overview of the guide for applying harmonic limits on
TRANSCRIPT
Overview of the Guide forApplying Harmonic Limits onPower Systems - IEEE P519A
Mark McGranaghan
Electrotek Concepts, Inc.1998 PATH WorkshopKnoxville, TennesseeOctober, 1998
P519A - 2
Scope of IEEE 519-1992
u Provide methodology for preventing harmonicvoltage and current distortion problems on thepower system through utility and customercooperation.
P519A - 3
Basic Philosophy of IEEE 519
u The customer isresponsible for limitingharmonic currentsinjected onto the powersystem.
u The utility is responsiblefor maintainingquality of voltagewaveform.
P519A - 4
Harmonic Voltage Limits
Harmonic Voltage Limits - Utility Responsibility
Maximum IndividualHarmonic Component (%)
MaximumTHD (%)
Bus Voltage
69 kV and below 3.0% 5.0%115 kV to 161 kV 1.5% 2.5%Above 161 kV 1.0% 1.5%
P519A - 5
Meeting Voltage Distortion Limitsu Limit the harmonic currents from nonlinear
devices on the system (customer harmonic currentlimits).
u Make sure that system resonances do not result inexcessive magnification of the customer harmoniccurrents (utility control of system response).
P519A - 6
Harmonic Current Limits
Harmonic Current Limits - Customer Responsibility
Values shown are in percent of “average maximum demand load current”
SCR = short circuit ratio (utility short circuit current at point of commoncoupling divided by customer average maximum demand load current)
TDD = Total Demand Distortion (uses maximum demand load current as thebase, rather than the fundamental current)
SCR =Isc/IL <11 11<h<17 17<h<23 23<h<35 35<h TDD
4.0 2.0 1.5 0.6 0.3 5.0
7.0 3.5 2.5 1.0 0.5 8.0
10.0 4.5 4.0 1.5 0.7 12.0
12.0 5.5 5.0 2.0 1.0 15.0
<20
20 - 50
50 - 100
100 - 1000
>1000 15.0 7.0 6.0 2.5 1.4 20.0
P519A - 7
Important Concepts
u Point of Common Coupling
u Average Maximum Demand Load Current
u SCR - Short Circuit Ratio
Utility System
Customer Under Study
Other UtilityCustomers
PCC
IL
Utility System
Customer Under Study
Other UtilityCustomers
PCC
IL
P519A - 8
Important Sections of P519A
u General Procedure
u Applying Limits for Large Nonlinear Loads
u Applying Limits for Industrial Facilities
u Applying Limits for Commercial Facilities
u Applying Limits for Residential Loads
u Utility Considerations
P519A - 9
General ProcedureUTILITY
Choose PCC,and Calculate Ssc
CUSTOMER
Estimate Sdw or % disturbing loads
Is PF correction existing
or planned?
Characterize harmonic levels
(measurement, calculation)
Design harmoniccontrol equipment
Verification bymeasurement and calculation
(if necessary)
Yes
No
YesNo
No
Yes
Stage 1: Automatic
acceptance?
Stage 2: Meet harmonic
limits?
P519A - 10
Automatic AcceptanceType of Load Typical Waveform
CurrentDistortion
WeightingFactor (Wi)
Single PhasePower Supply
0 10 20 30 40-1.0
-0.5
0.0
0.5
1.0
Time (mS)
Current
80%(high 3rd)
2.5
Semiconverter
0 10 20 30 40-1.0
-0.5
0.0
0.5
1.0
Time (mS)
Current
high 2nd,3rd,4th at partial
loads2.5
6 Pulse Converter,capacitive smoothing,no series inductance
0 10 20 30 40-1.0
-0.5
0.0
0.5
1.0
Time (mS)
Current
80% 2.0
6 Pulse Converter,capacitive smoothing
with series inductance > 3%,or dc drive
0 10 20 30 40-1.0
-0.5
0.0
0.5
1.0
Time (mS)
Current
40% 1.0
6 Pulse Converterwith large inductor
for current smoothing
0 10 20 30 40-1.0
-0.5
0.0
0.5
1.0
Time (mS)
Current
28% 0.8
12 Pulse Converter
0 10 20 30 40-1.0
-0.5
0.0
0.5
1.0
Current
15% 0.5
ac VoltageRegulator
0 10 20 30 40-1.0
-0.5
0.0
0.5
1.0
Current
varies withfiring angle 0.7
Automatic Acceptance if:
SDw / SSC < 0.1 %
Note: detailedevaluation shouldalways be performedif power factorcorrection capacitorsexist or are planned
P519A - 11
Important Concept -Time Varying Nature of Harmonics
0
2
4
6
8
10
0 10 20 30 40 50 60Tim e (minutes)
Cu
rren
t T
HD
(%
)
Current THD measured at Port of Vancouver, B.C.(harmonic bursts are caused by cranes lifting containers)
P519A - 12
Use statistics to describe theharmonic levels
0 5 10 15 20 0
250
500
750
1000
1250
1500
0
20
40
60
80
100
Current (A)
Count
Cumulative Probability (%)
Statistical Summary of Total Harmonic RMS Current (Amps)
Compare with519 Limits
P519A - 13
Short bursts vs. continuousharmonic distortion
Both cases have THDs exceeding 5% for 40% of themeasurement period. But case A is more severe since theharmonic bursts are concentrated in a single period.
