Asset: P.S. 192 - BROOKLYN, 4715 18 AVENUE, New York, 11204
Inspection Id Inspection Type Time In Last Edited
SA : K192 Architectural - Senior 2018-04-02 8:00 AM 2018-06-12 5:26 PM
AA : K192 Architectural - Associate 2018-04-02 7:32 AM 2018-04-10 12:28 PM
Asset Data
Question Answer
Was the building fully accessible for inspection No
Inspection Access Comment 1. Plaza Deck (Roof 5), Site/Paving Student Use/Concrete,Site/Drainage System for Concrete/Catchbasin/Manhole - Due tostaging area; 2. Cornice, Louver, Roof Barrier, Exterior Guards,Window Lintels, Security Lights - Due to scaffolding; 3. Site/PlayingSurface/Playing Field - Covered in snow.
Principal(s) Information
Principal Name Liset Isaac
Organization P.S./I.S. 192 - Brooklyn
Did you meet with this Principal? No
Did this Principal provide feedback? Yes
Summary of Principal's Feedback A Principal questionnaire form was returned with the followingcomments: 1. Student and Staff Toilet Rooms are in need of anupgrade. 2. Classroom door locks should be re-keyed with amaster-key system. 3. Exterior doors are in poor overall condition andshould be repaired or upgraded.
Principal Name Johanna Schneider
Organization P.S. 36K - Brooklyn
Did you meet with this Principal? No
Did this Principal provide feedback? No
Custodian James Orlando
Fireman Larry Guarinello
Building Square Footage 76000
Comments on the Area None
Comments on the Stories (Floors) plus Basements 5+B+PH
Comments on the Number of Classrooms 45
Comments on the Year Built 1923
Student Population 751
Staff Population 175
Weather Snow
Facade Photo
Corner of 18th Avenue and 48th Street -Northeast View
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2017 - 2018
K192
PB/A&W Print Date: 6/26/2018Page 1 of 32
Main Entrance Photo
Facade A - 18th Avenue
Roof Photo
Roof 1 - Southwest View
Have any Systems/Major Building Components been upgraded? Yes
Systems: Foundation Wall Waterproofing in Electrical Room
Year: 2017
Systems: New Playground at East side; 1st Floor Boys and GirlsToilet Rooms upgrade
Year: 2015
Systems: Partial Exterior Masonry renovation; Parapets repairs;Coping and main roof Parapets replacement; New MetalSiding on Bulkheads and Penthouse
Year: 2011
Systems: Partial Areaway Grating replacement
Year: 2010
Systems: Partial Foundation Wall waterproofing; Partial Structuralrepairs; Oil Tank Room reconstruction
Year: 2009
Systems: Roofing and Flashing replacement; Windows, WindowGuards and Shades replacement; Auditorium upgradeincluding Seating, Flooring, Curtains replacement
Year: 2008
Have there been any New Building Additions? No
Tandem Schools? No
Leased Space? No
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2017 - 2018
K192
PB/A&W Print Date: 6/26/2018Page 2 of 32
Priority Condition
PriorityCondition ExistLast Year?
PriorityCategory
ConditionDescription
ComponentAffected
LocationDescription
Person(s)Notified
Person(s) Title PhotoImage
Yes ProtrudingElements
MissingBackrest is aPotential SafetyHazard
INTERIOR |AUDITORIUM| Fixed Seating
Seat T/2 James Orlando Custodian
Structural Engineer Required
StructuralCondition Type
ConditionDescription
ComponentAffected
LocationDescription
Person(s)Notified
Person(s) Title PhotoImage
No condition recorded
Accessibility
Accessibility Status Question Response
Is the primary or secondary entrance on an accessible route? Yes
Is the building a multi-story building? Yes
Are all floors of the building accessible through compliant means? No
Are SOME floors other than the 1st floor and basement accessible through compliantmeans?
