operator’s manual...1mrk 504 039-uen 15 menu window how to use the human machine interface 4 menu...
TRANSCRIPT
-
Operator’s manualProtectIT Transformer protection terminal
RET 521*2.5
-
© Copyright 2003 ABB. All rights reserved.
��������������ProtectIT Transformer protection terminal
RET 521*2.5
������������
DocID: 1MRK 504 039-UENIssue date: November 2003
Revision: -
-
COPYRIGHT
WE RESERVE ALL RIGHTS TO THIS DOCUMENT, EVEN IN THE EVENT THAT A PATENT IS ISSUED AND A DIFFERENT COMMERCIAL PROPRIETARY RIGHT IS REGISTERED. IMPROPER USE, IN PARTICULAR REPRODUCTION AND DIS-SEMINATION TO THIRD PARTIES, IS NOT PERMITTED.
THIS DOCUMENT HAS BEEN CAREFULLY CHECKED. HOWEVER, IN CASE ANY ERRORS ARE DETECTED, THE READER IS KINDLY REQUESTED TO NOTIFY THE MANUFACTURER AT THE ADDRESS BELOW.
THE DATA CONTAINED IN THIS MANUAL IS INTENDED SOLELY FOR THE CONCEPT OR PRODUCT DESCRIPTION AND IS NOT TO BE DEEMED TO BE A STATEMENT OF GUARANTEED PROPERTIES. IN THE INTERESTS OF OUR CUSTOM-ERS, WE CONSTANTLY SEEK TO ENSURE THAT OUR PRODUCTS ARE DEVELOPED TO THE LATEST TECHNOLOGI-CAL STANDARDS. AS A RESULT, IT IS POSSIBLE THAT THERE MAY BE SOME DIFFERENCES BETWEEN THE HW/SW PRODUCT AND THIS INFORMATION PRODUCT.
IndustrialIT
Industrial IT enabled products from ABB are the building blocks for greater productivity, featuring all the tools necessary for lifecycle product support in consistent electronic form.
Manufacturer:
ABB AutomationTechnology Products ABSubstation AutomationSE-721 59 VästeråsSwedenTelephone: +46 (0) 21 34 20 00Facsimile: +46 (0) 21 14 69 18www.abb.com/substationautomation
-
Chapter Page
Contents
How to use the human machine interface 5
How to use different software tools 19
How to perform specific operations 27
Human machine interface 41
References 83
����� ��
�������������������� ��
1MRK 504 039-UEN
-
4 1MRK 504 039-UEN
-
How to use the humanmachine interface
The chapter “How to use the human machine interface”.This chapter instructs the user how to use the human machine interface (HMI).
Human Machine Interface Overview ....................................................................7
Application ......................................................................................................7Design.............................................................................................................7Functionality ..................................................................................................10
Human machine communication module ...........................................................11
LEDs .............................................................................................................12LCD display...................................................................................................12Pushbuttons ..................................................................................................12
Unattended HMI .................................................................................................14
Idle mode ...................................................................................................... 14Configuration mode.......................................................................................14
Menu window .....................................................................................................15
Dialog window....................................................................................................16
Starting the dialog ......................................................................................... 16Confirming a command.................................................................................17Selecting a command ...................................................................................17Cancelling a command .................................................................................18Selecting and cancelling a command ...........................................................18
51MRK 504 039-UEN
-
How to use the humanmachine interface
6 1MRK 504 039-UEN
-
Human Machine Interface How to use the human machine interface
1 Human Machine Interface Overview
1.1 Application
The human machine interface is used to monitor and in certain aspects affect the way the product operates. The configuration designer can add functions for alerting in case of important events that needs special attention from you as an operator.
1.2 Design
The human-machine interface consists of:
• the human-machine interface (HMI) module.
• the LED module.
Fig. 1 The figure shows the LED (upper) and the HMI (lower).
71MRK 504 039-UEN
-
Human Machine Interface Overview How to use the human machine interface
Fig. 2 The HMI module
The number of buttons used on the HMI module is reduced to a minimum to allow a communication as simple as possible for the user. The buttons normally have more than one function, depending on actual dialogue.
Pressing any button in idle mode will activate the HMI display.
The C button has three main functions:
• Cancel any operation in a dialogue window.
• Exit the present level in the menu tree. This means, it cancels the present function or the present menu selection and moves one step higher (back) in the menu tree.
• Clear the LEDs when the start window is displayed.
• Bring the HMI display into idle mode if pressed when the idle window is dis-played (Quit function).
1. Status indication LEDs
2. LCD display
3. Cancel and Enter buttons
4. Navigation buttons
5. Optical connector
E
C
�����
����������������
�����������
���� ���
2
3
1
5
4 en03000132.vsd
8 1MRK 504 039-UEN
-
Human Machine Interface How to use the human machine interface
The E button mainly provides an Enter/Execute function. It activates, for example, the selected menu tree branch. Further it is used to confirm settings and to acknowl-edge different actions.
The left and right arrow buttons have three functions:
• Position the cursor in a horizontal direction, for instance, to move between digits in a number during the parameter setting.
• Move between leafs within the same menu branch.
• Move between the confirmation alternatives (yes, no and cancel) in a command window.
The up and down arrow buttons have three functions:
• Move between selectable branches of the menu tree. This function also scrolls the menu tree when it contains more branches than shown on the display.
• Move between the confirmation alternatives in a command window.
• Change parameter values in a data window
The LED indication module is equipped with 18 LEDs, which can light or flash in either red, yellow or green color. A description text can be added for each of the LEDs.
91MRK 504 039-UEN
-
Human Machine Interface Overview How to use the human machine interface
Fig. 3 The LED module
1.3 Functionality
The HMI module is a bidirectional means of communicating. This means that:
• events may occur that activates for instance a LED, in purpose to draw your attention to something that has occured and needs some sort of action.
• you as the operator may of own interest view a certain data.
Use menus to navigate through menu commands and to locate the data of interest.
The LED module is a unidirectional means of communicating. This means that events may occur that activates a LED, in purpose to draw your attention to something that has occured and needs some sort of action.
1 Three-color LEDs
2 Descriptive label, user exchangeable
xx00000406.vsd
1
2
10 1MRK 504 039-UEN
-
Human machine communication How to use the human machine interface
2 Human machine communication module
The built-in human machine interface (HMI) provides local communication between the user and the terminal.
Local communication also occurs with a PC connected to the built-in HMI via a spe-cial optical interface. This communication works like the remote communication within the station monitoring system (SMS) described in the other corresponding doc-uments.
This chapter describes the basic principles of local human-machine communication (HMC).
See the section “Human Machine interface - tree structure” for a detailed description of the tree structure.
The HMI module consists of three light emitting diodes (LEDs), a liquid crystal dis-play (LCD), six membrane pushbuttons, and one optical connector that enables local human machine communication (HMC) with the aid of a personal computer (PC).
Fig. 4 Built-in human-machine interface module.
E
C
Ready Start TripRET 521 Ver 2.5C = Clear LEDsE = Enter menu
green yellow red
LEDs
optical connectorfor local PC
push buttons
liquid crystal displayfour rows16 characters/row
(en03000133.eps)
111MRK 504 039-UEN
-
Human machine communication How to use the human machine interface
2.1 LEDs
Three LEDs provide primary information on the status of a terminal. Each LED has a special function, which also depends on whether it is off, steady on, or flashing.
������� Indicates that:
�
����������������� The operating condition of a terminal is normal.
�
�������������������� An internal error is detected within the terminal. Youcan block a terminal or operate with reduced function-ality, depending on the type of error and the internalconfiguration. See “Internal events” on page 29.
��������������������� One or more disturbances are recorded and stored inthe terminal.
������������������������ The terminal is in test mode.
������������������ At least one of the protection functions issued a tripcommand.
��������������������� The terminal is in configuration mode.
2.2 LCD display
The liquid crystal display (LCD) provides detailed information on the terminal. Nor-mally, it is off. Select any button to turn on the current status of all LEDs and display the type of terminal with its version, together with instructions on how to continue local communication with the terminal.
The display shuts down after you exit the menu tree or if no button is selected for more than about 45 minutes.
The disturbance summary (automatic scrolling of disturbance data for the last two dis-turbances) is active if there is a disturbance report in a terminal, which is not yet acknowledged.
2.3 Pushbuttons
The number of buttons used on the HMI module was reduced to the minimum accept-able amount to make the communication as simple as possible for the user. The buttons normally have more than one function, depending on where they are used in the dia-log.
All buttons have one function in common: when the display is in idle (dark, non active) mode, selecting any of them results in activation of the display.
12 1MRK 504 039-UEN
-
Human machine communication How to use the human machine interface
The C button has three main functions, it:
• Cancels the operation, when used together with the dialog windows.
• Provides an Exit operation in a menu tree. This means that each selection of the C button within the menu tree results in stopping the current function or leaving the menu branch and moving one step higher in the menu tree.
• Clears LEDs when in an upper menu level.
The E button mainly provides an Enter function. It activates, for example, the selected menu tree branch, confirm settings, and different actions.
The left and right arrow buttons have two functions, to:
• Position the cursor in a horizontal direction, for instance, to move between the digits in a number during the setting procedures for real values.
• Move between the data windows within the same menu branch.
The up and down arrow buttons have three functions, to:
• Move among different menus within the menu and the dialog windows.
• Scroll the menu tree when it contains more branches than shown on the display.
• Change the parameter values in the data windows during the setting procedure.
131MRK 504 039-UEN
-
Unattended HMI How to use the human machine interface
3 Unattended HMI
When the HMI is unattended in normal operation, two things might occur:
• No reporting of a disturbance (idle mode)
• Reporting of a disturbance (reporting mode)
3.1 Idle mode
When the terminal is in normal operation after the latest disturbance has been acknowledged or no disturbance is stored in the memory, and no one has attended the HMI for more than 45 minutes, the green LED remains active. The yellow and red LEDs are off and no text is shown on the display. The display is dark, with no light behind.
The display and LEDs will turn their status when one of the buttons is pressed, or when a new disturbance is stored in the terminal memory.
3.2 Configuration mode
When the terminal is in configuration mode, the HMI looks like this:
�
���� Lit.