0
2
4
6
8
10
0 20 40 60 80 100
Time (minutes)
TH
D (
%)
0
2
4
6
8
10
0 20 40 60 80 100
Time (minutes)
TH
D (
%)
case A case B
P519A - 14
BC Hydro limits
Acceptableharmonic distortion level
Maximum duration ofa single harmonic burst
(Tmaximum)
Total duration ofall harmonic bursts
(Ttotal)
3.0 x (design limits) 1 sec < Tmaximum < 5 sec 15 sec < Ttotal < 60 sec
2.0 x (design limits) 5 sec < Tmaximum < 10 min 60 sec < Ttotal < 40 min
1.5 x (design limits) 10 min < Tmaximum < 30 min 40 min < Ttotal < 120 min
1.0 x (design limits) 30 min < Tmaximum 120 min < Ttotal
The limits apply to a 24 hour measurement period
P519A - 15
Measurement Considerations
u Where to measure– effect of transformer when measuring on the
low side and PCC is on the high side
u Voltage measurements
u Current measurements– what is the base current?
u Monitoring Durations
u Sampling Requirements
P519A - 16
System Conditions to Consider(for analysis of potential problems)
• power factor correction capacitors in the customer facility
• harmonic filter out of service
• power factor correction capacitors on the utility supplysystem
• alternative sources from the utility (e.g. alternate feeders)
• different load combinations than can be evaluated in thefield tests
• nearby customers with significant harmonic production
P519A - 17
1. A two staged procedure to evaluate a facility
2. Apply steady-state limits to time varying data
3. Conditions to evaluate limit compliance
• Stage 1: Automatic acceptance for facilities with little disturbing loads• Stage 2: Should demonstrate compliance to harmonic limits
• Methods to characterize time varying harmonic measurements• Methods to apply the limits to measured data• Consideration of plant operating cycles at the design stage
• Measurement: instrumentation, monitoring duration, ... • Calculation: modeling assumptions, plant operating conditions, ...
Summary
IEEE P519AConcerns for IndustrialFacilities
October, 1998
P519A Industrial Evaluations - 2
Industrial Concerns
u Nonlinear Loads– ASDs, dc drives, rectifiers for dc processes,
induction furnaces, arc furnaces
u Power Factor Correction– capacitors result in resonance concerns
u Motor Loads– do not provide much damping for harmonics
P519A Industrial Evaluations - 3
Industrial Evaluations:The Six-Step Process
u Step 1: Select the PCC– normally the high-side of the supply transformer(s)
u Step 2: Characterize the nonlinear loads– “typical” spectra may be used
– measurements are needed for load groups
u Step 3: Determine power factor correction needs– parallel resonance may magnify harmonics
– series resonance may “sink” harmonics from the utility
P519A Industrial Evaluations - 4
The Six-Step Process, cont.
u Step 4: Evaluate harmonic performance at PCC– frequency response of power circuits
– harmonic characteristics of loads
u Step 5: Design harmonic mitigation equipment– passive filters coordinated with power factor correction
capacitors
– active filters may be better for smaller needs
u Step 6: Verify performance with measurements– monitor long enough to capture temporal variations
P519A Industrial Evaluations - 5
Example case to illustrateindustrial evaluation issues
u multiple sources, harmonic cancellationeffects
u power factor correction/resonance concerns
u choosing the PCC
u design of harmonic filters to controlharmonic levels
u evaluating the time varying nature of theharmonic levels
P519A Industrial Evaluations - 6
Example System
P519A Industrial Evaluations - 7
Harmonic Source Characteristics
Wye-DeltaTransformer
Serves 16Rectifiers
SaturableReactors forDC Control
Full Wave Rectifier
DC CurrentTo Batteries
+
-
0
5
10
15
20
25
30
35
40
45
5 7 11 Total
Harmonic Order
Cu
rren
t D
isto
rtio
n, %
5A
10A
15A
20A
Rectifie rDC
Output
P519A Industrial Evaluations - 8
Resonance Concern
0.00
0.30
0.60
0.90
1.20
1.50
0 300 600 900 1200 1500
No Capaci tors
Impe
danc
e,
ΩΩ
Frequency (Hz)
Capaci tors
ResonancePoint
P519A Industrial Evaluations - 9
Avoiding Resonance Problems
0.00
0.30
0.60
0.90
1.20
1.50
0 300 600 900 1200 1500
2400 kvarCap Bank
2032 kvar4.7 th F ilter
Impe
danc
e,
ΩΩ
Frequency (Hz)
1200 kvarCap Bank
P519A Industrial Evaluations - 10
Measurement results -time varying characteristics
% Current TDD for a Daily Load Cycle
0
1
2
3
4
5
6
7
8
0 2 4 6 8 10 12 14 16 18 20 22
Hour
% C
urr
ent
TD
D
PCC 44 kV
PCC 480 V
P519A Industrial Evaluations - 11
Measurement results -statistical characteristics
0
1
2
3
4
5
6
7
8
9
0.00
00.