No
Do any of the following spaces exist on the First floor? Classroom, Art Room,Auditorium, Cafeteria, Computer, Gymnasiums, Library, Multipurpose Room, ScienceLabs
Yes
For the rooms that do exist, are SOME of them accessible on the 1st floor? Yes
Boys and Girls or Unisex accessible toilets exist on the 1st floor? No
Physical Breakdown Structure Exists Complies Required Deficiency
FUNCTIONAL ACCESSIBILITY
Exterior Routes
Exterior Entrances & Exits Yes
Exterior H/C Lifts No No
Exterior Ramps and Railings No No
Interior Routes
Corridor and Lobby H/C Lifts No No
Interior Corridor Doors and Hardware Yes Yes
Interior Corridors and Lobbies Yes
Interior Elevators No
Interior Lobby Doors and Hardware Yes
Interior Ramps No
Rooms & Spaces
Art Rooms No
Auditorium 2nd Floor No No Stage AccessNot on Accessible Route
Cafeteria 1st Floor Yes
Classrooms None on Accessible Route No Not on Accessible Route
Computer Rooms No
Gymnasium No
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2017 - 2018
K192
PB/A&W Print Date: 6/26/2018Page 3 of 32
Physical Breakdown Structure Exists Complies Required Deficiency
Rooms & Spaces
Library Room 409 No Not on Accessible Route
Main Office Room 205 (P.S./I.S. 192); Room 402 (P.S.36K)
No Not on Accessible Route
Multi-purpose Room 1st Floor - East, 1st Floor - West Yes
Nurse's Room Rooms 320, 451 No Clear opening < 32"Not on Accessible Route
Pool No
Science Lab No
Toilet Rooms (Boys) 1st Floor No Accessory ArrangementSink ArrangementTurning RadiusUrinal ArrangementWater Closet Arrangement
Toilet Rooms (Girls) 1st Floor No Accessory ArrangementSink ArrangementTurning RadiusWater Closet Arrangement
Toilet Rooms (Staff) 1st Floor - Men No Accessory ArrangementClear opening < 32"No Lever-type HardwareSink ArrangementTurning RadiusUrinal ArrangementWater Closet Arrangement
1st Floor - Women No Accessory ArrangementClear opening < 32"No Lever-type HardwareSink ArrangementUrinal ArrangementWater Closet Arrangement
Building Template
Inspection
Question Response
Architectural
EXTERIOR Inspected
AREAWAY Inspected
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2017 - 2018
K192
PB/A&W Print Date: 6/26/2018Page 4 of 32
Question Response
EXTERIOR
AREAWAY
InspectedInstance on AW1 - AW6
Instance Condition 1 - Good
Instance Quantity 6
Instance Quantity Uom EACH
Deficiency No deficiencies recorded
AWNINGS AND CANOPIES Does not Exist
CHIMNEY Inspected
Material Type(s) Masonry
Condition 1 - Good
Deficiency No deficiencies recorded
COPING Under Construction
CORNICE Inaccessible
DOORS Inspected
DOORS AND FRAMES Inspected
Condition 5 - Poor
Deficiency METAL: DETERIORATED DOOR - MAJOR DETERIORATION
Roof Plan reference
Deficiency Quantity 1
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade F - Boiler Room Exit
Violations No violations recorded.
Deficiency METAL CLAD: DETERIORATED DOOR - MAJORDETERIORATION
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2017 - 2018
K192
PB/A&W Print Date: 6/26/2018Page 5 of 32
Question Response
EXTERIOR
DOORS
DOORS AND FRAMES
Roof Plan reference
Deficiency Quantity 7
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade A - Main Entrance
Violations No violations recorded.
DOOR HARDWARE Inspected
Condition 3 - Fair
Deficiency No deficiencies recorded
LINTELS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
TRANSOM/SIDE LIGHT Does not Exist
EXTERIOR WALLS Inspected
Material Type(s) Masonry
Replacement Quantity 38,000
Replacement Uom S.F.
Under ConstructionInstance on All Facades
Instance Quantity 38,000
Instance Quantity Uom S.F.
EXTERIOR SOFFITS Does not Exist
LOADING DOCK Does not Exist
LOUVER Inaccessible
PARAPETS Inspected
Material Type(s) Masonry
Replacement Quantity 4,500
Replacement Uom C.F.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2017 - 2018
K192
PB/A&W Print Date: 6/26/2018Page 6 of 32
Question Response
EXTERIOR
PARAPETS Inspected
Under ConstructionInstance on All Facades
Instance Quantity 4,500
Instance Quantity Uom C.F.
