—RELION®
Substation Merging UnitSMU615Operation Manual
Document ID: 1MRS758406Issued: 2019-05-17
Revision: BProduct version: 1.0
© Copyright 2019 ABB. All rights reserved
Copyright
This document and parts thereof must not be reproduced or copied without writtenpermission from ABB, and the contents thereof must not be imparted to a third party,nor used for any unauthorized purpose.
The software or hardware described in this document is furnished under a license andmay be used, copied, or disclosed only in accordance with the terms of such license.
TrademarksABB and Relion are registered trademarks of the ABB Group. All other brand orproduct names mentioned in this document may be trademarks or registeredtrademarks of their respective holders.
WarrantyPlease inquire about the terms of warranty from your nearest ABB representative.
www.abb.com/substationautomation
Disclaimer
The data, examples and diagrams in this manual are included solely for the concept orproduct description and are not to be deemed as a statement of guaranteed properties.All persons responsible for applying the equipment addressed in this manual mustsatisfy themselves that each intended application is suitable and acceptable, includingthat any applicable safety or other operational requirements are complied with. Inparticular, any risks in applications where a system failure and/or product failurewould create a risk for harm to property or persons (including but not limited topersonal injuries or death) shall be the sole responsibility of the person or entityapplying the equipment, and those so responsible are hereby requested to ensure thatall measures are taken to exclude or mitigate such risks.
This product has been designed to be connected and communicate data andinformation via a network interface which should be connected to a secure network.It is the sole responsibility of the person or entity responsible for networkadministration to ensure a secure connection to the network and to take the necessarymeasures (such as, but not limited to, installation of firewalls, application ofauthentication measures, encryption of data, installation of anti virus programs, etc.)to protect the product and the network, its system and interface included, against anykind of security breaches, unauthorized access, interference, intrusion, leakage and/ortheft of data or information. ABB is not liable for any such damages and/or losses.
This document has been carefully checked by ABB but deviations cannot becompletely ruled out. In case any errors are detected, the reader is kindly requested tonotify the manufacturer. Other than under explicit contractual commitments, in noevent shall ABB be responsible or liable for any loss or damage resulting from the useof this manual or the application of the equipment.
Conformity
This product complies with the directive of the Council of the European Communitieson the approximation of the laws of the Member States relating to electromagneticcompatibility (EMC Directive 2014/30/EU) and concerning electrical equipment foruse within specified voltage limits (Low-voltage directive 2014/35/EU). Thisconformity is the result of tests conducted by ABB in accordance with the productstandard EN 60255-26 for the EMC directive, and with the product standards EN60255-1 and EN 60255-27 for the low voltage directive. The product is designed inaccordance with the international standards of the IEC 60255 series.
Safety information
Dangerous voltages can occur on the connectors, even though theauxiliary voltage has been disconnected.
Non-observance can result in death, personal injury or substantialproperty damage.
Only a competent electrician is allowed to carry out the electricalinstallation.
National and local electrical safety regulations must always befollowed.
The frame of the merging unit has to be carefully earthed.
When the plug-in unit has been detached from the case, do not touchthe inside of the case. The merging unit case internals may containhigh voltage potential and touching these may cause personal injury.
The merging unit contains components which are sensitive to electrostaticdischarge. Unnecessary touching of electronic components must therefore beavoided.
Whenever changes are made in the merging unit, measures should betaken to avoid inadvertent tripping.
Table of contents
Section 1 Introduction.......................................................................5This manual........................................................................................ 5Intended audience.............................................................................. 5Product documentation.......................................................................6
Product documentation set............................................................6Document revision history............................................................. 6Related documentation..................................................................6
Symbols and conventions...................................................................7Symbols.........................................................................................7Document conventions..................................................................7Functions, codes and symbols...................................................... 8
Section 2 Environmental aspects...................................................11Sustainable development................................................................. 11Disposal of a merging unit................................................................ 11
Section 3 SMU615 overview.......................................................... 13Overview...........................................................................................13Local HMI......................................................................................... 13
LEDs............................................................................................14Keypad........................................................................................ 14Local HMI functionality................................................................ 15
LED indications...................................................................... 15Front communication..............................................................16
Web HMI...........................................................................................16Command buttons....................................................................... 17
Authorization.....................................................................................19Audit trail......................................................................................19
Communication.................................................................................21Ethernet redundancy................................................................... 22Process bus.................................................................................24Secure communication................................................................28
PCM600 tool.....................................................................................28Connectivity packages.................................................................29PCM600 and merging unit's connectivity package version......... 29
Section 4 Using HMI.......................................................................31Using local HMI................................................................................ 31
Clearing and acknowledging....................................................... 31Using Web HMI................................................................................ 31
Table of contents
SMU615 1Operation Manual
Logging in....................................................................................31Logging out..................................................................................32Identifying device.........................................................................32Navigating in menus....................................................................33
Menu structure....................................................................... 34Showing parameters....................................................................34Editing values.............................................................................. 38Committing settings.....................................................................41Clearing and acknowledging....................................................... 42Selecting programmable LEDs view............................................43Selecting event view....................................................................44Selecting disturbance records view.............................................45
Saving disturbance records....................................................46Triggering disturbance recorder manually..............................46Deleting disturbance records..................................................47
Selecting phasor diagrams..........................................................48Exporting load profile records .....................................................49Import and export of settings.......................................................50
Exporting settings ..................................................................50Importing settings .................................................................. 50
Exporting report summary........................................................... 53Using Web HMI help....................................................................54
Section 5 Merging unit operation....................................................55Normal operation.............................................................................. 55Disturbance identification................................................................. 55
Disturbance recording triggering................................................. 56Disturbance record analysis........................................................ 56Disturbance reports..................................................................... 56Merging unit self-supervision.......................................................56
Merging unit parametrization............................................................ 57
Section 6 Operating procedures.....................................................59Monitoring.........................................................................................59
Indications................................................................................... 59Monitoring merging unit's internal fault...................................59
Measured and calculated values.................................................59Measured values.................................................................... 59
Recorded data.............................................................................60Creating disturbance recordings ........................................... 60Monitoring disturbance recorder data ....................................61Controlling and reading of disturbance recorder data............ 61
Remote monitoring...................................................................... 62Monitoring merging units remotely......................................... 62
Table of contents
2 SMU615Operation Manual
Resetting merging unit......................................................................62Clearing and acknowledging....................................................... 62
Changing merging unit functionality................................................. 63Activating programmable LEDs...................................................63
Section 7 Troubleshooting .............................................................65Fault tracing......................................................................................65
Identifying hardware errors..........................................................65Identifying runtime errors.............................................................65Identifying communication errors.................................................65
Checking front communication link operation.........................65Checking time synchronization...............................................66
Indication messages.........................................................................66Internal faults...............................................................................66Warnings..................................................................................... 67
Correction procedures...................................................................... 68Rebooting software......................................................................68Restoring factory settings............................................................69Restoring administrator password...............................................69Setting passwords....................................................................... 70Identifying merging unit application problems............................. 70
Inspecting wiring.....................................................................70Sample data interruptions...................................................... 71
Section 8 Commissioning...............................................................73Commissioning checklist.................................................................. 73Checking installation.........................................................................73
Checking power supply............................................................... 73Checking CT circuits....................................................................74Checking VT circuits....................................................................74Checking binary input and output circuits....................................75
Checking binary input circuits.................................................75Checking binary output circuits.............................................. 75
Authorizations...................................................................................76User authorization....................................................................... 76
Setting merging unit and communication......................................... 77Setting communication between merging units and PCM600.....77
Communication link options between PCM600 andmerging units..........................................................................77
Communication settings.............................................................. 78Defining Ethernet port settings............................................... 78Setting communication protocol parameters.......................... 79
Setting system time and time synchronization............................ 79Setting daylight saving time....................................................79
Table of contents
SMU615 3Operation Manual
Setting merging unit parameters................................................. 80Merging unit parametrization..................................................80Defining disturbance recorder channel settings .................... 81Configuring analog inputs.......................................................81
Testing merging unit operation......................................................... 81Selecting IED test mode .............................................................81Testing digital I/O interface..........................................................82Testing functions......................................................................... 83Selecting internal fault test.......................................................... 83Selecting IED blocked or IED test and blocked mode.................84
ABB Product Data Registration........................................................ 85
Section 9 Glossary......................................................................... 87
Table of contents
4 SMU615Operation Manual
Section 1 Introduction
1.1 This manual
The operation manual contains instructions on how to operate the merging unit onceit has been commissioned. The manual provides instructions for monitoring,controlling and setting the merging unit. The manual also describes how to identifydisturbances and how to view calculated and measured power grid data to determinethe cause of a fault.
1.2 Intended audience
This manual addresses the operator who operates the merging unit frequently.
The operator must be trained in and have a basic knowledge of how to operateprotection equipment. The manual contains terms and expressions commonly used todescribe this kind of equipment.
1MRS758406 B Section 1Introduction
SMU615 5Operation Manual
1.3 Product documentation
1.3.1 Product documentation set
Pla
nn
ing
&
pu
rch
ase
En
gin
ee
rin
g
Insta
llatio
n
Com
mis
sio
nin
g
Op
era
tio
n
Ma
inte
na
nce
Deco
mm
issio
nin
g,
de
insta
llatio
n &
dis
po
sa
l
Brochure
Product guide
Operation manual
Installation manual
Engineering manual
Technical manual
Application manual
IEC 61850 engineering guide
Cyber security deployment guideline
GUID-46AF8DD4-42E5-466B-840D-478D999D1D6D V1 EN
Figure 1: The intended use of documents during the product life cycle
1.3.2 Document revision historyDocument revision/date Product version HistoryA/2017-09-26 1.0 First release
B/2019-05-17 1.0 Content updated
1.3.3 Related documentation
Contact ABB for information on SMU615 related documentation.
Section 1 1MRS758406 BIntroduction
6 SMU615Operation Manual
1.4 Symbols and conventions
1.4.1 Symbols
The electrical warning icon indicates the presence of a hazard whichcould result in electrical shock.
The warning icon indicates the presence of a hazard which couldresult in personal injury.
The caution icon indicates important information or warning relatedto the concept discussed in the text. It might indicate the presence ofa hazard which could result in corruption of software or damage toequipment or property.
The information icon alerts the reader of important facts andconditions.
The tip icon indicates advice on, for example, how to design yourproject or how to use a certain function.
Although warning hazards are related to personal injury, it is necessary to understandthat under certain operational conditions, operation of damaged equipment may resultin degraded process performance leading to personal injury or death. Therefore,comply fully with all warning and caution notices.
1.4.2 Document conventions
A particular convention may not be used in this manual.
• Abbreviations and acronyms are spelled out in the glossary. The glossary alsocontains definitions of important terms.
• Menu paths are presented in bold.Select Main menu/Settings.
• WHMI menu names are presented in bold.Click Information in the WHMI menu structure.
• Parameter names are shown in italics.The function can be enabled and disabled with the Operation setting.
• Parameter values are indicated with quotation marks.
1MRS758406 B Section 1Introduction
SMU615 7Operation Manual
The corresponding parameter values are "On" and "Off".• Input/output messages and monitored data names are shown in Courier font.• This document assumes that the parameter setting visibility is "Advanced".