083
0.16
70.
250
0.33
30.
417
0.50
00.
583
0.66
70.
750
0.83
30.
917
1.00
0
Probability
% C
urr
ent
TD
D
2-Filters All-Filters
PCC 44 kV
The X-axis value represents the probability that the % Current
TDD will be greater than the Y-axis value
P(%TDD>8.0%) = 0.04
Probability that % TDD is Greater than the Limit for 2- Filters and for All-Filters
P519A Industrial Evaluations - 12
Evaluating ASD Loads -Example System for Analysis
480 Volt Bus
1500 kVAZ=6%
PCCShort Circuit Strength = 40 MVASCR = 40/1.2 = 33.33
ASD Load
Linear Load
Utility Distribution System
Power Factor Correction/Filters
P519A Industrial Evaluations - 13
ASD Harmonic Levels
30%
50%
70%
90%
110%
130%
0% 5% 10% 15% 20% 25% 30%
No Choke Choke
ASD kVA
Transformer kVA
I(t) at 33% kVA ratio
♦
◊◊
◊◊
◊◊
♦
♦ ♦◊◊
I(t) at 5% kVA ratio
Transformer5% Z
(on xfmr kVA)Choke3% Z
(on ASD kVA)ASD
I THD
P519A Industrial Evaluations - 14
ASD Harmonic Currents
0.05 0.06 0.07 0.08 0.09 0.10-400
-200
0
200
400
100 HP PWM ASD - No Choke/Filter
Time (Seconds)
Current (A
mps)
TYPE 1 Waveform100 HP PWM ASD - No Choke
Amps
TYPE 2 Waveform100 HP PWM ASD - 3% Choke
0.05 0.06 0.07 0.08 0.09 0.10-400
-200
0
200
400
Time (Seconds)
Current (A
mps)
Amps
1 3 5 7 9 11 13 15 17 19 21 23 25
Harmonic Number
0%
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
Harm
on
ic Mag
nitu
de (%
of F
un
dam
ental)
ITHD = 80.6%
IRMS = 148.2 Amps
IFund = 115.4 Amps
1 3 5 7 9 11 13 15 17 19 21 23 25
Harmonic Number
0%
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
Harm
on
ic Mag
nitu
de (%
of F
un
dam
ental)
ITHD = 37.7%
IRMS = 117.6 Amps
IFund = 110.1 Amps
P519A Industrial Evaluations - 15
Rules of Thumbu How much of the plant load can be ASDs without
exceeding IEEE 519 guidelines?
ASD Loading as % of Max Plant Load
To
tal P
lan
t 5t
h H
arm
on
ic C
urr
ent
(%o
f M
ax P
lan
t L
oad
Cu
rren
t)
0.0%
10.0%
20.0%
30.0%
40.0%
50.0%
60.0%
70.0%
0.0% 20.0% 40.0% 60.0% 80.0% 100.0%
Type 1 Current Waveform
Type 2 Current Waveform
IEEE 519 Limit (7%)
P519A Industrial Evaluations - 16
Designing for Cancellation
u Transformer connections can be used to getcancellation of harmonics from differentdrives.
ASD ASD
480 Volt Bus
P519A Industrial Evaluations - 17
Effect of Power Factor Correction
u Rules of thumb only apply if there are no powerfactor correction capacitors.
0.00
0.50
1.00
1.50
2.00
2.50
3.00
3.50
4.00
1 3 5 7 9 11 13 15 17 19 21 23 25
HARMONIC NUMBER
MA
GN
IFIC
AT
ION
OF
HA
RM
ON
IC
CU
RR
EN
T F
RO
M A
SD
S 300 kVAr
500 kVAr700 kVAr
No Capacitor Bank
P519A Industrial Evaluations - 18
Power Factor Correction as Filters
u Power factor correction can be applied asharmonic filters to solve both the powerfactor problem and the harmonic problem.
0.00
0.50
1.00
1.50
2.00
2.50
3.00
3.50
1 3 5 7 9 11 13 15 17 19 21 23 25
HARMONIC NUMBER
MA
GN
IFIC
AT
ION
OF
HA
RM
ON
IC
CU
RR
EN
T F
RO
M A
SD
S
500 kVAr Tuned Cap Bank
No Capacitor Bank
P519A Industrial Evaluations - 19
How many filter branches are needed?
