omt software user manual

28
User Manual Operation/Maintenance Terminal OMT Software Netop Technology Co., Ltd Tel: +86 21 6921 4567 B2, No.303 XinKe Rd, Qingpu Industrial Zone, Fax: +86 21 6921 3655 Shanghai, China P.C: 201707 www.netop-technology.com User Manual (Operation/Maintenance Terminal OMT Software ) Manual Version 1.1 No part of this documentation may be excerpted, reproduced, translated, annotated or duplicated. In any form or by any means without the prior written permission of Netop Technology Co., Ltd Copyright © 2009 Netop Technology Co., Ltd. All rights reserved.

Upload: ha-vy-tran-thanh

Post on 20-Apr-2015

196 views

Category:

Documents


3 download

TRANSCRIPT

Page 1: OMT Software User Manual

User Manual Operation/Maintenance Terminal OMT Software

Netop Technology Co., Ltd Tel: +86 21 6921 4567 B2, No.303 XinKe Rd, Qingpu Industrial Zone, Fax: +86 21 6921 3655 Shanghai, China P.C: 201707 www.netop-technology.com

User Manual

(Operation/Maintenance Terminal OMT Software)

Manual Version 1.1

No part of this documentation may be excerpted, reproduced, translated, annotated or duplicated.

In any form or by any means without the prior written permission of Netop Technology Co., Ltd

Copyright © 2009 Netop Technology Co., Ltd. All rights reserved.

Page 2: OMT Software User Manual

User Manual Operation/Maintenance Terminal OMT Software

Netop Technology Co., Ltd Tel: +86 21 6921 4567 B2, No.303 XinKe Rd, Qingpu Industrial Zone, Fax: +86 21 6921 3655 Shanghai, China P.C: 201707 www.netop-technology.com

- 1 -

Contents Hardware and Software Requirements ..................................................3

Chapter 1 .................................................................................................4

OMT Introduction ....................................................................................4

General Introduction ..................................................................... 4 Connecting Methods....................................................................................4 Functions ..................................................................................................4

Main Menu of OMT Software........................................................... 5 Menu Bar:Configuration .............................................................................5

Menu Bar:Tools ........................................................................................5

Menu Bar:Help .........................................................................................5

OMT Interface .............................................................................. 6

Chapter 2 .................................................................................................7

OMT Install & Remove.............................................................................7

OMT Install................................................................................................7 OMT Remove .............................................................................................8

Chapter 3 .................................................................................................9

Configuration management (System Operation CM).............................9

Set Communication/Local check ...................................................................9 Set Communication/Modem check .............................................................. 10 Com Port Configuration ............................................................................. 10 Establishing Remote Connection ................................................................. 10

Chapter 4 ...............................................................................................12

Device Operation ...................................................................................12

Device Create .............................................................................12 Get MOID From Device.............................................................................. 12 User Configuration.................................................................................... 13

Configuring the Device .................................................................14 The scope of monitoring items: .................................................................. 14 Monitoring parameters interface description ................................................. 15

Page 3: OMT Software User Manual

User Manual Operation/Maintenance Terminal OMT Software

Netop Technology Co., Ltd Tel: +86 21 6921 4567 B2, No.303 XinKe Rd, Qingpu Industrial Zone, Fax: +86 21 6921 3655 Shanghai, China P.C: 201707 www.netop-technology.com

- 2 -

Chapter 5 ...............................................................................................19

Fault Management (FM)........................................................................19

Alarm Monitor Window .............................................................................. 19

Chapter 6 ...............................................................................................21

Upgrade..................................................................................................21

Upgrade Firmware By Local Mode ............................................................... 21 Upgrade Memmap by Local Mode................................................................ 22

Chapter 7 ...............................................................................................24

Others ....................................................................................................24

Alarm Level Configuration.......................................................................... 24 Cmcc Packet Analyzer ............................................................................... 25 Version information .................................................................................. 26

Page 4: OMT Software User Manual

User Manual Operation/Maintenance Terminal OMT Software

Netop Technology Co., Ltd Tel: +86 21 6921 4567 B2, No.303 XinKe Rd, Qingpu Industrial Zone, Fax: +86 21 6921 3655 Shanghai, China P.C: 201707 www.netop-technology.com

3

Hardware and Software Requirements

• Supported Operating Systems: Windows XP ; Windows Server 2003; Windows Server

2008; Windows Vista

• Processor: 1GHz Pentium processor or equivalent (Minimum); 2GHz Pentium processor or

equivalent (Recommended)