1.4.3 Functions, codes and symbolsTable 1: Functions included in the merging unit
Function IEC 61850 IEC 60617 IEC-ANSIMeasurement
Disturbance recorder RDRE1 DR (1) DFR (1)
Three-phase currentmeasurement
CMMXU1 3I (1) 3I (1)
Sequence currentmeasurement
CSMSQI1 I1, I2, I0 (1) I1, I2, I0 (1)
Residual current measurement RESCMMXU1 Io (1) In (1)
Three-phase voltagemeasurement
VMMXU1 3U (1) 3V (1)
Sequence voltagemeasurement
VSMSQI1 U1, U2, U0 (1) V1, V2, V0 (1)
Three-phase power and energymeasurement
PEMMXU1 P, E (1) P, E (1)
Frequency measurement FMMXU1 f (1) f (1)
IEC 61850-9-2 LE sampledvalue sending
SMVSENDER SMVSENDER SMVSENDER
Condition monitoring and supervision
Circuit-breaker conditionmonitoring
SSCBR1 CBCM (1) CBCM (1)
Trip circuit supervision TCSSCBR1 TCS (1) TCM (1)
TCSSCBR2 TCS (2) TCM (2)
Current circuit supervision CCSPVC1 MCS 3I (1) MCS 3I (1)
Fuse failure supervision SEQSPVC1 FUSEF (1) 60 (1)
Arc detection ARCDSARC1 ARCD (1) AFD (1)
ARCDSARC2 ARCD (2) AFD (2)
ARCDSARC3 ARCD (3) AFD (3)
Control
Circuit-breaker control CBXCBR1 I <-> O CB (1) I <-> O CB (1)
Disconnector control DCXSWI1 I <-> O DCC (1) I <-> O DCC (1)
DCXSWI2 I <-> O DCC (2) I <-> O DCC (2)
Earthing switch control ESXSWI1 I <-> O ESC (1) I <-> O ESC (1)
Disconnector positionindication
DCSXSWI1 I <-> O DC (1) I <-> O DC (1)
DCSXSWI2 I <-> O DC (2) I <-> O DC (2)
Earthing switch indication ESSXSWI1 I <-> O ES (1) I <-> O ES (1)
Other
Table continues on next page
Section 1 1MRS758406 BIntroduction
8 SMU615Operation Manual
Function IEC 61850 IEC 60617 IEC-ANSIMinimum pulse timer (2 pcs) TPGAPC1 TP (1) TP (1)
TPGAPC2 TP (2) TP (2)
TPGAPC3 TP (3) TP (3)
TPGAPC4 TP (4) TP (4)
Minimum pulse timer (2 pcs,second resolution)
TPSGAPC1 TPS (1) TPS (1)
Minimum pulse timer (2 pcs,minute resolution)
TPMGAPC1 TPM (1) TPM (1)
Pulse timer (8 pcs) PTGAPC1 PT (1) PT (1)
PTGAPC2 PT (2) PT (2)
Time delay off (8 pcs) TOFGAPC1 TOF (1) TOF (1)
TOFGAPC2 TOF (2) TOF (2)
TOFGAPC3 TOF (3) TOF (3)
TOFGAPC4 TOF (4) TOF (4)
Time delay on (8 pcs) TONGAPC1 TON (1) TON (1)
TONGAPC2 TON (2) TON (2)
TONGAPC3 TON (3) TON (3)
TONGAPC4 TON (4) TON (4)
Set-reset (8 pcs) SRGAPC1 SR (1) SR (1)
SRGAPC2 SR (2) SR (2)
SRGAPC3 SR (3) SR (3)
SRGAPC4 SR (4) SR (4)
Move (8 pcs) MVGAPC1 MV (1) MV (1)
MVGAPC2 MV (2) MV (2)
Generic control point (16 pcs) SPCGAPC1 SPC (1) SPC (1)
SPCGAPC2 SPC (2) SPC (2)
Master trip TRPPTRC1 Master Trip (1) 94/86 (1)
TRPPTRC2 Master Trip (2) 94/86 (2)
TRPPTRC3 Master Trip (3) 94/86 (3)
TRPPTRC4 Master Trip (4) 94/86 (4)
TRPPTRC5 Master Trip (5) 94/86 (5)
1MRS758406 B Section 1Introduction
SMU615 9Operation Manual
10
Section 2 Environmental aspects
2.1 Sustainable development
Sustainability has been taken into account from the beginning of the product designincluding the pro-environmental manufacturing process, long life time, operationreliability and disposing of the merging unit.
The choice of materials and the suppliers have been made according to the EU RoHSdirective (2002/95/EC). This directive limits the use of hazardous substances whichare the following:
Table 2: Maximum concentration values by weight per homogeneous material
Substance Proposed maximum concentrationLead - Pb 0.1%
Mercury - Hg 0.1%
Cadmium - Cd 0.01%
Hexavalent Chromium Cr (VI) 0.1%
Polybrominated biphenyls - PBB 0.1%
Polybrominated diphenyl ethers - PBDE 0.1%
Operational reliability and long life time have been assured with extensive testingduring the design and manufacturing processes. Moreover, long life time is supportedby maintenance and repair services as well as by the availability of spare parts.
Design and manufacturing have been done under a certified environmental system.The effectiveness of the environmental system is constantly evaluated by an externalauditing body. We follow environmental rules and regulations systematically toevaluate their effect on our products and processes.
2.2 Disposal of a merging unit
Definitions and regulations of hazardous materials are country-specific and changewhen the knowledge of materials increases. The materials used in this product aretypical for electric and electronic devices.
All parts used in this product are recyclable. When disposing of a merging unit or itsparts, contact a local waste handler who is authorized and specialized in disposing ofelectronic waste. These handlers can sort the material by using dedicated sortingprocesses and dispose of the product according to the local requirements.
1MRS758406 B Section 2Environmental aspects
SMU615 11Operation Manual
Table 3: Materials of the merging unit parts
Merging unit Parts MaterialCase Metallic plates, parts and screws Steel
Plastic parts PC1), LCP2)
Electronics plug in module Various
Plug-in unit Electronics plug in modules Various
Electronics LHMI module Various
Plastic parts PC, PBT3), LCP, PA4)
Metallic parts Aluminium
Package Box Cardboard
Attached material Manuals Paper
1) Polycarbonate2) Liquid crystal polymer3) Polybutylene terephthalate4) Polyamide
Section 2 1MRS758406 BEnvironmental aspects
12 SMU615Operation Manual
Section 3 SMU615 overview
3.1 Overview
SMU615 is a dedicated substation merging unit intended for measuring current andvoltage signals from the instrument transformers and merging them into the standarddigital output format that other devices can further use for various power systemprotection application purposes. SMU615 itself includes no protection functionalitybut it offers the physical interface into the switchgear primary equipment, that is,circuit breaker, disconnector and earthing switch. SMU615 is a member of ABB’sRelion® product family and is characterized by the compactness, simplicity andwithdrawable-unit design.
SMU615 has been designed to unleash the full potential of the IEC 61850 standard forcommunication and interoperability in the digital substations. SMU615 supportsprocess bus according to IEC 61850-9-2 LE with IEEE 1588 v2 time synchronizationand both conventional CT/VT inputs and sensor inputs.
3.2 Local HMI
The LHMI is used for monitoring the merging unit. The LHMI comprises the pushbutton, LED indicators and communication port.
1MRS758406 B Section 3SMU615 overview
SMU615 13Operation Manual
GUID-45DD21AE-B64A-4508-B6DF-FC264C2171DB V2 EN
Figure 2: Example of the LHMI
3.2.1 LEDs
The LHMI includes a dedicated Ready LED indicator and 11 matrix programmableLEDs on front of the LHMI.
The LEDs can be configured with PCM600 and the operation mode can be selected viaWHMI or PCM600.
3.2.2 Keypad
The LHMI keypad contains a push button which is used to acknowledge alarms.
Section 3 1MRS758406 BSMU615 overview
14 SMU615Operation Manual
GUID-9101BAA6-AA5B-4747-A817-0FE8C8831B9F V2 EN
Figure 3: LHMI command push button and RJ-45 communication port
CommandsTable 4: Command push button
Name Description
Clear• Clearing programmable LEDs. After an initial three-second press, the
following three-second press clears the programmable LEDs.
3.2.3 Local HMI functionality
3.2.3.1 LED indications
Ready LED indicatorTable 5: Ready LED indications
LED state DescriptionOff Auxiliary supply voltage is disconnected.
On Normal operation
Flashing Internal fault has occurred or the merging unit is in test mode. Internal faultsare accompanied by an indication message.
Alarm indicatorsThe 11 matrix programmable LEDs are used for alarm indication.
Table 6: Alarm indications
LED state DescriptionOff Normal operation. All activation signals are off.
On • Non-latched mode: activation signal is still on.• Latched mode: activation signal is still on, or it is off but has not been
acknowledged.• Latched flashing mode: activation signal is still on but has been
acknowledged.
Flashing • Non-latched flashing mode: activation signal is still on.• Latched flashing mode: activation signal is still on, or it is off but has
not been acknowledged.
1MRS758406 B Section 3SMU615 overview
SMU615 15Operation Manual
3.2.3.2 Front communication
The RJ-45 port in the LHMI enables front communication. Two LEDs are locatedabove the communication port.
• The green uplink LED on the left is lit when the cable is successfully connectedto the port.
• The yellow communication LED on the right flashes when the merging unitcommunicates with the connected device.
21
A070816 V2 EN
Figure 4: RJ-45 communication port and indication LEDs
1 Uplink LED
2 Communication LED
When a computer is connected to the merging unit, the merging unit's DHCP serverfor the front interface assigns an IP address to the computer. The fixed IP address forthe front port is 192.168.0.254.
3.3 Web HMI
The WHMI allows secure access to the merging unit via a Web browser. When theSecure Communication parameter in the merging unit is activated, the Web server isforced to take a secured (HTTPS) connection to WHMI using TLS encryption. TheWHMI is verified with Internet Explorer 8.0, 9.0, 10.0 and 11.0.
WHMI offers several functions.
• Programmable LEDs and event lists• System supervision• Parameter settings• Measurement display• Disturbance records
Section 3 1MRS758406 BSMU615 overview
16 SMU615Operation Manual
• Phasor diagram• Importing/Exporting parameters• Report summary
GUID-27E59B74-A1B0-48F3-BE04-6ED4B17550A2 V1 EN
Figure 5: Example view of the WHMI
The WHMI can be accessed locally and remotely.
• Locally by connecting the laptop to the merging unit via the front communicationport.
• Remotely over LAN/WAN.
WHMI is enabled by default on the rear port and always enabled (cannot be disabled)on the front port.
If the WHMI is accessed locally via the front communication port, the followingfeatures are available.
• Setting the merging unit to test mode and testing of outputs• Trip circuit lockout reset• Restoring factory settings
3.3.1 Command buttons
Command buttons can be used to edit parameters and control information via theWHMI.
