operating instructions for temperature sensor model: … · operating instructions for temperature...

28
Operating Instructions for Temperature Sensor Model: TWL Explosion Proof Protection Ex d

Upload: vodang

Post on 05-Jun-2018

229 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Operating Instructions for Temperature Sensor Model: … · Operating Instructions for Temperature Sensor Model: ... The requirements of Regulation 94/9 ... Due to the use of a flame

Operating Instructions

for

Temperature Sensor

Model: TWL

Explosion Proof Protection Ex d

Page 2: Operating Instructions for Temperature Sensor Model: … · Operating Instructions for Temperature Sensor Model: ... The requirements of Regulation 94/9 ... Due to the use of a flame

TWL

page 2 DT0454

1. Contents

1. Contents ........................................................................................................ 2 2. Note .............................................................................................................. 3 3. Instrument Inspection .................................................................................... 3 4. Regulation Use .............................................................................................. 3 5. Operating Principle ........................................................................................ 4 6. Electrical connection ..................................................................................... 4 7. Use in hazardous Areas ................................................................................ 5

7.1 Area of validity ..................................................................................... 5 7.2 Guidelines ............................................................................................ 5 7.3 General ................................................................................................ 6 7.4 Protection against E.S.D. (Electro Static Discharge) ........................... 6 6.5 Maintenance and repairs ......................................................................... 6 7.5 Storage ................................................................................................ 6

8. Description of the Factory Label.................................................................... 7 9. Installation in the classified area ................................................................... 8

9.1 Examples of installation in explosion-proof areas conform to the protection type “Ex d” ........................................................................... 8

10. Technical Details ........................................................................................... 9 10.1 Sensor wiring ....................................................................................... 9 10.2 General details ..................................................................................... 9 10.3 Materials .............................................................................................. 9 10.4 Process connection ............................................................................. 9 10.5 ATEX-approval .................................................................................. 10 10.6 Head transmitter ................................................................................ 10 10.7 Display ............................................................................................... 10

11. Dimensions ................................................................................................. 11 11.1 Sensors .............................................................................................. 11 11.2 Thermowells ...................................................................................... 12 11.3 Lagging extension at thermowell “T”. ................................................ 17

12. Order details ............................................................................................... 18 13. CE-Certificates ............................................................................................ 20 14. ATEX-Certificates ....................................................................................... 21 15. Notes ........................................................................................................... 25

Manufactured by:

Kobold Mesura S.L.U

C/Guifré 655 08918 Badalona

Tel.: +34 93 460 38 83 Fax: +34 93 460 38 76

E-Mail: [email protected] www.kobold.com

Edition August 2012

Page 3: Operating Instructions for Temperature Sensor Model: … · Operating Instructions for Temperature Sensor Model: ... The requirements of Regulation 94/9 ... Due to the use of a flame

TWL

DT0454 page 3

2. Note

Please read these operating instructions before unpacking and putting the unit in operation. Follow the instructions precisely as described herein. The devices are only to be used, maintained and serviced by persons familiar with these operating instructions and in accordance with local regulations applying to Health & Safety and prevention of accidents. When used in machines, the measuring unit should be used only when the machines fulfil the EWG-machine guidelines.

3. Instrument Inspection

Instruments are inspected before shipping and sent out in perfect condition. Should damage to a device be visible, we recommend a thorough inspection of the delivery packaging. In case of damage, please inform your parcel service / forwarding agent immediately, since they are responsible for damages during transit. Scope of delivery: The standard delivery includes: • Device model: TWL • Operating Instructions

4. Regulation Use

The temperature sensors of series TWL are suitable for all applications where processes involving fluids, solid bodies or materials, or gases, require temperature recording and measurement. Our temperature sensors are suitable for use in the following industrial areas: chemicals, petrochemicals, water, feed, food, sanitary, etc. Any use of the Temperature Sensor, model: TWL, which exceeds the manufacturer’s specification may invalidate its warranty. Therefore, any resulting damage is not the responsibility of the manufacturer. The user assumes all risk for such usage.

