Asset: P.S. 1 - BROOKLYN, 309 47 STREET, , New York, 11220
Inspection Id Inspection Type Time In Last Edited
SA : K001 Architectural - Senior 2018-12-27 9:09 AM 2019-06-04 2:26 PM
AA : K001 Architectural - Associate 2018-12-27 8:47 AM 2018-12-27 5:34 PM
Asset Data
Question Answer
Was the building fully accessible for inspection No
Inspection Access Comment The following components are inaccessible: 2nd Floor Shower Roomdue to Storage.
Principal(s) Information
Principal Name Arlene Ramos
Organization P.S. 1 - Brooklyn
Did you meet with this Principal? No
Did this Principal provide feedback? Yes
Summary of Principal's Feedback A Principal questionnaire was returned with the following comments:1. The air conditioning system does not function properly. 2.Ventilation system in the building needs to be serviced.
Custodian Was not present
Fireman Noel Roman
Building Square Footage 91000
Comments on the Area None
Comments on the Stories (Floors) plus Basements 3+B
Comments on the Number of Classrooms 43
Comments on the Year Built 1965
Student Population 1076
Staff Population 139
Weather Fair
Facade Photo
46th Street-South View
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K001
PB/A&W Print Date: 6/21/2019Page 1 of 37
Main Entrance Photo
Facade A - Entry Court
Roof Photo
Roof 1-North View
Have any Systems/Major Building Components been upgraded? Yes
Systems: Partial Interior Door replacement (Auditorium, Cafeteria,Classrooms)
Year: 2017
Systems: Boiler/Mechanical Systems upgrade, Partial Exterior Doorreplacement
Year: 2016
Systems: Chimney Liner replacement
Year: 2015
Systems: Exterior Modernization including full Windows, Guards,Lintels replacement; full Parapets, Coping, Flashing, RoofBarrier replacement; full Bulkhead Windows and Doorsreplacement; full Exterior Wall repointing and graffitiremoval; Partial Exterior Doors replacement and Transomrepair
Year: 2014
Systems: Vinyl Floor replacement 1st Floor Corridor; PartialExterior Door Repairs
Year: 2013
Systems: Partial Interior Glazed Block repairs at Gymnasium
Year: 2011
Systems: Exterior Modernization including full Roof replacement atRoof 1, Flashing, Parapets, Coping, Leaders and Gutters,Bulkhead Doors replacement; full Plaza Deckreplacement; Partial Exterior Wall repairs
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K001
PB/A&W Print Date: 6/21/2019Page 2 of 37
Roof 1, Flashing, Parapets, Coping, Leaders and Gutters,Bulkhead Doors replacement; full Plaza Deckreplacement; Partial Exterior Wall repairs
Year: 2010
Systems: Auditorium upgrades including new Seating, Curtains,Vinyl Flooring, Wall repainting, Soundproof paneling, onenew HC Lift at Stage; second new HC lift at Foyer intoAuditorium and Gymnasium, Sidewalk replacement at46th and 47th Streets
Year: 2007
Systems: Library upgrades
Year: 2004
Have there been any New Building Additions? No
Tandem Schools? No
Leased Space? No
Priority Condition
PriorityCondition ExistLast Year?
PriorityCategory
ConditionDescription
ComponentAffected
LocationDescription
Person(s)Notified
Person(s) Title PhotoImage
No condition recorded
Structural Engineer Required
StructuralCondition Type
ConditionDescription
ComponentAffected
LocationDescription
Person(s)Notified
Person(s) Title PhotoImage
No condition recorded
Accessibility
Accessibility Status Question Response
Is the primary or secondary entrance on an accessible route? Yes
Is the building a multi-story building? Yes
Are all floors of the building accessible through compliant means? No
Are SOME floors other than the 1st floor and basement accessible through compliantmeans?
