Accessories Orifice Plate for Flow Measurement Model FOP-10 Differential pressure gauges Model 732.51 see Data Sheet PM 07.05 Differential pressure gauge multi purpose Model 732.14 see Data Sheet PM 07.13 Pressure transmitters for low pressures and differential pressures Model DP-10 see Data Sheet PE 81.06 Orifice plate FOP-10 Applications Power generation Oil production and refining Water treatment and distribution Gas processing and transmission Chemistry and petrochemistry Special Features Maximum working temperature 800 °C Maximum working pressure 400 bar Suitable for liquid, gas, and steam flow measurement Accuracy 1 % of actual flow rate Repeatability of measurement 0.1 % Description FOP-10 is an orifice plate for flow rate measurement of aggressive and non-aggressive media. It is particularly designed for large pipelines. This orifice plate produce a differential pressure signal proportional to the square of the flow rate. The differential pressure output is normally piped to a differ- ential pressure transmitter in order to generate an electrical signal proportional to the flow rate. A differential pressure gauge or switch can be used to provide local mechanical indication or flow rate switching. For certain applications, the differential pressure transmitter can be directly mounted on to the FOP-10 via an integral 3 or 5 valve manifold. WIKA Data Sheet AC 09.15 Page 1 of 4 WIKA Data Sheet AC 09.15 ∙ 07/2007

Upload: taimoor-khan

Post on 05-Mar-2015

406 views

Category:

Documents


4 download

TRANSCRIPT

Page 1: Orifice Plate Flow Meter Data Sheet

Accessories

Orifice Plate for Flow MeasurementModel FOP-10

Differential pressure gauges Model 732.51 see Data Sheet PM 07.05Differential pressure gauge multi purpose Model 732.14 see Data Sheet PM 07.13Pressure transmitters for low pressures and differential pressures Model DP-10 see Data Sheet PE 81.06

Orifice plate FOP-10

Applications

Power generationOil production and refiningWater treatment and distributionGas processing and transmissionChemistry and petrochemistry

Special Features

Maximum working temperature 800 °CMaximum working pressure 400 barSuitable for liquid, gas, and steam flow measurement Accuracy 1 % of actual flow rateRepeatability of measurement 0.1 %

Description

FOP-10 is an orifice plate for flow rate measurement of aggressive and non-aggressive media. It is particularly designed for large pipelines. This orifice plate produce a differential pressure signal proportional to the square of the flow rate.

The differential pressure output is normally piped to a differ-ential pressure transmitter in order to generate an electrical signal proportional to the flow rate. A differential pressure gauge or switch can be used to provide local mechanical indication or flow rate switching. For certain applications, the differential pressure transmitter can be directly mounted on to the FOP-10 via an integral 3 or 5 valve manifold.

WIKA Data Sheet AC 09.15

Page 1 of 4WIKA Data Sheet AC 09.15 ∙ 07/2007

Page 2: Orifice Plate Flow Meter Data Sheet

Page 2 of 4 WIKA Data Sheet AC 09.15 ∙ 07/2007

Specifications

Fits pipe sizes50 to 2000 mm

Nominal pressurePN 1 up to PN 100

Sealing typesmooth

Accuracy1 % of actual flow rate

Repeatability0.1 % of measurement

Reynolds numberMinimum 2 x 103

Suitable for mediaLiquid, gas and steam

Maximum viscosity50 cp (mPas)

Design of version with orifice flange

Orifice flangewith orifice plate, sealign-type smooth (RF)In every flange there are two outlet-bores (placed offset of 180 °) and a jackscrew aligned correspondingly. Special desings. i. e. other angle positions of the pressure taps and screwed-in pressure tabs are possible.

Standard Features

Probe materialStainless steel

IdentificationOn inlet side of handle: +, Tag-No., nominal pressure, inner pipe diamenter, bore diameter and material

Design Orifice plate

Optional extras

Fits pipe sizes 10 to 400 mm with seeling-type nose and tongue or lenseNominal pressure up to PN 400 with sealing-type lenseQuarter circle nozzle, orifice with nose, lense-sealing and ring-joint sealingWith orifice flnage and pressure-tapWith meter runs for welding in or with joint flangesRing chamber orifice plateOrifice plate with carrier ring, single bore pressure tabs

Page 3: Orifice Plate Flow Meter Data Sheet

DINDN Thickness “s“

mm

50 365 380 4

100 4125 4150 4175 4200 4250 4300 4350 4400 4450 4500 6550 x600 6650 x700 8750 8800 8850 x900 8950 x

10000 10

ANSIDN Thickness “s“

mm

2" 32.5" 33" 34" 35" 36" 37" 68" 6

10" 612" 614" 616" 618" 620" 622" 1024" 1026" 1028" 1030" 1032" 1034" 1036" 1238" 1240" 12

D

Page 3 of 4WIKA Data Sheet AC 09.15 ∙ 07/2007

Designs of orifice plate

They depend on nominal size, media and the required sealing-type. Normal configuration is the orifice plate (figure 1). A special configuration is the reducer orifice plate (figure 2). It servers mainly in small pipes for pressure-reduction and for flow-linitation. The quarter circle nozzle (figure 3) is assigned for use with small Reynold’s figures.

x = not standardised in DIN standard (DN 50 adapted to general practice)

Thickness is laid out for a differential pressure of max. 1000 mbar.

Thickness of the orifice plate

Orifice with nose, lense-sealing and ring-joint-sealing (figures 4 - 6) show you the possible sealing-types. Quarter circle nozzles according to VDI/VDE 2041 for special requirements are available for deliver.

Page 4: Orifice Plate Flow Meter Data Sheet

WIKA Alexander Wiegand GmbH & Co. KGAlexander-Wiegand-Straße 3063911 Klingenberg/GermanyTel. (+49) 9372/132-0Fax (+49) 9372/132-406E-mail [email protected]

D

1270

7849

07/

2007

GB

Specifications and dimensions given in this leaflet represent the state of engineering at the time of printing.Modifications may take place and materials specified may be replaced by others without prior notice.

Page 4 of 4 WIKA Data Sheet AC 09.15 ∙ 07/2007

DN 10 15 20 25 32 40 50 65 80 100 125 150 200

0.25" 0.5" 0.75" 1" 1.25" 1.5" 2" 2.5" 3" 4" 5" 6" 8"

L 400 550 700 900 1100 1300 1500 1600 1800 2200 2700 3200 4000

L1 230 380 500 650 800 1000 1200 1250 1400 1700 2000 2400 3000

L2 170 170 200 250 300 300 300 350 400 500 700 800 1000

Design of version with meter run

L = Total length of meter runL1 = Inlet runL2 = Outlet run