Page 4: Operating Instructions for Temperature Sensor Model: … · Operating Instructions for Temperature Sensor Model: ... The requirements of Regulation 94/9 ... Due to the use of a flame

TWL

page 4 DT0454

5. Operating Principle

Resistance thermometers work by using the continuous change of resistance of metals subject to temperature rising and decreasing. The most common resistance material used is platinum, as it is very stable and has very good repeatability. The temperature coefficient of platinum is positive, so its resistance increases as the temperature rises. This property is defined in the IEC751 standard, which defines measurements deviations categories A and B.

6. Electrical connection

1 x Pt100 2 wires 1 x Pt100 3 wires 1 x Pt100 4 wires 2 x Pt100 2 wires 2 x Pt100 3 wires

Note: For electrical connection of transmitter please refer to their separate manual

Page 5: Operating Instructions for Temperature Sensor Model: … · Operating Instructions for Temperature Sensor Model: ... The requirements of Regulation 94/9 ... Due to the use of a flame

TWL

DT0454 page 5

7. Use in hazardous Areas

7.1 Area of validity These security instructions apply to TWL Series temperature sensors and their accessories for use in explosion-proof atmospheres conform to CE certificate LOM 08ATEX2016 X 7.2 Guidelines The TWL Series temperature measuring instruments work according to the heat resistance measuring principle. This measuring principle acts to check and measure the temperature also in explosion-proof areas. TWL devices can be with a standard 4 to 20 mA signal transmitter, Hart protocol, Profibus/Fieldbus or with direct access to the sensor. They are appropriate for use in Group IIC and Categories 2G/D explosion-proof atmospheres. The sensor element can be installed in Category 2 explosion-proof areas in accordance with Certification 2G Ex d. The mechanical connecting element to the process can be installed in Category 2 explosion-proof areas, conform to Certification 2G Ex d. Devices labelled “Ex d” which have a mechanical separating element, such as a thermowell, are approved for Zone 0/20 to Zone 1/21, when using a sensor certified as 2GD. The temperature class and/or the surface temperature relates solely to a device operated at ambient temperature. On installation the actual temperature class for process operation has to be determined. The inlet bushings used must conform to the certification for their type in accordance with the directive.

The requirements of Regulation 94/9/CE, and the applicable national regulations for the use of measuring instruments in explosion-proof areas, such as EN 60079-0:2011, EN 60079-1:2004, EN 61241-0:2006, EN 61241-1:2004 and other regulations relating to this certification type, must be fulfilled. Only qualified specialist personnel may install devices in explosion-proof areas.

Page 6: Operating Instructions for Temperature Sensor Model: … · Operating Instructions for Temperature Sensor Model: ... The requirements of Regulation 94/9 ... Due to the use of a flame

TWL

page 6 DT0454

7.3 General • When installing the sensor it is necessary to follow all the instructions and

regulations for explosion-proof areas and the safety instructions included in these instructions.

• Make sure that the details on the sensor’s type label correspond to the working conditions for the application.

• When installing the device, make sure you do not create any mechanical deformation as a result of solder spots or the application of mechanical force.

• Important: Make sure there is an electrical connection between the device’s earth and the earth of the system.

• Make sure the lid are closed before putting the device into operation.

• Before re-opening the lid, remove the plug from the mains or de-energise the device and make sure there is no danger of explosion.

• Only use cable glands according norms for Ex d protection.

• Important: Due to the use of a flame path and its fit tolerance it is not

permissible to use standard measuring inserts as spare parts 7.4 Protection against E.S.D. (Electro Static Discharge) Temperature sensors with plastic parts that can become electrically charged bear a warning label. Electrical charging must be avoided at all costs. Pay attention to the following: - Avoid rubbing the device - Never clean the device dry - Do not install the device near material airflows or near steam outlets 6.5 Maintenance and repairs The instrument does not require maintenance or servicing. Repairs must be only carried out by Kobold Mesura ( manufacturer ) 7.5 Storage Measuring instruments should be protected against humidity and dust. Storage temperature: -40ºC….+85ºC for sensors without transmitter. Storage temperature: See manual of the corresponding transmitter and display model.

