Asset: P.S. 192 - BROOKLYN, 4715 18 AVENUE, New York, 11204 Inspection Id Inspection Type Time In Last Edited SA : K192 Architectural - Senior 2018-04-02 8:00 AM 2018-06-12 5:26 PM AA : K192 Architectural - Associate 2018-04-02 7:32 AM 2018-04-10 12:28 PM Asset Data Question Answer Was the building fully accessible for inspection No Inspection Access Comment 1. Plaza Deck (Roof 5), Site/Paving Student Use/Concrete, Site/Drainage System for Concrete/Catchbasin/Manhole - Due to staging area; 2. Cornice, Louver, Roof Barrier, Exterior Guards, Window Lintels, Security Lights - Due to scaffolding; 3. Site/Playing Surface/Playing Field - Covered in snow. Principal(s) Information Principal Name Liset Isaac Organization P.S./I.S. 192 - Brooklyn Did you meet with this Principal? No Did this Principal provide feedback? Yes Summary of Principal's Feedback A Principal questionnaire form was returned with the following comments: 1. Student and Staff Toilet Rooms are in need of an upgrade. 2. Classroom door locks should be re-keyed with a master-key system. 3. Exterior doors are in poor overall condition and should be repaired or upgraded. Principal Name Johanna Schneider Organization P.S. 36K - Brooklyn Did you meet with this Principal? No Did this Principal provide feedback? No Custodian James Orlando Fireman Larry Guarinello Building Square Footage 76000 Comments on the Area None Comments on the Stories (Floors) plus Basements 5+B+PH Comments on the Number of Classrooms 45 Comments on the Year Built 1923 Student Population 751 Staff Population 175 Weather Snow Facade Photo Corner of 18th Avenue and 48th Street - Northeast View NYC Department of Education Architectural Inspection Building Condition Assessment Survey 2017 - 2018 K192 PB/A&W Print Date: 6/26/2018 Page 1 of 32

Upload: leminh

Post on 12-Feb-2019

221 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: NYC Department of Education · Fireman Larry Guarinello Building Square Footage 76000 Comments on the Area None Comments on the Stories (Floors) plus Basements 5+B+PH

Asset: P.S. 192 - BROOKLYN, 4715 18 AVENUE, New York, 11204

Inspection Id Inspection Type Time In Last Edited

SA : K192 Architectural - Senior 2018-04-02 8:00 AM 2018-06-12 5:26 PM

AA : K192 Architectural - Associate 2018-04-02 7:32 AM 2018-04-10 12:28 PM

Asset Data

Question Answer

Was the building fully accessible for inspection No

Inspection Access Comment 1. Plaza Deck (Roof 5), Site/Paving Student Use/Concrete,Site/Drainage System for Concrete/Catchbasin/Manhole - Due tostaging area; 2. Cornice, Louver, Roof Barrier, Exterior Guards,Window Lintels, Security Lights - Due to scaffolding; 3. Site/PlayingSurface/Playing Field - Covered in snow.

Principal(s) Information

Principal Name Liset Isaac

Organization P.S./I.S. 192 - Brooklyn

Did you meet with this Principal? No

Did this Principal provide feedback? Yes

Summary of Principal's Feedback A Principal questionnaire form was returned with the followingcomments: 1. Student and Staff Toilet Rooms are in need of anupgrade. 2. Classroom door locks should be re-keyed with amaster-key system. 3. Exterior doors are in poor overall condition andshould be repaired or upgraded.

Principal Name Johanna Schneider

Organization P.S. 36K - Brooklyn

Did you meet with this Principal? No

Did this Principal provide feedback? No

Custodian James Orlando

Fireman Larry Guarinello

Building Square Footage 76000

Comments on the Area None

Comments on the Stories (Floors) plus Basements 5+B+PH

Comments on the Number of Classrooms 45

Comments on the Year Built 1923

Student Population 751

Staff Population 175

Weather Snow

Facade Photo

Corner of 18th Avenue and 48th Street -Northeast View

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2017 - 2018

K192

PB/A&W Print Date: 6/26/2018Page 1 of 32

Page 2: NYC Department of Education · Fireman Larry Guarinello Building Square Footage 76000 Comments on the Area None Comments on the Stories (Floors) plus Basements 5+B+PH

Main Entrance Photo

Facade A - 18th Avenue

Roof Photo

Roof 1 - Southwest View

Have any Systems/Major Building Components been upgraded? Yes

Systems: Foundation Wall Waterproofing in Electrical Room

Year: 2017

Systems: New Playground at East side; 1st Floor Boys and GirlsToilet Rooms upgrade

Year: 2015

Systems: Partial Exterior Masonry renovation; Parapets repairs;Coping and main roof Parapets replacement; New MetalSiding on Bulkheads and Penthouse

Year: 2011

Systems: Partial Areaway Grating replacement

Year: 2010

Systems: Partial Foundation Wall waterproofing; Partial Structuralrepairs; Oil Tank Room reconstruction

Year: 2009

Systems: Roofing and Flashing replacement; Windows, WindowGuards and Shades replacement; Auditorium upgradeincluding Seating, Flooring, Curtains replacement

Year: 2008

Have there been any New Building Additions? No

Tandem Schools? No

Leased Space? No

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2017 - 2018

K192

PB/A&W Print Date: 6/26/2018Page 2 of 32

Page 3: NYC Department of Education · Fireman Larry Guarinello Building Square Footage 76000 Comments on the Area None Comments on the Stories (Floors) plus Basements 5+B+PH

Priority Condition

PriorityCondition ExistLast Year?

