oil level indicator trip contact

Upload: mohamed-rafi

Post on 01-Jun-2018

339 views

Category:

Documents


2 download

TRANSCRIPT

  • 8/9/2019 OIL LEVEL INDICATOR TRIP CONTACT

    1/34

    www.precimeasure.com

    PRECIMEASURE

    The fully sealed liquid expansion in the system provides a self powered indication and operation to theinstruments, and does not require any trimming or other periodic adjustments.

    Instruments are fully compensated for ambient temperature.

    The WTI instruments have a built in Thermal imaging system for transformers hot spot indication.

    The WTIs are provided with gradient adjustment through a shunt for CT secondary input (1A to 5A).

    Instrument cases are aluminium die casted and polyester powder coated. Each instrument hasanti vibration mountings and are provided with projection mounting clamps.

    A maximum pointer facility is provided, can be reset from outside.

    All switch contacts are potential free micro switches

    MODEL - 1005/1005ADIAL TYPE THERMOMETER

    SPECIFICATIONS Model : 1005 Model : 1005A

    Temperature Range 0 -1500C, 0 -1600C, 30 -1500C,-20 to 1400C

    0 -1500C, 0 -1600C, 30 -1500C,-20 to 1400C

    Dial Size 150mm (6) Round 150mm (6) Round

    Dial angular Sweep 2700 2700

    Dial Graduation 10C 10C

    Accuracy Class 1% of FSD 1% of FSD

    Max. No. of Switches 5 5

    Switching Range 15% - 85% 15% - 85%

    Contact Rating 3A @ 250V AC/DC

    Magnetic Blowout Micro switch

    15A @ 250V AC

    0.5A @ 250V DCStandard Micro switch

    Switch Differential S1 & S2: 3C to 9C (630C)FixedS3 to S5: 8C to 400C Adjustable.

    S1 & S2: 3C to 90C (630C)FixedS3 to S5: 80C to 400C Adjustable.

    Switching Accuracy 2.5 0C of Set Value 2.50C of Set Value

    Remote Repeater Available (Potentiometer Output) Available (Potentiometer Output)

    Max. Capillary Length Up to 25 Mtrs Up to 25 Mtrs

    Switch Test Knob Available Available

    Electrical Connection Press Fit Wago Type Press Fit Wago Type

    Degree of Protection IP 55(IEC - 60529) IP 55(IEC - 60529)

    High Voltage Test 2.5 KV AC, 50Hz/60Hz for1 minute; all Terminals to ground

    2.5 KV AC, 50Hz/60Hz for1 minute; all Terminals to ground

    Electrical entry M20 - 3Nos M20 - 3Nos

    Cable Gland Optional Optional

    Thermometer Pocket Optional Optional

    Remote Repeater 96 Sq

    1005/1005A

    General Features

    STANDARD OTI / WTI

    SPECIFICATIONS

    Type 4 digits, 0.5 Seven Segments LEDs

    Auxillary Supply 90 260V AC/DC

    Resolution 0.10C

    Degree of protection of enclosure IP 20

    Operating Temperature Range 00C to 600C

    Signal output 4 sets of 4 - 20mA DC

    Optional RS 485

    Cutout dimension 92 Sq. mm

    DIALTYPE

  • 8/9/2019 OIL LEVEL INDICATOR TRIP CONTACT

    2/34

    www.precimeasure.com

    1. Protection class : IP55 as per IEC 60529 CAT 2.

    2. Cold and Dry Test : -40C to +70C

    3. Vibration Test : Amplitude 1mm, frequency 50Hz,

    1Hr / X,Y,Z axis

    4. Salt Spray Test :

    For polyester powder coating andSS 304 Armour for 500 Hrs as perDIN 50021 Standard

    5. Micro Switch rating Test : a) ML - 1005:

    3A @ 250V AC &3A @ 250V DC

    b) ML - 1005A:15A @250V AC &0.5A @250V DC

    Type Tested ForModel 1005 /1005A

    Type of Instrument OTI / WTI

    Range R1. 0 - 150CR2. 0 - 160CR3. 30 - 150CR4. -20 to140C(other ranges on request)

    No. of Switches S2 - 2switchesS3 - 3switchesS4 - 4switchesS5 - 5switches

    Switch Conguration L - Normally open contactL2 - Changeover contact

    Capillary Length C1 - 1mtsC2 - 2mts....... upto C25 - 25mts

    Union Type U1 - 1/2 BSP MaleU2 - 3/4 BSP MaleU3 - 1BSP MaleU4 - 1/2 BSP FemaleU5 - 3/4 BSP Female

    Repeater Y - RequriedN - Not Required

    If WTI please specify Transformer CT Secondary output..................(1A to 5A)Simulated Temperature rise over top oil........... (5C to 30C)

    Ordering Information

    Note: WTI Gradient is factory set. If required customer can adjust as per requirement.

    Sample Ordering Information :1005\WTI\R3\S2\L2\C2\U1\Y\........... Amps ...............C

    Registered Office & Works :No. 168/C Industrial Suburb,

    Peenya 3rd Phase, Bangalore - 560058. INDIA

    Phone : + 91-80-4260 2705 / 08

    Fax : + 91-80-4155 2205

    E-Mail : [email protected]

    Branch Office & Works :No. 27,28,30, Block-II, 2ndFloor,

    Sidco Electronics Complex, Guindy, Chennai - 600032. INDIA

    Phone : + 91-44-2250 0191 / 2250 0175

    Fax : + 91-44-2250 0175

    E-Mail : [email protected]

    PRECIMEASURE CONTROLS PVT. LTD.

    Western India Region Office :Mobile : 09377561070

    E-Mail : [email protected]

  • 8/9/2019 OIL LEVEL INDICATOR TRIP CONTACT

    3/34

    www.precimeasure.com

    PRECIMEASURE

    The fully sealed liquid expansion in the system provides a self powered indication and operation tothe instruments, and does not require any trimming or other periodic adjustments.

    Instruments are fully compensated for ambient temperature. The WTI instruments have a built in Thermal imaging system for transformers hot spot indication. The WTIs are provided with gradient adjustment through a shunt for CT secondary input (1A to 5A). Embedded PT-100 sensors in the sensing bulb of the local OTI/ WTI provide for a master

    indication. Current Converter Unit (CCU) is mounted inside the Local OTI/WTI, The output from which can be

    connected to remote indicator or SCADA are a combination of both. For the WTIs additional Winding temperature simulator is provided Instrument cases are aluminium die casted and polyester powder coated. Each instrument has

    anti vibration mountings and are provided with projection mounting clamps.

    A maximum pointer facility is provided, can be reset from outside. All switch contacts are potential free micro switches

    MODEL - 1005H/1005AHDIAL TYPE THERMOMETER

    SPECIFICATIONS Model : 1005H Model : 1005AH

    Temperature Range 0-1500C, 0-1600C, 30-1500C,-20 to 1400C

    0-1500C, 0-1600C, 30-1500C,-20 to1400C

    Dial Size 150mm (6) Round 150mm (6) Round

    Dial angular Sweep 2700 2700

    Dial Graduation 10C 10C

    Accuracy Class 1% of FSD 1% of FSD

    Max.No. of Switches 5 5

    Switching Range 15% - 85% 15% - 85%

    Contact Rating 3A @ 250V AC/DCMagnetic Blowout Micro switch

    15A @ 250V AC0.5A @ 250V DCStandard Micro switch

    Switch Differential S1 & S2: 3C to 9C (630C) FixedS3 to S5: 8C to 400C Adjustable.

    S1 & S2: 3C to 90C (630C)FixedS3 to S5: 80C to 400C Adjustable.

    Switching Accuracy 2.5 0C of Set Value 2.50C of Set Value

    Remote indicator Available / 4 - 20mA / RS - 485 Available / 4-20mA / RS - 485

    Max. Capillary Length Up to 25 Mtrs. Up to 25 Mtrs.

    Switch Test Knob Available Available

    Electrical Connection Press Fit Wago Type Press Fit Wago Type

    Degree of Protection IP 55(IEC-60529) IP 55(IEC-60529)

    High Voltage Test 2.5 KV AC, 50Hz/60Hz for 1minute; Switch connection & C.T.Terminal to ground.

    CCU output 0.5 KV AC50Hz / 60Hz for 1 minute

    2.5 KV AC, 50Hz/60Hz for 1minute; Switch connection & C.T.Terminal to ground.

    CCU output 0.5 KV AC50Hz / 60Hz for 1 minute

    Electrical entry M20 - 3Nos M20 - 3Nos

    Cable Gland Optional Optional

    Thermometer Pocket Optional OptionalRemote indicator 96 Sq

    ML : 1005H/1005AH

    General Features

    Hybrid OTI / WTI

    SPECIFICATIONS

    Type 4 digits, 0.5 Seven Segments LEDs

    Auxillary Supply 90 260V AC/DC

    Resolution 0.10C

    Degree of protection of enclosure IP 20

    Operating Temperature Range 00

    C to 600

    C

    Signal output 4 sets of 4 - 20mA DC

    Optional RS 485

    Cutout dimension 92 Sq.mm

    DIALTYPE

  • 8/9/2019 OIL LEVEL INDICATOR TRIP CONTACT

    4/34

    www.precimeasure.com

    1. Protection class : IP55 as per IEC 60529 CAT 2.

    2. Cold and Dry Test : -40C to +70C

    3. Vibration Test : Amplitude 1mm, frequency 50Hz,

    1Hr / X,Y,Z axis

    4. Salt Spray Test :

    For polyster powder coating andSS 304 Armour for 500 Hrs as perDIN 50021 Standard

    5. Micro Switch rating Test : a) ML - 1005H:

    3A @ 250V AC &3A @ 250V DC

    b) ML - 1005AH:15A @250V AC &0.5A @250V DC

    Type Tested For

    MODEL 1005H/1005AH

    Type of Instrument OTI / WTI

    Range R1. 0 - 150CR2. 0 - 160CR3. 30 - 150CR4. -20 to140C(other ranges on request)

    No. of Switches S2 - 2switchesS3 - 3switchesS4 - 4switches

    S5 - 5switchesSwitch Congura-tion

    L - Normally open contactL2 - Changeover contact

    Capillary Length C1 - 1mtsC2 - 2mts....... upto C25 - 25mts

    Union Type U1 - 1/2 BSP MaleU2 - 3/4 BSP MaleU3 - 1BSP MaleU4 - 1/2 BSP FemaleU5 - 3/4 BSP Female

    CCU Output forindication / Scada

    RI - Remote indicator - T1/T2/T3/T4 (for types, Refer Drawing)PSU - External power supply with 2 Nos. of 4-20mA output

    If WTI please

    specify

    Transformer CT Secondary output..................(1A to 5A)

    Simulated Temperature rise over top oil........... (5C to 30C)

    Ordering Information

    Note: WTI Gradient is factory set. If required customer can adjust as per requirment.