No
Do any of the following spaces exist on the First floor? Classroom, Art Room,Auditorium, Cafeteria, Computer, Gymnasiums, Library, Multipurpose Room, ScienceLabs
Yes
For the rooms that do exist, are SOME of them accessible on the 1st floor? Yes
Boys and Girls or Unisex accessible toilets exist on the 1st floor? No
Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem
FireAlarmStrobe
FUNCTIONAL ACCESSIBILITY
Exterior Routes
Exterior Entrances & Exits Yes
Exterior H/C Lifts No No
Exterior Ramps and Railings Yes Yes
Interior Routes
Corridor and Lobby H/C Lifts No No
Interior Corridor Doors and Hardware No No
Interior Corridors and Lobbies Yes
Interior Elevators No
Interior Lobby Doors and Hardware Yes
Interior Ramps No
Rooms & Spaces
Art Rooms Room B15 Yes No Not on Accessible Route
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K001
PB/A&W Print Date: 6/21/2019Page 3 of 37
Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem
FireAlarmStrobe
Rooms & Spaces
Auditorium 1st Floor Yes No No Stage AccessNot on Accessible Route
No Yes
Cafeteria Basement Yes No Not on Accessible Route No Yes
Classrooms None on Accessible Route Yes No Not on Accessible Route
Computer Rooms No
Gymnasium 1st Floor Yes No Not on Accessible Route No Yes
Library Room 236 Yes No Not on Accessible Route
Main Office Room 135 Yes No Not on Accessible Route
Multi-purpose Room No
Nurse's Room Room 131 Yes No Not on Accessible Route
Pool No
Science Lab No
Toilet Rooms (Boys) None on Accessible Route Yes No Not on Accessible Route
Toilet Rooms (Girls) None on Accessible Route Yes No Not on Accessible Route
Toilet Rooms (Staff) None on Accessible Route Yes No Not on Accessible Route
Building Template
Inspection
Question Response
Architectural
EXTERIOR Inspected
AREAWAY Does not Exist
AWNINGS AND CANOPIES Does not Exist
CHIMNEY Inspected
Material Type(s) Masonry
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
COPING Inspected
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K001
PB/A&W Print Date: 6/21/2019Page 4 of 37
Question Response
EXTERIOR
COPING
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
CORNICE Does not Exist
DOORS Inspected
DOORS AND FRAMES Inspected
Condition 4 - Between Fair and Poor
Deficiency ROLL-UP DOOR: DETERIORATED DOOR - MAJORDETERIORATION
Roof Plan reference
Deficiency Quantity 2
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade B
Violations No violations recorded.
Deficiency METAL CLAD: DETERIORATED DOOR - MINORDETERIORATION
Roof Plan reference
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K001
PB/A&W Print Date: 6/21/2019Page 5 of 37
Question Response
EXTERIOR
DOORS
DOORS AND FRAMES
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade C-Exit 11
Violations No violations recorded.
Deficiency METAL CLAD: DETERIORATED DOOR AND FRAME - MINORDETERIORATION
Roof Plan reference
Deficiency Quantity 3
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade B-Exit 6
Violations No violations recorded.
DOOR HARDWARE Inspected
Condition 3 - Fair
Deficiency No deficiencies recorded
LINTELS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
TRANSOM/SIDE LIGHT Inspected
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K001
PB/A&W Print Date: 6/21/2019Page 6 of 37
Question Response
EXTERIOR
DOORS Inspected
TRANSOM/SIDE LIGHT
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
EXTERIOR WALLS Inspected
Material Type(s) Masonry, Other
Replacement Quantity 35,000
Replacement Uom S.F.
InspectedInstance on All Facades
Instance Condition 3 - Fair
Instance Quantity 35,000
Instance Quantity Uom S.F.
Deficiency STUCCO CEMENT SURFACE: CRACKS, SPALLING
Roof Plan reference
Elevation
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade A
Violations No violations recorded.
Deficiency BRICK: OPEN JOINTS
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K001
PB/A&W Print Date: 6/21/2019Page 7 of 37
Question Response
EXTERIOR
EXTERIOR WALLS Inspected
Roof Plan reference
Elevation
Deficiency Quantity 1,300
Quantity Uom S.F.
Potential Action REPOINT
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade E
Violations No violations recorded.
EXTERIOR SOFFITS Inspected
Condition 2 - Between Good and Fair
Deficiency CONCRETE: MINOR CRACKS/SPALLING
Roof Plan reference
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K001
PB/A&W Print Date: 6/21/2019Page 8 of 37
Question Response
EXTERIOR
EXTERIOR SOFFITS
Elevation
Deficiency Quantity 75
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade B
Violations No violations recorded.
LOADING DOCK Does not Exist
LOUVER Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
PARAPETS Inspected
Material Type(s) Masonry
Replacement Quantity 5,500
Replacement Uom C.F.