PLAZA DECK Inspected
Under ConstructionInstance on Pavers: Roof 4
Instance Quantity 2,600
Instance Quantity Uom S.F.
InaccessibleInstance on Concrete: Roof 5 - at Schoolyard
Instance Quantity 2,000
Instance Quantity Uom S.F.
ROOF Inspected
Roofing Inspected
Replacement Quantity 12,800
Replacement Uom S.F.
ROOF HATCH/SMOKE HATCH Does not Exist
LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
ROOF BARRIER Inaccessible
ROOF CAGE Under Construction
ROOF FENCE Does not Exist
ROOFING Inspected
InspectedInstance on Built-Up: All Roofs
Instance Condition 2 - Between Good and Fair
Instance Quantity 12,800
Instance Quantity Uom S.F.
Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?
No
Installation Year 2008
Source of Installation Documented
Deficiency No deficiencies recorded
ROOFING DRAINS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Specialties Inspected
BULKHEAD/PENTHOUSE Inspected
Condition 4 - Between Fair and Poor
Deficiency BULKHEAD/PENTHOUSE DOORS: DETERIORATED DOOR
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2017 - 2018
K192
PB/A&W Print Date: 6/26/2018Page 7 of 32
Question Response
EXTERIOR
ROOF
Specialties
BULKHEAD/PENTHOUSE
Roof Plan reference
Deficiency Quantity 1
Quantity Uom EACH
Potential Action REPLACE DOOR
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
PH - South (Door is very difficult to open)
Violations No violations recorded.
Deficiency BULKHEAD/PENTHOUSE WALLS/INTERIOR: BRICKCRACKS/SPALLING
Roof Plan reference
Deficiency Quantity 40
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2017 - 2018
K192
PB/A&W Print Date: 6/26/2018Page 8 of 32
Question Response
EXTERIOR
ROOF
Specialties
BULKHEAD/PENTHOUSE
Deficiency Photo1
Fan Room at BH2
Violations No violations recorded.
Deficiency BULKHEAD/PENTHOUSE WALLS/INTERIOR: PLASTERCRACKS/SPALLING
Roof Plan reference
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 1 - BH1
Violations No violations recorded.
CUPOLA/ SPIRES/ TOWERS Does not Exist
DORMER Does not Exist
DUNNAGE STEEL Does not Exist
SKYLIGHT/ROOF VENT Does not Exist
ROOF/GRAVITY TANK Does not Exist
STAIRS/RAMPS: EXTERIOR Inspected
BUILDING CHEEK/FLANK WALLS Does not Exist
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2017 - 2018
K192
PB/A&W Print Date: 6/26/2018Page 9 of 32
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
RAILINGS Does not Exist
STAIRS/RAMPS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
WINDOWS Inspected
Replacement Quantity 13,000
Replacement Uom S.F.
EXTERIOR GUARDS Inaccessible
LINTELS Inaccessible
WINDOWS Inspected
Material Type(s) Aluminum
InspectedInstance on Aluminum - Double Hung: All Facades
Instance Condition 2 - Between Good and Fair
Instance Quantity 13,000
Instance Quantity Uom S.F.
Installation Year 2008
Source of Installation Documented
Deficiency ALUMINUM - DOUBLE HUNG: INOPERABLE BALANCE
Roof Plan reference
Elevation
Deficiency Quantity 10
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
INTERIOR Inspected
POOLS Does not Exist
STRUCTURAL Inspected
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2017 - 2018
K192
PB/A&W Print Date: 6/26/2018Page 10 of 32
Question Response
INTERIOR
STRUCTURAL
COLUMNS/BEAMS/BEARING WALLS Inspected
Condition 3 - Fair
Deficiency CONCRETE COLUMNS/BEAMS:CRACKED/SPALLED/REINFORCEMENT EXPOSED
Deficiency Location/Instance Basement - Boiler Room, near Oil Tank Room, Fan Room nearElectrical Room
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
Deficiency Photo1
Basement - Near Oil Tank Room
Violations No violations recorded.