PriorityCategory

ConditionDescription

ComponentAffected

LocationDescription

Person(s)Notified

Person(s) Title PhotoImage

Yes ProtrudingElements

MissingBackrest is aPotential SafetyHazard

INTERIOR |AUDITORIUM| Fixed Seating

Seat T/2 James Orlando Custodian

Structural Engineer Required

StructuralCondition Type

ConditionDescription

ComponentAffected

LocationDescription

Person(s)Notified

Person(s) Title PhotoImage

No condition recorded

Accessibility

Accessibility Status Question Response

Is the primary or secondary entrance on an accessible route? Yes

Is the building a multi-story building? Yes

Are all floors of the building accessible through compliant means? No

Are SOME floors other than the 1st floor and basement accessible through compliantmeans?

No

Do any of the following spaces exist on the First floor? Classroom, Art Room,Auditorium, Cafeteria, Computer, Gymnasiums, Library, Multipurpose Room, ScienceLabs

Yes

For the rooms that do exist, are SOME of them accessible on the 1st floor? Yes

Boys and Girls or Unisex accessible toilets exist on the 1st floor? No

Physical Breakdown Structure Exists Complies Required Deficiency

FUNCTIONAL ACCESSIBILITY

Exterior Routes

Exterior Entrances & Exits Yes

Exterior H/C Lifts No No

Exterior Ramps and Railings No No

Interior Routes

Corridor and Lobby H/C Lifts No No

Interior Corridor Doors and Hardware Yes Yes

Interior Corridors and Lobbies Yes

Interior Elevators No

Interior Lobby Doors and Hardware Yes

Interior Ramps No

Rooms & Spaces

Art Rooms No

Auditorium 2nd Floor No No Stage AccessNot on Accessible Route

Cafeteria 1st Floor Yes

Classrooms None on Accessible Route No Not on Accessible Route

Computer Rooms No

Gymnasium No

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2017 - 2018

K192

PB/A&W Print Date: 6/26/2018Page 3 of 32

Page 4: NYC Department of Education · Fireman Larry Guarinello Building Square Footage 76000 Comments on the Area None Comments on the Stories (Floors) plus Basements 5+B+PH

Physical Breakdown Structure Exists Complies Required Deficiency

Rooms & Spaces

Library Room 409 No Not on Accessible Route

Main Office Room 205 (P.S./I.S. 192); Room 402 (P.S.36K)

No Not on Accessible Route

Multi-purpose Room 1st Floor - East, 1st Floor - West Yes

Nurse's Room Rooms 320, 451 No Clear opening < 32"Not on Accessible Route

Pool No

Science Lab No

Toilet Rooms (Boys) 1st Floor No Accessory ArrangementSink ArrangementTurning RadiusUrinal ArrangementWater Closet Arrangement

Toilet Rooms (Girls) 1st Floor No Accessory ArrangementSink ArrangementTurning RadiusWater Closet Arrangement

Toilet Rooms (Staff) 1st Floor - Men No Accessory ArrangementClear opening < 32"No Lever-type HardwareSink ArrangementTurning RadiusUrinal ArrangementWater Closet Arrangement

1st Floor - Women No Accessory ArrangementClear opening < 32"No Lever-type HardwareSink ArrangementUrinal ArrangementWater Closet Arrangement

Building Template

Inspection

Question Response

Architectural

EXTERIOR Inspected

AREAWAY Inspected

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2017 - 2018

K192

PB/A&W Print Date: 6/26/2018Page 4 of 32

Page 5: NYC Department of Education · Fireman Larry Guarinello Building Square Footage 76000 Comments on the Area None Comments on the Stories (Floors) plus Basements 5+B+PH

Question Response

EXTERIOR

AREAWAY

InspectedInstance on AW1 - AW6

Instance Condition 1 - Good

Instance Quantity 6

Instance Quantity Uom EACH

Deficiency No deficiencies recorded

AWNINGS AND CANOPIES Does not Exist

CHIMNEY Inspected

Material Type(s) Masonry

Condition 1 - Good

Deficiency No deficiencies recorded

COPING Under Construction

CORNICE Inaccessible

DOORS Inspected

DOORS AND FRAMES Inspected

Condition 5 - Poor

Deficiency METAL: DETERIORATED DOOR - MAJOR DETERIORATION

Roof Plan reference

Deficiency Quantity 1

Quantity Uom EACH

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Facade F - Boiler Room Exit

Violations No violations recorded.