����� Flashing.
14 1MRK 504 039-UEN
-
Menu window How to use the human machine interface
4 Menu window
Fig. 5 Menu window, general configuration (2a) and typical example (2b)
For row one:
• A dot always appears at the beginning of the row when the selected menu win-dow does not represent the main menu.
• path1 displays the name of the superior menu.
• path2 displays the name of the active menu window.
For rows two, three, and four:
• Menus k, k + 1 and k + 2 appear in the three bottom rows.
• When the cursor highlights one of the rows, it indicates the path that you can acti-vate by selecting the E button.
The up arrow appears in row 2 when more menus are available before the k menu. The down arrow appears in the bottom row when more menus are available after the k+2 menu. To change the active path within the menu tree (scrolling the menu) select the up or down arrow button.
To change the menu window into a new menu window or into a data window select the E button. In same case the paths in the first row change in such a way that the old path2 now becomes a path1 and the previous menu line with the cursor then changes into path2.
Fig. 5b shows a menu window that appears during the configuration procedure on the terminal. The configuration of function inputs will become possible by selecting the E button, since this submenu appears marked as an active path by a cursor. The down arrow informs the user about the additional menus that are available for a configura-tion.
.path1/path2Menu (k)Menu (k+1)Menu (k+2)
V
Va)
REL 531/ConFunction InputsSlot 11-BIM1Slot 13-BOM2 V
b)
151MRK 504 039-UEN
-
Dialog window How to use the human machine interface
5 Dialog window
The dialog windows instruct the operator how to perform the actions defined by the text in the third and fourth rows. The first and second rows usually display a headline that provides more information to the user about the proposed action or the terminal.
RET 521 has five different dialog windows:
• Start window (Starting the dialog)
• Command without selection (Confirming a command)
• Command with selection (Selecting a command)
• Command with cancellation (Cancelling a command)
• Command with selection and cancellation (Selecting and cancelling a command)
The five dialog windows are described in the following sections.
5.1 Starting the dialog
Fig. 6a and Fig. 6b show two typical dialog windows to start communication with the terminal. Select the:
• C button to clear the LEDs (if required), or
• E button to enter the menu tree
The text (Ready, Start, Trip) in row one of the window in Fig. 6a and Fig. 6b describesthe function of the LEDs that are at the top of the display when it is active.
Fig. 6 Start dialog windows, typical examples
RE.5.. VER 1.0C=Clear LEDsE=Enter menu
a) b)
TripStartReady RE.5.. VER 1.0C=QuitE=Enter menu
TripStartReady
16 1MRK 504 039-UEN
-
Dialog window How to use the human machine interface
5.2 Confirming a command
Fig. 7 shows a typical example of a dialog window for command without selection. The instructions in the first two rows describe possible actions. YES and NO with the flashing cursor on one of them appear in the bottom row. You can move the cursor from one to another possibility by selecting the right or left arrows. The user must, after taking the decision, confirm the same one by selecting the E button.
Fig. 7 Dialogue window for command with confirmation
1 Position the cursor on YES and select the E button to confirm the instruc-tions (commands) in rows one and two.
2 Position the cursor on NO and select the E button to exit the dialog window. without saving changes that were made during communication within the menu tree. Or select C with the same result.
5.3 Selecting a command
Fig. 8 Dialogue window for command with selection
Use the up or down buttons to position the cursor on a command. Select YES to exe-cute the command. Select NO to cancel and exit the dialog window.
Instruction 2Instruction 1
NOYES
Command nInstruction 1
NOYES
V
171MRK 504 039-UEN
-
Dialog window How to use the human machine interface
5.4 Cancelling a command
Fig. 9 shows a typical dialog window for command with cancellation. Use the right or left arrows to move to YES, NO or CANCEL. Then select E to confirm your selection. If you select CANCEL confirmed with E, you return to the window that was shown on the display before the dialog window appeared.
Fig. 9 Dialogue window for command with cancellation
5.5 Selecting and cancelling a command
Fig. 10 Dialogue window for a command with selection and cancelling
Here you can select the command in row two, which is indicated by the up or down arrow at the end of the row.
Use the right or left arrows to position the cursor on YES, NO or CANCEL. Select YES to execute the command. Select NO or CANCEL to cancel and exit the dialog window.
Instruction 2Instruction 1
NOYES CANCEL
Command Instruction V
NOYES CANCEL
18 1MRK 504 039-UEN
-
How to use different softwaretools
The chapter “How to use different software tools”.This chapter instructs the user how different software tools can be used for handling the protection terminal. These software products are used in a personal computer for interacting with the terminal.
Setting ....................................................................................................................21
PST ....................................................................................................................21
Product overview ..........................................................................................21Operating environment .................................................................................21Functionality ..................................................................................................21PST documentation ......................................................................................22
HV/REx 500 .......................................................................................................22
Product overview ..........................................................................................22Operating environment .................................................................................22Functionality ..................................................................................................23HV/RET 521 documentation .........................................................................23
HV/Control..........................................................................................................23
Product overview ..........................................................................................23Operating environment .................................................................................24Functionality ..................................................................................................24HV/Control documentation............................................................................ 24
HV/Voltage Control ............................................................................................25
Product overview ..........................................................................................25Operating environment .................................................................................25Functionality ..................................................................................................25HV/Control documentation............................................................................ 26
191MRK 504 039-UEN
-
How to use different softwaretools
20 1MRK 504 039-UEN
-
PST
Setting
How to use different SW-tools
Setting
1 PST
1.1 Product overview
The Parameter Setting Tool (PST) is a tool for managing parameters for protection and control terminals and relays.You can read the parameters from the terminal, edit the parameter values and write the parameter values to the terminal. You can also edit the parameters in advance and later, when the terminal is available, write the parameters to the terminal.
PST is delivered as a part of the selected navigation environment. Supported naviga-tion environments are CAP 531 and MicroSCADA. The combination of CAP 531 and PST is denoted CAP 540.
Since PST also supports communication via telephone modems, it gives the possibility to “travel” to the station by communication link, making physical presence in the sta-tion unnecessary.
1.2 Operating environment
PST is primarily a MS Windows application intended to run on a standard PC. The application is available for many Windows operating systems 95/98, NT, 2000, XP. See details in the PST manual. PSTcan also be installed as a one-place application as well as a client-server application in a LAN network of computers.
1.3 Functionality
Terminal parameter setting and supervision, sometimes also called protection/control monitoring, lets the user display information and change settings from a PC in the same way as from the built-in HMI (Human-Machine-Interface) on the front of the ter-minal.
211MRK 504 039-UEN
-
HV/REx 500
Setting
How to use different SW-tools
1.4 PST documentation
The PST user’s manual consists of these main parts:
See “Referenced publications” on page 83.
2 HV/REx 500
2.1 Product overview
HV/REx 500 is intended for parameter setting and event handling, in MicroSCADA applications, of the corresponding RET 521 terminal.
The HV/REx 500 software module is included in the LIB 520 high-voltage process package, which is a part of the Application Software Library within MicroSCADA applications. The information presented on the MicroSCADA screen is similar to the presentation of the Station Monitoring System (SMS).
The HV/REx 500 software consists of three functional parts:
• Read terminal information
• Change terminal settings
• Handling of spontaneous events for presentation in lists
2.2 Operating environment
The software runs on a PC system using many operating system Windows/NT/2000. To run the HV/REx 500 software, also the MicroSCADA 8.4.4 and LIB 520 rev. 4.0.4 must be available. See own manuals for requirement details.
Table 1:
Item: Description:
Instructions Instructions for:• Installation.
• Setup of communication.
• Change of parameter values
• Compare PST parameters with terminal values
• Read and write parameters to/from the terminal.
• Graphical User Interface (GUI).
Appendix Glossary and references to Users Manuals.
22 1MRK 504 039-UEN
-
HV/Control
Setting
How to use different SW-tools
2.3 Functionality
Protection parameter setting and supervision, sometimes also called protection moni-toring, lets the user display information and change settings from a MicroSCADA sys-tem in the same way as from the built-in HMI (Human-Machine-Interface) on the front of the terminal.
There are also information available only by using HV/REx 500 and MicroSCADA, such as time tagged disturbance reports.
2.4 HV/RET 521 documentation
The HV/RET 521 user’s manual consists of these main parts:
See “Referenced publications” on page 83.
3 HV/Control
3.1 Product overview
The HV/Control software module is intended to be used for control functions in REx 5xx terminals. The software module includes parts intended to be used together with the voltage control function in RET 521. These parts contain the process picture, dia-logs and process database for the application in the MicroSCADA.
The HV/Control software module is included in the LIB 520 high-voltage process package, which is a part of the Application Software Library within MicroSCADA applications.
Item: Description:
Instructions Installation instruction.
Technical descrip-tion
Describes the general functionality and graphical representation for these functions:
• Data groups
• Password handling
• Event tool
Appendix Includes a complete file listing, list of process objects and updated files.
231MRK 504 039-UEN
-
HV/Control
Setting
How to use different SW-tools
The HV/Control software consists of these functional parts:
• HV General bay
• HV Breaker, Disconnector and Earthing switch
• Overview Bay
• HV Measurement
• HV REx 5xx Supervision
HV Measurement and HV REx 5xx Supervision can be used for RET 521.
3.2 Operating environment
The software runs on a PC system using many operating system Windows/NT/2000. To run the HV/Control software, also the MicroSCADA 8.4.4 and LIB 520 rev. 4.0.4 must be available. See own manuals for requirement details.
3.3 Functionality
HV/Control is mainly used to handle control and supervision functions via a process picture in MicroSCADA applications. The control function consists of open/close commands of high-voltage apparatuses including corresponding position indications. The commands are performed from a control dialog window, which is automatically displayed when the device to be controlled is selected. Within the control dialog also other features are available such as e.g. blocking functions and remote/station han-dling.
3.4 HV/Control documentation
The HV/Control user’s manual consists of these main parts:
See “Referenced publications” on page 83.
Item: Description:
Instructions Installation instruction.
Technical descrip-tion
Describes the general functionality and graphical representation for these functions:
• HV General bay
• HV Breaker, Disconnector and Earthing switch
• Overview Bay
• HV Measurement
• HV REx 5xx Supervision
Appendix Files, such as format pictures, dialog pictures, text files and help files are listed here.