ASD Loading as % of Max Plant Load
To
tal P
lan
t 11
th H
arm
on
ic C
urr
ent
(%o
f M
ax P
lan
t L
oad
Cu
rren
t)
0.0%
1.0%
2.0%
3.0%
4.0%
5.0%
6.0%
0.0% 20.0% 40.0% 60.0% 80.0% 100.0%
Type 1 or Type 2Current Waveform
IEEE Limit (3.5%)
u With a fifth harmonic filter, the evaluation will typicallybe dominated by the 11th harmonic component.
P519A Industrial Evaluations - 20
Filter design procedureu Make sure the filter is designed for harmonic loading from
other loads and the supplying power system, as well as thenonlinear loads being evaluated.
Characterize harmonicproducing loads
Characterize power systembackground voltage
distortion
Design minimum size filters tuned to individual harmonic frequencies,starting with the fifth harmonic
Calculate (simulate) harmonic currents
at PCC
Check against IEEE-519current limits
Another steprequired
Done
P519A Industrial Evaluations - 21
Another Alternative is the APLC
Controlsand
Gating SignalGenerators
IGBTPWM
Inverter
Is
If
IL
Main CustomerBus
NONLINEARLOAD
M
Interface Filter
P519A Industrial Evaluations - 22
Characteristics of other importantharmonic sources
u Dc drives
u Induction furnaces (heating processes)
u Arc furnaces
P519A Industrial Evaluations - 23
DC Drives
u Usually displacement power factor characteristicsare important (power factor correction oftenneeded)
P519A Industrial Evaluations - 24
Induction furnace loads
u Rectifier/inverter configurations often exhibitimportant interharmonic components (coupling ofoutput frequency to the input)
P519A Industrial Evaluations - 25
Arc furnace characteristics
u Unbalanced arc characteristics results in non-characteristic harmonic components (e.g. 3rd).
u Dynamic nature of the arc results in interharmoniccomponents and 2nd harmonic.
P519A Industrial Evaluations - 26
Semiconvertersu Concerns for even harmonics - makes filtering
very difficult
60 80 100 120-600
-400
-200
0
200
400
600
Firing Angle (Degree)
Current (A)
50 300 550 800 1050 0
50
100
150
200
250
300
350
Time (mS)
Firing Angle (Deg.) and Currents I1, I2, I4 (A)
I1
I2
I4
Alpha
50 300 550 800 1050 0
50
100
150
200
250
300
350
Time (mS)
Firing Angle (Deg.) and Currents I1, I5, and I7 (A)
I1
I5I7
Alpha
P519A Industrial Evaluations - 27
Cycloconverters
u Concern for interharmonics - interaction ofoutput frequency with the input frequency
u Traction power applications
u Mining, steel industry applications
P519A Industrial Evaluations - 28
Measurements to verify performance
Step 1 Step 2 Step 14
50 kVAr 50 kVAr 50 kVAr
Plant Load200 kVA0.85 dPF
1000 HPDC Drive
4160 V 480 V
1000 kVA5.5%Imp.
30 MVAX/R=12.0
PowerAnalyzer
Curr
ent P
robe A
Curr
ent P
robe B
Volta
ge P
robe B
Volta
ge P
robe C
Curr
ent P
robe C
Volta
ge P
robe A
P519A Industrial Evaluations - 29
Notching Concerns -example case
144 kV
25 kV Bus
other
loads
2 km 266 MCM
4.16 kV
10 MVA
7.87%
7.5 MVA
5.75%
10 km
1/0
other
loads
480 Volt bus4.16 kV
6000 hp
ASD
harmonic
filters
5,7,11
Motor Load
(650 hp)
PF Correction
Capacitors(160 kvar)
800 hp
0.5 uF
surge capacitors
Short Circuit Level =74 MVA
1500 kVA
4.7%
1500 kVA
4.7%
Voltage Waveform on 25 kV System During Drive Operation
0 5 10 15 20-1.5
-1.0
-0.5
0.0
0.5
1.0
1.5
Time (mS)
Voltage (pu)
PASS Waveform
P519A Industrial Evaluations - 30
Summary - Industrial Concerns
u Variety of Nonlinear Loads
u Power factor correction results in resonanceconcerns
u Time varying nature of the harmonicsources
u Other special concerns (non-characteristicharmonics, interharmonics, notching)
u Filter design issues
P519A Industrial Evaluations - 31
Exercises forIndustrial facility evaluations
u Simple circuit to evaluate 519 complianceand filter design issues
u Develop rules of thumb
u Nonlinear load models
u Evaluate alternative solutions
u Filter design - effectiveness evaluation
IEEE P519AConcerns for CommercialFacilities
October, 1998
P519A Commercial Evaluations - 2
Commercial Facility Concerns
u Proliferation of electronic loads
u Distortion levels within facility vs. serviceentrance– transformer derating
– neutral currents
– harmonic cancellation from multiple sources
u Impact of ASDs for HVAC systems
u Standby generators - harmonic concerns
P519A Commercial Evaluations - 3
Commercial Facility HarmonicSources
u Electronic Loads (switch mode powersupplies)
u Fluorescent Lighting
u Adjustable Speed Drives (HVACApplications)
P519A Commercial Evaluations - 4
Switch Mode Power Supplies
Waveform and spectrumfor a circuit supplyingelectronic loads.
P519A Commercial Evaluations - 5
Fluorescent Lighting
Typical waveform and spectrum for lighting circuit withmagnetic ballasts
P519A Commercial Evaluations - 6
ASDs (HVAC Systems)
PWM Type ASDwith 3% input choke
P519A Commercial Evaluations - 7
How do the harmonic currents combine?
P519A Commercial Evaluations - 8
Commercial Facility Concerns
u Neutral currents
u Transformer derating requirements
u Standby generator rating requirements
P519A Commercial Evaluations - 9
Example of High Neutral CurrentPhase A (50 Amps)
Phase B (50 Amps)
Phase C (57 Amps)
Neutral (82 Amps)
P519A Commercial Evaluations - 10
Estimating neutral currents
u Neutral currents can be estimated based on the percentageof the load on the three phase circuit that consists of singlephase electronic equipment
rms Neutral Current in pu of rms Phase Current
0.00
0.20
0.40
0.60
0.80
1.00
1.20
1.40
1.60
1.80
0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
Electronic Load (% of Total Load)
Neu
tral
Cu
rren
t
Ineutralp
pIphaserms
nl
nlrms=
+3
0 5
1 0 5
2
2
.
.
P519A Commercial Evaluations - 11
Solutions to Overloaded Neutrals
u Increase the neutral conductor size
u Neutral for each phase
u Double neutral
u Third harmonic filter at each load
u Zig Zag transformer close to loads
u Active filter(s)
P519A Commercial Evaluations - 12
Transformer Derating Considerations
u Transformer derating requirements for harmonicsspecified in ANSI/IEEE C57.110-1991.
u Function of Transformer Eddy Current Losses
u Derating needs to be applied whenever the fullload current distortion exceeds 5%
u K-Factor transformers designed to supplynonlinear loads without derating
P519A Commercial Evaluations - 13
Transformer Derating - ANSI C57.110
Required Transformer Derating for Electronic Load as a Function of the Per Unit Eddy Current Losses
50.0%
60.0%
70.0%
80.0%
90.0%
100.0%
0% 5% 10% 15% 20%
Eddy Current Loss Factor (%)
Req
uir
ed D
erat
ing
(%
)
IP
K Prms
EC R
EC R
=+
+−
−
1
1 *
KI h
Ih
h
=∗∑
∑
2 2
2
P519A Commercial Evaluations - 14
Derating vs. Nonlinear Load
Required Derating for Conventional Transformer vs. Percent Electronic Load
84.0%
86.0%
88.0%
90.0%
92.0%
94.0%
96.0%
98.0%
100.0%
0% 20% 40% 60% 80% 100%
Percent Electronic Load
Req
uir
ed D
erat
ing
The required derating also depends on the percent of theload made up of electronic equipment (or other nonlinearloads).
P519A Commercial Evaluations - 15
K-Factor Transformers
K-Factor Transformers are designed to supplynonlinear loads without derating. The K-Factor definesthe level of current distortion that is acceptable.
Required Transform e r K-Factor vs P e rce n t Electronic Load
0.00
1.00
2.00
3.00
4.00
5.00
6.00
7.00
0% 20% 40% 60% 80% 100%
Percent Electronic Load
K-F
acto
r KI h
Ih
h
=∗∑
∑
2 2
2
P519A Commercial Evaluations - 16
Standby Generator Requirementsu Harmonics can be more of a problem during backup
generator operation due to generator impedance.
u Calculate voltage distortion with generator operating andlimit to 5%
u Make sure harmonic currents do not exceed generatorcapabilities Automatic
TransferSwitch (ATS)
Line fromFeeder toBuilding
AirConditioningEquipment
AC
DC
DC
AC
Battery Systemwith
DC Disconnect
StaticBypass
Panelboard
UPS
ToLoad
GEN
Typical configurationof UPS system forcritical loads withbackup generator
P519A Commercial Evaluations - 17
Overall Facility Harmonic Levels
Example System to evaluate distortion levels at the PCC
Single PhaseElectronic
Load
1500 kVAZ=6%
Distribution System
Other120/208 V
Load
FlourescentLighting Load
HVACLoad
500 kVAZ=3%
Short Circuit Level = 50 MVA
Max. Demand Load = 1200 kVA
(300 kVA)
P519A Commercial Evaluations - 18
Voltage and Current Distortionwithout ASDs
Voltage Distortion at 480 volt Bus Caused by Facility Nonlinear Loads
0.00%
1.00%
2.00%
3.00%
4.00%
5.00%
6.00%
0% 5% 10% 15% 20% 25% 30% 35%
Electronic Load as % of Maximum Facility Load
Vo
ltag
e T
HD
Current Distortion (TDD) at PCC Caused by Facility Nonlinear Loads
0.00%
4.00%
8.00%
12.00%
16.00%
0% 5% 10% 15% 20% 25% 30% 35%
Electronic Load as % of Maximum Facility Load
Cu
rren
t D
isto
rtio
n (
TD
D)
P519A Commercial Evaluations - 19
Voltage and Current DistortionLevels with ASDs
Voltage Distortion at 480 volt Bus Caused by Facility Nonlinear Loads
0.00%
1.00%
2.00%
3.00%
4.00%
5.00%
6.00%
7.00%
8.00%
0% 5% 10% 15% 20% 25% 30% 35%
ASD Load as % of Maximum Facility Load
Vo
ltag
e T
HD
Current Distortion (TDD) at PCC Caused by Facility Nonlinear Loads
0.00%
4.00%
8.00%
12.00%
16.00%
20.00%
0% 5% 10% 15% 20% 25% 30% 35%
ASD Load as % of Maximum Facility Load
Cu
rren
t D
isto
rtio
n (
TD
D)
P519A Commercial Evaluations - 20
Summary - Concerns for 120/208 circuits
u Neutral conductors in 3-phase, 4-wire circuits servingelectronic loads should be rated for 170% of the maximumline current.