InspectedInstance on All Facades
Instance Condition 2 - Between Good and Fair
Instance Quantity 5,500
Instance Quantity Uom C.F.
Deficiency No deficiencies recorded
PLAZA DECK Inspected
InspectedInstance on Pavers: Above Cafeteria
Instance Condition 1 - Good
Instance Quantity 5,000
Instance Quantity Uom S.F.
Installation Year 2010
Source of Installation Custodial Staff
Deficiency No deficiencies recorded
ROOF Inspected
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K001
PB/A&W Print Date: 6/21/2019Page 9 of 37
Question Response
EXTERIOR
ROOF
Roofing Inspected
Replacement Quantity 30,000
Replacement Uom S.F.
ROOF HATCH/SMOKE HATCH Does not Exist
LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
ROOF BARRIER Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
ROOF CAGE Does not Exist
ROOF FENCE Does not Exist
ROOFING Inspected
InspectedInstance on Built-Up: Roof 2-4
Instance Condition 3 - Fair
Instance Quantity 9,000
Instance Quantity Uom S.F.
Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?
No
Installation Year 1995
Source of Installation Custodial Staff
Deficiency BUILT-UP: FLASHING: CAP FLASHING DAMAGED
Roof Plan reference
Deficiency Quantity 10
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 2
Violations No violations recorded.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K001
PB/A&W Print Date: 6/21/2019Page 10 of 37
Question Response
EXTERIOR
ROOF
Roofing
ROOFING
Deficiency BUILT-UP: ROOFING: LOSS OF GRAVEL
Roof Plan reference
Deficiency Quantity 100
Quantity Uom S.F.
Potential Action INSTALL NEW GRAVEL
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 2
Violations No violations recorded.
Deficiency BUILT-UP: ROOFING: BEYOND USEFUL LIFE
Deficiency Location/Instance Built-Up: Roof 2-4
Deficiency Quantity 9,000
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 1
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
InspectedInstance on Modified Bitumen: Roof 1
Instance Condition 2 - Between Good and Fair
Instance Quantity 21,000
Instance Quantity Uom S.F.
Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?
No
Installation Year 2010
Source of Installation Custodial Staff
Deficiency No deficiencies recorded
ROOFING DRAINS Inspected
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K001
PB/A&W Print Date: 6/21/2019Page 11 of 37
Question Response
EXTERIOR
ROOF
Roofing
ROOFING DRAINS
Condition 3 - Fair
Deficiency DETERIORATED
Roof Plan reference
Deficiency Quantity 1
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 2
Violations No violations recorded.
Specialties Inspected
BULKHEAD/PENTHOUSE Inspected
Condition 3 - Fair
Deficiency BULKHEAD/PENTHOUSE WALLS/INTERIOR: CMUCRACKS/SPALLING
Roof Plan reference
Deficiency Quantity 25
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K001
PB/A&W Print Date: 6/21/2019Page 12 of 37
Question Response
EXTERIOR
ROOF
Specialties
BULKHEAD/PENTHOUSE
Purpose of Action LEVEL 2
Deficiency Photo1
BH3
Violations No violations recorded.
CUPOLA/ SPIRES/ TOWERS Does not Exist
DORMER Does not Exist
DUNNAGE STEEL Inspected
Condition 1 - Good
Deficiency No deficiencies recorded
SKYLIGHT/ROOF VENT Inspected
Material Type(s) Glass
Condition 3 - Fair
Deficiency BROKEN GLASS
Roof Plan reference
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
Deficiency Photo1
SK
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K001
PB/A&W Print Date: 6/21/2019Page 13 of 37
Question Response
EXTERIOR
ROOF Inspected
Specialties Inspected
SKYLIGHT/ROOF VENT Inspected
Violations No violations recorded.
ROOF/GRAVITY TANK Does not Exist
STAIRS/RAMPS: EXTERIOR Inspected
BUILDING CHEEK/FLANK WALLS Does not Exist
RAILINGS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
STAIRS/RAMPS Inspected
Condition 3 - Fair
Deficiency CONCRETE: CRACKS/SPALLING - MINOR
Roof Plan reference
Deficiency Quantity 15
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade B-Exit 6
Violations No violations recorded.
WINDOWS Inspected
Replacement Quantity 10,000
Replacement Uom S.F.
