operational updates to south of allston - dec. 6, 2017 · 2020. 7. 22. · • soa has a dynamic...
TRANSCRIPT
![Page 1: Operational Updates to South of Allston - Dec. 6, 2017 · 2020. 7. 22. · • SOA has a dynamic TTC that takes into account actual generation conditions • Operational transition](https://reader035.vdocuments.us/reader035/viewer/2022071108/5fe2b402fc738f7cf774c999/html5/thumbnails/1.jpg)
Operational Updates to South of Allston (SOA)
2016 - 2017
![Page 2: Operational Updates to South of Allston - Dec. 6, 2017 · 2020. 7. 22. · • SOA has a dynamic TTC that takes into account actual generation conditions • Operational transition](https://reader035.vdocuments.us/reader035/viewer/2022071108/5fe2b402fc738f7cf774c999/html5/thumbnails/2.jpg)
B O N N E V I L L E P O W E R A D M I N I S T R A T I O N
• South of Allston Dynamic Total Transfer Capability (TTC)
• Implementation of Peak Reliability’s System Operating Limit Methodology for Operations Horizon v8.1
• Keeler-Allston/Pearl-Keeler RAS Automation
Agenda
For Discussion Purposes Only 2
![Page 3: Operational Updates to South of Allston - Dec. 6, 2017 · 2020. 7. 22. · • SOA has a dynamic TTC that takes into account actual generation conditions • Operational transition](https://reader035.vdocuments.us/reader035/viewer/2022071108/5fe2b402fc738f7cf774c999/html5/thumbnails/3.jpg)
B O N N E V I L L E P O W E R A D M I N I S T R A T I O N
Prior to June 1, 2016 • BPA’s Operations Planning engineers assumed
conservative assumptions when calculating SOA TTC for outage studies
• Studies were updated to reflect actual generation when high flows were observed
On June 1, 2016 • Outage Study TTCs are posted for Hourly TTC Path
Limits • BPA’s Operation Planning engineers developed a
dynamic TTC that takes into account a range of generation scenarios in real-time
SOA Dynamic TTC
For Discussion Purposes Only 3
![Page 4: Operational Updates to South of Allston - Dec. 6, 2017 · 2020. 7. 22. · • SOA has a dynamic TTC that takes into account actual generation conditions • Operational transition](https://reader035.vdocuments.us/reader035/viewer/2022071108/5fe2b402fc738f7cf774c999/html5/thumbnails/4.jpg)
B O N N E V I L L E P O W E R A D M I N I S T R A T I O N
80 generation scenarios are studied to generate the table that the improved dynamic TTC uses
Real-time SOA Dynamic TTC
For Discussion Purposes Only 4
![Page 5: Operational Updates to South of Allston - Dec. 6, 2017 · 2020. 7. 22. · • SOA has a dynamic TTC that takes into account actual generation conditions • Operational transition](https://reader035.vdocuments.us/reader035/viewer/2022071108/5fe2b402fc738f7cf774c999/html5/thumbnails/5.jpg)
B O N N E V I L L E P O W E R A D M I N I S T R A T I O N
Motivation for Improved Dynamic TTC
For Discussion Purposes Only 5
![Page 6: Operational Updates to South of Allston - Dec. 6, 2017 · 2020. 7. 22. · • SOA has a dynamic TTC that takes into account actual generation conditions • Operational transition](https://reader035.vdocuments.us/reader035/viewer/2022071108/5fe2b402fc738f7cf774c999/html5/thumbnails/6.jpg)
Effective April 1, 2017
![Page 7: Operational Updates to South of Allston - Dec. 6, 2017 · 2020. 7. 22. · • SOA has a dynamic TTC that takes into account actual generation conditions • Operational transition](https://reader035.vdocuments.us/reader035/viewer/2022071108/5fe2b402fc738f7cf774c999/html5/thumbnails/7.jpg)
B O N N E V I L L E P O W E R A D M I N I S T R A T I O N
• BPA and many utilities in the Western Interconnection managed transmission systems based on “path” (e.g. COI, South of Allston) limits
• Studies established transfer limits which became the System Operating Limit (SOL) of the path and the TTC for commercial sales
• Reliability was maintained by operating the path within the path SOL
Before April 1, 2017
For Discussion Purposes Only 7
![Page 8: Operational Updates to South of Allston - Dec. 6, 2017 · 2020. 7. 22. · • SOA has a dynamic TTC that takes into account actual generation conditions • Operational transition](https://reader035.vdocuments.us/reader035/viewer/2022071108/5fe2b402fc738f7cf774c999/html5/thumbnails/8.jpg)
B O N N E V I L L E P O W E R A D M I N I S T R A T I O N
• NERC White Paper, “System Operating Limit Definition and Exceedance Clarification”, January 2015
• WECC Path Operator Implementation Task Force (POITF) recommendations, 2015
• TOP-001-3 and TOP-002-4 NERC reliability standards effective April 1, 2017
What Drove the SOL Methodology Change?
For Discussion Purposes Only 8
![Page 9: Operational Updates to South of Allston - Dec. 6, 2017 · 2020. 7. 22. · • SOA has a dynamic TTC that takes into account actual generation conditions • Operational transition](https://reader035.vdocuments.us/reader035/viewer/2022071108/5fe2b402fc738f7cf774c999/html5/thumbnails/9.jpg)
B O N N E V I L L E P O W E R A D M I N I S T R A T I O N
April 1st Changes
For Discussion Purposes Only 9
![Page 10: Operational Updates to South of Allston - Dec. 6, 2017 · 2020. 7. 22. · • SOA has a dynamic TTC that takes into account actual generation conditions • Operational transition](https://reader035.vdocuments.us/reader035/viewer/2022071108/5fe2b402fc738f7cf774c999/html5/thumbnails/10.jpg)
B O N N E V I L L E P O W E R A D M I N I S T R A T I O N
• Path SOLs are no longer used for thermally limited Paths – SOA is a thermally limited path
• To ensure system reliability, BPA monitors SOA area using real-time reliability assessment tools for thermal and steady-state voltage issues
• BPA continues to study SOA path to set path TTC
Post April 1, 2017
For Discussion Purposes Only 10
![Page 11: Operational Updates to South of Allston - Dec. 6, 2017 · 2020. 7. 22. · • SOA has a dynamic TTC that takes into account actual generation conditions • Operational transition](https://reader035.vdocuments.us/reader035/viewer/2022071108/5fe2b402fc738f7cf774c999/html5/thumbnails/11.jpg)
Keeler-Allston/Pearl-Keeler RAS Automation
May 3, 2017
![Page 12: Operational Updates to South of Allston - Dec. 6, 2017 · 2020. 7. 22. · • SOA has a dynamic TTC that takes into account actual generation conditions • Operational transition](https://reader035.vdocuments.us/reader035/viewer/2022071108/5fe2b402fc738f7cf774c999/html5/thumbnails/12.jpg)
B O N N E V I L L E P O W E R A D M I N I S T R A T I O N
• Keeler – Allston RAS was installed soon after the August 10, 1996 event that created a massive system blackout in the western power grid
• BPA RAS dispatchers could arm up to 2,700 MW of generation for dropping if the Single Line Loss (SLL) of Keeler – Allston 500kV contingency were to occur
• In 2016, BPA transmission planning and operations re-evaluated and reduced the amount of N-1 RAS Gen Drop from 2,700 MW to 2,200 MW
South of Allston RAS
For Discussion Purposes Only 12
![Page 13: Operational Updates to South of Allston - Dec. 6, 2017 · 2020. 7. 22. · • SOA has a dynamic TTC that takes into account actual generation conditions • Operational transition](https://reader035.vdocuments.us/reader035/viewer/2022071108/5fe2b402fc738f7cf774c999/html5/thumbnails/13.jpg)
B O N N E V I L L E P O W E R A D M I N I S T R A T I O N
• SOA RAS Automation arming allows BPA to arm a more precise amount of generation, compared to manual RAS arming
• Result: Over-arming is greatly reduced, in both MW amount and duration
SOA RAS Automation
For Discussion Purposes Only 13
![Page 14: Operational Updates to South of Allston - Dec. 6, 2017 · 2020. 7. 22. · • SOA has a dynamic TTC that takes into account actual generation conditions • Operational transition](https://reader035.vdocuments.us/reader035/viewer/2022071108/5fe2b402fc738f7cf774c999/html5/thumbnails/14.jpg)
B O N N E V I L L E P O W E R A D M I N I S T R A T I O N
SOA RAS Automation Testing
For Discussion Purposes Only 14
![Page 15: Operational Updates to South of Allston - Dec. 6, 2017 · 2020. 7. 22. · • SOA has a dynamic TTC that takes into account actual generation conditions • Operational transition](https://reader035.vdocuments.us/reader035/viewer/2022071108/5fe2b402fc738f7cf774c999/html5/thumbnails/15.jpg)
B O N N E V I L L E P O W E R A D M I N I S T R A T I O N
8/31/17: Amount of SOA flows Reached 3,150 MW The new Automatic Arming responded with 2,000 MW of arming as adequate for system reliability, when the old methodology would have armed 2,700 MW
SOA RAS Automation
For Discussion Purposes Only 15
![Page 16: Operational Updates to South of Allston - Dec. 6, 2017 · 2020. 7. 22. · • SOA has a dynamic TTC that takes into account actual generation conditions • Operational transition](https://reader035.vdocuments.us/reader035/viewer/2022071108/5fe2b402fc738f7cf774c999/html5/thumbnails/16.jpg)
B O N N E V I L L E P O W E R A D M I N I S T R A T I O N
SOA RAS Automation 2017 RAS Arming MW-Hours
Hours
MW
s
For Discussion Purposes Only 16
![Page 17: Operational Updates to South of Allston - Dec. 6, 2017 · 2020. 7. 22. · • SOA has a dynamic TTC that takes into account actual generation conditions • Operational transition](https://reader035.vdocuments.us/reader035/viewer/2022071108/5fe2b402fc738f7cf774c999/html5/thumbnails/17.jpg)
B O N N E V I L L E P O W E R A D M I N I S T R A T I O N
• SOA has a dynamic TTC that takes into account actual generation conditions
• Operational transition from thermal path SOLs to real-time reliability assessment
• RAS Automation - arming less gen drop while also providing system reliability
Summary of Operational Updates
For Discussion Purposes Only 17