24 1MRK 504 039-UEN
-
HV/Voltage Control
Setting
How to use different SW-tools
4 HV/Voltage Control
4.1 Product overview
The HV/Voltage Control software module is intended to be used for voltage control functions in RET 521 terminals. The software module includes parts intended to be used together with the voltage control function in RET 521. The module contains the process picture, dialogs and process database for the voltage control application in the MicroSCADA.
The HV/ Voltage Control software module is included in the LIB 520 high-voltage process package, which is a part of the Application Software Library within MicroSCADA applications.
The HV/Voltage Control software consists of these functional parts:
• HV Voltage Control
• HV Voltage Control measurements
4.2 Operating environment
The software runs on a PC system using many operating system Windows/NT/2000. To run the HV/Control software, also the MicroSCADA 8.4.4 and LIB 520 rev. 4.0.4 must be available. See own manuals for requirement details.
4.3 Functionality
HV/Voltage Control is used for monitoring and controlling the voltage on the second-ary side of the power transformer via a process picture in MicroSCADA applications. The raise/lower commands are performed, automatically or manually, from a control dialog window, which is automatically displayed when the device to be controlled is selected. Within the control dialog also other features are available such as e.g. block-ing functions and remote/station handling.
251MRK 504 039-UEN
-
HV/Voltage Control
Setting
How to use different SW-tools
4.4 HV/Control documentation
The HV/Control user’s manual consists of these main parts:
See “Referenced publications” on page 83.
Table 2:
Item: Description:
Instructions Installation instruction.
Technical descrip-tion
Describes the general functionality and graphical representation for these functions:
• HV Voltage Control
• HV Voltage Control measurements
Appendix Files, such as format pictures, dialog pictures, text files and help files are listed here.
261MRK 504 039-UEN
-
How to perform specificoperations
The chapter “How to perform specific operations”This chapter instructs the user how to perform specific operations, eg how to read ser-vice values, internal events, disturbance reports and terminal status.
How to set internal terminal time........................................................................29
Internal events....................................................................................................29
Using the built-in HMI....................................................................................30Using front-connected PC or SMS................................................................32
How to read service values ................................................................................34
General .........................................................................................................34Information subgroups .................................................................................. 35
Analog Input Module (AIM) ......................................................................35Different I/O units .....................................................................................35Transformer Differential Protection ..........................................................36Disturbance report ...................................................................................36Earth Fault ............................................................................................... 36Frequency Measurement .........................................................................37Frequency Function .................................................................................37OverCurrent .............................................................................................38General Function .....................................................................................38Overexcitation Protection.........................................................................38Overvoltage..............................................................................................39Thermal overload .....................................................................................39Under Voltage ..........................................................................................39Voltage Control ........................................................................................40Active group .............................................................................................40Internal time .............................................................................................40
271MRK 504 039-UEN
-
How to perform specificoperations
28 1MRK 504 039-UEN
-
How to set internal terminal time How to perform specific operations
1 How to set internal terminal time
Use the setting menu to set the internal time for a complete terminal, acc. to Fig. 1.
Fig. 1 Setting internal time within a terminal
After you select the E button, the data window changes from Fig. 1a to Fig. 1b. Note that the cursor is always positioned under the seconds value when you begin. Select the left arrow to move to the date value.
Real time in a terminal uses these values:
• YYYY, year
• MMM, first three letters of the month’s name
• DD, day in the month
• hh, hour
• mm, minutes
• ss, seconds
Apply the rules for setting a string when you set the month value. All other values are real values.
Note! If the TIME function block is configured in a downloaded CAP configuration the time can only be set from the HMI, if the “SYNSOURC” and “COARSE” parameters are set to “none” in the CAP configuration
2 Internal events
Internal events are generated by the built-in supervisory functions. The supervisory functions supervise the status of the various modules in the terminal and, in case of failure, a corresponding event is generated. Similarly, when the failure is corrected, a corresponding event is generated.
.Set/TimeDate & Time=YYYY-MMM-DD
a)
YYYY-MMM-DD
b)
E.Set/TimeDate & Time=
hh:mm:ss hh:mm:ss
291MRK 504 039-UEN
-
Internal events How to perform specific operations
Apart from the built-in supervision of the various modules, events are also generated when these functions change status:
• Built-in real time clock (in operation/out of order)
• External time synchronization (in operation/out of order)
Events are also generated on these occasions:
• Whenever any setting in the terminal is changed
• When the content of the disturbance report is erased
Internal events can be presented at three different locations:
• At the terminal using the built-in HMI
• Remotely using front-connected PC or SMS
• Remotely using SCS
2.1 Using the built-in HMI
If an internal fault has occurred, the built-in HMI displays information under:
TerminalReportSelfSuperv
Here, there are indications of internal failure (serious fault), or internal warning (minor problem).
There are also indications regarding the faulty unit, according to Table 1.
30 1MRK 504 039-UEN
-
Internal events How to perform specific operations
You can also connect the internal signals, such as INT--FAIL and INT--WARN to binary output contacts for signalling to a control room.
In the Terminal Status information, you can view the present information from the self-supervision function. Indications of failure or warnings for each hardware module are provided, as well as information about the external time synchronization and the internal clock, according to Table 1. Recommendations are given on measures to be taken to correct the fault. Loss of time synchronization can be considered as a warning only. The terminal has full functionality without time synchronization.
Table 1: Self-supervision signals in the built-in HMI
HMI information: Status: Signal name:
Activates summary signal:
Description:
InternFail OK / FAIL INT--FAIL Internal fail sum-mary. Signal activa-tion will reset the terminal
Intern Warning OK /WARNING INT--WARNING
Internal warning summary
NUM-modFail OK / FAIL INT--NUMFAIL
INT--FAIL Numerical module failed. Signal activa-tion will reset the ter-minal
NUM-modWarning OK /WARNING INT--NUMWARN
INT--WARNING
Numerical module warning (failure of clock, time synch.
PCIPx-AIMn OK / FAIL AIMn-Error INT--FAIL Analogue input mod-ule n failed. Signal activation will reset the terminal
CANPx-YYYn OK / FAIL IOn--Error INT--FAIL I/O module (YYY = BIM, BOM, IOM) n failed. Signal activa-tion will reset the ter-minal
CANPx-MIM1 OK / FAIL MIM1-Error INT--FAIL mA input module MIM1 failed. Signal activation will reset the terminal
Real Time Clock OK /WARNING INT--RTC INT--WARNING
Internal clock is reset - Set the clock
Time Sync OK /WARNING INT--TSYNC INT--WARNING
No time synchroniza-tion
311MRK 504 039-UEN
-
Internal events How to perform specific operations
2.2 Using front-connected PC or SMS
Here two summary signals appear, self-supervision summary and numerical module status summary. These signals can be compared to the internal signals as:
• Self-supervision summary = INT--FAIL and INT--WARNING
• CPU-module status summary = INT--NUMFAIL and INT--NUMWARN
When an internal fault has occurred, you can retrieve extensive information about the fault from the list of internal events available in the PST part:
Terminal Report- Internal Events
The list of internal events provides valuable information, which can be used during commissioning and during fault tracing.
The internal events are time tagged with a resolution of 1 ms and stored in a list. The list can store up to 40 events. The list is based on the FIFO principle, when it is full, the oldest event is overwritten. The list cannot be cleared; its content cannot be erased.
The internal events in this list not only refer to faults in the terminal, but also to other activities, such as change of settings, clearing of disturbance reports, and loss of exter-nal time synchronization.
The information can only be retrieved with the aid of the SM/RET 521 software pack-age. The PC can be connected either to the port at the front or at the rear of the termi-nal.
These events are logged as internal events.
32 1MRK 504 039-UEN
-
Internal events How to perform specific operations
Table 2: Events available for the internal event list in the terminal
Event message: Description: Generating signal:
INT--FAIL Off Internal fail status INT--FAIL (reset event)
INT--FAIL ■ On INT--FAIL (set event)
INT--WARNING Off Internal warning status lNT--WARNING (reset event)
INT--WARNING ■ On INT--WARNING (set event)
INT--NUMFAIL Off Numerical module fatal error status
INT--NUMFAIL (reset event)
INT--NUMFAIL ■ On INT--NUMFAIL (set event)
INT--NUMWARN Off Numerical module non-fatal error status
INT--NUMWARN (reset event)
INT--NUMWARN ■ On INT--NUMWARN (set event)
IOn--Error Off In/Out module No. n sta-tus
IOn--Error (reset event)
IOn--Error ■ On IOn--Error (set event)
AIMn-Error Off Analogue input module No. n status
AIMn-Error (reset event)
AIMn-Error ■ On AIMn-Error (set event)
MIM1-Error Off mA-input module status MIM1-Error (reset event)
MIM1-Error ■ On MIM1-Error (set event)
INT--RTC Off Real Time Clock (RTC) status
INT--RTC (reset event)
INT--RTC ■ On INT--RTC (set event)
INT--TSYNC Off External time synchroni-zation status
INT--TSYNC (reset event)
INT--TSYNC ■ On INT--TSYNC (set event)
INT--SETCHGD Any settings in terminal changed
DRPC-CLEARED All disturbances in Dis-turbance report cleared
331MRK 504 039-UEN
-
How to read service values How to perform specific operations
3 How to read service values
3.1 General
The Service report menu lets you display information about the:
• Measured values from protection functions.
• Operation conditions for protected objects in the power systems.
• Terminal.
The amount of available information depends on the number of basic and optional functions in a terminal.
A certain subgroup is displayed on the local HMI if the corresponding function is installed in the terminal. These subgroups describe possible types of informationincluding amongst others the following:
• Analog Input Module (AIM)
• Binary Inputs/Outputs
• Differential current
• DisturbReport
• EarthFault
• Frequency Measurement
• Milliampere input module (MIM)
• OverCurrent
• Overexcitation
• OverVoltage
• Thermal Overload
• UnderVoltage
• Voltage Control
• Active Group
• Internal time
34 1MRK 504 039-UEN
-
How to read service values How to perform specific operations
3.2 Information subgroups
3.2.1 Analog Input Module (AIM)
HMI branch:
ServiceReportPCIPx-AIMy (x=3, 7; y=1, 2)
The terminal displays the values of currents and voltages connected to the analogue input board.
