER SUPPLY AND RETURN BRANCH PIPING TO TERMINALBOXES SHALL BE 3/4" UNLESS NOTED OTHERWISE. ALL PIPING TAKE-OFFSFROM MAINS SHALL BE BOTTOM/TOP TAKE-OFFS WITH SWING JOINTS.
PROVIDE EOMD AT ALL LOW POINTS FOR STEAM SUPPLY PIPING ASREQUIRED WHICH MAY NOT NECESSARILY BE SHOWN.
ALL BRANCH STEAM SUPPLY AND CONDENSATE RETURN PIPING FROMMAINS SHALL BE TOP TAKE-OFFS WHICH SWING JOINTS.
1.
2.
3.
FLAG NOTES:
XXX1
23
45
67
ACFH BG
MECHANICAL
X525
D
STAIR
STX500
SHAFT 1 SHAFT 2
B.1
86.1
5.5
2.5
1
CONFERENCE
X590
STAIR
STX590
WOMEN
RRWX542
MEN
RRMX544
SHAFT 4
SHAFT 3
E
CORRIDOR
CRX555
STAIR
STX550
ELEVATOR
ELX590
6.5
VESTIBULE
CRX590
6"CWS/R DN
4"MPS DN2"LPC DN
3"HWS/R DN
3"HWS/R
1 1/2"HWS/R
2 1/2"HWS/R DN
HX
2A
HX
2B
TO AHU-1
STACKEDSTACKED
TO AHU-1
2 1/2"HWS/R
4"MPS
2"LPC
4"HWS/R
HX
1B
HX
1A
E
D
C
B
A
1 2 3 4 5 6
E
D
C
B
A
1 2 3 4 5 6
SCALE
PROJECT NUMBER
KEY PLAN
X
CD
F
E G
A
S
B
NORTH
IF THIS SHEET IS NOT 30" X 42", IT IS A REDUCEDSIZE PLOT. USE GRAPHIC SCALE ACCORDINGLY.
NOT FOR CONSTRUCTION
PRELIMINARY
JILAUNIVERSITY OF COLORADO440 UCBBOULDER, CO 80309−0440
JILA ADDITION
CATOR RUMA & ASSOCIATES, CO.896 TABOR STREETLAKEWOOD, CO 80401P: 303.232.6200F: 303.233.3701
MARTIN / MARTIN CONSULTING ENGINEERS12499 WEST COLFAX AVENUEPO BOX 151500LAKEWOOD, CO 80215P: 303.431.6100F: 303.431.6866
M−E ENGINEERS, INC.10055 W. 43RD AVENUEWHEAT RIDGE, CO 80033P: 303.421.6655F: 303.421.0331
HDR ARCHITECTURE, INC.303 EAST 17TH AVENUE, SUITE 1000DENVER, CO 80203P: 303.764.1520F: 303.860.7139
ARCHITECT:
MECHANICAL / ELECTRICAL ENGINEER:
STRUCTURAL / CIVIL ENGINEER:
TELECOMMUNICATIONS ENGINEER:
BELT COLLINS WEST, LTD.4909 PEARL EAST CIRCLE, SUITE 300BOULDER, CO 80301P: 303.442.4588F: 303.786.8026
LANDSCAPE ARCHITECT:
CU PROJECT NO. PR 002650
UNIVERSITY OF COLORADOAT BOULDEROFFICE OF FACILITIES PLANNINGRL−2, THIRD FLOOR, ROOM 301BOULDER, CO 80309P: 303.492.1275F: 303.492.4082
OWNER:
GALLUN SNOW1920 MARKET STREET, SUITE 201DENVER, CO 80202P: 303.433.9500F: 303.433.5624
INTERIOR ARCHITECT:
303 EAST 17TH AVENUE SUITE 1000 DENVER, COLORADO 80203 303.764.1520
HDR ARCHITECTURE, INC.