    Sample Ordering Information :1005AH\OTI\R4\S4\L\C6\U4\RI-T2 ........... Amps ...............C

    Registered Office & Works :No. 168/C Industrial Suburb,

    Peenya 3rd Phase, Bangalore - 560058. INDIA

    Phone : + 91-80-4260 2705 / 08

    Fax : + 91-80-4155 2205

    E-Mail : [email protected]

    Branch Office & Works :No. 27,28,30, Block-II, 2ndFloor,

    Sidco Electronics Complex, Guindy, Chennai - 600032. INDIA

    Phone : + 91-44-2250 0191 / 2250 0175

    Fax : + 91-44-2250 0175

    E-Mail : [email protected]

    PRECIMEASURE CONTROLS PVT. LTD.

    Western India Region Office :Mobile : 09377561070

    E-Mail : [email protected]

  • 8/9/2019 OIL LEVEL INDICATOR TRIP CONTACT

    5/34

    www.precimeasure.com

    PRECIMEASURE

    PSU

    MODEL - 1005HX / 1005AHXDIAL TYPE THERMOMETER

    Remote Indicator 96 Sq

    Duplex Hybrid OTI / WTI

    SPECIFICATIONS MODEL : 1005HX MODEL : 1005AHX

    Temperature Range 0-1500C, 0-1600C, 30-1500C,-20 to 1400C

    0-1500C, 0-1600C, 30-1500C,-20 to1400C

    Dial Size 150mm (6) Round 150mm (6) Round

    Dial angular Sweep 2700 2700

    Dial Graduation 10C 10C

    Accuracy Class 1% of FSD 1% of FSD

    Max.No. of Switches 5 5

    Switching Range 15% - 85% 15% - 85%

    Contact Rating 3A @ 250V AC/DCMagnetic Blowout Micro switch 15A @ 250V AC0.5A @ 250V DCStandard Micro switch

    Switch Differential S1 & S2: 3C to 9C (630C) FixedS3 to S5: 8C to 400C Adjustable.

    S1 & S2: 3C to 90C (630C)FixedS3 to S5: 80C to 400C Adjustable.

    Switching Accuracy 2.5 0C of Set Value 2.50C of Set Value

    Remote indicator Available / 4-20mA / RS - 485 Available / 4-20mA / RS - 485

    Max. Capillary Length Up to 25 Mtrs. Up to 25 Mtrs.

    Switch Test Knob Available Available

    Electrical Connection Press Fit Wago Type Press Fit Wago Type

    Degree of Protection IP 55(IEC-60529) IP 55(IEC-60529)

    High Voltage Test 2.5 KV AC, 50Hz/60Hz for 1minute; Switch connection & C.T.Terminal to ground.CCU output 0.5 KV AC50Hz / 60Hz for 1 minute

    2.5 KV AC, 50Hz/60Hz for 1minute; Switch connection & C.T.Terminal to ground.CCU output 0.5 KV AC50Hz / 60Hz for 1 minute

    Electrical entry M20 - 3Nos M20 - 3Nos

    Cable Gland Optional Optional

    Thermometer pocket Optional Optional

    ML: 1005 HX/1005 AHX

    The fully sealed liquid expansion in the system provides a self powered indication and operation to theinstruments, and does not require any trimming or other periodic adjustments.

    Instruments are fully compensated for ambient temperature. The WTI instruments have a built in Thermal imaging system for transformers hot spot indication. The WTIs are provided with gradient adjustment through a shunt for CT secondary input (1A to 5A). Embedded Duplex PT-100 sensors in the sensing bulb of the local OTI/ WTI provide for a

    master indication. Current Converter Units (CCUs) are mounted inside the Local OTI/WTI, The output from which can be

    connected to remote indicator and SCADA through external power supply units (PSUs). For the WTIs additional Winding temperature simulator is provided Instrument cases are aluminium die casted and polyester powder coated. Each instrument has

    anti vibration mountings and are provided with projection mounting clamps. A maximum pointer facility is provided, can be reset from outside. All switch contacts are potential free micro switches

    General Features

    POWER SUPPLY UNIT - (PSU)

    a. Output Voltage: 24V

    b. Output Signal: Analogue output2nos. 4-20mA DC(Output - 1, Burden 250 Ohms)(Output- 2, Burden 600 Ohms)

    c. Auxiliary supply: 90-260V AC/DC

    REMOTE INDICATOR

    a Type : 4 digits, 0.5 Seven Segment LEDs

    b Auxiliary Supply : 90 260V AC/DC

    d Resolution : 0.10C

    e Degree of protection of enclosure : IP-20f Operating Temperature Range : 0C to 60C

    g Signal output: 4sets of 4-20mA DC, OptionalRS 485

    h Cutout Dimension: 92Sq.mm

    DIALTYPE

  • 8/9/2019 OIL LEVEL INDICATOR TRIP CONTACT

    6/34

    www.precimeasure.com

    1. Protection class : IP55 as per IEC 60529 CAT 2.

    2. Cold and Dry Test : -40C to +70C

    3. Vibration Test : Amplitude 1mm, frequency 50Hz,

    1Hr / X,Y,Z axis

    4. Salt Spray Test :

    For polyster powder coating andSS 304 Armour for 500 Hrs as perDIN 50021 Standard

    5. Micro Switchrating Test : a) ML - 1005HX:

    3A @ 250V AC &3A @ 250V DC

    b) ML - 1005AHX:15A @250V AC &0.5A @250V DC

    Type Tested ForMODEL 1005HX/1005AHX

    Type of Instrument OTI / WTI

    Range R1. 0 - 150CR2. 0 - 160CR3. 30 - 150CR4. -20 to140C(other ranges on request)

    No. of Switches S2 - 2switchesS3 - 3switchesS4 - 4switches

    S5 - 5switchesSwitch Conguration L - Normally open contact

    L2 - Changeover contact

    Capillary Length C1 - 1mtsC2 - 2mts....... upto C25 - 25mts

    Union Type U1 - 1/2 BSP MaleU2 - 3/4 BSP MaleU3 - 1BSP MaleU4 - 1/2 BSP FemaleU5 - 3/4 BSP Female

    CCU Output forindication / Scada

    RI - Remote indicator - T1/T2/T3/T4 (For Types, Refer Drawing)(Connected through external powersupply PSUs)

    If WTI please specify Transformer CT Secondary output..................(1A to 5A)

    Simulated Temperature rise over top oil........... (5C to 30

    C)

    Ordering Information

    Note: WTI Gradient is factory set. If required customer can adjust as per requirment.

    Sample Ordering Information :1005AHX\OTI\R4\S4\L\C6\U4\RI-T1........... Amps.............C

    Registered Office & Works :No. 168/C Industrial Suburb,

    Peenya 3rd Phase, Bangalore - 560058. INDIA

    Phone : + 91-80-4260 2705 / 08

    Fax : + 91-80-4155 2205

    E-Mail : [email protected]

    Branch Office & Works :No. 27,28,30, Block-II, 2ndFloor,

    Sidco Electronics Complex, Guindy, Chennai - 600032. INDIA

    Phone : + 91-44-2250 0191 / 2250 0175

    Fax : + 91-44-2250 0175

    E-Mail : [email protected]

    PRECIMEASURE CONTROLS PVT. LTD.

    Western India Region Office :Mobile : 09377561070

    E-Mail : [email protected]

  • 8/9/2019 OIL LEVEL INDICATOR TRIP CONTACT

    7/34

    www.precimeasure.com

    PRECIMEASURE

    The fully sealed liquid expansion in the system provides a self powered indication and operation to theinstruments, and does not require any trimming or other periodic adjustments.

    Instruments are fully compensated for ambient temperature.

    The WTI instruments have a built in Thermal imaging system for transformers hot spot indication.

    The WTIs are provided with gradient adjustment through a shunt for CT secondary input (1A to 5A).

    Instrument cases are aluminium die casted and polyester powder coated. Each instrument hasanti vibration mountings and are provided with projection mounting clamps.

    A maximum pointer facility is provided, can be reset from outside.

    All switch contacts are potential free micro switches

    MODEL - 1007DIAL TYPE THERMOMETER

    Remote Repeater 96 Sq

    General Features

    Standard OTI / WTI

    ML : 1007

    PSU

    SPECIFICATIONS MODEL : 1007

    Temperature Range 0-1500C, 0-1600C, 30-1500C,-20 to 1400C

    Dial Size 115mm, Segment Dial

    Dial angular Sweep 600

    Dial Graduation 20C

    Accuracy Class 1.5% of FSD

    Max.No. of Switches 4

    Switching Range 15% - 85%

    Contact Rating 15A @ 250V AC0.5A @ 250V DCStandard Micro switch

    Switch Differential S1 & S2: 3C to 9C (630C) FixedS3 & S4: 8C to 400C Adjustable.

    Switching Accuracy 2.5 0C of Set Value

    Remote Repeater Available (Potentiometer Output)

    Max. Capillary Length Up to 25 Mtrs.