FLOOR STRUCTURE Inspected
Condition 3 - Fair
Deficiency CONCRETE: CRACKS/SPALLED/REINFORCEMENT EXPOSED
Deficiency Location/Instance Basement - Fan Room near Sprinkler Head Room, 3rd Floor -Auditorium Fan Room, Penthouse
Deficiency Quantity 80
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
Deficiency Photo1
Auditorium Fan Room
Violations No violations recorded.
Deficiency CONCRETE SLAB ON GRADE: MINOR CRACKS
Deficiency Location/Instance Basement - Fan Room near Electrical Room
Deficiency Quantity 40
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2017 - 2018
K192
PB/A&W Print Date: 6/26/2018Page 11 of 32
Question Response
INTERIOR
STRUCTURAL
FLOOR STRUCTURE
Purpose of Action LEVEL 5
Deficiency Photo1
Fan Room near Electrical Room
Violations No violations recorded.
FOUNDATION WALLS Inspected
Material Type(s) Concrete
Condition 3 - Fair
Deficiency CONCRETE: WATER INFILTRATION IN NON- INSTRUCTIONALSPACE
Deficiency Location/Instance Basement - Near Entrance to Heating Chamber
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action INSTALL WATERPROOFING
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 5
Deficiency Photo1
Near Entrance to Heating Chamber
Violations No violations recorded.
Deficiency CONCRETE: CRACKED/SPALLED/REINFORCEMENTEXPOSED
Deficiency Location/Instance Basement - Boiler Room, Area near Sprinkler Head Room Corridor toHeating Chamber
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2017 - 2018
K192
PB/A&W Print Date: 6/26/2018Page 12 of 32
Question Response
INTERIOR
STRUCTURAL
FOUNDATION WALLS
Deficiency Photo1
Basement - Area near Sprinkler Head Room
Violations No violations recorded.
ROOF STRUCTURE Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
VAULTS-BUNKERS Inspected
Foundation Walls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Slab Structure Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Vault/Ash Hoist Doors and Framing Inspected
Condition 5 - Poor
Deficiency DETERIORATED/DAMAGED VAULT/ASH HOIST DOORS ANDFRAMING
Deficiency Location/Instance Basement - Ash Hoist Door
Deficiency Quantity 1
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Ash Hoist Door
Violations No violations recorded.
AUDITORIUM Inspected
InspectedInstance on 2nd Floor- 540 Seats
Ceiling
InspectedInstance on 2nd Floor- 540 Seats
Condition 2 - Between Good and Fair
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2017 - 2018
K192
PB/A&W Print Date: 6/26/2018Page 13 of 32
Question Response
INTERIOR
AUDITORIUM
Ceiling
Deficiency No deficiencies recorded
Door(s)
InspectedInstance on 2nd Floor- 540 Seats
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Fixed H/C Lift
Does not ExistInstance on 2nd Floor- 540 Seats
Fixed Seating
InspectedInstance on 2nd Floor- 540 Seats
Condition 2 - Between Good and Fair
Deficiency DAMAGED/BROKEN/INOPERABLE
Deficiency Location/Instance Seats B/110, J/105, M/5, P/17
Deficiency Quantity 4
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Seat M/5
Violations No violations recorded.
Deficiency DAMAGED/BROKEN/INOPERABLE
Deficiency Location/Instance Seat T/2
Deficiency Quantity 1
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 6
Deficiency Photo1
Seat T/2
Violations No violations recorded.