• RAM: 256 MB (Minimum); 1GB (Recommended)

• Hard Disk: Up to 500 MB of available space may be required ; 1GB (Recommended)

• DVD Drive: required

• Display: 1024 x 768 high color, 16-bit (Minimum); 1280 x 1024 high color, 32-bit

(Recommended)

Page 5: OMT Software User Manual

User Manual Operation/Maintenance Terminal OMT Software

Netop Technology Co., Ltd Tel: +86 21 6921 4567 B2, No.303 XinKe Rd, Qingpu Industrial Zone, Fax: +86 21 6921 3655 Shanghai, China P.C: 201707 www.netop-technology.com

4

C h a p t e r 1

OMT Introduction

General Introduction Connecting Methods

1. Local Communication via RS232-cable.

2. Remote Communication via Modem (Short Message).

Functions

1. Control Functions : Parameters of devices can be configured via local or remote

communication.

2. Search Functions:Current parameter settings and alarm setting can be displayed.

3. Alarm Functions:Active alarms can send back to control center (OMT)

Laptop with

OMT

software

Modem and cable

External Antenna

MU Site-A

MU Site-B

MU Site-C

Network(SMS)

Page 6: OMT Software User Manual

User Manual Operation/Maintenance Terminal OMT Software

Netop Technology Co., Ltd Tel: +86 21 6921 4567 B2, No.303 XinKe Rd, Qingpu Industrial Zone, Fax: +86 21 6921 3655 Shanghai, China P.C: 201707 www.netop-technology.com

5

Main Menu of OMT Software Menu Bar:Configuration

1. MOID List Config: To define the parameters of the monitoring equipment.

2. Alarm Level Config: To define the level of alarm items.

Menu Bar:Tools

1. Upgrade Firmware: To upgrade firmware by local communication.

2. Upgrade Memmap: To upgrade memmap by local communication.

3. Packet Analyzer: To analyze the data sent and received.

Menu Bar:Help

1. About: To display version of OMT and something about corporation.

Page 7: OMT Software User Manual

User Manual Operation/Maintenance Terminal OMT Software

Netop Technology Co., Ltd Tel: +86 21 6921 4567 B2, No.303 XinKe Rd, Qingpu Industrial Zone, Fax: +86 21 6921 3655 Shanghai, China P.C: 201707 www.netop-technology.com

6

OMT Interface

Menu Bar

Monitoring parameter list of the main interface

Alarm Monitor

Data Send & Receive

Device Info.

Communication Mode

Page 8: OMT Software User Manual

User Manual Operation/Maintenance Terminal OMT Software

Netop Technology Co., Ltd Tel: +86 21 6921 4567 B2, No.303 XinKe Rd, Qingpu Industrial Zone, Fax: +86 21 6921 3655 Shanghai, China P.C: 201707 www.netop-technology.com

7

C h a p t e r 2

OMT Install & Remove

OMT Install

1. Double click the Setup.exe file in OMT installation folder

2. OMT installation interface ->Select path ->Click Next 3. Continuously click Next 4. Click Close and OMT installation finished

Page 9: OMT Software User Manual

User Manual Operation/Maintenance Terminal OMT Software

Netop Technology Co., Ltd Tel: +86 21 6921 4567 B2, No.303 XinKe Rd, Qingpu Industrial Zone, Fax: +86 21 6921 3655 Shanghai, China P.C: 201707 www.netop-technology.com

8

OMT Remove

1. Select program-Netop -> Uninstall OMT

2. OMT remove interface -> Select Yes

Page 10: OMT Software User Manual

User Manual Operation/Maintenance Terminal OMT Software

Netop Technology Co., Ltd Tel: +86 21 6921 4567 B2, No.303 XinKe Rd, Qingpu Industrial Zone, Fax: +86 21 6921 3655 Shanghai, China P.C: 201707 www.netop-technology.com

9

C h a p t e r 3

Configuration management (System Operation CM)

Set Communication/Local check

1. Communication Port:Select the correct port number

2. Communication Speed:Default: 9600

3. Communication Mode:Select RS232

4. Communication Timeout:30 Sec.

1. R Switch: To refresh the serial port

2. Start: To establish connection between the computer and devices.

3. Stop: To terminate connection between computer and devices.

Page 11: OMT Software User Manual

User Manual Operation/Maintenance Terminal OMT Software

Netop Technology Co., Ltd Tel: +86 21 6921 4567 B2, No.303 XinKe Rd, Qingpu Industrial Zone, Fax: +86 21 6921 3655 Shanghai, China P.C: 201707 www.netop-technology.com