The appearance of analogue input quantities as they enter the terminal from the current and voltage instrument transformers, depends on the number of current and voltage inputs on the Analogue Input Module.
3.2.2 Different I/O units
HMI branch:
ServiceReportCANPxx-MODULEy
(xx=9, 10, 11, 12; MODULE=BIM, BOM, IOM, MIM; y=1, 2, 3, 4)
Different RET 521 terminals can comprise different I/O units, which serve like an interface between the terminal and external elements of the power system, such as cir-cuit breakers, isolators, and measuring converters.
The current values of input logical signals, logical signals configured to different out-put elements (relays) and analogue direct current measuring inputs are available under respective CANPx- submenu.
The terminal displays analogue values of each input on each MIM and in case the MIM is used for measuring the tap changer position, a calculated value shows the posi-tion of the tap changer.
351MRK 504 039-UEN
-
How to read service values How to perform specific operations
3.2.3 Transformer Differential Protection
HMI branch:
ServiceReportFunctions
TransfDiffMeasurands
Protection terminals which have differential protection displays values of the differen-tial and bias currents:
• Bias current in A
• Differential current, phase 1, in A
• Differential current, phase 2, in A
• Differential current, phase 3, in A
• Actual tap changer position
3.2.4 Disturbance report
HMI branch:
ServiceReportFunctions
DisturbReport
The service report on the disturbance report function contains the:
• Percentage of the used dedicated memory capacity for purposes of the distur-bance recording when it is built into the terminal.
• Sequence numbers of the disturbances recorded during the same day
• Status of built-in analogue triggers that can start the operation of the disturbance recorder
• Status of function outputs
3.2.5 Earth Fault
HMI branch:
ServiceReportFunctions
EarthFaultTEFx
Measurands
36 1MRK 504 039-UEN
-
How to read service values How to perform specific operations
The terminal displays
• Residual current in A
• Residual voltage in kV
HMI branch:
ServiceReportFunctions
RestrictedEFREFx
• Bias current in A
• Differential current in A
3.2.6 Frequency Measurement
HMI branch:
ServiceReportFunctions
FreqMeasurmntMeasurands
The terminal displays the power system frequency in Hz. The frequency is calculated from voltage analogue input(s).
3.2.7 Frequency Function
HMI branch:
ServiceReportFunctions
FreqFunctionFRFx
Measurands
The terminal displays the power system frequency in Hz.
371MRK 504 039-UEN
-
How to read service values How to perform specific operations
3.2.8 OverCurrent
HMI branch:
Service ReportFunctions
OverCurrentTOCx
Measurands
The terminal displays the highest current in A.
3.2.9 General Function
HMI branch:
Service ReportFunctions
GenFunctionGFxx
Measurands
The terminal displays the measured current in A.The terminal displays the measured voltage in kV.
3.2.10 Overexcitation Protection
HMI branch:
ServiceReportFunctions
OverexcitationMeasurands
The terminal displays
• Relative voltage to frequency ratio, in %
• Time to trip overexcitation in seconds
• Thermal status in % of trip value
38 1MRK 504 039-UEN
-
How to read service values How to perform specific operations
3.2.11 Overvoltage
HMI branch:
ServiceReportFunctions
OverVoltageTOVx
Measurands
The terminal displays the highest of measured voltages in kV.
3.2.12 Thermal overload
HMI branch:
ServiceReportFunctions
ThermOverloadMeasurands
The terminal displays:
• Measured current in % of thermal overload base current
• Thermal status in % of heat content trip level
• Time to trip calc. NotActive/>1.3*TimeConst/Active
• Time to trip thermal overload, in min.
• Time to reset lockout calc. NotActive/>1.3*TimeConst/Active
• Time to reset lockout function, in min.
3.2.13 Under Voltage
HMI branch:
ServiceReportFunctions
UnderVoltageTUVx
Measurands
The terminal displays the lowest of measured voltages in kVl
391MRK 504 039-UEN
-
How to read service values How to perform specific operations
3.2.14 Voltage Control
HMI branch:
ServiceReportFunctions
Voltage ControlMeasurands
The terminal displays:
• Actual busbar voltage (line voltage) in kV
• Calculated phase-to-phase compensated voltage in kV
• Actual set voltage (own terminal) compensated for voltage adj. in kV
• Status of the voltage ctrl. blocking cond, None/Tot/Auto/Part
• Actual reactive circulating current in A (for parallel voltage control)
• Actual tap changer position
• Number of remaining operations for contacts, count(s)
• SPA presentation of last date of reset of the contact life counter (CL)
• Total number of operations, count(s)
• SPA presentation of last date of reset of the operation counter
• Calculated mean busbar voltage for a group (for parallel voltage control)
• Actual set group voltage (mean values of terminals in a group) compensated for voltage adj. in kV (for parallel voltage control)
• Activated LVA-input
3.2.15 Active group
HMI branch:
ServiceReportActive Group
The current active setting group is displayed under this submenu.
3.2.16 Internal time
HMI branch:
ServiceReportTime
The internal terminal time can be checked under this submenu. The data comprises information on the date and on the time down to 1 second.
40 1MRK 504 039-UEN
-
Human machine interface
The chapter “Human machine interface”.This chapter describes the tree structure of the human machine interface. Each menu is displayed with its submenues.
Introduction ........................................................................................................43
Display for Disturbance Report menu ................................................................44
Display for Service Report menu .......................................................................45
Display for the Settings menu ............................................................................ 61
Display for Terminal Report menu ..................................................................... 75
Display for Configuration menu..........................................................................76
Display for Command menu...............................................................................79
Display for Test menu ........................................................................................81
411MRK 504 039-UEN
-
Human machine interface
42 1MRK 504 039-UEN
-
Introduction Human machine interface – tree structure
1 Introduction
This chapter describes the structure of the human machine interface (HMI).
The following conventions are used:
1 The table header displays the actual path of the information shown in the cells. The information in the header is displayed in an cell with a greyscale-fill.
Example:
Is equal to:
RET 521ServRep
FuncDistRep
2 The path to the end-nodes appear in ����.
3 Data nodes (parameters) appear in ������.
Example:
4 Dialogues and references to other documents are located in thicker frames.
RET 521 RET 521/ServRep .ServRep/Func .Func/DistRep
.TripVal/Fault
Input1 (*)
Input2 (*)
431MRK 504 039-UEN
-
Display for Disturbance Report menu Human machine interface – tree structure
2 Display for Disturbance Report menu
RET 521 RET 521/DistRep .DistRep/Disturb .Disturb/Dist1 .Dist1/Time .TripVal/PreFlt
DisturbReport Disturbances Disturbance1 TimeOfDisturb Time Of Disturb Input1 (*)
ServiceReport ManualTrig Disturbance2 TrigSignal Input2 (*)
Settings ClearDistRep Disturbance3 Indications .Dist1/TrigSig Input3 (*)
TerminalReport ClearLEDs Disturbance4 TripValues Trig Signal Input4 (*)
Configuration Disturbance5 Input5 (*)
Command Disturbance6 .Dist1/Indic Input6 (*)
Test Disturbance7 Input7 (*)
Disturbance8 Input1 (*) Input8 (*)
Disturbance9 . Input9 (*)
Disturbance10 Input48 (*) Input10 (*)
Frequency
.Dist1/TripVal .TripVal/Fault
PreFault Input1 (*)
Fault Input2 (*)
Input3 (*)
“Manual Trig” Input4 (*)
Command Input5 (*)
with confirmation Input6 (*)
Input7 (*)
“Clear DistRep” Input8 (*)
Command Input9 (*)
with confirmation Input10 (*)
“Clear LEDs” (*) User name
Command default name is
with confirmation shown
44 1MRK 504 039-UEN
-
Display for Service Report menu Human machine interface – tree structure
3 Display for Service Report menu
RET 521 RET 521/ServRep .ServRep/Func .Func/HLED .HLED/Status
DisturbReport Functions HMI LED Status StatusHMILED1
ServiceReport ActiveGroup DisturbReport FuncOutputs StatusHMILED2
Settings PCIP3-AIM1 TransfDiff StatusHMILED3
TerminalReport PCIP7-AIM2 ($) VoltageControl StatusHMILED4
Configuration CANP9/10/11/12 OverCurrent StatusHMILED5
BOM1/BIM2/IOM3/ StatusHMILED6
MIM1 ($) StatusHMILED7
Command Time GenFunction StatusHMILED8
Test RestrictedEF StatusHMILED9
EarthFault StatusHMILED10
UnderVoltage StatusHMILED11
OverVoltage StatusHMILED12
Overexcitation StatusHMILED13
ThermOverload StatusHMILED14
FreqFunction StatusHMILED15
FreqMeasurmnt StatusHMILED16
($) Visible only if that StatusHMILED17
option is installed StatusHMILED18
Functions visible only .HLED/Outputs
if they are installed HLED-NEWIND
HLED-FAIL
451MRK 504 039-UEN
-
Display for Service Report menu Human machine interface – tree structure
RET 521 RET 521/ServRep .ServRep/Func .Func/DistRep .DistRep/Memory
DisturbReport Functions HMI LED MemoryUsed Memory Used
ServiceReport ActiveGroup DisturbReport SequenceNo
Settings PCIP3-AIM1 ($) TransfDiff AnalogTrigStat .DistRep/SeqNo
TerminalReport PCIP7-AIM2 ($) VoltageControl FuncOutputs SequenceNo
Configuration CANP9/10/11/12 OverCurrent
BOM1/BIM2/IOM3/ RestrictedEF .DistRep/AnaTrig
MIM1 ($) EarthFault Input1 < (*)
Command Time UnderVoltage Input1 > (*)
Test OverVoltage Input2 < (*)
Overexcitation Input2 > (*)
ThermOverload Input3 < (*)
FreqFunction Input3 > (*)
FreqMeasurmnt Input4 < (*)
($) Visible only if that Input4 > (*)
option is installed Input5 < (*)
Input5 > (*)
Input6 < (*)
Input6 > (*)
.ServRep/ActGrp Input7 < (*)
Active Group Input7 > (*)
Input8 < (*)
Input8 > (*)
Functions visible only Input9 < (*)
if they are installed Input9 > (*)
Input10 < (*)
Input10 > (*)
.DistRep/Outputs
DREP-ERROR
DREP-OFF
DREP-RECSTART
DREP-RECMADE
DREP-CLEARED
DREP-MEMUSED
(*) User name
default name is
shown
46 1MRK 504 039-UEN
-
Display for Service Report menu Human machine interface – tree structure
RET 521 RET 521/ServRep .ServRep/Func .Func/DIFP .DIFP/Meas
DisturbReport Functions HMI LED Measurands Ibias
ServiceReport ActiveGroup DisturbReport FuncOutputs IdiffL1
Settings PCIP3-AIM1 ($) TransfDiff IdiffL2
TerminalReport PCIP7-AIM2 ($) VoltageControl IdiffL3
Configuration CANP9/10/11/12 OverCurrent TapPosition
BOM1/BIM2/IOM3/ GenFunction
MIM1 ($) RestrictedEF .DIFP/Outputs
Command Time EarthFault DIFP-ERROR
Test UnderVoltage DIFP-TRIP
OverVoltage DIFP-TRUNR
Overexcitation DIFP-TRRES
ThermOverload DIFP-STL1
FreqFunction DIFP-STL2
FreqMeasurmnt DIFP-STL3
($) Visible only if that DIFP-WAVBLKL1
option is installed DIFP-WAVBLKL2
Functions visible only DIFP-WAVBLKL3
if they are installed DIFP-I2BLKL1
DIFP-I2BLKL2
DIFP-I2BLKL3
DIFP-I5BLKL1
DIFP-I5BLKL2
DIFP-I5BLKL3
471MRK 504 039-UEN
-
Display for Service Report menu Human machine interface – tree structure
RET 521 RET 521/ServRep .ServRep/Func .Func/VCTR .VCTR/Meas .VCTR/Outputs
DisturbReport Functions HMI LED Measurands BusbarVoltage VCTR-ERROR
ServiceReport ActiveGroup DisturbReport FuncOutputs CompVoltage VCTR-REMOTE
Settings PCIP3-AIM1 ($) TransfDiff ActualUsetSngl VCTR-STATION
TerminalReport PCIP7-AIM2 ($) VoltageControl BlockCond VCTR-LOCAL
Configuration CANP9/10/11/12 OverCurrent CircCurrent (*) VCTR-LOCALMMI
BOM1/BIM2/IOM3/ GenFunction TapPosition VCTR-MAN
MIM1 ($) RestrictedEF ContactLife VCTR-AUTO
Command Time EarthFault CLResetDate VCTR-SINGLE (*)
Test UnderVoltage NoOfOperations VCTR-PARALLEL (*)
OverVoltage OCResetDate VCTR-ADAPT (*)
Overexcitation BusvoltParl (*) VCTR-TOTBLK
ThermOverload ActualUsetParl (*) VCTR-AUTOBLK
FreqFunction LVAInput VCTR-IBLK
FreqMeasurmnt VCTR-UBLK
($) Visible only if that VCTR-REVACBLK
option is installed (*) Visible only if VCTR-HUNTING
Functions visible VCTR parallell VCTR-TRFDISC
only if they are option is used VCTR-POSERR
installed VCTR-CMDERR
VCTR-UMIN
(**) Visible only if VCTR-UMAX
VCTR parallell VCTR-LOPOS
option for eight VCTR-HIPOS
transformer is VCTR-TCOPER
used VCTR-TCERR
VCTR-COMMERR (*)
VCTR-ICIRC (*)
VCTR-T1PG (*)
VCTR-T2PG (*)
VCTR-T3PG (*)
VCTR-T4PG (*)
VCTR-T5PG (**)
VCTR-T6PG (**)
VCTR-T7PG (**)
VCTR-T8PG (**)
VCTR-RAISE
VCTR-LOWER
VCTR-URAISE
VCTR-ULOWER
48 1MRK 504 039-UEN
-
Display for Service Report menu Human machine interface – tree structure
VCTR-WINHUNT
VCTR-TIMERON
VCTR-VTALARM (*)
VCTR-HOMING (*)
VCTR-POWERMON
RET 521 RET 521/ServRep .ServRep/Func .Func/VCTR .VCTR/Meas .VCTR/Outputs
491MRK 504 039-UEN
-
Display for Service Report menu Human machine interface – tree structure
RET 521 RET 521/ServRep .ServRep/Func .Func/TOC .TOC/TOC1 (*) .TOC1/Meas
DisturbReport Functions HMI LED TOC1 Measurands Imax
ServiceReport ActiveGroup DisturbReport TOC2 FuncOutputs
Settings PCIP3-AIM1 ($) TransfDiff TOC3 .TOC1/Outputs
TerminalReport PCIP7-AIM2 ($) VoltageControl TOC1-ERROR
Configuration CANP9/10/11/12 OverCurrent TOC1-TRIP
BOM1/BIM2/IOM3/ GenFunction TOC1-TRLS
MIM1 ($) RestrictedEF TOC1-TRHS
Command Time EarthFault TOC1-STLSL1
Test UnderVoltage TOC1-STLSL2
OverVoltage TOC1-STLSL3
Overexcitation TOC1-STHSL1
ThermOverload TOC1-STHSL2
FreqFunction TOC1-STHSL3
FreqMeasurmnt
($) Visible only if that
option is installed
Functions visible (*) Similar for
only if they are TOC2 & TOC3
installed
50 1MRK 504 039-UEN
-
Display for Service Report menu Human machine interface – tree structure
RET 521 RET 521/ServRep .ServRep/Func .Func/GF .GF/GF01 (*) .GF01/Meas
DisturbReport Functions HMI LED GF01 Measurands Imeasured
ServiceReport ActiveGroup DisturbReport GF02 FuncOutputs Umeasured
Settings PCIP3-AIM1 ($) TransfDiff GF03
TerminalReport PCIP7-AIM2 ($) VoltageControl GF04 .GF01/Outputs
Configuration CANP9/10/11/12 OverCurrent GF05 GF01-ERROR
BOM1/BIM2/IOM3/ GenFunction GF06 GF01-TROC
MIM1 ($) RestrictedEF GF07 GF01-TROCLS
Command Time EarthFault GF08 GF01-STOCLS
Test UnderVoltage GF09 GF01-TROCHS
OverVoltage GF10 GF01-STOCHS
Overexcitation GF11 GF01-I2BLK
ThermOverload GF12 GF01-TROV
FreqFunction GF01-STOV
FreqMeasurmnt GF01-TRUV
($) Visible only if that GF01-STUV
option is installed
Functions visible (*) Similar for
only if they are GF02 to GF12
installed
511MRK 504 039-UEN
-
Display for Service Report menu Human machine interface – tree structure
RET 521 RET 521/ServRep .ServRep/Func .Func/REF .REF/REF1 (*) .REF1/Meas
DisturbReport Functions HMI LED REF1 Measurands Ibias
ServiceReport ActiveGroup DisturbReport REF2 FuncOutputs Idiff
Settings PCIP3-AIM1 ($) TransfDiff REF3
TerminalReport PCIP7-AIM2 ($) VoltageControl .REF1/Outputs
Configuration CANP9/10/11/12 OverCurrent REF1-ERROR
BOM1/BIM2/IOM3/ GenFunction REF1-TRIP
MIM1 ($) RestrictedEF REF1-START
Command Time EarthFault
Test UnderVoltage
OverVoltage
Overexcitation
ThermOverload
FreqFunction
FreqMeasurmnt
($) Visible only if that
option is installed
Functions visible (*) Similar for
only if they are REF2 & REF3
installed
52 1MRK 504 039-UEN
-
Display for Service Report menu Human machine interface – tree structure
RET 521 RET 521/ServRep .ServRep/Func .Func/TEF .TEF/TEF1 (*) .TEF1/Meas If TEF1 is
DisturbReport Functions HMI LED TEF1 Measurands 3Io Directional
ServiceReport ActiveGroup DisturbReport TEF2 FuncOutputs 3Uo
Settings PCIP3-AIM1 ($) TransfDiff TEF3
TerminalReport PCIP7-AIM2 ($) VoltageControl .TEF1/Outputs
Configuration CANP9/10/11/12 OverCurrent TEF1-ERROR
BOM1/BIM2/IOM3/ GenFunction TEF1-TRIP
MIM1 ($) RestrictedEF TEF1-TRLS
Command Time EarthFault TEF1-TRHS
Test UnderVoltage TEF1-STLS
OverVoltage TEF1-STHS
Overexcitation TEF1-I2BLK
ThermOverload
FreqFunction
FreqMeasurmnt
($) Visible only if that
option is installed .TEF/TEF1 (*) .TEF1/Meas If TEF1 is
Functions visible Measurands 3Io Non-Directional
only if they are FuncOutputs
installed .TEF1/Outputs
TEF1-ERROR
TEF1-TRIP
TEF1-TRLS
TEF1-TRHS
TEF1-STLS
TEF1-STHS
TEF1-I2BLK
(*) Similar for
TEF2 & TEF3
531MRK 504 039-UEN
-
Display for Service Report menu Human machine interface – tree structure
RET 521 RET 521/ServRep .ServRep/Func .Func/TUV .TUV/TUV1 (*) .TUV1/Meas .Outputs/Error
DisturbReport Functions HMI LED TUV1 Measurands Umin TUV1-ERROR
ServiceReport ActiveGroup DisturbReport TUV2 FuncOutputs
Settings PCIP3-AIM1 ($) TransfDiff TUV3 .TUV1/Outputs .Outputs/SU
TerminalReport PCIP7-AIM2 ($) VoltageControl Error TUV1-TRIP
Configuration CANP9/10/11/12 OverCurrent SU TUV1-TRLS
BOM1/BIM2/IOM3/ GenFunction G3U TUV1-TRHS
MIM1 ($) RestrictedEF TUV1-STLS
Command Time EarthFault TUV1-STHS
Test UnderVoltage
OverVoltage .Outputs/G3U
Overexcitation TUV1-TRIPONE
ThermOverload TUV1-TRLSONE
FreqFunction TUV1-TRHSONE
FreqMeasurmnt TUV1-TRIPALL
($) Visible only if that TUV1-TRLSALL
option is installed TUV1-TRHSALL
Functions visible (*) Similar for TUV1-STLSL1
only if they are TUV2 & TUV3 TUV1-STLSL2
installed TUV1-STLSL3
TUV1-STHSL1
TUV1-STHSL2
TUV1-STHSL3
54 1MRK 504 039-UEN
-
Display for Service Report menu Human machine interface – tree structure
RET 521 RET 521/ServRep .ServRep/Func .Func/TOV .TOV/TOV1 (*) .TOV1/Meas .Outputs/Error
DisturbReport Functions HMI LED TOV1 Measurands Umax TOV1-ERROR
ServiceReport ActiveGroup DisturbReport TOV2 FuncOutputs
Settings PCIP3-AIM1 ($) TransfDiff TOV3 .TOV1/Outputs .Outputs/SU
TerminalReport PCIP7-AIM2 ($) VoltageControl TOV4 Error TOV1-TRIP
Configuration CANP9/10/11/12 OverCurrent TOV5 SU TOV1-TRLS
BOM1/BIM2/IOM3/ GenFunction TOV6 G3U TOV1-TRHS
MIM1 ($) RestrictedEF G3URES TOV1-STLS
Command Time EarthFault TOV1-STHS
Test UnderVoltage
OverVoltage .Outputs/G3U
Overexcitation TOV1-TRIPONE
ThermOverload TOV1-TRLSONE
FreqFunction TOV1-TRHSONE
FreqMeasurmnt TOV1-TRIPALL
($) Visible only if that TOV1-TRLSALL
option is installed TOV1-TRHSALL
Functions visible (*) Similar for TOV1-STLSL1
only if they are TOV2 to TOV6 TOV1-STLSL2
installed TOV1-STLSL3
TOV1-STHSL1
TOV1-STHSL2
TOV1-STHSL3
.Outputs/G3URES
TOV1-TRIP
TOV1-TRLS
TOV1-TRHS
TOV1-STLS
TOV1-STHS
551MRK 504 039-UEN
-
Display for Service Report menu Human machine interface – tree structure
RET 521 RET 521/ServRep .ServRep/Func .Func/OVEX .OVEX/Meas
DisturbReport Functions HMI LED Measurands V/Hz
ServiceReport ActiveGroup DisturbReport FuncOutputs tTRIP
Settings PCIP3-AIM1 ($) TransfDiff ThermalStatus
TerminalReport PCIP7-AIM2 ($) VoltageControl
Configuration CANP9/10/11/12 OverCurrent .OVEX/Outputs
BOM1/BIM2/IOM3/ GenFunction OVEX-ERROR
MIM1 ($) RestrictedEF OVEX-TRIP
Command Time EarthFault OVEX-ALARM
Test UnderVoltage
OverVoltage
Overexcitation
ThermOverload
FreqFunction
FreqMeasurmnt
.Func/THOL .THOL/Meas
Measurands Imeasured
FuncOutputs ThermalStatus
($) Visible only if that TimeToTrCalc
option is installed TimeToTrip
Functions visible TimeToRstCalc
only if they are TimeToReset
installed
.THOL/Outputs
THOL-ERROR
THOL-TRIP
THOL-ALARM1
THOL-ALARM2
THOL-LOCKOUT
56 1MRK 504 039-UEN
-
Display for Service Report menu Human machine interface – tree structure
RET 521 RET 521/ServRep .ServRep/Func .FUNC/FRF .FRF/FRF1 .FRF1/Meas
DisturbReport Functions HMI LED FRF1 Measurands f
ServiceReport ActiveGroup DisturbReport FRF2 FuncOutputs
Settings PCIP3-AIM1 ($) TransfDiff FRF2 .FRF1/Outputs
TerminalReport PCIP7-AIM2 ($) VoltageControl FRF1-ERROR
Configuration CANP9/10/11/12 OverCurrent FRF1-TROFR
BOM1/BIM2/IOM3/ GenFunction FRF1-STOFR
MIM1 ($) RestrictedEF FRF1-TRUFR
Command Time EarthFault FRF1-STUFR
Test UnderVoltage
OverVoltage
Overexcitation
ThermOverload
FreqFunction
FreqMeasurmnt
($) Visible only if that
option is installed (*) Similar for
Functions visible FRF2 & FRF3
only if they are
installed
571MRK 504 039-UEN
-
Display for Service Report menu Human machine interface – tree structure
RET 521 RET 521/ServRep .ServRep/Func .Func/FRME .FRME/Meas
DisturbReport Functions HMI LED Measurands f
ServiceReport ActiveGroup DisturbReport FuncOutputs
Settings PCIP3-AIM1 ($) TransfDiff
TerminalReport PCIP7-AIM2 ($) VoltageControl .FRME/Outputs
Configuration CANP9/10/11/12 OverCurrent FRME-ERROR
BOM1/BIM2/IOM3/ GenFunction
MIM1 ($) RestrictedEF
Command Time EarthFault
Test UnderVoltage
OverVoltage
Overexcitation
ThermOverload
FreqFunction
FreqMeasurmnt
($) Visible only if that
option is installed
Functions visible
only if they are
installed
58 1MRK 504 039-UEN
-
Display for Service Report menu Human machine interface – tree structure
RET 521 RET 521/ServRep .ServRep/AIM1 .AIM1/CH01(**) If channel one in AIM1
DisturbReport Functions AIM1-CH01 (*) MagCI01 is Current Channel
ServiceReport ActiveGroup AIM1-CH02 (*) AngleCI01
Settings PCIP3-AIM1 ($) AIM1-CH03 (*)
TerminalReport PCIP7-AIM2 ($) AIM1-CH04 (*)
Configuration CANP9/10/11/12 AIM1-CH05 (*)
BOM1/BIM2/IOM3/ AIM1-CH06 (*)
MIM1 ($) AIM1-CH07 (*)
Command Time AIM1-CH08 (*)
Test AIM1-CH09 (*)
AIM1-CH10 (*)
AIM1-ERROR .AIM1/ERROR
AIM1-ERROR
.ServRep/AIM2
AIM2-CH01 (*)
($) Visible only if that AIM2-CH02 (*)
option is installed AIM2-CH03 (*)
AIM2-CH04 (*)
AIM2-CH05 (*)
AIM2-CH06 (*)
AIM2-CH07 (*)
AIM2-CH08 (*)
AIM2-CH09 (*) .AIM2/CH09(**) If channel nine in AIM2
AIM2-CH10 (*) MagVI09 is Voltage Channel
AIM2-ERROR AngleVI09
.AIM2/ERROR
AIM2-ERROR
(*) User name (**) User name
Default name is will not be shown
shown
591MRK 504 039-UEN
-
Display for Service Report menu Human machine interface – tree structure
RET 521 RET 521/ServRep .ServRep/BIM1 (**)
DisturbReport Functions IO01-BI1 (*)
ServiceReport ActiveGroup IO01-BI2 (*)Settings PCIP3-AIM1 ($) .....TerminalReport PCIP7-AIM2 ($) .....
Configuration CANP9/10/11/12 IO01-BI15 (*)BOM1/BIM2/IOM3/ IO01-BI16 (*)MIM1 ($) IO1--Error
Command TimeTest .ServRep/IOM2 (**)
IO02-BI1 (*)
.....IO02-BI8 (*)IO02-BO1 (*)
.....($) Visible only if that IO02-BO12 (*)option is installed IO2--Error
.ServRep/BOM3 (**)IO03-BO1 (*)
(*) User name IO03-BO2 (*)default name is .....shown .....
IO03-BO23 (*)IO03-BO24 (*)
(**) This is an IO3--Errorexample of afull framework .ServRep/MIM1 (**)
MI11-ValueMI11-OltcMI12-Value
MI13-ValueMI14-ValueMI15-Value
MI16-Value
.ServRep/TimeDate & Time
60 1MRK 504 039-UEN
-
Display for the Settings menu Human machine interface – tree structure
4 Display for the Settings menu
RET 521 RET 521/Set .Set/DistRep .DistRep/Oper .Binary/Input1
DisturbReport DisturbReport Operation Operation TrigOperation
ServiceReport Functions SequenceNo PostRetrig TrigLevel
Settings ChangeActGrp SamplingRate SetLED
TerminalReport Time RecordingTimes .DistRep/SeqNo
Configuration BinarySignals SequenceNo
Command AnalogSignals
Test FreqSource .DistRep/SamRate
SamplingRate
.DistRep/RecTime
tPre
tPost
tLim
.DistRep/Binary
Input1 (*)
Input2 (*)
-
Input47 (*)
Input48 (*)
.DistRep/Analog .Analog/Input1 (**)
Input1 (*) Operation
Input2 (*) NominalValue
Input3 (*) TrigOperation
Input5 (*) TrigLevel
Input7 (*)
Input8 (*)
Input9 (*)
Input10 (*)
.DistRep/FreqSrc
FreqSource
(*) User name (**) User name will
shown by default not be shown
611MRK 504 039-UEN
-
Display for the Settings menu Human machine interface – tree structure
RET 521 RET 521/Set .Set/Func .Func/Grp1 .Grp1/HLED
DisturbReport DisturbReport Group1 HMI LED Operation
ServiceReport Functions Group2 TransfData tMax
Settings ChangeActGrp Group3 TransfDiff tRestart
TerminalReport Time Group4 VoltageControl SeqTypeLED1
Configuration OverCurrent SeqTypeLED2
Command GenFunction SeqTypeLED3
Test RestrictedEF SeqTypeLED4
Save as Group 1 EarthFault SeqTypeLED5
Save as Group 2 UnderVoltage SeqTypeLED6
Save as Group 3 OverVoltage SeqTypeLED7
Save as Group 4 Overexcitation SeqTypeLED8
Command with ThermOverload SeqTypeLED9
Confirmation FreqFunction SeqTypeLED10
According to ref. 2 FreqMeasurmnt SeqTypeLED11
SeqTypeLED12
SeqTypeLED13
“ChangeAct Grp” SeqTypeLED14
Command SeqTypeLED16
with confirmation SeqTypeLED17
According to ref. 2 SeqTypeLED18
62 1MRK 504 039-UEN
-
Display for the Settings menu Human machine interface – tree structure
RET 521 RET 521/Set .Set/Func .Func/Grp1 .Grp1/TfrData (*) .TfrData/Basic
DisturbReport DisturbReport Group1 HMI LED Basic Data VectorGroup 2W (***)
ServiceReport Functions Group2 TransfData Winding 1 Sr
Settings ChangeActGrp Group3 TransfDiff Winding 2
TerminalReport Time Group4 VoltageControl .TfrData/Wind1
Configuration OverCurrent Ir1
Command GenFunction Ur1
Test RestrictedEF
Save as Group 1 EarthFault .TfrData/Wind2
Save as Group 2 UnderVoltage Ir2
Save as Group 3 OverVoltage Ur2
Save as Group 4 Overexcitation
Command with ThermOverload
Confirmation FreqFunction
According to ref. 2 FreqMeasurmnt
“ChangeAct Grp” .Grp1/TfrData (**) .TfrData/Basic
Command Basic Data VectorGroup 3W (***)
with confirmation Winding 1
According to ref. 2 Winding 2 .TfrData/Wind1
Winding 3 Sr1
Ir1
(*) 2-winding Ur1
transformer
(**) 3-winding .TfrData/Wind2
transformer Sr2
(***) Both string Ir2
and value are Ur2
shown
.TfrData/Wind3
Sr3
Ir3
Ur3
631MRK 504 039-UEN
-
Display for the Settings menu Human machine interface – tree structure
RET 521 RET 521/Set .Set/Func .Func/Grp1 .Grp1/DIFP .DIFP/Basic
DisturbReport DisturbReport Group1 HMI LED BasicSettings Operation
ServiceReport Functions Group2 TransfData TapChanger CharactNo
Settings ChangeActGrp Group3 TransfDiff Idmin
TerminalReport Time Group4 VoltageControl Idunre
Configuration OverCurrent StabByOption
Command GenFunction I2/I1ratio
Test RestrictedEF I5/I1ratio
Save as Group 1 EarthFault ZSCSub
Save as Group 2 UnderVoltage CrossBlock
Save as Group 3 OverVoltage
Save as Group 4 Overexcitation .DIFP/TapCh
Command with ThermOverload NoOfTaps
Confirmation FreqFunction RatedTap
According to ref. 2 FreqMeasurmnt MinTapVoltage
MaxTapVoltage
“ChangeAct Grp”
Command
with confirmation
According to ref. 2
64 1MRK 504 039-UEN
-
Display for the Settings menu Human machine interface – tree structure
RET 521 RET 521/Set .Set/Func .Func/Grp1 .Grp1/VCTR .VCTR/Oper
DisturbReport DisturbReport Group1 HMI LED Operation Operation
ServiceReport Functions Group2 TransfData Voltages FSDMode
Settings ChangeActGrp Group3 TransfDiff Time Charact
TerminalReport Time Group4 VoltageControl Load Drop Comp .VCTR/Volt
Configuration OverCurrent Load Volt Adj Uset
Command GenFunction Manual Control Udeadband
Test RestrictedEF Rev Action Blk UdeadbandInner
Save as Group 1 EarthFault TapChangerCtrl Umax
Save as Group 2 UnderVoltage Power monitor Umin
Save as Group 3 OverVoltage Parallel Ctrl (*) Ublock
Save as Group 4 Overexcitation
Command with ThermOverload .VCTR/Time
Confirmation FreqFunction t1Use
According to ref. 2 FreqMeasurmnt t1
t2Use
t2
tMin
“ChangeAct Grp”
Command
with confirmation .VCTR/LDC
According to ref. 2 OperationLDC
OperCapaLDC
Rline
Xline
.VCTR/LVA
(*) Visible only LVAConst1
if VCTR parallel LVAConst2
option is used LVAConst3
LVAConst4
(**) Visible only VRAuto
if VCTR parallel
option for eight .VCTR/ManCtrl
transformers is ExtMMIPrio
used AutoBlock
Total block
.VCTR/Rev Act
OperationRA
tRevAct
651MRK 504 039-UEN
-
Display for the Settings menu Human machine interface – tree structure
.VCTR/TCCtrl
Iblock
LowVoltTap
HighVoltTap
tPulseDur
tTCTimeout
CLFactor
InitCLCounter
DayHuntDetect
HourHuntDetect
tHuntDetect
NoOpWindow
.VCTR/Power
Pforw
Prev
Qforw
Qrev
.VCTR/Ctrl (*)
OperationPAR
T1Xr2
T2Xr2
T3Xr2
T4Xr2
T4Xr2
T5Xr2 (**)
T6Xr2 (**)
T7Xr2 (**)
T8Xr2 (**)
OperationCC
CircCurrLimit
tCircCurr
Comp
OperSimTap
OperUsetPar
OperHoming
VTmismatch
RET 521 RET 521/Set .Set/Func .Func/Grp1 .Grp1/VCTR .VCTR/Oper
66 1MRK 504 039-UEN
-
Display for the Settings menu Human machine interface – tree structure
RET 521 RET 521/Set .Set/Func .Func/Grp1 .Grp1/TOC .TOC/TOC1 (*) If TOC1 is
DisturbReport DisturbReport Group1 HMI LED TOC1 Operation directional
ServiceReport Functions Group2 TransfData TOC2 IrUserDef
Settings ChangeActGrp Group3 TransfDiff TOC3 BlockLow
TerminalReport Time Group4 VoltageControl IsetLow
Configuration OverCurrent CurveType
Command GenFunction tDefLow
Test RestrictedEF k
Save as Group 1 EarthFault tMin
Save as Group 2 UnderVoltage BlockHigh
Save as Group 3 OverVoltage IsetHigh
Save as Group 4 Overexcitation tDefHigh
Command with ThermOverload DirectionLow
Confirmation FreqFunction DirectionHigh
According to ref. 2 FreqMeasurmnt rca
roa
UrUserDef
UActionLow
“ChangeAct Grp” UActionHigh
Command
with confirmation
According to ref. 2 .TOC/TOC1 (*) If TOC1 isNon-DirectionalOperation
(*) Similar for IrUserDef
TOC2 & TOC3 BlockLow
IsetLow
CurveType
tDefLow
k
tMin
BlockHigh
IsetHigh
tDefHigh
671MRK 504 039-UEN
-
Display for the Settings menu Human machine interface – tree structure
RET 521 RET 521/Set .Set/Func .Func/Grp1 .Grp1/GF .GF/GF01 (*)
DisturbReport DisturbReport Group1 HMI LED GF01 SelectAnalog .GF01/Input
ServiceReport Functions Group2 TransfData GF02 OverCurrent CurrentInput
Settings ChangeActGrp Group3 TransfDiff GF03 CurrentRestr IrUserDef
TerminalReport Time Group4 VoltageControl GF04 VoltageFunc VoltageInput
Configuration OverCurrent GF05 Directional UrUserDef
Command GenFunction GF06 VoltageRestr
Test RestrictedEF GF07 .GF01/OverCu
Save as Group 1 EarthFault GF08 Operation
Save as Group 2 UnderVoltage GF09 BlockLow
Save as Group 3 OverVoltage GF10 IsetLow
Save as Group 4 Overexcitation GF11 tDefLow
Command with ThermOverload GF12 CurveType
Confirmation FreqFunction tMin
According to ref 2 FreqMeasurmnt k
A
(*) Similar for B
GF02 to GF12 C
“ChangeAct Grp” P
Command tReset
with confirmation I2/I1ratio
According to ref 2 2harLow
BlockHigh
IsetHigh
tDefHigh
2harHigh
.GF01/CurRstr
OperIrestr
RestrCurr
RestrCoeff
.GF01/VoltFnc
OperVoltage
BlockOver
UsetOver
tDefOver
BlockUnder
UsetUnder
tDefUnder
68 1MRK 504 039-UEN
-
Display for the Settings menu Human machine interface – tree structure
.GF01/Direct
DirectionLow
DirectionHigh
rca
roa
DirPrincLow
DirprincHigh
UminOper
UActionLow
UActionHigh
.GF01/VltRstr
OperUrestr
ULevel
UFactor
IFactorLow
IFactorHigh
RET 521 RET 521/Set .Set/Func .Func/Grp1 .Grp1/GF .GF/GF01 (*)
691MRK 504 039-UEN
-
Display for the Settings menu Human machine interface – tree structure
RET 521 RET 521/Set .Set/Func .Func/Grp1 .Grp1/REF .REF/REF1 (*)
DisturbReport DisturbReport Group1 HMI LED REF1 Operation
ServiceReport Functions Group2 TransfData REF2 Idmin
Settings ChangeActGrp Group3 TransfDiff REF3 roa
TerminalReport Time Group4 VoltageControl
Configuration OverCurrent
Command GenFunction
Test RestrictedEF
Save as Group 1 EarthFault
Save as Group 2 UnderVoltage
Save as Group 3 OverVoltage
Save as Group 4 Overexcitation
Command with ThermOverload
Confirmation FreqFunction
According to ref. 2 FreqMeasurmnt
“ChangeAct Grp”
Command
with confirmation
According to ref. 2
(*) Similar for
REF2 & REF3
70 1MRK 504 039-UEN
-
Display for the Settings menu Human machine interface – tree structure
RET 521 RET 521/Set .Set/Func .Func/Grp1 .Grp1/TEF .TEF/TEF1 (*) If TEF1 is
DisturbReport DisturbReport Group1 HMI LED TEF1 Operation Directional
ServiceReport Functions Group2 TransfData TEF2 IrUserDef
Settings ChangeActGrp Group3 TransfDiff TEF3 BlockLow
TerminalReport Time Group4 VoltageControl IsetLow
Configuration OverCurrent CurveType
Command GenFunction tDefLow
Test RestrictedEF k
Save as Group 1 EarthFault tMin
Save as Group 2 UnderVoltage IStart
Save as Group 3 OverVoltage tLog
Save as Group 4 Overexcitation I2/I1ratio
Command with ThermOverload 2harLow
Confirmation FreqFunction 2harHigh
According to ref. 2 FreqMeasurmnt BlockHigh
IsetHigh
tDefHigh
DirectionLow
“ChangeAct Grp” DirectionHigh
Command rca
with confirmation roa
According to ref. 2 UrUserDef
(*) Similar for
TEF2 & TEF3
.TEF/TEF1 (*) If TEF1 isNon-DirectionalOperation
IrUserDef
BlockLow
IsetLow
CurveType
tDefLow
k
tMin
IStart
tLog
I2/I1ratio
2harLow
2harHigh
BlockHigh
IsetHigh
tDefHigh
711MRK 504 039-UEN
-
Display for the Settings menu Human machine interface – tree structure
RET 521 RET 521/Set .Set/Func .Func/Grp1 .Grp1/TUV .TUV/TUV1 (*)
DisturbReport DisturbReport Group1 HMI LED TUV1 Operation
ServiceReport Functions Group2 TransfData TUV2 BlockLow
Settings ChangeActGrp Group3 TransfDiff TUV3 UsetLow
TerminalReport Time Group4 VoltageControl tDefLow
Configuration OverCurrent BlockHigh
Command GenFunction UsetHigh
Test RestrictedEF tDefHigh
Save as Group 1 EarthFault
Save as Group 2 UnderVoltage
Save as Group 3 OverVoltage
Save as Group 4 Overexcitation
Command with ThermOverload
Confirmation FreqFunction
According to ref. 2 FreqMeasurmnt
.Grp1/TOV .TOV/TOV1 (*)
TOV1 Operation
TOV2 BlockLow
“ChangeAct Grp” TOV3 UsetLow
Command TOV4 CurveType
with confirmation TOV5 tDefLow
According to ref. 2 TOV6 k
tMin
(*) Similar for BlockHigh
TOV2 & TOV3 UsetHigh
and TOV2-TOV6 tDefHigh
72 1MRK 504 039-UEN
-
Display for the Settings menu Human machine interface – tree structure
RET 521 RET 521/Set .Set/Func .Func/Grp1 .Grp1/OVEX
DisturbReport DisturbReport Group1 HMI LED Operation
ServiceReport Functions Group2 TransfData Emaxcont
Settings ChangeActGrp Group3 TransfDiff Emax
TerminalReport Time Group4 VoltageControl Xleak
Configuration OverCurrent Tcool
Command GenFunction tAlarm
Test RestrictedEF CurveType
Save as Group 1 EarthFault k
Save as Group 2 UnderVoltage tMin
Save as Group 3 OverVoltage tMax
Save as Group 4 Overexcitation t1
Command with ThermOverload t2
Confirmation FreqFunction t3
According to ref. 2 FreqMeasurmnt t4
t5
t6
“ChangeAct Grp”
Command .Grp1/THOL
with confirmation Operation
According to ref. 2 Ib1
Ib2
Itr
ThetaInit
TimeConstant1
TimeConstant2
Alarm1
Alarm2
ResetLockOut
731MRK 504 039-UEN
-
Display for the Settings menu Human machine interface – tree structure
RET 521 RET 521/Set .Set/Func .Func/Grp1 .Grp1/FRF .FRF/FRF1 (*)
DisturbReport DisturbReport Group1 HMI LED FRF1 Operation
ServiceReport Functions Group2 TransfData FRF2 BlockOver
Settings ChangeActGrp Group3 TransfDiff FRF3 FrsetOver
TerminalReport Time Group4 VoltageControl tDefOver
Configuration OverCurrent kResetOver
Command GenFunction BlockUnder
Test RestrictedEF FrsetUnder
Save as Group 1 EarthFault tDefUnder
Save as Group 2 UnderVoltage kResetUnder
Save as Group 3 OverVoltage
Save as Group 4 Overexcitation
Command with ThermOverload
Confirmation FreqFunction
According to ref. 2 FreqMeasurmnt
(*) Similar for
FRF2 & FRF3
“ChangeAct Grp”
Command
with confirmation
According to ref. 2
.Set/Time .Grp1/FRME
Date & Time Operation
74 1MRK 504 039-UEN
-
Display for Terminal Report menu Human machine interface – tree structure
5 Display for Terminal Report menu
RET 521 RET 521/TermRep .TermSt/SelfSup
DisturbReport SelfSuperv InternFail
ServiceReport IdentityNo InternWarning
Settings NUM-modFail
TerminalReport NUM-modWarning
Configuration PCIP3-AIM1
Command PCIP7-AIM2 ($)
Test CANP9-BOM1/
BIM2/IOM3/MIM1
Real Time Clock
Time Sync
.TermSt/IdentNo .IdentNo/Observe .Observe/General
Observed General OrderingNo
Noted IO-modules SerialNo
SW Version
NUM-module
.Observe/IO-mod
PCIP3-AIM1
PCIP7-AIM2 ($)
CANP9-BOM1/
BIM2/IOM3/MIM1
.IdentNo/Note
MMI-module
Casing
PSM-module
SLM-module
751MRK 504 039-UEN
-
Display for Configuration menu Human machine interface – tree structure
6 Display for Configuration menu
RET 521 RET 521/Config .Config/Ident
DisturbReport Identifiers Station Name
ServiceReport Frequency Station No
Settings AnalogInputs Object Name
TerminalReport PCIP3-AIM1 Object No
Configuration PCIP7-AIM2 ($) Unit Name
Command CANP9-BOM1/BIM2/IOM3/MIM1
Unit No
Test Time
BuiltInMMI .Config/Freq
SPAComm fr
LONComm ($)
.Config/AnInp
RefCh
.Config/AIM1
AIM1-CH01 (*)
AIM1-CH02 (*)
AIM1-CH03 (*) .AIM1/CH01 (**)
(*) User name AIM1-CH04 (*) InputCTTap
default name is shown AIM1-CH05 (*) CTprim
AIM1-CH06 (*) CTsec
AIM1-CH07 (*) CTstarpoint
AIM1-CH08 (*)
(**) User name will not be AIM1-CH09 (*)
shown AIM1-CH10 (*)
.Config/AIM2
AIM2-CH01 (*)
($) Visible only if AIM2-CH02 (*)
that option is installed AIM2-CH03 (*)
AIM2-CH04 (*)
AIM2-CH05 (*)
AIM2-CH06 (*)
AIM2-CH07 (*) .AIM2/CH08 (**) If channel eight in AIM2is Voltage ChannelAIM2-CH08 (*) VTprim
AIM2-CH09 (*) VTsec
AIM2-CH10 (*)
76 1MRK 504 039-UEN
-
Display for Configuration menu Human machine interface – tree structure
RET 521 RET 521/Config .Config/BIM1
DisturbReport Identifiers Operation
ServiceReport Frequency Oscil Block
Settings AnalogInputs Oscil Release
TerminalReport PCIP3-AIM1
Configuration PCIP7-AIM2 ($)
Command CANP9-BOM1/BIM2/IOM3/MIM1
Test Time .Config/BOM2
BuiltInMMI Operation
SPAComm
LONComm ($)
.Config/IOM3
Operation
.Config/MIM1
Operation
($) Visible only if
that option is installed
771MRK 504 039-UEN
-
Display for Configuration menu Human machine interface – tree structure
RET 521 RET 521/Config .Config/Time .Time/Source
DisturbReport Identifiers FineTimeSrc TIME-MINSYNC (**)
ServiceReport Frequency CoarseTimeSrc TimeSyncSource
Settings AnalogInputs
TerminalReport PCIP3-AIM1 .Config/MMI .Time/Coarse
Configuration PCIP7-AIM2 ($) MMI--BLOCKSET (*) CoarseTimeSourc
Command CANP9-BOM1/BIM2/IOM3/MIM1
SettingRestrict
Test Time
BuiltInMMI .Config/SPACom .SPACom/Rear
SPACom Rear SlaveNo
LONCom ($) Front BaudRate
SelectLanguage ($) ActGrpRestrict
SettingRestrict
.SPACom/Front
($) Visible only if SlaveNo
that option is installed BaudRate
.Config/LONCom .LONCom/NodeInf .NodeInf/AdrInfo
NodeInfo AdressInfo DomainID
(%) Only in local MMI ServicePinMsg (%) NeuronID SubnetID
LONDefault (%) Location NodeID
SessionTimers (%)
Enable Flash (%) .NodeInf/NeurID
Disable Flash (%) .LONCom/Session NeuronID
SessionTmo
“ServicePinMsg”, RetryTmo .NodeInf/Locat
“LONDefault”, IdleAckCycle Location
“Enable Flash”, BusyAckTmo
(*) Functions “Disable Flash” ErrNackCycle
according to Command with
SIGNAL LIST A confirmation
According to ref. 2
(**) Functions
according to .Config/SelLang
SIGNAL LIST B ActiveLanguage
78 1MRK 504 039-UEN
-
Display for Command menu Human machine interface – tree structure
7 Display for Command menu
RET 521 RET 521/Cmd .Cmd/CD01
DisturbReport CD01 CD01-CMDOUT1 (*)
ServiceReport VoltageControl ...
Settings ...
TerminalReport CD01-CMDOUT16 (*)
Configuration
Command
Test “CD01-CMDOUT1”
Command with status and confirmation
According to ref. 2
(*) User name
Default name is shown
791MRK 504 039-UEN
-
Display for Command menu Human machine interface – tree structure
RET 521/Cmd .Cmd/VoltCtr O p r M o d e = I n t M M I
CD01 Set Int/Ext C h n g t o E x t M M I ? O p r M o d e = I n t M M I
VoltageControl Set Manual/Auto = = = = = = = = after C h n g t o E x t M M I ?
RaiseVoltage || Y E S || N O || ENTER = = = = = = = =
LowerVoltage || Y E S || N O ||
ResetCLCnt OR
ResetOpCnt
O p r M o d e = E x t M M I
C h n g t o I n t M M I ? O p r M o d e = E x t M M I
= = = = = = = = after C h n g t o I n t M M I ?
|| Y E S || N O || ENTER = = = = = = = =
Depends on actual state of VC function || Y E S || N O ||
“ResetCLCnt” and
“ResetOpCnt” C o n t r o l = M a n u a l
Command with C h n g t o A u t o ? C o n t r o l = M a n u a l
confirmation = = =