Floor Finish
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2017 - 2018
K192
PB/A&W Print Date: 6/26/2018Page 14 of 32
Question Response
INTERIOR
AUDITORIUM
Floor Finish
InspectedInstance on 2nd Floor- 540 Seats
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Sliding-folding Partition
Does not ExistInstance on 2nd Floor- 540 Seats
Stage
InspectedInstance on 2nd Floor- 540 Seats
Stage Inspected
InspectedInstance on 2nd Floor- 540 Seats
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stage Curtain Rigging Inspected
InspectedInstance on 2nd Floor- 540 Seats
Condition 1 - Good
Deficiency No deficiencies recorded
Stage Curtains Inspected
InspectedInstance on 2nd Floor- 540 Seats
Condition 1 - Good
Deficiency No deficiencies recorded
Walls
InspectedInstance on 2nd Floor- 540 Seats
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Window Curtains/Shades/Blinds
InspectedInstance on 2nd Floor- 540 Seats
Condition 1 - Good
Deficiency No deficiencies recorded
CAFETERIA Inspected
InspectedInstance on 1st Floor
Ceiling
Does not ExistInstance on 1st Floor
Door(s)
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Fixed Equipment
Does not ExistInstance on 1st Floor
Floor Finish
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency WOOD: DAMAGED/DETERIORATED
Deficiency Location/Instance Southwest
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2017 - 2018
K192
PB/A&W Print Date: 6/26/2018Page 15 of 32
Question Response
INTERIOR
CAFETERIA
Floor Finish
Deficiency Photo1
Southwest
Violations No violations recorded.
Sliding-folding Partition
Does not ExistInstance on 1st Floor
Stage
Does not ExistInstance on 1st Floor
Walls
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Window Curtains/Shades/Blinds
Does not ExistInstance on 1st Floor
CLASSROOMS/CORRIDORS/ADMIN SPACES Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s) Inspected
Condition 5 - Poor
Deficiency METAL CLAD WOOD: DETERIORATED DOOR
Deficiency Location/Instance Cross Corridor Near Room 308
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Cross Corridor Near Room 308
Violations No violations recorded.
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance Rooms 302, 303, 351, 406, 504, 551
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2017 - 2018
K192
PB/A&W Print Date: 6/26/2018Page 16 of 32
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Door(s)
Deficiency Quantity 6
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 406
Violations No violations recorded.
Floor Finish Inspected
Condition 3 - Fair
Deficiency VINYL TILES: TRIPPING HAZARD - ELECTRICAL OUTLET
Deficiency Location/Instance Room 510
Deficiency Quantity 5
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 6
Deficiency Photo1
Room 510
Violations No violations recorded.
Deficiency TERRAZZO: CRACKS
Deficiency Location/Instance Main Entrance Lobby, Corridor near Room 209, Corridor NearAuditorium
Deficiency Quantity 150
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2017 - 2018
K192
PB/A&W Print Date: 6/26/2018Page 17 of 32
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Floor Finish
Deficiency Photo1
Main Entrance Lobby
Violations No violations recorded.
Deficiency VINYL TILES: DETERIORATED SUBSTRATE
Deficiency Location/Instance Rooms 204, 310, 402, 505, 509 and Others
Deficiency Quantity 1,600
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 505
Violations No violations recorded.
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Exit 4 Vestibule
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2017 - 2018
K192
PB/A&W Print Date: 6/26/2018Page 18 of 32
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Walls
Exit 4 Vestibule
Violations No violations recorded.
Deficiency CERAMIC TILE: BROKEN/ MISSING
Deficiency Location/Instance Exit 6I Vestibule
Deficiency Quantity 5
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Exit 6I Vestibule
Violations No violations recorded.
Specialties Inspected
Classroom Locker(s) Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Fixed Seating Does not Exist
GYMNASIUM Does not Exist
INTERIOR DOOR HARDWARE Inspected
Condition 3 - Fair
Deficiency No deficiencies recorded
INTERIOR GUARDS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
KITCHEN Inspected
InspectedInstance on 1st Floor
Ceiling
Does not ExistInstance on 1st Floor
Door(s)
InspectedInstance on 1st Floor
Condition 3 - Fair
Deficiency METAL CLAD WOOD: DETERIORATED DOOR
Deficiency Location/Instance Entrance
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2017 - 2018
K192
PB/A&W Print Date: 6/26/2018Page 19 of 32
Question Response
INTERIOR
KITCHEN
Door(s)
Deficiency Photo1
Entrance
Violations No violations recorded.
Floor Finish
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency CONCRETE: CRACKS
Deficiency Location/Instance Storage Room
Deficiency Quantity 5
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Storage Room
Violations No violations recorded.