Deficiency METAL CLAD: DETERIORATED DOOR - MAJORDETERIORATION

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2017 - 2018

K192

PB/A&W Print Date: 6/26/2018Page 5 of 32

Page 6: NYC Department of Education · Fireman Larry Guarinello Building Square Footage 76000 Comments on the Area None Comments on the Stories (Floors) plus Basements 5+B+PH

Question Response

EXTERIOR

DOORS

DOORS AND FRAMES

Roof Plan reference

Deficiency Quantity 7

Quantity Uom EACH

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Facade A - Main Entrance

Violations No violations recorded.

DOOR HARDWARE Inspected

Condition 3 - Fair

Deficiency No deficiencies recorded

LINTELS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

TRANSOM/SIDE LIGHT Does not Exist

EXTERIOR WALLS Inspected

Material Type(s) Masonry

Replacement Quantity 38,000

Replacement Uom S.F.

Under ConstructionInstance on All Facades

Instance Quantity 38,000

Instance Quantity Uom S.F.

EXTERIOR SOFFITS Does not Exist

LOADING DOCK Does not Exist

LOUVER Inaccessible

PARAPETS Inspected

Material Type(s) Masonry

Replacement Quantity 4,500

Replacement Uom C.F.

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2017 - 2018

K192

PB/A&W Print Date: 6/26/2018Page 6 of 32

Page 7: NYC Department of Education · Fireman Larry Guarinello Building Square Footage 76000 Comments on the Area None Comments on the Stories (Floors) plus Basements 5+B+PH

Question Response

EXTERIOR

PARAPETS Inspected

Under ConstructionInstance on All Facades

Instance Quantity 4,500

Instance Quantity Uom C.F.

PLAZA DECK Inspected

Under ConstructionInstance on Pavers: Roof 4

Instance Quantity 2,600

Instance Quantity Uom S.F.

InaccessibleInstance on Concrete: Roof 5 - at Schoolyard

Instance Quantity 2,000

Instance Quantity Uom S.F.

ROOF Inspected

Roofing Inspected

Replacement Quantity 12,800

Replacement Uom S.F.

ROOF HATCH/SMOKE HATCH Does not Exist

LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

ROOF BARRIER Inaccessible

ROOF CAGE Under Construction

ROOF FENCE Does not Exist

ROOFING Inspected

InspectedInstance on Built-Up: All Roofs

Instance Condition 2 - Between Good and Fair

Instance Quantity 12,800

Instance Quantity Uom S.F.

Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?

No

Installation Year 2008

Source of Installation Documented

Deficiency No deficiencies recorded

ROOFING DRAINS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Specialties Inspected

BULKHEAD/PENTHOUSE Inspected

Condition 4 - Between Fair and Poor

Deficiency BULKHEAD/PENTHOUSE DOORS: DETERIORATED DOOR

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2017 - 2018

K192

PB/A&W Print Date: 6/26/2018Page 7 of 32

Page 8: NYC Department of Education · Fireman Larry Guarinello Building Square Footage 76000 Comments on the Area None Comments on the Stories (Floors) plus Basements 5+B+PH

Question Response

EXTERIOR

ROOF

Specialties

BULKHEAD/PENTHOUSE

Roof Plan reference

Deficiency Quantity 1

Quantity Uom EACH

Potential Action REPLACE DOOR

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

PH - South (Door is very difficult to open)

Violations No violations recorded.

Deficiency BULKHEAD/PENTHOUSE WALLS/INTERIOR: BRICKCRACKS/SPALLING

Roof Plan reference

Deficiency Quantity 40

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2017 - 2018

K192

PB/A&W Print Date: 6/26/2018Page 8 of 32

Page 9: NYC Department of Education · Fireman Larry Guarinello Building Square Footage 76000 Comments on the Area None Comments on the Stories (Floors) plus Basements 5+B+PH

Question Response

EXTERIOR

ROOF

Specialties

BULKHEAD/PENTHOUSE

Deficiency Photo1

Fan Room at BH2

Violations No violations recorded.

Deficiency BULKHEAD/PENTHOUSE WALLS/INTERIOR: PLASTERCRACKS/SPALLING

Roof Plan reference

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Roof 1 - BH1

Violations No violations recorded.

CUPOLA/ SPIRES/ TOWERS Does not Exist

DORMER Does not Exist

DUNNAGE STEEL Does not Exist

SKYLIGHT/ROOF VENT Does not Exist

ROOF/GRAVITY TANK Does not Exist

STAIRS/RAMPS: EXTERIOR Inspected

BUILDING CHEEK/FLANK WALLS Does not Exist

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2017 - 2018

K192

PB/A&W Print Date: 6/26/2018Page 9 of 32

Page 10: NYC Department of Education · Fireman Larry Guarinello Building Square Footage 76000 Comments on the Area None Comments on the Stories (Floors) plus Basements 5+B+PH

Question Response

EXTERIOR

STAIRS/RAMPS: EXTERIOR

RAILINGS Does not Exist

STAIRS/RAMPS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

WINDOWS Inspected

Replacement Quantity 13,000

Replacement Uom S.F.