10

Set Communication/Modem check

1. Communication Port:Select the correct port number

2. Communication Speed:Default: 9600

3. Communication Mode:Select SMS

4. Communication Timeout:60 Sec.

Com Port Configuration

Note: Communication Port represents to the serial port used by the computer. Usually, serial port

of the computer’s default setting is COM 1

For the latest laptop, which is not equipped with serial port, we have to create the serial

port by USB-Serial conversion cable. In this condition, the COM port will not be COM1,

but COM5 or COM6 etc.

Establishing Remote Connection

1. Connect a wireless modem to the computer of control center.

2. Login to the main screen of the OMT. Choose SMS

Page 12: OMT Software User Manual

User Manual Operation/Maintenance Terminal OMT Software

Netop Technology Co., Ltd Tel: +86 21 6921 4567 B2, No.303 XinKe Rd, Qingpu Industrial Zone, Fax: +86 21 6921 3655 Shanghai, China P.C: 201707 www.netop-technology.com

11

3. Create a new device:

Enter the SIM card number inside the device’s modem in Device Phone column and

then Set the site ID.

4. Set Remote Communication Setup:

Enter the SIM card number of the modem that will be connected with the laptop in

Control Center Phone No.1~ 5 (You can set Phone2~5 or not).

Choose Short Message as Remote Communication Mode, and then Set. User can

choose suitable service that the operator has provided.

5. Click Get and then Search to confirm whether Remote Communication

Parameters has been set successfully.

6. Connect the BTS port with donor antenna cable, before remote communication; it

will take 1 minute for the initialization of the modem inside the device.

7. If Short Message is set during Remote Communication Setup setting, click Start. After 10 seconds, choose the site ID and then click Get. The

device’s parameters will be read and displayed on the screen.

Page 13: OMT Software User Manual

User Manual Operation/Maintenance Terminal OMT Software

Netop Technology Co., Ltd Tel: +86 21 6921 4567 B2, No.303 XinKe Rd, Qingpu Industrial Zone, Fax: +86 21 6921 3655 Shanghai, China P.C: 201707 www.netop-technology.com

12

C h a p t e r 4

Device Operation

Device Create Get MOID From Device

1. Equipment Number : Select the equipment type(Single:FF ; Master:00 ;

Slave:01~FE)

2. Protocol:Select the protocol

3. Device Phone:Configure the device phone number in remote mode

4. Open the com. port -> Click Get MOID From Device -> Build MOID list automatic

Page 14: OMT Software User Manual

User Manual Operation/Maintenance Terminal OMT Software

Netop Technology Co., Ltd Tel: +86 21 6921 4567 B2, No.303 XinKe Rd, Qingpu Industrial Zone, Fax: +86 21 6921 3655 Shanghai, China P.C: 201707 www.netop-technology.com

13

User Configuration

1. Build MOID list by user Configuration

2. Equipment Number : Select the equipment type(Single:FF ; Master:00 ;

Slave:01~FE)

3. Protocol:Select the protocol

4. Device Phone:Configure the device phone number in remote mode

5. Open Menu Bar->MOID List Config ->The user to configure the equipment needed

for monitoring parameters

6. Open the com. port ->Choose Device Type -> Click User Configuration

Page 15: OMT Software User Manual

User Manual Operation/Maintenance Terminal OMT Software

Netop Technology Co., Ltd Tel: +86 21 6921 4567 B2, No.303 XinKe Rd, Qingpu Industrial Zone, Fax: +86 21 6921 3655 Shanghai, China P.C: 201707 www.netop-technology.com

14

Configuring the Device The scope of monitoring items:

Scope Items Description

0x0000~0x00FF Device Information Equipment general information

0x0100~0x01FF Monitoring Parameter Configure the number and Communication mode

0x0200~0x02FF Alarm Enable/Disable

Equipment won’t send the alarm when it is disable; and

the alarm status will be normal when OMT enquiry it (Non-

alarm status)

0x0300~0x03FF Alarm Status Equipment will send out the related alarm when meet the alarm condition

0x0400~0x04FF RF Parameters Details monitoring parameters of modules

0x0500~0x05FF Operation Status To provide the active sampling data of operating status to

the OMC, and manage all the active sampling data of

device modules

Page 16: OMT Software User Manual

User Manual Operation/Maintenance Terminal OMT Software

Netop Technology Co., Ltd Tel: +86 21 6921 4567 B2, No.303 XinKe Rd, Qingpu Industrial Zone, Fax: +86 21 6921 3655 Shanghai, China P.C: 201707 www.netop-technology.com

15

Scope Items Description

0x0600~0x09FF Engineering Parameter

0x0A00~0x0FFF Custom Manufacturers

Monitoring parameters interface description

1. Get: Search all the parameters checked

2. Set: Set all the parameters checked

3. Select All: Pick up all items in the interface

4. Clear All: Clear all items in the interface

5. MultiSelect: Pick up some items

6. MultiDeSelect: Clear some items

7. Check: Pick or Clear

8. SetValue: Set parameters according to type of equipment(Grey one is not

available)

9. GetValue: Display information of equipment. In Alarm Status will display Alarm or Normal

10. Unit: The unit of parameters

11. Status: Display feedback or not with Success or Failure, and no operation with

None

Page 17: OMT Software User Manual

User Manual Operation/Maintenance Terminal OMT Software

Netop Technology Co., Ltd Tel: +86 21 6921 4567 B2, No.303 XinKe Rd, Qingpu Industrial Zone, Fax: +86 21 6921 3655 Shanghai, China P.C: 201707 www.netop-technology.com

16

Device Information

Monitoring Parameter (available to get and set)

Alarm Enable/Disable(available to get and set)

Page 18: OMT Software User Manual

User Manual Operation/Maintenance Terminal OMT Software

Netop Technology Co., Ltd Tel: +86 21 6921 4567 B2, No.303 XinKe Rd, Qingpu Industrial Zone, Fax: +86 21 6921 3655 Shanghai, China P.C: 201707 www.netop-technology.com

17

Alarm Status (available to get but can not set)

RF Parameter(available to get and set)

Page 19: OMT Software User Manual

User Manual Operation/Maintenance Terminal OMT Software

Netop Technology Co., Ltd Tel: +86 21 6921 4567 B2, No.303 XinKe Rd, Qingpu Industrial Zone, Fax: +86 21 6921 3655 Shanghai, China P.C: 201707 www.netop-technology.com

18

Operation Status(available to get but can not set)

Engineering Parameter

Page 20: OMT Software User Manual

User Manual Operation/Maintenance Terminal OMT Software

Netop Technology Co., Ltd Tel: +86 21 6921 4567 B2, No.303 XinKe Rd, Qingpu Industrial Zone, Fax: +86 21 6921 3655 Shanghai, China P.C: 201707 www.netop-technology.com

19

C h a p t e r 5

Fault Management (FM)

Alarm Monitor Window

Send alarm automatically

Equipment sends the status automatically to OMC, such as alarm, alarm removed, and

channel configured. The confirm package OMC feedback to equipment do not need any

parameters and equipment can confirm it by package series number.

Set Remote Communication Setup:

Enter the SIM card number of the modem that will be connected with the laptop in

Report Phone No.1、2 (You can set Phone2 or not) .

Choose Short Message as Remote Communication Mode, and then Set. User can

choose suitable service that the operator has provided.

Page 21: OMT Software User Manual

User Manual Operation/Maintenance Terminal OMT Software

Netop Technology Co., Ltd Tel: +86 21 6921 4567 B2, No.303 XinKe Rd, Qingpu Industrial Zone, Fax: +86 21 6921 3655 Shanghai, China P.C: 201707 www.netop-technology.com

20

The items will display red highlight if the module is power off or unlinked.

Page 22: OMT Software User Manual

User Manual Operation/Maintenance Terminal OMT Software

Netop Technology Co., Ltd Tel: +86 21 6921 4567 B2, No.303 XinKe Rd, Qingpu Industrial Zone, Fax: +86 21 6921 3655 Shanghai, China P.C: 201707 www.netop-technology.com

21

C h a p t e r 6

Upgrade

Upgrade Firmware By Local Mode

1. Confirm the local communication is okay

2. Click Tools -> Upgrade Firmware -> UpgradeFirmware interface”

3. Click button Open File ->Select upgrade application program file(.hex) -> Click OK

4. Click Start -> Start obtain Firmware Version

5. Display Erasing flash,please wait...

6. Display Upgrade in progress..., start udgrade

7. Upgrade finished, display Upgrade Succeed! -> Click OK, upgrade successful!

8. Search Device Parameters -> Check the version

Configuration:

Module Address:00-FF

Timer(Sec):5,10,20,30,60,90,120,200,600

Packet Size(Byte):1024,2048,3072,4096,7168

Send Count:Count of package

DeviceType:Equipment type

Firmware Version:Displays the current Firmware version

Page 23: OMT Software User Manual

User Manual Operation/Maintenance Terminal OMT Software

Netop Technology Co., Ltd Tel: +86 21 6921 4567 B2, No.303 XinKe Rd, Qingpu Industrial Zone, Fax: +86 21 6921 3655 Shanghai, China P.C: 201707 www.netop-technology.com

22

Upgrade Memmap by Local Mode

1. Confirm the local communication is okay

2. Click Tools -> Upgrade Memmap -> Upgrade Memmap interface”

3. Click button Open File -> Select upgrade application program file(.hex) -> Click OK

4. Click Start -> Start obtain Memmap Version

5. Display Erasing flash...

6. Display Upgrade in progress..., start upgrade

7. Upgrade finished, display Upgrade Succeed! -> Click OK, upgrade successful!

8. Search Device Parameters -> Check the version

Page 24: OMT Software User Manual

User Manual Operation/Maintenance Terminal OMT Software

Netop Technology Co., Ltd Tel: +86 21 6921 4567 B2, No.303 XinKe Rd, Qingpu Industrial Zone, Fax: +86 21 6921 3655 Shanghai, China P.C: 201707 www.netop-technology.com

23

Page 25: OMT Software User Manual

User Manual Operation/Maintenance Terminal OMT Software

Netop Technology Co., Ltd Tel: +86 21 6921 4567 B2, No.303 XinKe Rd, Qingpu Industrial Zone, Fax: +86 21 6921 3655 Shanghai, China P.C: 201707 www.netop-technology.com

24

C h a p t e r 7

Others

Alarm Level Configuration

Users can configure the alarm level flexibly according to the conditions of definition

Alarm level definitions

Alarm Level Description Color

Serious 3 Interrupt the service of BTS coverage area and interference

the network such as shut down, power off, self oscillations red

Major 2 Interrupt the coverage of equipment or lower the service

quality such as main modules are damaged orange

General 1

Reduce the coverage range of equipment or lower the

service quality such as functional components are

damaged

yellow

Normal 0 Alarm removed green

1. Configuration ->Alarm Level Configuration

2. Choose Alarm Level

3. Save

Page 26: OMT Software User Manual

User Manual Operation/Maintenance Terminal OMT Software

Netop Technology Co., Ltd Tel: +86 21 6921 4567 B2, No.303 XinKe Rd, Qingpu Industrial Zone, Fax: +86 21 6921 3655 Shanghai, China P.C: 201707 www.netop-technology.com

25

Cmcc Packet Analyzer

Transmit data packet analysis 1. Copy SendData or ReceiveData to the CmccPacketAnalyzer

2. Click Analyzer,and the data will display as the following figure

3. Click Exit to escape

Page 27: OMT Software User Manual

User Manual Operation/Maintenance Terminal OMT Software

Netop Technology Co., Ltd Tel: +86 21 6921 4567 B2, No.303 XinKe Rd, Qingpu Industrial Zone, Fax: +86 21 6921 3655 Shanghai, China P.C: 201707 www.netop-technology.com

26

Data Send & Receive interface

1. Hex Display:Display hexadecimal when selected, or display decimal

2. Clear All:Clear all data display in the interface

Version information

Help ->About...

Page 28: OMT Software User Manual

User Manual Operation/Maintenance Terminal OMT Software

Netop Technology Co., Ltd Tel: +86 21 6921 4567 B2, No.303 XinKe Rd, Qingpu Industrial Zone, Fax: +86 21 6921 3655 Shanghai, China P.C: 201707 www.netop-technology.com

27

Revision Record Title NETOP Operation/Maintenance Terminal OMT Software User Manual Document NO. Revision Description Date Writer Approved

V1.0 Operation/Maintenance Terminal OMT Software User Manual Release 2008-10-15 Stella_Qian ShiXin

V1.1 Increasing function on multi-system shows 2009-07-23 Stella_Qian ShiXin