EXTERIOR GUARDS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LINTELS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
WINDOWS Inspected
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K001
PB/A&W Print Date: 6/21/2019Page 14 of 37
Question Response
EXTERIOR
WINDOWS
WINDOWS
Material Type(s) Aluminum
InspectedInstance on Aluminum - Double Hung: All Facades
Instance Condition 1 - Good
Instance Quantity 10,000
Instance Quantity Uom S.F.
Installation Year 2014
Source of Installation Custodial Staff
Deficiency No deficiencies recorded
INTERIOR Inspected
POOLS Does not Exist
STRUCTURAL Inspected
COLUMNS/BEAMS/BEARING WALLS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
FLOOR STRUCTURE Inspected
Condition 3 - Fair
Deficiency CONCRETE SLAB ON GRADE: MINOR CRACKS
Deficiency Location/Instance Basement-MER
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
Deficiency Photo1
Basement-MER
Violations No violations recorded.
FOUNDATION WALLS Inspected
Material Type(s) Concrete
Condition 2 - Between Good and Fair
Deficiency CONCRETE: CRACKED/SPALLED/REINFORCEMENTEXPOSED
Deficiency Location/Instance Basement-Storage Room, Electrical Room
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K001
PB/A&W Print Date: 6/21/2019Page 15 of 37
Question Response
INTERIOR
STRUCTURAL
FOUNDATION WALLS
Deficiency Photo1
Basement-Storage Room
Violations No violations recorded.
ROOF STRUCTURE Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
VAULTS-BUNKERS Does not Exist
AUDITORIUM Inspected
InspectedInstance on 1st Floor (459 Seats)
Ceiling
InspectedInstance on 1st Floor (459 Seats)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
InspectedInstance on 1st Floor (459 Seats)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Fixed H/C Lift
Does not ExistInstance on 1st Floor (459 Seats)
Fixed Seating
InspectedInstance on 1st Floor (459 Seats)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish
InspectedInstance on 1st Floor (459 Seats)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Sliding-folding Partition
Does not ExistInstance on 1st Floor (459 Seats)
Stage
InspectedInstance on 1st Floor (459 Seats)
Stage Inspected
InspectedInstance on 1st Floor (459 Seats)
Condition 2 - Between Good and Fair
Deficiency DAMAGED FLOOR
Deficiency Location/Instance Near radiator
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K001
PB/A&W Print Date: 6/21/2019Page 16 of 37
Question Response
INTERIOR
AUDITORIUM
Stage
Stage
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near radiator
Violations No violations recorded.
Stage Curtain Rigging Inspected
InspectedInstance on 1st Floor (459 Seats)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stage Curtains Inspected
InspectedInstance on 1st Floor (459 Seats)
Condition 3 - Fair
Deficiency WORN/DETERIORATED
Deficiency Location/Instance Left side of Stage
Deficiency Quantity 200
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Left side of Stage
Violations No violations recorded.
Walls
InspectedInstance on 1st Floor (459 Seats)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Window Curtains/Shades/Blinds
Does not ExistInstance on 1st Floor (459 Seats)
CAFETERIA Inspected
InspectedInstance on Basement
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K001
PB/A&W Print Date: 6/21/2019Page 17 of 37
Question Response
INTERIOR
CAFETERIA
Ceiling
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency ACOUSTIC TILES ON PLASTER: DAMAGED/MISSING
Deficiency Location/Instance Center
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Center
Violations No violations recorded.
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Center
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Center
Violations No violations recorded.
Door(s)
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Fixed Equipment
Does not ExistInstance on Basement
Floor Finish
InspectedInstance on Basement
Condition 1 - Good
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K001
PB/A&W Print Date: 6/21/2019Page 18 of 37
Question Response
INTERIOR
CAFETERIA
Floor Finish
Deficiency No deficiencies recorded
Sliding-folding Partition
Does not ExistInstance on Basement
Stage
Does not ExistInstance on Basement
Walls
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Window Curtains/Shades/Blinds
Does not ExistInstance on Basement
CLASSROOMS/CORRIDORS/ADMIN SPACES Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency ACOUSTIC TILES ON PLASTER: DAMAGED/MISSING
Deficiency Location/Instance Corridor near Cafeteria
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Corridor near Cafeteria
Violations No violations recorded.
Door(s) Inspected
Condition 5 - Poor
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance Rooms 202, 226, 307, 327, 338, and others
Deficiency Quantity 10
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K001
PB/A&W Print Date: 6/21/2019Page 19 of 37
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Door(s)
Deficiency Photo1
Room 307
Violations No violations recorded.
Floor Finish Inspected
Condition 2 - Between Good and Fair
Deficiency SHEET VINYL: BROKEN/DETERIORATED
Deficiency Location/Instance Room 134
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 134
Violations No violations recorded.
Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES
Deficiency Location/Instance Room 202
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K001
PB/A&W Print Date: 6/21/2019Page 20 of 37
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Floor Finish Inspected
Room 202
Violations No violations recorded.
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency GLAZED BLOCK: CRACKS/SPALLING
Deficiency Location/Instance Corridor near Room 323
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Corridor near Room 323
Violations No violations recorded.
Specialties Does not Exist
GYMNASIUM Inspected
InspectedInstance on 1st Floor
Ceiling
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Fixed Equipment
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency WOOD: DAMAGED/DETERIORATED
Deficiency Location/Instance Near Office, Near Drinking Fountain
Deficiency Quantity 70
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K001
PB/A&W Print Date: 6/21/2019Page 21 of 37
Question Response
INTERIOR
GYMNASIUM
Floor Finish
Deficiency Photo1
Near Office
Violations No violations recorded.
Seating
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Sliding-folding Partition
Does not ExistInstance on 1st Floor
Stage
Does not ExistInstance on 1st Floor
Walls
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency MASONRY: CRACKS/SPALLING
Deficiency Location/Instance Left side
Deficiency Quantity 25
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Left side
Violations No violations recorded.
Window Curtains/Shades/Blinds
Does not ExistInstance on 1st Floor
INTERIOR DOOR HARDWARE Inspected
Condition 3 - Fair
Deficiency No deficiencies recorded
INTERIOR GUARDS Inspected
Condition 2 - Between Good and Fair
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K001
PB/A&W Print Date: 6/21/2019Page 22 of 37
Question Response
INTERIOR
INTERIOR GUARDS Inspected
Deficiency No deficiencies recorded
KITCHEN Inspected
InspectedInstance on Basement
Ceiling
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
InspectedInstance on Basement
Condition 5 - Poor
Deficiency METAL: DETERIORATED DOOR AND FRAME
Deficiency Location/Instance Serving Area Entrance
Deficiency Quantity 3
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Serving Area Entrance
Violations No violations recorded.
Floor Finish
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Walls
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LIBRARY Inspected
InspectedInstance on Room 236
Built-in Furnishing
InspectedInstance on Room 236
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Ceiling
InspectedInstance on Room 236
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
InspectedInstance on Room 236
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K001
PB/A&W Print Date: 6/21/2019Page 23 of 37
Question Response
INTERIOR
LIBRARY
Door(s)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish
InspectedInstance on Room 236
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Walls
InspectedInstance on Room 236
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LOCKER ROOM Inspected
InspectedInstance on 2nd Floor (60 Lockers)
Alternative use Yes
Ceiling
InspectedInstance on 2nd Floor (60 Lockers)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
InspectedInstance on 2nd Floor (60 Lockers)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish
InspectedInstance on 2nd Floor (60 Lockers)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Locker Room Lockers
InspectedInstance on 2nd Floor (60 Lockers)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Walls
InspectedInstance on 2nd Floor (60 Lockers)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
MULTI-PURPOSE ROOM Does not Exist
SCIENCE DEMO ROOM Does not Exist
SCIENCE LAB Does not Exist
SCIENCE PREP ROOM Does not Exist
SHOWER ROOM Inspected
InaccessibleInstance on 2nd Floor
STAIRS/RAMPS: INTERIOR Inspected
Do Letter Stair Signs Exist? Yes
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s) Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K001
PB/A&W Print Date: 6/21/2019Page 24 of 37
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Partition Does not Exist
Railings Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stairs and Landings Inspected
Condition 2 - Between Good and Fair
Deficiency TERRAZZO: CRACKS
Deficiency Location/Instance Corridor near Gymnasium
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Corridor near Gymnasium
Violations No violations recorded.
Deficiency STONE: BROKEN/MISSING
Deficiency Location/Instance Stair C/3, Exit 12 Stair inside Gymnasium
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stair C/3
Violations No violations recorded.
Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES
Deficiency Location/Instance Stairs C/1, 2
Deficiency Quantity 75
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K001
PB/A&W Print Date: 6/21/2019Page 25 of 37
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Stairs and Landings
Purpose of Action LEVEL 2
Deficiency Photo1
Stair C/1
Violations No violations recorded.
Deficiency VINYL TILES: DETERIORATED SUBSTRATE
Deficiency Location/Instance Stair C/Basement
Deficiency Quantity 25
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stair C/Basement
Violations No violations recorded.
Deficiency METAL: RUST - MAJOR
Deficiency Location/Instance Stair B/Basement
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stair B/Basement
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K001
PB/A&W Print Date: 6/21/2019Page 26 of 37
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Stairs and Landings Inspected
Violations No violations recorded.
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
TOILET ROOMS - STAFF Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s) Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stalls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
TOILET ROOMS - STUDENTS Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Room 113
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 113
Violations No violations recorded.
Door(s) Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish Inspected
Condition 2 - Between Good and Fair
Deficiency CERAMIC TILE: BROKEN/MISSING TILES
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K001
PB/A&W Print Date: 6/21/2019Page 27 of 37
Question Response
INTERIOR
TOILET ROOMS - STUDENTS
Floor Finish
Deficiency Location/Instance Room 213
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 213
Violations No violations recorded.
Stalls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Room 213
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 213
Violations No violations recorded.
Deficiency CERAMIC TILE: BROKEN/ MISSING
Deficiency Location/Instance Rooms 109, 209
Deficiency Quantity 15
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K001
PB/A&W Print Date: 6/21/2019Page 28 of 37
Question Response
INTERIOR
TOILET ROOMS - STUDENTS
Walls
Deficiency Photo1
Room 209
Violations No violations recorded.
LIFE SAFETY Inspected
F.D. HOLDING AREA Does not Exist
STEEL STAIRS Does not Exist
SITE Inspected
CONTAINERIZATION Does not Exist
Drainage System for Asphalt Inspected
Catch Basins/Manhole - Surrounded by asphalt Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Culverts - Asphalt Covering Does not Exist
Drainage System for Concrete Inspected
Catch Basins/Manhole - Surrounded by concrete Inspected
Condition 4 - Between Fair and Poor
Deficiency DAMAGED COVER
Deficiency Location/Instance Walkway near Exits 7 & 9
Deficiency Quantity 2
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 6
Deficiency Photo1
Walkway near Exits 7 & 9
Violations No violations recorded.
Culverts - Concrete Covering Does not Exist
Drainage System for Soil Does not Exist
DRINKING FOUNTAINS Inspected
Condition 2 - Between Good and Fair
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K001
PB/A&W Print Date: 6/21/2019Page 29 of 37
Question Response
SITE
DRINKING FOUNTAINS Inspected
Deficiency No deficiencies recorded
FENCES Inspected
Condition 4 - Between Fair and Poor
Deficiency CHAIN LINK: DAMAGED POST/RAIL
Deficiency Location/Instance South side of Building
Deficiency Quantity 20
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
South side of Building
Violations No violations recorded.
Deficiency CHAIN LINK: RUST - MAJOR
Deficiency Location/Instance South side of Building
Deficiency Quantity 150
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
South side of Building
Violations No violations recorded.
Deficiency CHAIN LINK: DAMAGED/DETERIORATED
Deficiency Location/Instance North side of Building behind Mini Building, 46th Street
Deficiency Quantity 750
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K001
PB/A&W Print Date: 6/21/2019Page 30 of 37
Question Response
SITE
FENCES Inspected
Deficiency Photo1
North side of Building behind Mini Building
Violations No violations recorded.
Deficiency CONCRETE CURB: DAMAGED/DETERIORATED
Deficiency Location/Instance North side of Building, 46th Street, 47th Street
Deficiency Quantity 40
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
North side of Building
Violations No violations recorded.
IRRIGATION SYSTEM Does not Exist
PAVING Inspected
Student Non-Use Does not Exist
Student Use Inspected
Gravel Exists? No
Asphalt Does not Exist
Concrete Inspected
Condition 3 - Fair
Deficiency HEAVING
Deficiency Location/Instance 47th Street Garden
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K001
PB/A&W Print Date: 6/21/2019Page 31 of 37
Question Response
SITE
PAVING
Student Use
Concrete
Deficiency Photo1
47th Street Garden
Violations No violations recorded.
Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS
Deficiency Location/Instance North side of Building, 47th Street Garden
Deficiency Quantity 250
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
North side of Building
Violations No violations recorded.
Pavers Does not Exist
Site Sidewalks & Walkways Inspected
Asphalt Inspected
Condition 2 - Between Good and Fair
Deficiency CRACKS - MINOR
Deficiency Location/Instance Behind Mini Building
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
Deficiency POTHOLES
Deficiency Location/Instance Walkway between Mini Building and Main Building
Deficiency Quantity 10
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K001
PB/A&W Print Date: 6/21/2019Page 32 of 37
Question Response
SITE
PAVING
Site Sidewalks & Walkways
Asphalt
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Walkway between Mini Building and Main Building
Violations No violations recorded.
Concrete Inspected
Condition 3 - Fair
Deficiency HEAVING
Deficiency Location/Instance South side of Building
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
South side of Building
Violations No violations recorded.
Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS
Deficiency Location/Instance North side of Building, Main Entrance, 47th Street, South side ofBuilding
Deficiency Quantity 275
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K001
PB/A&W Print Date: 6/21/2019Page 33 of 37
Question Response
SITE
PAVING
Site Sidewalks & Walkways
Concrete
Deficiency Photo1
North side of Building
Violations No violations recorded.
Pavers Does not Exist
DOT Sidewalk Inspected
Asphalt Does not Exist
Concrete Inspected
Condition 4 - Between Fair and Poor
Deficiency HEAVING
Deficiency Location/Instance 46th Street
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
46th Street
Violations No violations recorded.
Deficiency DAMAGED CURBS
Deficiency Location/Instance 46th Street, 47th Street
Deficiency Quantity 50
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K001
PB/A&W Print Date: 6/21/2019Page 34 of 37
Question Response
SITE
PAVING
DOT Sidewalk
Concrete
Deficiency Photo1
47th Street
Violations No violations recorded.
Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS
Deficiency Location/Instance 46th Street, 47th Street
Deficiency Quantity 450
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
47th Street
Violations No violations recorded.
Pavers Does not Exist
PLAYGROUNDS Inspected
InspectedInstance on Adjacent to Mini-School Building
InspectedInstance on Courtyard (Plaza Deck)
Benches
Does not ExistInstance on Adjacent to Mini-School Building
Does not ExistInstance on Courtyard (Plaza Deck)
Fence
Does not ExistInstance on Adjacent to Mini-School Building
Does not ExistInstance on Courtyard (Plaza Deck)
Pavement
Does not ExistInstance on Adjacent to Mini-School Building
Does not ExistInstance on Courtyard (Plaza Deck)
Play Equipment
InspectedInstance on Adjacent to Mini-School Building
Condition 2 - Between Good and Fair
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K001
PB/A&W Print Date: 6/21/2019Page 35 of 37
Question Response
SITE
PLAYGROUNDS
Play Equipment
Deficiency No deficiencies recorded
Does not ExistInstance on Courtyard (Plaza Deck)
Safety Surfacing
InspectedInstance on Adjacent to Mini-School Building
Condition 2 - Between Good and Fair
Deficiency DETERIORATED/MISSING
Deficiency Location/Instance North side
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
North side
Violations No violations recorded.
Unpaved Area
Does not ExistInstance on Courtyard (Plaza Deck)
Does not ExistInstance on Adjacent to Mini-School Building
PLAYING SURFACE Does not Exist
RETAINING WALLS Inspected
Are there any Retaining Walls 6' OR higher facing publicstreet/sidewalk?
No
Condition 3 - Fair
Deficiency CAST IN PLACE CONCRETE: CRACKS/SPALLING - MINOR
Deficiency Location/Instance 47th Street
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
Deficiency CAST IN PLACE CONCRETE: CRACKS/SPALLING - MAJOR
Deficiency Location/Instance 46th Street, 47th Street
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K001
PB/A&W Print Date: 6/21/2019Page 36 of 37
Question Response
SITE
RETAINING WALLS
Deficiency Photo1
46th Street
Violations No violations recorded.
SEATING Does not Exist
SITE WALLS (NOT RETAINING WALLS) Does not Exist
STAIRS/RAMPS: EXTERIOR Does not Exist
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K001
PB/A&W Print Date: 6/21/2019Page 37 of 37