1MRS758406 B Section 3SMU615 overview
SMU615 17Operation Manual
Table 7: Command buttons
Name DescriptionEnabling parameter editing
Disabling parameter editing
Writing parameters to the merging unit
Refreshing parameter values
Printing out parameters
Committing changes to merging unit's non-volatile flash memory
Rejecting changes
Showing context sensitive help messages
Error icon
Clearing events
Triggering the disturbance recorder manually
Saving values to TXT or CSV file format
Freezing the values so that updates are not displayed
Receiving continuous updates to the monitoring view
Deleting the disturbance record
Deleting all disturbance records
Saving the disturbance record files
Viewing all fault records
Clearing all fault records
Importing settings
Exporting settings
Selecting all
Clearing all selections
Clearing load profile record
Refreshing the parameter list view
Section 3 1MRS758406 BSMU615 overview
18 SMU615Operation Manual
3.4 Authorization
Four user categories have been predefined for the WHMI, each with different rightsand default passwords.
The default passwords in the merging unit delivered from the factory can be changedwith Administrator user rights.
Table 8: Predefined user categories
Username User rightsVIEWER Read only access
OPERATOR • Clearing indications
ENGINEER • Changing settings• Clearing event list• Clearing disturbance records• Changing system settings such as IP address, serial baud rate or
disturbance recorder settings• Setting the merging unit to test mode• Selecting language
ADMINISTRATOR • All listed above• Changing password• Factory default activation
For user authorization for PCM600, see PCM600 documentation.
3.4.1 Audit trail
The merging unit offers a large set of event-logging functions. Critical system andmerging unit security-related events are logged to a separate nonvolatile audit trail forthe administrator.
Audit trail is a chronological record of system activities that allows the reconstructionand examination of the sequence of system and security-related events and changes inthe merging unit. Both audit trail events and process related events can be examinedand analyzed in a consistent method with the help of Event List in WHMI and EventViewer in PCM600.
The merging unit stores 2048 audit trail events to the nonvolatile audit trail.Additionally, 1024 process events are stored in a nonvolatile event list. Both the audittrail and event list work according to the FIFO principle. Nonvolatile memory is basedon a memory type which does not need battery backup nor regular component changeto maintain the memory storage.
1MRS758406 B Section 3SMU615 overview
SMU615 19Operation Manual
Audit trail events related to user authorization (login, logout, violation remote andviolation local) are defined according to the selected set of requirements from IEEE1686. The logging is based on predefined user names or user categories. The user audittrail events are accessible with IEC 61850-8-1, PCM600 and WHMI.
Table 9: Audit trail events
Audit trail event DescriptionConfiguration change Configuration files changed
Firmware change Firmware changed
Firmware change fail Firmware change failed
Attached to retrofit test case Unit has been attached to retrofit case
Removed from retrofit test case Removed from retrofit test case
Control remote DPC object control remote
Test on Test mode on
Test off Test mode off
Reset trips Reset latched trips (TRPPTRC*)
Time change Time changed directly by the user. Note that this is not usedwhen the merging unit is synchronised properly by theappropriate protocol (IEEE 1588 v2).
View audit log Administrator accessed audit trail
Login Successful login from IEC 61850-8-1 (MMS), WHMI or FTP.
Logout Successful logout from IEC 61850-8-1 (MMS), WHMI or FTP.
Password change Password changed
Firmware reset Reset issued by user or tool
Audit overflow Too many audit events in the time period
Violation remote Unsuccessful login attempt from IEC 61850-8-1 (MMS),WHMI or FTP.
Violation local Unsuccessful login attempt from IEC 61850-8-1 (MMS),WHMI or FTP.
PCM600 Event Viewer can be used to view the audit trail events and process relatedevents. Audit trail events are visible through dedicated Security events view. Sinceonly the administrator has the right to read audit trail, authorization must be used inPCM600. The audit trail cannot be reset, but PCM600 Event Viewer can filter data.Audit trail events can be configured to be visible also in WHMI Event list togetherwith process related events.
To expose the audit trail events through Event list, define theAuthority logging level parameter via Configuration/Authorization/Security. This exposes audit trail events to all users.
Section 3 1MRS758406 BSMU615 overview
20 SMU615Operation Manual
Table 10: Comparison of authority logging levels
Audit trail event Authority logging level None Configuration
changeSettings edit All
Configuration change ● ● ●
Firmware change ● ● ●
Firmware change fail ● ● ●
Attached to retrofit test case ● ● ●
Removed from retrofit test case ● ● ●
Control remote ● ●
Test on ● ●
Test off ● ●
Reset trips ● ●
Time change ●
View audit log ●
Login ●
Logout ●
Password change ●
Firmware reset ●
Violation local ●
Violation remote ●
3.5 Communication
The merging unit supports a range of communication protocols including IEC 61850and IEC 61850-9-2 LE. Operational information and controls are available throughthese protocols. However, some communication functionality, for example,horizontal communication between the merging units, is only enabled by the IEC61850 communication protocol.
The IEC 61850 communication implementation supports all monitoring and controlfunctions. Additionally, parameter settings and disturbance recordings can beaccessed using the IEC 61850 protocol. Disturbance recordings are available to anyEthernet-based application in the IEC 60255-24 standard COMTRADE file format.The merging unit can send and receive binary signals from other devices (so-calledhorizontal communication) using the IEC 61850-8-1 GOOSE profile, where thehighest performance class with a total transmission time of 3 ms is supported.Furthermore, the merging unit supports sending of analog values using GOOSEmessaging. The merging unit meets the GOOSE performance requirements fortripping applications in distribution substations, as defined by the IEC 61850standard.
1MRS758406 B Section 3SMU615 overview
SMU615 21Operation Manual
The merging unit can support five simultaneous clients. If PCM600 reserves oneclient connection, only four connections are left for other clients.
All communication connectors, except for the front port connector, are placed onintegrated optional communication modules. The merging unit can be connected toEthernet-based communication systems via the RJ-45 connector (100Base-TX) or thefiber-optic LC connector (100Base-FX).
3.5.1 Ethernet redundancy
IEC 61850 specifies a network redundancy scheme that improves the systemavailability for substation communication. It is based on two complementaryprotocols defined in the IEC 62439-3:2012 standard: parallel redundancy protocolPRP-1 and high-availability seamless redundancy HSR protocol. Both protocols relyon the duplication of all transmitted information via two Ethernet ports for one logicalnetwork connection. Therefore, both are able to overcome the failure of a link orswitch with a zero-switchover time, thus fulfilling the stringent real-timerequirements for the substation automation horizontal communication and timesynchronization.
PRP specifies that each device is connected in parallel to two local area networks.HSR applies the PRP principle to rings and to the rings of rings to achieve cost-effective redundancy. Thus, each device incorporates a switch element that forwardsframes from port to port.
IEC 62439-3:2012 cancels and replaces the first edition published in2010. These standard versions are also referred to as IEC 62439-3Edition 1 and IEC 62439-3 Edition 2. The merging unit supports IEC62439-3:2012 and it is not compatible with IEC 62439-3:2010.
PRPEach PRP node, called a doubly attached node with PRP (DAN), is attached to twoindependent LANs operated in parallel. These parallel networks in PRP are calledLAN A and LAN B. The networks are completely separated to ensure failureindependence, and they can have different topologies. Both networks operate inparallel, thus providing zero-time recovery and continuous checking of redundancy toavoid communication failures. Non-PRP nodes, called single attached nodes (SANs),are either attached to one network only (and can therefore communicate only withDANs and SANs attached to the same network), or are attached through a redundancybox, a device that behaves like a DAN.
Section 3 1MRS758406 BSMU615 overview
22 SMU615Operation Manual
Ethernet switchIEC 61850 PRPEthernet switch
SCADACOM600
GUID-334D26B1-C3BD-47B6-BD9D-2301190A5E9D V3 EN
Figure 6: PRP solution
In case a laptop or a PC workstation is connected as a non-PRP node to one of the PRPnetworks, LAN A or LAN B, it is recommended to use a redundancy box device or anEthernet switch with similar functionality between the PRP network and SAN toremove additional PRP information from the Ethernet frames. In some cases, defaultPC workstation adapters are not able to handle the maximum-length Ethernet frameswith the PRP trailer.
There are different alternative ways to connect a laptop or a workstation as SAN to aPRP network.
• Via an external redundancy box (RedBox) or a switch capable of connecting toPRP and normal networks
• By connecting the node directly to LAN A or LAN B as SAN• By connecting the node to the merging unit's interlink port
HSRHSR applies the PRP principle of parallel operation to a single ring, treating the twodirections as two virtual LANs. For each frame sent, a node, DAN, sends two frames,one over each port. Both frames circulate in opposite directions over the ring and eachnode forwards the frames it receives, from one port to the other. When the originatingnode receives a frame sent to itself, it discards that to avoid loops; therefore, no ringprotocol is needed. Individually attached nodes, SANs, such as laptops and printers,must be attached through a “redundancy box” that acts as a ring element. For example,a merging unit with HSR support can be used as a redundancy box.
1MRS758406 B Section 3SMU615 overview
SMU615 23Operation Manual
GUID-207430A7-3AEC-42B2-BC4D-3083B3225990 V3 EN
Figure 7: HSR solution
3.5.2 Process bus
Process bus IEC 61850-9-2 defines the transmission of Sampled Measured Valueswithin the substation automation system. International Users Group created aguideline IEC 61850-9-2 LE that defines an application profile of IEC 61850-9-2 tofacilitate implementation and enable interoperability. Process bus is used fordistributing process data from the primary circuit to all process bus compatibledevices in the local network in a real-time manner. The data can then be processed byany protection relay to perform different protection, automation and control functions.
With process bus the galvanic wiring for sharing busbar voltage value can be replacedwith Ethernet communication. Transmitting measurement samples over process busbrings also higher error detection because the signal transmission is automaticallysupervised. Additional contribution to the higher availability is the possibility to useredundant Ethernet network for transmitting SMV signals.
Section 3 1MRS758406 BSMU615 overview
24 SMU615Operation Manual
SMV
Current Sensors
Protection and Control Relay
Substation Merging Unit
GUID-9215CB30-01E3-4D90-B9BA-473FE657DE4F V2 EN
Figure 8: SMU615 sending current measurements as sampled measuredvalues to a protection relay
1MRS758406 B Section 3SMU615 overview
SMU615 25Operation Manual
SMV
Protection and Control Relay
Substation Merging Unit
Current Sensors
Voltage Sensor
GUID-1504F322-B34D-409E-A7A9-512FB235921A V2 EN
Figure 9: SMU615 sending voltage measurements as sampled measuredvalues to protection relays
Section 3 1MRS758406 BSMU615 overview
26 SMU615Operation Manual
SMV and GOOSE
Smart Substation Control and Protection
Substation Merging Unitwith Binary I/0
Current Sensors
GUID-D8A746E4-6E21-4A4F-A963-7D66FE6A7255 V1 EN
Figure 10: Smart substation control and protection SSC600 with SMU615
The merging unit supports IEC 61850 process bus with sampled values of analogcurrents and voltages. The measured values are transferred as sampled values usingthe IEC 61850-9-2 LE protocol which uses the same physical Ethernet network as theIEC 61850-8-1 station bus. The intended application for sampled values is sharing themeasured voltages and currents from the merging unit to other devices with 9-2support.
The merging units with process bus based applications use IEEE 1588 v2 PrecisionTime Protocol (PTP) according to IEEE C37.238-2011 Power Profile for highaccuracy time synchronization. With IEEE 1588 v2, the cabling infrastructurerequirement is reduced by allowing time synchronization information to betransported over the same Ethernet network as the data communications.