EXTERIOR GUARDS Inaccessible

LINTELS Inaccessible

WINDOWS Inspected

Material Type(s) Aluminum

InspectedInstance on Aluminum - Double Hung: All Facades

Instance Condition 2 - Between Good and Fair

Instance Quantity 13,000

Instance Quantity Uom S.F.

Installation Year 2008

Source of Installation Documented

Deficiency ALUMINUM - DOUBLE HUNG: INOPERABLE BALANCE

Roof Plan reference

Elevation

Deficiency Quantity 10

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1 No photo recorded

Violations No violations recorded.

INTERIOR Inspected

POOLS Does not Exist

STRUCTURAL Inspected

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2017 - 2018

K192

PB/A&W Print Date: 6/26/2018Page 10 of 32

Page 11: NYC Department of Education · Fireman Larry Guarinello Building Square Footage 76000 Comments on the Area None Comments on the Stories (Floors) plus Basements 5+B+PH

Question Response

INTERIOR

STRUCTURAL

COLUMNS/BEAMS/BEARING WALLS Inspected

Condition 3 - Fair

Deficiency CONCRETE COLUMNS/BEAMS:CRACKED/SPALLED/REINFORCEMENT EXPOSED

Deficiency Location/Instance Basement - Boiler Room, near Oil Tank Room, Fan Room nearElectrical Room

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 5

Deficiency Photo1

Basement - Near Oil Tank Room

Violations No violations recorded.

FLOOR STRUCTURE Inspected

Condition 3 - Fair

Deficiency CONCRETE: CRACKS/SPALLED/REINFORCEMENT EXPOSED

Deficiency Location/Instance Basement - Fan Room near Sprinkler Head Room, 3rd Floor -Auditorium Fan Room, Penthouse

Deficiency Quantity 80

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 5

Deficiency Photo1

Auditorium Fan Room

Violations No violations recorded.

Deficiency CONCRETE SLAB ON GRADE: MINOR CRACKS

Deficiency Location/Instance Basement - Fan Room near Electrical Room

Deficiency Quantity 40

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2017 - 2018

K192

PB/A&W Print Date: 6/26/2018Page 11 of 32

Page 12: NYC Department of Education · Fireman Larry Guarinello Building Square Footage 76000 Comments on the Area None Comments on the Stories (Floors) plus Basements 5+B+PH

Question Response

INTERIOR

STRUCTURAL

FLOOR STRUCTURE

Purpose of Action LEVEL 5

Deficiency Photo1

Fan Room near Electrical Room

Violations No violations recorded.

FOUNDATION WALLS Inspected

Material Type(s) Concrete

Condition 3 - Fair

Deficiency CONCRETE: WATER INFILTRATION IN NON- INSTRUCTIONALSPACE

Deficiency Location/Instance Basement - Near Entrance to Heating Chamber

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action INSTALL WATERPROOFING

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 5

Deficiency Photo1

Near Entrance to Heating Chamber

Violations No violations recorded.

Deficiency CONCRETE: CRACKED/SPALLED/REINFORCEMENTEXPOSED

Deficiency Location/Instance Basement - Boiler Room, Area near Sprinkler Head Room Corridor toHeating Chamber

Deficiency Quantity 50

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 5

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2017 - 2018

K192

PB/A&W Print Date: 6/26/2018Page 12 of 32

Page 13: NYC Department of Education · Fireman Larry Guarinello Building Square Footage 76000 Comments on the Area None Comments on the Stories (Floors) plus Basements 5+B+PH

Question Response

INTERIOR

STRUCTURAL

FOUNDATION WALLS

Deficiency Photo1

Basement - Area near Sprinkler Head Room

Violations No violations recorded.

ROOF STRUCTURE Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

VAULTS-BUNKERS Inspected

Foundation Walls Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Slab Structure Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Vault/Ash Hoist Doors and Framing Inspected

Condition 5 - Poor

Deficiency DETERIORATED/DAMAGED VAULT/ASH HOIST DOORS ANDFRAMING

Deficiency Location/Instance Basement - Ash Hoist Door

Deficiency Quantity 1

Quantity Uom EACH

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Ash Hoist Door

Violations No violations recorded.

AUDITORIUM Inspected

InspectedInstance on 2nd Floor- 540 Seats

Ceiling

InspectedInstance on 2nd Floor- 540 Seats

Condition 2 - Between Good and Fair

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2017 - 2018

K192

PB/A&W Print Date: 6/26/2018Page 13 of 32

Page 14: NYC Department of Education · Fireman Larry Guarinello Building Square Footage 76000 Comments on the Area None Comments on the Stories (Floors) plus Basements 5+B+PH

Question Response

INTERIOR

AUDITORIUM

Ceiling

Deficiency No deficiencies recorded

Door(s)

InspectedInstance on 2nd Floor- 540 Seats

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Fixed H/C Lift

Does not ExistInstance on 2nd Floor- 540 Seats

Fixed Seating

InspectedInstance on 2nd Floor- 540 Seats

Condition 2 - Between Good and Fair

Deficiency DAMAGED/BROKEN/INOPERABLE

Deficiency Location/Instance Seats B/110, J/105, M/5, P/17

Deficiency Quantity 4

Quantity Uom EACH

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Seat M/5

Violations No violations recorded.

Deficiency DAMAGED/BROKEN/INOPERABLE

Deficiency Location/Instance Seat T/2

Deficiency Quantity 1

Quantity Uom EACH

Potential Action REPLACE

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 6

Deficiency Photo1

Seat T/2

Violations No violations recorded.

Floor Finish

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2017 - 2018

K192

PB/A&W Print Date: 6/26/2018Page 14 of 32

Page 15: NYC Department of Education · Fireman Larry Guarinello Building Square Footage 76000 Comments on the Area None Comments on the Stories (Floors) plus Basements 5+B+PH

Question Response

INTERIOR

AUDITORIUM

Floor Finish

InspectedInstance on 2nd Floor- 540 Seats

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Sliding-folding Partition

Does not ExistInstance on 2nd Floor- 540 Seats

Stage

InspectedInstance on 2nd Floor- 540 Seats

Stage Inspected

InspectedInstance on 2nd Floor- 540 Seats

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Stage Curtain Rigging Inspected

InspectedInstance on 2nd Floor- 540 Seats

Condition 1 - Good

Deficiency No deficiencies recorded

Stage Curtains Inspected

InspectedInstance on 2nd Floor- 540 Seats

Condition 1 - Good

Deficiency No deficiencies recorded

Walls

InspectedInstance on 2nd Floor- 540 Seats

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Window Curtains/Shades/Blinds

InspectedInstance on 2nd Floor- 540 Seats

Condition 1 - Good

Deficiency No deficiencies recorded

CAFETERIA Inspected

InspectedInstance on 1st Floor

Ceiling

Does not ExistInstance on 1st Floor

Door(s)

InspectedInstance on 1st Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Fixed Equipment

Does not ExistInstance on 1st Floor

Floor Finish

InspectedInstance on 1st Floor

Condition 2 - Between Good and Fair

Deficiency WOOD: DAMAGED/DETERIORATED

Deficiency Location/Instance Southwest

Deficiency Quantity 50

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2017 - 2018

K192

PB/A&W Print Date: 6/26/2018Page 15 of 32

Page 16: NYC Department of Education · Fireman Larry Guarinello Building Square Footage 76000 Comments on the Area None Comments on the Stories (Floors) plus Basements 5+B+PH

Question Response

INTERIOR

CAFETERIA

Floor Finish

Deficiency Photo1

Southwest

Violations No violations recorded.

Sliding-folding Partition

Does not ExistInstance on 1st Floor

Stage

Does not ExistInstance on 1st Floor

Walls

InspectedInstance on 1st Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Window Curtains/Shades/Blinds

Does not ExistInstance on 1st Floor

CLASSROOMS/CORRIDORS/ADMIN SPACES Inspected

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s) Inspected

Condition 5 - Poor

Deficiency METAL CLAD WOOD: DETERIORATED DOOR

Deficiency Location/Instance Cross Corridor Near Room 308

Deficiency Quantity 1

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Cross Corridor Near Room 308

Violations No violations recorded.

Deficiency WOOD: DETERIORATED DOOR

Deficiency Location/Instance Rooms 302, 303, 351, 406, 504, 551

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2017 - 2018

K192

PB/A&W Print Date: 6/26/2018Page 16 of 32

Page 17: NYC Department of Education · Fireman Larry Guarinello Building Square Footage 76000 Comments on the Area None Comments on the Stories (Floors) plus Basements 5+B+PH

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Door(s)

Deficiency Quantity 6

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room 406

Violations No violations recorded.

Floor Finish Inspected

Condition 3 - Fair

Deficiency VINYL TILES: TRIPPING HAZARD - ELECTRICAL OUTLET

Deficiency Location/Instance Room 510

Deficiency Quantity 5

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 6

Deficiency Photo1

Room 510

Violations No violations recorded.

Deficiency TERRAZZO: CRACKS

Deficiency Location/Instance Main Entrance Lobby, Corridor near Room 209, Corridor NearAuditorium

Deficiency Quantity 150

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2017 - 2018

K192

PB/A&W Print Date: 6/26/2018Page 17 of 32

Page 18: NYC Department of Education · Fireman Larry Guarinello Building Square Footage 76000 Comments on the Area None Comments on the Stories (Floors) plus Basements 5+B+PH

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Floor Finish

Deficiency Photo1

Main Entrance Lobby

Violations No violations recorded.

Deficiency VINYL TILES: DETERIORATED SUBSTRATE

Deficiency Location/Instance Rooms 204, 310, 402, 505, 509 and Others

Deficiency Quantity 1,600

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room 505

Violations No violations recorded.

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency PLASTER: CRACKS/SPALLING

Deficiency Location/Instance Exit 4 Vestibule

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2017 - 2018

K192

PB/A&W Print Date: 6/26/2018Page 18 of 32

Page 19: NYC Department of Education · Fireman Larry Guarinello Building Square Footage 76000 Comments on the Area None Comments on the Stories (Floors) plus Basements 5+B+PH

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Walls

Exit 4 Vestibule

Violations No violations recorded.

Deficiency CERAMIC TILE: BROKEN/ MISSING

Deficiency Location/Instance Exit 6I Vestibule

Deficiency Quantity 5

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Exit 6I Vestibule

Violations No violations recorded.

Specialties Inspected

Classroom Locker(s) Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Fixed Seating Does not Exist

GYMNASIUM Does not Exist

INTERIOR DOOR HARDWARE Inspected

Condition 3 - Fair

Deficiency No deficiencies recorded

INTERIOR GUARDS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

KITCHEN Inspected

InspectedInstance on 1st Floor

Ceiling

Does not ExistInstance on 1st Floor

Door(s)

InspectedInstance on 1st Floor

Condition 3 - Fair

Deficiency METAL CLAD WOOD: DETERIORATED DOOR

Deficiency Location/Instance Entrance

Deficiency Quantity 1

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2017 - 2018

K192

PB/A&W Print Date: 6/26/2018Page 19 of 32

Page 20: NYC Department of Education · Fireman Larry Guarinello Building Square Footage 76000 Comments on the Area None Comments on the Stories (Floors) plus Basements 5+B+PH

Question Response

INTERIOR

KITCHEN

Door(s)

Deficiency Photo1

Entrance

Violations No violations recorded.

Floor Finish

InspectedInstance on 1st Floor

Condition 2 - Between Good and Fair

Deficiency CONCRETE: CRACKS

Deficiency Location/Instance Storage Room

Deficiency Quantity 5

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Storage Room

Violations No violations recorded.

Walls

InspectedInstance on 1st Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

LIBRARY Inspected

InspectedInstance on Room 409

Built-in Furnishing

Does not ExistInstance on Room 409

Ceiling

InspectedInstance on Room 409

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s)

InspectedInstance on Room 409

Condition 2 - Between Good and Fair

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2017 - 2018

K192

PB/A&W Print Date: 6/26/2018Page 20 of 32

Page 21: NYC Department of Education · Fireman Larry Guarinello Building Square Footage 76000 Comments on the Area None Comments on the Stories (Floors) plus Basements 5+B+PH

Question Response

INTERIOR

LIBRARY

Door(s)

Deficiency No deficiencies recorded

Floor Finish

InspectedInstance on Room 409

Condition 2 - Between Good and Fair

Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES

Deficiency Location/Instance Center, West, East

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Center

Violations No violations recorded.

Walls

InspectedInstance on Room 409

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

LOCKER ROOM Does not Exist

MULTI-PURPOSE ROOM Inspected

InspectedInstance on 1st Floor- West

InspectedInstance on 1st Floor- East

Ceiling

Does not ExistInstance on 1st Floor- East

Does not ExistInstance on 1st Floor- West

Door(s)

InspectedInstance on 1st Floor- West

Condition 4 - Between Fair and Poor

Deficiency WOOD: DETERIORATED DOOR

Deficiency Location/Instance Entrance

Deficiency Quantity 2

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2017 - 2018

K192

PB/A&W Print Date: 6/26/2018Page 21 of 32

Page 22: NYC Department of Education · Fireman Larry Guarinello Building Square Footage 76000 Comments on the Area None Comments on the Stories (Floors) plus Basements 5+B+PH

Question Response

INTERIOR

MULTI-PURPOSE ROOM

Door(s)

Deficiency Photo1

Entrance

Violations No violations recorded.

InspectedInstance on 1st Floor- East

Condition 4 - Between Fair and Poor

Deficiency WOOD: DETERIORATED DOOR

Deficiency Location/Instance Entrance

Deficiency Quantity 2

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Entrance

Violations No violations recorded.

Fixed Equipment

InspectedInstance on 1st Floor- West

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

InspectedInstance on 1st Floor- East

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Floor Finish

InspectedInstance on 1st Floor- West

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

InspectedInstance on 1st Floor- East

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Sliding-folding Partition

Does not ExistInstance on 1st Floor- East

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2017 - 2018

K192

PB/A&W Print Date: 6/26/2018Page 22 of 32

Page 23: NYC Department of Education · Fireman Larry Guarinello Building Square Footage 76000 Comments on the Area None Comments on the Stories (Floors) plus Basements 5+B+PH

Question Response

INTERIOR

MULTI-PURPOSE ROOM

Sliding-folding Partition

Does not ExistInstance on 1st Floor- West

Stage

Does not ExistInstance on 1st Floor- West

Does not ExistInstance on 1st Floor- East

Walls

InspectedInstance on 1st Floor- East

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

InspectedInstance on 1st Floor- West

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Window Curtains/Shades/Blinds

Does not ExistInstance on 1st Floor- East

Does not ExistInstance on 1st Floor- West

SCIENCE DEMO ROOM Does not Exist

SCIENCE LAB Does not Exist

SCIENCE PREP ROOM Does not Exist

SHOWER ROOM Does not Exist

STAIRS/RAMPS: INTERIOR Inspected

Do Letter Stair Signs Exist? Yes

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s) Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Partition Inspected

Condition 2 - Between Good and Fair

Deficiency GLASS PANEL: DAMAGED/DETERIORATED

Deficiency Location/Instance Stairs BC/2,4,Bulkhead, FG/2,4 and Others

Deficiency Quantity 45

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Stair BC/2

Violations No violations recorded.

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2017 - 2018

K192

PB/A&W Print Date: 6/26/2018Page 23 of 32

Page 24: NYC Department of Education · Fireman Larry Guarinello Building Square Footage 76000 Comments on the Area None Comments on the Stories (Floors) plus Basements 5+B+PH

Question Response

INTERIOR

STAIRS/RAMPS: INTERIOR

Railings Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Stairs and Landings Inspected

Condition 4 - Between Fair and Poor

Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES

Deficiency Location/Instance Stairs BC/1, D/2, E/4

Deficiency Quantity 50

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Stair BC/1

Violations No violations recorded.

Deficiency ROLLED ASPHALT: CRACKS

Deficiency Location/Instance Stairs BC/Bulkhead, FG/Bulkhead

Deficiency Quantity 360

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Stair BC/Bulkhead

Violations No violations recorded.

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

TOILET ROOMS - STAFF Inspected

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2017 - 2018

K192

PB/A&W Print Date: 6/26/2018Page 24 of 32

Page 25: NYC Department of Education · Fireman Larry Guarinello Building Square Footage 76000 Comments on the Area None Comments on the Stories (Floors) plus Basements 5+B+PH

Question Response

INTERIOR

TOILET ROOMS - STAFF

Door(s) Inspected

Condition 5 - Poor

Deficiency WOOD: DETERIORATED DOOR

Deficiency Location/Instance 1st Floor Men Toilet Room, 1st Floor Kitchen Staff Toilet Room

Deficiency Quantity 2

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

1st Floor Men Toilet Room

Violations No violations recorded.

Floor Finish Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Stalls Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency CERAMIC TILE: BROKEN/ MISSING

Deficiency Location/Instance Inside Room 451

Deficiency Quantity 5

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Inside Room 451

Violations No violations recorded.

TOILET ROOMS - STUDENTS Inspected

Ceiling Inspected

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2017 - 2018

K192

PB/A&W Print Date: 6/26/2018Page 25 of 32

Page 26: NYC Department of Education · Fireman Larry Guarinello Building Square Footage 76000 Comments on the Area None Comments on the Stories (Floors) plus Basements 5+B+PH

Question Response

INTERIOR

TOILET ROOMS - STUDENTS

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s) Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Floor Finish Inspected

Condition 2 - Between Good and Fair

Deficiency CERAMIC TILE: BROKEN/MISSING TILES

Deficiency Location/Instance 4th Floor Boys Toilet Room

Deficiency Quantity 5

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

4th Floor Boys Toilet Room

Violations No violations recorded.

Stalls Inspected

Condition 3 - Fair

Deficiency BROKEN/MISSING

Deficiency Location/Instance 4th Floor Boys Toilet Room

Deficiency Quantity 1

Quantity Uom EACH

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

4th Floor Boys Toilet Room

Violations No violations recorded.

Walls Inspected

Condition 2 - Between Good and Fair

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2017 - 2018

K192

PB/A&W Print Date: 6/26/2018Page 26 of 32

Page 27: NYC Department of Education · Fireman Larry Guarinello Building Square Footage 76000 Comments on the Area None Comments on the Stories (Floors) plus Basements 5+B+PH

Question Response

INTERIOR Inspected

TOILET ROOMS - STUDENTS Inspected

Walls

Deficiency No deficiencies recorded

LIFE SAFETY Inspected

F.D. HOLDING AREA Does not Exist

STEEL STAIRS Does not Exist

SITE Inspected

CONTAINERIZATION Inspected

Condition 5 - Poor

Deficiency FENCING MISSING

Deficiency Location/Instance Near 47th Street

Deficiency Quantity 600

Quantity Uom S.F.

Potential Action INSTALL NEW

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1 No photo recorded

Violations No violations recorded.

Deficiency CONTAINER DAMAGED

Deficiency Location/Instance Near 47th Street

Deficiency Quantity 1

Quantity Uom EACH

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Near 47th Street

Violations No violations recorded.

Drainage System for Asphalt Inspected

Catch Basins/Manhole - Surrounded by asphalt Inspected

Condition 1 - Good

Deficiency No deficiencies recorded

Culverts - Asphalt Covering Does not Exist

Drainage System for Concrete Inspected

Catch Basins/Manhole - Surrounded by concrete Inaccessible

Culverts - Concrete Covering Does not Exist

Drainage System for Soil Does not Exist

DRINKING FOUNTAINS Inspected

Condition 1 - Good

Deficiency No deficiencies recorded

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2017 - 2018

K192

PB/A&W Print Date: 6/26/2018Page 27 of 32

Page 28: NYC Department of Education · Fireman Larry Guarinello Building Square Footage 76000 Comments on the Area None Comments on the Stories (Floors) plus Basements 5+B+PH

Question Response

SITE

FENCES Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

IRRIGATION SYSTEM Does not Exist

PAVING Inspected

Student Non-Use Inspected

Gravel Exists? No

Asphalt Does not Exist

Concrete Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Pavers Does not Exist

Student Use Inspected

Gravel Exists? No

Asphalt Inspected

Condition 3 - Fair

Deficiency CRACKS - MAJOR

Deficiency Location/Instance Schoolyard

Deficiency Quantity 320

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Schoolyard- East

Violations No violations recorded.

Concrete Inaccessible

Pavers Inspected

Condition 1 - Good

Deficiency No deficiencies recorded

Site Sidewalks & Walkways Inspected

Asphalt Does not Exist

Concrete Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Pavers Does not Exist

DOT Sidewalk Inspected

Asphalt Does not Exist

Concrete Inspected

Condition 4 - Between Fair and Poor

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2017 - 2018

K192

PB/A&W Print Date: 6/26/2018Page 28 of 32

Page 29: NYC Department of Education · Fireman Larry Guarinello Building Square Footage 76000 Comments on the Area None Comments on the Stories (Floors) plus Basements 5+B+PH

Question Response

SITE

PAVING

DOT Sidewalk

Concrete

Deficiency DAMAGED CURBS

Deficiency Location/Instance Along 18th Avenue, Along 47th Street, Along 48th Street

Deficiency Quantity 30

Quantity Uom L.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Along 47th Street

Violations No violations recorded.

Deficiency HEAVING

Deficiency Location/Instance Along 47th Street, Along 48th Street

Deficiency Quantity 125

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 6

Deficiency Photo1

Along 48th Street

Violations No violations recorded.

Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS

Deficiency Location/Instance Along 18th Avenue, Along 47th Street, Along 48th Street

Deficiency Quantity 700

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2017 - 2018

K192

PB/A&W Print Date: 6/26/2018Page 29 of 32

Page 30: NYC Department of Education · Fireman Larry Guarinello Building Square Footage 76000 Comments on the Area None Comments on the Stories (Floors) plus Basements 5+B+PH

Question Response

SITE

PAVING

DOT Sidewalk

Concrete

Deficiency Photo1

Along 48th Street

Violations No violations recorded.

Pavers Does not Exist

PLAYGROUNDS Inspected

InspectedInstance on Schoolyard- Center West

InspectedInstance on Schoolyard- East

InspectedInstance on Schoolyard- Northwest

InspectedInstance on Schoolyard- Southwest

Benches

InspectedInstance on Schoolyard- Northwest

Condition 1 - Good

Deficiency No deficiencies recorded

InspectedInstance on Schoolyard- Southwest

Condition 1 - Good

Deficiency No deficiencies recorded

InspectedInstance on Schoolyard- Center West

Condition 1 - Good

Deficiency No deficiencies recorded

InspectedInstance on Schoolyard- East

Condition 1 - Good

Deficiency No deficiencies recorded

Fence

InspectedInstance on Schoolyard- Center West

Condition 1 - Good

Deficiency No deficiencies recorded

InspectedInstance on Schoolyard- East

Condition 1 - Good

Deficiency No deficiencies recorded

InspectedInstance on Schoolyard- Northwest

Condition 1 - Good

Deficiency No deficiencies recorded

InspectedInstance on Schoolyard- Southwest

Condition 1 - Good

Deficiency No deficiencies recorded

Pavement

InspectedInstance on Schoolyard- Southwest

Condition 1 - Good

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2017 - 2018

K192

PB/A&W Print Date: 6/26/2018Page 30 of 32

Page 31: NYC Department of Education · Fireman Larry Guarinello Building Square Footage 76000 Comments on the Area None Comments on the Stories (Floors) plus Basements 5+B+PH

Question Response

SITE

PLAYGROUNDS

Pavement

Deficiency No deficiencies recorded

InspectedInstance on Schoolyard- Center West

Condition 1 - Good

Deficiency No deficiencies recorded

InspectedInstance on Schoolyard- East

Condition 1 - Good

Deficiency No deficiencies recorded

InspectedInstance on Schoolyard- Northwest

Condition 1 - Good

Deficiency No deficiencies recorded

Play Equipment

InspectedInstance on Schoolyard- Center West

Condition 1 - Good

Deficiency No deficiencies recorded

InspectedInstance on Schoolyard- East

Condition 1 - Good

Deficiency No deficiencies recorded

InspectedInstance on Schoolyard- Northwest

Condition 1 - Good

Deficiency No deficiencies recorded

InspectedInstance on Schoolyard- Southwest

Condition 1 - Good

Deficiency No deficiencies recorded

Safety Surfacing

InspectedInstance on Schoolyard- Center West

Condition 1 - