overview guide qdm-05-0000225. provide training on proper installation of all view equipment and...
TRANSCRIPT
1 of 37 ©2019 View, Inc.Rev 6 | Aug 2019
OVERVIEW GUIDE QDM-05-000022
Installation Overview
2 of 37 ©2019 View, Inc.Rev 6 | Aug 2019
OVERVIEW GUIDE
View responsibilities:
1. Shipment of IGUs, System Controls, programming and commissioning.
2. The View Project Manager will guide the project team successfully through the implementation process.
3. Provide all product documentation including IGU, roof sensor, control panel, Wall Controls, BMS integration, window controller, and wiring datasheets.
4. Provide Preliminary Interconnect and Final Interconnect Drawings.
5. Provide training on proper installation of all View equipment and best practices.
6. Provide IGU and System Controls shipments on committed ship dates.
7. Mobilize Field Service Engineers to perform functional hardware testing and commissioning.
8. Mobilize Customer Success Manager to work directly with end user during the construction phase and end phase to customize system and provide occupant training.
9. Provide a turnover package and operations training.
10. Provide warranty, support and service.
Responsibilities: Installation Scope of Each Trade
3 of 37 ©2019 View, Inc.Rev 6 | Aug 2019
OVERVIEW GUIDE
Glazier responsibilities:1. Provide the shop drawings of Dynamic Glass usage as specified by the architect.
2. Provide the final IGU sizes and makeup, IGU cable lengths and routing in the glazing system, phased shipment schedule, and packaging needs.
3. Provide safe and secure storage of View materials until building is ready for installation.IGU installation in facade with IGU cable stubbed out to agreed upon accessible location for easy hand-off to Low-Voltage Contractor or Electrician.
4. IGU installation in facade with IGU cable stubbed out to agreed upon accessible location for easy hand-off to Low-Voltage Contractor or Electricial.
5. Label all IGU cables per View interconnect drawing. Glazier responsible for testing each IGU post installation using the 4-state controller (provided by View), after testing is completed, label each cable with green “TESTED” label (green “TESTED” labels provided by View).
6. Provide glazier support during View functional hardware testing and commissioning phase, glazing contractor shall be responsible for repairing items identified by the View FSE during functional hardware testing and commissioning phase.
4 of 37 ©2019 View, Inc.Rev 6 | Aug 2019
OVERVIEW GUIDE
1. Define location of System Controls including control panel location, roof sensor, window controller location, trunk cable routing, and drop cable routing (based on View’s design guidelines and datasheets). Provide final lengths of all cabling based on View’s Preliminary Interconnect Drawing that will result in the System Controls Bill of Materials (BOM).
2. Define any phased delivery needs based on the construction plans.
3. Installation of Control Panels, trunk, power insert and drop cables, window controllers, roof sensor, Wall Interface Devices and WAPs (wireless access points).
4. Shall be responsible for all building penetrations, coring, raceways and sleeves necessary to accommodate View control cables. This work should be coordinated with glazing contractor and GC in accordance with local building codes.
5. If IGU cable needs to be extended, LVE shall test using 4-state controller and provide green tested labels.
6. Responsible for labeling all trunk lines, power insert lines and IGU cables per View interconnect drawing.
7. Responsible for testing each IGU post installation using the 4-state controller (provided by View), after testing is completed, label each cable with green “TESTED” label (green “TESTED” labels provided by View).
8. Provide field support as needed during functional hardware testing and commissioning phase, Low-Voltage contractor shall be responsible for repairing items identified by the View FSE during functional hardware testing and commissioning phase. Any billable hours for troubleshooting should be coordinated with the GC.
9. Keep track of all cable and equipment changes including lengths, locations and cable pathways. Provide accurate redline drawings to View Project Manager at completion of project.
10. Electrician to provide stable power prior to functional hardware testing and commissioning.
Low Voltage Contractor or Electrician responsibilities:
5 of 37 ©2019 View, Inc.Rev 6 | Aug 2019
OVERVIEW GUIDE
11. Responsible for all network connections between View equipment (control panels, sky sensor, wall controls and WAPs).
12. LVE may be responsible for installing IGU cables into the glazing system based on Union guidelines.
13. Assist VIEW FSE during functional hardware testing.
14. Take delivery and provide safe and secure storage of View materials until building is ready for installation.
6 of 37 ©2019 View, Inc.Rev 6 | Aug 2019
OVERVIEW GUIDE
Glazier scope (in green) and LVE scope (in red)
Low Voltage Electrician
Glazier
7 of 37 ©2019 View, Inc.Rev 6 | Aug 2019
OVERVIEW GUIDE
Viewing from inside out
IGU TesterUsed to test
the IGUs
IGU
IGU Cable
Illustration Purposes OnlyNot to scale
Ring Photo Sensor
10
IGU Smart Window Connector
Basic components for Glaziers (IGU testing equipment is provided by VIEW)
8 of 37 ©2019 View, Inc.Rev 6 | Aug 2019
OVERVIEW GUIDE
https://view.com/training
Training Videos Available
Glazier Installation Video
9 of 37 ©2019 View, Inc.Rev 6 | Aug 2019
OVERVIEW GUIDE
Below is a table showing an example IGU quantity for a 10,000 sq. ft. (glass area) building. Also shown are the expected additional installation labor minutes per IGU and extended total labor hours accounting for the total number of IGUs. This additional installation time is related to the glazier preparing the IGU frames by drilling holes, deburring hole edges or inserting silicone grommets, and sealing penetrations with silicone as needed to route View cable per View interconnect drawings. Glazier is also responsible for labeling IGU cables per View interconnect drawing. Glazier responsible for testing each IGU post installation using the 4-state controller (provided by View), after testing is completed, label each cable with a green “TESTED” label (green “TESTED” labels provided by View). In this example, we are using $100.00/hr. for the labor rate. We suggest using local market labor rates for this project.
For this example, the IGU and Smart Window Connector are shown in the chart below. The IGU Smart Window Connector will be connected to the IGU cable by the glazing contractor and needs to be made accessible for the LV Electrician.
DEVICE/ITEM QTYLABOR
MINUTES PER DEVICE
ESTIMATED TOTAL LABOR
HOURSLABOR RATE TOTAL
IGU 500 10 83.33 $100.00 $8,333.00
Glazing Installation Labor Estimate Example
10 of 37 ©2019 View, Inc.Rev 6 | Aug 2019
OVERVIEW GUIDE
TYPICAL ELEVATIONSCALE: NONE
1 --3 --
2 --
5--
4--
DETAIL 1HEAD
DETAIL 3SILL
DETAIL 2HORIZONTAL MULLION, SILICONE GLAZED
DETAIL 5LEFT JAMB
DETAIL 4VERTICAL MULLION, SILICONE GLAZED
7/16" DIA. HOLE FOR IGU CABLE TOSMART WINDOW CONNECTOR (SWC) .FILE ALL EDGES SMOOTH.FILL WITH SILICONE SEALANT.
7/16" DIA. HOLES FOR IGU CABLESAT ALL VERTICALS. REQ. (1) PER IGUCABLE. FILE ALL EDGES SMOOTH.
IGU CABLE CONNECTION TO IGUSMART WINDOW CONNECTOR(SWC) IN GLASS POCKET
7/16" DIA. HOLE FOR IGU CABLE TO SMARTWINDOW CONNECTOR (SWC) . FILE ALL EDGESSMOOTH. FILL WITH SILICONE SEALANT.
7/16" DIA. HOLE FOR IGUCABLE TO SMART WINDOWCONNECTOR (SWC) . FILEALL EDGES SMOOTH. FILLWITH SILICONE SEALANT.
7/16" DIA. HOLE FOR IGUCABLE TO SMART WINDOWCONNECTOR (SWC) . FILEALL EDGES SMOOTH. FILLWITH SILICONE SEALANT.
IGU CABLE CONNECTION TO SMARTWINDOW CONNECTOR (SWC) IN 7/16"HOLE. LAY REMAINDER OF SMARTWINDOW CONNECTOR (SWC) IN GLASSPOCKET.
WRAP ZIP TIE AROUND END OF SMARTWINDOW CONNECTOR (SWC) CONNECTORTO RETAIN SMART WINDOW CONNECTOR(SWC) ACCESSIBLE IN GLASS POCKET FORSERVICE.
7/16" DIA. HOLES FOR IGU CABLESAT ALL VERTICALS. REQ. (1) PER IGUCABLE. FILE ALL EDGES SMOOTH.
IGU CABLE CONNECTION TOSMART WINDOW CONNECTOR(SWC) IN 7/16" HOLE. LAYREMAINDER OF SMART WINDOWCONNECTOR (SWC) IN GLASSPOCKET.
WRAP ZIP TIE AROUND END OF SMART WINDOW CONNECTOR(SWC) CONNECTOR TO RETAIN SMART WINDOW CONNECTOR(SWC) ACCESSIBLE IN GLASS POCKET FOR SERVICE.
IGU CABLE CONNECTION TO IGUSMART WINDOW CONNECTOR(SWC) IN GLASS POCKET
VIEW, INC.®195 SOUTH MILPITAS BLVD.MILPITAS, CA 95035v. 408/263.9200www.viewglass.com
Mar
ch 2
6, 2
019
PLO
T D
ATE
:
: THIS DOCUMENT ANDTHE INFORMATION CONTAINED IN IT ARE CONFIDENTIAL,AND CANNOT BE COPIED OR DISCLOSED IN WHOLE OR INPART WITHOUT THE EXPRESS WRITTEN CONSENT OF
.
VIEW INC. CONFIDENTIAL
VIEW, INC ®
®
SCALE:1 INSTALLATION DETAILS: CURTAINWALL - FOR ARCADIA Ti BEAM 3 SERIES, SSGNONE
Glazier Shop Drawings
11 of 37 ©2019 View, Inc.Rev 6 | Aug 2019
OVERVIEW GUIDE
Input Power100-240 VAC
View TouchDisplay
Sky Sensor
Fiber OpticConnection
Input Power110-120 VAC
Cell ModemAssembly
12
Sky Sensor
11
IGU
01
IGU Smart Window Connector
08 08
IGU Cable
07IGU Cable
07
Power Insert Cable
09
Trunk Cable
02
Trunk Connector (WYE)
03
Trunk Connector (TEE)
03
Trunk Terminator10
Drop Cable
05
Window Controller06
Window Controller
06
View ControlPanel
Power Insert Connector
Viewing from inside out
NetworkConnection
Network or Cell Modem Connection
02 03 04 05 06 07 08 09 10 11 13
IGU Smart Window Connector
Components of View Control System without Dropbox
12 of 37 ©2019 View, Inc.Rev 6 | Aug 2019
OVERVIEW GUIDE
Basic Control System Components Descriptions
Cabling SystemThe View cabling system uses a trunk line/drop line net-work topology. In this topology, the trunk cable carries both power and data through the entire length of the installation. Drop cables are then tapped off of the trunk cable using trunk connectors at locations where window controllers are installed. The window controllers are then connected to individual IGU units via an IGU cable. Note: Component data sheets will supersede the information found here.
01 02 03 04 05 06 07 08 09 10 11 12Control PanelWall-mounted enclosure (21” x 29” x 9”) that contains the power supplies, master controller, as well as auxiliary con-nections such as Ethernet and external sensors. At least one control panel is required for each installation. Each control panel can support up to 256 window controllers. For larger or multi-floor installations, multiple control panels may be required. Each Control Panel requires a dedicated 20-amp circuit (20-amp@120 VAC or 10-amp @240VAC).
Specifications for Control Panel:Input AC 100-240V + 15%Frequency 50-60 Hz + 6%Output Class 2 24 VDC
01 02 03 04 05 06 07 08 09 10 11 12Trunk CablePre-terminated cables fitted with 7/8”, 5-pin connectors. Sim-ple, hand-screw connection with no special tools required.
Specifications for Trunk Cabling:• Max combined length approx. 1,500’• Available in lengths from 1’ to 160’ (meter or fractional
meter increments)• Available in standard and plenum rated cables
01 02 03 04 05 06 07 08 09 10 11 12Trunk ConnectorsUsed to connect drop cables to the trunk cable. Connectors available in both “Tee” and “Wye” configurations for installa-tion flexibility.
01 02 03 04 05 06 07 08 09 10 11 12Drop CableProvides power and data to the window controller. Ties into the trunk cable via the trunk connector.
Specifications for Drop Cabling:• Available in lengths from 1’ to 32.9’ (meter or fractional
meter increments)• Available in standard and plenum rated cables
01 02 03 04 05 06 07 08 09 10 11 12Window ControllerFacilitates power transmission to each IGU. Connected to a drop cable on one end and an IGU cable on the other end. Must be installed at an accessible, environmentally-controlled location. Typically one window controller is installed per IGU.
Specifications for Window Controllers:Input 24 VDCOutput Range between + 5 VDCDimensions 4-5/8” x 3/4” x 3/4”
01 02 03 04 05 06 07 08 09 10 11 12IGU CableConnects a window controller to the IGU Smart Window Connector cable.
Specifications for IGU Cabling:• Available in lengths from 1’ to 100’ (meter or fractional
meter increments)• Available in standard and plenum rated cables• Max combined length from the WC to the IGU is 100’
01 02 03 04 05 06 07 08 09 10 11 12IGU Smart Window ConnectorEach IGU receives power from the control system through an IGU Smart Window Connector. The Smart Window Connec-tor connector is embedded with a digital ID that is unique to that IGU’s dimensions and specifications.
Specifications for IGU Smart Window Connector:• ~12” length located 3” from corner. Location changes
based on shape and dimensions. See IGU data sheet for exact location.
• Requires 7/16” hole size
01 02 03 04 05 06 07 08 09 10 11 12Power Insert CableTransmits power from a power source to the trunk line via a power insert connector. The power insert cable is 14/4 wire (14-AWG/4-conductor) spool options.
For long trunk lines, power inserts may be required to provide appropriate power. The power inserts can originate from:
1. Power output ports from the control panel2. Standalone power injection panel (not shown in diagram)
Specifications for Power Insert Cabling:• Field wireable power insert cables available in up to
1,000’ spools• One power insert is typically required after every (24)
window controller connections• All power insert cables are plenum rated
01 02 03 04 05 06 07 08 09 10 11 12Trunk TerminatorInstalled at the end of each trunk line and also all unused trunk ports at the View control panel.
01 02 03 04 05 06 07 08 09 10 11 12Sky SensorUsed to detect external light and infrared levels. Data from the sensor is transmitted to the control panel for Intelligence. It is typically mounted on the roof top.
Specifications for Sky Sensor:• Connects to View control panel via CAT5 cable• Mounts to rooftop, must be clear of obstructions, 360-de-
gree view of the horizon
01 02 03 04 05 06 07 08 09 10 11 12Cell ModemUsed as a temporary network connection to the View Site Ops monitoring system. Requires 110/120VAC 60Hz.
01 02 03 04 05 06 07 08 09 10 11 12 Fiber Kit For connection of multiple control panels on a site:2 Optional Fiber-optic kits are available for network connec-tivity greater than 328’.
• Multi Mode fiber for distances greater than 328’ but less than 1500 feet.
• Single Mode fiber for distances greater than 1500 feet.• Maximum 2 Fiber Kits per Control Panel.
13 of 37 ©2019 View, Inc.Rev 6 | Aug 2019
OVERVIEW GUIDE
01
IGU
08
Power Insert Cable
04
09
Trunk Terminator10
Drop Cable
05
Window Controller
06
View ControlPanel
Power Insert Connector
8 PortDrop Box
Viewing from inside out Viewing from inside out
Illustration Purposes OnlyNot to scale
IGU Cable
07
Trunk Cable02
Sky Sensor11
Input Power100-240 VAC
View TouchDisplay
Sky Sensor
NetworkConnection
Fiber OpticConnection
Input Power110-120 VAC
Cell ModemAssembly
12
Network or Cell Modem Connection
02 03 04 05 06 07 08 09 10 11 13
IGU Smart Window Connector
Components of View Control System with Dropbox
14 of 37 ©2019 View, Inc.Rev 6 | Aug 2019
OVERVIEW GUIDE
Basic Control System Components DescriptionsCabling SystemThe View cabling system uses a trunk line/drop line net-work topology. In this topology, the trunk cable carries both power and data through the entire length of the installation. Drop cables are then tapped off of the trunk cable using trunk connectors at locations where window controllers are installed. The window controllers are then connected to individual IGU units via an IGU cable. Note: Component data sheets will supersede the information found here.
01 02 03 04 05 06 07 08 09 10 11 12Control PanelWall-mounted enclosure (21” x 29” x 9”) that contains the power supplies, master controller, as well as auxiliary con-nections such as Ethernet and external sensors. At least one control panel is required for each installation. Each control panel can support up to 256 window controllers. For larger or multi-floor installations, multiple control panels may be required. Each Control Panel requires a dedicated 20-amp circuit (20-amp@120 VAC or 10-amp @240VAC).
Specifications for Control Panel:Input AC 100-240V + 15%Frequency 50-60 Hz + 6%Output Class 2 24 VDC
01 02 03 04 05 06 07 08 09 10 11 12Trunk CablePre-terminated cables fitted with 7/8”, 5-pin connectors. Sim-ple, hand-screw connection with no special tools required.
Specifications for Trunk Cabling:• Max combined length approx. 1,500’• Available in lengths from 1’ to 160’ (meter or fractional
meter increments)• Available in standard and plenum rated cables
01 02 03 04 05 06 07 08 09 10 11 128-Port Drop BoxA network distribution component used to connect multiple Drop Cables to a Trunk Line. The distribution component will have 8 Drop Cable connection ports.
01 02 03 04 05 06 07 08 09 10 11 12Drop CableProvides power and data to the window controller. Ties into the trunk cable via the trunk connector.Specifications for Drop Cabling:• Available in lengths from 1’ to 32.9’ (meter or fractional
meter increments)• Available in standard and plenum rated cables
01 02 03 04 05 06 07 08 09 10 11 12Window ControllerFacilitates power transmission to each IGU. Connected to a drop cable on one end and an IGU cable on the other end. Must be installed at an accessible, environmentally-con-trolled location. Typically one window controller is installed per IGU.
Specifications for Window Controllers:Input 24 VDCOutput Range between + 5 VDCDimensions 4-5/8” x 3/4” x 3/4”
01 02 03 04 05 06 07 08 09 10 11 12IGU CableConnects a window controller to the IGU Smart Window Connector cable.
Specifications for IGU Cabling:• Available in lengths from 1’ to 100’ (meter or fractional
meter increments)• Available in standard and plenum rated cables• Max combined length from the WC to the IGU is 100’
01 02 03 04 05 06 07 08 09 10 11 12IGU Smart Window ConnectorEach IGU receives power from the control system through an IGU Smart Window Connector. The Smart Window Connec-tor connector is embedded with a digital ID that is unique to that IGU’s dimensions and specifications.
Specifications for IGU Smart Window Connector:• ~12” length located 3” from corner. Location changes
based on shape and dimensions. See IGU data sheet for exact location.
• Requires 7/16” hole size
01 02 03 04 05 06 07 08 09 10 11 12Power Insert CableTransmits power from a power source to the trunk line via a
power insert connector. The power insert cable is 14/4 wire (14-AWG/4-conductor) spool options.
For long trunk lines, power inserts may be required to provide appropriate power. The power inserts can originate from:
1. Power output ports from the control panel2. Standalone power injection panel (not shown in diagram)
Specifications for Power Insert Cabling:• Field wireable power insert cables available in up to
1,000’ spools• One power insert is typically required after every (24)
window controller connections• All power insert cables are plenum rated
01 02 03 04 05 06 07 08 09 10 11 12Trunk TerminatorInstalled at the end of each trunk line and also all unused trunk ports at the View control panel.
01 02 03 04 05 06 07 08 09 10 11 12Sky SensorUsed to detect external light and temperature levels. Data from the sensor is transmitted to the control panel for Intelli-gence. It is typically mounted on the roof top.
Specifications for Sky Sensor:• Connects to View control panel via CAT5 cable• Mounts to rooftop, must be clear of obstructions, 360-de-
gree view of the horizon
01 02 03 04 05 06 07 08 09 10 11 12Cell ModemUsed as a temporary network connection to the View Site Ops monitoring system. Requires 110/120VAC 60Hz.
01 02 03 04 05 06 07 08 09 10 11 12 Fiber Kit For connection of multiple control panels on a site:Two optional fiber-optic kits are available for network con-nectivity greater than 328’.
• Multi Mode fiber for distances greater than 328’ but less than 1500 feet.
• Single Mode fiber for distances greater than 1500 feet.• Maximum 2 Fiber Kits per Control Panel.
15 of 37 ©2019 View, Inc.Rev 6 | Aug 2019
OVERVIEW GUIDE
https://view.com/training
Training Videos Available
Low Voltage Systems Controls Installation Video
16 of 37 ©2019 View, Inc.Rev 6 | Aug 2019
OVERVIEW GUIDE
01P
RE
LIM
INA
RY
00.0
0.19
THA
RR
ELL
TH
VIE
W T
RA
ININ
G P
RO
JEC
T18
330
NO
THIN
G R
OA
DS
OM
EW
HE
RE
, CA
950
00
DR
AW
ING
RE
LEA
SE
SD
ES
CR
IPTI
ON
NO
.D
ATE
RE
LEA
SE
#
DR
AW
N:
DE
SIG
N:
RE
VIE
W:
ISS
UE
DA
TE:
INFO
RM
ATI
ON
®
VIEW, INC. ®195 SOUTH MILPITAS BLVD.MILPITAS, CA 95035PH: 408-263-9200WWW.VIEWGLASS.COM
PLO
T D
ATE
:
SFI
D:
VIE
W D
OC
UM
EN
T N
UM
BE
R
SH
EE
T TI
TLE
:
SHEET NUMBER:
VIEW, INC. CONFIDENTIAL:THIS DOCUMENT AND THE INFORMATIONCONTAINED IN IT ARE CONFIDENTIAL,AND CANNOT BE COPIED OR DISCLOSEDIN WHOLE OR IN PART WITHOUT THEEXPRESS WRITTEN CONSENT OFVIEW, INC. ® © - VIEW, INC.
XG-0.1
4.29
.201
9 12
:39
PM
2019
00.0
0.19
0134
0-10
133313
0067
130
THTI
TLE
SH
EE
T A
ND
SH
EE
TIN
DE
X
®
CONTRACTORSTREET ADDRESSCITY, STATE, ZIPCOUNTRY
PREPARED FOR: PROJECT:
195 SOUTH MILPITAS BLVD.MILPITAS, CA 95035
TEL 408.263.9200 FAX 408.263.9228WWW.VIEW.COM
DYNAMIC GLASS CABLE AND COMPONENTINTERCONNECT DRAWINGS
GENERAL NOTES:
01 00.00.19 PRELIMINARY
PROJECT SCOPE:
REVISION SUMMARY:
INSTALLATION: CONTROLS AND DYNAMIC GLASS INTEGRATED INTOVIEW TRAINING PROJECT .
SHEET INDEX:
XG-0.1 TITLE SHEET X . . . . . . . . . . .XG-1.1.1 SYMBOLS, LEGEND & ABBREVIATIONS XXG-1.2.1 NETWORK DIAGRAM XXG-1.3.1 ONE LINE DIAGRAM - FLOOR 1, 2 XXG-2.1.1 TRUNK LAYOUT - FLOOR 1 XXG-2.2.1 TRUNK LAYOUT - FLOOR 2 XXG-2.R SKY SENSOR LAYOUT - ROOF XXG-3.0.1 BUILDING ELEVATIONS & ZONES - NORTH, EAST XXG-3.0.2 BUILDING ELEVATIONS & ZONES - SOUTH, WEST XXG-3.1.1 ENLARGED ELEVATIONS - NORTH, EAST XXG-3.2.1 ENLARGED ELEVATIONS - SOUTH, WEST XXG-4.01 INTERCONNECT- PATTERN 1, 2, 3, 4 XXG-4.02 INTERCONNECT- PATTERN 5, 6, 7 XXG-4.03 INTERCONNECT- PATTERN 8, 9, 10, P.I. XXG-5.0.1 INSTALLATION DETAILS - SYSTEM ACCESSORIES XXG-5.0.2 INSTALLATION DETAILS - SKY SENSOR XXG-5.1.1 WINDOW CONTROL PANEL DETAILS, TYPICAL XXG-6.01 BILL OF MATERIALS XXG-7.1.1 LOADING SCHEDULE - CP 1.1 XXG-7.1.2 LOADING SCHEDULE - CP 2.1 XXG-8.1.1 TYPICAL SYSTEM LAYOUT XXG-8.2.1 GLAZIER IGU CONNECTION DIAGRAMS XXG-9.1.1 DEVICE DETAILS AND SYMBOLOGY X
XG-9.2.1 FIELD WIREABLE CONNECTIONS AND PRETERMINATEDCORDSETS X
SH
EE
T S
TATU
S:
R
= R
EV
ISE
DX
=
INC
LUD
ED
- =
NO
T IS
SU
ED
ISS
UE
DA
TE:
ISS
UE
DE
SC
RIP
TIO
N:
00.0
0.19
PR
ELI
MIN
AR
Y
IGU SCOPE QTY: 248
· CREATED INTERCONNECT· TRAINED OTHERS
1. VIEW, INC. IS NOT RESPONSIBLE FOR CONNECTION / HANDLING ERRORS BY OTHERS.2. WINDOW CONTROL PANEL(S) SHALL BE INSTALLED AT LOCATION AS SHOWN ON THE DRAWINGS.3. ALL WORK SHALL BE IN ACCORDANCE WITH ALL LOCAL, STATE AND NATIONAL CODES.4. GENERAL LAYOUT SHOWN SHALL BE FOLLOWED, EXCEPT WHERE OTHER WORK MAY CONFLICT WITH
DRAWINGS.5. ALL EXPOSED EQUIPMENT AND PANELS MOUNTED IN OR ON EXTERIOR WALL SHALL BE WEATHER
RESISTANT AND RAIN TIGHT.6. WHERE ELECTRICAL RECEPTACLES, ELECTRICAL DISTRIBUTION PANELS OR ELECTRICAL SWITCHES
ARE INDICATED, IT IS FOR THE PURPOSE OF LOCATION AND COORDINATION.7. ALL EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER RECOMMENDATIONS.8. IF CONDUIT IS REQUIRED, INSTALL BY APPLICABLE CODE AND AUTHORITY HAVING JURISDICTION (AHJ)
REQUIREMENTS. (3/4” DIA. MIN.)9. ALL SYSTEM COMPONENT LOCATIONS AND CORD SET LENGTHS SHALL BE DETERMINED AND VERIFIED
BY CONTRACTOR PRIOR TO ORDERING FROM VIEW, INC.10. INTERCONNECT DIAGRAMS ARE NOT TO SCALE.11. CORD SETS ARE PRE-TERMINATED WITH CONNECTORS. FEMALE CONNECTORS LEAD FROM WINDOW
CONTROL PANEL. MALE CONNECTORS FACE TOWARD WINDOW CONTROL PANEL. OBSERVE GENDERWHEN INSTALLING.
12. TRUNK AND POWER CABLE CONNECTORS ARE 1.06”Ø X 1 7/8” LONG. ALLOW FOR ADEQUATEPENETRATION OR CONDUIT SIZE. CABLE SIZE 7/8”Ø NOMINAL.
13. INSTALLER SHALL PROVIDE CABLE HANGERS, J-HOOK OR OPEN BRIDLE RINGS EVERY 4 FEET (MAXSPACING) TO SUPPORT TRUNK, POWER OR IGU CABLES. (1M MAXIMUM IN CANADA)
14. INSTALLER SHALL PROVIDE J-HOOK (MIN 2” LOOP) AT WALL MOUNTED WINDOW CONTROLLERLOCATIONS TO COIL SLACK IGU CABLES. DO NOT HANG SLACK FROM WINDOW CONTROLLER. NEATLYCOIL AND HANG SLACK. VELCRO WRAP PREFERRED. DO NOT PINCH CABLES.
15. ALL CONNECTIONS TO BE MADE HAND TIGHT ONLY. DO NOT USE TOOLS TO TIGHTEN CONNECTORS.16. PROVIDE GROMMETS AT FRAME PENETRATIONS TO AVOID CABLE DAMAGE. FILE ALL ROUGH
OPENINGS SMOOTH - NO SHARP EDGES. PROVIDE RELIEF CUT IN FRAMING TO AVOID DAMAGE TOCORD SET AND/OR SMART WINDOW CONNECTOR (SWC).
17. SKY SENSOR SHALL BE MAST MOUNTED ON ROOF. ELEVATE SENSOR HEIGHT AS REQUIRED TO OBTAINCLEAR LINE OF SIGHT TO HORIZON FOR OPTIMUM SYSTEM PERFORMANCE.
18. THE FOLLOWING ITEMS ARE REFERENCED IN THIS DRAWING, BUT ARE NOT INCLUDED BY VIEW INCONTRACT AND SHALL BE PROVIDED BY OTHERS:
a. E.C. SHALL PROVIDE 120VAC, 60HZ, 20 AMP DEDICATED UNSWITCHED CIRCUIT WITH GREEN WIREEARTH GROUND TO VIEW WINDOW CONTROL PANEL. CONNECTION TO CRITICAL POWER SOURCEPREFERRED TO MAINTAIN WINDOW STATE IN THE EVENT OF A POWER FAILURE. UPSTREAMFACILITY CIRCUIT BREAKER SHALL BE UL489 LISTED. DO NOT SHARE GROUND OR NEUTRALS.
b. ETHERNET, NETWORK DROPS AT ALL CONTROL PANELS - SEE NETWORK DIAGRAM FOR QTY. c. ETHERNET, (1) PoE NETWORK CABLE AT PHOTO SENSOR ON ROOF.
19. WINDOW CONTROLLERS (WC) ARE PRELABELED WITH SPECIFIC DESIGNATIONS. INSTALLER MUSTENSURE THEY ARE PLACED PER INTERCONNECT DRAWINGS.
20. IGU CABLES SHALL BE LABELED BY THE INSTALLER WITH THE "IGU" NAME TO WHICH IT IS CONNECTED.SEE DETAIL 3, SHEET XG-9.2.1 FOR FURTHER INFORMATION.
VIEW TRAINING PROJECT18330 NOTHING ROADSOMEWHERE, CA 95000
Front Page of the Interconnect Drawing
17 of 37 ©2019 View, Inc.Rev 6 | Aug 2019
OVERVIEW GUIDE
General Notes1. VIEW, INC. IS NOT RESPONSIBLE FOR CONNECTION /
HANDLING ERRORS BY OTHERS.2. WINDOW CONTROL PANEL(S) SHALL BE INSTALLED
AT LOCATION AS SHOWN ON THE DRAWINGS.3. ALL WORK SHALL BE IN ACCORDANCE WITH ALL
LOCAL, STATE AND NATIONAL CODES.4. GENERAL LAYOUT SHOWN SHALL BE FOLLOWED,
EXCEPT WHERE OTHER WORK MAY CONFLICT WITH DRAWINGS.
5. ALL EXPOSED EQUIPMENT AND PANELS MOUNTED IN OR ON EXTERIOR WALL SHALL BE WEATHER RESISTANT AND RAIN TIGHT.
6. WHERE ELECTRICAL RECEPTACLES, ELECTRICAL DISTRIBUTION PANELS OR ELECTRICAL SWITCHES ARE INDICATED, IT IS FOR THE PURPOSE OF LOCATION AND COORDINATION.
7. ALL EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER RECOMMENDATIONS.
8. IF CONDUIT IS REQUIRED, INSTALL BY APPLICABLE CODE AND AUTHORITY HAVING JURISDICTION (AHJ)REQUIREMENTS. (3/4” DIA. MIN.)
9. ALL SYSTEM COMPONENT LOCATIONS AND CORD SET LENGTHS SHALL BE DETERMINED AND VERIFIED BY CONTRACTOR PRIOR TO ORDERING FROM VIEW, INC.
10. INTERCONNECT DIAGRAMS ARE NOT TO SCALE.11. CORD SETS ARE PRE-TERMINATED WITH
CONNECTORS. FEMALE CONNECTORS LEAD FROM WINDOW CONTROL PANEL. MALE CONNECTORS FACE TOWARD WINDOW CONTROL PANEL. OBSERVE GENDER WHEN INSTALLING.
12. TRUNK AND POWER CABLE CONNECTORS ARE 1.06”Ø X 1 7/8” LONG. ALLOW FOR ADEQUATE PENETRATION OR CONDUIT SIZE. CABLE SIZE 7/8”Ø NOMINAL.
13. INSTALLER SHALL PROVIDE CABLE HANGERS, J-HOOK OR OPEN BRIDLE RINGS EVERY 4 FEET (MAX SPACING) TO SUPPORT TRUNK, POWER OR IGU CABLES. (1M MAXIMUM IN CANADA)
14. INSTALLER SHALL PROVIDE J-HOOK (MIN 2” LOOP) AT WALL MOUNTED WINDOW CONTROLLER LOCATIONS
TO COIL SLACK IGU CABLES. DO NOT HANG SLACK FROM WINDOW CONTROLLER. NEATLY COIL AND HANG SLACK. VELCRO WRAP PREFERRED. DO NOT PINCH CABLES.
15. ALL CONNECTIONS TO BE MADE HAND TIGHT ONLY. DO NOT USE TOOLS TO TIGHTEN CONNECTORS.
16. PROVIDE GROMMETS AT FRAME PENETRATIONS TO AVOID CABLE DAMAGE. FILE ALL ROUGH OPENINGS SMOOTH - NO SHARP EDGES. PROVIDE RELIEF CUT IN FRAMING TO AVOID DAMAGE TO CORD SET AND/OR SMART WINDOW CONNECTOR (SWC).
17. SKY SENSOR SHALL BE MAST MOUNTED ON ROOF. ELEVATE SENSOR HEIGHT AS REQUIRED TO OBTAIN CLEAR LINE OF SIGHT TO HORIZON FOR OPTIMUM SYSTEM PERFORMANCE.
18. THE FOLLOWING ITEMS ARE REFERENCED IN THIS DRAWING, BUT ARE NOT INCLUDED BY VIEW IN CONTRACT AND SHALL BE PROVIDED BY OTHERS:
a. E.C. SHALL PROVIDE 120VAC, 60HZ, 20 AMP DEDICATED UNSWITCHED CIRCUIT WITH GREEN WIRE EARTH GROUND TO VIEW WINDOW CONTROL PANEL. CONNECTION TO CRITICAL POWER SOURCE PREFERRED TO MAINTAIN WINDOW STATE IN THE EVENT OF A POWER FAILURE. UPSTREAM FACILITY CIRCUIT BREAKER SHALL BE UL489 LISTED. DO NOT SHARE GROUND OR NEUTRALS. b. ETHERNET, NETWORK DROPS AT ALL CONTROL PANELS - SEE NETWORK DIAGRAM FOR QTY. c. ETHERNET, (1) PoE NETWORK CABLE AT PHOTO SENSOR ON ROOF.
19. WINDOW CONTROLLERS (WC) ARE PRELABELED WITH SPECIFIC DESIGNATIONS. INSTALLER MUST ENSURE THEY ARE PLACED PER INTERCONNECT DRAWINGS.
20. IGU CABLES SHALL BE LABELED BY THE INSTALLER WITH THE “IGU” NAME TO WHICH IT IS CONNECTED. SEE DETAIL 3, SHEET XG-9.2.1 FOR FURTHER INFORMATION
18 of 37 ©2019 View, Inc.Rev 6 | Aug 2019
OVERVIEW GUIDE
Symbols, Legends and Abbreviations Used
#X##
WC-#X##
01P
RE
LIM
INA
RY
00.0
0.19
THA
RR
ELL
TH
VIE
W T
RA
ININ
G P
RO
JEC
T18
330
NO
THIN
G R
OA
DS
OM
EW
HE
RE
, CA
950
00
DR
AW
ING
RE
LEA
SE
SD
ES
CR
IPTI
ON
NO
.D
ATE
RE
LEA
SE
#
DR
AW
N:
DE
SIG
N:
RE
VIE
W:
ISS
UE
DA
TE:
INFO
RM
ATI
ON
®
VIEW, INC. ®195 SOUTH MILPITAS BLVD.MILPITAS, CA 95035PH: 408-263-9200WWW.VIEWGLASS.COM
PLO
T D
ATE
:
SFI
D:
VIE
W D
OC
UM
EN
T N
UM
BE
R
SH
EE
T TI
TLE
:
SHEET NUMBER:
VIEW, INC. CONFIDENTIAL:THIS DOCUMENT AND THE INFORMATIONCONTAINED IN IT ARE CONFIDENTIAL,AND CANNOT BE COPIED OR DISCLOSEDIN WHOLE OR IN PART WITHOUT THEEXPRESS WRITTEN CONSENT OFVIEW, INC. ® © - VIEW, INC.
XG-1.1.1
4.29
.201
9 12
:39
PM
2019
00.0
0.19
0134
0-10
133313
0067
130
THS
YM
BO
LS, L
EG
EN
D A
ND
AB
BR
EV
IATI
ON
S
REFERENCE SYMBOLS LEGEND:
KEY CODE:
INTERCONNECT ABBREVIATIONS:
INSTALLATION GENERAL NOTES:
A.F.F. ABOVE FINISHED FLOORAWG AMERICAN WIRE GAUGEBLDG BUILDINGBOM BILL OF MATERIALSCB CIRCUIT BREAKERCBL CABLECKT CIRCUITCP CONTROL PANEL(E), EX. EXISTINGEC, E.C. ELECTRICAL CONTRACTORFF FINISHED FLOORFLR FLOOR (LEVEL)Hz HERTZIDF INTERMEDIATE DISTRIBUTION FRAMEI.T. INFORMATION TECHNOLOGYIGU INSULATED GLASS UNITGS GROUND STUDLAN LOCAL AREA NETWORKLV, L.V. LOW VOLTAGE (CONTRACTOR)M8K KEYED M8 CONNECTOR(N) NEWNC NETWORK CONTROLLERNTS NOT TO SCALE
N.I.S. NOT IN SCOPEPI, P.I. POWER INSERTP.O.C. POINT OF CONNECTIONPoE POWER OVER ETHERNETPM PROJECT MANAGERPT POWER TRANSFERSHLD SHIELDSWC SMART WINDOW CONNECTORTB TERMINAL BLOCKTBD TO BE DETERMINEDVAC VOLTS ALTERNATING CURRENTvLAN VIRTUAL LOCAL AREA NETWORKWC WINDOW CONTROLLERW.I. WALL INTERFACEw IGU IDENTIFIER4P 4 PIN5P 5 PIN
1. CORDSETS ARE PRETERMINATED WITH CONNECTORS. FEMALE CONNECTORS LEAD FROMWINDOW CONTROL PANEL. MALE CONNECTORS FACE TOWARD WINDOW CONTROL PANEL.OBSERVE GENDER WHEN INSTALLING.
2. CONNECTORS ARE KEYED TO RETAIN PROPER PINOUT. OBSERVE CONNECTOR KEY ATASSEMBLY. DO NOT FORCE CONNECTION OR USE TOOLS TO TIGHTEN.
3. TRUNK AND POWER CABLE CONNECTORS ARE 1.06" Ø x 1 7/8" LONG. IGU CABLE CONNECTORSARE 0.38" Ø x 1 1/4" LONG. ALLOW FOR ADEQUATE PENETRATION / CONDUIT SIZE.
4. TRUNK CABLE SIZE 7/8" Ø NOMINAL. IGU CABLE SIZE IS 3/8" Ø NOMINAL.
5. OBSERVE MINIMUM BEND RADII TO PREVENT CONDUCTOR AND INSULATION DAMAGE.STANDARD CABLE IS 8x DIAMETER. PLENUM CABLE IS 15x DIAMETER.
CABLE TYPE: DIAMETER: MINIMUM BEND RADIUS:TRUNK, STANDARD 0.45" 3.60"TRUNK, PLENUM 0.41" 6.15"IGU/DROP, STANDARD 0.31" 2.50"IGU/DROP, PLENUM 0.25" 3.75"
6. TRUNK CABLE AND POWER INSERT CABLE NAMES ARE SHOWN FOR REFERENCE TO TRACECABLE PATHS FROM END TO CONTROL PANEL. REFER TO ONE LINE DIAGRAMS FOR SPECIFICPORTS ON THE CONTROL PANEL TO CONNECT TO.
7. CONNECTION ORDER OF WINDOW CONTROLLER WITHIN GROUPS OF TEES OR ON DB-8BLOCKS DOES NOT MATTER. CONNECTION LOCATION RELATIVE TO POWER INSERT POINTSDOES MATTER. REFER TO ONE LINE DIAGRAMS FOR QUANTITY OF WINDOW CONTROLLERSWITHIN A POWER SESSION.
8. WINDOW CONTROLLER NAMES MUST BE MATCHED TO THE IGU THEY ARE CONNECTED TO.LABELING OF IGU CABLES IS RECOMMENDED TO AID IN PROPER INSTALLATION.
1XG-X.X.X
ELEVATION OR SECTIONORIENTATION
REFERENCE NUMBER
SHEET NUMBER
1XG-X.X.X
1XG-X.X.X
DETAIL LOCATION
DETAIL NUMBER
SHEET NUMBER
KEYED NOTE NUMBER
WINDOW FRAME ID NUMBER
11.01
A1
1
#-# BOM REFERENCE NUMBERREFER TO "FIND" COLUMN
INTERCONNECT PATTERN NUMBER
PATTERN - FLOOR . INSTANCE
1 REFERENCE TAG NUMBERREFER TO TABLE ON SAME SHEET
# X ##
TRUNK CABLE, 7/8" 5-PIN CONNECTORS
TRUNK CABLE- PLENUM, 7/8" 5-PIN CONNECTORS
POWER INSERT CABLE, 4-PIN CONNECTORS(FIELD TERMINATED)
WINDOW CONTROL PANEL, MAXIMUM 128 WINDOW CONTROLLERS (2 TRUNKS, 6 POWER INSERTS)
WINDOW CONTROL PANEL, MAXIMUM 256 WINDOW CONTROLLERS
ENTERPRISE MASTER SERVER(RACK MOUNT, OPTION FOR LARGER PROJECTS >2,000 ZONES)
DROP CABLE, M8 MALE, M12 FEMALE CONNECTORS
DROP CABLE- PLENUM, M8 MALE, M12 FEMALE CONNECTORS
IGU CABLE, M8 CONNECTORS
IGU CABLE- PLENUM, M8 CONNECTORS
LARGE CONNECTOR - TRUNK TEE
LARGE CONNECTOR - TRUNK WYE - MALE
LARGE CONNECTOR - TRUNK WYE - FEMALE
LARGE CONNECTOR - TRUNK 90 DEGREE ELBOW
LARGE CONNECTOR - TRUNK TERMINATOR
LARGE CONNECTOR - POWER INSERT TEE
LARGE CONNECTOR - POWER INSERT WYE
WINDOW CONTROLLER, BASE, v2.0
CAT6 NETWORK CABLE (NOT BY VIEW)
FIBER OPTIC CABLE, MULTI-MODE (NOT BY VIEW)
FIBER OPTIC CABLE, SINGLE MODE (NOT BY VIEW)
DATA CONNECTION (NOT BY VIEW)
DEVICENET DROP BOX, 8 - PORT - INSTALL PROTECTIVECAPS (P/N: 050-101183) ON ALL UNUSED PORTS
WALL INTERFACE, ASSEMBLY
SKY PHOTO SENSOR (PoE DEVICE) - E.C. TO PROVIDE CAT5E (ORGREATER) CABLE FROM NEAREST CONTROL PANEL LOCATION TOROOF OR DEVICE MOUNTING LOCATION (100 M MAXIMUM)
CABLE TRANSFER, SLIDING(INSTALLATION KIT ALSO PROVIDED)
CABLE TRANSFER, SPRING CONDUIT(VERIFY FINISH AND SIZE)
CABLE TRANSFER, CONCEALED(VERIFY FINISH)
CABLE TRANSFER, ARMORED DOOR LOOP(VERIFY FINISH AND SIZE)
WIRELESS ACCESS POINT (WAP)
REMOTE POWER INSERT BOX
CELL MODEM
#X##
IGU LABELINGWINDOW CONTROLLER NAME
FLOOR NUMBER (LEVEL) FACADE ORIENTATION (N, E, S, W)WINDOW COUNT
IGU LABEL / WINDOWCONTROLLER NAME
IGU SMART WINDOWCONNECTOR (SWC) LOCATION(3" FROM CORNER)
IGU CONNECTOR (M8 FEMALE)
WINDOW CONTROLLER NAME
IGU CONNECTOR (M8 MALE)
INTERCONNECT SYMBOLS LEGEND:
FIND LABEL (BOM) SYMBOL DESCRIPTIONDIAGRAM SYMBOLSHOWN ON PLANS
WT
PI
WT
MALE
CAT6 CAT6
F/O mm F/O mm
CP #.#
CP #.#
CONNECTION POINTFIXED LENGTH
F/O sm F/O sm
WTPI PI
MALE FEMALE
FEMALEMALE
MALE FEMALE
FEMALE
FEMALE
FEMALE
FEMALE
MALE
MALE
MALE
MALE
MALE FEMALE
MALE
MALE
FEMALE
FEMALE
EIC-1
REFERENCE BORDER:
· AREA OF PATTERN· AREA OF CONTROL ZONE· LOCATION OF AUXILIARY
ELEVATION
10XG-9.1.1
DETAIL REFERENCE
11XG-9.1.1
1 - 4XG-5.0.4
1XG-5.1.1
4XG-9.1.1
6XG-9.1.1
5XG-9.1.1
2XG-9.1.1
8XG-9.1.1
7XG-9.1.1
3XG-9.1.1
12XG-9.1.1
1XG-9.1.1
2XG-5.0.1
1XG-5.0.3
1 - 3XG-5.0.2
9XG-9.1.1
CONNECTION POINT
2XG-9.2.1
MALE
1XG-5.0.1PWR
24V
CELL (US)
WAP
W.I.
3XG-5.0.1
1'0"
1'0" P
CBL-14/4P
CP2-128N
CP2-256N
EIC-1
1'0"
1'0" P
1'0"
1'0" P
LC-1
LC-2
LC-3
LC-4
LT-M
PT-1
PY-1
WC-B
DB-8
WI-K
SSA
PB-2
CP-ME
SC6-A
DPT-A
SICM-1
DL-A18
WAP-W
# X ##
FLOOR NUMBER (LEVEL) FACADE ORIENTATION (N, E, S, W)WINDOW COUNT
MALEFEMALE
19 of 37 ©2019 View, Inc.Rev 6 | Aug 2019
OVERVIEW GUIDE
Detail Example2
XG
-3.1
.1
2X
G-3
.2.1
1X
G-3
.2.1
1X
G-3
.1.1
3--
4--
2E37
2E36
2E35
2E34
2E33
2E32
2E31
2E30
2E29
2E28
2E27
2E26
2E25 2E24 2E22
2E23 2E21
2E20
2E19
2E18
2E17
2E16
2E15
2E14
2E13
2E12
2E11
2E10
2E09
2E08
2E07
2E06
2E05
2E04
2E03
2E02
2E01
1E22 1E20 1E18 1E16 1E14 1E12 1E10 1E08 1E06 1E04 1E02
1E21 1E19 1E17 1E15 1E13 1E11 1E09 1E07 1E05 1E03 1E01
1E26
1E25
1E241E
23
XW15
XW14
XW13
XW12
XW11
XW10
XW09
XW08
XW07
XW06
XW05
XW04
XW03
XW02
XW01
XE
06
XE
04
XE
02
XE
05
XE
03
XE
01
2N13
1N13
2N12
1N12
2N11
1N11
2N10
1N10
2N09
1N09
2N48
2N47
1N55
1N54
2N46
2N45
1N53
1N52
2N42
2N41
1N48
1N47
2N40
2N39
1N46
1N45
2N38
2N37
1N44
1N43
2N36
2N35
1N42
1N41
2N34
2N33
1N40
1N39
2N32
2N31
1N38
1N37
2N30
2N29
1N36
2N28
2N27
1N33
1N32
2N26
2N25
1N31
1N30
2N24
2N23
1N28
1N27
1N29
2N22
2N21
1N25
1N24
1N26
2N20 2N19 2N17
2N16
1N18
1N17
1N19
2N15
2N14
1N15
1N14
1N16
1N51
2N44
2N43 2N18
1N23
1N22
1N21 1N201N35
1N34
1N50
1N49
2N08
2N07
2N06
2N05
2N04
2N03
2N02
2N01
1N08
1N07
1N06
1N05
1N04
1N03
1N02
1N01
WT WT WT WT WT WT WT WT WT WT WT WT
WT WT WT WT WT WT WT WT WT WT WT WT WT WT WT WT WT WT WT WT WT WT WT WT
WT WT WT
WTWTWTWTWTWTWTWTWTWTWT
WT WT WT WT WT WT WT WT WT WT WT WT WTWTWTWTWTWTWTWTWTWTWTWTWTWTWTWT
WTWTWTWTWTWTWTWTWTWTWTWT
LT-M
LT-M
LT-M
LT-M
TRUNK 1.1B
TRUNK 2.1B TRUNK 2.1A
TRUNK 1.1A
TRUNK 2.1A
TRUNK 1.1A
TRUNK 2.1ATRUNK 2.1BTRUNK 2.1C
TRUNK 1.1B
P.I. 1.1A
P.I. 1.1C
P.I. 2.1D P.I. 2.1A P.I. 2.1B P.I. 2.1C
P.I. 2.1F P.I. 2.1E
P.I. 1.1B
102.01
102.03
102.04
82.07
82.08
82.06
82.05
82.04
52.01
62.01
52.02
12.01
12.02
12.03
31.01
11.01
41.01
81.07
81.08
81.06
81.05
81.04
101.01
101.02
101.03
101.04
11.03
11.02
21.01
12.04
12.05
12.06
92.01
92.02
92.03
92.04
82.01
81.01
81.02
81.03
82.01
82.02
82.03
72.01
2XG-4.03
2XG-4.01
1XG-4.01
102.02
3XG-4.02
3XG-4.01
4XG-4.01
2XG-4.02
1XG-4.02
1XG-4.03
3XG-4.03
01P
RE
LIM
INA
RY
00.0
0.19
THA
RR
ELL
TH
VIE
W T
RA
ININ
G P
RO
JEC
T18
330
NO
THIN
G R
OA
DS
OM
EW
HE
RE
, CA
950
00
DR
AW
ING
RE
LEA
SE
SD
ES
CR
IPTI
ON
NO
.D
ATE
RE
LEA
SE
#
DR
AW
N:
DE
SIG
N:
RE
VIE
W:
ISS
UE
DA
TE:
INFO
RM
ATI
ON
®
VIEW, INC. ®195 SOUTH MILPITAS BLVD.MILPITAS, CA 95035PH: 408-263-9200WWW.VIEWGLASS.COM
PLO
T D
ATE
:
SFI
D:
VIE
W D
OC
UM
EN
T N
UM
BE
R
SH
EE
T TI
TLE
:
SHEET NUMBER:
VIEW, INC. CONFIDENTIAL:THIS DOCUMENT AND THE INFORMATIONCONTAINED IN IT ARE CONFIDENTIAL,AND CANNOT BE COPIED OR DISCLOSEDIN WHOLE OR IN PART WITHOUT THEEXPRESS WRITTEN CONSENT OFVIEW, INC. ® © - VIEW, INC.
XG-3.1.1
4.29
.201
9 12
:40
PM
2019
00.0
0.19
0134
0-10
133313
0067
130
THE
NLA
RG
ED
ELE
VA
TIO
N -
NO
RTH
, EA
ST
SCALE:1 ELEVATION - NORTH3/16" = 1'-0"
SCALE:2 ELEVATION - EAST3/16" = 1'-0" SCALE:3 AUX. ELEV. - WEST
3/16" = 1'-0" SCALE:4 AUX. ELEV. - EAST3/16" = 1'-0"
20 of 37 ©2019 View, Inc.Rev 6 | Aug 2019
OVERVIEW GUIDE
Detail Example 2
INTE
RC
ON
NE
CT
DIA
GR
AM
-P
ATT
ER
N 1
, 2, 3
, 4
PATTERN 1PART # FIND DESCRIPTION QTY ROUTING
370-000024 DB-8 DEVICENET DROP BOX, 8-PORT, LC5P-M/F, M5P-F 1 046010-101584 WC-B ASSEMBLY, 2.0 WINDOW CONTROLLER 8 061
380-101510-02 D-2'0"P DROP CABLE, PLENUM, MED CONN, 5P M, SML CONN, 5PK F, 2' 0" (0.6M) 8 334380-101509-03 I-3'3"P IGU CABLE, PLENUM, SML CONN, 5PK MF, 3' 3" (1M) 4 462380-101509-06 I-8'2"P IGU CABLE, PLENUM, SML CONN, 5PK MF, 8' 2" (2.5M) 4 465380-101509-02 I-2'0"P IGU CABLE, PLENUM, SML CONN, 5PK MF, 2' 0" (0.6M) 4 561380-101509-10 I-14'9"P IGU CABLE, PLENUM, SML CONN, 5PK MF, 14' 9" (4.5M) 4 569
PATTERN 2PART # FIND DESCRIPTION QTY ROUTING
370-000002 LC-1 TEE, LRG CONN 5P-F, LRG CONN 5P-M, MED CONN 5P-F 2 041370-000024 DB-8 DEVICENET DROP BOX, 8-PORT, LC5P-M/F, M5P-F 1 046010-101584 WC-B ASSEMBLY, 2.0 WINDOW CONTROLLER 10 061
380-000038-03 T-3'3"P TRUNK CABLE, PLENUM, LRG CONN, 5P MF, 3' 3" (1M) 1 140380-101510-02 D-2'0"P DROP CABLE, PLENUM, MED CONN, 5P M, SML CONN, 5PK F, 2' 0" (0.6M) 10 334380-101509-03 I-3'3"P IGU CABLE, PLENUM, SML CONN, 5PK MF, 3' 3" (1M) 4 462380-101509-06 I-8'2"P IGU CABLE, PLENUM, SML CONN, 5PK MF, 8' 2" (2.5M) 2 465380-101509-08 I-11'5"P IGU CABLE, PLENUM, SML CONN, 5PK MF, 11' 5" (3.5M) 4 467380-101509-02 I-2'0"P IGU CABLE, PLENUM, SML CONN, 5PK MF, 2' 0" (0.6M) 5 561380-101509-05 I-6'6"P IGU CABLE, PLENUM, SML CONN, 5PK MF, 6' 6" (2M) 2 564380-101509-08 I-11'5"P IGU CABLE, PLENUM, SML CONN, 5PK MF, 11' 5" (3.5M) 1 567380-101509-10 I-14'9"P IGU CABLE, PLENUM, SML CONN, 5PK MF, 14' 9" (4.5M) 3 569010-101596-01 DPT-A ASM, TRANSITION, POWER TRANSFER, CONCEALED, ALUMINUM, M8K 1 601
PATTERN 3PART # FIND DESCRIPTION QTY ROUTING
370-000002 LC-1 TEE, LRG CONN 5P-F, LRG CONN 5P-M, MED CONN 5P-F 1 041370-000024 DB-8 DEVICENET DROP BOX, 8-PORT, LC5P-M/F, M5P-F 1 046010-101584 WC-B ASSEMBLY, 2.0 WINDOW CONTROLLER 9 061
380-000038-03 T-3'3"P TRUNK CABLE, PLENUM, LRG CONN, 5P MF, 3' 3" (1M) 1 140380-101510-02 D-2'0"P DROP CABLE, PLENUM, MED CONN, 5P M, SML CONN, 5PK F, 2' 0" (0.6M) 9 334380-101509-03 I-3'3"P IGU CABLE, PLENUM, SML CONN, 5PK MF, 3' 3" (1M) 5 462380-101509-06 I-8'2"P IGU CABLE, PLENUM, SML CONN, 5PK MF, 8' 2" (2.5M) 4 465380-101509-02 I-2'0"P IGU CABLE, PLENUM, SML CONN, 5PK MF, 2' 0" (0.6M) 3 561380-101509-05 I-6'6"P IGU CABLE, PLENUM, SML CONN, 5PK MF, 6' 6" (2M) 4 564380-101509-10 I-14'9"P IGU CABLE, PLENUM, SML CONN, 5PK MF, 14' 9" (4.5M) 3 569010-101596-01 DPT-A ASM, TRANSITION, POWER TRANSFER, CONCEALED, ALUMINUM, M8K 2 601
PATTERN 4PART # FIND DESCRIPTION QTY ROUTING
370-000002 LC-1 TEE, LRG CONN 5P-F, LRG CONN 5P-M, MED CONN 5P-F 1 041370-000024 DB-8 DEVICENET DROP BOX, 8-PORT, LC5P-M/F, M5P-F 1 046010-101584 WC-B ASSEMBLY, 2.0 WINDOW CONTROLLER 9 061
380-000038-03 T-3'3"P TRUNK CABLE, PLENUM, LRG CONN, 5P MF, 3' 3" (1M) 1 140380-101510-02 D-2'0"P DROP CABLE, PLENUM, MED CONN, 5P M, SML CONN, 5PK F, 2' 0" (0.6M) 9 334380-101509-03 I-3'3"P IGU CABLE, PLENUM, SML CONN, 5PK MF, 3' 3" (1M) 4 462380-101509-06 I-8'2"P IGU CABLE, PLENUM, SML CONN, 5PK MF, 8' 2" (2.5M) 5 465380-101509-02 I-2'0"P IGU CABLE, PLENUM, SML CONN, 5PK MF, 2' 0" (0.6M) 3 561380-101509-05 I-6'6"P IGU CABLE, PLENUM, SML CONN, 5PK MF, 6' 6" (2M) 4 564380-101509-10 I-14'9"P IGU CABLE, PLENUM, SML CONN, 5PK MF, 14' 9" (4.5M) 3 569010-101596-01 DPT-A ASM, TRANSITION, POWER TRANSFER, CONCEALED, ALUMINUM, M8K 2 601
#X##
#X##
#X##
#X##
#X##
#X##
#X##
#X##
#X##
#X##
WTWTWTWTTO NEXTPATTERNSEE PLAN
WTWTWTWTTO CP
FROM PREV.PATTERNSEE PLAN
#X##
#X##
#X##
#X##
#X##
#X##
DB-8
2'0"P(x4)
WC-B(x4)
2'0"P
WC-BNOTES:1. CAP UNUSED PORTS ON WITH .2. CONNECT WINDOW CONTROLLERS TO
DB-8 PORTS IN ORDER THAT WILLPROVIDE THE CLEANEST INSTALL.
DB-8CAP-M-2
14'9" P
2'0"P
14'9" P
2'0"P
14'9" P
2'0"P
14'9" P
2'0"P
8'2"P(x2)
3'3" P(x2)
3'3" P(x2)
8'2"P(x2)
(x4)
(x4)
L.V.GLAZIER
L.V.GLAZIER
1E23
DPT-A
6'6"P
1E22
1E21
1E20
1E19
1E18
1E17
1E26
1E25
1E24
WT WT WT
LC-1
WT WT WTTO CP
FROM PREV.PATTERNSEE PLAN
(x2)
1E26
2'0"P
WC-B
1E25
(x2)
(x2)
1E23
1E24
1E22
1E21
NOTES:1. CAP UNUSED PORTS ON WITH .2. CONNECT WINDOW CONTROLLERS TO
DB-8 PORTS IN ORDER THAT WILLPROVIDE THE CLEANEST INSTALL.
DB-8CAP-M-21E
201E
19
2'0"P(x4)
WC-B(x4)
WT WT WT WTTO NEXTPATTERNSEE PLAN
DB-83'3"P
14'9" P
2'0"P
14'9" P
2'0"P
14'9" P
2'0"P2'0"P
2'0"P
6'6"P
11'5" P
3'3" P(x2)
3'3" P(x2)
1E18
1E17
2'0"P(x4)
WC-B(x4)
8'2"P(x2)
11'5" P(x4)
L.V.GLAZIER
L.V.GLAZIER
1N50 1N49
DPT-A
6'6"P
1N55
1N54
1N53
1N52
1N48
1N47
1N51
1N54
1N53
1N52
1N50
1N51
1N49
2'0"P(x4)
WC-B(x4)
DB-8
WT WT WT WTTO NEXTPATTERNSEE PLAN
LC-1
WT WTTO CP
FROM PREV.PATTERNSEE PLAN
1N55
WT WT WT
3'3"P
2'0"P
WC-BNOTES:1. CAP UNUSED PORTS ON WITH .2. CONNECT WINDOW CONTROLLERS TO
DB-8 PORTS IN ORDER THAT WILLPROVIDE THE CLEANEST INSTALL.
DB-8CAP-M-2
1N48
1N47
2'0"P(x4)
WC-B(x4)
8'2"P(x2)
6'6"P 6'6"P6'6"P2'0"P 2'0"P 2'0"P
14'9" P14'9" P
DPT-A
8'2"P(x2)
3'3"P(x3)
3'3"P(x2)
14'9" P
L.V.GLAZIER
L.V.GLAZIER
1N35 1N34
DPT-A
1N38
1N37
1N33
1N32
1N31
1N30
1N36
1N37
1N35
1N36
1N34
1N33
1N32
2'0"P(x4)
WC-B(x4)
DB-8
WT WT WT WTTO NEXTPATTERNSEE PLAN
LC-1
WT WTTO CP
FROM PREV.PATTERNSEE PLAN
WT WT WT
3'3"P
2'0"P
NOTES:1. CAP UNUSED PORTS ON WITH .2. CONNECT WINDOW CONTROLLERS TO
DB-8 PORTS IN ORDER THAT WILLPROVIDE THE CLEANEST INSTALL.
DB-8CAP-M-2
1N31
1N30
2'0"P(x4)
WC-B(x4)
8'2"P(x2)
2'0"P
14'9" P
1N38WC-B
2'0"P
14'9" P
6'6"P
DPT-A
6'6"P 6'6"P6'6"P2'0"P
14'9" P
8'2"P(x3)
3'3" P(x2)
3'3"P(x2)
L.V.GLAZIER
L.V.GLAZIER
SCALE:1 INTERCONNECT, PATTERN 1 ; THUS 9NONE SCALE:2 INTERCONNECT, PATTERN 2 ; THUS 1
NONE
SCALE:3 INTERCONNECT, PATTERN 3 ; THUS 1NONE SCALE:4 INTERCONNECT, PATTERN 4 ; THUS 1
NONE
L.V
.G
LAZI
ER
L.V
.G
LAZI
ER
L.V
.G
LAZI
ER
L.V
.G
LAZI
ER
01P
RE
LIM
INA
RY
00.0
0.19
THA
RR
ELL
TH
VIE
W T
RA
ININ
G P
RO
JEC
T18
330
NO
THIN
G R
OA
DS
OM
EW
HE
RE
, CA
950
00
DR
AW
ING
RE
LEA
SE
SD
ES
CR
IPTI
ON
NO
.D
ATE
RE
LEA
SE
#
DR
AW
N:
DE
SIG
N:
RE
VIE
W:
ISS
UE
DA
TE:
INFO
RM
ATI
ON
®
VIEW, INC. ®195 SOUTH MILPITAS BLVD.MILPITAS, CA 95035PH: 408-263-9200WWW.VIEWGLASS.COM
PLO
T D
ATE
:
SFI
D:
VIE
W D
OC
UM
EN
T N
UM
BE
R
SH
EE
T TI
TLE
:
SHEET NUMBER:
VIEW, INC. CONFIDENTIAL:THIS DOCUMENT AND THE INFORMATIONCONTAINED IN IT ARE CONFIDENTIAL,AND CANNOT BE COPIED OR DISCLOSEDIN WHOLE OR IN PART WITHOUT THEEXPRESS WRITTEN CONSENT OFVIEW, INC. ® © - VIEW, INC.
XG-4.01
4.29
.201
9 12
:40
PM
2019
00.0
0.19
0134
0-10
133313
0067
130
TH
WINDOW CONTROLLERSMUST BE INSTALLED AT ANACCESSIBLE, ENVIRON-MENTALLY -CONTROLLEDLOCATION
21 of 37 ©2019 View, Inc.Rev 6 | Aug 2019
OVERVIEW GUIDE
Trunk Line Layout Example
POWER INSERT 2.1-1
POWER INSERT 2.1-2
POWER INSERT 2.1-3
POWER INSERT 2.1-4
POWER INSERT 2.1-5
POWER INSERT 2.1-6
POWER INSERT 2.1-7
TRUNK 2.1A
TRUNK 2.1B
TRUNK 2.1C
TRUNK 2.1D
1XG-3.1.1
2X
G-3
.2.1
2X
G-3
.1.1
1XG-3.2.1
WT
WT
WT
WT
WT WT WT WT WT WT
WT
WT
WT
WT
WT
WT
WT
WT
WT
WT
WT
WT
WT
WT WT WT WT WT
WT
WT WT WT
WT
WT
WT
WT
WT
WT
WT
WT
WT
WT
WT
WT
WT
WT
WT
WT
WT
WT
WT
WT
WT
WT
WT
WT
WT WT WT WT WT WT WT WT WT WT WTW
TW
TW
TW
TW
TW
TW
TW
T
92.15
92.14
92.13
92.12
92.11
92.10
92.09
92.08
92.07
92.06
92.05
102.12
102.11
102.10
102.09
102.08
102.07
102.06
102.05
102.01
102.02
102.03
102.04
82.07
82.08
82.06
82.05
82.04
82.01
82.02 8
2.03
72.01
52.01
62.01
52.02
12.01
12.02
12.03
12.04
12.05
12.06
92.01
92.02
92.03
92.04
82.01
4 LT-M
4LT-M
4LT-M
4 LT-M
CP2-256N
1XG-5.1.1
1
WINDOW CONTROLPANEL CP 2.1 2 3
PI PI PI PI PI PI PI PI PI PI PI PI PI PI PI PI
PI
PI
PI
PI
PI
PI
PIPIPIPIPIPIPI
PI
PI
PI
PI
PI
PI
PI
PI
PI
PI
PI
PI
PI
PI
PI
PI
PI
PIPIPI
PI
PI
PI
PI
PI
PI
PI
PI
PI
PI
PIPIPIPIPI
PI
PI
PI
PI
PI
PI
PI
PI
PI
PI
PIPIPIPIPI
PI
PIPI
PI
PI
PI
PI
PI
PI
PI
PI
PI
PI
PI
PI
PI
PI
PI PI PI PI PI PI PI PI PI
PI
PI
PI
PI
PI
PI
PI
PI
PI
PI
PI
PI
PI
PI
PI PI PI PI PI PI PI PI PI PI PIP
IP
IP
IP
I
4'11"P
4'11"P
4'11"P
4'11"P
4'11
"P
4'11
"P
4'11
"P
4'11
"P
4'11"P
4'11
"P
4'11
"P
4'11
"P
4'11
"P
4'11
"P
32'9
"P8'
2"P
8'2"P
8'2"P
19'8" P
4'11"P
4'11"P
19'8" P
9'10" P
6'6"P
4'11
"P
4'11
"P
4'11
"P
4'11"P
4'11"P
8'2"P
4'11
"P
4'11
"P
4'11
"P
4'11
"P
14'9" P
4'11"P
9'10
"P
9'10
"P
98'5"P
98'5"P
65'7"P
65'7"P
24'7"P 24'7"P21'3"P
24'7"P
26'2"P
CP 2.1
TRUNK 2.1A
TRUNK 2.1B
TRUNK 2.1C
TRUNK 2.1D
FIELD TERMINATED POWER INSERT. SEE DETAIL 2XG-9.2.1
01P
RE
LIM
INA
RY
00.0
0.19
THA
RR
ELL
TH
VIE
W T
RA
ININ
G P
RO
JEC
T18
330
NO
THIN
G R
OA
DS
OM
EW
HE
RE
, CA
950
00
DR
AW
ING
RE
LEA
SE
SD
ES
CR
IPTI
ON
NO
.D
ATE
RE
LEA
SE
#
DR
AW
N:
DE
SIG
N:
RE
VIE
W:
ISS
UE
DA
TE:
INFO
RM
ATI
ON
®
VIEW, INC. ®195 SOUTH MILPITAS BLVD.MILPITAS, CA 95035PH: 408-263-9200WWW.VIEWGLASS.COM
PLO
T D
ATE
:
SFI
D:
VIE
W D
OC
UM
EN
T N
UM
BE
R
SH
EE
T TI
TLE
:
SHEET NUMBER:
VIEW, INC. CONFIDENTIAL:THIS DOCUMENT AND THE INFORMATIONCONTAINED IN IT ARE CONFIDENTIAL,AND CANNOT BE COPIED OR DISCLOSEDIN WHOLE OR IN PART WITHOUT THEEXPRESS WRITTEN CONSENT OFVIEW, INC. ® © - VIEW, INC.
XG-2.2.1
4.29
.201
9 12
:39
PM
2019
00.0
0.19
E.C. TO PROVIDE60Hz, DEDICATED 20 AMPCKT. CRITICAL POWERSOURCE PREFERRED.
E.C. TO PROVIDEETHERNET DROP(S) ATWINDOW CONTROLPANEL LOCATION - SEENETWORK DIAGRAM.
(1) ETHERNET DROP ATWINDOW CONTROLPANEL TO CONNECT TORING SENSORLOCATION.
TRUNK TERMINATOR -INSTALL IN ACCESSIBLELOCATION
KEY NOTES
1
2
3
4
0134
0-10
133313
0067
130
THTR
UN
K L
AY
OU
T -
FLO
OR
2
SCALE:1 TRUNK LAYOUT - FLOOR 23/16" = 1'-0"
E.C. TO PROVIDE 120VAC,
CKT. CRITICAL POWERSOURCE PREFERRED.
E.C. TO PROVIDEETHERNET DROP(S) ATWINDOW CONTROLPANEL LOCATION - SEENETWORK DIAGRAM.
(1) ETHERNET DROP ATWINDOW CONTROLPANEL TO CONNECT TORING SENSORLOCATION.
TRUNK TERMINATOR -INSTALL IN ACCESSIBLELOCATION
KEY NOTES
1
2
3
4
22 of 37 ©2019 View, Inc.Rev 6 | Aug 2019
OVERVIEW GUIDE
One-Line Diagram Example
01P
RE
LIM
INA
RY
00.0
0.19
THA
RR
ELL
XX
XX
XX
XX
SIT
E N
AM
EB
UIL
DIN
GS
TRE
ET
AD
DR
ES
SC
ITY
, STA
TE 0
0000
DR
AW
ING
RE
LEA
SE
SD
ES
CR
IPTI
ON
NO
.D
ATE
RE
LEA
SE
#
DR
AW
N:
DE
SIG
N:
RE
VIE
W:
ISS
UE
DA
TE:
INFO
RM
ATI
ON
®
VIEW, INC. ®195 SOUTH MILPITAS BLVD.MILPITAS, CA 95035PH: 408-263-9200WWW.VIEWGLASS.COM
PLO
T D
ATE
:
SFI
D:
VIE
W D
OC
UM
EN
T N
UM
BE
R
SH
EE
T TI
TLE
:
SHEET NUMBER:
VIEW, INC. CONFIDENTIAL:THIS DOCUMENT AND THE INFORMATIONCONTAINED IN IT ARE CONFIDENTIAL,AND CANNOT BE COPIED OR DISCLOSEDIN WHOLE OR IN PART WITHOUT THEEXPRESS WRITTEN CONSENT OFVIEW, INC. ® © - VIEW, INC.
XG-1.3.1
4.29
.201
9 12
:39
PM
2019
00.0
0.19
E.C. TO PROVIDE 120VAC60Hz, DEDICATED 20 AMPCKT. CRITICAL POWERSOURCE PREFERRED.
E.C. TO PROVIDEETHERNET DROP(S) ATWINDOW CONTROLPANEL LOCATION - SEENETWORK DIAGRAM.
(1) ETHERNET DROP ATWINDOW CONTROLPANEL TO CONNECT TORING SENSORLOCATION.
TRUNK TERMINATOR -INSTALL IN ACCESSIBLELOCATION
KEY NOTES
1
2
3
4
0134
0-10
1#####
####
##
XX
XX
XX
XX
ON
E L
INE
DIA
GR
AM
-FL
OO
R 1
, 2
SCALE:1 TRUNK LAYOUT - CP 1.1NONE
SCALE:2 TRUNK LAYOUT - CP 2.1NONE
PI
PI
PI PI PI PI PI
PI
PI PI PI
WT
WT WT WT WT WT WT
10 WC 8 WC
4
1 2
9 WC 9 WCWINDOW CONTROLPANEL
CP 1.1
WT
WTWTWTWTWTWTWTWTWTWTWTWTWTWT
4
PI
PIPIPIPIPIPIPIPI
P.I. 1.1-1
2 WC 1 WC
TRUNK 1.1BTRUNK 1.1AP.I. 1.1-2 P.I. 1.1-3
31.01
11.01
41.01
81.07
81.08
81.06
81.05
81.04
81.01
81.02
81.03
101.01
101.02
101.03
101.04
101.10
101.09
101.08
101.07
101.06
101.05
11.03
11.02
21.01
92.15
92.14
92.13
92.12
92.11
92.10
92.09
92.08
92.07
92.06
92.05
102.12
102.11
102.10
102.09
102.08
102.07
102.06
102.05
102.01
102.02
102.03
102.04
82.07
82.08
82.06
82.05
82.04
82.01
82.02
82.03
72.01
52.01
62.01
52.02
12.01
12.02
12.03
12.04
12.05
12.06
92.01
92.02
92.03
92.04
82.01
PI
PI
PI PI PI PI
PI
PI PI
WT
WT
WT
WT
WT WT WT WT WT WT WT WT WT
WT
WT WT WT WT WT
4
1 2
4
WINDOW CONTROLPANEL
CP 2.1
WT
WT
WT
WT
WTWTWTWTWTWTWTWTWTWTWTWTWTWT
WT
WTWTWTWTWTWTWTWTWTWTWTWTWTWT
4
4P
IP
I
PIPIPIPI
PI
PIPI
P.I. 2.1-1
PI
PI
PIPIPIPIPIPI
P.I. 2.1-2P.I. 2.1-3
1 WCP
I
PI PI PI PI PI PI
P.I. 2.1-7P
I
PIPIPIPIPIPIPIPI
15 WC 10 WC 7 WC
3 WC
TRUNK 2.1BTRUNK 2.1A
TRUNK 2.1DTRUNK 2.1C
P.I. 2.1-4 P.I. 2.1-5
P.I. 2.1-6
8 WC 8 WC2 WC2 WC2 WC2 WC2 WC2 WC2 WC2 WC2 WC 1 WC 1 WC 1 WC 1 WC 1 WC 1 WC 1 WC
TRUNK SCHEDULEFLOOR 1, CP 1.1
DESC: POWER INSERT (FT) TRUNK (FT) WC QTYTRUNK 1.1A 0 193.3 12
PI 1.1-1 178 88.2 16TRUNK 1.1B 0 183.6 18
PI 1.1-2 163 47.5 17PI 1.1-3 197 26.1 17TOTAL 538 538.7 80
CONNECTION J3-J8, J11-J16 J9, J10
TRUNK SCHEDULEFLOOR 2, CP 2.1
DESC: POWER INSERT (FT) TRUNK (FT) WC QTYTRUNK 2.1A 0 111.5 10
PI 2.1-1 109 18 17PI 2.1-2 120 22.9 16PI 2.1-3 138 67 15
TRUNK 2.1B 0 147.6 16PI 2.1-4 156 45.9 16PI 2.1-5 193 26.1 16TOTAL 716 439 106
CONNECTION J3-J8, J11-J16 J9, J10TRUNK 2.1C 0 127.6 16
PI 2.1-6 104 40.8 12TRUNK 2.1D 0 170.1 18
PI 2.1-7 150 101.3 16TOTAL 254 439.8 62
CONNECTION J3-J8, J11-J16 J1, J2CP TOTAL 970 878.8 168
2 WC 2 WC 2 WC 2 WC 1 WC 1 WC 1 WC 1 WC 1 WC 1 WC 1 WC 1 WC 10 WC 8 WC 8 WC 8 WC 8 WC 8 WC 8 WC
2 WC 2 WC 2 WC 2 WC 2 WC 2 WC 2 WC 2 WC 3 WC3 WC3 WC3 WC3 WC 3 WC3 WC3 WC3 WC 3 WC3 WC3 WC3 WC3 WC
3
23 of 37 ©2019 View, Inc.Rev 6 | Aug 2019
OVERVIEW GUIDE
Pattern Example
INTE
RC
ON
NE
CT
DIA
GR
AM
-P
ATT
ER
N 8
, 9, 1
0, P
.I.
PATTERN 8PART # FIND DESCRIPTION QTY ROUTING
370-000002 LC-1 TEE, LRG CONN 5P-F, LRG CONN 5P-M, MED CONN 5P-F 1 041010-101584 WC-B ASSEMBLY, 2.0 WINDOW CONTROLLER 1 061
380-101510-02 D-2'0"P DROP CABLE, PLENUM, MED CONN, 5P M, SML CONN, 5PK F, 2' 0" (0.6M) 1 334380-101509-04 I-4'11"P IGU CABLE, PLENUM, SML CONN, 5PK MF, 4' 11" (1.5M) 1 563
PATTERN 9PART # FIND DESCRIPTION QTY ROUTING
370-000002 LC-1 TEE, LRG CONN 5P-F, LRG CONN 5P-M, MED CONN 5P-F 3 041010-101584 WC-B ASSEMBLY, 2.0 WINDOW CONTROLLER 3 061
380-000038-03 T-3'3"P TRUNK CABLE, PLENUM, LRG CONN, 5P MF, 3' 3" (1M) 2 140380-101510-02 D-2'0"P DROP CABLE, PLENUM, MED CONN, 5P M, SML CONN, 5PK F, 2' 0" (0.6M) 3 334380-101509-03 I-3'3"P IGU CABLE, PLENUM, SML CONN, 5PK MF, 3' 3" (1M) 3 562
PATTERN 10PART # FIND DESCRIPTION QTY ROUTING
370-000002 LC-1 TEE, LRG CONN 5P-F, LRG CONN 5P-M, MED CONN 5P-F 2 041010-101584 WC-B ASSEMBLY, 2.0 WINDOW CONTROLLER 2 061
380-000038-03 T-3'3"P TRUNK CABLE, PLENUM, LRG CONN, 5P MF, 3' 3" (1M) 1 140380-101510-02 D-2'0"P DROP CABLE, PLENUM, MED CONN, 5P M, SML CONN, 5PK F, 2' 0" (0.6M) 2 334380-101509-03 I-3'3"P IGU CABLE, PLENUM, SML CONN, 5PK MF, 3' 3" (1M) 2 562
#X##
WTTO NEXTPATTERNSEE PLAN
#X## WC-B
2'0"P
LC-1
WTTO CP
FROM PREV.PATTERNSEE PLAN
4'11"P
#X###X## #X##
3'3" PLC-1
#X##
WTTO CP
FROM PREV.PATTERNSEE PLAN
WTTO NEXTPATTERNSEE PLAN
WC-B
2'0"P
#X## WC-B
2'0"P
#X## WC-B
2'0"P
WTWT
3'3"PLC-1LC-1
3'3"P 3'3"P 3'3"P
#X## #X##
3'3"P
WTTO CP
FROM PREV.PATTERNSEE PLAN
WTTO NEXTPATTERNSEE PLAN
#X## WC-B
2'0"P
#X## WC-B
2'0"P
WT
LC-1LC-1
3'3"P 3'3" P
SCALE:4 INTERCONNECT, POWER INSERT @ 1-2 TEESNONE
NEXT POWER SESSION
## PART # FIND DESCRIPTION QTY1 370-000025 PT-1 TEE, POWER, LRG CONN 5P-F, LRG CONN 5P-M, LRG CONN 4P-M 12 310-000061 FW-LC4-1 CONNECTOR, FIELD WIREABLE, LRG CONN, 4P-M 13 310-000063 FW-LC4-2 CONNECTOR, FIELD WIREABLE, LRG CONN, 4P-F 1
PT-1
WT WTTO CP
FROM PREV.PATTERNSEE PLAN
WT WTTO NEXTPATTERNSEE PLAN
PI
PI
PI
PI
FW-LC4-2
FW-LC4-1
(CONNECT AT CONTROL PANEL)FIELD WIRED 4 PIN MALE POWER CONNECTOR
(CONNECT AT CONTROL PANEL)
FIELD WIRED 4 PIN FEMALEPOWER CONNECTOR
POWER INSERT CABLE.SEE PLAN FOR ROUTING.
USE THIS POWER INSERT PATTERN TO CONNECT BEFORE 1-2 DROP TEES.MAXIMUM (3) CONNECTORS TOGETHER BEFORE NEEDING STRAIN RELIEF,UNLESS CONNECTORS ARE MOUNTED TO A SOLID SURFACE.
USE FIELD WIRED CONNECTORS WITH 14/4P POWER INSERT CABLE: 500' SPOOL, PART NUMBER 300-101032-01 1000' SPOOL, PART NUMBER 300-101032
FOR ASSEMBLY OF FIELD WIRED CONNECTORS, SEE DETAIL 2XG-9.2.1
SCALE:5 INTERCONNECT, POWER INSERT @ DB-8 BOX, TEENONE
NEXT POWER SESSION
PT-1
WT WTTO CP
FROM PREV.PATTERNSEE PLAN
WTTO NEXTPATTERNSEE PLAN
PI
PI
PI
PI
FW-LC4-2
FW-LC4-1
(CONNECT AT CONTROL PANEL)FIELD WIRED 4 PIN MALE POWER CONNECTOR
(CONNECT AT CONTROL PANEL)
FIELD WIRED 4 PIN FEMALEPOWER CONNECTOR
POWER INSERT CABLE.SEE PLAN FOR ROUTING.
WT
1'0" P
## PART # FIND DESCRIPTION QTY1 370-000025 PT-1 TEE, POWER, LRG CONN 5P-F, LRG CONN 5P-M, LRG CONN 4P-M 12 310-000061 FW-LC4-1 CONNECTOR, FIELD WIREABLE, LRG CONN, 4P-M 13 310-000063 FW-LC4-2 CONNECTOR, FIELD WIREABLE, LRG CONN, 4P-F 14 380-000038-01 T-1'0"P TRUNK CABLE, PLENUM, LRG CONN, 5P MF, 1' 0" (0.3M) 1
USE THIS POWER INSERT PATTERN TO CONNECT BEFORE DB-8 BOX.
USE FIELD WIRED CONNECTORS WITH 14/4P POWER INSERT CABLE: 500' SPOOL, PART NUMBER 300-101032-01 1000' SPOOL, PART NUMBER 300-101032
FOR ASSEMBLY OF FIELD WIRED CONNECTORS, SEE DETAIL 2XG-9.2.1
SCALE:1 INTERCONNECT, PATTERN 8 ; THUS 17NONE SCALE:2 INTERCONNECT, PATTERN 9 ; THUS 15
NONE SCALE:3 INTERCONNECT, PATTERN 10 ; THUS 22NONE
01P
RE
LIM
INA
RY
00.0
0.19
THA
RR
ELL
TH
VIE
W T
RA
ININ
G P
RO
JEC
T18
330
NO
THIN
G R
OA
DS
OM
EW
HE
RE
, CA
950
00
DR
AW
ING
RE
LEA
SE
SD
ES
CR
IPTI
ON
NO
.D
ATE
RE
LEA
SE
#
DR
AW
N:
DE
SIG
N:
RE
VIE
W:
ISS
UE
DA
TE:
INFO
RM
ATI
ON
®
VIEW, INC. ®195 SOUTH MILPITAS BLVD.MILPITAS, CA 95035PH: 408-263-9200WWW.VIEWGLASS.COM
PLO
T D
ATE
:
SFI
D:
VIE
W D
OC
UM
EN
T N
UM
BE
R
SH
EE
T TI
TLE
:
SHEET NUMBER:
VIEW, INC. CONFIDENTIAL:THIS DOCUMENT AND THE INFORMATIONCONTAINED IN IT ARE CONFIDENTIAL,AND CANNOT BE COPIED OR DISCLOSEDIN WHOLE OR IN PART WITHOUT THEEXPRESS WRITTEN CONSENT OFVIEW, INC. ® © - VIEW, INC.
XG-4.03
4.29
.201
9 12
:40
PM
2019
00.0
0.19
0134
0-10
133313
0067
130
TH
WINDOW CONTROLLERSMUST BE INSTALLED AT ANACCESSIBLE, ENVIRON-MENTALLY -CONTROLLEDLOCATION
24 of 37 ©2019 View, Inc.Rev 6 | Aug 2019
OVERVIEW GUIDE
Control Panel Configuration Example
01P
RE
LIM
INA
RY
00.0
0.19
THA
RR
ELL
TH
VIE
W T
RA
ININ
G P
RO
JEC
T18
330
NO
THIN
G R
OA
DS
OM
EW
HE
RE
, CA
950
00
DR
AW
ING
RE
LEA
SE
SD
ES
CR
IPTI
ON
NO
.D
ATE
RE
LEA
SE
#
DR
AW
N:
DE
SIG
N:
RE
VIE
W:
ISS
UE
DA
TE:
INFO
RM
ATI
ON
®
VIEW, INC. ®195 SOUTH MILPITAS BLVD.MILPITAS, CA 95035PH: 408-263-9200WWW.VIEWGLASS.COM
PLO
T D
ATE
:
SFI
D:
VIE
W D
OC
UM
EN
T N
UM
BE
R
SH
EE
T TI
TLE
:
SHEET NUMBER:
VIEW, INC. CONFIDENTIAL:THIS DOCUMENT AND THE INFORMATIONCONTAINED IN IT ARE CONFIDENTIAL,AND CANNOT BE COPIED OR DISCLOSEDIN WHOLE OR IN PART WITHOUT THEEXPRESS WRITTEN CONSENT OFVIEW, INC. ® © - VIEW, INC.
XG-5.1.1
4.29
.201
9 12
:40
PM
2019
00.0
0.19
E.C. TO PROVIDE 120VAC, 60Hz, DEDICATED 20 AMPCKT. CRITICAL POWERSOURCE PREFERRED.
E.C. TO PROVIDEETHERNET DROP(S) ATWINDOW CONTROLPANEL LOCATION - SEENETWORK DIAGRAM.
(1) ETHERNET DROP ATWINDOW CONTROLPANEL TO CONNECT TORING SENSORLOCATION.
TRUNK TERMINATOR -INSTALL IN ACCESSIBLELOCATION
KEY NOTES
1
2
3
4
0134
0-10
133313
0067
130
THW
IND
OW
CO
NTR
OL
PA
NE
LD
ETA
ILS
, TY
PIC
AL
E.C. TO PROVIDE 120VAC, 60Hz,1Ø, 20 AMP UNSWITCHED CKT
WITH GREEN WIRE EARTHGROUND. CRITICAL POWER
SOURCE PREFERRED. DO NOTSHARE GROUND OR NEUTRALS.
RJ-45 BULKHEAD PORTS
POWER INSERT BULKHEADPORTS, TYP. OF 6 EACH.-03 AND -04 CP MODELS.
POWER INSERT BULKHEADPORTS, TYP. OF 6 EACH.
ONLY -04 CP MODEL.
TRUNK BULKHEAD PORTS, TYP. OF 2 EACH.ONLY -04 CP MODEL.
IF TRUNK NOT ATTACHED TO PORT, CONNECTLT-M (TERMINATOR), P/N 370-000008
TRUNK BULKHEAD PORTS, TYP. OF 2 EACH.-03 AND -04 CP MODELS.IF TRUNK NOT ATTACHED TO PORT, CONNECTLT-M (TERMINATOR), P/N 370-000008
(2) OPTIONAL PORTSFROM SFP MODULES
SCALE:1 CONTROL PANEL - BULKHEAD CONNECTIONSNONE SCALE:2 CONTROL PANEL - INSTALLATION REQUIREMENTS AND DIMENSIONS
NONE
SCALE:3 CONTROL PANELS - PARTS AND OPTIONAL ACCESSORY LISTNONE
29"
NOTE: TRUNK AND POWER INSERT NAMES MAY DIFFER FROMTHOSE REPRESENTED HERE. SEE ONE LINE DIAGRAMS FOR EACHCONTROL PANEL FOR TRUNK AND POWER CONNECTIONS USED.
60"
21"
WINDOW CONTROL PANEL
9"
MA
INTA
IN 6
" CLE
AR
SP
AC
EB
OTH
SID
ES
OF
CO
NTR
OL
PA
NE
L
MA
INTA
IN 6
" CLE
AR
SP
AC
EB
OTH
SID
ES
OF
CO
NTR
OL
PA
NE
L
MAINTAIN 36" CLEAR SPACEIN FRONT OF CONTROL PANEL
MA
INTA
IN 6
" CLE
AR
SP
AC
EB
OTH
SID
ES
OF
CO
NTR
OL
PA
NE
L
MA
INTA
IN 6
" CLE
AR
SP
AC
EB
OTH
SID
ES
OF
CO
NTR
OL
PA
NE
L
FINISH FLOOR
FIN
ISH
WA
LL S
UR
FAC
E
ECAFRUS LLAW HSINIF
INSTALLATION NOTES:
1. MAY BE MOUNTED TO FIRE RESISTANT BACKBOARDOR DIRECTLY TO WALL.
2. CONTRACTOR TO DETERMINE SUITABLE MOUNTINGMETHOD & ANCHORS.
3. CONTROL PANEL AND PULL BOX DOORS ARE LEFTSWING ONLY.
4. CONTROL PANEL WEIGHT: APPROX. 70 POUNDSINSTALLED.
5. E.C. TO PROVIDE NETWORK DROP 10" ABOVE TOP OFCONTROL PANEL. SEE NETWORK DIAGRAM FORNUMBER OF DROPS AND ROUTING.
6. IF PULLBOX ENCLOSURE IS PROVIDED, LOCATENETWORK DROP WITHIN ENCLOSURE.
7. E.C. TO PROVIDE CAT5E / CAT6 PATCH CORDS TOCONNECT CONTROL PANEL BULKHEAD FITTINGS TONETWORK DROP.
FRONT ELEVATION SIDE ELEVATION
PLAN AND CLEARANCES
E.C. TO PROVIDE 120VAC, 60Hz,1Ø, 20 AMP UNSWITCHED CKT
WITH GREEN WIRE EARTHGROUND. CRITICAL POWER
SOURCE PREFERRED. DO NOTSHARE GROUND OR NEUTRALS.
LADDER RACK OR OTHER CABLE MANAGEMENT SHOWN AS INSTALLATION SUGGESTION
CP-256N (-04)
CP-128N (-03)
MOUNTING WEIGHT:APPROX. 70 LBS.
9"
E.C. TO PROVIDE NETWORK DROP10" ABOVE TOP OF CONTROL PANEL.SEE NETWORK DIAGRAM FORNUMBER OF DROPS AND ROUTING.
10"
## PART # FIND DESCRIPTION QTY NOTES1 010-101604-03 CP2-128N ASSY, CP2.0, 2 PS, 24V, CLASS 2, 128 WC, NETWORKED -2 010-101604-04 CP2-256N ASSY, CP2.0, 3 PS, 24V, CLASS 2, 256 WC, NETWORKED -3 010-101611 CP-PB PULL BOX ENCLOSURE, CP2.0 -4 015-101821-01 POE-1 KIT, 1 POE - ADD (1) PoE PORT5 015-101821-02 POE-2 KIT, 2 POE - ADD (2) PoE PORTS6 015-101844-01 SFP-OPT1 KIT, OPTICAL, SFP PORTS, 1000BASE-SX SHORT WAVELENGTH; RUGGED - ADD MULTIMODE FIBER PORT 300'-1500' RANGE7 015-101844-02 SFP-OPT2 KIT, OPTICAL, SFP PORTS, 1000BASE-LX/LH LONG WAVELENGTH; RUGGED - ADD SINGLE MODE FIBER PORT >1500' RANGE8 015-101844-03 SFP-RJ45 KIT, OPTICAL, SFP PORTS, 1000BASE-T STANDARD - ADD RJ-45 NETWORK PORT9 050-101565-02 LATCH, COMPRESSION, VISE ACTION, E3 SERIES W/ TUBULAR KEY - OPTIONAL CASE LOCK
BULKHEAD PORT CONNECTION DESCRIPTIONCP MODEL
NOTES-03 -04
J1 TRUNK X.C N/A X TRUNK PAIR #2, 128 WCs MAX.J2 TRUNK X.D N/A XJ3 POWER INSERT X-7 N/A XJ4 POWER INSERT X-8 N/A XJ5 POWER INSERT X-9 N/A XJ6 POWER INSERT X-10 N/A XJ7 POWER INSERT X-11 N/A XJ8 POWER INSERT X-12 N/A XJ9 TRUNK X.A X X TRUNK PAIR #1, 128 WCs MAX.J10 TRUNK X.B X XJ11 POWER INSERT X-1 X XJ12 POWER INSERT X-2 X XJ13 POWER INSERT X-3 X XJ14 POWER INSERT X-4 X XJ15 POWER INSERT X-5 X XJ16 POWER INSERT X-6 X XJ17 RJ-45 X X TO W.W.W./CUSTOMER NETWORKJ18 RJ-45 X X PoE-1J19 SFP MODULE N/A N/A OPTIONAL RJ-45 OR FIBERJ20 RJ-45 X X TO NEXT CP PORT J21J21 RJ-45 X X FROM PREVIOUS CP PORT J20J22 SFP MODULE N/A N/A OPTIONAL RJ-45 OR FIBER
BULKHEAD CONNECTIONS FORTRUNK, POWER AND NETWORK.SEE LEFT.
2 31
44
25 of 37 ©2019 View, Inc.Rev 6 | Aug 2019
OVERVIEW GUIDE
System Network Requirements Example
RJ-45 - WWW FROM EN01
J21 - RJ-45 - SW PORT 3
J22 - SFP - FIBER OR COPPERJ19 - SFP - FIBER OR COPPER
J18 - RJ-45 - SW PORT 1 / PoE-1
J20 - RJ-45 - SW PORT 2 / PoE-2
SCALE:4 CONTROL PANEL BULKHEAD MAPPINGNONE
SCALE:1 BOM INFORMATIONNONE SCALE:5 BULKHEAD CONNECTIONS - FLOOR 1
NONE SCALE:6 BULKHEAD CONNECTIONS - FLOOR 2NONE
CP 1.1PORT # TYPE CONNECTION NAME CONNECT TO
J17 RJ-45 W.W.W. VIA CUSTOMER NETWORK OR CELL MODEMJ18 RJ-45 SW PORT 1 PoE-1 TO SKY SENSORJ19 BLANK FIBER OR COPPER -1J20 RJ-45 SW PORT 2 NEXT CP - PORT J21J21 RJ-45 SW PORT 3 PREVIOUS CP - PORT J20J22 BLANK FIBER OR COPPER -2
CP 2.1PORT # TYPE CONNECTION NAME CONNECT TO
J17 RJ-45 -- RESERVED FOR W.W.W. CONNECTIONJ18 RJ-45 SW PORT 1 PoE-1 TO SKY SENSORJ19 BLANK FIBER OR COPPER -1J20 RJ-45 SW PORT 2 NEXT CP - PORT J21J21 RJ-45 SW PORT 3 PREVIOUS CP - PORT J20J22 BLANK FIBER OR COPPER -2
CAT5e
CA
T5e
CA
T5e
CAT5eCAT5eCAT5eCAT5eCAT5eCAT5eCAT5eCAT5eCAT5e
CA
T5e
CAT5e TO CUSTOMER NETWORK OR CELL MODEM
CA
T5e-
PoE
USE CASE:
· TIER 2 MC· MULTIPLE CP· NO FIBER· ALL DROPS LESS THAN 300 CABLE FEET
SKY SENSOR - ON ROOF
NETWORK MEDIUM KEY:
· COPPER Cat5e <300'· COPPER Cat6 <300'· COPPER Cat5 / PoE <300'· COPPER Cat6 / PoE <300'· Fiber OM2 Multimode <1500'· Fiber Single Mode >1500'
SCALE:3 USE CASENONE
SCALE:2 NETWORK MEDIUM KEYNONE
BOM INFORMATION:
· KIT, POE-1 015-101821-011 kit required for SKY Sensor
CAT5eCAT6
CAT5e-PoECAT6-PoE
F/O mmF/O sm
01P
RE
LIM
INA
RY
00.0
0.19
THA
RR
ELL
TH
VIE
W T
RA
ININ
G P
RO
JEC
T18
330
NO
THIN
G R
OA
DS
OM
EW
HE
RE
, CA
950
00
DR
AW
ING
RE
LEA
SE
SD
ES
CR
IPTI
ON
NO
.D
ATE
RE
LEA
SE
#
DR
AW
N:
DE
SIG
N:
RE
VIE
W:
ISS
UE
DA
TE:
INFO
RM
ATI
ON
®
VIEW, INC. ®195 SOUTH MILPITAS BLVD.MILPITAS, CA 95035PH: 408-263-9200WWW.VIEWGLASS.COM
PLO
T D
ATE
:
SFI
D:
VIE
W D
OC
UM
EN
T N
UM
BE
R
SH
EE
T TI
TLE
:
SHEET NUMBER:
VIEW, INC. CONFIDENTIAL:THIS DOCUMENT AND THE INFORMATIONCONTAINED IN IT ARE CONFIDENTIAL,AND CANNOT BE COPIED OR DISCLOSEDIN WHOLE OR IN PART WITHOUT THEEXPRESS WRITTEN CONSENT OFVIEW, INC. ® © - VIEW, INC.
XG-1.2.1
4.29
.201
9 12
:39
PM
2019
00.0
0.19
0134
0-10
133313
0067
130
THN
ETW
OR
K D
IAG
RA
M
26 of 37 ©2019 View, Inc.Rev 6 | Aug 2019
OVERVIEW GUIDE
Roof Layout for Sky Sensor
01P
RE
LIM
INA
RY
00.0
0.19
THA
RR
ELL
TH
VIE
W T
RA
ININ
G P
RO
JEC
T18
330
NO
THIN
G R
OA
DS
OM
EW
HE
RE
, CA
950
00
DR
AW
ING
RE
LEA
SE
SD
ES
CR
IPTI
ON
NO
.D
ATE
RE
LEA
SE
#
DR
AW
N:
DE
SIG
N:
RE
VIE
W:
ISS
UE
DA
TE:
INFO
RM
ATI
ON
®
VIEW, INC. ®195 SOUTH MILPITAS BLVD.MILPITAS, CA 95035PH: 408-263-9200WWW.VIEWGLASS.COM
PLO
T D
ATE
:
SFI
D:
VIE
W D
OC
UM
EN
T N
UM
BE
R
SH
EE
T TI
TLE
:
SHEET NUMBER:
VIEW, INC. CONFIDENTIAL:THIS DOCUMENT AND THE INFORMATIONCONTAINED IN IT ARE CONFIDENTIAL,AND CANNOT BE COPIED OR DISCLOSEDIN WHOLE OR IN PART WITHOUT THEEXPRESS WRITTEN CONSENT OFVIEW, INC. ® © - VIEW, INC.
XG-2.R
4.29
.201
9 12
:39
PM
2019
00.0
0.19
0134
0-10
133313
0067
130
THS
KY
SE
NS
OR
LA
YO
UT
-R
OO
F
SCALE:1 SKY SENSOR LAYOUT - ROOFNONE
MOUNT MIN. 2 FEET (0.6M) ABOVE HIGHESTOBSTRUCTION ONROOF. PROVIDE 360°UNOBSTRUCTED VIEWHORIZONTAL, 200°VERTICAL (10° BELOWHORIZONTAL).
ENSURE MOUNTINGHEIGHT WILL NOT BEOBSCURED BASED ONAVERAGE SNOWFALLACCUMULATION.
MOUNT MUST BEBONDED TO BUILDINGGROUND.
VERIFY MOUNTINGLOCATION IN FIELDWITH BUILDING OWNER.
PROVIDE CAT5E (ORGREATER) CABLE FROMNEAREST IDF LOCATIONTO ROOF OR DEVICEMOUNTING LOCATION(100 M MAXIMUM).
SEE DETAILS ONXG-9.4.1 FOR FURTHERMOUNTING AND SETUPINFORMATION.
KEY NOTES
1
2
3
4
5
CAT5e
CAT5e CAT5e
CAT5e
CAT5e
SSA
1 2 3 45
SKY SENSOR TO BE MOUNTEDON ELEVATOR OVERRUN WITHINEQUIPMENT SCREEN
27 of 37 ©2019 View, Inc.Rev 6 | Aug 2019
OVERVIEW GUIDE
Bill of Materials Example
\CustSig_1_sig\ \CSDate_1_date\
Controls Order Acknowledgment(Standard lead times apply from the date of signed approval or submittal to View)
I __CustomerName___ of _____Company Name_____ have reviewed the materials list on this drawing and verify that the information is correct.By signing below I accept release of the materials listed to be procured for this job.
Signed: ____________________________________ Date: ______________________
01P
RE
LIM
INA
RY
03.2
0.19
JKA
NG
XX
XX
XX
XX
BLD
G 1
DE
MO
INS
TALL
123
MA
IN S
TRE
ET,
AN
YTO
WN
, ST
DR
AW
ING
RE
LEA
SE
SD
ES
CR
IPTI
ON
NO
.D
ATE
RE
LEA
SE
#
DR
AW
N:
DE
SIG
N:
RE
VIE
W:
ISS
UE
DA
TE:
INFO
RM
ATI
ON
®
VIEW, INC. ®195 SOUTH MILPITAS BLVD.MILPITAS, CA 95035PH: 408-263-9200WWW.VIEW.COM
PLO
T D
ATE
:
SFI
D:
VIE
W D
OC
UM
EN
T N
UM
BE
R
SH
EE
T TI
TLE
:
SHEET NUMBER:
VIEW, INC. CONFIDENTIAL:THIS DOCUMENT AND THE INFORMATIONCONTAINED IN IT ARE CONFIDENTIAL,AND CANNOT BE COPIED OR DISCLOSEDIN WHOLE OR IN PART WITHOUT THEEXPRESS WRITTEN CONSENT OFVIEW, INC. ® © - VIEW, INC.