1MRS758406 B Section 3SMU615 overview
SMU615 27Operation Manual
IEC 61850 HSR
SMV traffi
c
Backup 1588master clock
Managed HSREthernet switch
PrimaryIEEE 1588 v2 master clock
SecondaryIEEE 1588 v2 master clock(optional)
Managed HSREthernet switch
GUID-7C56BC1F-F1B2-4E74-AB8E-05001A88D53D V6 EN
Figure 11: Example network topology with process bus, redundancy and IEEE1588 v2 time synchronization
The process bus is available for all merging units. See the IEC 61850 engineeringguide for detailed system requirements and configuration details.
3.5.3 Secure communication
The merging unit supports secure communication for WHMI and file transferprotocol. If the Secure Communication parameter is activated, protocols require TLSbased encryption method support from the clients. In this case WHMI must beconnected from a Web browser using the HTTPS protocol and in case of file transferthe client must use FTPS.
3.6 PCM600 tool
Protection and Control IED Manager PCM600 offers all the necessary functionalityto work throughout all stages of the merging unit life cycle.
• Planning• Engineering• Commissioning• Operation and disturbance handling• Functional analysis
Section 3 1MRS758406 BSMU615 overview
28 SMU615Operation Manual
The whole substation can be controlled and different tasks and functions can beperformed with the individual tool components. PCM600 can operate with manydifferent topologies, depending on the customer needs.
For more information, see the PCM600 documentation.
3.6.1 Connectivity packages
A connectivity package is a software component that consists of executable code anddata which enables system tools to communicate with a merging unit. Connectivitypackages are used to create configuration structures in PCM600. The latest PCM600and connectivity packages are backward compatible with older merging unit versions.
A connectivity package includes all of the data which is used to describe the mergingunit, for example, it contains a list of the existing parameters, data format used, units,setting range, access rights and visibility of the parameter. In addition, it contains codewhich allows software packages that consume the connectivity package to properlycommunicate with the merging unit. It also allows for localization of text even whenits read from the merging unit in a standard format such as COMTRADE.
Update Manager is a tool that helps in defining the right connectivity package versionsfor different system products and tools. Update Manager is included with productsthat use connectivity packages.
3.6.2 PCM600 and merging unit's connectivity package version
• Protection and Control IED Manager PCM600 2.7 or later• SMU615 Connectivity Package Ver.1.0 or later
Contact ABB for information on the latest connectivity package.
1MRS758406 B Section 3SMU615 overview
SMU615 29Operation Manual
30
Section 4 Using HMI
4.1 Using local HMI
4.1.1 Clearing and acknowledging
The Clear button is used to reset and acknowledge latched programmable LEDindications. It is a shortcut for clearing.
• Press for three seconds to clear the latched programmable LEDs.
4.2 Using Web HMI
• As secure communication is enabled by default, access the WHMI from a Webbrowser using the HTTPS protocol.
To establish a remote WHMI connection to the merging unit, contactthe network administrator to check the company rules for IP andremote connections.
Disable the Web browser proxy settings or make an exception to theproxy rules to allow the merging unit's WHMI connection, forexample, by including the merging unit's IP address in InternetOptions/Connections/LAN Settings/Advanced/Exceptions.
4.2.1 Logging in
1. Open Internet Explorer.2. Type the merging unit's IP address in the Address bar and press ENTER.3. Type the username with capital letters.4. Type the password.
1MRS758406 B Section 4Using HMI
SMU615 31Operation Manual
GUID-0AB12E2C-429A-45C8-B988-1B642151BF1B V1 EN
Figure 12: Entering username and password to use the WHMI
5. Click OK.The language file starts loading and the progress bar is displayed.
4.2.2 Logging out
The user is logged out after session timeout. The timeout can be set in Main menu/Configuration/HMI/Web HMI timeout.
• To log out manually, click Logout on the menu bar.
4.2.3 Identifying device
The Information menu includes detailed information about the device, for example,revision and serial number.
1. Click the Information menu in the left navigation bar.2. Click a submenu to see the data.
Section 4 1MRS758406 BUsing HMI
32 SMU615Operation Manual
GUID-B0043C52-2019-4107-9E0C-8479160C4E23 V1 EN
Figure 13: Device information
4.2.4 Navigating in menus
• Use the menu bar to access different views.• The General view shows the merging unit version and status.• The Events view contains a list of events produced by the application
configuration.• The Programmable LEDs view shows the status of programmable LEDs.• The Phasor diagrams view shows phasor diagrams.• The Disturbance records view shows the list of disturbance records.• The Report summary page allows to save events, fault records,
disturbance records, the load profile record and the parameter list.• The Import/Export page allows to import and export parameters settings.• Logout ends the session.
1MRS758406 B Section 4Using HMI
SMU615 33Operation Manual
GUID-EDC36E53-BED1-41B4-A145-929CD9F400D8 V1 EN
Figure 14: Navigating in Web HMI menus
4.2.4.1 Menu structure
The Main menu contains main groups which are divided further into more detailedsubmenus.
• Control• Events• Measurements• Disturbance records• Configuration• Monitoring• Tests• Information• Clear• Language• Load profile record• Parameter list• WHMI settings
4.2.5 Showing parameters
Some function blocks have a function-specific On/Off setting. When the functionsetting is “Off”, all settings are hidden and when the function setting is “On”, allsettings are visible based on the other visibility and hiding rules.
Section 4 1MRS758406 BUsing HMI
34 SMU615Operation Manual
Switch a function block on or off via the Operation parameter underthe required function block.
GUID-46D55DE4-0DC3-4DFC-ABC8-5E5504D9BDB2 V1 EN
Figure 15: Function block On
GUID-9CDFAC5C-A3F1-4FF2-85E9-A8497457A160 V1 EN
Figure 16: Function block Off
1MRS758406 B Section 4Using HMI
SMU615 35Operation Manual
The Parameter list page offers filtering functionality where only chosen parametersare displayed, saved or printed. There are various options for filtering.
• Enabled settings hides settings of disabled function blocks.• Writable settings displays only writable settings. This option is checked by
default.• Basic settings displays only basic settings.• Setting group displays only settings of the selected setting group. With “All”
selected, all setting groups are displayed.
Options can be combined. For example, with the Enabled settings and Writablesettings selected, only enabled and writable settings are displayed. If none of theoptions is selected, all settings are displayed.
The values “Basic” or "Advanced" of the Setting visibility parameterin Main Menu/Configuration/HMI have no effect on the Parameterlist page. This page has its own Basic settings option which can beused to hide or show the advanced settings on the Parameter list page.
GUID-01AE031C-EAE9-43F1-AD3D-4129FD898BF9 V1 EN
Figure 17: Parameter list filter
1. Click Parameter list in the left navigation bar.
Section 4 1MRS758406 BUsing HMI
36 SMU615Operation Manual
GUID-F84CDCC5-8FC6-4611-98BF-CA8F7A39A7A2 V1 EN
Figure 18: Displaying parameters
2. Select only those settings that are wanted to be shown and click Refresh. Ifnothing is selected, all settings are shown.
1MRS758406 B Section 4Using HMI
SMU615 37Operation Manual
GUID-C76B08BF-EFD9-4C62-8A4A-A7D2FA6D2E9F V1 EN
Figure 19: Enabled settings
3. Select text (.txt) or comma separated values (.csv) file format and click Save tosave the settings.
4. Click Print to print all the selected parameters.
4.2.6 Editing values
1. Select a menu in the left navigation bar.2. Click a submenu to see function blocks.3. Click a function block to see the setting values.4. Click Enable Write.
Some parameters, for example the Web HMI mode, cannot beset via the WHMI.
Section 4 1MRS758406 BUsing HMI
38 SMU615Operation Manual
GUID-2B6D2DD5-5FC1-4DB4-A236-EE5B22345256 V1 EN
Figure 20: Enable writing to edit a value
5. Edit the value.• The minimum, maximum and step values for a parameter are shown in the
Min., Max. and Step columns.
GUID-B5325CB7-ACD6-43A0-A127-8EF42D0EA422 V1 EN
Figure 21: Editing a value
• If the entered value is within the accepted value range, the selection ishighlighted in green. If the value is out of range, the row is highlighted inred and a warning dialog box is displayed. Write to IED is unavailable.
1MRS758406 B Section 4Using HMI
SMU615 39Operation Manual
GUID-9F1E94E3-7158-43D2-A5C1-CF0DD26A323A V1 EN
Figure 22: Warning indicating that the entered value is incorrect
• If writing values fails, a warning dialog box is displayed.
GUID-DECD6544-3F83-4180-96D9-DE4E417B5CCF V1 EN
Figure 23: Warning indicating that the values were not written to themerging unit
If writing is enabled accidentally, click Disable Write. DisableWrite cannot be selected when a value has already been written to themerging unit. After clicking Write to IED, click either Commit orReject.
Section 4 1MRS758406 BUsing HMI
40 SMU615Operation Manual
4.2.7 Committing settings
Editable values are stored either in RAM or a nonvolatile flash memory. Values storedin the flash memory are in effect also after a reboot.
Some parameters have an edit-copy. If editing is cancelled, the values with an edit-copy are immediately restored to the original value. The values without an edit-copy,such as string values, are restored to the original value only after a reboot even thoughthe edited value is not stored in the flash memory.
1. Click Write to IED after editing parameter values to put the values into mergingunit's database for use.
GUID-483C33DD-395D-4B98-8AA3-6F7F921AB66F V1 EN
Figure 24: Writing values to merging unit
The values are not stored to the flash memory.2. Click Commit to write the values to the flash memory.
• Click Reject to cancel saving settings.• If the parameter has an edit-copy, the original parameter value is
restored.• If the parameter does not have an edit-copy, the edited parameter
value remains visible until the merging unit is rebooted. However,the edited value is not stored in the nonvolatile memory and thusthe reboot restores the original value.
1MRS758406 B Section 4Using HMI
SMU615 41Operation Manual
GUID-7B3457D2-FCA3-4140-A2F8-426365388C70 V1 EN
Figure 25: Committing changes
Committing values takes a few seconds.
If the values are not committed, they are not taken into use and they arelost after a reboot.
4.2.8 Clearing and acknowledging
All messages and indications, including LEDs and latched outputs as well as registersand recordings, can be reset, acknowledged or cleared using the Clear menu.
1. Click Clear in the left navigation bar.
Section 4 1MRS758406 BUsing HMI
42 SMU615Operation Manual
GUID-3A9198A2-9C76-4510-8A8C-3FA69C643137 V1 EN
Figure 26: Selecting clear menu
2. In the New Value list, select Clear to choose the item to be cleared.3. Click Write to IED.
4.2.9 Selecting programmable LEDs view
The programmable LEDs view shows the status of the programmable LEDs. Theseare the same LEDs that are located on the upper right side of the LHMI panel.
• Click Programmable LEDs on the menu bar.
GUID-4833221F-9B24-435A-9BDC-E7CA63441262 V1 EN
Figure 27: Monitoring programmable LEDs
1MRS758406 B Section 4Using HMI
SMU615 43Operation Manual
4.2.10 Selecting event view
The event view contains a list of events produced by the application configuration.When the event page is opened, it displays up to 100 latest events at one time. Theevent list is updated automatically.