Walls
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LIBRARY Inspected
InspectedInstance on Room 409
Built-in Furnishing
Does not ExistInstance on Room 409
Ceiling
InspectedInstance on Room 409
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
InspectedInstance on Room 409
Condition 2 - Between Good and Fair
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2017 - 2018
K192
PB/A&W Print Date: 6/26/2018Page 20 of 32
Question Response
INTERIOR
LIBRARY
Door(s)
Deficiency No deficiencies recorded
Floor Finish
InspectedInstance on Room 409
Condition 2 - Between Good and Fair
Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES
Deficiency Location/Instance Center, West, East
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Center
Violations No violations recorded.
Walls
InspectedInstance on Room 409
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LOCKER ROOM Does not Exist
MULTI-PURPOSE ROOM Inspected
InspectedInstance on 1st Floor- West
InspectedInstance on 1st Floor- East
Ceiling
Does not ExistInstance on 1st Floor- East
Does not ExistInstance on 1st Floor- West
Door(s)
InspectedInstance on 1st Floor- West
Condition 4 - Between Fair and Poor
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance Entrance
Deficiency Quantity 2
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2017 - 2018
K192
PB/A&W Print Date: 6/26/2018Page 21 of 32
Question Response
INTERIOR
MULTI-PURPOSE ROOM
Door(s)
Deficiency Photo1
Entrance
Violations No violations recorded.
InspectedInstance on 1st Floor- East
Condition 4 - Between Fair and Poor
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance Entrance
Deficiency Quantity 2
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Entrance
Violations No violations recorded.
Fixed Equipment
InspectedInstance on 1st Floor- West
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
InspectedInstance on 1st Floor- East
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish
InspectedInstance on 1st Floor- West
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
InspectedInstance on 1st Floor- East
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Sliding-folding Partition
Does not ExistInstance on 1st Floor- East
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2017 - 2018
K192
PB/A&W Print Date: 6/26/2018Page 22 of 32
Question Response
INTERIOR
MULTI-PURPOSE ROOM
Sliding-folding Partition
Does not ExistInstance on 1st Floor- West
Stage
Does not ExistInstance on 1st Floor- West
Does not ExistInstance on 1st Floor- East
Walls
InspectedInstance on 1st Floor- East
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
InspectedInstance on 1st Floor- West
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Window Curtains/Shades/Blinds
Does not ExistInstance on 1st Floor- East
Does not ExistInstance on 1st Floor- West
SCIENCE DEMO ROOM Does not Exist
SCIENCE LAB Does not Exist
SCIENCE PREP ROOM Does not Exist
SHOWER ROOM Does not Exist
STAIRS/RAMPS: INTERIOR Inspected
Do Letter Stair Signs Exist? Yes
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s) Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Partition Inspected
Condition 2 - Between Good and Fair
Deficiency GLASS PANEL: DAMAGED/DETERIORATED
Deficiency Location/Instance Stairs BC/2,4,Bulkhead, FG/2,4 and Others
Deficiency Quantity 45
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stair BC/2
Violations No violations recorded.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2017 - 2018
K192
PB/A&W Print Date: 6/26/2018Page 23 of 32
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Railings Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stairs and Landings Inspected
Condition 4 - Between Fair and Poor
Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES
Deficiency Location/Instance Stairs BC/1, D/2, E/4
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stair BC/1
Violations No violations recorded.
Deficiency ROLLED ASPHALT: CRACKS
Deficiency Location/Instance Stairs BC/Bulkhead, FG/Bulkhead
Deficiency Quantity 360
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stair BC/Bulkhead
Violations No violations recorded.
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
TOILET ROOMS - STAFF Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2017 - 2018
K192
PB/A&W Print Date: 6/26/2018Page 24 of 32
Question Response
INTERIOR
TOILET ROOMS - STAFF
Door(s) Inspected
Condition 5 - Poor
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance 1st Floor Men Toilet Room, 1st Floor Kitchen Staff Toilet Room
Deficiency Quantity 2
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
1st Floor Men Toilet Room
Violations No violations recorded.
Floor Finish Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stalls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency CERAMIC TILE: BROKEN/ MISSING
Deficiency Location/Instance Inside Room 451
Deficiency Quantity 5
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Inside Room 451
Violations No violations recorded.
TOILET ROOMS - STUDENTS Inspected
Ceiling Inspected
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2017 - 2018
K192
PB/A&W Print Date: 6/26/2018Page 25 of 32
Question Response
INTERIOR
TOILET ROOMS - STUDENTS
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s) Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish Inspected
Condition 2 - Between Good and Fair
Deficiency CERAMIC TILE: BROKEN/MISSING TILES
Deficiency Location/Instance 4th Floor Boys Toilet Room
Deficiency Quantity 5
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
4th Floor Boys Toilet Room
Violations No violations recorded.
Stalls Inspected
Condition 3 - Fair
Deficiency BROKEN/MISSING
Deficiency Location/Instance 4th Floor Boys Toilet Room
Deficiency Quantity 1
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
4th Floor Boys Toilet Room
Violations No violations recorded.
Walls Inspected
Condition 2 - Between Good and Fair
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2017 - 2018
K192
PB/A&W Print Date: 6/26/2018Page 26 of 32
Question Response
INTERIOR Inspected
TOILET ROOMS - STUDENTS Inspected
Walls
Deficiency No deficiencies recorded
LIFE SAFETY Inspected
F.D. HOLDING AREA Does not Exist
STEEL STAIRS Does not Exist
SITE Inspected
CONTAINERIZATION Inspected
Condition 5 - Poor
Deficiency FENCING MISSING
Deficiency Location/Instance Near 47th Street
Deficiency Quantity 600
Quantity Uom S.F.
Potential Action INSTALL NEW
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
Deficiency CONTAINER DAMAGED
Deficiency Location/Instance Near 47th Street
Deficiency Quantity 1
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near 47th Street
Violations No violations recorded.
Drainage System for Asphalt Inspected
Catch Basins/Manhole - Surrounded by asphalt Inspected
Condition 1 - Good
Deficiency No deficiencies recorded
Culverts - Asphalt Covering Does not Exist
Drainage System for Concrete Inspected
Catch Basins/Manhole - Surrounded by concrete Inaccessible
Culverts - Concrete Covering Does not Exist
Drainage System for Soil Does not Exist
DRINKING FOUNTAINS Inspected
Condition 1 - Good
Deficiency No deficiencies recorded
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2017 - 2018
K192
PB/A&W Print Date: 6/26/2018Page 27 of 32
Question Response
SITE
FENCES Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
IRRIGATION SYSTEM Does not Exist
PAVING Inspected
Student Non-Use Inspected
Gravel Exists? No
Asphalt Does not Exist
Concrete Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Pavers Does not Exist
Student Use Inspected
Gravel Exists? No
Asphalt Inspected
Condition 3 - Fair
Deficiency CRACKS - MAJOR
Deficiency Location/Instance Schoolyard
Deficiency Quantity 320
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Schoolyard- East
Violations No violations recorded.
Concrete Inaccessible
Pavers Inspected
Condition 1 - Good
Deficiency No deficiencies recorded
Site Sidewalks & Walkways Inspected
Asphalt Does not Exist
Concrete Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Pavers Does not Exist
DOT Sidewalk Inspected
Asphalt Does not Exist
Concrete Inspected
Condition 4 - Between Fair and Poor
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2017 - 2018
K192
PB/A&W Print Date: 6/26/2018Page 28 of 32
Question Response
SITE
PAVING
DOT Sidewalk
Concrete
Deficiency DAMAGED CURBS
Deficiency Location/Instance Along 18th Avenue, Along 47th Street, Along 48th Street
Deficiency Quantity 30
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Along 47th Street
Violations No violations recorded.
Deficiency HEAVING
Deficiency Location/Instance Along 47th Street, Along 48th Street
Deficiency Quantity 125
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 6
Deficiency Photo1
Along 48th Street
Violations No violations recorded.
Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS
Deficiency Location/Instance Along 18th Avenue, Along 47th Street, Along 48th Street
Deficiency Quantity 700
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2017 - 2018
K192
PB/A&W Print Date: 6/26/2018Page 29 of 32
Question Response
SITE
PAVING
DOT Sidewalk
Concrete
Deficiency Photo1
Along 48th Street
Violations No violations recorded.
Pavers Does not Exist
PLAYGROUNDS Inspected
InspectedInstance on Schoolyard- Center West
InspectedInstance on Schoolyard- East
InspectedInstance on Schoolyard- Northwest
InspectedInstance on Schoolyard- Southwest
Benches
InspectedInstance on Schoolyard- Northwest
Condition 1 - Good
Deficiency No deficiencies recorded
InspectedInstance on Schoolyard- Southwest
Condition 1 - Good
Deficiency No deficiencies recorded
InspectedInstance on Schoolyard- Center West
Condition 1 - Good
Deficiency No deficiencies recorded
InspectedInstance on Schoolyard- East
Condition 1 - Good
Deficiency No deficiencies recorded
Fence
InspectedInstance on Schoolyard- Center West
Condition 1 - Good
Deficiency No deficiencies recorded
InspectedInstance on Schoolyard- East
Condition 1 - Good
Deficiency No deficiencies recorded
InspectedInstance on Schoolyard- Northwest
Condition 1 - Good
Deficiency No deficiencies recorded
InspectedInstance on Schoolyard- Southwest
Condition 1 - Good
Deficiency No deficiencies recorded
Pavement
InspectedInstance on Schoolyard- Southwest
Condition 1 - Good
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2017 - 2018
K192
PB/A&W Print Date: 6/26/2018Page 30 of 32
Question Response
SITE
PLAYGROUNDS
Pavement
Deficiency No deficiencies recorded
InspectedInstance on Schoolyard- Center West
Condition 1 - Good
Deficiency No deficiencies recorded
InspectedInstance on Schoolyard- East
Condition 1 - Good
Deficiency No deficiencies recorded
InspectedInstance on Schoolyard- Northwest
Condition 1 - Good
Deficiency No deficiencies recorded
Play Equipment
InspectedInstance on Schoolyard- Center West
Condition 1 - Good
Deficiency No deficiencies recorded
InspectedInstance on Schoolyard- East
Condition 1 - Good
Deficiency No deficiencies recorded
InspectedInstance on Schoolyard- Northwest
Condition 1 - Good
Deficiency No deficiencies recorded
InspectedInstance on Schoolyard- Southwest
Condition 1 - Good
Deficiency No deficiencies recorded
Safety Surfacing
InspectedInstance on Schoolyard- Center West
Condition 1 - Good
Deficiency No deficiencies recorded
InspectedInstance on Schoolyard- Southwest
Condition 1 - Good
Deficiency No deficiencies recorded
InspectedInstance on Schoolyard- East
Condition 1 - Good
Deficiency No deficiencies recorded
InspectedInstance on Schoolyard- Northwest
Condition 1 - Good
Deficiency No deficiencies recorded
Unpaved Area
Does not ExistInstance on Schoolyard- Southwest
Does not ExistInstance on Schoolyard- Center West
Does not ExistInstance on Schoolyard- East
Does not ExistInstance on Schoolyard- Northwest
PLAYING SURFACE Inspected
Playing Field Inspected
InaccessibleInstance on Schoolyard- South
Running Track Does not Exist
RETAINING WALLS Inspected
Are there any Retaining Walls 6' OR higher facing publicstreet/sidewalk?
No
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2017 - 2018
K192
PB/A&W Print Date: 6/26/2018Page 31 of 32
Question Response
SITE
RETAINING WALLS
Condition 3 - Fair
Deficiency CAST IN PLACE CONCRETE: CRACKS/SPALLING - MAJOR
Deficiency Location/Instance Along 48th Street, Along 47th Street
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Along 48th Street
Violations No violations recorded.
SEATING Inspected
Benches Inspected
Concrete Does not Exist
Metal/Wood/Plastic Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Bleachers Does not Exist
SITE WALLS (NOT RETAINING WALLS) Does not Exist
STAIRS/RAMPS: EXTERIOR Does not Exist
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2017 - 2018
K192
PB/A&W Print Date: 6/26/2018Page 32 of 32