Page 7: Operating Instructions for Temperature Sensor Model: … · Operating Instructions for Temperature Sensor Model: ... The requirements of Regulation 94/9 ... Due to the use of a flame

TWL

DT0454 page 7

8. Description of the Factory Label

Page 8: Operating Instructions for Temperature Sensor Model: … · Operating Instructions for Temperature Sensor Model: ... The requirements of Regulation 94/9 ... Due to the use of a flame

TWL

page 8 DT0454

9. Installation in the classified area

9.1 Examples of installation in explosion-proof areas conform to

the protection type “Ex d”

Hazardous area Safe area

Page 9: Operating Instructions for Temperature Sensor Model: … · Operating Instructions for Temperature Sensor Model: ... The requirements of Regulation 94/9 ... Due to the use of a flame

TWL

DT0454 page 9

10. Technical Details

10.1 Sensor wiring

- 2 wires Error due to the lead resistance of the sensor - 3 wires With connecting wires up to 25 m, lead resistance is negligible. - 4 wires The lead resistance of the connecting wires is negligible

10.2 General details

Ambient temperature: -40…+150ºC with ceramic terminal base -40… +85ºC with transmitter -20…..+70ºC with LCD display -20…..+80ºC with led display Meas. Range: -30…..+550ºC

-80…..+600ºC ( Other on request )

Operating pressure: 250 bar ( depending on thermowell ) Connection head: form XD ( IP54÷IP68 depending on cable gland and

sealing “not included” M20 x 1,5mm )

10.3 Materials Sensor: Stainless steel 1.4404 ( others on request ) Thermowell: Stainless steel 1.4404 ( others on request ) Neckpipe: Stainless steel 1.4404 ( others on request ) Connection head: Aluminium, painted Terminal base: Ceramic ( without transmitter )

10.4 Process connection Thread: G1/2” , G3/4, G1”, ½” NPT, ¾” NPT, 1” NPT Din-flange: DN 15, 20, 25, 32, 40, 50 Ansi flange: ½”, ¾”, 1”, 1 ½”, 2“ Weld-in: ¾”, 1”, 1 ¼”

Page 10: Operating Instructions for Temperature Sensor Model: … · Operating Instructions for Temperature Sensor Model: ... The requirements of Regulation 94/9 ... Due to the use of a flame

TWL

page 10 DT0454

10.5 ATEX-approval

II 2 GD Exd IIC T6 / Ex tD A21 IP65 T85 ºC

10.6 Head transmitter - Output: analogue output 4…20 mA - Communication: HART®-protocol

PROFIBUS®/Fieldbus - Minimum meas. span: standard transmitter 25ºK transmitter with HART® 10ºK transmitter with PROFIBUS®/Fieldbus 5ºK

- Supply voltage: 8…35 Vdc for standard transmitter and transmitter with Hart

9…32 Vdc for transmitter with PROFIBUS®/Fieldbus

10.7 Display - Only for 4..20 mA or Hart transmitters. - Type: 4 digit LCD or LED - Supply: loop powered - Voltage drop out: LCD max. 2,5 Vdc LED 3,3 V at 4 mA 3,7 V at 20 mA Note For programming of transmitter and display please refer to their separate programming manuals.

Page 11: Operating Instructions for Temperature Sensor Model: … · Operating Instructions for Temperature Sensor Model: ... The requirements of Regulation 94/9 ... Due to the use of a flame

TWL

DT0454 page 11

11. Dimensions

11.1 Sensors Dimensions Temperature Sensor TWL-1 Dimensions Temperature Sensor TWL-2

HL: Neckpipe length 130 mm TWL-1 ( other on request ) U: Immersion length thermowell ( see drawing thermowell ) 150 mm TWL-2 ( other on request ) H: Length thermowell ( see drawing thermowell )

LN: Screw-in-length by hand ( approx. 8,1 mm at ½”NPT ) EL: Immersion length EL : U+H-7 mm for thermowell type B EL : U+H-8 mm for thermowell type G and D Measuring Insert TWL-3 Dimensions Connection Head with Display

IMPORTANT!! * Due to the use of a flame path and its fit tolerance it is no permissible to use standard measuring inserts as spare parts.

Page 12: Operating Instructions for Temperature Sensor Model: … · Operating Instructions for Temperature Sensor Model: ... The requirements of Regulation 94/9 ... Due to the use of a flame

TWL

page 12 DT0454

11.2 Thermowells Dimensions Thermowell Model TWL-…B… Nominal pressure: max. PN25 at 400ºC Cylindrical thermowell, welded, with process connection G-thread

Nominal pressure: max. PN25 at 400ºC Cylindrical thermowell, welded, with process connection NPT- thread

Process Connection

Max. Total length AF F i d H L Q

G-thread 5000 mm

27 G ½ B 10 12

36 14 26 12 14

32 G ¾ B 10 12

38 16 31.7 12 14

41 G 1 B 10 12

40 18 39 12 14

Process Connection

Max. Total length AF F i d H L

NPT-thread 5000 mm

24 ½ NPT

10 12 42 17

12 14

27 ¾ NPT

10 12 43 18

12 14

36 1 NPT

10 12 46 21

12 14

Page 13: Operating Instructions for Temperature Sensor Model: … · Operating Instructions for Temperature Sensor Model: ... The requirements of Regulation 94/9 ... Due to the use of a flame

TWL

DT0454 page 13

Nominal pressure: max. PN6..40 at 400ºC Cylindrical thermowell, welded, with process connection flange acc. DIN or ANSI

Dimensions Thermowell Model TWL-…G…

Nominal pressure: max.PN100 at 400ºC Cylindrical thermowell out of solid material with stepped shaft and process connection G-thread

Process connection

Max. Total Length F i d H e

With flange

ANSI ½”

5000mm

½” NPT

10/12 12/14 40 30 ANSI ¾” ½ NPT

ANSI 1” ¾ NPT ANSI 1” ½ 1 NPT 35 ANSI 2” 1 NPT DIN DN 15 ½ NPT

10/12 12/14 40

30 DIN DN 20 ½ NPT DIN DN 25 ¾ NPT DIN DN 32 1 NPT

35 DIN DN 40 1 NPT DIN DN 50 1 NPT

Process Connection

Max. Total Length AF F i d D H L Q

G-thread 1000mm

27 G ½ B 7-8-9 15 17.5

46 20

26 10-12 17,5 17,5

36 G ¾ B 7-8-9 15 18

31.7 10-12 18 21

41 G 1 B 7-8-9 15 21

51 39 10-12 18 25

Page 14: Operating Instructions for Temperature Sensor Model: … · Operating Instructions for Temperature Sensor Model: ... The requirements of Regulation 94/9 ... Due to the use of a flame

TWL

page 14 DT0454

Nominal pressure: max. PN100 at 400ºC Cylindrical thermowell out of solid material withstepped shaft and process connection NPT-thread

Nominal pressure: as flange rating ( max. PN100 at 400ºC ) Cylindrical thermowell out of solid material with stepped shaft and process connection flanges acc. DIN or ANSI

Process Connection

Max. Total Length AF F i d D H L

NPT-thread 1000mm

24 ½ NPT 7-8-9 15 17.5

46 20 10-12 17,5 17,5

27 ¾ NPT 7-8-9 15 18

10-12 18 21

36 1 NPT 7-8-9 15 21

51 25 10-12 18 25

Process Connection

Max.total Length F i d D H e

Flange

ANSI ¾”

1000mm

½ NPT 7-8-9 15 17.5

60

30 10-12 17,5 17,5

ANSI 1” ¾ NPT 7-8-9 15 18

10-12 18 21

ANSI 1 ½” 1 NPT 7-8-9 15 21

35 10-12 18 25

ANSI 2” 1 NPT 7-8-9 15 21

10-12 18 25

DIN DN 20 ½ NPT 7-8-9 15 17.5

60

30 10-12 17,5 17,5

DIN DN 25 ¾ NPT 7-8-9 15 18

10-12 18 21

DIN DN 32 1 NPT 7-8-9 15 21

35

10-12 18 25

DIN DN 40 1 NPT 7-8-9 15 21

10-12 18 25

DIN DN 50 1 NPT 7-8-9 15 21

10-12 18 25

Page 15: Operating Instructions for Temperature Sensor Model: … · Operating Instructions for Temperature Sensor Model: ... The requirements of Regulation 94/9 ... Due to the use of a flame

TWL

DT0454 page 15

Nominal pressure: PN100 at 400ºC Cylindrical thermowell out of solid material with stepped shaft and process connection for weld-on

Dimensions Thermowell Model TWL-…D…

Nominal pressure: PN250 at 400ºC Conical thermowell out of solid material with process connection G-thread

Nominal pressure: PN250 at 400ºC

Process Connection

Max. Total Length F i d D H

For weld-on

DN ¾”

1000mm

26,9 7-8-9 15

19 46 10-12 18

DN 1” 33.4 7-8-9 15

22 51 10-12 18

Process Connection

Max. Total Length AF F i d D H L Q

G-thread 1000mm

36 G ¾ B 7-8-9 18

23 46 20 31.7 10-12 21

41 G 1 B 7-8-9 18

29 51 25 39 10-12 21

Page 16: Operating Instructions for Temperature Sensor Model: … · Operating Instructions for Temperature Sensor Model: ... The requirements of Regulation 94/9 ... Due to the use of a flame

TWL

page 16 DT0454

Conical thermowell out of solid material with process connection NPT-thread

Process Connection

Max. Total Length AF F i d D H L

NPT-thread 1000mm

27 ¾ NPT 7-8-9 18

23 46 20 10-12 21

36 1 NPT 7-8-9 18

29 51 25 10-12 21

Nominal pressure: as flange rating ( max. PN250 at 400ºC ) Conical thermowell out of solid material with process connection flange acc, DIN or ANSI

Nominal pressure: PN250 at 400ºC

Process Connection

Max. Total Length F i d D H e

Flange

ANSI 1”

1000mm

¾ NPT 7-8-9 18 23

60

30 10-12 21

ANSI 1 ½” 1 NPT 7-8-9 18

29 35 10-12 21

ANSI 2” 1 NPT 7-8-9 18 10-12 21

DIN DN 25 ¾ NPT 7-8-9 18 23

60

30 10-12 21

DIN DN 32 1 NPT 7-8-9 18

29 35

10-12 21

DIN DN 40 1 NPT 7-8-9 18 10-12 21

DIN DN 50 1 NPT 7-8-9 18 10-12 21

Page 17: Operating Instructions for Temperature Sensor Model: … · Operating Instructions for Temperature Sensor Model: ... The requirements of Regulation 94/9 ... Due to the use of a flame

TWL

DT0454 page 17

Conical thermowell out of solid material with process connection flange acc. DIN or ANSI

11.3 Lagging extension at thermowell “T”.

In case of ordering with lagging extension at thermowell please see drawing and specify length “T” ( total length is “T”+”H” ). “H” is fix.

Process Connection

Max. Total Length i d D H

For weld-on

DN 1”

1000mm

7-8-9 18 33.4 51

10-12 21

DN 1 ¼” 7-8-9 18

38.1 51 10-12 21

Page 18: Operating Instructions for Temperature Sensor Model: … · Operating Instructions for Temperature Sensor Model: ... The requirements of Regulation 94/9 ... Due to the use of a flame

TWL

page 18 DT0454

12. Order details

Order Details (example: TWL-113LGBG4AA0)

Model Sensor specification

Sensor type Sensor type/cat. Sensor wiring Connection head/transmitter Sensor connection

TWL-

0 = without 0 = without 0 = without 0 = without

N2)=1/2” NPT male G= G1/2” male X= special

1= standard 2= with nipple and union

1= 1 x Pt100 cat B -30…+550ºC 2= 1 x Pt100 cat B -30…+550ºC 3= 1 x Pt100 cat B -80…+660ºC 4= 1 x Pt100 cat B -80…+660ºC 5= 1 x Pt100 cat A -30…+550ºC 6= 1 x Pt100 cat A -30…+550ºC 7= 1 x Pt100 cat A -80…+660ºC 8= 1 x Pt100 cat A -80…+660ºC X= special

2= 2-wire 3= 3-wire 41)= 4-wire

L= Atex Exd without transmitter A= Atex Exd with programmable 2-wire Transmitter B= Atex Exd with 2-wire transmitter HART® protocol C= Atex Exd with transnmitter Profibus®/ Fieldbus

3= measuring insert

0= without

Order Details continued:

Thermowell specification Length ( meas. Insert, sensor, thermowell )4)

Special option Thermowell type Process

connection Process

connection size Nominal pressure6)

( process connection ) 0 = without 0 = without 0 = without 0 = without

Only for TWL-0 ( only thermowell )

0 = without lagging extension “T” 1 = with lagging extension “ T “

Sensor with thermowell ( only for TWL-1/TWL-2 )

A = with standard neckpipe “HL” and without lagging extension “T” B = with standard neckpipe “HL” and with lagging extension “T“ C5) = without neckpipe “HL” and with lagging extension “T“ D5) = without neckpipe “HL” and without lagging extension “T“ E = with special neckpipe “HL“ length and with lagging extension “T“ F = with special neckpipe length “HL” and without lagging extension “T”

Sensor without thermowell ( only TWL-1/TWL-2 )

G = with standard neckpipe “HL” H = with special neckpipe “HL” J = without neckpipe length “HL” X = special option ( specify in clear text )

Only TWL-3 M = measuring insert ( only for TWL-3, specify length “ML” )

0 = without 16) = with LCD display 26) = with led display Y = special option ( specify in clear text )

B = cylindrical, multipart, welded G = cylindrical, bar stock/drilled with stepped shank D = tapered shank, bar stock/drilled X = special option

G = G-thread

4 = 1/2” ( not for thermowell type D ) 5 = 3/4" 6 = 1 “ Y= special

A = PN25 ( only for thermowell type B ) B = PN100 ( only for thermowell type G ) C = PN250 ( only for thermowell type D )

N = NPT-thread

4 = 1/2" ( not for thermowell type D ) 5 = 3/4” 6= 1” Y = special

A = PN25 ( only for thermowell type B ) B = PN100 ( only for thermowell type G ) C = PN250 ( only for thermowell type D )

S3) = welded

5 = 3/4" ( only for thermowell type G ) 6 = 1” 7 = 1 1/4" ( only for thermowell type D ) Y = special

B = PN100 ( only for thermowell type G ) C = PN250 ( only for thermowell type D )

F = DIN flange

4 = DN15 5 = DN20 6 = DN25 7 = DN32 8 = DN40 9 = DN50 Y = special

1 = PN6 2 = PN16 3 = PN40 4 = PN100 Y = special

A = ANSI flange

4 = 1/2" 5 = 3/4" 6 = 1” 8 = 1 1/2" 9 = 2” Y = special

5 = 150 lbs 6 = 300 lbs 7 = 600 lbs 8 = 900 lbs ( not for 1/2" ) 9 = 1500 lbs ( not for 1/2" ) Y = special

Page 19: Operating Instructions for Temperature Sensor Model: … · Operating Instructions for Temperature Sensor Model: ... The requirements of Regulation 94/9 ... Due to the use of a flame

TWL

DT0454 page 19

1) 4-wire only for 1 sensor 2) choose N for TWL-2 3) not for thermowell type B 4) immersion length “U“ and hole dia. “i“ (when ordering a/with thermowell) or “EL“ (when ordering without thermowell), neckpipe length “HL“ (when different from stdd. i.e. for TWL-1 stdd. Is 130 mm, for TWL-2 standard is150 mm), lagging extension “T“ (when ordering) and measuring insert length “ML“ (when ordering TWL-3) must be specified in clear text when ordering. Pls. check lengths very precisely in order to ensure a perfect match between sensor and thermowell. 5) not for TWL-2 6) display only available for 4...20 mA or Hart transmitters. NOTE: Nominal pressure for TWL-3 and sensors without thermowell is atmospheric pressure. Order Details for ordering only the thermowell (example: TWL-0000NBG4A00)

Model Sensor specification

Sensor type Sensor type/cat. Sensor wiring Connection head/transmitter Sensor connection

TWL-

0 = without 0 = without 0 = without 0 = without

N1)=1/2” NPT male G= G1/2” male X= special

1) choose N for TWL-2 Order Details for ordering only the thermowell continued:

Thermowell specification Length ( meas. Insert, sensor, thermowell )1)

Special option Thermowell type Process

connection Process

connection size Nominal pressure (

process connection ) Please use the specification codes according to order table shown on page 16

0 = without lagging extension “T” 1 = with lagging extension “T”

0 = without Y = special option ( specify in clear text )

1) immersion length “U“ , hole dia. “i“ and lagging extension “T“ must be specified in clear text when ordering. Pls. check lengths very precisely in order to ensure a perfect match between sensor and thermowell.

Page 20: Operating Instructions for Temperature Sensor Model: … · Operating Instructions for Temperature Sensor Model: ... The requirements of Regulation 94/9 ... Due to the use of a flame

TWL

page 20 DT0454

13. CE-Certificates

DECLARACIÓN DE CONFORMIDAD CE EC DECLARATION OF CONFORMITY

EG-KONFOMITÄTSERKLÄRUNG DÉCLARATION DE CONFORMITÉ

DICHIARAZIONE DI CONFORMITÀ CE

KOBOLD MESURA SLU Guifré, 655 08918 Badalona (España)

Declara, bajo la propia responsabilidad, que el producto Declares under our sole responsibility, that the product Erklärt in alleiniger Verantwortung, daß das produkt Déclare sous sa seule responsabilité, que le produit Dichiara sotto la propia responsabilità, che il prodotto TWL-1……. TWL-2……. A los cuales se refiere esta declaración, son conformes a las siguiente Directivas Europeas: To which this declaration relates is in conformity with the following European Directives: An auf das diese Erklärung verweist, sie mit den Europäischen Richtlinien im Einklang stehen folgend: À auxquels se réfère cette déclaration, ils sont conformes aux Directives Européennes suivant : A ai quali si riferisce questa dichiarazione, sono conformi alle direttive europee seguente:

EMC89/336/CE Directiva Ex 94/9/EC Normas armonizadas y documentos de la normativa aplicados: Applied harmonised standards and normative documents: Angewandte harmonisierte Normen oder normativer Dokumente: Normes harmonisées et documents normatifs appliqués Norme armonizzate e documenti normativi applicati: EN 61010-1 :2001 EN 60079-1:2004 (acc.EN 60079-1:2005) EN 61241-0:2006 EN 61000-6-2 :2006 EN 61241-1:2004 (acc. EN 61241-1:2005) EN 60079-0:2006 Certificado de examen CE de tipo Marcado EC-type examination certificate Marking EG-baumusterprübescheinigung Markierung Attestation d´examen CE de type Inscription Certificazione per esame di tipo CE Marcatura

LOM 08ATEX2016 X II 2 GD Exd IIC T6 / Ex tD A21 IP65 T85 ºC Fabricado en: KOBOLD MESURA SLU C/ Guifré, 655 08918 BADALONA (Spain) Made in: Hergesteltlt in: Fabriqué dans: Fabbricato in: Organismo notificado : LOM 0163 Número notificación : LOM 05ATEX9070 Notified organism Number notification Mitgeteilter Organismus Zahlmitteilung Organization annoncée Nombre notification Organismo informato Notifica di numero Badalona Junio 2012 Gerente Antonio Sánchez Tomás

Page 21: Operating Instructions for Temperature Sensor Model: … · Operating Instructions for Temperature Sensor Model: ... The requirements of Regulation 94/9 ... Due to the use of a flame

TWL

DT0454 page 21

14. ATEX-Certificates

Page 22: Operating Instructions for Temperature Sensor Model: … · Operating Instructions for Temperature Sensor Model: ... The requirements of Regulation 94/9 ... Due to the use of a flame

TWL

page 22 DT0454

Page 23: Operating Instructions for Temperature Sensor Model: … · Operating Instructions for Temperature Sensor Model: ... The requirements of Regulation 94/9 ... Due to the use of a flame

TWL

DT0454 page 23

Page 24: Operating Instructions for Temperature Sensor Model: … · Operating Instructions for Temperature Sensor Model: ... The requirements of Regulation 94/9 ... Due to the use of a flame

TWL

page 24 DT0454

Page 25: Operating Instructions for Temperature Sensor Model: … · Operating Instructions for Temperature Sensor Model: ... The requirements of Regulation 94/9 ... Due to the use of a flame

TWL

DT0390 page 25

15. Note

Page 26: Operating Instructions for Temperature Sensor Model: … · Operating Instructions for Temperature Sensor Model: ... The requirements of Regulation 94/9 ... Due to the use of a flame

TWL

page 26 DT0390

Page 27: Operating Instructions for Temperature Sensor Model: … · Operating Instructions for Temperature Sensor Model: ... The requirements of Regulation 94/9 ... Due to the use of a flame

TWL

DT0390 page 27

Page 28: Operating Instructions for Temperature Sensor Model: … · Operating Instructions for Temperature Sensor Model: ... The requirements of Regulation 94/9 ... Due to the use of a flame

KOBOLD MESURA S.L.U C/Guifré 655 08918 Badalona Tel.: +34 93 460 38 83 Fax: +34 93 460 38 76 E-Mail: [email protected] www.kobold.com

Technical data Subject to change without prior notice