1. Click Events on the menu bar.
GUID-E9A051E2-5E44-4030-9B98-5E7A8EE0D192 V1 EN
Figure 28: Monitoring events
2. Click Freeze to stop updating the event list.3. Select a page from the drop-down list to view older events or select View all to
show all events on the same page.
Section 4 1MRS758406 BUsing HMI
44 SMU615Operation Manual
GUID-FB32E6A6-3D67-435B-A641-9355808FCEF4 V1 EN
Figure 29: Events view
4. To save the events in TXT or CSV file formats, select the file format from thedrop-down list and click Save.
The CSV file can be opened with a spreadsheet program such asOpenOffice.org Calc or Microsoft Excel.
5. Click Clear events to clear all events from the merging unit.6. Click Print to print all the selected events.
4.2.11 Selecting disturbance records view
Disturbance records are listed in the disturbance records view.
• Click Disturbance records on the menu bar.
1MRS758406 B Section 4Using HMI
SMU615 45Operation Manual
GUID-84D7BB2A-D0CE-42DF-BEB3-5ECA484DC5F7 V1 EN
Figure 30: Selecting disturbance records view
4.2.11.1 Saving disturbance records
1. Click Disturbance records on the menu bar.2. To save the disturbance record files, click the icon in the Download Files
column of the record.Both the disturbance record files CFG and DAT are saved at once.
3. Open the disturbance record files with a suitable program.
4.2.11.2 Triggering disturbance recorder manually
1. Click Disturbance records on the menu bar.2. Click Manual trigger.
Section 4 1MRS758406 BUsing HMI
46 SMU615Operation Manual
GUID-6E4E3018-7E42-4A31-8789-418254CCCC6E V1 EN
Figure 31: Manual triggering
4.2.11.3 Deleting disturbance records
1. Click Disturbance records on the menu bar.2. Delete records.
• Click Delete all to delete all records.• Select one or more recordings and click Delete to delete selected records.
GUID-E7CEA6CF-553A-4E3E-B8D2-455021979C69 V1 EN
Figure 32: Deleting disturbance records
3. Click OK to confirm or Cancel to cancel the deletion.
1MRS758406 B Section 4Using HMI
SMU615 47Operation Manual
4.2.12 Selecting phasor diagrams
Install or enable the SVG plugin to view the phasor diagrams, ifneeded.
1. Click Phasor diagrams on the menu bar.
GUID-35E11BD4-72E2-4A67-B0DF-7ADCBF4293B1 V1 EN
Figure 33: Monitoring phasors
2. Toggle the diagram visibility by selecting the diagram from the drop-downmenu.
GUID-F2F9EDE0-5327-4447-8814-90398A7B3AED V1 EN
Figure 34: Toggling the diagram visibility
Visible diagrams are indicated with an asterisk *.3. Change the size of the diagram by changing the zoom value.
Section 4 1MRS758406 BUsing HMI
48 SMU615Operation Manual
GUID-B5578CE5-EC7F-4957-AD35-666708587EC5 V1 EN
Figure 35: Zooming the diagram
4. Click Freeze to stop updating the phasor diagram.No updates are displayed in the diagram.
GUID-09863F7A-D07B-4617-8E7F-4D511D75F75B V1 EN
Figure 36: The arrow extends outside the circle if the current value is toohigh
4.2.13 Exporting load profile records
1. Click Load profile record in the left navigation bar.2. To export the load profile record files, click the icon in the Download Files
column.
1MRS758406 B Section 4Using HMI
SMU615 49Operation Manual
Both the load profile record files CFG and DAT are saved at once.3. Save the CFG and DAT files in the same folder on the computer.4. Open the load profile record COMTRADE files with a suitable program.
Open the load profile files, for example, with the Wavewin toolincluded in PCM600.
4.2.14 Import and export of settings
Merging unit's setting parameters can be imported and exported in the XRIO fileformat.
4.2.14.1 Exporting settings
Merging unit's setting parameters can be exported in XRIO file format.
1. Click Import/Export on the menu bar.2. Click Export Settings. The export file includes all parameters except status
parameters.
GUID-E6E705B1-CA97-4E70-AACD-DA222739E9D4 V1 EN
Figure 37: Exporting settings
3. Click Save to export the settings to the computer.
4.2.14.2 Importing settings
The parameter export and import function can be utilized, for example, when themerging unit parameters are set using the WHMI instead of PCM600. The merging
Section 4 1MRS758406 BUsing HMI
50 SMU615Operation Manual
unit settings engineered with PCM600 can be exported to XRIO files and imported tothe WHMI. The WHMI can be used to write the settings to the merging units. TheWHMI can also be used to read the merging unit setting parameters and to export thoseto files, which can be used by PCM600. WHMI imports all parameters from the importfile except lockable and read only parameters.
The exporting and importing of settings is sensitive to the mergingunit contents. Settings are exported and imported for one merging unitat a time. The export files of a specific merging unit can be exchangedbetween PCM600, WHMI and the actual physical merging unit. Toavoid errors and to efficiently manage the exporting and importing ofsettings, for example, in a substation with several devices, ensure thatthe names of the export files identify the merging unit to which the fileshould be imported.
Ensure that the correct settings are imported to the correct mergingunit. Wrong settings may cause the merging unit to malfunction.
1. Click Import/Export on the menu bar.2. Click Browse and choose the file to be imported.
GUID-DEF079A4-B520-4F36-8521-E667742CDAF5 V1 EN
Figure 38: Browsing import settings
3. Click Import Settings.Wait until the file transfer is complete.
1MRS758406 B Section 4Using HMI
SMU615 51Operation Manual
GUID-9B3ABBCE-CA5F-4155-B1A4-CF44287CD490 V1 EN
Figure 39: Importing settings
4. Click OK to commit the imported settings to the merging unit.Wait until the import is complete.• Click Cancel to cancel the importing. Both the WHMI and the merging
unit revert to the settings in use prior to the import.
GUID-80DEBFAD-10A5-470A-94B8-4EA4C344FDFB V1 EN
Figure 40: Writing parameter settings
Section 4 1MRS758406 BUsing HMI
52 SMU615Operation Manual
GUID-5985CB9C-2120-4FE6-B2A4-3CDA26124413 V1 EN
Figure 41: Parameter settings written to merging unit
Only editable parameters are written to the merging unit during theimport. If part of the import fails, the faulty parameters are listedseparately.
4.2.15 Exporting report summary
The Report summary page allows exporting events, disturbance records, the loadprofile record and the parameter list. Events and the parameter list are saved in TXTformat. Saved files contain all events and settings.Disturbance records and loadprofile record files are saved in CFG and DAT formats.
1. Click Report summary on the menu bar.2. Select the items to be exported.
Click Select all to select all items and click Clear all to clear all selections.3. From the Disturbance records drop-down list, select the amount of records to
be saved.• All• Last 1• Last 10
4. Click Save to export the ZIP file with the selected files.
1MRS758406 B Section 4Using HMI
SMU615 53Operation Manual
GUID-4CE30BB5-2324-4DFB-B3F7-6C6989EB5FB0 V1 EN
Figure 42: Report summary page
4.2.16 Using Web HMI help
The context-sensitive WHMI help provides information on a single parameter, forexample.
• Move the mouse over the to display the help dialog box.
GUID-159BC906-F846-4F19-9B19-68943EBDC36B V1 EN
Figure 43: Opening the WHMI help
Section 4 1MRS758406 BUsing HMI
54 SMU615Operation Manual
Section 5 Merging unit operation
5.1 Normal operation
In a normal merging unit use situation, the basic operation includes monitoring andchecking procedures.
• Monitoring measured values• Checking object states• Checking function setting parameters• Checking events and alarms
All basic operations can be performed via the WHMI or with PCM600.
For more information, see the PCM600 documentation.
5.2 Disturbance identification
Disturbances and their causes can be identified by the Ready indicator LED. Duringnormal operation, the Ready LED is steady green.
Table 11: Disturbance indications
LED State DescriptionReady LED Green, flashing Internal fault
Further actions to be taken to identify the disturbance:
• Checking programmable LEDs• Reading event history• Checking fault records• Analyzing disturbance recordings
Document the disturbance before clearing the information from themerging unit.
1MRS758406 B Section 5Merging unit operation
SMU615 55Operation Manual
Only authorized and skilled personnel should analyze possible errorsand decide on further actions. Otherwise, stored disturbance data canbe lost.
5.2.1 Disturbance recording triggering
Disturbance recordings are normally triggered by merging unit applications whenthey detect fault events. Disturbance recordings can also be triggered manually orperiodically. The manual trigger generates an instant disturbance report. Use thisfunction to get a snapshot of the monitored signals.
5.2.2 Disturbance record analysis
The merging unit collects disturbance records of fault events which are set to triggerthe disturbance recorder. Disturbance data is collected and stored for later viewing andanalysis. The disturbance recorder data can be read and analyzed with PCM600.
For more information, see the PCM600 documentation.
5.2.3 Disturbance reports
PCM600 can be used for creating reports of disturbance recorder data.
For more information, see the PCM600 documentation.
5.2.4 Merging unit self-supervision
The merging unit self-supervision handles internal run-time fault situations.The mainindication of an internal fault is a flashing green Ready LED.
Internal faults can be divided to hardware errors, run-time errors in the application oroperating system and communication errors. Further actions always depend on thecause of the error.
Only authorized and skilled personnel should analyze the errors anddecide on further actions.
The merging unit records system registrations, merging unit status data and events.
Section 5 1MRS758406 BMerging unit operation
56 SMU615Operation Manual
Document all the recorded data from the merging unit before resettingthe tripping and lockout functions.
5.3 Merging unit parametrization
Merging unit parameters are set via the WHMI or PCM600.
Setting parameters need to be calculated according to the electrical networkconditions and the electrical characteristics of the protected equipment. The mergingunit's settings need to be verified before the merging unit is connected to a system.
Document all changes to parameter settings.
For more information, see the PCM600 documentation.
1MRS758406 B Section 5Merging unit operation
SMU615 57Operation Manual
58
Section 6 Operating procedures
6.1 Monitoring
6.1.1 Indications
The operation of the merging unit can be monitored via two different indications onthe LHMI.
• One indicator LED with fixed functionality: Ready• 11 programmable LEDs
6.1.1.1 Monitoring merging unit's internal fault
The flashing green LED indicates an internal fault.
• Use the WHMI to monitor the internal fault of the merging unit.
See the troubleshooting section for more details.
6.1.2 Measured and calculated values
Measurement view in Main Menu/Measurements shows the momentary actualvalues for various power system measurements.
All values show the momentary measurement value and some include demand valuescalculated from a set period.
Invalid or questionable measurement values are presented inparentheses.
6.1.2.1 Measured values
Measured values can be accessed through the WHMI or PCM600.