SCHEMATIC DESIGN04/30/2009
01/19/2010 DESIGN DEVELOPMENT TECHNICAL REVIEW
C:\Revit Local Projects\2010\2008-124 JILA Addition\llange_MECH-2008-124 CU JILA.rvt
1/15/2010 8:54:58 AM
As indicated
MP-105
282-89589
5th FLOOR HVACPIPING PLAN
DESIGN DEVELOPMENT TECHNICAL REVIEW
SCALE: 1/8" = 1'-0"
5TH FLOOR HVAC PIPING PLAN
MARK DATE DESCRIPTION
DN
DN
DN
GENERAL NOTES:WORK INCLUDED IN THE CONTRACT IS DENOTED IN BOLD. EXISTING CONDITIONS TOREMAIN ARE DENOTED LIGHTLY.
A DETAILED METHOD OF PROCEDURE IS REQUIRED WHEN A CONSTRUCTIONACTIVITY AFFECTS THE SAFETY OF THE OCCUPANTS, TELEPHONE EQUIPMENT ORVALUABLE CONTENTS OR ANY SYSTEM WHICH SUPPORTS THESE SYSTEMS; ORESSENTIALLY AFFECTS THE BUILDING MANAGEMENT, OPERATIONS OR SECURITY.
CONTRACTOR IS RESPONSIBLE FOR FIELD VERIFICATION OF ALL EXISTINGCONDITIONS PRIOR TO COMMENCEMENT OF ANY WORK AND SHALL NOTIFY THEENGINEER/ARCHITECT OF ANY DISCREPANCIES FOR RESOLUTION.
COORDINATE WORK WITH ALL TRADES.
CONTRACTOR IS RESPONSIBLE FOR SECURING AND WEATHERPROOFING ANYROOF OPENING NOT COMPLETED DURING WORKING HOURS.
COORDINATE ALL DUCTWORK AND PIPING WITH EQUIPMENT, STRUCTURE, ETC.
CONTRACTOR SHALL BE RESPONSIBLE FOR DEACTIVATION OF ROOF-MOUNTEDEQUIPMENT AND ASSOCIATED INDOOR EQUIPMENT. ONLY ONE UNIT SHALL BETAKEN OUT OF SERVICE AT ANY TIME, WITH REMAINDER OF UNITS LEFTOPERATIONAL. COORDINATE WITH GENERAL CONTRACTOR AND ELECTRICALCONTRACTOR.
CONTRACTOR SHALL NOT SHUT DOWN / TAKE OUT OF SERVICE ANY SYSTEMSWITHOUT FIRST COORDINATING WITH OWNER AND PREPARING M.O.P.
1.
2.
3.
4.
5.
6.
7.
8.
HVAC PIPING NOTES:ALL HEATING WATER SUPPLY AND RETURN BRANCH PIPING TO TERMINALBOXES SHALL BE 3/4" UNLESS NOTED OTHERWISE. ALL PIPING TAKE-OFFSFROM MAINS SHALL BE BOTTOM/TOP TAKE-OFFS WITH SWING JOINTS.
PROVIDE EOMD AT ALL LOW POINTS FOR STEAM SUPPLY PIPING ASREQUIRED WHICH MAY NOT NECESSARILY BE SHOWN.
ALL BRANCH STEAM SUPPLY AND CONDENSATE RETURN PIPING FROMMAINS SHALL BE TOP TAKE-OFFS WHICH SWING JOINTS.
1.
2.
3.
FLAG NOTES:
XXX1
23
45
67
ACFH BG
D
B.1
86.1
5.5
2.5
1
E
6.5
E
D
C
B
A
1 2 3 4 5 6
E
D
C
B
A
1 2 3 4 5 6
SCALE
PROJECT NUMBER
KEY PLAN
X
CD
F
E G
A
S
B
NORTH
IF THIS SHEET IS NOT 30" X 42", IT IS A REDUCEDSIZE PLOT. USE GRAPHIC SCALE ACCORDINGLY.
NOT FOR CONSTRUCTION
PRELIMINARY
JILAUNIVERSITY OF COLORADO440 UCBBOULDER, CO 80309−0440
JILA ADDITION
CATOR RUMA & ASSOCIATES, CO.896 TABOR STREETLAKEWOOD, CO 80401P: 303.232.6200F: 303.233.3701
MARTIN / MARTIN CONSULTING ENGINEERS12499 WEST COLFAX AVENUEPO BOX 151500LAKEWOOD, CO 80215P: 303.431.6100F: 303.431.6866
M−E ENGINEERS, INC.10055 W. 43RD AVENUEWHEAT RIDGE, CO 80033P: 303.421.6655F: 303.421.0331
HDR ARCHITECTURE, INC.303 EAST 17TH AVENUE, SUITE 1000DENVER, CO 80203P: 303.764.1520F: 303.860.7139
ARCHITECT:
MECHANICAL / ELECTRICAL ENGINEER:
STRUCTURAL / CIVIL ENGINEER:
TELECOMMUNICATIONS ENGINEER:
BELT COLLINS WEST, LTD.4909 PEARL EAST CIRCLE, SUITE 300BOULDER, CO 80301P: 303.442.4588F: 303.786.8026
LANDSCAPE ARCHITECT:
CU PROJECT NO. PR 002650
UNIVERSITY OF COLORADOAT BOULDEROFFICE OF FACILITIES PLANNINGRL−2, THIRD FLOOR, ROOM 301BOULDER, CO 80309P: 303.492.1275F: 303.492.4082
OWNER:
GALLUN SNOW1920 MARKET STREET, SUITE 201DENVER, CO 80202P: 303.433.9500F: 303.433.5624
INTERIOR ARCHITECT:
303 EAST 17TH AVENUE SUITE 1000 DENVER, COLORADO 80203 303.764.1520
HDR ARCHITECTURE, INC.
SCHEMATIC DESIGN04/30/2009
01/19/2010 DESIGN DEVELOPMENT TECHNICAL REVIEW
C:\Revit Local Projects\2010\2008-124 JILA Addition\llange_MECH-2008-124 CU JILA.rvt
1/15/2010 8:55:17 AM
As indicated
MP-106
282-89589
6th FLOOR HVACPIPING PLAN
DESIGN DEVELOPMENT TECHNICAL REVIEW
SCALE: 1/8" = 1'-0"
6TH FLOOR HVAC PIPING PLAN
MARK DATE DESCRIPTION
GENERAL NOTES:WORK INCLUDED IN THE CONTRACT IS DENOTED IN BOLD. EXISTING CONDITIONS TOREMAIN ARE DENOTED LIGHTLY.
A DETAILED METHOD OF PROCEDURE IS REQUIRED WHEN A CONSTRUCTIONACTIVITY AFFECTS THE SAFETY OF THE OCCUPANTS, TELEPHONE EQUIPMENT ORVALUABLE CONTENTS OR ANY SYSTEM WHICH SUPPORTS THESE SYSTEMS; ORESSENTIALLY AFFECTS THE BUILDING MANAGEMENT, OPERATIONS OR SECURITY.
CONTRACTOR IS RESPONSIBLE FOR FIELD VERIFICATION OF ALL EXISTINGCONDITIONS PRIOR TO COMMENCEMENT OF ANY WORK AND SHALL NOTIFY THEENGINEER/ARCHITECT OF ANY DISCREPANCIES FOR RESOLUTION.
COORDINATE WORK WITH ALL TRADES.
CONTRACTOR IS RESPONSIBLE FOR SECURING AND WEATHERPROOFING ANYROOF OPENING NOT COMPLETED DURING WORKING HOURS.
COORDINATE ALL DUCTWORK AND PIPING WITH EQUIPMENT, STRUCTURE, ETC.
CONTRACTOR SHALL BE RESPONSIBLE FOR DEACTIVATION OF ROOF-MOUNTEDEQUIPMENT AND ASSOCIATED INDOOR EQUIPMENT. ONLY ONE UNIT SHALL BETAKEN OUT OF SERVICE AT ANY TIME, WITH REMAINDER OF UNITS LEFTOPERATIONAL. COORDINATE WITH GENERAL CONTRACTOR AND ELECTRICALCONTRACTOR.
CONTRACTOR SHALL NOT SHUT DOWN / TAKE OUT OF SERVICE ANY SYSTEMSWITHOUT FIRST COORDINATING WITH OWNER AND PREPARING M.O.P.
1.
2.
3.
4.
5.
6.
7.
8.
HVAC PIPING NOTES:ALL HEATING WATER SUPPLY AND RETURN BRANCH PIPING TO TERMINALBOXES SHALL BE 3/4" UNLESS NOTED OTHERWISE. ALL PIPING TAKE-OFFSFROM MAINS SHALL BE BOTTOM/TOP TAKE-OFFS WITH SWING JOINTS.
PROVIDE EOMD AT ALL LOW POINTS FOR STEAM SUPPLY PIPING ASREQUIRED WHICH MAY NOT NECESSARILY BE SHOWN.
ALL BRANCH STEAM SUPPLY AND CONDENSATE RETURN PIPING FROMMAINS SHALL BE TOP TAKE-OFFS WHICH SWING JOINTS.
1.
2.
3.
23
45
67
ACFH BG D B.1
86.1
5.5
2.5
1
E
6.5
FLAG NOTES:
XXX1
E
D
C
B
A
1 2 3 4 5 6
E
D
C
B
A
1 2 3 4 5 6
SCALE
PROJECT NUMBER
KEY PLAN
X
CD
F
E G
A
S
B
NORTH
IF THIS SHEET IS NOT 30" X 42", IT IS A REDUCEDSIZE PLOT. USE GRAPHIC SCALE ACCORDINGLY.
NOT FOR CONSTRUCTION
PRELIMINARY
JILAUNIVERSITY OF COLORADO440 UCBBOULDER, CO 80309−0440
JILA ADDITION
CATOR RUMA & ASSOCIATES, CO.896 TABOR STREETLAKEWOOD, CO 80401P: 303.232.6200F: 303.233.3701
MARTIN / MARTIN CONSULTING ENGINEERS12499 WEST COLFAX AVENUEPO BOX 151500LAKEWOOD, CO 80215P: 303.431.6100F: 303.431.6866
M−E ENGINEERS, INC.10055 W. 43RD AVENUEWHEAT RIDGE, CO 80033P: 303.421.6655F: 303.421.0331
HDR ARCHITECTURE, INC.303 EAST 17TH AVENUE, SUITE 1000DENVER, CO 80203P: 303.764.1520F: 303.860.7139
ARCHITECT:
MECHANICAL / ELECTRICAL ENGINEER:
STRUCTURAL / CIVIL ENGINEER:
TELECOMMUNICATIONS ENGINEER:
BELT COLLINS WEST, LTD.4909 PEARL EAST CIRCLE, SUITE 300BOULDER, CO 80301P: 303.442.4588F: 303.786.8026
LANDSCAPE ARCHITECT:
CU PROJECT NO. PR 002650
UNIVERSITY OF COLORADOAT BOULDEROFFICE OF FACILITIES PLANNINGRL−2, THIRD FLOOR, ROOM 301BOULDER, CO 80309P: 303.492.1275F: 303.492.4082
OWNER:
GALLUN SNOW1920 MARKET STREET, SUITE 201DENVER, CO 80202P: 303.433.9500F: 303.433.5624
INTERIOR ARCHITECT:
303 EAST 17TH AVENUE SUITE 1000 DENVER, COLORADO 80203 303.764.1520
HDR ARCHITECTURE, INC.
SCHEMATIC DESIGN04/30/2009
01/19/2010 DESIGN DEVELOPMENT TECHNICAL REVIEW
C:\Revit Local Projects\2010\2008-124 JILA Addition\llange_MECH-2008-124 CU JILA.rvt
1/15/2010 8:55:39 AM
As indicated
MP-107
282-89589
ROOF HVAC PIPINGPLAN
DESIGN DEVELOPMENT TECHNICAL REVIEW
SCALE: 1/8" = 1'-0"
ROOF HVAC PIPING PLAN
MARK DATE DESCRIPTION