    Electrical Connection Press Fit Wago Type

    Degree of Protection IP 55 (IEC-60529)

    High Voltage Test 2.5 KV AC, 50Hz/60Hz for 1 minute; all Terminalsto ground

    Electrical entry M20 - 3Nos

    Cable Gland Optional

    Thermometer Pocket Optional

    DIALTYPE

    POWER SUPPLY UNIT - (PSU)

    a. Output Voltage: 24V

    b. Output Signal: Analogue output2nos. 4-20mA DC(Output - 1, Burden 250 Ohms)(Output- 2, Burden 600 Ohms)

    c. Auxiliary supply: 90-260V AC/DC

    REMOTE INDICATOR

    a Type : 4 digits, 0.5 Seven Segment LEDs

    b Auxiliary Supply : 90 260V AC/DC

    d Resolution : 0.10C

    e Degree of protection of enclosure : IP-20f Operating Temperature Range : 0C to 60C

    g Signal output: 4sets of 4-20mA DC, OptionalRS 485

    h Cutout Dimension: 92Sq.mm

  • 8/9/2019 OIL LEVEL INDICATOR TRIP CONTACT

    8/34

    www.precimeasure.com

    1. Protection class : IP55 as per IEC 60529 CAT 2.

    2. Cold and Dry Test : -40C to +70C

    3. Vibration Test : Amplitude 1mm, frequency 50Hz,

    1Hr / X,Y,Z axis

    4. Salt Spray Test :

    For polyster powder coating andSS 304 Armour for 500 Hrs as perDIN 50021 Standard

    5. Micro Switch rating Test : 15A @250V AC &

    0.5A @250V DC

    Type Tested For

    Model 1007

    Type of Instrument OTI / WTI

    Range R1. 0 - 150CR2. 0 - 160CR3. 30 - 150CR4. -20 to140C(other ranges on request)

    No. of Switches S2 - 2switchesS3 - 3switchesS4 - 4switches

    Switch Conguration L - Normally open contactL2 - Changeover contact

    Capillary Length C1 - 1mtsC2 - 2mts....... upto C25 - 25mts

    Union Type U1 - 1/2 BSP MaleU2 - 3/4 BSP MaleU3 - 1BSP MaleU4 - 1/2 BSP FemaleU5 - 3/4 BSP Female

    Repeater Y - Requried,N - Not Required

    If WTI please specify Transformer CT Secondary output..................(1A to 5A)Simulated Temperature rise over top oil........... (5C to 30C)

    Ordering Information

    Note: WTI Gradient is factory set. If required customer can adjust as per requirment.

    Sample Ordering Information :1007\OTI\R3\S2\L2\C8\U5\Y\........... Amps ...............C

    Registered Office & Works :No. 168/C Industrial Suburb,

    Peenya 3rd Phase, Bangalore - 560058. INDIA

    Phone : + 91-80-4260 2705 / 08

    Fax : + 91-80-4155 2205

    E-Mail : [email protected]

    Branch Office & Works :No. 27,28,30, Block-II, 2ndFloor,

    Sidco Electronics Complex, Guindy, Chennai - 600032. INDIA

    Phone : + 91-44-2250 0191 / 2250 0175

    Fax : + 91-44-2250 0175

    E-Mail : [email protected]

    PRECIMEASURE CONTROLS PVT. LTD.

    Western India Region Office :Mobile : 09377561070

    E-Mail : [email protected]

  • 8/9/2019 OIL LEVEL INDICATOR TRIP CONTACT

    9/34

    www.precimeasure.com

    PRECIMEASURE

    The fully sealed liquid expansion in the system provides a self powered indication and operation to the instruments, anddoes not require any trimming or other periodic adjustments.

    Instruments are fully compensated for ambient temperature.

    The WTI instruments have a built in Thermal imaging system for transformers hot spot indication.

    The WTIs are provided with gradient adjustment through a shunt for CT secondary input (1A to 5A).

    Embedded PT-100 sensorsin the sensing bulb of the local OTI/ WTI provide for a master indication.

    Current Converter Unit (CCU) is mounted inside the Local OTI/WTI, The output from which can be connected to remoteindicator or SCADA are a combination of both.

    For the WTIs additional Winding temperature simulator is provided

    Instrument cases are aluminium die casted and polyester powder coated. Each instrument has anti vibration mountingsand are provided with projection mounting clamps.

    A maximum pointer facility is provided, can be reset from outside.

    All switch contacts are potential free micro switches

    MODEL - 1007HDIAL TYPE THERMOMETER

    General Features

    Hybrid OTI / WTI

    ML : 1007H Specifications Model : 1007HTemperature Range 0-1500C, 0-1600C, 30-1500C,-20 to 1400C

    Dial Size 115mm, Segment Dial

    Dial angular Sweep 600

    Dial Graduation 20C

    Accuracy Class 1.5% of FSD

    Max.No. of Switches 4

    Switching Range 15% - 85%

    Contact Rating 15A @ 250V AC

    0.5A @ 250V DCStandard Micro switch

    Switch Differential S1 & S2: 3C to 9C (630C) FixedS3 & S4: 8C to 400C Adjustable.

    Switching Accuracy 2.5 0C of Set Value

    Remote Indicator Available / 4-20mA / RS - 485

    Max. Capillary Length Up to 25 Mtrs

    Electrical Connection Press Fit Wago Type

    Degree of Protection IP 55(IEC-60529)

    High Voltage Test 2.5 KV AC, 50Hz/60Hz for 1 minute; Switchconnection & C.T. Terminal to ground.CCU output 0.5 Kv Ac50Hz / 60Hz for 1 minute

    Electrical entry M20 - 3Nos

    Cable Gland Optional

    Thermometer Packet Optional

    DIALTYPE

    POWER SUPPLY UNIT - (PSU)

    a. Output Voltage: 24V

    b. Output Signal: Analogue output2nos. 4-20mA DC(Output - 1, Burden 250 Ohms)(Output- 2, Burden 600 Ohms)

    c. Auxiliary supply: 90-260V AC/DC

    REMOTE INDICATOR

    a Type : 4 digits, 0.5 Seven Segment LEDs

    b Auxiliary Supply : 90 260V AC/DC

    d Resolution : 0.10C

    e Degree of protection of enclosure : IP-20f Operating Temperature Range : 0C to 60C

    g Signal output: 4sets of 4-20mA DC, OptionalRS 485

    h Cutout Dimension: 92Sq.mm

    Remote Repeater 96 Sq

    PSU

  • 8/9/2019 OIL LEVEL INDICATOR TRIP CONTACT

    10/34

    www.precimeasure.com

    1. Protection class : IP55 as per IEC 60529 CAT 2.

    2. Cold and Dry Test : -40C to +70C

    3. Vibration Test : Amplitude 1mm, frequency 50Hz,

    1Hr / X,Y,Z axis

    4. Salt Spray Test : For polyster powder coating and

    SS 304 Armour for 500 Hrs as perDIN 50021 Standard

    5. Micro Switch rating Test : 15A @250V AC & 0.5A @250V DC

    Type Tested For

    Model 1007H

    Type of Instrument OTI / WTI

    Range R1. 0 - 150CR2. 0 - 160CR3. 30 - 150CR4. -20 to140C(other ranges on request)

    No. of Switches S2 - 2switchesS3 - 3switchesS4 - 4switches

    Switch Conguration L - Normally open contactL2 - Changeover contact

    Capillary Length C1 - 1mtsC2 - 2mts....... upto C25 - 25mts

    Union Type U1 - 1/2 BSP MaleU2 - 3/4 BSP MaleU3 - 1BSP MaleU4 - 1/2 BSP FemaleU5 - 3/4 BSP Female

    CCU Output for

    indication / Scada

    RI - Remote indicator - T1/T2/T3/T4 (For types, refer Drawing)

    PSU - External power supply with 2 Nos. of 4-20mA outputIf WTI please specify Transformer CT Secondary output..................(1A to 5A)

    Simulated Temperature rise over top oil........... (5C to 30C)

    Ordering Information

    Note: WTI Gradient is factory set. If required customer can adjust as per requirment.

    Sample Ordering Information :1007H\OTI\R3\S2\L2\C8\U5\RI-T4........... Amps ...............C

    Registered Office & Works :No. 168/C Industrial Suburb,

    Peenya 3rd Phase, Bangalore - 560058. INDIA

    Phone : + 91-80-4260 2705 / 08

    Fax : + 91-80-4155 2205

    E-Mail : [email protected]

    Branch Office & Works :No. 27,28,30, Block-II, 2ndFloor,

    Sidco Electronics Complex, Guindy, Chennai - 600032. INDIA

    Phone : + 91-44-2250 0191 / 2250 0175

    Fax : + 91-44-2250 0175

    E-Mail : [email protected]

    PRECIMEASURE CONTROLS PVT. LTD.

    Western India Region Office :Mobile : 09377561070

    E-Mail : [email protected]

  • 8/9/2019 OIL LEVEL INDICATOR TRIP CONTACT

    11/34

    www.precimeasure.com

    PRECIMEASURE

    The fully sealed liquid expansion in the system provides a self powered indication and operation to theinstruments, and does not require any trimming or other periodic adjustments.

    Instruments are fully compensated for ambient temperature.

    The WTI instruments have a built in Thermal imaging system for transformers hot spot indication.

    The WTIs are provided with gradient adjustment through a shunt for CT secondary input (1A to 5A).

    Instrument cases are aluminium die casted and polyester powder coated. Each instrument hasanti vibration mountings and are provided with projection mounting clamps.

    A maximum pointer facility is provided, can be reset from outside.

    All switch contacts are potential free micro switches.

    MODEL - 1006DIAL TYPE THERMOMETER

    General Features

    Standard OTI / WTI

    ML : 1006

    SPECIFICATIONS MODEL : 1006

    Temperature Range 0-1500C, 0-2400C

    Dial angular Sweep 2700

    Dial Graduation 20C

    Accuracy Class 1.5% of FSD

    Max.No. of Switches 2

    Switching Range 15% - 85%

    Contact Rating5A @ 250V AC,

    0.5A @ 220V DC

    Switch Differential 10C to 50C (30C20C) Fixed

    Switching Accuracy 2.50C of Set Value

    Max. Capillary Length Up to 6 Mtrs.

    Switch Test Knob Available

    Electrical Connection 1Sq mm. Copper Cable, 1mtr LengthDegree of Protection IP 55(IEC-60529)

    High Voltage Test2.5 KV AC, 50Hz / 60Hz for 1 minute ; all Terminal to ground

    DIALTYPE

  • 8/9/2019 OIL LEVEL INDICATOR TRIP CONTACT

    12/34

    www.precimeasure.com

    Model 1006

    Type of Instrument OTI / WTI

    Range R1. 0 - 150C.

    R2. 0 - 240C

    No. of Switches S2 - 2switchesSwitch Conguration L - Normally open contact

    L2 - Changeover contact

    Capillary Length C1 - 1mtsC2 - 2mts....... upto C6 - 6mts

    Union Type U1 - 1/2 BSP MaleU2 - 3/4 BSP MaleU3 - 1 BSP MaleU4 - 1/2 BSP FemaleU5 - 3/4 BSP Female

    If WTI please specify Transformer CT Secondary output..................(1A to 5A)Simulated Temperature rise over top oil........... (5C to 30C)

    Ordering Information

    Note: WTI Gradient is factory set. If required customer can adjust as per requirment.