1MRS758406 B Section 6Operating procedures
SMU615 59Operation Manual
Table 12: Examples of the measured values
Indicator DescriptionIL1-A Current measured on phase L1
IL2-A Current measured on phase L2
IL3-A Current measured on phase L3
I0-A Measured earth-fault current
U0-kV Measured residual voltage
U12-kV Measured phase-to-phase voltage U12
U23-kV Measured phase-to-phase voltage U23
U31-kV Measured phase-to-phase voltage U31
f-Hz Measured frequency
S-MVA Total apparent power
P-MW Total active power
Q-MVar Total reactive power
PF Average power factor
Ng-Seq-A Negative-phase-sequence current
Ps-Seq-A Positive-phase-sequence current
Zro-Seq-A Zero-phase-sequence current
Ng-Seq-kV Negative-phase-sequence voltage
Ps-Seq-kV Positive-phase-sequence voltage
Zro-Seq-kV Zero-phase-sequence voltage
6.1.3 Recorded data
The merging unit is provided with intelligent and flexible functionality that collectsdifferent kinds of data. The recorded data gives substantial information for post faultanalysis.
• Disturbance records• Events
6.1.3.1 Creating disturbance recordings
Normally disturbance recordings are triggered by the merging unit applications butthe recording can also be triggered manually via the WHMI.
1. Click Disturbance records on the menu bar.2. Click Manual trigger.
The disturbance recorder is now triggered.
Section 6 1MRS758406 BOperating procedures
60 SMU615Operation Manual
6.1.3.2 Monitoring disturbance recorder data
Disturbance recorder data can be monitored via the WHMI.
• Click Disturbance records on the menu bar.All the disturbance recorder information is listed.• Number of recordings currently in the merging unit's memory• Remaining amount of recordings that fit into the available recording
memory• Recording memory used in percentage• If the periodic triggering function is used, the time to trigger which
indicates the remaining time to the next periodic triggering of thedisturbance recorder.
GUID-97B2F1DD-6BB2-4C71-80F6-93600B29356B V1 EN
Figure 44: Monitoring disturbance recorder via Web HMI
Individual disturbance recordings can be uploaded from the merging unit with thePCM600 software to monitor disturbance recorder data.
6.1.3.3 Controlling and reading of disturbance recorder data
Disturbance recorder data can be controlled and read with PCM600. It can also be readvia WHMI.
For more information, see the PCM600 documentation.
1MRS758406 B Section 6Operating procedures
SMU615 61Operation Manual
6.1.4 Remote monitoring
The merging unit supports comprehensive remote monitoring.
6.1.4.1 Monitoring merging units remotely
Use the PCM600 tool and WHMI to operate the merging unit remotely.
• Read maintenance record and version log.• Analyze disturbance record data.• Create disturbance records.• Monitor merging unit values.
For more information, see the PCM600 documentation.
6.2 Resetting merging unit
6.2.1 Clearing and acknowledging
All messages and indications, including LEDs and latched outputs as well as registersand indications, including recordings can be reset, acknowledged or cleared via theWHMI using the Clear menu.
• Click Clear in the left navigation bar.All the items that can be cleared are shown.• Programmable LEDs• Events• Metering records• Disturbance records• Master trip• Acc. energy of three-phase power and energy measurement
Use the button as a shortcut for clearing. The first three-secondpress clears the indications. The second three-second press clears theprogrammable LEDs.
Section 6 1MRS758406 BOperating procedures
62 SMU615Operation Manual
6.3 Changing merging unit functionality
6.3.1 Activating programmable LEDs
Programmable LEDs can be activated via the WHMI.
1. Click the Configuration menu in the left navigation bar and selectProgrammable LEDs.
2. Select a programmable LED to change its mode.3. Click Enable Write.4. In the New Value list, select the LED mode.5. Click Write to IED.
1MRS758406 B Section 6Operating procedures
SMU615 63Operation Manual
64
Section 7 Troubleshooting
7.1 Fault tracing
7.1.1 Identifying hardware errors
1. Check the module with an error.Check the supervision events via the Web HMI for a faulty hardware module.
2. Inspect the merging unit visually.• Inspect the merging unit visually to find any physical error causes.• If you can find some obvious physical damage, contact ABB for repair or
replacement actions.3. Check whether the error is external or internal.
• Check that the error is not caused by external origins.• Remove the wiring from the merging unit and test the input and output
operation with an external test device.• If the problem remains, contact ABB for repair or replacement actions.
7.1.2 Identifying runtime errors
1. Check the error origin from the merging unit's supervision events via the WebHMI.
2. Reboot the merging unit and recheck the supervision events to see if the fault hascleared.
3. In case of persistent faults, contact ABB for corrective actions.
7.1.3 Identifying communication errors
Communication errors are normally communication interruptions or synchronizationmessage errors due to communication link breakdown.
• In case of persistent faults originating from merging unit's internal faults such ascomponent breakdown, contact ABB for repair or replacement actions.
7.1.3.1 Checking front communication link operation
• To verify front communication, check that both LEDs above the RJ-45communication port are lit.
1MRS758406 B Section 7Troubleshooting
SMU615 65Operation Manual
Table 13: Front communication LEDs
LED Communication okUplink Steady green light
Communication Flashing yellow light
7.1.3.2 Checking time synchronization
1. Click the Monitoring menu in the left navigation bar and select IED status.2. Check Time synchronization.
7.2 Indication messages
7.2.1 Internal faults
An event about the fault is stored as a message on the WHMI. The text InternalFault with an additional text message, a code, date and time, is stored to indicate thefault type.
Different actions are taken depending on the severity of the fault. The merging unittries to eliminate the fault by restarting. After the fault is found to be permanent, themerging unit stays in the internal fault mode. All other output contacts are released andlocked for the internal fault. The merging unit continues to perform internal testsduring the fault situation.
The internal fault code indicates the type of internal fault. When a fault appears, thecode must be recorded so that it can be reported to ABB customer service.
Table 14: Internal fault indications and codes
Fault indication Fault code Additional informationInternal FaultSystem error
2 An internal system error has occurred.
Internal FaultFile system error
7 A file system error has occurred.
Internal FaultTest
8 Internal fault test activated manually by theuser.
Internal FaultSW watchdog error
10 Watchdog reset has occurred too manytimes within an hour.
Internal FaultSO-relay(s),X100
43 Faulty Signal Output relay(s) in cardlocated in slot X100.
Internal FaultSO-relay(s),X110
44 Faulty Signal Output relay(s) in cardlocated in slot X110.
Internal FaultPO-relay(s),X100
53 Faulty Power Output relay(s) in cardlocated in slot X100.
Internal FaultPO-relay(s),X110
54 Faulty Power Output relay(s) in cardlocated in slot X110.
Table continues on next page
Section 7 1MRS758406 BTroubleshooting
66 SMU615Operation Manual
Fault indication Fault code Additional informationInternal FaultConf. error,X000
62 Card in slot X000 is wrong type, is missing,does not belong to original configuration orcard firmware is faulty.
Internal FaultConf. error,X100
63 Card in slot X100 is wrong type or does notbelong to the original composition.
Internal FaultConf. error,X110
64 Card in slot X110 is wrong type, is missingor does not belong to the originalcomposition.
Internal FaultConf. error,X120
65 Card in slot X120 is wrong type, is missingor does not belong to the originalcomposition.
Internal FaultConf.error,X130
66 Card in slot X130 is wrong type, is missingor does not belong to the originalcomposition.
Internal FaultCard error,X000
72 Card in slot X000 is faulty.
Internal FaultCard error,X100
73 Card in slot X100 is faulty.
Internal FaultCard error,X110
74 Card in slot X110 is faulty.
Internal FaultCard error,X120
75 Card in slot X120 is faulty.
Internal FaultCard error,X130
76 Card in slot X130 is faulty.
Internal FaultLHMI module
79 LHMI module is faulty. The fault indicationmay not be seen on the LHMI during thefault.
Internal FaultRAM error
80 Error in the RAM memory on the CPUcard.
Internal FaultROM error
81 Error in the ROM memory on the CPUcard.
Internal FaultEEPROM error
82 Error in the EEPROM memory on the CPUcard.
Internal FaultFPGA error
83 Error in the FPGA on the CPU card.
Internal FaultRTC error
84 Error in the RTC on the CPU card.
Internal FaultCOM card error
116 Error in the COM card.
7.2.2 Warnings
An event about the warnings are stored with the text Warning additionally providedwith the name of the warning, a numeric code and the date and time on the WHMI.
If a warning appears, record the name and code so that it can beprovided to ABB customer service.
1MRS758406 B Section 7Troubleshooting
SMU615 67Operation Manual
Table 15: Warning indications and codes
Warning indication Warning code Additional informationWarningWatchdog reset
10 A watchdog reset has occurred.
WarningPower down det.
11 The auxiliary supply voltage has droppedtoo low.
WarningIEC61850 error
20 Error when building the IEC 61850 datamodel.
WarningDataset error
24 Error in the Data set(s).
WarningReport cont. error
25 Error in the Report control block(s).
WarningGOOSE contr. error
26 Error in the GOOSE control block(s).
WarningSCL config error
27 Error in the SCL configuration file or the fileis missing.
WarningLogic error
28 Too many connections in theconfiguration.
WarningSMT logic error
29 Error in the SMT connections.
WarningGOOSE input error
30 Error in the GOOSE connections.
ACT error 31 Error in the ACT connections.
WarningGOOSE Rx. error
32 Error in the GOOSE message receiving.
WarningAFL error
33 Analog channel configuration error.
WarningSMV config error
34 Error in the SMV configuration.
WarningComm. channel down
35 Redundant Ethernet (HSR/PRP)communication interrupted.
WarningUnack card comp.
40 A new composition has not beenacknowledged/accepted.
7.3 Correction procedures
7.3.1 Rebooting software
1. Click the Configuration menu in the left navigation bar and select General.2. Click Enable Write.3. Edit the Software reset parameter.
• In the New Value list, select Activate.4. Click Write to IED.
Section 7 1MRS758406 BTroubleshooting
68 SMU615Operation Manual
7.3.2 Restoring factory settings
In case of configuration data loss or any other file system error that prevents themerging unit from working properly, the whole file system can be restored to theoriginal factory state. All default settings and configuration files stored in the factoryare restored. Only the administrator can restore the factory settings.
1. Click the Configuration menu in the left navigation bar and select General.2. Click Enable Write.3. Edit the Factory setting parameter.
• In the New Value list, select Activate.4. Click Write to IED.
The merging unit restores the factory settings and restarts. Restoring takes 1...3minutes. Confirmation of restoring the factory settings is shown on the display a fewseconds, after which the merging unit restarts.
Avoid the unnecessary restoring of factory settings, because all theparameter settings that are written earlier to the merging unit will beoverwritten with the default values.
7.3.3 Restoring administrator password
If authentication is enabled in the merging unit and the administrator password is lost,it is no longer possible to change passwords or operate the merging unit with fullaccess rights.
The administrator password can be restored to the default value using a one-timepassword. The OTP functionality is only available via the merging unit's front port.
Contact ABB technical customer support to retrieve the administrator level access tothe merging unit.
1. Using the front RJ-45 port, connect a PC to the merging unit.2. Open the Web browser and go to https://192.168.0.254/otp.html.3. Forward the displayed OTP related information to ABB technical customer
support to receive a one-time password.4. Reset the administrator password.
4.1. Type the ADMINISTRATOR username with capital letters.4.2. Type the one-time password.4.3. Click Reset.
1MRS758406 B Section 7Troubleshooting
SMU615 69Operation Manual
• If the password is successfully reset, restart the browser and log in asadministrator using the default password.
• If the password reset fails, try again or contact ABB technical customersupport again.
7.3.4 Setting passwords
If user authorization is off or the user is logged in as an administrator, user passwordscan be set via the WHMI or with PCM600.
Local passwords can be changed in WHMI only via the merging unit's front RJ-45port. Remote passwords can be changed via the WHMI or with PCM600.
1. Click Configuration in the left navigation bar and select Authorization.2. Select the Passwords submenu and edit the values.3. Click Write to IED.
If the administrator password is lost, contact ABB's technicalcustomer support to retrieve the administrator level access.
7.3.5 Identifying merging unit application problems
• Check that the function is on.• Check the blocking.• Check the mode.• Check the measurement value.• Check the connection to trip and disturbance recorder functions.• Check the channel settings.
7.3.5.1 Inspecting wiring
The physical inspection of wiring connections often reveals the wrong connection forphase currents or voltages. However, even though the phase current or voltageconnections to merging unit terminals might be correct, wrong polarity of one or moremeasurement transformers can cause problems.
• Check the current or voltage measurements and their phase information fromMain menu/Measurements.
• Check that the phase information and phase shift between phases is correct.• Correct the wiring if needed.• Check the actual state of the connected binary inputs from Main menu/
Monitoring/I/O status/Binary input values.• Test and change the relay state manually in Main menu/Tests/Binary outputs.
Section 7 1MRS758406 BTroubleshooting
70 SMU615Operation Manual
7.3.5.2 Sample data interruptions
Occasionally merging units can receive corrupted or faulty measurement data duringruntime. In these cases the operation system halts the corresponding applicationexecution until correct data is received. In case of permanent faults, the measurementchain should be checked to remove the origin of the faulty measurement data.
In case of persistent faults originating from merging unit's internalfaults, contact ABB for repair or replacement actions.
1MRS758406 B Section 7Troubleshooting
SMU615 71Operation Manual
72
Section 8 Commissioning
8.1 Commissioning checklist
Familiarize yourself with the merging unit and its functionality before you start thecommissioning work.
• Ensure that your version of the technical manual applies to the merging unitversion you test.
• Ensure that your setting software and connectivity packages work with themerging unit version you test.
• Find out if you need any additional software.• Ensure that you have the merging unit settings either on paper or in electronic
format. The settings and logic should be well documented.• Inspect the settings to ensure that they are correct.• Ensure that you have the correct cable to connect your PC to the merging unit's
communication port. The RJ-45 port supports any CAT 5 Ethernet cable but therecommendation is STP.
• Test your PC's communication port before you go to the site.• Find out who to contact if you have trouble and make sure you have a means to
contact them.• Find out who is responsible for the settings.• Ensure that you have with you the proper test equipment and all needed
connection cables.• Ensure that the owner of the switchgear familiarizes you with the work site and
any special aspects of it.• Ensure that you know how to operate in emergency situations. Find out where the
first aid and safety materials and exit routes are.
8.2 Checking installation
8.2.1 Checking power supply
• Check that the auxiliary supply voltage remains within the permissible inputvoltage range under all operating conditions.
• Check that the polarity is correct before powering the merging unit.
1MRS758406 B Section 8Commissioning
SMU615 73Operation Manual
8.2.2 Checking CT circuits
Check that the wiring is in strict accordance with the suppliedconnection diagram.
The CTs must be connected in accordance with the terminal diagram provided withthe merging unit, both with regards to phases and polarity. The following tests arerecommended for every primary CT or CT core connected to the merging unit.
• Primary injection test to verify the current ratio of the CT, the correct wiring upto the merging unit and correct phase sequence connection (that is L1, L2, L3.)
• Polarity check to prove that the predicted direction of the secondary current flowis correct for a given direction of the primary current flow. This is an essential testfor the proper operation of the directional function, protection or measurement inthe merging unit.
• CT secondary loop resistance measurement to confirm that the currenttransformer secondary loop DC resistance is within specification and that thereare no high resistance joints in the CT winding or wiring.
• CT excitation test to ensure that the correct core in the CT is connected to themerging unit. Normally only a few points along the excitation curve are checkedto ensure that there are no wiring errors in the system, for example, due to amistake in connecting the CT's measurement core to the merging unit.
• CT excitation test to ensure that the CT is of the correct accuracy rating and thatthere are no short circuited turns in the CT windings. Manufacturer's designcurves should be available for the CT to compare the actual results.
• Earthing check of the individual CT secondary circuits to verify that each three-phase set of main CTs is properly connected to the station earth and only at oneelectrical point.
• Insulation resistance check.• Phase identification of CT shall be made.
Both the primary and the secondary sides must be disconnected fromthe line and the merging unit when plotting the excitationcharacteristics.
If the CT secondary circuit is opened or its earth connection is missingor removed without the CT primary being de-energized first,dangerous voltages may be produced. This can be lethal and causedamage to the insulation. The re-energizing of the CT primary shouldbe prohibited as long as the CT secondary is open or unearthed.
8.2.3 Checking VT circuits
Check that the wiring is in strict accordance with the supplied connection diagram.
Section 8 1MRS758406 BCommissioning
74 SMU615Operation Manual
Correct possible errors before continuing to test the circuitry.
Test the circuitry.
• Polarity check• VT circuit voltage measurement (primary injection test)• Earthing check• Phase relationship• Insulation resistance check
The polarity check verifies the integrity of circuits and the phase relationships. Thepolarity must be measured as close to the merging unit as possible to ensure that mostof the wiring is also checked.
The primary injection test verifies the VT ratio and the wiring all the way from theprimary system to the merging unit. Injection must be performed for each phase-to-neutral circuit and each phase-to-phase pair. In each case, voltages in all phases andneutral are measured.
8.2.4 Checking binary input and output circuits
8.2.4.1 Checking binary input circuits
• Preferably, disconnect the binary input connector from the binary input cards.• Check all the connected signals so that both the input level and the polarity are in
accordance with the merging unit specifications.
Do not use AC voltage. Binary inputs are rated for DC voltage only.
8.2.4.2 Checking binary output circuits
• Preferably, disconnect the binary output connector from the binary outputcards.
• Check all connected signals so that both load and voltage are in accordance withthe merging unit specifications.
1MRS758406 B Section 8Commissioning
SMU615 75Operation Manual
8.3 Authorizations
8.3.1 User authorization
The user categories have been predefined for the WHMI via front port RJ-45 and rearport RJ-45, each with different rights and default passwords.
Passwords are settable for all predefined user categories. The WHMI password via thefront port RJ-45 must be at least four characters and the WHMI password via the rearport RJ-45 at least nine characters. The maximum number of characters is 8 for theWHMI front port password and 20 for the WHMI rear port password. Only thefollowing characters are accepted.
• Numbers 0-9• Letters a-z, A-Z• Space• Special characters !"#%&'()*+¡ä-./:;<=>?@[\]^_`{|}~
User authorization is disabled by default and can be enabled via theWHMI path Main Menu/Configuration/Authorization/Passwords.
Table 16: Predefined user categories and default passwords
Username Front panelWHMIpassword
Rear panelWHMI password
User rights
VIEWER 0001 remote0001 Only allowed to view
OPERATOR 0002 remote0002 Authorized to make operations
ENGINEER 0003 remote0003 Allowed to change merging unit parameters, butno operation rights
ADMINISTRATOR 0004 remote0004 Full access
For user authorization for PCM600, see PCM600 documentation.
Section 8 1MRS758406 BCommissioning
76 SMU615Operation Manual
8.4 Setting merging unit and communication
8.4.1 Setting communication between merging units and PCM600
The communication between the merging unit and PCM600 is independent of theused communication protocol within the substation or to the NCC. It can be seen as asecond channel for communication.
The media is always Ethernet and communication is based on TCP/IP.
Each merging unit has an Ethernet front connector for PCM600 access. Depending onthe station concept and the used station protocol, additional Ethernet interfaces maybe available on the rear side of the merging unit. All Ethernet interfaces can be usedto connect PCM600.
When an Ethernet based station protocol is used, the PCM600 communication can usethe same Ethernet port and IP address. The merging unit is able to separate theinformation belonging to the PCM600 dialog.
To configure the physical connection and the IP addresses:
1. Set up or get the IP addresses of the merging units.2. Set up the PC for a direct link or connect the PC or workstation to the network.3. Configure the IP addresses in the PCM600 project for each merging unit.
The addresses are used for communication between merging units and PCM600.
8.4.1.1 Communication link options between PCM600 and merging units
Two options are available for the connection of PCM600 to the merging unit.
• Direct point to point link between PCM600 and the merging unit• Indirect link via a station LAN or from remote via a network
Point to point linkThe merging unit is provided with an RJ-45 connector on the LHMI. The frontcommunication port is mainly used for configuration and setting purposes. The frontcommunication port should not be connected to any Ethernet network.
The merging unit has a DHCP server for the front interface. The DHCP server assignsan IP address to the computer connected to the front interface. The computer's LANinterface has to be configured to obtain the IP address automatically.
LAN or WAN networkIn TCP/IP networking, a LAN is often but not always implemented as a single IPsubnet. A router connects LANs to a WAN. In IP networking, the router maintainsboth a LAN address and a WAN address. Design considerations for computer
1MRS758406 B Section 8Commissioning
SMU615 77Operation Manual
networks cover a wide range of topics including layout, capacity planning, andsecurity. To some extent, the network configuration also depends on user preferences.
8.4.2 Communication settings
The merging unit is provided with an RJ-45 front port on the LHMI. This connectoris mainly used for configuration and setting purposes. The rear port IP address and thecorresponding subnet masks can be set via the WHMI. The front port uses a fixed IPaddress 192.168.0.254, and it also provides DHCP server to assign an IP address forthe connected computer. The rear Ethernet interface has a factory default IP address192.168.2.10 when the complete merging unit is delivered.
Different communication ports are available via optional communication modules.Ethernet RJ-45 and optical Ethernet LC are the two rear port Ethernet communicationoptions. Rear port Ethernet is intended for station bus communication.Communication protocols used via Ethernet ports are IEC 61850-8-1 and IEC61850-9-2 LE.
If the protocol does not operate as expected, check that other serialprotocols are not using the COM port.
Use the correct Ethernet connectors in the merging unit withredundant communication protocols like HSR and PRP. mergingunits with HSR/PRP support have three Ethernet connectors andredundant Ethernet ports are marked as LAN A and LAN B. The thirdEthernet port without any LAN marking works as an interlink port.Thus, an additional redundancy box is not needed. For example,laptops with PCM600 must be connected via a redundancy box toaccess a merging unit which is part of the HSR network.
The redundant communication module has three operation modes:“Normal”, “HSR” and “PRP”. The operation mode can be changedfrom communication settings.
For more information, see the communication protocol manuals andthe technical manual.
8.4.2.1 Defining Ethernet port settings
Change the Ethernet port settings primarily via PCM600 to ensure thatPCM600 is able to export a consistent configuration to SYS600.
Section 8 1MRS758406 BCommissioning
78 SMU615Operation Manual
Ethernet port settings are recommended to be changed only when thedevice is stand-alone and properly configured.
1. Click Configuration in the left navigation bar and select Communication.2. In the Ethernet submenu, define the Rear port settings.
• IP address• Subnet mask• Default gateway of the optional rear port Ethernet connector
3. Click Write to IED.
8.4.2.2 Setting communication protocol parameters
1. Click Configuration in the left navigation bar and select Communication.2. Change the protocol specific settings.
The possible settings to be changed are, for example, the selectedcommunication port, address and link mode.
8.4.3 Setting system time and time synchronization
1. Click Configuration in the left navigation bar and select Time.2. Select a submenu and edit the parameters.
• System time• Daylight saving time• Synchronization
3. Click Write to IED.
8.4.3.1 Setting daylight saving time
The merging unit can be set to determine the correct date for the DST shift every year.The UTC time is used to set the DST.
1. Set the DST on day (weekday) and DST off day (weekday) parameters to defineon which week day the time shift occurs.
2. Set the DST on date (day), DST on date (month) and DST off date (month)parameters to define on which month and week the time shift occurs.The DST on/off date must precede the selected DST on/off day and be within thesame week as the DST shift.
1MRS758406 B Section 8Commissioning
SMU615 79Operation Manual
Table 17: Possible date values for DST change on Sunday
Day of the DST shift DST on/off date (day)First Sunday of the month 1
Second Sunday of the month 8
Third Sunday of the month 15
Fourth Sunday of the month 22
Last Sunday, if the month has 30 days 24
Last Sunday, if the month has 31 days 25
For example, if the DST is observed from the last Sunday in March to the lastSunday in October and the time shift occurs at 01:00 UTC, the setting parametersare the following.
DST on time (hours): 2 h
DST on time (minutes): 0 min
DST on date (day): 25
DST on date (month): March
DST on day (weekday): Sunday
DST off time (hours): 1 h
DST off time (minutes): 0 min
DST off date (day): 25
DST off date (month): October
DST off day (weekday): Sunday
Set the DST on day (weekday) and DST off day (weekday) to"reserved" to determine the exact date and time for the DST shift.Repeat the setting yearly, as the time for the DST shift is not on thesame date every year.
To disable the DST, set the DST in use parameter to "False".
8.4.4 Setting merging unit parameters
8.4.4.1 Merging unit parametrization
Merging unit parameters are set via the WHMI or PCM600.
Setting parameters need to be calculated according to the electrical networkconditions and the electrical characteristics of the protected equipment. The mergingunit's settings need to be verified before the merging unit is connected to a system.
Section 8 1MRS758406 BCommissioning
80 SMU615Operation Manual
Document all changes to parameter settings.
For more information, see the PCM600 documentation.
8.4.4.2 Defining disturbance recorder channel settings
1. Click Configuration in the left navigation bar and select Disturbancerecorder.
2. Edit the Channel settings.
Each analog channel has an equal set of parameters and correspondingly, each binarychannel has an equal set of parameters.
8.4.4.3 Configuring analog inputs
• Click Configuration in the left navigation bar and select Analog inputs.• Edit the values.
• For CTs, the secondary current and primary current need to be set to thecorrect values.
• For VTs, the secondary voltage and primary voltage need to be set to thecorrect values.
8.5 Testing merging unit operation
The merging unit has to be in the test mode before the digital outputs and certainoutput signals of protection and other functions can be activated.
8.5.1 Selecting IED test mode
The test mode can be activated using the WHMI via the front port. The green ReadyLED is flashing to indicate that the test mode is activated. By default, the test mode canonly be changed from the WHMI via the front port. Activation by remote client ispossible, see the technical manual.
The Ready LED also flashes if the merging unit detects a diagnosticfailure. Check the test mode setting and the merging unit's IRF alarmcontact status to find the reason for the failure.
1MRS758406 B Section 8Commissioning
SMU615 81Operation Manual
The test mode is useful for simulated testing of functions and outputs withoutproviding current inputs.
1. Click Tests in the left navigation bar and select IED test.2. Click Enable Write.3. Edit the Test mode parameter.
• In the New Value list, select IED test.
GUID-D7290D1C-3914-4EF8-848E-1DF1CC5AED69 V1 EN
Figure 45: Entering test mode
4. Click Write to IED.
If the test mode is not cancelled, it remains on and the Ready LEDremains flashing.
8.5.2 Testing digital I/O interface
1. Click Tests in the left navigation bar and select, for example, Binary outputs.2. Select the module and output to be edited. For example, X100 (PSM) and X100-
PO1.3. Select the value to activate or deactivate the digital output.4. Click Write to IED.
If the optional BIO-module (X110) is included in the merging unit, themenu path could also be Main menu/Tests/Binary Outputs/X110(BIO)/<binary output>.
Section 8 1MRS758406 BCommissioning
82 SMU615Operation Manual
8.5.3 Testing functions
Activate or deactivate an output signal for protection or other function to test thefunction.
1. Click Tests in the left navigation bar and select Function tests.2. In the Current protection submenu, select the function block to be tested.3. Select the output signal to be activated or deactivated.4. To deactivate all output signals for the function, select reset and confirm the
selection.
8.5.4 Selecting internal fault test
The internal fault may be tested by using the WHMI via the front port. When enablingthe test, the internal fault output contact is activated, the green Ready LED is flashing.See the technical manual for the internal fault output contact location. The internalfault can only be activated by using the WHMI via the front port.
Differing from real internal fault situation, the other output contactsare not released and locked during the test. In other words, protectionfunctions can operate and trip the outputs when the internal fault istested.
1. Click Tests in the left navigation bar and select IED test.2. Click Enable Write.3. Edit the Internal fault test parameter.
• In the New Value list, select Test on.
1MRS758406 B Section 8Commissioning
SMU615 83Operation Manual
GUID-4050FBF7-980D-4A46-80D0-E8FC5C87A824 V1 EN
Figure 46: Internal fault test
4. Click Write to IED.
8.5.5 Selecting IED blocked or IED test and blocked mode
The IED blocked mode and the IED test and blocked mode can be activated by usingthe WHMI via the front port. The green Ready LED flashes to indicate that the IEDtest and blocked mode is activated. By default, the test mode can only be changed fromthe WHMI via the front port. Activation by remote client is possible, see the technicalmanual.
The Ready LED also flashes if the merging unit detects a diagnosticfailure. Check the test mode setting and the merging unit's IRF alarmcontact status to find the reason of the failure.
The test mode can be used for simulated testing of functions and outputs withoutproviding current inputs. The IED blocked mode can be used to block the physicaloutputs to the process.
1. Click Tests in the left navigation bar and select IED test.2. Click Enable Write.3. Edit the Test mode parameter.
• In the New Value list, select the test mode status.
Section 8 1MRS758406 BCommissioning
84 SMU615Operation Manual
GUID-75BF06BC-D55A-4CD5-9FF0-526E03743A41 V1 EN
Figure 47: Entering IED blocked or IED test and blocked mode
4. Click Write to IED.
If the IED blocked or IED test and blocked mode is not cancelled, itremains on and the Ready LED remains flashing.
8.6 ABB Product Data Registration
The ABB Product Data Registration feature traces composition changes in themerging unit's SW or HW. Traceability allows better support and maintenancepossibilities.
The PCM600 reads the changed data from the merging unit. Therefore a connectionto the merging unit must be established first. Composition data can be read withPCM600 by enabling LCT during PCM600 installation and activating collection inPCM600 from 'Lifecycle Handling' menu. For detailed information see PCM600online help.
The LCT composition changed report does not affect the functionalityof the merging unit.
The number of composition changes can be seen from the Composition changesparameter in Main Menu/Monitoring/IED status.
1MRS758406 B Section 8Commissioning
SMU615 85Operation Manual
86
Section 9 Glossary
100BASE-FX A physical medium defined in the IEEE 802.3 Ethernetstandard for local area networks (LANs) that uses fiberoptic cabling
100BASE-TX A physical medium defined in the IEEE 802.3 Ethernetstandard for local area networks (LANs) that usestwisted-pair cabling category 5 or higher with RJ-45connectors
AC Alternating currentACT 1. Application Configuration tool in PCM600
2. Trip status in IEC 61850CAT 5 A twisted pair cable type designed for high signal integrityCOMTRADE Common format for transient data exchange for power
systems. Defined by the IEEE Standard.CPU Central processing unitCSV Comma-separated valuesCT Current transformerDAN Doubly attached nodeDC 1. Direct current
2. Disconnector3. Double command
DHCP Dynamic Host Configuration ProtocolDPC Double-point controlDST Daylight-saving timeEEPROM Electrically erasable programmable read-only memoryEMC Electromagnetic compatibilityEthernet A standard for connecting a family of frame-based
computer networking technologies into a LANFIFO First in, first outFPGA Field-programmable gate arrayFTP File transfer protocolFTPS FTP SecureGOOSE Generic Object-Oriented Substation Event
1MRS758406 B Section 9Glossary
SMU615 87Operation Manual
HMI Human-machine interfaceHSR High-availability seamless redundancyHTTPS Hypertext Transfer Protocol SecureHW HardwareIEC International Electrotechnical CommissionIEC 61850 International standard for substation communication and
modelingIEC 61850-8-1 A communication protocol based on the IEC 61850
standard seriesIEC 61850-9-2 A communication protocol based on the IEC 61850
standard seriesIEC 61850-9-2 LE Lite Edition of IEC 61850-9-2 offering process bus
interfaceIED Intelligent electronic deviceIEEE 1686 Standard for Substation Intelligent Electronic Devices'
(IEDs') Cyber Security CapabilitiesIP address A set of four numbers between 0 and 255, separated by
periods. Each server connected to the Internet isassigned a unique IP address that specifies the locationfor the TCP/IP protocol.
IRF 1. Internal fault2. Internal relay fault
LAN Local area networkLC Connector type for glass fiber cable, IEC 61754-20LCP Liquid crystal polymerLCT Life cycle traceabilityLE Light EditionLED Light-emitting diodeLHMI Local human-machine interfaceMMS 1. Manufacturing message specification
2. Metering management systemNCC Network control centerOTP One-time passwordPA PolyamidePBT Polybutylene terephthalatePC 1. Personal computer
2. Polycarbonate
Section 9 1MRS758406 BGlossary
88 SMU615Operation Manual
PCM600 Protection and Control IED ManagerPRP Parallel redundancy protocolPTP Precision Time ProtocolRAM Random access memoryRJ-45 Galvanic connector typeRoHS Restriction of hazardous substancesROM Read-only memoryRTC Real-time clockSAN Single attached nodeSCL XML-based substation description configuration
language defined by IEC 61850SMT Signal Matrix tool in PCM600SMU615 Substation merging unitSMV Sampled measured valuesSTP Shielded twisted-pairSVG Scalable vector graphicsSW SoftwareTCP/IP Transmission Control Protocol/Internet ProtocolUTC Coordinated universal timeVT Voltage transformerWAN Wide area networkWHMI Web human-machine interfaceXRIO eXtended Relay Interface by OMICRON
1MRS758406 B Section 9Glossary
SMU615 89Operation Manual
90
91
ABB Distribution SolutionsDistribution AutomationP.O. Box 699FI-65101 VAASA, FinlandPhone +358 10 22 11
www.abb.com/mediumvoltagewww.abb.com/substationautomation
—
© Copyright 2019 ABB. All rights reserved. 1MR
S75
840
6 B