u Neutral conductors in fluorescent lighting circuits shouldbe rated for maximum line current.
u Transformers for step down to 120/208 that supplyelectronic loads should be derated for harmonics or shouldbe k-factor transformers
u Voltage distortion on 120/208 v secondary circuits will bedominated by electronic loads. Distortion should be below5% if total electronic load is below 25% of transformerrating.
P519A Commercial Evaluations - 21
Summary - Concerns for overall facility
u Voltage distortion in 480 v circuits will depend on thecumulative effect of office loads, fluorescent lighting, andHVAC equipment.
u Most commercial facilities should not exceed 519 limitsunless there is significant penetration of ASDs for HVACapplications or a large percentageof the load is electronic(some type of filtering could be needed in these cases).
u Retrofitting with electronic ballasts should not havesignificant impacts on building harmonic levels if ballastswith less than 30% current distortion are used.
P519A Commercial Evaluations - 22
Exercises forcommercial facility evaluations
u Simple circuit to evaluate effects of different loadcombinations
u Harmonic source representations for differenttypes of loads– electronic loads
– lighting
– asds
u Neutral currents, transformer derating, interactionevaluations
IEEE P519AConcerns for ResidentialSystems
October, 1998
P519A Residential Evaluations - 2
Harmonic concerns for circuitssupplying residential customers
u Characteristics of nonlinear loads– electronic loads
– ASD heat pumps and air conditioners
– compact fluorescents
– electric vehicle battery chargers
u System frequency response characteristics
u How to apply limits
P519A Residential Evaluations - 3
Evaluate response to CFLsas an example
u CFLs are being promoted as part of energyconservation programs at many electricutilities.
u A recent study has concluded that low CFLpenetration levels can cause the feedervoltage distortion to exceed 5%.
u Previous studies have indicated that furtherinvestigation needs to be done.
P519A Residential Evaluations - 4
Introduction - cont.
u Measurements were performed to identifyharmonic characteristics for different CFLs
u Transient models utilized to develop adetailed representation of typical loads.
u Harmonic simulations used to examinecumulative effect of CFLs.
P519A Residential Evaluations - 5
High Distortion Electronic Ballast CFLs
Electronic High Distortion Lamp 3 Waveform
0 10 20 30 40-0.4
-0.2
0.0
0.2
0.4
Time (mS)
Current (A)
Electronic High Distortion Lamp 3 Spectrum
0 600 1200 1800 2400 30000.00
0.01
0.02
0.03
0.04
0.05
0.06
0.07
Frequency (Hz)
Current (A)
Freq :Fund :THD :TID :TD :RMSh :RMSi :RMSfh:RMS :ASUM :TIF :IT :
60 0.0665344 144.009 0 144.009 0.0958158 0.0665344 0.116651 0.116651 0.313131 939.301 109.571
Harmonic Current Distortion of 140%
P519A Residential Evaluations - 6
Low Distortion Electronic Ballast CFLs
Electronic Ballast, Low THD, Lamp 1 Waveform
0 10 20 30 40-0.8
-0.6
-0.4
-0.2
0.0
0.2
0.4
0.6
0.8
Time (mS)
Current (A) Electronic Ballast, Low THD, Lamp 1 Spectrum
0 600 1200 1800 24000.00
0.05
0.10
0.15
0.20
0.25
0.30
Frequency (Hz)
Current (A)
Freq :Fund :THD :TID :TD :RMSh :RMSi :RMSfh:RMS :ASUM :TIF :IT :
60 0.266187 33.8903 0 33.8903 0.0902114 0.266187 0.281058 0.281058 0.517387 628.985 176.781
Harmonic Current Distortion of 30%
P519A Residential Evaluations - 7
Magnetic Ballast CFLsMagnetic Ballast, Low THD, Low PF, Lamp 1 Waveform
0 10 20 30 40-0.3
-0.2
-0.1
-0.0
0.1
0.2
0.3
Time (mS)
Current (A)
Magnetic Ballast, Low THD, Low PF, Lamp 1 Spectrum
0 240 480 720 960 12000.00
0.02
0.04
0.06
0.08
0.10
0.12
0.14
Frequency (Hz)
Current (A)
Freq :Fund :THD :TID :TD :RMSh :RMSi :RMSfh:RMS :ASUM :TIF :IT :
60 0.133063 14.4984 0 14.4984 0.019292 0.133063 0.134454 0.134454 0.16235 21.272 2.8601
Harmonic Current Distortion of 20%
P519A Residential Evaluations - 8
Residential Circuit Example
P519A Residential Evaluations - 9
Assumed Harmonic Spectrum
Harmonic Magnitude Angle
1 100.0% -11.53 82.0% -385 53.4% -62.57 31.6% -85.19 16.6% -103.311 8.2% -11113 1.5% -99.115 1.0% -88.417 0.6% -95.519 0.5% -109.521 0.3% -120.523 0.1% -107.525 0.1% -67.4
High Distortion ElectronicBallast CFLs Including Cancellation Effects
P519A Residential Evaluations - 10
Distribution System StudiedSubstationNorth Bus
Feeder1 Feeder 2 Feeder 3 Feeder 5Feeder 4
44.8 MVA66/12kV
∆∆ ∆∆Y Y
600kVAr
600kVAr
1800kVAr
1800kVAr
1800kVAr
1200kVAr
1200kVAr
1800kVAr
1200kVAr1200kVAr
1200kVAr1200kVAr
6000 kVAr SwitchedSubstation Capacitor
Bank
31% of loads are commercial
P519A Residential Evaluations - 11
System Frequency ResponseFrequency Scan at Feeder End
0 6 12 18 24
0
10
20
30
40
50
Harmonic Level
Impedance (ohms)
Light Load
Heavy Load
This case was selected to represent worst case realisticThis case was selected to represent worst case realisticcircuit conditions due to the system resonance at the fifthcircuit conditions due to the system resonance at the fifthharmonic.harmonic.
P519A Residential Evaluations - 12
System Frequency ResponseComparison
Frequency Scan at Mid-Feeder
0 6 12 18 24
0
10
20
30
40
Harmonic Level
Impedance (ohms)
With non-linear and linear loads
With linear loads only
P519A Residential Evaluations - 13
Effect of CFL Penetration
0%
4%
8%
12%
16%
Sub Mid End Sub Mid End Sub Mid End
% THD
50 W/House 100 W/House 150 W/House
P519A Residential Evaluations - 14
Effect of CFL Type
0%
4%
8%
12%
16%
Sub Mid End Sub Mid End Sub Mid End
% THD
Magnetic Low THD Electronic
High THD Electronic
P519A Residential Evaluations - 15
Summary of potential impactsu High penetration levels of CFLs that use
high distortion electronic ballasts can resultin unacceptable voltage distortion levels.
u CFLs with lower current distortion levels(30% or less) should not cause problems onthe feeder.
u Distortion levels are dependent on systemconditions (capacitance, representation ofelectronic loads, etc.)
P519A Residential Evaluations - 16
Summary of Voltage Distortion
Case with No Resonance
0
2
4
6
8
10
12
14
16
0 50 100 150
CFL Load per Residence (W)
Feed
er V
olta
ge D
isto
rtio
n
Sub
End
P519A Residential Evaluations - 17
Summary - cont.
Resonance Case
0
2
4
6
8
10
12
14
16
0 50 100 150
CFL Load per Residence (W)
Feed
er V
olta
ge D
isto
rtio
n
Sub
End
P519A Residential Evaluations - 18
How to apply limits
u Limit harmonics from individual loads (IEC1000-3-2)
u Limit harmonics per resonance (verydifficult to enforce)
u Prevent resonance conditions on thedistribution system or control harmonics onthe distribution system
P519A Residential Evaluations - 19
IEC Approach
u Limit harmonic currents for individual equipment(type testing).
u IEC 1000-3-2 for equipment up to 16 amps.
u IEC 1000-3-4 for equipment up to 75 amps(under development).
u This should limit overall harmonic distortionlevels to acceptable values.
u Procedure for evaluating customers supplied atmedium voltage and high voltage (1000-3-6).
P519A Residential Evaluations - 20
IEC 1000-3-2 (General Loads)
u Equipment currentlimits for equipment upto 16 amps.
u Designed for 380 voltsystems (L-L).
u Class A equipment isgeneral purpose loads.
Maximum PermissibleHarmonic Harmonic Current
Order (in Amperes)Odd Harmonics
3 2.35 1.147 0.779 0.4
11 0.3313 0.21
15-39 0.15 x (15/n)Even Harmonics
2 1.084 0.436 0.3
8-40 0.23 x (8/n)
P519A Residential Evaluations - 21
IEC 1000-3-2 (Lighting Loads)
u Class C equipment:
Maximum value expressed as a percentage of the fundamental input
Harmonic Order current of luminaires2 2%3 30% x PF5 10%7 7%9 5%
11-39 3%
P519A Residential Evaluations - 22
IEC 1000-3-2 (Power Supply Loads)
u Class D equipment(special waveform).
u Note that relative limitsonly apply up to 300watts. Absolute limitapplies up to the 16 ampmaximum.
Relative Limit Maximum permissible Harmonic Order (mA/W) harmonic current (A)
3 3.4 2.35 1.9 1.147 1 0.779 0.5 0.411 0.35 0.33
13-39 linear extrapolation: see table for Class A 3.85/n equipment
P519A Residential Evaluations - 23
Limits for electronic loadsClass D Harmonic Limits
0.0%
10.0%
20.0%
30.0%
40.0%
50.0%
60.0%
70.0%
80.0%
90.0%
0 500 1000 1500 2000 2500 3000 3500 4000
Power Rating (Watts)
Har
mo
nic
Lim
it (
% o
f ra
ted
cu
rren
t)
Third
Fifth
Seventh
Ninth
Eleventh
P519A Residential Evaluations - 24
IEC 1000-3-4 (Loads up to 75 Amps)
u Under development.
u Limits dependent onshort circuit ratio.
u Initial draft set of limitsunder discussion.
I1/Ic < 1/35 I1/Ic < 1/170
Harmonic Order In/I1 (% ) In/I1 (% )
3 21.6 50.45 10.7 257 7.2 16.99 3.8 8.8
11 3.1 7.213 2 4.615 0.7 1.617 1.2 2.819 1.1 2.6
P519A Residential Evaluations - 25
Summary-handling residential harmonics
u Where to apply limits?
u What should the limits be?
u Resonance concerns
u Controlling harmonics on the distributionsystem
u Effect of new load types (electric vehiclechargers)
P519A Residential Evaluations - 26
Exercises for residential evaluation
u Example circuit, capacitor configurations
u Representation for residential customers– without nonlinear loads
– with nonlinear loads
u Characteristics of other large harmonicsources– asds
– electric vehicle chargers
IEEE P519AUtility Considerations
October, 1998
P519A Utility Considerations - 2
System Response Characteristics
u Voltage distortion is a result of the voltage drop createdacross the equivalent power system impedance.
u At 60 Hz, power systems are primarily inductive. Theequivalent inductance can be calculated:
Xsc= system short circuit reactance
f = power system fundamental frequency (60 Hz)
LX
feqsc=∗2π
P519A Utility Considerations - 3
Utility Considerations
u Controlling system voltage distortion levels
u Resonance considerations
u Utility equipment applications (e.g. SVC)
u Economic Considerations
u Telephone Interference
u Using rates to control harmonics?
P519A Utility Considerations - 4
Distribution System ResponseDistribution Substation Bus
Harmonic currents tend to flowfrom the harmonic source (nonlinear load)into the utility source because it is the lowest impedance.
P519A Utility Considerations - 5
Effect of Capacitors -Parallel Resonance
Capacitor increases harmonic current flow into the substation.
Distribution Substation Bus
Magnified Harmonic Current
P519A Utility Considerations - 6
Effect of Capacitors -Series Resonance
Distribution Substation Bus
Equivalent Circuit
Feeder branch and capacitor appear to be a series LC circuit.
P519A Utility Considerations - 7
Some Modeling Guidelines
u Substation transformer with short circuit equivalent on the high side.
u Overhead distribution lines can be modeled with series impedances.Cables must include shunt capacitance.
u Include all capacitor bank locations in the model.
u Model transformers and low side buses for customers with low voltagepower factor correction or filters.
u Include simple resistive representation for load or resistance with aseries inductance to represent step down transformers.
u Three phase model is needed to evaluate positive and zero sequenceharmonic components together. Otherwise, positive sequencerepresentation usually adequate.
P519A Utility Considerations - 8
Utility Equipment Applications
u Apply harmonic limits based on studies ofthe impact on the overall system voltagedistortion levels and other impacts (e.g.telephone interference)
u Economic evaluation of harmonic controllalternatives
P519A Utility Considerations - 9
Economics of controlling harmonicdistortion levels
u System perspective for the economicanalysis
u Alternatives– control at individual loads
– control at customer level
– control on the system
u Minimize total costs
P519A Utility Considerations - 10
How Can Harmonics be Controlled?
u Control at the equipment level (IEC 1000-3-2).
u Control at the customer level (IEEE 519 -current).
u Control on the utility system (IEEE 519 -voltage).
Some combination of these will probably be necessary.
P519A Utility Considerations - 11
Future of Harmonic Control
u Harmonics will be controlled at individual nonlinear loadswith better power supplies and active compensation.
u Harmonics will be controlled at the customer level withactive devices that can provide var control, harmoniccontrol, and some power conditioning(e.g. voltage sag ride through support).
u Harmonics will be controlled on the distribution systemalong with vars using active filter technology.