    Sample Ordering Information :1006\WTI\R1\S2\L2\C5\U5 ........... Amps ...............C

    1. Protection class : IP55 as per IEC 60529 CAT 2.

    2. Vibration Test : Amplitude 1mm,

    frequency 50Hz, 1Hr / X,Y,Z axis

    3. Salt Spray Test : For polyster powder coating

    and SS 304 Armour for 500 Hrsas per DIN 50021Standard

    4. Micro Switch rating Test : 5A @ 250V AC, 0.5A @ 220V DC

    Type Tested For

    Registered Office & Works :No. 168/C Industrial Suburb,

    Peenya 3rd Phase, Bangalore - 560058. INDIA

    Phone : + 91-80-4260 2705 / 08

    Fax : + 91-80-4155 2205

    E-Mail : [email protected]

    Branch Office & Works :No. 27,28,30, Block-II, 2ndFloor,

    Sidco Electronics Complex, Guindy, Chennai - 600032. INDIA

    Phone : + 91-44-2250 0191 / 2250 0175

    Fax : + 91-44-2250 0175

    E-Mail : [email protected]

    PRECIMEASURE CONTROLS PVT. LTD.

    Western India Region Office :Mobile : 09377561070

    E-Mail : [email protected]

  • 8/9/2019 OIL LEVEL INDICATOR TRIP CONTACT

    13/34

    www.precimeasure.com

    PRECIMEASURE

    The fully sealed liquid expansion in the system provides a self powered indication and operation to theinstruments, and does not require any trimming or other periodic adjustments.

    Instruments are fully compensated for ambient temperature.

    The WTI instruments have a built in Thermal imaging system for transformers hot spot indication.

    The WTIs are provided with gradient adjustment through a shunt for CT secondary input (1A to 5A). Embedded PT-100 sensorsin the sensing bulb of the local OTI/ WTI provide for a master indication.

    Instrument cases are aluminium die casted and polyester powder coated. Each instrument hasanti vibration mountings and are provided with projection mounting clamps.

    A maximum pointer facility is provided, can be reset from outside.

    All switch contacts are potential free micro switches.

    MODEL - 1006HDIAL TYPE THERMOMETER

    General Features

    Hybrid OTI / WTI

    ML : 1006H SPECIFICATIONS MODEL : 1006H

    Temperature Range 0-1500C, 0-2400C

    Dial angular Sweep 2700

    Dial Graduation 20C

    Accuracy Class 1.5% of FSD

    Max.No. of Switches 2

    Switching Range 15% - 85%

    Contact Rating

    5A @ 250V AC,

    0.5A @ 220V DC

    Switch Differential 10C to 50C (30C20C) Fixed

    Switching Accuracy 2.50C of Set Value

    Remote Indicator Availbale

    Max. Capillary Length Up to 6 Mtrs.

    Switch Test Knob Available

    Electrical Connection 1Sq mm. Copper Cable, 1mtr Length

    Degree of Protection IP 55(IEC-60529)

    High Voltage Test

    (a) Local OTI / WTI

    (b) Local OTI / WTI

    (c) CCU

    (d) CCU

    Test Voltage

    2.5 KV AC, 50Hz / 60Hz

    500 V AC, 50Hz / 60Hz

    500 V AC, 50Hz / 60Hz

    2.5 KV AC, 50Hz / 60Hz

    Terminals Details

    Switch connection / CT Connection

    Pt 100 sensor output

    Pt 100 sensor input +4-20mA Output

    CT connection with power supply

    ML : 2220-R2 (CCU)

    Remote Indicator 96 Sq

    SPECIFICATION

    Type 4 digits, 0.5 Seven Segments LEDs

    Auxillary Supply 90 260V AC/DC

    Resolution 0.10C

    Degree of protection of enclosure IP 20

    Operating Temperature Range 00C to 600C

    Signal output 4 sets of 4 - 20mA DC, Optional RS 485

    Cutout dimension 92 Sq.mm

    DIALTYPE

  • 8/9/2019 OIL LEVEL INDICATOR TRIP CONTACT

    14/34

    www.precimeasure.com

    1. Protection class : IP55 as per IEC 60529 CAT 2.

    2. Vibration Test : Amplitude 1mm, frequency 50Hz,

    1Hr / X,Y,Z axis

    3. Salt Spray Test : For polyster powder coating and

    SS 304 Armour for 500 Hrs as perDIN 50021 Standard

    4. Micro Switch rating Test : 5A @ 250V AC,

    0.5A @ 220V DC

    Type Tested For

    Model 1006H

    Type of Instrument OTI / WTI

    Range R1. 0 - 150C.

    R2. 0 - 240C

    No. of Switches S2 - 2switches

    Switch Conguration L - Normally open contactL2 - Changeover contact

    Capillary Length C1 - 1mtsC2 - 2mts....... upto C6 - 6mts

    Union Type U1 - 1/2 BSP MaleU2 - 3/4 BSP MaleU3 - 1 BSP MaleU4 - 1/2 BSP FemaleU5 - 3/4 BSP Female

    If WTI please specify Transformer CT Secondary output..................(1A to 5A)Simulated Temperature rise over top oil........... (5C to 30C)

    Ordering Information

    Note: 1) WTI Gradient is factory set. If required customer can adjust as per requirment. 2) External CCU and Remote Indicator is Part of the scheme.

    Sample Ordering Information :1006H\WTI\R1\S2\L\C3\U2 ........... Amps ...............C

    Registered Office & Works :No. 168/C Industrial Suburb,

    Peenya 3rd Phase, Bangalore - 560058. INDIA

    Phone : + 91-80-4260 2705 / 08

    Fax : + 91-80-4155 2205

    E-Mail : [email protected]

    Branch Office & Works :No. 27,28,30, Block-II, 2ndFloor,

    Sidco Electronics Complex, Guindy, Chennai - 600032. INDIA

    Phone : + 91-44-2250 0191 / 2250 0175

    Fax : + 91-44-2250 0175

    E-Mail : [email protected]

    PRECIMEASURE CONTROLS PVT. LTD.

    Western India Region Office :Mobile : 09377561070

    E-Mail : [email protected]

  • 8/9/2019 OIL LEVEL INDICATOR TRIP CONTACT

    15/34

    www.precimeasure.com

    PRECIMEASURE MODEL - 1006DHDIAL TYPE THERMOMETER for

    DRY TYPE TRANSFORMER

    General Features

    ML : 1006DHSpecifications Model : 1006DH

    Temperature Range 0-2400C

    Dial angular Sweep 2700

    Dial Graduation 20C

    Accuracy Class 1.5% of FSD

    Max.No. of Switches 2

    Switching Range 15% - 85%

    Contact Rating 5A @ 250V AC,

    0.5A @ 220V DCSwitch Differential 10C to 50C (30C20C) Fixed

    Switching Accuracy 40C of Set Value

    Remote Indicator Availbale

    Max. Capillary Length Up to 6 mtrs

    Electrical Connection 1Sq mm. Copper Cable, 1mtr Length

    Degree of Protection IP 55 (IEC-60529)

    High Voltage Test

    Switch Contact - 2.5KV AC,50Hz/60Hz for 1 Minutebetween Switch Terminals to ground

    CCU- 500V AC,50Hz/60Hz for 1 Minute between CCUTerminals to ground

    PSU

    Hybrid Instrument

    This is a high performance temperature Monitoring instrument with built-in PT-100 Sensor (RTD) & CurrentConverter Unit and external Remote indicator with built-in power supply unit

    Winding temperatures Indicator & Controller for Dry Type Transformers / Cast-Resin Transformers with built-inRTD scheme for Independent Remote indication and 4-20mA DC output for SCADA connection.

    Power Supply Unit

    Signal out put 2 nos 4-20 mA DC

    Aux Supply voltage 90-260V AC/DC

    Burden on signal output 600 max including loop resistance

    Temperature range 0-240C

    Degree of protection IP-40

    Temperature range 0-240C

    Signal input 4-20 mA DC

    Aux Supply voltage 90-260V AC/DC

    Communication RS-485MODBUS RTU Communication(Optional)

    Degree of protection IP 20

    Cutout Dimension 92 sq.mm

    Digital Remote indicator

    Remote Indicator 96 Sq

    The fully sealed liquid expansion in the system provides a self powered indication and operation to theinstruments, and does not require any trimming or other periodic adjustments.

    Instruments are fully compensated for ambient temperature.

    Instrument cases are aluminium die casted and polyester powder coated. Each instrument hasanti vibration mountings and are provided with projection mounting clamps.

    A maximum pointer facility is provided, can be reset from outside. All switch contacts are potential free micro switches

    DIALTYPE

  • 8/9/2019 OIL LEVEL INDICATOR TRIP CONTACT

    16/34

    www.precimeasure.com

    1. Protection class : IP55 as per IEC 60529 CAT 2.

    2. Vibration Test : Amplitude 1mm, frequency 50Hz,

    1Hr / X,Y,Z axis

    3. Salt Spray Test : For polyster powder coating and

    SS 304 Armour for 500 Hrs as perDIN 50021 Standard

    4. Micro Switch rating Test : 5A @ 250V AC,

    0.5A @ 220V DC

    Type Tested ForModel 1006DH

    Type of Instrument WTI

    Range R1. 0 - 240C

    No. of Switches S2 - 2switches

    Switch Conguration L - Normally open contactL2 - Changeover contact

    Capillary Length C1 - 1mtsC2 - 2mts....... upto C6 - 6mts

    Ordering Information

    Note: WTI Gradient is factory set. If required customer can adjust as per requirment.

    Sample Ordering Information :1006DH\WTI\R1\S2\L\C4

    Registered Office & Works :No. 168/C Industrial Suburb,

    Peenya 3rd Phase, Bangalore - 560058. INDIA

    Phone : + 91-80-4260 2705 / 08

    Fax : + 91-80-4155 2205

    E-Mail : [email protected]

    Branch Office & Works :No. 27,28,30, Block-II, 2ndFloor,

    Sidco Electronics Complex, Guindy, Chennai - 600032. INDIA

    Phone : + 91-44-2250 0191 / 2250 0175

    Fax : + 91-44-2250 0175

    E-Mail : [email protected]

    PRECIMEASURE CONTROLS PVT. LTD.

    Western India Region Office :Mobile : 09377561070

    E-Mail : [email protected]

  • 8/9/2019 OIL LEVEL INDICATOR TRIP CONTACT

    17/34

    www.precimeasure.com

    PRECIMEASURE MODEL - 1006HXDIAL TYPE THERMOMETER

    Duplex Hybrid OTI / WTI

    ML : 1006HX

    SPECIFICATIONS MODEL : 1006HX

    Temperature Range 0-1500C, 0-2400C

    Dial angular Sweep 2700

    Dial Graduation 20C

    Accuracy Class 1.5% of FSD

    Max.No. of Switches 2

    Switching Range 15% - 85%

    Contact Rating5A @ 250V AC,

    0.5A @ 220V DC

    Switch Differential 10C to 50C (30C20C) Fixed

    Switching Accuracy 2.50C of Set Value

    Remote Indicator Availbale

    Max. Capillary Length Up to 6 Mtrs.

    Switch Test Knob Available

    Electrical Connection 1Sq mm. Copper Cable, 1mtr length

    Degree of Protection IP 55(IEC-60529)

    High Voltage Test

    (a) Local OTI / WTI

    (b) Local OTI / WTI

    (c) CCU

    (d) CCU

    Test Voltage

    2.5 KV AC, 50Hz / 60Hz

    500 V AC, 50Hz / 60Hz

    500 V AC, 50Hz / 60Hz

    2.5 KV AC, 50Hz / 60Hz

    Terminals Details

    Switch connection / CT Connection

    Pt 100 sensor output

    Pt 100 sensor input +4-20mA Output

    CT connection with power supply

    The fully sealed liquid expansion in the system provides a self powered indication and operation to theinstruments, and does not require any trimming or other periodic adjustments.

    Instruments are fully compensated for ambient temperature.

    The WTI instruments have a built in Thermal imaging system for transformers hot spot indication.

    The WTIs are provided with gradient adjustment through a shunt for CT secondary input (1A to 5A).

    Embedded Duplex PT-100 sensorsin the sensing bulb of the local OTI/ WTI provide for amaster indication.

    This output can be connected to Remote Indicator or SCADA or combination of both.

    WTI additional Winding temperature simulator is provided.

    Instrument cases are aluminium die casted and polyester powder coated. Each instrument has

    anti vibration mountings and are provided with projection mounting clamps. A maximum pointer facility is provided, can be reset from outside.

    All switch contacts are potential free micro switches.

    General Features

    PSU

    Remote Indicator 96 Sq

    POWER SUPPLY UNIT - (PSU)

    a. Output Voltage: 24V

    b. Output Signal: Analogue output2nos. 4-20mA DC(Maximum burden 600 OhmsIncluding Loop resistantance)

    c. Auxiliary supply: 90-260V AC/DC

    REMOTE INDICATOR

    a Type : 4 digits, 0.5 Seven Segment LEDs

    b Auxiliary Supply : 90 260V AC/DC

    d Resolution : 0.10C

    e Degree of protection of enclosure : IP-20

    f Operating Temperature Range : 0C to 60C

    g Signal output: 4sets of 4-20mA DC, OptionalRS 485

    h Cutout Dimension: 92Sq.mm

    DIALTYPE

  • 8/9/2019 OIL LEVEL INDICATOR TRIP CONTACT

    18/34

    www.precimeasure.com

    1. Protection class : IP55 as per IEC 60529 CAT 2.

    2. Vibration Test : Amplitude 1mm, frequency 50Hz,

    1Hr / X,Y,Z axis

    3. Salt Spray Test : For polyster powder coating and

    SS 304 Armour for 500 Hrs as perDIN 50021 Standard

    4. Micro Switch rating Test : a) ML - 1006HX:

    5A @ 250V AC,

    0.5A @ 220V DC

    Type Tested ForModel 1006HX

    Type of Instrument OTI / WTI

    Range R1. 0 - 150C.

    R2. 0 - 240C

    No. of Switches S2 - 2switches

    Switch Conguration L - Normally open contactL2 - Changeover contact

    Capillary Length C1 - 1mtsC2 - 2mts....... upto C6 - 6mts

    Union Type U1 - 1/2 BSP MaleU2 - 3/4 BSP MaleU3 - 1 BSP MaleU4 - 1/2 BSP FemaleU5 - 3/4 BSP Female

    CCU Output forindication / Scada

    RI - Remote indicator - T1/T2/T3/T4 (For types, Refer Drawing(Connected through external powersupply PSUs)

    If WTI please specify Transformer CT Secondary output..................(1A to 5A)Simulated Temperature rise over top oil........... (5C to 30C)

    Ordering Information

    Note: WTI Gradient is factory set. If required customer can adjust as per requirment.

    Sample Ordering Information :1006HX\OTI\R2\S2\L\C4\U1\RI-T3 ........... Amps ...............C

    Registered Office & Works :No. 168/C Industrial Suburb,

    Peenya 3rd Phase, Bangalore - 560058. INDIA

    Phone : + 91-80-4260 2705 / 08

    Fax : + 91-80-4155 2205

    E-Mail : [email protected]

    Branch Office & Works :No. 27,28,30, Block-II, 2ndFloor,

    Sidco Electronics Complex, Guindy, Chennai - 600032. INDIA

    Phone : + 91-44-2250 0191 / 2250 0175

    Fax : + 91-44-2250 0175

    E-Mail : [email protected]

    PRECIMEASURE CONTROLS PVT. LTD.

    Western India Region Office :Mobile : 09377561070

    E-Mail : [email protected]

  • 8/9/2019 OIL LEVEL INDICATOR TRIP CONTACT

    19/34

    www.precimeasure.com

    PRECIMEASURE

    The fully sealed liquid expansion in the system provides a self powered indication and operation to theinstruments, and does not require any trimming or other periodic adjustments.

    Instruments are fully compensated for ambient temperature.

    The WTI instruments have a built in Thermal imaging system for transformers hot spot indication.

    The WTIs are provided with gradient adjustment through a shunt for CT secondary input (1A to 5A).

    Instrument cases are aluminium die casted and polyester powder coated. Each instrument has antivibration mountings and are provided with projection mounting clamps.

    A maximum pointer facility is provided, can be reset from outside.

    All switch contacts are potential free micro switches.

    MODEL - 1031DIAL TYPE THERMOMETER

    General Features

    Standard OTI / WTI

    ML : 1031

    SPECIFICATIONS Model : 1031

    Temperature Range 0-1500C

    Dial size 115mm, Segment Dial

    Dial angular Sweep 600

    Dial Graduation 20C

    Accuracy Class 1.5% of FSD

    Max.No. of Switches 2

    Switching Range 15% - 85%

    Contact Rating5A @ 250V AC

    0.5A @ 220V DC

    Switch Differential 10C to 50C (30C20C) Fixed

    Switching Accuracy 2.50C of Set Value

    Max. Capillary Length Up to 6 Mtrs.Electrical Connection 1Sq mm. Copper Cable, 1mtr Length

    Degree of Protection IP 55(IEC-60529)

    High Voltage Test 2.5KV AC, 50Hz/60Hz for 1 minute; All terminal to ground

    DIALTYPE

  • 8/9/2019 OIL LEVEL INDICATOR TRIP CONTACT

    20/34

    www.precimeasure.com

    Model 1031

    Type of Instrument OTI / WTI

    Range R1. 0 - 150C.

    No. of Switches S2 - 2switches

    Switch Conguration L - Normally open contactL2 - Changeover contact

    Capillary Length C1 - 1mtsC2 - 2mts....... upto C6 - 6mts

    Union Type U1 - 1/2 BSP MaleU2 - 3/4 BSP MaleU3 - 1 BSP MaleU4 - 1/2 BSP FemaleU5 - 3/4 BSP Female

    If WTI please specify Transformer CT Secondary output..................(1A to 5A)Simulated Temperature rise over top oil........... (5C to 30C)

    Ordering Information

    Note: WTI Gradient is factory set. If required customer can adjust as per requirment.

    Sample Ordering Information :1031\OTI\R1\S2\L2\C6\U2 ........... Amps ...............C

    1. Protection class : IP55 as per IEC 60529 CAT 2.

    2. Vibration Test : Amplitude 1mm, frequency 50Hz,

    1Hr / X,Y,Z axis

    3. Salt Spray Test : For polyster powder coating and

    SS 304 Armour for 500 Hrs as perDIN 50021 Standard

    4. Micro Switch rating Test : 5A @ 250V AC,

    0.5A @ 220V DC

    Type Tested For

    Registered Office & Works :No. 168/C Industrial Suburb,

    Peenya 3rd Phase, Bangalore - 560058. INDIA

    Phone : + 91-80-4260 2705 / 08

    Fax : + 91-80-4155 2205

    E-Mail : [email protected]

    Branch Office & Works :No. 27,28,30, Block-II, 2ndFloor,

    Sidco Electronics Complex, Guindy, Chennai - 600032. INDIA

    Phone : + 91-44-2250 0191 / 2250 0175

    Fax : + 91-44-2250 0175

    E-Mail : [email protected]

    PRECIMEASURE CONTROLS PVT. LTD.

    Western India Region Office :Mobile : 09377561070

    E-Mail : [email protected]

  • 8/9/2019 OIL LEVEL INDICATOR TRIP CONTACT

    21/34

    www.precimeasure.com

    PRECIMEASURE

    The fully sealed liquid expansion in the system provides a self powered indication and operation to theinstruments, and does not require any trimming or other periodic adjustments.

    Instruments are fully compensated for ambient temperature.

    The WTI instruments have a built in Thermal imaging system for transformers hot spot indication.

    The WTIs are provided with gradient adjustment through a shunt for CT secondary input (1A to 5A). Embedded PT-100 sensorsin the sensing bulb of the local OTI/ WTI provide for a master indication.

    Instrument cases are aluminium die casted and polyester powder coated. Each instrument hasanti vibration mountings and are provided with projection mounting clamps.

    A maximum pointer facility is provided, can be reset from outside.

    All switch contacts are potential free micro switches.

    MODEL - 1031HDIAL TYPE THERMOMETER

    General Features

    Hybrid OTI / WTI

    ML : 1031H SPECIFICATIONS MODEL : 1031H

    Temperature Range 0-1500C

    Dial Size 115mm, Segment Dial

    Dial angular Sweep 600

    Dial Graduation 20C

    Accuracy Class 1.5% of FSD

    Max.No. of Switches 2

    Switching Range 15% - 85%

    Contact Rating5A @ 250V AC,

    0.5A @ 220V DC

    Switch Differential 10C to 50C (30C20C) Fixed

    Switching Accuracy 2.50C of Set Value

    Remote Indicator Availbale

    Max. Capillary Length Up to 6 Mtrs.

    Electrical Connection 1Sq mm. Copper Cable, 1mtr Lenght

    Degree of Protection IP 55(IEC-60529)ML : 2220-R2 (CCU)

    Remote Indicator

    SPECIFICATIONS

    Type 4 digits, 0.5 Seven Segments LEDs

    Auxillary Supply 90 260V AC/DC

    Resolution 0.10C

    Degree of protection of enclosure IP 20

    Operating Temperature Range 00C to 600C

    Signal output 4 sets of 4 - 20mA DC, Optional RS 485Cutout dimension 92 Sq.mm

    High Voltage Test

    (a) Local OTI / WTI

    (b) Local OTI / WTI

    (c) CCU

    (d) CCU

    Test Voltage

    2.5 KV AC, 50Hz / 60Hz

    500 V AC, 50Hz / 60Hz

    500 V AC, 50Hz / 60Hz

    2.5 KV AC, 50Hz / 60Hz

    Terminals Details

    Switch connection / CT Connection

    Pt 100 sensor output

    Pt 100 sensor input +4-20mA Output

    CT connection with power supply

    DIALTYPE

  • 8/9/2019 OIL LEVEL INDICATOR TRIP CONTACT

    22/34

    www.precimeasure.com

    Model 1031H

    Type of Instrument OTI / WTI

    Range R1. 0 - 150C.

    No. of Switches S2 - 2switches

    Switch Conguration L - Normally open contact

    L2 - Changeover contactCapillary Length C1 - 1mts

    C2 - 2mts....... upto C6 - 6mts

    Union Type U1 - 1/2 BSP MaleU2 - 3/4 BSP MaleU3 - 1 BSP MaleU4 - 1/2 BSP FemaleU5 - 3/4 BSP Female

    If WTI please specify Transformer CT Secondary output..................(1A to 5A)Simulated Temperature rise over top oil........... (5C to 30C)

    Ordering Information

    Sample Ordering Information :1031H\WTI\R1\S2\L\C3\U2 ........... Amps ...............C

    1. Protection class : IP55 as per IEC 60529 CAT 2.

    2. Vibration Test : Amplitude 1mm, frequency 50Hz,

    1Hr / X,Y,Z axis

    3. Salt Spray Test : For polyster powder coating and

    SS 304 Armour for 500 Hrs as perDIN 50021 Standard

    4. Micro Switch rating Test : 5A @ 250V AC,

    0.5A @ 220V DC

    Type Tested For

    Note: 1) WTI Gradient is factory set. If required customer can adjust as per requirment. 2) External CCU and Remote Indicator is Part of the scheme.

    Registered Office & Works :No. 168/C Industrial Suburb,

    Peenya 3rd Phase, Bangalore - 560058. INDIA

    Phone : + 91-80-4260 2705 / 08

    Fax : + 91-80-4155 2205

    E-Mail : [email protected]

    Branch Office & Works :No. 27,28,30, Block-II, 2ndFloor,

    Sidco Electronics Complex, Guindy, Chennai - 600032. INDIA

    Phone : + 91-44-2250 0191 / 2250 0175

    Fax : + 91-44-2250 0175

    E-Mail : [email protected]

    PRECIMEASURE CONTROLS PVT. LTD.

    Western India Region Office :Mobile : 09377561070

    E-Mail : [email protected]

  • 8/9/2019 OIL LEVEL INDICATOR TRIP CONTACT

    23/34

    www.precimeasure.com

    PRECIMEASURE DIAL TYPE BI - METALLICTHERMOMETER

    Bi-metallic type thermometer consists of Helical Bimetal Coil, which will expand or contract according to thetemperature changes, which in turn operates indicating pointer.

    General Featuresa No external power supply required for indication or operation.

    a Sealed system which requires no trimming or periodic site adjustments

    a Directly mounted on the Transformer & Other Process Control Equipments.

    a A maximum pointer facility is provided, can be reset from outside.

    a The instruments are capable of working at an ambient temperature range of 00C to +600C.

    MODEL 1070 (THERMOMETER WITHOUT CONTACT, TOP MOUNTING)

    SPECIFICATIONS

    Dial Segment Dial

    Angular Sweep 1050

    Range 0-1200C (Other ranges on request)

    Accuracy 40C Between 400C & 1100C

    Graduation 20C per division

    Instrument Case PDC Aluminum Casting with Polyester Powder Coated.

    ML :1070

    ML :1071

    MODEL 1071 (THERMOMETER WITH 2 CONTACT, TOP MOUNTING)

    SPECIFICATIONS

    Dial Segment Dial

    Angular Sweep 1050

    Range 0-1200C (Other ranges on request)

    Accuracy 40C Between 400C & 1100C

    Graduation 20C per division

    Instrument Case PDC Aluminum Casting with Polyester Powder Coated.

    Max. Number of Switches 2

    Switch Type Micro Switch

    Switch Rating 5A at 240V AC

    Switches Normally Open Type or Changeover Type

    Adjustable Range 200C 1050C

    Accuracy of switch setting 40C of Set Value

    Switch Differential Range 60C30C

    Contact Type Potential Free

    Cable Gland (Polyamide / Brass) Cable Gland Size PG16

    High Voltage Test 2KV AC, 50/60 Hz for 1 Minute, All terminals to ground

    BI-METALLIC

  • 8/9/2019 OIL LEVEL INDICATOR TRIP CONTACT

    24/34

    www.precimeasure.com

    MODEL 1068 (4" DIAL THERMOMETER WITH 2 CONTACT, HORIZONTAL MOUNTING)

    SPECIFICATIONS

    Dial Round Dial 4

    Angular Sweep 1350

    Range 0-1200C (Other ranges on request)

    Accuracy 40C Between 400C & 1100C

    Graduation 20C per division

    Instrument Case PDC Aluminum Casting with Polyester Powder Coated

    * The WTI instruments have a built in Thermal imaging system for transformers hotspot indication.

    * WTI Gradient calibration is factory set as per customer specication. If required, aprovision is made for small adjustment at site.

    MODEL 1071 WTI (THERMOMETER WITH 2 CONTACT, TOP MOUNTING)WINDING TEMPERATURE INDICATOR :

    SPECIFICATIONS

    Dial Segment Dial

    Angular Sweep 1050

    Range 0-1200C (Other ranges on request)

    Accuracy 40C Between 400C & 1100C

    Graduation 20C per division

    Instrument Case PDC Aluminum Casting with Polyester Powder Coated

    Max. Number of Switches 2

    Switch Type Micro Switch

    Switch Rating 5A at 240V AC

    Switches Normally Open Type or Changeover Type

    Adjustable Range 200C 1050C

    Switching Accuracy 40C of Set Value

    Switch Differential 60C30C

    Contact Type Potential Free

    Cable Gland (Polyamide / Brass) Cable Gland Size PG11-2Nos

    High Voltage Test 2KV AC, 50Hz for 1 Minute, All terminals to ground

    ML :1071-WTI

    Registered Office & Works :No. 168/C Industrial Suburb,

    Peenya 3rd Phase, Bangalore - 560058. INDIA

    Phone : + 91-80-4260 2705 / 08

    Fax : + 91-80-4155 2205

    E-Mail : [email protected]

    Branch Office & Works :No. 27,28,30, Block-II, 2ndFloor,

    Sidco Electronics Complex, Guindy, Chennai - 600032. INDIA

    Phone : + 91-44-2250 0191 / 2250 0175

    Fax : + 91-44-2250 0175

    E-Mail : [email protected]

    PRECIMEASURE CONTROLS PVT. LTD.

    Western India Region Office :Mobile : 09377561070

    E-Mail : [email protected]

    Max. Number of Switches 2

    Switch Type Micro Switch

    Switch Rating 5A at 240V AC

    Switches Normally Open Type or Changeover Type

    Adjustable Range 400C 1050C

    Accuracy of switch setting 40C of Set Value

    Switch Differential Range 60C30CContact Type Potential Free

    Cable Gland (Polyamide / Brass) Cable Gland Size PG16

    High Voltage Test 2KV AC, 50/60 Hz for 1 Minute, All terminals to ground

    ML :1068

  • 8/9/2019 OIL LEVEL INDICATOR TRIP CONTACT

    25/34

    www.precimeasure.com

    PRECIMEASURE

    ML :1075

    DIAL TYPE BI - METALLICTHERMOMETER

    MODEL 1075 (3 DIAL HORIOZONTAL MOUNTING WITHMAXIMUM POINTER)

    SPECIFICATIONS

    Dial Round Dial 3

    Angular Sweep 2400

    Range 0-1200C (Other ranges on request)

    Accuracy 40C Between 400C & 1100C

    Graduation 20C per divisionInstrument Case SS-304 Case (Natural Finish).

    MODEL 1073 (4 DIAL TOP MOUNTING WITH MAXIMUM POINTER)

    SPECIFICATIONS

    Dial Round Dial 4

    Angular Sweep 2400

    Range 0-1200C (Other ranges on request)

    Accuracy 40C Between 400C & 1100C

    Graduation 20C per division

    Instrument Case SS-304 Case (Natural Finish)

    MODEL 1074 (6 DIAL TOP MOUNTING WITH MAXIMUM POINTER)

    SPECIFICATIONS

    Dial Round Dial 6

    Angular Sweep 2400

    Range 0-1200C (Other ranges on request)

    Accuracy 40C Between 400C & 1100C

    Graduation 20C per division

    Instrument Case SS-304 Case (Natural Finish).

    ML :1073 / 1074

    BI-METALLIC

  • 8/9/2019 OIL LEVEL INDICATOR TRIP CONTACT

    26/34

    www.precimeasure.com

    ML :1078

    1. Protection class : IP55 as per IEC 60529 CAT 2.

    2. Salt Spray Test : Model-1068 / 1070 / 1071 For polyster powder coating

    500 Hrs as per DIN 50021Standard

    All the Models Type Tested For :

    MODEL 1078 (3 DIAL TOP MOUNTING WITH MAXIMUM POINTER)

    SPECIFICATIONS

    Dial Round Dial 3

    Angular Sweep 2400

    Range 0 -1200C (Other ranges on request)

    Accuracy 40C Between 400C & 1100C

    Graduation 20C per division

    Instrument Case SS-304 Case (Natural Finish).

    ML :1079

    MODEL 1079 (3 DIAL ENTRY AT ANGLE 450WITH MAXIMUM POINTER)

    SPECIFICATIONS

    Dial Round Dial 3

    Angular Sweep 2400

    Range 0 -1200C ( Other ranges on request)

    Accuracy 40C Between 400C & 1100C

    Graduation 20C per division

    Instrument Case SS-304 Case (Natural Finish).

    Registered Office & Works :No. 168/C Industrial Suburb,

    Peenya 3rd Phase, Bangalore - 560058. INDIA

    Phone : + 91-80-4260 2705 / 08

    Fax : + 91-80-4155 2205

    E-Mail : [email protected]

    Branch Office & Works :No. 27,28,30, Block-II, 2ndFloor,

    Sidco Electronics Complex, Guindy, Chennai - 600032. INDIA

    Phone : + 91-44-2250 0191 / 2250 0175

    Fax : + 91-44-2250 0175

    E-Mail : [email protected]

    PRECIMEASURE CONTROLS PVT. LTD.

    Western India Region Office :Mobile : 09377561070

    E-Mail : [email protected]

  • 8/9/2019 OIL LEVEL INDICATOR TRIP CONTACT

    27/34

    www.precimeasure.com

    PRECIMEASURE

    ML :2241B

    MODEL 2241B & 2242 WINDING TEMPERATURE INDICATOR / CONTROLLER FOR DRY TYPE TRANSFORMERS

    APPLICATION :MODEL 2241B/2242/2244T3 is designed for monitoring the temperatures of L.V. windings of the Dry-Type Transformer / Cast ResinTransformers. It will display winding temperatures and take necessary control action as per set and differential values programmedby the user. The protection system also records maximum temperatures and will display the same along with corresponding channelnumber whenever relevant push button is pressed.

    SALIENT FEATURES :

    a Power line lter with Fuse is incorporated in the input of the power supply to protect the equipment from High Energy Surgeand Electrical Fast Transient.

    a High Scanning Speed

    a Remote Indication & Data Acquisition facility with burden upto 600 ohms.

    a Optional RS-485 MODBUS RTU Communication

    ML :2242

    SPECIFICATIONS Model 2241B Model 2242

    Temperature Sensorinput

    RTD (Pt-100 DIN 43760) K Type thermocouples

    No. of Sensor inputs Four, Eight & Twelve Three

    No. of Set-points Three (Fan, Alarm and Trip) Four (Alarm, Trip, Fan1,Fan2)

    Range 00C -3000C 00C 2500C

    Resolution 0.10C 10C

    Accuracy 10C 0.8%, one count undernormal conditions.

    Display Speed User Settable (1-99 Seconds) 5 Seconds

    Display Six Nos. 0.5 Seven Segment LEDs Four nos 0.5 Seven Seg-ment LEDs

    Auxiliary Supply Voltage 90-260 V AC/DC 0-20V AC or 0-240V AC

    Output Analogue output DC 4-20mA(Maximum burden 600 Ohms)

    Analogue O/P DC0-1mA (10000 Ohms)4-20mA(600 Ohmsburden)

    Communication Isolated RS-485 MODBUS RTUCommunication (Optional).

    RS-485 & RS-232Communication

    Contact Rating @Resistive Load

    5A @ 220 VAC / 5A @ 30 DC Alarm & Trip 10A@120VAC & 8A@240 VAC, Fan1& Fan2 30A@120/240VAC

    Power Consumption 5 Watts 8 Watts

    Weight 2Kgs. Approx without packing box 2kgs Approx. withoutpacking box

    Enclosure Aluminium Pressure Diecastingenclosure, powder coated all sideswith acrylic viewing window, IP-55

    Panel Mount thru CutoutIndoor Mounting only

    Operating conditions Temp:-300C to 700C Temp : -300C to 550C

    Electronic TemperatureControllers

    Model: 2241B

    1. Cold and Dry Test : -30C to +70C

    2. Vibration Test : Amplitude 1mm,frequency 50Hz, 1Hr / X,Y,Z axis

    Model: 2242

    1. Shock Test : 11ms/15g Procedure as per the

    IS: 13779 (12 shots)2. Vibration Test : Amplitude 0.5mm,

    Frequency 05 to 50Hz,02 sweeps / X,Y,Z axis

    Type Tested For

    ELECTRONIC

  • 8/9/2019 OIL LEVEL INDICATOR TRIP CONTACT

    28/34

    www.precimeasure.com

    SPECIFICATIONS

    Temperature Sensor input RTD (PT-100 DIN 43760)

    No. of Sensor inputs one

    No. of Set-points Two (Alarm,Trip)

    Range 00C 2000C (Other Ranges on Request)

    Resolution 10C

    Accuracy 1%

    Display Speed -

    Display Three nos 0.5 Seven Segment LEDs

    Auxiliary Supply Voltage 90-260V AC/DC (Other voltages on Request)

    Output Analogue output DC 4-20mA (Maximum burden 600 Ohms)

    Communication -

    Contact Rating @ Resistive Load 5A@220 VAC / 5A@30 VDC

    Power Consumption 2 Watts

    Weight 0.5kgs Approx. without packing box.

    Enclosure 96 Sq mm ABS Box Enclosure Panel Mount through Cutout,

    IP-20Operating conditions Temp : 00C to 600C

    SPECIFICATIONS

    Temperature Sensor input RTD (PT-100 DIN 43760)

    No. of Sensor inputs Four

    No. of Set-points Three (Fan, Alarm and Trip)

    Range -20 to+3000C / 0 - 3000C

    Resolution 10C

    Accuracy 20C

    Display Speed User Settable (1- 30 Seconds)

    Display 4 Nos. 0.5 Seven Segment LEDs

    Auxiliary Supply Voltage 90-260 V AC/DC

    Output Analogue output DC 4-20mA (Maximum burden 600 Ohms)

    Communication RS-485 MODBUS RTU Communication (Optional)

    Contact Rating @ Resistive Load 5A @ 220 VAC / 5A @ 30 VDC

    Power Consumption 5 Watts

    Weight 0.5Kgs Approx without packing

    Enclosure 96 Sq mm ABS Box Enclosure Panel Mount through Cutout,IP-20

    Operating conditions Temp: 00C to 600C

    ML : 2253

    ML : 2244T3

    MODEL 2244T3 & 2253 WINDING TEMPERATURE INDICATOR / CONTROLLER FOR DRY TYPE TRANSFORMERS

    APPLICATION :

    MODEL 2244T3 & 2253 is designed for monitoring the temperatures of L.V. windings of the Dry-Type Transformer / Cast ResinTransformers. It will display winding temperatures and take necessary control action as per set and differential values programmedby the user. The protection system also records maximum temperatures and will display the same along with correspondingchannel number whenever relevant push button is pressed.

    SALIENT FEATURES :

    a Power line lter with Fuse is incorporated in the input of the power supply to protect the equipment from High Energy Surgeand Electrical Fast Transient.

    a High Scanning Speed

    a Remote Indication & Data Acquisition facility with burden upto 600 ohms.

    a Optional RS-485 MODBUS RTU Communication

    Electronic TemperatureControllers

    Registered Office & Works :

    No. 168/C Industrial Suburb,Peenya 3rd Phase, Bangalore - 560058. INDIA

    Phone : + 91-80-4260 2705 / 08

    Fax : + 91-80-4155 2205

    E-Mail : [email protected]

    Branch Office & Works :

    No. 27,28,30, Block-II, 2nd

    Floor,Sidco Electronics Complex, Guindy, Chennai - 600032. INDIA

    Phone : + 91-44-2250 0191 / 2250 0175

    Fax : + 91-44-2250 0175

    E-Mail : [email protected]

    PRECIMEASURE CONTROLS PVT. LTD.

    Western India Region Office :Mobile : 09377561070

    E-Mail : [email protected]

  • 8/9/2019 OIL LEVEL INDICATOR TRIP CONTACT

    29/34

    www.precimeasure.com

    PRECIMEASURE Electronic TemperatureControllers

    SPECIFICATION :

    DESCRIPTION DETAILS

    Temperature Sensor input RTD (Pt 100 DIN 43760)

    No. of sensor inputs ONE

    CT Sec Current Input 1.0A to 5.0A (User Selectable)

    Temperature Rise 10C to 450C (User Selectable)

    No. of Set-points OTI Two Relays for Alarm and Trip (1C/O SPDT Relay

    contacts)No. of Set-points WTI Four Relays for Alarm, Trip, Fan 1 and Fan 2

    (1C/O SPDT Relay contacts)

    Contact Rating 5A @ 220 VAC / 5A @ 30 VDC Resistive Load

    Range 0-1500C

    Resolution 0.10C

    Accuracy 10C

    Display 0.5 Seven Segment LED Display

    Auxiliary Supply Voltage 90-260 V AC/DC

    Signal Outputs Two analogue Outputs (4-20mA Suitable for 600Ohms Burdon) Each 1 No.

    Power Consumption 5 Watts (Max.)

    Weight 2 Kgs Approx. without packing

    Enclosure Aluminium Pressure Die Casting enclosure,powder coated with acrylic viewing window, IP-55

    Communication RS-485 MODBUS RTU (Optional)

    Operating Temperature -300C to 700C

    MODEL 2243A OTI / WTI TEMPERATURE INDICATOR / CONTROLLER

    APPLICATION :

    This scheme is used to Indicate Oil & Winding Temperature of the oil immersed transformers. Relays are provided for Alarm, Trip

    and Cooler Duties, are operated as per the set value. 4-20mA DC signal outputs are provided separately for OTI & WTI for RemoteIndication or SCADA Purpose. The System has the facility to store the maximum temperature attained.

    SCHEME CONSISTS OF :1. PT -100 Sensor 1 No. 2. Electronic Temperature Controller 1 No. 3. Thermometer Pocket 1 No. (Optional)

    ML : 2243A

    ML : 2246

    Model: 2243A

    1. Cold and Dry Test : -30C to +70C

    2. Vibration Test : Amplitude 1mm,

    frequency 50Hz, 1Hr / X,Y,Z axis

    Type Tested For

    MODEL 2246 TAP POSITION INDICATOR

    SPECIFICATIONS MODEL 2246

    Signal Input Resistance (1Kohms per step)

    Range 1-39 Position (User settable)

    Display 3 nos. 0.5 7 Segment LEDS

    Auxiliary Supply Voltage 90-260 V AC/DC

    Out put Four sets of 4-20 mA DC ( MaximumBurndon 600 Ohms)

    Communication RS - 485 Modbus RTU Communication(Optional)

    Power Consumption 5 Watts (Max.)

    Weight 0.5Kgs Approx. without packing

    Enclosure 96 sq mm ABS Box Enclousure PanelMount through cutout IP-20

    Operating Temperature 00C to 600C

    ELECTRONIC

  • 8/9/2019 OIL LEVEL INDICATOR TRIP CONTACT

    30/34

    www.precimeasure.com

    Electronic TemperatureControllers

    ELECTRONIC TYPE

    MODEL 2220-R1 & 2220-R2 TEMPERATURE INDICATOR

    APPLICATION : PRECIMEASURE Electronic Instruments are designed to indicatethe Top Oil Temperature / Winding Temperature of the oil-immersed transformersin remote control room. This scheme has 2 Nos of 4-20 mA DC Signal outputsproportional to the temperature range. Signal OUTPUT 1 is connected to anindicator for indicating temperature at remote and OUTPUT 2 can be connectedto Recorder or Data Acquisition System.

    SCHEME CONSISTS OF :

    1. PT -100 Sensor 1 No.

    2. Current Converter Unit 1 No.

    3. Remote Indicator 1 No.

    4. Thermometer Pocket 1 No. (Optional)

    SPECIFICATIONS :

    SL. DESCRIPTION MODEL 2220 R1 MODEL 2220 R2

    1 PT 100 SENSOR ASSEMBLY

    a. Element : Simplex, 3 wire system / Duplex, 6 Wire System

    b. Tolerance : DIN 43760, Class B

    2 CURRENT CONVERTER UNIT WITH POWER SUPPLY UNIT

    a Signal Input : PT 100 RTD, Simplex 3 wire

    b Auxiliary Supply : 90 260V AC/DC

    c Signal Outputs : 4 20mA DC corresponding to temperature range

    d Burden on Output Signal : 600 Ohms maximum including loop resistance

    e Accuracy of Signal Output : 1% of F.S.D.

    f Degree of protection of enclosure IP-55 IP-40

    g Casing Aluminium Casting. ABS, DIN Enclosure Box.

    3 REMOTE INDICATOR

    a Type : 4 digits, 0.5 Seven Segment LEDs

    b Auxiliary Supply : 90 260V AC/DC

    c Temperature indicator range : 0-1500C (Other ranges on request)

    d Resolution : 0.10C

    e Degree of protection of enclosure : IP-20

    Model: 2220-R1& 2220-R21. 2220-R1, Protection class :

    IP55 as per IEC 60529 CAT 2.

    2. 2220-R2, Protection class:IP40 as per IEC 60529 CAT 2

    3.Cold and Dry Teast :-30C to +70C

    4.Vibration Test :Amplitude 1mm, frequency50Hz,1Hr / X,Y,Z axis

    5. EMI / EMC Test :a) Electrostatic Discharge

    Immunity Test as perIEC61000-4-2, 2001

    b) Electrical Fast TransientImmunity Test as perIEC61000-4-4, 2004

    c) High Energy SurgeImmunity Test as perIEC61000-45, 2005

    Type Tested For

    Registered Office & Works :

    No. 168/C Industrial Suburb,Peenya 3rd Phase, Bangalore - 560058. INDIA

    Phone : + 91-80-4260 2705 / 08

    Fax : + 91-80-4155 2205

    E-Mail : [email protected]

    Branch Office & Works :

    No. 27,28,30, Block-II, 2nd

    Floor,Sidco Electronics Complex, Guindy, Chennai - 600032. INDIA

    Phone : + 91-44-2250 0191 / 2250 0175

    Fax : + 91-44-2250 0175

    E-Mail : [email protected]

    PRECIMEASURE CONTROLS PVT. LTD.

    Western India Region Office :Mobile : 09377561070

    E-Mail : [email protected]

  • 8/9/2019 OIL LEVEL INDICATOR TRIP CONTACT

    31/34

    www.precimeasure.com

    PRECIMEASURE

    Ordering Information

    Model 1080 - 4" & 6"

    MODEL: 1090SIZE: 1 B.S.P MALE

    SPECIFICATIONS :

    Liquid in Tank Transformer oil to IS 335 and or any other Oil

    Working Temperature -30 to 100C of oil

    Working Pressure 0 to 4 Kg / Cm2

    Working Environment Indoor or Outdoor

    INDICATION :

    Dial size 4" & 6" RoundColor Black marking on white background orany other combination as required. Standard

    Red Line Indication for Min. to Empty LevelAngular Sweep 300

    FLOAT (SENSOR) AND ARM :

    Material Float :Polyurethane Foam/Brass

    Float Arm : Brass

    Float-Arm Length Fixed Length as given by Customer

    Travel Max. 45 Below & Above from the centre

    Margin Leave Min. 40 mm beyond lower & higherlimit markings to avoid striking of oat tobottom & top of conservator.

    SWITCH :

    Type Micro switchContact Rating 5A @ 240V AC, 0.25A 220V DC

    MAGNETIC OIL LEVELGUAGE

    APPLICATION:

    Magnetic Oil Level Gauge (MOG) is used to Measure Oil Level of oil lled Transformers & Oil lled Tanks.

    Model No 1080/4

    Float Arm Length

    Conservator Diameter

    Mounting Vertical/Inclined

    If Inclined Mention Angle

    And other Specications if any

    Type Tested For

    1. Protection class : IP55 as per IEC 60529 CAT 2.

    2. Vibration Test : Amplitude 1mm, frequency 50Hz,

    1Hr / X,Y,Z axis

    PRESSURE RELIEF DEVICE

    APPLICATION:PRD is a safety device for the distribution transformer up to 5000KVA, OLTC and other similarequipments. This PRD is used to prevent heavy damages of the tank in case of sudden rise ofinternal pressure.

    OPERATING PRESSURE :Operating Pressure range available from 0.2 to 0.7 kg/sq.cm with tolerance0.05 kg/sq.cm.

    Safe spring loaded design that does not require external power supply for operation

    Positive downward directional ow limits horizontal spraying of hot oil on adjacent equipment

    Large diameter top cover with improved operating force providing better protection

    Transport safety clip to prevent oil spillage during transportation of oil lled transformers

    Available in brass or Zamak body construction

    General Features

    OTHERS

  • 8/9/2019 OIL LEVEL INDICATOR TRIP CONTACT

    32/34www.precimeasure.com

    PRECIMEASUREBEARING / AIR

    TEMPERATURE INDICATOR /CONTROLLER

    APPLICATION :

    This Instruments is used for monitoring and controlling the Bearing/ Air Temperature of the Motor and Generators

    Model 1006 - BTD/ATD

    SPECIFICATIONS :

    Temperature Range 0-150C (Other Rangeson request)

    Dial Size 150mm (6") Round

    Dial Angular Sweep 270

    Dial Graduations 2C per Division

    Accuracy Class 1.5% of F.S.D

    Max. No. of Switches 2

    Switch Setting 15% to 85%

    Switch Contact Rating 5A at 250 V AC & 0.5Aat 220V DC

    Switch Differential 3 C 2 C (Fixed)

    Accuracy of Switch Setting 2.5C of Set Value

    Max. Capillary Length Up to 15 Meters

    Mounting Flush / Projection

    1. Protection class : IP55 as per IEC 60529 CAT 2.

    2. Vibration Test : Amplitude 1mm, frequency 50Hz,

    1Hr / X,Y,Z axis

    3. Micro Switch rating Test :

    5A @ 250V AC &0.5A @ 220V DC

    Type Tested For

    Registered Office & Works :

    No. 168/C Industrial Suburb,Peenya 3rd Phase, Bangalore - 560058. INDIA

    Phone : + 91-80-4260 2705 / 08

    Fax : + 91-80-4155 2205

    E-Mail : [email protected]

    Branch Office & Works :

    No. 27,28,30, Block-II, 2nd

    Floor,Sidco Electronics Complex, Guindy, Chennai - 600032. INDIA

    Phone : + 91-44-2250 0191 / 2250 0175

    Fax : + 91-44-2250 0175

    E-Mail : [email protected]

    PRECIMEASURE CONTROLS PVT. LTD.

    Western India Region Office :Mobile : 09377561070

    E-Mail : [email protected]

    PORTABLE OIL BATH

    Model HOB -180For OTI & WTI Caliberation

    DISPLAY SPECIFICATION

    Range Ambient +5C To 180C

    Display Dual 4 Digit Display

    Disply Resolution 0.1C

    Temp-Setting With Push Button Data Entry

    GENERAL SPECIFICATION

    System Acuracy Better Then 0.5% Of Reading Or 0.5%C(Which Ever Is Higher)

    Stability Better Then 0.5%C

    Set Point Archive Time Approx. 30 Minutes

    Stabilization Time Approx. 20 Minutes After Reaching Set Value

    ELECTRICAL SPECIFICATION

    Power Consumption 300 Watts Approx.

    Power Supply 230Vac, 50Hz

    PHYSICAL SPECIFICATIONDimensions 6 (W) X 14 (H) X 9(L)

    Weight 5.5 Kgs Approx.

    Heating Media Silicon Oil / Transformer Oil

    Oil Volume 1.5 Ltr Approx

    Well Depth 160 mm

    Accessories Drain Locking O Ring

    Stirring By Mechanical Stirrer Of Ig Motor

  • 8/9/2019 OIL LEVEL INDICATOR TRIP CONTACT

    33/34

  • 8/9/2019 OIL LEVEL INDICATOR TRIP CONTACT

    34/34

    SCHEM

    EDRAWING