XG-6.01
7.23
.201
9 12
:10
PM
2019
03.2
0.19
0134
0-10
1#####
####
##
XX
XX
XX
XX
BIL
L O
F M
ATE
RIA
LS
SCALE:1 CP 2.1, HEAD ENDNONE
015-101###-01INTERCONNECT DIAGRAM 340-101xxx
SECOND FLOOR, CP 2.1, HEAD END## PART # FIND DESCRIPTION QTY
Control Panels, Accessories1 010-101604-03 CP2-128N ASSY, CP2.0, 2 PS, 24V, CLASS 2, 128 WC, NETWORKED 12 010-101611 CP-PB PULL BOX ENCLOSURE, CP2.0 13 015-101821-01 POE-1 KIT, 1 POE 1
Large Connectors4 370-000002 LC-1 TEE, LRG CONN 5P-F, LRG CONN 5P-M, MED CONN 5P-F 265 370-000008 LT-M TERMINATOR, LRG CONN 5P-M 2
CapsWindow Controllers
6 010-101584 WC-B ASSEMBLY, 2.0 WINDOW CONTROLLER 26Trunk Cables
7 380-101549 T-8"P TRUNK CABLE, PLENUM, STUB, LRG CONN, 5P MF 48 380-000038-04 T-4'11"P TRUNK CABLE, PLENUM, LRG CONN, 5P MF, 4' 11" (1.5M) 19 380-000038-06 T-8'2"P TRUNK CABLE, PLENUM, LRG CONN, 5P MF, 8' 2" (2.5M) 2
10 380-000038-07 T-9'10"P TRUNK CABLE, PLENUM, LRG CONN, 5P MF, 9' 10" (3M) 211 380-000038-13 T-19'8"P TRUNK CABLE, PLENUM, LRG CONN, 5P MF, 19' 8" (6M) 212 380-000038-21 T-32'9"P TRUNK CABLE, PLENUM, LRG CONN, 5P MF, 32' 9" (10M) 113 380-000038-23 T-98'5"P TRUNK CABLE, PLENUM, LRG CONN, 5P MF, 98' 5" (30M) 2
Drop Cables
8 380-101510-02 D-2'0"PDROP CABLE, PLENUM, MED CONN, 5P M, SML CONN, 5PK F, 2' 0"
(0.6M) 26
IGU Cables9 380-101509-03 I-3'3"P IGU CABLE, PLENUM, SML CONN, 5PK MF, 3' 3" (1M) 1
10 380-101509-04 I-4'11"P IGU CABLE, PLENUM, SML CONN, 5PK MF, 4' 11" (1.5M) 811 380-101509-05 I-6'6"P IGU CABLE, PLENUM, SML CONN, 5PK MF, 6' 6" (2M) 112 380-101509-06 I-8'2"P IGU CABLE, PLENUM, SML CONN, 5PK MF, 8' 2" (2.5M) 513 380-101509-07 I-9'10"P IGU CABLE, PLENUM, SML CONN, 5PK MF, 9' 10" (3M) 114 380-101509-09 I-13'1"P IGU CABLE, PLENUM, SML CONN, 5PK MF, 13' 1" (4M) 415 380-101509-11 I-16'4"P IGU CABLE, PLENUM, SML CONN, 5PK MF, 16' 4" (5M) 516 380-101509-12 I-18'0"P IGU CABLE, PLENUM, SML CONN, 5PK MF, 18' 0" (5.5M) 1
015-101###-02INTERCONNECT DIAGRAM 340-101xxx
SECOND FLOOR, CP 2.1, GLAZIER## PART # FIND DESCRIPTION QTY
IGU Cables1 380-101509-05 I-6'6"P IGU CABLE, PLENUM, SML CONN, 5PK MF, 6' 6" (2M) 26
015-101###-03INTERCONNECT DIAGRAM 340-101xxx
SECOND FLOOR, CP 2.1, SPARE## PART # FIND DESCRIPTION QTY
Large Connectors1 370-000002 LC-1 TEE, LRG CONN 5P-F, LRG CONN 5P-M, MED CONN 5P-F 1
CapsWindow Controllers
2 010-101584 WC-B ASSEMBLY, 2.0 WINDOW CONTROLLER 1Trunk Cables
3 380-101549 T-8"P TRUNK CABLE, PLENUM, STUB, LRG CONN, 5P MF 14 380-000038-04 T-4'11"P TRUNK CABLE, PLENUM, LRG CONN, 5P MF, 4' 11" (1.5M) 15 380-000038-06 T-8'2"P TRUNK CABLE, PLENUM, LRG CONN, 5P MF, 8' 2" (2.5M) 16 380-000038-07 T-9'10"P TRUNK CABLE, PLENUM, LRG CONN, 5P MF, 9' 10" (3M) 1
Drop Cables
7 380-101510-02 D-2'0"PDROP CABLE, PLENUM, MED CONN, 5P M, SML CONN, 5PK F, 2' 0"
(0.6M) 1
IGU Cables
8 380-101509-04 I-4'11"P IGU CABLE, PLENUM, SML CONN, 5PK MF, 4' 11" (1.5M) 19 380-101509-05 I-6'6"P IGU CABLE, PLENUM, SML CONN, 5PK MF, 6' 6" (2M) 1
10 380-101509-06 I-8'2"P IGU CABLE, PLENUM, SML CONN, 5PK MF, 8' 2" (2.5M) 1
SCALE:2 CP 2.1, GLAZIERNONE
SCALE:3 CP 2.1, SPARENONE
SCALE:4 4 STATE TESTERS - LVENONE
SCALE:5 4 STATE TESTERS - GLAZIERNONE
Transfers015-101###-700
INTERCONNECT DIAGRAM 340-101xxx4 STATE TESTERS, L.V.
## PART # FIND DESCRIPTION QTY1 010-101543 4ST-B ASSY, 4 STATE CONTROLLER / TESTER 12 380-101516 ADAPT 1 ADAPT 1, IGU CABLE, PLENUM, SML CONN-F 5PK, SML CONN-M 5P 13 380-101509-03 I-3'3"P IGU CABLE, PLENUM, SML CONN, 5PK MF, 3' 3" (1M) 1
015-101###-701INTERCONNECT DIAGRAM 340-101xxx
4 STATE TESTERS, GLAZIER## PART # FIND DESCRIPTION QTY1 010-101543 4ST-B ASSY, 4 STATE CONTROLLER / TESTER 12 380-101516 ADAPT 1 ADAPT 1, IGU CABLE, PLENUM, SML CONN-F 5PK, SML CONN-M 5P 13 380-101509-03 I-3'3"P IGU CABLE, PLENUM, SML CONN, 5PK MF, 3' 3" (1M) 1
015-101###-800INTERCONNECT DIAGRAM 340-101xxx
CELL MODEM## PART # FIND DESCRIPTION QTY1 010-101130 CP-ME ASSY, WIRELESS ROUTER, VERIZON WIRELESS 12 380-000012-04 ETH-4 CABLE, ETHERNET, RJ45, 84 IN BLK (7.0 FT) 1
SCALE:6 CELL MODEMNONE
SCALE:7 SKY SENSORNONE
015-101###-900INTERCONNECT DIAGRAM 340-101xxx
SKY SENSOR## PART # FIND DESCRIPTION QTY1 010-101619-01 SSA ASSEMBLY, SKY SENSOR 1
28 of 37 ©2019 View, Inc.Rev 6 | Aug 2019
OVERVIEW GUIDE
01P
RE
LIM
INA
RY
00.0
0.19
THA
RR
ELL
XX
XX
XX
XX
SIT
E N
AM
EB
UIL
DIN
GS
TRE
ET
AD
DR
ES
SC
ITY
, STA
TE 0
0000
DR
AW
ING
RE
LEA
SE
SD
ES
CR
IPTI
ON
NO
.D
ATE
RE
LEA
SE
#
DR
AW
N:
DE
SIG
N:
RE
VIE
W:
ISS
UE
DA
TE:
INFO
RM
ATI
ON
®
VIEW, INC. ®195 SOUTH MILPITAS BLVD.MILPITAS, CA 95035PH: 408-263-9200WWW.VIEWGLASS.COM
PLO
T D
ATE
:
SFI
D:
VIE
W D
OC
UM
EN
T N
UM
BE
R
SH
EE
T TI
TLE
:
SHEET NUMBER:
VIEW, INC. CONFIDENTIAL:THIS DOCUMENT AND THE INFORMATIONCONTAINED IN IT ARE CONFIDENTIAL,AND CANNOT BE COPIED OR DISCLOSEDIN WHOLE OR IN PART WITHOUT THEEXPRESS WRITTEN CONSENT OFVIEW, INC. ® © - VIEW, INC.
XG-7.1.1
4.29
.201
9 12
:40
PM
2019
00.0
0.19
0134
0-10
1#####
####
##
XX
XX
XX
XX
IGU
AN
D W
C Z
ON
ING
(LO
AD
ING
SC
HE
DU
LE)
CP
1.1
SCALE:1 LOADING SCHEDULE - CP 1.1 ; TRUNKS ON J9, J10NONE SCALE:2 LOADING SCHEDULE - CP 1.1 ; TRUNKS ON J1, J2
NONE
ZONE # MARK ID IGU # WIDTH HEIGHT SF WC#ID NOTES TRUNK IDCONF 105 N 1N01 1 1.1ACONF 105 N 1N02 2 1.1ACONF 105 N 1N03 3 1.1ACONF 105 N 1N04 4 1.1ACONF 104 N 1N05 5 1.1ACONF 104 N 1N06 6 1.1ACONF 104 N 1N07 7 1.1ACONF 104 N 1N08 8 1.1ACONF 103 N1 1N09 9 1.1ACONF 103 N2 1N10 10 1.1ACONF 103 N3 1N11 11 1.1ACONF 103 N4 1N12 12 1.1ACONF 103 N5 1N13 13 1.1ACONF 106 W1 1W01 14 1.1ACONF 106 W1 1W02 15 1.1ACONF 106 W2 1W03 16 1.1ACONF 106 W2 1W04 17 1.1ACONF 106 W3 1W05 18 1.1ACONF 106 W3 1W06 19 1.1ACONF 105 W1 1W07 20 1.1ACONF 105 W1 1W08 21 1.1ACONF 105 W2 1W09 22 1.1ACONF 105 W2 1W10 23 1.1ACONF 105 W3 1W11 24 1.1ACONF 105 W3 1W12 25 1.1ACONF 104 XE XE01 26 1.1ACONF 104 XE XE03 27 1.1ACONF 104 XE XE05 28 1.1A
PROD 110 E1_B 1E01 29 1.1BPROD 110 E1_T 1E02 30 1.1BPROD 110 E1_B 1E03 31 1.1BPROD 110 E1_T 1E04 32 1.1BPROD 110 E1_B 1E05 33 1.1BPROD 110 E1_T 1E06 34 1.1BPROD 110 E1_B 1E07 35 1.1BPROD 110 E1_T 1E08 36 1.1BPROD 110 E2_B 1E09 37 1.1BPROD 110 E2_T 1E10 38 1.1BPROD 110 E2_B 1E11 39 1.1BPROD 110 E2_T 1E12 40 1.1BPROD 110 E2_B 1E13 41 1.1BPROD 110 E2_T 1E14 42 1.1BPROD 110 E2_B 1E15 43 1.1BPROD 110 E2_T 1E16 44 1.1BPROD 110 E3_B 1E17 45 1.1BPROD 110 E3_T 1E18 46 1.1BPROD 110 E3_B 1E19 47 1.1BPROD 110 E3_T 1E20 48 1.1BPROD 110 E3_B 1E21 49 1.1BPROD 110 E3_T 1E22 50 1.1BPROD 110 DR3 1E23 51 OPERABLE 1.1BPROD 110 E3_T 1E24 52 1.1BPROD 110 E3_B 1E25 53 1.1BPROD 110 E3_T 1E26 54 1.1BPROD 110 N1_B 1N30 55 1.1BPROD 110 N1_T 1N31 56 1.1BPROD 110 N1_B 1N32 57 1.1BPROD 110 N1_T 1N33 58 1.1BPROD 110 DR1 1N34 59 OPERABLE 1.1BPROD 110 DR1 1N35 60 OPERABLE 1.1B
PROD 110 N1_T 1N36 61 1.1BPROD 110 N1_B 1N37 62 1.1BPROD 110 N1_T 1N38 63 1.1BPROD 110 N2_B 1N39 64 1.1BPROD 110 N2_T 1N40 65 1.1BPROD 110 N2_B 1N41 66 1.1BPROD 110 N2_T 1N42 67 1.1BPROD 110 N2_B 1N43 68 1.1BPROD 110 N2_T 1N44 69 1.1BPROD 110 N2_B 1N45 70 1.1BPROD 110 N2_T 1N46 71 1.1BPROD 110 N3_B 1N47 72 1.1BPROD 110 N3_T 1N48 73 1.1BPROD 110 DR2 1N49 74 OPERABLE 1.1BPROD 110 DR2 1N50 75 OPERABLE 1.1BPROD 110 N3_T 1N51 76 1.1BPROD 110 N3_B 1N52 77 1.1BPROD 110 N3_T 1N53 78 1.1BPROD 110 N3_B 1N54 79 1.1BPROD 110 N3_T 1N55 80 1.1B
81828384858687888990919293949596979899
100101102103104105106107108109110111112113114115116117118119120121122123124125126127128
NOT USED
Loading Schedule Example
29 of 37 ©2019 View, Inc.Rev 6 | Aug 2019
OVERVIEW GUIDE
Loading Schedule Example
01P
RE
LIM
INA
RY
00.0
0.19
THA
RR
ELL
XX
XX
XX
XX
SIT
E N
AM
EB
UIL
DIN
GS
TRE
ET
AD
DR
ES
SC
ITY
, STA
TE 0
0000
DR
AW
ING
RE
LEA
SE
SD
ES
CR
IPTI
ON
NO
.D
ATE
RE
LEA
SE
#
DR
AW
N:
DE
SIG
N:
RE
VIE
W:
ISS
UE
DA
TE:
INFO
RM
ATI
ON
®
VIEW, INC. ®195 SOUTH MILPITAS BLVD.MILPITAS, CA 95035PH: 408-263-9200WWW.VIEWGLASS.COM
PLO
T D
ATE
:
SFI
D:
VIE
W D
OC
UM
EN
T N
UM
BE
R
SH
EE
T TI
TLE
:
SHEET NUMBER:
VIEW, INC. CONFIDENTIAL:THIS DOCUMENT AND THE INFORMATIONCONTAINED IN IT ARE CONFIDENTIAL,AND CANNOT BE COPIED OR DISCLOSEDIN WHOLE OR IN PART WITHOUT THEEXPRESS WRITTEN CONSENT OFVIEW, INC. ® © - VIEW, INC.
XG-7.2.1
4.29
.201
9 12
:41
PM
2019
00.0
0.19
0134
0-10
1#####
####
##
XX
XX
XX
XX
IGU
AN
D W
C Z
ON
ING
(LO
AD
ING
SC
HE
DU
LE)
CP
2.1
SCALE:1 LOADING SCHEDULE - CP 2.1 ; TRUNKS ON J9, J10NONE SCALE:2 LOADING SCHEDULE - CP 2.1 ; TRUNKS ON J1, J2
NONE
ZONE # MARK ID IGU # WIDTH HEIGHT SF WC#ID NOTES TRUNK ID ZONE # MARK ID IGU # WIDTH HEIGHT SF WC#ID NOTES TRUNK IDLOBBY 101 N_B 1N14 1 2.1ALOBBY 101 N_M 1N15 2 2.1ALOBBY 101 N_T 1N16 3 2.1ALOBBY 101 N_B 1N17 4 2.1ALOBBY 101 N_M 1N18 5 2.1ALOBBY 101 N_T 1N19 6 2.1ALOBBY SLIDER 1N20 7 SLIDER 2.1ALOBBY SLIDER 1N21 8 2.1ALOBBY 101 N_M 1N22 9 2.1ALOBBY 101 N_T 1N23 10 2.1ALOBBY 101 N_B 1N24 11 2.1ALOBBY 101 N_M 1N25 12 2.1ALOBBY 101 N_T 1N26 13 2.1ALOBBY 101 N_B 1N27 14 2.1ALOBBY 101 N_M 1N28 15 2.1ALOBBY 101 N_T 1N29 16 2.1A
OFC 204 N1 2N01 17 2.1AOFC 204 N1 2N02 18 2.1AOFC 204 N2 2N03 19 2.1AOFC 204 N2 2N04 20 2.1AHALL 201 N1 2N05 21 2.1AHALL 201 N1 2N06 22 2.1AHALL 201 N2 2N07 23 2.1AHALL 201 N2 2N08 24 2.1AOFC 203 N1 2N09 25 2.1AOFC 203 N2 2N10 26 2.1AOFC 203 N3 2N11 27 2.1AOFC 203 N4 2N12 28 2.1AOFC 203 N5 2N13 29 2.1A
HALL 200 N_B 2N14 30 2.1AHALL 200 N_T 2N15 31 2.1AHALL 200 N_B 2N16 32 2.1AHALL 200 N_T 2N17 33 2.1AHALL 200 N_B 2N18 34 2.1AHALL 200 N_T 2N19 35 2.1AHALL 200 N_T 2N20 36 2.1AHALL 200 N_B 2N21 37 2.1AHALL 200 N_T 2N22 38 2.1AHALL 200 N_B 2N23 39 2.1AHALL 200 N_T 2N24 40 2.1AHALL 201 XE XE02 41 2.1AHALL 201 XE XE04 42 2.1AHALL 201 XE XE06 43 2.1A
LOBBY 101 XS_B XW01 44 2.1ALOBBY 101 XS_M XW02 45 2.1ALOBBY 101 XS_T XW03 46 2.1AHALL 200 XS_B XW04 47 2.1AHALL 200 XS_T XW05 48 2.1A
LOBBY 101 XS_B XW06 49 2.1ALOBBY 101 XS_M XW07 50 2.1ALOBBY 101 XS_T XW08 51 2.1AHALL 200 XS_B XW09 52 2.1AHALL 200 XS_T XW10 53 2.1A
LOBBY 101 XS_B XW11 54 2.1ALOBBY 101 XS_M XW12 55 2.1ALOBBY 101 XS_T XW13 56 2.1AHALL 200 XS_B XW14 57 2.1AHALL 200 XS_T XW15 58 2.1AOPEN 219 E1_B 2E01 59 2.1BOPEN 219 E1_T 2E02 60 2.1BOPEN 219 E1_B 2E03 61 2.1BOPEN 219 E1_T 2E04 62 2.1BOPEN 219 E1_B 2E05 63 2.1BOPEN 219 E1_T 2E06 64 2.1BOPEN 219 E1_B 2E07 65 2.1BOPEN 219 E1_T 2E08 66 2.1BOPEN 219 E2_B 2E09 67 2.1BOPEN 219 E2_T 2E10 68 2.1BOPEN 219 E2_B 2E11 69 2.1BOPEN 219 E2_T 2E12 70 2.1BOPEN 219 E2_B 2E13 71 2.1BOPEN 219 E2_T 2E14 72 2.1BOPEN 219 E2_B 2E15 73 2.1BOPEN 219 E2_T 2E16 74 2.1BOPEN 219 E3_B 2E17 75 2.1BOPEN 219 E3_T 2E18 76 2.1BOPEN 219 E3_B 2E19 77 2.1BOPEN 219 E3_T 2E20 78 2.1BOPEN 219 E3_B 2E21 79 2.1BOPEN 219 E3_T 2E22 80 2.1BOPEN 219 E3_B 2E23 81 2.1BOPEN 219 E3_T 2E24 82 2.1BOPEN 219 N1_B 2N25 83 2.1BOPEN 219 N1_T 2N26 84 2.1BOPEN 219 N1_B 2N27 85 2.1BOPEN 219 N1_T 2N28 86 2.1BOPEN 219 N1_B 2N29 87 2.1BOPEN 219 N1_T 2N30 88 2.1BOPEN 219 N1_B 2N31 89 2.1BOPEN 219 N1_T 2N32 90 2.1BOPEN 219 N2_B 2N33 91 2.1BOPEN 219 N2_T 2N34 92 2.1BOPEN 219 N2_B 2N35 93 2.1BOPEN 219 N2_T 2N36 94 2.1BOPEN 219 N2_B 2N37 95 2.1BOPEN 219 N2_T 2N38 96 2.1BOPEN 219 N2_B 2N39 97 2.1BOPEN 219 N2_T 2N40 98 2.1BOPEN 219 N3_B 2N41 99 2.1BOPEN 219 N3_T 2N42 100 2.1BOPEN 219 N3_B 2N43 101 2.1BOPEN 219 N3_T 2N44 102 2.1BOPEN 219 N3_B 2N45 103 2.1BOPEN 219 N3_T 2N46 104 2.1BOPEN 219 N3_B 2N47 105 2.1BOPEN 219 N3_T 2N48 106 2.1B
107108109110111112113114115116117118119120121122123124125126127128
OFC 217 E 2E25 129 2.1COFC 217 E 2E26 130 2.1COFC 217 E 2E27 131 2.1COFC 217 E 2E28 132 2.1COFC 216 E 2E29 133 2.1COFC 216 E 2E30 134 2.1COFC 216 E 2E31 135 2.1COFC 216 E 2E32 136 2.1COFC 215 E 2E33 137 2.1COFC 215 E 2E34 138 2.1COFC 215 E 2E35 139 2.1COFC 215 E 2E36 140 2.1COFC 215 E 2E37 141 2.1COFC 215 S1 2S01 142 2.1COFC 215 S1 2S02 143 2.1COFC 215 S2 2S03 144 2.1COFC 215 S2 2S04 145 2.1COFC 215 S3 2S05 146 2.1COFC 215 S3 2S06 147 2.1COFC 215 S4 2S07 148 2.1COFC 215 S4 2S08 149 2.1COFC 214 S 2S09 150 2.1COFC 214 S 2S10 151 2.1COFC 214 S 2S11 152 2.1COFC 214 S 2S12 153 2.1COFC 214 S 2S13 154 2.1C
HALL 221 S1 2S14 155 2.1CHALL 221 S1 2S15 156 2.1CHALL 221 S1 2S16 157 2.1DHALL 221 S1 2S17 158 2.1DHALL 221 S1 2S18 159 2.1DHALL 221 S2 2S19 160 2.1DHALL 221 S2 2S20 161 2.1DHALL 221 S2 2S21 162 2.1DHALL 221 S2 2S22 163 2.1DHALL 221 S2 2S23 164 2.1DHALL 221 S3 2S24 165 2.1DHALL 221 S3 2S25 166 2.1DHALL 221 S3 2S26 167 2.1DHALL 221 S3 2S27 168 2.1DHALL 221 S3 2S28 169 2.1DOFC 213 S 2S29 170 2.1DOFC 213 S 2S30 171 2.1DOFC 213 S 2S31 172 2.1DOFC 213 S 2S32 173 2.1DOFC 213 S 2S33 174 2.1D
BOARD 225 W1 2W01 175 2.1DBOARD 225 W1 2W02 176 2.1DBOARD 225 W2 2W03 177 2.1DBOARD 225 W2 2W04 178 2.1D
OFC 209 W 2W05 179 2.1DOFC 209 W 2W06 180 2.1DOFC 208 W 2W07 181 2.1DOFC 208 W 2W08 182 2.1DOFC 208 W 2W09 183 2.1DOFC 207 W 2W10 184 2.1DOFC 207 W 2W11 185 2.1DOFC 207 W 2W12 186 2.1DOFC 206 W 2W13 187 2.1DOFC 206 W 2W14 188 2.1DOFC 205 W 2W15 189 2.1DOFC 205 W 2W16 190 2.1D
191192193194195196197198199200201202203204205206207208209210211212213214215216217218219220221222223224225226227228229230231232233234235236237238239240241242243244245246247248249250251252253254255256
30 of 37 ©2019 View, Inc.Rev 6 | Aug 2019
OVERVIEW GUIDE
Typical System Layout
WT WT WT WT WT#X
##
#X##
#X##
#X##
#X##
#X##
#X##
#X##
01P
RE
LIM
INA
RY
00.0
0.19
THA
RR
ELL
TH
VIE
W T
RA
ININ
G P
RO
JEC
T18
330
NO
THIN
G R
OA
DS
OM
EW
HE
RE
, CA
950
00
DR
AW
ING
RE
LEA
SE
SD
ES
CR
IPTI
ON
NO
.D
ATE
RE
LEA
SE
#
DR
AW
N:
DE
SIG
N:
RE
VIE
W:
ISS
UE
DA
TE:
INFO
RM
ATI
ON
®
VIEW, INC. ®195 SOUTH MILPITAS BLVD.MILPITAS, CA 95035PH: 408-263-9200WWW.VIEWGLASS.COM
PLO
T D
ATE
:
SFI
D:
VIE
W D
OC
UM
EN
T N
UM
BE
R
SH
EE
T TI
TLE
:
SHEET NUMBER:
VIEW, INC. CONFIDENTIAL:THIS DOCUMENT AND THE INFORMATIONCONTAINED IN IT ARE CONFIDENTIAL,AND CANNOT BE COPIED OR DISCLOSEDIN WHOLE OR IN PART WITHOUT THEEXPRESS WRITTEN CONSENT OFVIEW, INC. ® © - VIEW, INC.
XG-8.1.1
4.29
.201
9 12
:41
PM
2019
00.0
0.19
E.C. TO PROVIDE120VAC, 60Hz, 20 AMPCKT. CRITICAL POWERSOURCE PREFERRED.
E.C. TO PROVIDEETHERNET DROP(S) ATWINDOW CONTROLPANEL LOCATION - SEENETWORK DIAGRAM.
(1) ETHERNET DROP ATWINDOW CONTROLPANEL TO CONNECT TORING SENSORLOCATION.
TRUNK TERMINATOR -INSTALL IN ACCESSIBLELOCATION
KEY NOTES
1
2
3
4
0134
0-10
133313
0067
130
THTY
PIC
AL
SY
STE
M L
AY
OU
T
WINDOW CONTROLPANEL
CP NAME
SCALE:1 TYPICAL SYSTEM LAYOUTNONE
PI
PI
PI
PI
PI
PI
PI PI PI PI PI PI PI PI PI PI PI PI PI PI PI PI PI PI PI PI PI PI PI PI PI
DB-8
X'X"
WC-B
WT WT WT WT WT WT WT WT WT WT WT WT WT WT WTWT WT WT WT WT WT
WT
WT
WT
WT
WT
#X##
#X##
#X##
#X##
#X##
#X##
#X##
#X##
w#X##
w#X##
w#X##
w#X##
w#X##
w#X##
w#X##
w#X##
L.V.GLAZIER
w#X##
w#X##
w#X##
w#X##
w#X##
w#X##
w#X##
w#X##
PT-14 LT-M
TRU
NK
# (S
EE
FLO
OR
PLA
NS
)
PO
WE
R IN
SE
RT
# (S
EE
FLO
OR
PLA
NS
)
12" IGU SMART WINDOWCONNECTOR (SWC),
ORIGIN 3" FROM EDGE OFGLASS, M8 MALE KEYED
CONNECTOR
END OF LINE TERMINATORREQUIRED AT END OF
EACH TRUNK
TRUNK CABLE TO NEXTINTERCONNECT PATTERN
POWER INSERT REQUIRED EVERY16-18 WINDOW CONTROLLERSAS SHOWN ON FLOOR PLANS
POWER TEE
POWER INSERT CABLE
LC-1
#X## WC-B
#X## WC-B
LC-2
w#X##
w#X##
TRUNK TEETRUNK WYE
X'X"
IGU CABLE FROMWINDOW CONTROLLERTO IGU SMART WINDOWCONNECTOR (SWC),MAX. 100' TOTAL
WINDOW CONTROLLER,BASE
X'X"
DROP CABLE, 15' MAX.
TRUNK CABLE
L.V.GLAZIER OPTIONAL CABLE TO GLAZIER
OPTIONAL CABLE TO LOWVOLTAGE ELECTRICIAN
2
SKY SENSOR, LOCATED ON ROOF
CA
T6C
AT6
CA
T6C
AT6
CA
T6C
AT6
CA
T6C
AT6
CA
T6C
AT6
CA
T6C
AT6
CA
T6
31
7XG-9.1.1
8XG-9.1.1
CBL-14/4P
1XG-5.1.1
5XG-9.1.1
1XG-9.1.1
DEVICENET DROP BOX
OPTIONAL CABLES TO GLAZIER
OPTIONAL CABLES TO LOWVOLTAGE ELECTRICIAN
1 - 3XG-5.0.2
X'X"
NOTE: CONNECT TRUNK TERMINATORS TO ALLUNUSED TRUNK CONNECTIONS (J9, J10, J1, J2) ONTOP OF CONTROL PANEL.
CP-128N HAS (2) TRUNK CONNECTIONSCP-256N HAS (4) TRUNK CONNECTIONS
3XG-8.2.1
X'X"
WC-B
X'X"
WINDOW CONTROLLER,BASE
WINDOW CONTROLLER,BASE
IGU CABLE FROMWINDOW CONTROLLERTO IGU SMART WINDOWCONNECTOR (SWC),MAX. 100' TOTAL
IGU CABLE FROMWINDOW CONTROLLERTO IGU SMART WINDOWCONNECTOR (SWC),MAX. 100' TOTAL
31 of 37 ©2019 View, Inc.Rev 6 | Aug 2019
OVERVIEW GUIDE
Glazier IGU Connection Diagrams
IGU NAME
IGU NAME
1 2
IGU SMART WINDOW CONNECTOR(SWC), CONNECT TO IGU CABLE INGLASS POCKET. EXIT TO CLOSESTVERTICAL FRAME.
IGU SMART WINDOW CONNECTOR(SWC), CONNECT TO IGU CABLE INGLASS POCKET. OPTIONALLYGATHER ALL IGU CABLES TO SAMEVERTICAL FRAME.
MIN. 7/16" DIA. HOLES OR SLOTFOR IGU CABLES AT ALLVERTICALS. FILE ALL EDGESSMOOTH. GROMMETSRECOMMENDED.
IGU CABLE TO EXIT VERTICALS ATTOP OR THROUGH DRILLED HOLEON FRAME FACE ABOVE CEILINGLINE OR IN OTHER HIDDENLOCATION. GROMMETSRECOMMENDED AT ALL FRAMEPENETRATIONS TO PREVENTCABLE DAMAGE.
KEY NOTES
1
CAPTURED CURTAINWALL GLAZING STRUCTURAL SILICONE GLAZING TYPICAL ENTRY DOORS, DUAL TYPICAL SINGLE DOOR, OPTIONAL CABLE ROUTINGCORNER
(SEE ELEVATIONS)
(SEE ELEVATIONS)
IGU NAME
(SEE ELEVATIONS)
A. HORIZONTAL MULLION
C. VERTICAL MULLION E. VERTICAL MULLION, SSGD. LEFT JAMB
B. HORIZONTAL MULLION, SSG
ALTERNATE IGUSMART WINDOWCONNECTOR(SWC) LOCATION.SEE ELEVATIONSFOR ORIENTATION.
OPTIONAL WINDOW CONTROLLERLOCATION WITHIN REMOVABLE COVER
TYPICAL FIXEDWINDOW ASSEMBLY,
BY OTHERS
TYPICAL FIXEDWINDOW ASSEMBLY,
BY OTHERS(PORTRAIT ORIENTATION) (LANDSCAPE ORIENTATION)
IGU SMART WINDOWCONNECTOR (SWC) LOCATION.CONNECT IGU CABLE TOSMART WINDOW CONNECTOR(SWC) AND ROUTE INACCESSIBLE LOCATIONFOR FUTURE MAINTENANCEACCESS.
ALTERNATE IGU SMARTWINDOW CONNECTOR (SWC)LOCATION. SEE ELEVATIONSFOR ORIENTATION.
X'X"
IGU NAME
(SEE ELEVATIONS)
IGU NAME
(SEE ELEVATIONS)
X'X"IGU CABLE FROM WINDOWCONTROLLER TO IGU SMARTWINDOW CONNECTOR (SWC), MIN. 1',MAX. 100' LENGTH.
IGU SMART WINDOW CONNECTOR (SWC)LOCATION. CONNECT IGU CABLE TO SMARTWINDOW CONNECTOR (SWC) AND ROUTE INACCESSIBLE LOCATION FOR FUTUREMAINTENANCE ACCESS.
ALTERNATE IGU SMARTWINDOW CONNECTOR (SWC)LOCATION. SEE ELEVATIONSFOR ORIENTATION. DOWNWARDSMART WINDOW CONNECTOR(SWC) ORIENTATION NOTRECOMMENDED DUE TOPOSSIBLE DRAINAGE ISSUES.
IGU CABLE FROM WINDOWCONTROLLER TO IGU SMARTWINDOW CONNECTOR (SWC), MIN. 1',MAX. 100' LENGTH.
2
3
4
1 1
11
4 44 4 4
21
3 3 3 3
SEE DETAIL D SEE DETAIL A
SEE DETAIL C SEE DETAIL E
SEE DETAIL B
33
IGU CABLE TRANSFER FROMUPPER DOOR TO FRAME.SEE GLAZIER BOMs FORINCLUDED TYPE AND FINISH.
OPTIONAL IGU CABLETRANSFER LOCATION ATLOWER DOOR TO FRAME.
44 4
1 1
IGU CABLE TRANSFER FROMUPPER DOOR TO FRAME.SEE GLAZIER BOMs FORINCLUDED TYPE AND FINISH.
X'X"IGU CABLE THROUGHDOOR.
IGU NAME IGU NAME
(SEE ELEVATIONS) (SEE ELEVATIONS)
IGU NAME
(SEE ELEVATIONS)
IGU NAME
(SEE ELEVATIONS)
01P
RE
LIM
INA
RY
00.0
0.19
THA
RR
ELL
TH
VIE
W T
RA
ININ
G P
RO
JEC
T18
330
NO
THIN
G R
OA
DS
OM
EW
HE
RE
, CA
950
00
DR
AW
ING
RE
LEA
SE
SD
ES
CR
IPTI
ON
NO
.D
ATE
RE
LEA
SE
#
DR
AW
N:
DE
SIG
N:
RE
VIE
W:
ISS
UE
DA
TE:
INFO
RM
ATI
ON
®
VIEW, INC. ®195 SOUTH MILPITAS BLVD.MILPITAS, CA 95035PH: 408-263-9200WWW.VIEWGLASS.COM
PLO
T D
ATE
:
SFI
D:
VIE
W D
OC
UM
EN
T N
UM
BE
R
SH
EE
T TI
TLE
:
SHEET NUMBER:
VIEW, INC. CONFIDENTIAL:THIS DOCUMENT AND THE INFORMATIONCONTAINED IN IT ARE CONFIDENTIAL,AND CANNOT BE COPIED OR DISCLOSEDIN WHOLE OR IN PART WITHOUT THEEXPRESS WRITTEN CONSENT OFVIEW, INC. ® © - VIEW, INC.
XG-8.2.1
4.29
.201
9 12
:41
PM
2019
00.0
0.19
0134
0-10
133313
0067
130
THG
LAZI
ER
IGU
CO
NN
EC
TIO
ND
IAG
RA
MS
SCALE:1 TYPICAL CURTAINWALL CABLE ROUTING, KAWNEER 1600 SERIES EXAMPLENONE SCALE:2 TYPICAL DOOR CABLE ROUTING, KAWNEER 350 DOORS EXAMPLE
NONE
SCALE:3 TYPICAL WINDOW IGU INTERCONNECTSNONE
32 of 37 ©2019 View, Inc.Rev 6 | Aug 2019
OVERVIEW GUIDE
Device Details and Symbology
01P
RE
LIM
INA
RY
00.0
0.19
THA
RR
ELL
TH
VIE
W T
RA
ININ
G P
RO
JEC
T18
330
NO
THIN
G R
OA
DS
OM
EW
HE
RE
, CA
950
00
DR
AW
ING
RE
LEA
SE
SD
ES
CR
IPTI
ON
NO
.D
ATE
RE
LEA
SE
#
DR
AW
N:
DE
SIG
N:
RE
VIE
W:
ISS
UE
DA
TE:
INFO
RM
ATI
ON
®
VIEW, INC. ®195 SOUTH MILPITAS BLVD.MILPITAS, CA 95035PH: 408-263-9200WWW.VIEWGLASS.COM
PLO
T D
ATE
:
SFI
D:
VIE
W D
OC
UM
EN
T N
UM
BE
R
SH
EE
T TI
TLE
:
SHEET NUMBER:
VIEW, INC. CONFIDENTIAL:THIS DOCUMENT AND THE INFORMATIONCONTAINED IN IT ARE CONFIDENTIAL,AND CANNOT BE COPIED OR DISCLOSEDIN WHOLE OR IN PART WITHOUT THEEXPRESS WRITTEN CONSENT OFVIEW, INC. ® © - VIEW, INC.
XG-9.1.1
4.29
.201
9 12
:41
PM
2019
00.0
0.19
0134
0-10
133313
0067
130
THD
EV
ICE
DE
TAIL
S A
ND
SY
MB
OLO
GY
SCALE:1 DEVICENET DROP BOX1:1 SCALE:2 TRUNK ELBOW 90°
1:1 SCALE:3 POWER INSERT WYE1:1
SCALE:7 POWER INSERT TEE1:1SCALE:6 DROP WYE (LRG - MED)
1:1SCALE:5 DROP WYE (LRG - MED)1:1SCALE:4 DROP TEE (LRG - MED)
1:1
SCALE:8 TRUNK TERMINATOR (LRG, MALE)1:1 SCALE:9 TRUNK CORDSET
1:1 SCALE:10 DROP CORDSET1:1 SCALE:11 IGU CORDSET
1:1
SCALE:12 WINDOW CONTROLLER, BASE v2.01:1
LC-1 LC-2 LC-3 PT-1
DB-8 LC-4 PY-1
LT-M
WC-B
4XG-9.2.1
5XG-9.2.1
6XG-9.2.1
CAP-M-2
WT
MALE CONNECTOR FACESTOWARD CONTROL PANEL
MALE CONNECTOR FACESTOWARD CONTROL PANEL
MALE CONNECTOR FACESTOWARD CONTROL PANEL
PART NO: 370-000024 PART NO: 370-000026 PART NO: 370-000030
PART NO: 370-000025 PART NO: 370-000021 PART NO: 370-000022 PART NO: 370-000002
PART NO: 380-000038-XX (PLENUM)PART NO: 370-000008 PART NO: 380-101510-XX (PLENUM) PART NO: 380-101509-XX (PLENUM)
PART NO: 380-000057-XX (STANDARD) PART NO: 380-101512-XX (STANDARD) PART NO: 380-101511-XX (STANDARD)
ALL TRUNK ENDS TO BE TERMINATED. UNUSED TRUNKCONNECTORS ON CONTROL PANELS TO BE TERMINATED.TERMINATORS ARE PROVIDED BY VIEW AND SHOULD BEPLACED IN AN ACCESSIBLE (BY NONDESTRUCTIVE MEANS)LOCATION IN CASE THEY NEED TO BE REACHED FORMAINTENANCE AND/OR TROUBLESHOOTING PURPOSES.
634"
2716
"
1132
"
WT
WT
PLACE A DUST PROTECTIONCAP (PROVIDED BY VIEW) ONALL UNUSED PORTS.
23132"
1916"
278"
1916"
115 16
"
1516
"
131 32
"1516
"
127
32"
1916"
22932"
7/8" CONNECTOR, MALE
M12 CONNECTOR, FEMALE
7/8" CONNECTOR, MALE
11516"
1.06
"
1.06
"
11516" 115
16"
1.06
"
117
32"
M12 CONNECTOR, FEMALE
7/8" CONNECTOR, MALE
7/8" CONNECTOR, FEMALE
6"
34"
34"
KEYED M8 CONNECTOR, FEMALE
KEYED M8 CONNECTOR, FEMALE
KEYED M8 CONNECTOR, MALE
KEYED M8 CONNECTOR, MALE
PART NO: 010-101584
7/8" CONNECTOR, FEMALE7/8" CONNECTOR, MALE
1.06
"
7/8" CONNECTOR, FEMALE
M12 CONNECTOR, FEMALE
M12 CONNECTOR, FEMALE
7/8" CONNECTOR, FEMALE7/8" CONNECTOR, MALE
7/8" CONNECTOR, MALE 7/8" CONNECTOR, FEMALE
1916"
21516"
115 16
"1.
06"
WC-#X##
LENGTH PER BOM DESCRIPTION
12532" 19
32"
LENGTH PER BOM DESCRIPTION
KEYED M8 CONNECTOR, FEMALEM12 CONNECTOR, MALE
11332" 19
32"
LENGTH PER BOM DESCRIPTION
KEYED M8 CONNECTOR, FEMALEKEYED M8 CONNECTOR, MALE
214"
2"
3"
218"
6" 6"
7/8" POWERCONNECTOR, MALE
7/8" CONNECTOR, MALE
7/8" CONNECTOR, FEMALE
7/8" CONNECTOR, FEMALE
7/8" POWERCONNECTOR, MALE
7/8" CONNECTOR, MALE
1916"
7/8" CONNECTOR, MALE
7/8" CONNECTOR, FEMALE
X'X"
X'X" P
X'X"
X'X" P
X'X"
X'X" P
1.06"
1.06"
1.06"
1.06
"
1.06
"
9 16"
0.38
"
0.38
"
0.38
"
0.25"Ø PLENUM0.31"Ø STANDARD
0.25"Ø PLENUM0.31"Ø STANDARD
0.41"Ø PLENUM0.45"Ø STANDARD
33 of 37 ©2019 View, Inc.Rev 6 | Aug 2019
OVERVIEW GUIDE
Field Wireable Connections and Preterminated Cordset
01P
RE
LIM
INA
RY
00.0
0.19
THA
RR
ELL
TH
VIE
W T
RA
ININ
G P
RO
JEC
T18
330
NO
THIN
G R
OA
DS
OM
EW
HE
RE
, CA
950
00
DR
AW
ING
RE
LEA
SE
SD
ES
CR
IPTI
ON
NO
.D
ATE
RE
LEA
SE
#
DR
AW
N:
DE
SIG
N:
RE
VIE
W:
ISS
UE
DA
TE:
INFO
RM
ATI
ON
®
VIEW, INC. ®195 SOUTH MILPITAS BLVD.MILPITAS, CA 95035PH: 408-263-9200WWW.VIEWGLASS.COM
PLO
T D
ATE
:
SFI
D:
VIE
W D
OC
UM
EN
T N
UM
BE
R
SH
EE
T TI
TLE
:
SHEET NUMBER:
VIEW, INC. CONFIDENTIAL:THIS DOCUMENT AND THE INFORMATIONCONTAINED IN IT ARE CONFIDENTIAL,AND CANNOT BE COPIED OR DISCLOSEDIN WHOLE OR IN PART WITHOUT THEEXPRESS WRITTEN CONSENT OFVIEW, INC. ® © - VIEW, INC.
XG-9.2.1
4.29
.201
9 12
:41
PM
2019
00.0
0.19
0134
0-10
133313
0067
130
THFI
ELD
WIR
EA
BLE
CO
NN
EC
TIO
NS
AN
DP
RE
TER
MIN
ATE
DC
OR
DS
ETS
M12, MALE M8 FEMALE, KEYED M8 FEMALE, KEYEDM8 MALE, KEYED7/8, MALE 7/8, FEMALE
V-V+V+
V-
1234 GRN 14 AWG
BLK 14 AWG
RED 14 AWGWHT 14 AWG
V-V+V+
V-
1234GRN 14 AWG
BLK 14 AWG
RED 14 AWGWHT 14 AWG
12345
12345
CAN_H
V+
CAN_L
V-
SHIELD
CAN_H
V+
CAN_L
V-
SHIELDRED 14 AWGBLK 14 AWGWHT 18 AWGBLU 18 AWG
BARERED 14 AWGBLK 14 AWG
WHT 18 AWGBLU 18 AWG
BARE
FIND NUMBER (LENGTH)ON COLORED WRAP,
BOTH ENDS OF CABLE
PART NO: 380-000038-XX (PLENUM) PART NO: 380-101510-XX (PLENUM) PART NO: 380-101509-XX (PLENUM)
PART NO: 380-000057-XX (STANDARD) PART NO: 380-101512-XX (STANDARD) PART NO: 380-101511-XX (STANDARD)
1. MACHINE PRINTED LABEL SHOULD BE LOCATED WITHIN 4" OF CABLE END.2. EACH LABEL SHOULD BE MACHINE PRINTED - BLACK PRINT ON WHITE MATERIAL.3. USE PROPORTIONAL FONT, MINIMUM 14 PT BOLD.4. CABLE IDENTIFIER SHOULD APPEAR TWO TIMES ON THE LABEL FOR VISIBILITY.5. LABELS SHOULD BE OF PERMANENT TYPE MATERIAL.6. HAND WRITTEN LABELS SHOULD NOT BE USED.7. DO NOT MAKE LABELS FROM MASKING TAPE, ELECTRICAL TAPE, DUCT TAPE,
PAPER COVERED SCOTCH TAPE OR ANY NON LABEL MATERIAL.8. WIRE MARKER TAPE CAN BE USED FOR IGU CABLES. USE NUMBER TO MATCH
IGU MARKING ON INTERCONNECT.9. LABELS AND MARKER TAPE NOT PROVIDED BY VIEW.10. TESTED LABEL, PROVIDED BY VIEW, TO BE PLACED ON EACH END OF CABLE
AFTER INSTALLATION AND TESTING.
SCALE:1 FIELD TERMINATED TRUNK (2x14 AWG / 2x18 AWG) CONNECTIONNONE SCALE:2 FIELD TERMINATED POWER CONNECTION
NONE SCALE:3 REQURED CABLE LABELINGNONE
SCALE:6 IGU CORDSET DETAIL AND DESCRIPTION LISTNONESCALE:5 DROP CORDSET DETAIL AND DESCRIPTION LIST
NONESCALE:4 TRUNK CORDSET DETAIL AND DESCRIPTION LISTNONE
STANDARD PLENUM DESCRIPTIONT-1'0" T-1'0"P TRUNK CABLE, LRG CONN, 5P MF, 1' 0" (0.3M)T-2'0" T-2'0"P TRUNK CABLE, LRG CONN, 5P MF, 2' 0" (0.6M)T-3'3" T-3'3"P TRUNK CABLE, LRG CONN, 5P MF, 3' 3" (1M)
T-4'11" T-4'11"P TRUNK CABLE, LRG CONN, 5P MF, 4' 11" (1.5M)T-6'6" T-6'6"P TRUNK CABLE, LRG CONN, 5P MF, 6' 6" (2M)T-8'2" T-8'2"P TRUNK CABLE, LRG CONN, 5P MF, 8' 2" (2.5M)
T-9'10" T-9'10"P TRUNK CABLE, LRG CONN, 5P MF, 9' 10" (3M)T-11'5" T-11'5"P TRUNK CABLE, LRG CONN, 5P MF, 11' 5" (3.5M)T-13'1" T-13'1"P TRUNK CABLE, LRG CONN, 5P MF, 13' 1" (4M)T-14'9" T-14'9"P TRUNK CABLE, LRG CONN, 5P MF, 14' 9" (4.5M)T-16'4" T-16'4"P TRUNK CABLE, LRG CONN, 5P MF, 16' 4" (5M)T-18'0" T-18'0"P TRUNK CABLE, LRG CONN, 5P MF, 18' 0" (5.5M)T-19'8" T-19'8"P TRUNK CABLE, LRG CONN, 5P MF, 19' 8" (6M)T-21'3" T-21'3"P TRUNK CABLE, LRG CONN, 5P MF, 21' 3" (6.5M)T-22'11" T-22'11"P TRUNK CABLE, LRG CONN, 5P MF, 22' 11" (7M)T-24'7" T-24'7"P TRUNK CABLE, LRG CONN, 5P MF, 24' 7" (7.5M)T-26'2" T-26'2"P TRUNK CABLE, LRG CONN, 5P MF, 26' 2" (8M)T-27'10" T-27'10"P TRUNK CABLE, LRG CONN, 5P MF, 27' 10" (8.5M)T-29'6" T-29'6"P TRUNK CABLE, LRG CONN, 5P MF, 29' 6" (9M)T-31'2" T-31'2"P TRUNK CABLE, LRG CONN, 5P MF, 31' 2" (9.5M)T-32'9" T-32'9"P TRUNK CABLE, LRG CONN, 5P MF, 32' 9" (10M)T-65'7" T-65'7"P TRUNK CABLE, LRG CONN, 5P MF, 65' 7" (20M)T-98'5" T-98'5"P TRUNK CABLE, LRG CONN, 5P MF, 98' 5" (30M)T-131'2" T-131'2"P TRUNK CABLE, LRG CONN, 5P MF, 131' 2" (40M)T-164'0" T-164'0"P TRUNK CABLE, LRG CONN, 5P MF, 164' 0" (50M)
T-8"P TRUNK CABLE, PLENUM, STUB, LRG CONN, 5P MF
STANDARD PLENUM DESCRIPTIOND-1'0" D-1'0"P DROP CABLE, MED CONN, 5P M, SML CONN, 5PK F, 1' 0" (0.3M)D-2'0" D-2'0"P DROP CABLE, MED CONN, 5P M, SML CONN, 5PK F, 2' 0" (0.6M)D-3'3" D-3'3"P DROP CABLE, MED CONN, 5P M, SML CONN, 5PK F, 3' 3" (1M)D-4'11" D-4'11"P DROP CABLE, MED CONN, 5P M, SML CONN, 5PK F, 4' 11" (1.5M)D-6'6" D-6'6"P DROP CABLE, MED CONN, 5P M, SML CONN, 5PK F, 6' 6" (2M)D-8'2" D-8'2"P DROP CABLE, MED CONN, 5P M, SML CONN, 5PK F, 8' 2" (2.5M)D-9'10" D-9'10"P DROP CABLE, MED CONN, 5P M, SML CONN, 5PK F, 9' 10" (3M)D-11'5" D-11'5"P DROP CABLE, MED CONN, 5P M, SML CONN, 5PK F, 11' 5" (3.5M)D-13'1" D-13'1"P DROP CABLE, MED CONN, 5P M, SML CONN, 5PK F, 13' 1" (4M)D-14'9" D-14'9"P DROP CABLE, MED CONN, 5P M, SML CONN, 5PK F, 14' 9" (4.5M)D-16'4" D-16'4"P DROP CABLE, MED CONN, 5P M, SML CONN, 5PK F, 16' 4" (5M)D-18'0" D-18'0"P DROP CABLE, MED CONN, 5P M, SML CONN, 5PK F, 18' 0" (5.5M)D-19'8" D-19'8"P DROP CABLE, MED CONN, 5P M, SML CONN, 5PK F, 19' 8" (6M)D-21'3" D-21'3"P DROP CABLE, MED CONN, 5P M, SML CONN, 5PK F, 21' 3" (6.5M)D-22'11" D-22'11"P DROP CABLE, MED CONN, 5P M, SML CONN, 5PK F, 22' 11" (7M)D-24'7" D-24'7"P DROP CABLE, MED CONN, 5P M, SML CONN, 5PK F, 24' 7" (7.5M)D-26'2" D-26'2"P DROP CABLE, MED CONN, 5P M, SML CONN, 5PK F, 26' 2" (8M)D-27'10" D-27'10"P DROP CABLE, MED CONN, 5P M, SML CONN, 5PK F, 27' 10" (8.5M)D-29'6" D-29'6"P DROP CABLE, MED CONN, 5P M, SML CONN, 5PK F, 29' 6" (9M)D-31'2" D-31'2"P DROP CABLE, MED CONN, 5P M, SML CONN, 5PK F, 31' 2" (9.5M)D-32'9" D-32'9"P DROP CABLE, MED CONN, 5P M, SML CONN, 5PK F, 32' 9" (10M)
STANDARD PLENUM DESCRIPTIONI-1'0" I-1'0"P IGU CABLE, SML CONN, 5PK MF, 1' 0" (0.3M)I-2'0" I-2'0"P IGU CABLE, SML CONN, 5PK MF, 2' 0" (0.6M)I-3'3" I-3'3"P IGU CABLE, SML CONN, 5PK MF, 3' 3" (1M)I-4'11" I-4'11"P IGU CABLE, SML CONN, 5PK MF, 4' 11" (1.5M)I-6'6" I-6'6"P IGU CABLE, SML CONN, 5PK MF, 6' 6" (2M)I-8'2" I-8'2"P IGU CABLE, SML CONN, 5PK MF, 8' 2" (2.5M)I-9'10" I-9'10"P IGU CABLE, SML CONN, 5PK MF, 9' 10" (3M)I-11'5" I-11'5"P IGU CABLE, SML CONN, 5PK MF, 11' 5" (3.5M)I-13'1" I-13'1"P IGU CABLE, SML CONN, 5PK MF, 13' 1" (4M)I-14'9" I-14'9"P IGU CABLE, SML CONN, 5PK MF, 14' 9" (4.5M)I-16'4" I-16'4"P IGU CABLE, SML CONN, 5PK MF, 16' 4" (5M)I-18'0" I-18'0"P IGU CABLE, SML CONN, 5PK MF, 18' 0" (5.5M)I-19'8" I-19'8"P IGU CABLE, SML CONN, 5PK MF, 19' 8" (6M)I-21'3" I-21'3"P IGU CABLE, SML CONN, 5PK MF, 21' 3" (6.5M)I-22'11" I-22'11"P IGU CABLE, SML CONN, 5PK MF, 22' 11" (7M)I-24'7" I-24'7"P IGU CABLE, SML CONN, 5PK MF, 24' 7" (7.5M)I-26'2" I-26'2"P IGU CABLE, SML CONN, 5PK MF, 26' 2" (8M)I-27'10" I-27'10"P IGU CABLE, SML CONN, 5PK MF, 27' 10" (8.5M)I-29'6" I-29'6"P IGU CABLE, SML CONN, 5PK MF, 29' 6" (9M)I-31'2" I-31'2"P IGU CABLE, SML CONN, 5PK MF, 31' 2" (9.5M)I-32'9" I-32'9"P IGU CABLE, SML CONN, 5PK MF, 32' 9" (10M)I-35'0" I-35'0"P IGU CABLE, SML CONN, 5PK MF, 35' 0" (10.66M)I-40'0" I-40'0"P IGU CABLE, SML CONN, 5PK MF, 40' 0" (12.19M)I-45'0" I-45'0"P IGU CABLE, SML CONN, 5PK MF, 45' 0" (13.71M)I-50'0" I-50'0"P IGU CABLE, SML CONN, 5PK MF, 50' 0" (15.24M)I-55'0" I-55'0"P IGU CABLE, SML CONN, 5PK MF, 55' 0" (16.76M)I-60'0" I-60'0"P IGU CABLE, SML CONN, 5PK MF, 60' 0" (18.28M)I-65'0" I-65'0"P IGU CABLE, SML CONN, 5PK MF, 65' 0" (19.81M)I-70'0" I-70'0"P IGU CABLE, SML CONN, 5PK MF, 70' 0" (21.33M)I-75'0" I-75'0"P IGU CABLE, SML CONN, 5PK MF, 75' 0" (22.86M)I-80'0" I-80'0"P IGU CABLE, SML CONN, 5PK MF, 80' 0" (24.38M)I-85'0" I-85'0"P IGU CABLE, SML CONN, 5PK MF, 85' 0" (25.90M)I-90'0" I-90'0"P IGU CABLE, SML CONN, 5PK MF, 90' 0" (27.43M)I-95'0" I-95'0"P IGU CABLE, SML CONN, 5PK MF, 95' 0" (28.95M)I-100'0" I-100'0"P IGU CABLE, SML CONN, 5PK MF, 100' 0" (30.48M)
MALE CONNECTOR FACESTOWARD CONTROL PANEL
WT
MALE CONNECTOR FACESTOWARD CONTROL PANEL
MALE CONNECTOR FACESTOWARD CONTROL PANEL
1.06
"Ø
FIND NUMBER (LENGTH)ON COLORED WRAP,
BOTH ENDS OF CABLE
X'X"
X'X" P
X'X"
X'X" P
X'X"
X'X" P
0.25"Ø PLENUM0.31"Ø STANDARD
BEND RADIUS, STANDARD 2.5"
BEND RADIUS, PLENUM 3.75"
FIND NUMBER (LENGTH)ON COLORED WRAP,
BOTH ENDS OF CABLE
0.41"Ø PLENUM0.45"Ø STANDARD
TO CONTROL PANEL AWAY FROMCONTROL PANEL
CABLE ORIENTATION LABEL,BOTH ENDS OF CABLEMANUFACTURER AND DATE
CODE, BOTH ENDS OF CABLE0.25"Ø PLENUM
0.31"Ø STANDARD
TO CONTROL PANEL
MANUFACTURER AND DATECODE, BOTH ENDS OF CABLE
AWAY FROMCONTROL PANEL
CABLE ORIENTATION LABEL,BOTH ENDS OF CABLE
BEND RADIUS, STANDARD 2.5"
BEND RADIUS, PLENUM 3.75"
BEND RADIUS, PLENUM 6.15"
BEND RADIUS, STANDARD 3.6"
TO CONTROL PANEL
MANUFACTURER AND DATECODE, BOTH ENDS OF CABLE
AWAY FROMCONTROL PANEL
CABLE ORIENTATION LABEL,BOTH ENDS OF CABLE
7/8, MALE 7/8, FEMALE
1. REMOVE THE UPPER SECTION OF CONNECTOR -HOLD THE UPPER SECTION OF THE CONNECTOR INPLACE THEN TWIST THE LOWER SECTION OF THECONNECTOR COUNTERCLOCKWISE.
2. LOOSEN THE NUT FOR THE STRAIN RELIEF ON THELOWER SECTION OF THE CONNECTOR.
3. FEED THE CABLE THRU BOTTOM HOLE.4. CUT THE OUTER JACKET ~ 1.5” TO EXPOSE THE 4
WIRES INSIDE THE CABLE.5. STRIP THE 4 INDIVIDUAL WIRES ~ 1/4” .
6. WITH A SMALL SCREW DRIVER LOOSEN THE SCREWON THE TERMINALS.
7. INSERT AND TIGHTEN THE WIRES IN THE UPPERSECTION OF THE CONNECTOR PER THE SCHEMATIC.
8. DO A PULL TEST MAKING SURE THAT NO STRAYWIRES ARE STICKING OUT.
9. SLIP THE LOWER SECTION OF THE CONNECTORONTO THE UPPER SECTION AND TIGHTEN.
10. TIGHTEN THE STRAIN RELIEF NUT.
PIPIPI
MALE CONNECTOR FACESTOWARD CONTROL PANEL
FW-LC4-1 FW-LC4-2
~3.43" ~3.37"
1.10
"Ø
CBL-14/4P
ASSEMBLY INSTRUCTIONS
CABLE PINOUT
SHIELD
1. REMOVE THE UPPER SECTION OF CONNECTOR -HOLD THE UPPER SECTION OF THE CONNECTOR INPLACE THEN TWIST THE LOWER SECTION OF THECONNECTOR COUNTERCLOCKWISE.
2. LOOSEN THE NUT FOR THE STRAIN RELIEF ON THELOWER SECTION OF THE CONNECTOR.
3. FEED THE CABLE THRU BOTTOM HOLE.4. CUT THE OUTER JACKET ~ 1.5” TO EXPOSE THE 4
WIRES AND SHIELD INSIDE THE CABLE.5. STRIP THE 4 INDIVIDUAL WIRES ~ 14 " AND TWIST THE
SHIELD TO FIT INTO A TERMINAL.
6. WITH A SMALL SCREW DRIVER LOOSEN THE SCREWON THE TERMINALS.
7. INSERT AND TIGHTEN THE WIRES IN THE UPPERSECTION OF THE CONNECTOR PER THE SCHEMATIC.
8. DO A PULL TEST MAKING SURE THAT NO STRAYWIRES ARE STICKING OUT.
9. SLIP THE LOWER SECTION OF THE CONNECTORONTO THE UPPER SECTION AND TIGHTEN.
10. TIGHTEN THE STRAIN RELIEF NUT.
ASSEMBLY INSTRUCTIONS
CABLE PINOUT
SHIELD
~3.43" ~3.37"
1.10
"Ø
7/8, MALE 7/8, FEMALECUT TO LENGTH AS NEEDED
~1.5"
WTWTWT
MALE CONNECTOR FACESTOWARD CONTROL PANEL
FW-LC5-1
FW-LC5-3
~1.5"
PLENUM TRUNK ONLY
STANDARD TRUNK ONLY FW-LC5-2
FW-LC5-4
TO CONTROL PANEL
4" MAXIMUM
4" MAXIMUM
4" MAXIMUM
4" MAXIMUM
2N25
2 5
P.I. 1.1A
TRUNK 1.1A
TRUNK CABLES
WRAPPED LABEL, TRUNK NAME, BOTH ENDS OFFIRST TRUNK SEGMENT FROM CONTROL PANEL
POWER INSERT CABLES
IGU CABLES
IGU CABLES, OPTIONAL
WRAPPED LABEL, POWER INSERT NAME,BOTH ENDS OF CABLE
WRAPPED LABEL, IGU WC NAME, BY GLAZIER,MALE END OF CABLE OUTSIDE OF FRAME
WIRE MARKER TAPE, IGU WC NUMBER, BY GLAZIER,MALE END OF CABLE OUTSIDE OF FRAME
~1.5" ~1.5"
0.41"Ø PLENUM0.45"Ø STANDARD
0.25"Ø
TO CONTROL PANEL
TO CONTROL PANEL
2
1 5
3
42
15
3
4
PART # FIND DESCRIPTION310-000061 FW-LC4-1 CONNECTOR, FIELD WIREABLE, LRG CONN, 4P-M310-000063 FW-LC4-2 CONNECTOR, FIELD WIREABLE, LRG CONN, 4P-F
300-101032-01 CBL-14/4P CABLE, 4 COND, 14AWG, PLENUM, L 500ft300-101032 CBL-14/4P CABLE, 4 COND, 14AWG, PLENUM, L 1000ft
PART # FIND DESCRIPTION310-000047 FW-LC5-1 CONNECTOR, FIELD WIREABLE, LRG CONN, 5P-M310-000051 FW-LC5-2 CONNECTOR, FIELD WIREABLE, LRG CONN, 5P-F310-000071 FW-LC5-3 CONNECTOR, FIELD WIREABLE, LRG CONN, 5P-MALE, 14AWG310-000070 FW-LC5-4 CONNECTOR, FIELD WIREABLE, LRG CONN, 5P-FEMALE, 14AWG
300-101041-01 T-500 CABLE, TRUNK , 2x14AWG, 2x18AWG, SHIELD, NON-PLENUM, 500 FT SPOOL300-101041-02 T-1000 CABLE, TRUNK , 2x14AWG, 2x18AWG, SHIELD, NON-PLENUM, 1000 FT SPOOL300-101042-01 T-P-500 CABLE, TRUNK , 2x14AWG, 2x18AWG, SHIELD, PLENUM, 500 FT SPOOL
2
1
3
4
2
1
3
4
TESTED LABEL
34 of 37 ©2019 View, Inc.Rev 6 | Aug 2019
OVERVIEW GUIDE
List of typically used Data Sheets
• IGU
• IGU Cable
• Drop Cable
• Trunk Cable
• Power Cable
• Door Loop
• Control Panel
• Window Controller
• Sky Sensor
35 of 37 ©2019 View, Inc.Rev 6 | Aug 2019
OVERVIEW GUIDE
Glass Implementation Process
Project Kicko�Meeting(scope,
schedule,planning)
Provide feedback
for ControlsSystem design
Install View controls andassist with functional hardware
testing
Review anditerate on
PreliminaryInterconnect
Drawing
Consolidateinput andproduce
PreliminaryInterconnect
Drawing
Consolidateinput andproduce
FinalInterconnect
Drawing
Manufactureand ship IGU
cables toGlazier
Commissionsystem and
provideturnover
package andoperation
ShipControlsSystem
Provideproduct
informationand designguidelines
Provide facadeshop detail
Finalize IGUorder with
signed OrderAcknowledge-
ment
Install IGUs,functional
check
GCElectrician
LV Contractor
Glazier
View
36 of 37 ©2019 View, Inc.Rev 6 | Aug 2019
OVERVIEW GUIDE
Proper Cable Labeling
01P
RE
LIM
INA
RY
00.0
0.19
THA
RR
ELL
TH
VIE
W T
RA
ININ
G P
RO
JEC
T18
330
NO
THIN
G R
OA
DS
OM
EW
HE
RE
, CA
950
00
DR
AW
ING
RE
LEA
SE
SD
ES
CR
IPTI
ON
NO
.D
ATE
RE
LEA
SE
#
DR
AW
N:
DE
SIG
N:
RE
VIE
W:
ISS
UE
DA
TE:
INFO
RM
ATI
ON
®
VIEW, INC. ®195 SOUTH MILPITAS BLVD.MILPITAS, CA 95035PH: 408-263-9200WWW.VIEWGLASS.COM
PLO
T D
ATE
:
SFI
D:
VIE
W D
OC
UM
EN
T N
UM
BE
R
SH
EE
T TI
TLE
:
SHEET NUMBER:
VIEW, INC. CONFIDENTIAL:THIS DOCUMENT AND THE INFORMATIONCONTAINED IN IT ARE CONFIDENTIAL,AND CANNOT BE COPIED OR DISCLOSEDIN WHOLE OR IN PART WITHOUT THEEXPRESS WRITTEN CONSENT OFVIEW, INC. ® © - VIEW, INC.
XG-9.2.1
4.29
.201
9 12
:41
PM
2019
00.0
0.19
0134
0-10
133313
0067
130
THFI
ELD
WIR
EA
BLE
CO
NN
EC
TIO
NS
AN
DP
RE
TER
MIN
ATE
DC
OR
DS
ETS
M12, MALE M8 FEMALE, KEYED M8 FEMALE, KEYEDM8 MALE, KEYED7/8, MALE 7/8, FEMALE
V-V+V+
V-
1234 GRN 14 AWG
BLK 14 AWG
RED 14 AWGWHT 14 AWG
V-V+V+
V-
1234GRN 14 AWG
BLK 14 AWG
RED 14 AWGWHT 14 AWG
12345
12345
CAN_H
V+
CAN_L
V-
SHIELD
CAN_H
V+
CAN_L
V-
SHIELDRED 14 AWGBLK 14 AWGWHT 18 AWGBLU 18 AWG
BARERED 14 AWGBLK 14 AWG
WHT 18 AWGBLU 18 AWG
BARE
FIND NUMBER (LENGTH)ON COLORED WRAP,
BOTH ENDS OF CABLE
PART NO: 380-000038-XX (PLENUM) PART NO: 380-101510-XX (PLENUM) PART NO: 380-101509-XX (PLENUM)
PART NO: 380-000057-XX (STANDARD) PART NO: 380-101512-XX (STANDARD) PART NO: 380-101511-XX (STANDARD)
1. MACHINE PRINTED LABEL SHOULD BE LOCATED WITHIN 4" OF CABLE END.2. EACH LABEL SHOULD BE MACHINE PRINTED - BLACK PRINT ON WHITE MATERIAL.3. USE PROPORTIONAL FONT, MINIMUM 14 PT BOLD.4. CABLE IDENTIFIER SHOULD APPEAR TWO TIMES ON THE LABEL FOR VISIBILITY.5. LABELS SHOULD BE OF PERMANENT TYPE MATERIAL.6. HAND WRITTEN LABELS SHOULD NOT BE USED.7. DO NOT MAKE LABELS FROM MASKING TAPE, ELECTRICAL TAPE, DUCT TAPE,
PAPER COVERED SCOTCH TAPE OR ANY NON LABEL MATERIAL.8. WIRE MARKER TAPE CAN BE USED FOR IGU CABLES. USE NUMBER TO MATCH
IGU MARKING ON INTERCONNECT.9. LABELS AND MARKER TAPE NOT PROVIDED BY VIEW.10. TESTED LABEL, PROVIDED BY VIEW, TO BE PLACED ON EACH END OF CABLE
AFTER INSTALLATION AND TESTING.
SCALE:1 FIELD TERMINATED TRUNK (2x14 AWG / 2x18 AWG) CONNECTIONNONE SCALE:2 FIELD TERMINATED POWER CONNECTION
NONE SCALE:3 REQURED CABLE LABELINGNONE
SCALE:6 IGU CORDSET DETAIL AND DESCRIPTION LISTNONESCALE:5 DROP CORDSET DETAIL AND DESCRIPTION LIST
NONESCALE:4 TRUNK CORDSET DETAIL AND DESCRIPTION LISTNONE
STANDARD PLENUM DESCRIPTIONT-1'0" T-1'0"P TRUNK CABLE, LRG CONN, 5P MF, 1' 0" (0.3M)T-2'0" T-2'0"P TRUNK CABLE, LRG CONN, 5P MF, 2' 0" (0.6M)T-3'3" T-3'3"P TRUNK CABLE, LRG CONN, 5P MF, 3' 3" (1M)
T-4'11" T-4'11"P TRUNK CABLE, LRG CONN, 5P MF, 4' 11" (1.5M)T-6'6" T-6'6"P TRUNK CABLE, LRG CONN, 5P MF, 6' 6" (2M)T-8'2" T-8'2"P TRUNK CABLE, LRG CONN, 5P MF, 8' 2" (2.5M)
T-9'10" T-9'10"P TRUNK CABLE, LRG CONN, 5P MF, 9' 10" (3M)T-11'5" T-11'5"P TRUNK CABLE, LRG CONN, 5P MF, 11' 5" (3.5M)T-13'1" T-13'1"P TRUNK CABLE, LRG CONN, 5P MF, 13' 1" (4M)T-14'9" T-14'9"P TRUNK CABLE, LRG CONN, 5P MF, 14' 9" (4.5M)T-16'4" T-16'4"P TRUNK CABLE, LRG CONN, 5P MF, 16' 4" (5M)T-18'0" T-18'0"P TRUNK CABLE, LRG CONN, 5P MF, 18' 0" (5.5M)T-19'8" T-19'8"P TRUNK CABLE, LRG CONN, 5P MF, 19' 8" (6M)T-21'3" T-21'3"P TRUNK CABLE, LRG CONN, 5P MF, 21' 3" (6.5M)T-22'11" T-22'11"P TRUNK CABLE, LRG CONN, 5P MF, 22' 11" (7M)T-24'7" T-24'7"P TRUNK CABLE, LRG CONN, 5P MF, 24' 7" (7.5M)T-26'2" T-26'2"P TRUNK CABLE, LRG CONN, 5P MF, 26' 2" (8M)T-27'10" T-27'10"P TRUNK CABLE, LRG CONN, 5P MF, 27' 10" (8.5M)T-29'6" T-29'6"P TRUNK CABLE, LRG CONN, 5P MF, 29' 6" (9M)T-31'2" T-31'2"P TRUNK CABLE, LRG CONN, 5P MF, 31' 2" (9.5M)T-32'9" T-32'9"P TRUNK CABLE, LRG CONN, 5P MF, 32' 9" (10M)T-65'7" T-65'7"P TRUNK CABLE, LRG CONN, 5P MF, 65' 7" (20M)T-98'5" T-98'5"P TRUNK CABLE, LRG CONN, 5P MF, 98' 5" (30M)T-131'2" T-131'2"P TRUNK CABLE, LRG CONN, 5P MF, 131' 2" (40M)T-164'0" T-164'0"P TRUNK CABLE, LRG CONN, 5P MF, 164' 0" (50M)
T-8"P TRUNK CABLE, PLENUM, STUB, LRG CONN, 5P MF
STANDARD PLENUM DESCRIPTIOND-1'0" D-1'0"P DROP CABLE, MED CONN, 5P M, SML CONN, 5PK F, 1' 0" (0.3M)D-2'0" D-2'0"P DROP CABLE, MED CONN, 5P M, SML CONN, 5PK F, 2' 0" (0.6M)D-3'3" D-3'3"P DROP CABLE, MED CONN, 5P M, SML CONN, 5PK F, 3' 3" (1M)D-4'11" D-4'11"P DROP CABLE, MED CONN, 5P M, SML CONN, 5PK F, 4' 11" (1.5M)D-6'6" D-6'6"P DROP CABLE, MED CONN, 5P M, SML CONN, 5PK F, 6' 6" (2M)D-8'2" D-8'2"P DROP CABLE, MED CONN, 5P M, SML CONN, 5PK F, 8' 2" (2.5M)D-9'10" D-9'10"P DROP CABLE, MED CONN, 5P M, SML CONN, 5PK F, 9' 10" (3M)D-11'5" D-11'5"P DROP CABLE, MED CONN, 5P M, SML CONN, 5PK F, 11' 5" (3.5M)D-13'1" D-13'1"P DROP CABLE, MED CONN, 5P M, SML CONN, 5PK F, 13' 1" (4M)D-14'9" D-14'9"P DROP CABLE, MED CONN, 5P M, SML CONN, 5PK F, 14' 9" (4.5M)D-16'4" D-16'4"P DROP CABLE, MED CONN, 5P M, SML CONN, 5PK F, 16' 4" (5M)D-18'0" D-18'0"P DROP CABLE, MED CONN, 5P M, SML CONN, 5PK F, 18' 0" (5.5M)D-19'8" D-19'8"P DROP CABLE, MED CONN, 5P M, SML CONN, 5PK F, 19' 8" (6M)D-21'3" D-21'3"P DROP CABLE, MED CONN, 5P M, SML CONN, 5PK F, 21' 3" (6.5M)D-22'11" D-22'11"P DROP CABLE, MED CONN, 5P M, SML CONN, 5PK F, 22' 11" (7M)D-24'7" D-24'7"P DROP CABLE, MED CONN, 5P M, SML CONN, 5PK F, 24' 7" (7.5M)D-26'2" D-26'2"P DROP CABLE, MED CONN, 5P M, SML CONN, 5PK F, 26' 2" (8M)D-27'10" D-27'10"P DROP CABLE, MED CONN, 5P M, SML CONN, 5PK F, 27' 10" (8.5M)D-29'6" D-29'6"P DROP CABLE, MED CONN, 5P M, SML CONN, 5PK F, 29' 6" (9M)D-31'2" D-31'2"P DROP CABLE, MED CONN, 5P M, SML CONN, 5PK F, 31' 2" (9.5M)D-32'9" D-32'9"P DROP CABLE, MED CONN, 5P M, SML CONN, 5PK F, 32' 9" (10M)
STANDARD PLENUM DESCRIPTIONI-1'0" I-1'0"P IGU CABLE, SML CONN, 5PK MF, 1' 0" (0.3M)I-2'0" I-2'0"P IGU CABLE, SML CONN, 5PK MF, 2' 0" (0.6M)I-3'3" I-3'3"P IGU CABLE, SML CONN, 5PK MF, 3' 3" (1M)I-4'11" I-4'11"P IGU CABLE, SML CONN, 5PK MF, 4' 11" (1.5M)I-6'6" I-6'6"P IGU CABLE, SML CONN, 5PK MF, 6' 6" (2M)I-8'2" I-8'2"P IGU CABLE, SML CONN, 5PK MF, 8' 2" (2.5M)I-9'10" I-9'10"P IGU CABLE, SML CONN, 5PK MF, 9' 10" (3M)I-11'5" I-11'5"P IGU CABLE, SML CONN, 5PK MF, 11' 5" (3.5M)I-13'1" I-13'1"P IGU CABLE, SML CONN, 5PK MF, 13' 1" (4M)I-14'9" I-14'9"P IGU CABLE, SML CONN, 5PK MF, 14' 9" (4.5M)I-16'4" I-16'4"P IGU CABLE, SML CONN, 5PK MF, 16' 4" (5M)I-18'0" I-18'0"P IGU CABLE, SML CONN, 5PK MF, 18' 0" (5.5M)I-19'8" I-19'8"P IGU CABLE, SML CONN, 5PK MF, 19' 8" (6M)I-21'3" I-21'3"P IGU CABLE, SML CONN, 5PK MF, 21' 3" (6.5M)I-22'11" I-22'11"P IGU CABLE, SML CONN, 5PK MF, 22' 11" (7M)I-24'7" I-24'7"P IGU CABLE, SML CONN, 5PK MF, 24' 7" (7.5M)I-26'2" I-26'2"P IGU CABLE, SML CONN, 5PK MF, 26' 2" (8M)I-27'10" I-27'10"P IGU CABLE, SML CONN, 5PK MF, 27' 10" (8.5M)I-29'6" I-29'6"P IGU CABLE, SML CONN, 5PK MF, 29' 6" (9M)I-31'2" I-31'2"P IGU CABLE, SML CONN, 5PK MF, 31' 2" (9.5M)I-32'9" I-32'9"P IGU CABLE, SML CONN, 5PK MF, 32' 9" (10M)I-35'0" I-35'0"P IGU CABLE, SML CONN, 5PK MF, 35' 0" (10.66M)I-40'0" I-40'0"P IGU CABLE, SML CONN, 5PK MF, 40' 0" (12.19M)I-45'0" I-45'0"P IGU CABLE, SML CONN, 5PK MF, 45' 0" (13.71M)I-50'0" I-50'0"P IGU CABLE, SML CONN, 5PK MF, 50' 0" (15.24M)I-55'0" I-55'0"P IGU CABLE, SML CONN, 5PK MF, 55' 0" (16.76M)I-60'0" I-60'0"P IGU CABLE, SML CONN, 5PK MF, 60' 0" (18.28M)I-65'0" I-65'0"P IGU CABLE, SML CONN, 5PK MF, 65' 0" (19.81M)I-70'0" I-70'0"P IGU CABLE, SML CONN, 5PK MF, 70' 0" (21.33M)I-75'0" I-75'0"P IGU CABLE, SML CONN, 5PK MF, 75' 0" (22.86M)I-80'0" I-80'0"P IGU CABLE, SML CONN, 5PK MF, 80' 0" (24.38M)I-85'0" I-85'0"P IGU CABLE, SML CONN, 5PK MF, 85' 0" (25.90M)I-90'0" I-90'0"P IGU CABLE, SML CONN, 5PK MF, 90' 0" (27.43M)I-95'0" I-95'0"P IGU CABLE, SML CONN, 5PK MF, 95' 0" (28.95M)I-100'0" I-100'0"P IGU CABLE, SML CONN, 5PK MF, 100' 0" (30.48M)
MALE CONNECTOR FACESTOWARD CONTROL PANEL
WT
MALE CONNECTOR FACESTOWARD CONTROL PANEL
MALE CONNECTOR FACESTOWARD CONTROL PANEL
1.06
"Ø
FIND NUMBER (LENGTH)ON COLORED WRAP,
BOTH ENDS OF CABLE
X'X"
X'X" P
X'X"
X'X" P
X'X"
X'X" P
0.25"Ø PLENUM0.31"Ø STANDARD
BEND RADIUS, STANDARD 2.5"
BEND RADIUS, PLENUM 3.75"
FIND NUMBER (LENGTH)ON COLORED WRAP,
BOTH ENDS OF CABLE
0.41"Ø PLENUM0.45"Ø STANDARD
TO CONTROL PANEL AWAY FROMCONTROL PANEL
CABLE ORIENTATION LABEL,BOTH ENDS OF CABLEMANUFACTURER AND DATE
CODE, BOTH ENDS OF CABLE0.25"Ø PLENUM
0.31"Ø STANDARD
TO CONTROL PANEL
MANUFACTURER AND DATECODE, BOTH ENDS OF CABLE
AWAY FROMCONTROL PANEL
CABLE ORIENTATION LABEL,BOTH ENDS OF CABLE
BEND RADIUS, STANDARD 2.5"
BEND RADIUS, PLENUM 3.75"
BEND RADIUS, PLENUM 6.15"
BEND RADIUS, STANDARD 3.6"
TO CONTROL PANEL
MANUFACTURER AND DATECODE, BOTH ENDS OF CABLE
AWAY FROMCONTROL PANEL
CABLE ORIENTATION LABEL,BOTH ENDS OF CABLE
7/8, MALE 7/8, FEMALE
1. REMOVE THE UPPER SECTION OF CONNECTOR -HOLD THE UPPER SECTION OF THE CONNECTOR INPLACE THEN TWIST THE LOWER SECTION OF THECONNECTOR COUNTERCLOCKWISE.
2. LOOSEN THE NUT FOR THE STRAIN RELIEF ON THELOWER SECTION OF THE CONNECTOR.
3. FEED THE CABLE THRU BOTTOM HOLE.4. CUT THE OUTER JACKET ~ 1.5” TO EXPOSE THE 4
WIRES INSIDE THE CABLE.5. STRIP THE 4 INDIVIDUAL WIRES ~ 1/4” .
6. WITH A SMALL SCREW DRIVER LOOSEN THE SCREWON THE TERMINALS.
7. INSERT AND TIGHTEN THE WIRES IN THE UPPERSECTION OF THE CONNECTOR PER THE SCHEMATIC.
8. DO A PULL TEST MAKING SURE THAT NO STRAYWIRES ARE STICKING OUT.
9. SLIP THE LOWER SECTION OF THE CONNECTORONTO THE UPPER SECTION AND TIGHTEN.
10. TIGHTEN THE STRAIN RELIEF NUT.
PIPIPI
MALE CONNECTOR FACESTOWARD CONTROL PANEL
FW-LC4-1 FW-LC4-2
~3.43" ~3.37"
1.10
"Ø
CBL-14/4P
ASSEMBLY INSTRUCTIONS
CABLE PINOUT
SHIELD
1. REMOVE THE UPPER SECTION OF CONNECTOR -HOLD THE UPPER SECTION OF THE CONNECTOR INPLACE THEN TWIST THE LOWER SECTION OF THECONNECTOR COUNTERCLOCKWISE.
2. LOOSEN THE NUT FOR THE STRAIN RELIEF ON THELOWER SECTION OF THE CONNECTOR.
3. FEED THE CABLE THRU BOTTOM HOLE.4. CUT THE OUTER JACKET ~ 1.5” TO EXPOSE THE 4
WIRES AND SHIELD INSIDE THE CABLE.5. STRIP THE 4 INDIVIDUAL WIRES ~ 14 " AND TWIST THE
SHIELD TO FIT INTO A TERMINAL.
6. WITH A SMALL SCREW DRIVER LOOSEN THE SCREWON THE TERMINALS.
7. INSERT AND TIGHTEN THE WIRES IN THE UPPERSECTION OF THE CONNECTOR PER THE SCHEMATIC.
8. DO A PULL TEST MAKING SURE THAT NO STRAYWIRES ARE STICKING OUT.
9. SLIP THE LOWER SECTION OF THE CONNECTORONTO THE UPPER SECTION AND TIGHTEN.
10. TIGHTEN THE STRAIN RELIEF NUT.
ASSEMBLY INSTRUCTIONS
CABLE PINOUT
SHIELD
~3.43" ~3.37"
1.10
"Ø
7/8, MALE 7/8, FEMALECUT TO LENGTH AS NEEDED
~1.5"
WTWTWT
MALE CONNECTOR FACESTOWARD CONTROL PANEL
FW-LC5-1
FW-LC5-3
~1.5"
PLENUM TRUNK ONLY
STANDARD TRUNK ONLY FW-LC5-2
FW-LC5-4
TO CONTROL PANEL
4" MAXIMUM
4" MAXIMUM
4" MAXIMUM
4" MAXIMUM
2N25
2 5
P.I. 1.1A
TRUNK 1.1A
TRUNK CABLES
WRAPPED LABEL, TRUNK NAME, BOTH ENDS OFFIRST TRUNK SEGMENT FROM CONTROL PANEL
POWER INSERT CABLES
IGU CABLES
IGU CABLES, OPTIONAL
WRAPPED LABEL, POWER INSERT NAME,BOTH ENDS OF CABLE
WRAPPED LABEL, IGU WC NAME, BY GLAZIER,MALE END OF CABLE OUTSIDE OF FRAME
WIRE MARKER TAPE, IGU WC NUMBER, BY GLAZIER,MALE END OF CABLE OUTSIDE OF FRAME
~1.5" ~1.5"
0.41"Ø PLENUM0.45"Ø STANDARD
0.25"Ø
TO CONTROL PANEL
TO CONTROL PANEL
2
1 5
3
42
15
3
4
PART # FIND DESCRIPTION310-000061 FW-LC4-1 CONNECTOR, FIELD WIREABLE, LRG CONN, 4P-M310-000063 FW-LC4-2 CONNECTOR, FIELD WIREABLE, LRG CONN, 4P-F
300-101032-01 CBL-14/4P CABLE, 4 COND, 14AWG, PLENUM, L 500ft300-101032 CBL-14/4P CABLE, 4 COND, 14AWG, PLENUM, L 1000ft
PART # FIND DESCRIPTION310-000047 FW-LC5-1 CONNECTOR, FIELD WIREABLE, LRG CONN, 5P-M310-000051 FW-LC5-2 CONNECTOR, FIELD WIREABLE, LRG CONN, 5P-F310-000071 FW-LC5-3 CONNECTOR, FIELD WIREABLE, LRG CONN, 5P-MALE, 14AWG310-000070 FW-LC5-4 CONNECTOR, FIELD WIREABLE, LRG CONN, 5P-FEMALE, 14AWG
300-101041-01 T-500 CABLE, TRUNK , 2x14AWG, 2x18AWG, SHIELD, NON-PLENUM, 500 FT SPOOL300-101041-02 T-1000 CABLE, TRUNK , 2x14AWG, 2x18AWG, SHIELD, NON-PLENUM, 1000 FT SPOOL300-101042-01 T-P-500 CABLE, TRUNK , 2x14AWG, 2x18AWG, SHIELD, PLENUM, 500 FT SPOOL
2
1
3
4
2
1
3
4
TESTED LABEL
01P
RE
LIM
INA
RY
00.0
0.19
THA
RR
ELL
TH
VIE
W T
RA
ININ
G P
RO
JEC
T18
330
NO
THIN
G R
OA
DS
OM
EW
HE
RE
, CA
950
00
DR
AW
ING
RE
LEA
SE
SD
ES
CR
IPTI
ON
NO
.D
ATE
RE
LEA
SE
#
DR
AW
N:
DE
SIG
N:
RE
VIE
W:
ISS
UE
DA
TE:
INFO
RM
ATI
ON
®
VIEW, INC. ®195 SOUTH MILPITAS BLVD.MILPITAS, CA 95035PH: 408-263-9200WWW.VIEWGLASS.COM
PLO
T D
ATE
:
SFI
D:
VIE
W D
OC
UM
EN
T N
UM
BE
R
SH
EE
T TI
TLE
:
SHEET NUMBER:
VIEW, INC. CONFIDENTIAL:THIS DOCUMENT AND THE INFORMATIONCONTAINED IN IT ARE CONFIDENTIAL,AND CANNOT BE COPIED OR DISCLOSEDIN WHOLE OR IN PART WITHOUT THEEXPRESS WRITTEN CONSENT OFVIEW, INC. ® © - VIEW, INC.
XG-9.2.1
4.29
.201
9 12
:41
PM
2019
00.0
0.19
0134
0-10
133313
0067
130
THFI
ELD
WIR
EA
BLE
CO
NN
EC
TIO
NS
AN
DP
RE
TER
MIN
ATE
DC
OR
DS
ETS
M12, MALE M8 FEMALE, KEYED M8 FEMALE, KEYEDM8 MALE, KEYED7/8, MALE 7/8, FEMALE
V-V+V+
V-
1234 GRN 14 AWG
BLK 14 AWG
RED 14 AWGWHT 14 AWG
V-V+V+
V-
1234GRN 14 AWG
BLK 14 AWG
RED 14 AWGWHT 14 AWG
12345
12345
CAN_H
V+
CAN_L
V-
SHIELD
CAN_H
V+
CAN_L
V-
SHIELDRED 14 AWGBLK 14 AWGWHT 18 AWGBLU 18 AWG
BARERED 14 AWGBLK 14 AWG
WHT 18 AWGBLU 18 AWG
BARE
FIND NUMBER (LENGTH)ON COLORED WRAP,
BOTH ENDS OF CABLE
PART NO: 380-000038-XX (PLENUM) PART NO: 380-101510-XX (PLENUM) PART NO: 380-101509-XX (PLENUM)
PART NO: 380-000057-XX (STANDARD) PART NO: 380-101512-XX (STANDARD) PART NO: 380-101511-XX (STANDARD)
1. MACHINE PRINTED LABEL SHOULD BE LOCATED WITHIN 4" OF CABLE END.2. EACH LABEL SHOULD BE MACHINE PRINTED - BLACK PRINT ON WHITE MATERIAL.3. USE PROPORTIONAL FONT, MINIMUM 14 PT BOLD.4. CABLE IDENTIFIER SHOULD APPEAR TWO TIMES ON THE LABEL FOR VISIBILITY.5. LABELS SHOULD BE OF PERMANENT TYPE MATERIAL.6. HAND WRITTEN LABELS SHOULD NOT BE USED.7. DO NOT MAKE LABELS FROM MASKING TAPE, ELECTRICAL TAPE, DUCT TAPE,
PAPER COVERED SCOTCH TAPE OR ANY NON LABEL MATERIAL.8. WIRE MARKER TAPE CAN BE USED FOR IGU CABLES. USE NUMBER TO MATCH
IGU MARKING ON INTERCONNECT.9. LABELS AND MARKER TAPE NOT PROVIDED BY VIEW.10. TESTED LABEL, PROVIDED BY VIEW, TO BE PLACED ON EACH END OF CABLE
AFTER INSTALLATION AND TESTING.
SCALE:1 FIELD TERMINATED TRUNK (2x14 AWG / 2x18 AWG) CONNECTIONNONE SCALE:2 FIELD TERMINATED POWER CONNECTION
NONE SCALE:3 REQURED CABLE LABELINGNONE
SCALE:6 IGU CORDSET DETAIL AND DESCRIPTION LISTNONESCALE:5 DROP CORDSET DETAIL AND DESCRIPTION LIST
NONESCALE:4 TRUNK CORDSET DETAIL AND DESCRIPTION LISTNONE
STANDARD PLENUM DESCRIPTIONT-1'0" T-1'0"P TRUNK CABLE, LRG CONN, 5P MF, 1' 0" (0.3M)T-2'0" T-2'0"P TRUNK CABLE, LRG CONN, 5P MF, 2' 0" (0.6M)T-3'3" T-3'3"P TRUNK CABLE, LRG CONN, 5P MF, 3' 3" (1M)
T-4'11" T-4'11"P TRUNK CABLE, LRG CONN, 5P MF, 4' 11" (1.5M)T-6'6" T-6'6"P TRUNK CABLE, LRG CONN, 5P MF, 6' 6" (2M)T-8'2" T-8'2"P TRUNK CABLE, LRG CONN, 5P MF, 8' 2" (2.5M)
T-9'10" T-9'10"P TRUNK CABLE, LRG CONN, 5P MF, 9' 10" (3M)T-11'5" T-11'5"P TRUNK CABLE, LRG CONN, 5P MF, 11' 5" (3.5M)T-13'1" T-13'1"P TRUNK CABLE, LRG CONN, 5P MF, 13' 1" (4M)T-14'9" T-14'9"P TRUNK CABLE, LRG CONN, 5P MF, 14' 9" (4.5M)T-16'4" T-16'4"P TRUNK CABLE, LRG CONN, 5P MF, 16' 4" (5M)T-18'0" T-18'0"P TRUNK CABLE, LRG CONN, 5P MF, 18' 0" (5.5M)T-19'8" T-19'8"P TRUNK CABLE, LRG CONN, 5P MF, 19' 8" (6M)T-21'3" T-21'3"P TRUNK CABLE, LRG CONN, 5P MF, 21' 3" (6.5M)T-22'11" T-22'11"P TRUNK CABLE, LRG CONN, 5P MF, 22' 11" (7M)T-24'7" T-24'7"P TRUNK CABLE, LRG CONN, 5P MF, 24' 7" (7.5M)T-26'2" T-26'2"P TRUNK CABLE, LRG CONN, 5P MF, 26' 2" (8M)T-27'10" T-27'10"P TRUNK CABLE, LRG CONN, 5P MF, 27' 10" (8.5M)T-29'6" T-29'6"P TRUNK CABLE, LRG CONN, 5P MF, 29' 6" (9M)T-31'2" T-31'2"P TRUNK CABLE, LRG CONN, 5P MF, 31' 2" (9.5M)T-32'9" T-32'9"P TRUNK CABLE, LRG CONN, 5P MF, 32' 9" (10M)T-65'7" T-65'7"P TRUNK CABLE, LRG CONN, 5P MF, 65' 7" (20M)T-98'5" T-98'5"P TRUNK CABLE, LRG CONN, 5P MF, 98' 5" (30M)T-131'2" T-131'2"P TRUNK CABLE, LRG CONN, 5P MF, 131' 2" (40M)T-164'0" T-164'0"P TRUNK CABLE, LRG CONN, 5P MF, 164' 0" (50M)
T-8"P TRUNK CABLE, PLENUM, STUB, LRG CONN, 5P MF
STANDARD PLENUM DESCRIPTIOND-1'0" D-1'0"P DROP CABLE, MED CONN, 5P M, SML CONN, 5PK F, 1' 0" (0.3M)D-2'0" D-2'0"P DROP CABLE, MED CONN, 5P M, SML CONN, 5PK F, 2' 0" (0.6M)D-3'3" D-3'3"P DROP CABLE, MED CONN, 5P M, SML CONN, 5PK F, 3' 3" (1M)D-4'11" D-4'11"P DROP CABLE, MED CONN, 5P M, SML CONN, 5PK F, 4' 11" (1.5M)D-6'6" D-6'6"P DROP CABLE, MED CONN, 5P M, SML CONN, 5PK F, 6' 6" (2M)D-8'2" D-8'2"P DROP CABLE, MED CONN, 5P M, SML CONN, 5PK F, 8' 2" (2.5M)D-9'10" D-9'10"P DROP CABLE, MED CONN, 5P M, SML CONN, 5PK F, 9' 10" (3M)D-11'5" D-11'5"P DROP CABLE, MED CONN, 5P M, SML CONN, 5PK F, 11' 5" (3.5M)D-13'1" D-13'1"P DROP CABLE, MED CONN, 5P M, SML CONN, 5PK F, 13' 1" (4M)D-14'9" D-14'9"P DROP CABLE, MED CONN, 5P M, SML CONN, 5PK F, 14' 9" (4.5M)D-16'4" D-16'4"P DROP CABLE, MED CONN, 5P M, SML CONN, 5PK F, 16' 4" (5M)D-18'0" D-18'0"P DROP CABLE, MED CONN, 5P M, SML CONN, 5PK F, 18' 0" (5.5M)D-19'8" D-19'8"P DROP CABLE, MED CONN, 5P M, SML CONN, 5PK F, 19' 8" (6M)D-21'3" D-21'3"P DROP CABLE, MED CONN, 5P M, SML CONN, 5PK F, 21' 3" (6.5M)D-22'11" D-22'11"P DROP CABLE, MED CONN, 5P M, SML CONN, 5PK F, 22' 11" (7M)D-24'7" D-24'7"P DROP CABLE, MED CONN, 5P M, SML CONN, 5PK F, 24' 7" (7.5M)D-26'2" D-26'2"P DROP CABLE, MED CONN, 5P M, SML CONN, 5PK F, 26' 2" (8M)D-27'10" D-27'10"P DROP CABLE, MED CONN, 5P M, SML CONN, 5PK F, 27' 10" (8.5M)D-29'6" D-29'6"P DROP CABLE, MED CONN, 5P M, SML CONN, 5PK F, 29' 6" (9M)D-31'2" D-31'2"P DROP CABLE, MED CONN, 5P M, SML CONN, 5PK F, 31' 2" (9.5M)D-32'9" D-32'9"P DROP CABLE, MED CONN, 5P M, SML CONN, 5PK F, 32' 9" (10M)
STANDARD PLENUM DESCRIPTIONI-1'0" I-1'0"P IGU CABLE, SML CONN, 5PK MF, 1' 0" (0.3M)I-2'0" I-2'0"P IGU CABLE, SML CONN, 5PK MF, 2' 0" (0.6M)I-3'3" I-3'3"P IGU CABLE, SML CONN, 5PK MF, 3' 3" (1M)I-4'11" I-4'11"P IGU CABLE, SML CONN, 5PK MF, 4' 11" (1.5M)I-6'6" I-6'6"P IGU CABLE, SML CONN, 5PK MF, 6' 6" (2M)I-8'2" I-8'2"P IGU CABLE, SML CONN, 5PK MF, 8' 2" (2.5M)I-9'10" I-9'10"P IGU CABLE, SML CONN, 5PK MF, 9' 10" (3M)I-11'5" I-11'5"P IGU CABLE, SML CONN, 5PK MF, 11' 5" (3.5M)I-13'1" I-13'1"P IGU CABLE, SML CONN, 5PK MF, 13' 1" (4M)I-14'9" I-14'9"P IGU CABLE, SML CONN, 5PK MF, 14' 9" (4.5M)I-16'4" I-16'4"P IGU CABLE, SML CONN, 5PK MF, 16' 4" (5M)I-18'0" I-18'0"P IGU CABLE, SML CONN, 5PK MF, 18' 0" (5.5M)I-19'8" I-19'8"P IGU CABLE, SML CONN, 5PK MF, 19' 8" (6M)I-21'3" I-21'3"P IGU CABLE, SML CONN, 5PK MF, 21' 3" (6.5M)I-22'11" I-22'11"P IGU CABLE, SML CONN, 5PK MF, 22' 11" (7M)I-24'7" I-24'7"P IGU CABLE, SML CONN, 5PK MF, 24' 7" (7.5M)I-26'2" I-26'2"P IGU CABLE, SML CONN, 5PK MF, 26' 2" (8M)I-27'10" I-27'10"P IGU CABLE, SML CONN, 5PK MF, 27' 10" (8.5M)I-29'6" I-29'6"P IGU CABLE, SML CONN, 5PK MF, 29' 6" (9M)I-31'2" I-31'2"P IGU CABLE, SML CONN, 5PK MF, 31' 2" (9.5M)I-32'9" I-32'9"P IGU CABLE, SML CONN, 5PK MF, 32' 9" (10M)I-35'0" I-35'0"P IGU CABLE, SML CONN, 5PK MF, 35' 0" (10.66M)I-40'0" I-40'0"P IGU CABLE, SML CONN, 5PK MF, 40' 0" (12.19M)I-45'0" I-45'0"P IGU CABLE, SML CONN, 5PK MF, 45' 0" (13.71M)I-50'0" I-50'0"P IGU CABLE, SML CONN, 5PK MF, 50' 0" (15.24M)I-55'0" I-55'0"P IGU CABLE, SML CONN, 5PK MF, 55' 0" (16.76M)I-60'0" I-60'0"P IGU CABLE, SML CONN, 5PK MF, 60' 0" (18.28M)I-65'0" I-65'0"P IGU CABLE, SML CONN, 5PK MF, 65' 0" (19.81M)I-70'0" I-70'0"P IGU CABLE, SML CONN, 5PK MF, 70' 0" (21.33M)I-75'0" I-75'0"P IGU CABLE, SML CONN, 5PK MF, 75' 0" (22.86M)I-80'0" I-80'0"P IGU CABLE, SML CONN, 5PK MF, 80' 0" (24.38M)I-85'0" I-85'0"P IGU CABLE, SML CONN, 5PK MF, 85' 0" (25.90M)I-90'0" I-90'0"P IGU CABLE, SML CONN, 5PK MF, 90' 0" (27.43M)I-95'0" I-95'0"P IGU CABLE, SML CONN, 5PK MF, 95' 0" (28.95M)I-100'0" I-100'0"P IGU CABLE, SML CONN, 5PK MF, 100' 0" (30.48M)
MALE CONNECTOR FACESTOWARD CONTROL PANEL
WT
MALE CONNECTOR FACESTOWARD CONTROL PANEL
MALE CONNECTOR FACESTOWARD CONTROL PANEL
1.06
"Ø
FIND NUMBER (LENGTH)ON COLORED WRAP,
BOTH ENDS OF CABLE
X'X"
X'X" P
X'X"
X'X" P
X'X"
X'X" P
0.25"Ø PLENUM0.31"Ø STANDARD
BEND RADIUS, STANDARD 2.5"
BEND RADIUS, PLENUM 3.75"
FIND NUMBER (LENGTH)ON COLORED WRAP,
BOTH ENDS OF CABLE
0.41"Ø PLENUM0.45"Ø STANDARD
TO CONTROL PANEL AWAY FROMCONTROL PANEL
CABLE ORIENTATION LABEL,BOTH ENDS OF CABLEMANUFACTURER AND DATE
CODE, BOTH ENDS OF CABLE0.25"Ø PLENUM
0.31"Ø STANDARD
TO CONTROL PANEL
MANUFACTURER AND DATECODE, BOTH ENDS OF CABLE
AWAY FROMCONTROL PANEL
CABLE ORIENTATION LABEL,BOTH ENDS OF CABLE
BEND RADIUS, STANDARD 2.5"
BEND RADIUS, PLENUM 3.75"
BEND RADIUS, PLENUM 6.15"
BEND RADIUS, STANDARD 3.6"
TO CONTROL PANEL
MANUFACTURER AND DATECODE, BOTH ENDS OF CABLE
AWAY FROMCONTROL PANEL
CABLE ORIENTATION LABEL,BOTH ENDS OF CABLE
7/8, MALE 7/8, FEMALE
1. REMOVE THE UPPER SECTION OF CONNECTOR -HOLD THE UPPER SECTION OF THE CONNECTOR INPLACE THEN TWIST THE LOWER SECTION OF THECONNECTOR COUNTERCLOCKWISE.
2. LOOSEN THE NUT FOR THE STRAIN RELIEF ON THELOWER SECTION OF THE CONNECTOR.
3. FEED THE CABLE THRU BOTTOM HOLE.4. CUT THE OUTER JACKET ~ 1.5” TO EXPOSE THE 4
WIRES INSIDE THE CABLE.5. STRIP THE 4 INDIVIDUAL WIRES ~ 1/4” .
6. WITH A SMALL SCREW DRIVER LOOSEN THE SCREWON THE TERMINALS.
7. INSERT AND TIGHTEN THE WIRES IN THE UPPERSECTION OF THE CONNECTOR PER THE SCHEMATIC.
8. DO A PULL TEST MAKING SURE THAT NO STRAYWIRES ARE STICKING OUT.
9. SLIP THE LOWER SECTION OF THE CONNECTORONTO THE UPPER SECTION AND TIGHTEN.
10. TIGHTEN THE STRAIN RELIEF NUT.
PIPIPI
MALE CONNECTOR FACESTOWARD CONTROL PANEL
FW-LC4-1 FW-LC4-2
~3.43" ~3.37"
1.10
"Ø
CBL-14/4P
ASSEMBLY INSTRUCTIONS
CABLE PINOUT
SHIELD
1. REMOVE THE UPPER SECTION OF CONNECTOR -HOLD THE UPPER SECTION OF THE CONNECTOR INPLACE THEN TWIST THE LOWER SECTION OF THECONNECTOR COUNTERCLOCKWISE.
2. LOOSEN THE NUT FOR THE STRAIN RELIEF ON THELOWER SECTION OF THE CONNECTOR.
3. FEED THE CABLE THRU BOTTOM HOLE.4. CUT THE OUTER JACKET ~ 1.5” TO EXPOSE THE 4
WIRES AND SHIELD INSIDE THE CABLE.5. STRIP THE 4 INDIVIDUAL WIRES ~ 14 " AND TWIST THE
SHIELD TO FIT INTO A TERMINAL.
6. WITH A SMALL SCREW DRIVER LOOSEN THE SCREWON THE TERMINALS.
7. INSERT AND TIGHTEN THE WIRES IN THE UPPERSECTION OF THE CONNECTOR PER THE SCHEMATIC.
8. DO A PULL TEST MAKING SURE THAT NO STRAYWIRES ARE STICKING OUT.
9. SLIP THE LOWER SECTION OF THE CONNECTORONTO THE UPPER SECTION AND TIGHTEN.
10. TIGHTEN THE STRAIN RELIEF NUT.
ASSEMBLY INSTRUCTIONS
CABLE PINOUT
SHIELD
~3.43" ~3.37"
1.10
"Ø
7/8, MALE 7/8, FEMALECUT TO LENGTH AS NEEDED
~1.5"
WTWTWT
MALE CONNECTOR FACESTOWARD CONTROL PANEL
FW-LC5-1
FW-LC5-3
~1.5"
PLENUM TRUNK ONLY
STANDARD TRUNK ONLY FW-LC5-2
FW-LC5-4
TO CONTROL PANEL
4" MAXIMUM
4" MAXIMUM
4" MAXIMUM
4" MAXIMUM
2N25
2 5
P.I. 1.1A
TRUNK 1.1A
TRUNK CABLES
WRAPPED LABEL, TRUNK NAME, BOTH ENDS OFFIRST TRUNK SEGMENT FROM CONTROL PANEL
POWER INSERT CABLES
IGU CABLES
IGU CABLES, OPTIONAL
WRAPPED LABEL, POWER INSERT NAME,BOTH ENDS OF CABLE
WRAPPED LABEL, IGU WC NAME, BY GLAZIER,MALE END OF CABLE OUTSIDE OF FRAME
WIRE MARKER TAPE, IGU WC NUMBER, BY GLAZIER,MALE END OF CABLE OUTSIDE OF FRAME
~1.5" ~1.5"
0.41"Ø PLENUM0.45"Ø STANDARD
0.25"Ø
TO CONTROL PANEL
TO CONTROL PANEL
2
1 5
3
42
15
3
4
PART # FIND DESCRIPTION310-000061 FW-LC4-1 CONNECTOR, FIELD WIREABLE, LRG CONN, 4P-M310-000063 FW-LC4-2 CONNECTOR, FIELD WIREABLE, LRG CONN, 4P-F
300-101032-01 CBL-14/4P CABLE, 4 COND, 14AWG, PLENUM, L 500ft300-101032 CBL-14/4P CABLE, 4 COND, 14AWG, PLENUM, L 1000ft
PART # FIND DESCRIPTION310-000047 FW-LC5-1 CONNECTOR, FIELD WIREABLE, LRG CONN, 5P-M310-000051 FW-LC5-2 CONNECTOR, FIELD WIREABLE, LRG CONN, 5P-F310-000071 FW-LC5-3 CONNECTOR, FIELD WIREABLE, LRG CONN, 5P-MALE, 14AWG310-000070 FW-LC5-4 CONNECTOR, FIELD WIREABLE, LRG CONN, 5P-FEMALE, 14AWG
300-101041-01 T-500 CABLE, TRUNK , 2x14AWG, 2x18AWG, SHIELD, NON-PLENUM, 500 FT SPOOL300-101041-02 T-1000 CABLE, TRUNK , 2x14AWG, 2x18AWG, SHIELD, NON-PLENUM, 1000 FT SPOOL300-101042-01 T-P-500 CABLE, TRUNK , 2x14AWG, 2x18AWG, SHIELD, PLENUM, 500 FT SPOOL
2
1
3
4
2
1
3
4
TESTED LABEL
37 of 37 ©2019 View, Inc.Rev 6 | Aug 2019
OVERVIEW GUIDE
IGU Cable
4” Adapter
IGU Smart Window Connector
IGU Cable
IGU Cable
IGU Pigtail
Required IGU testing by glazier and LVE, the installer needs to observe each glass IGU tinting from the busbars (allow 1 minute per IGU)
4-State Controller/Tester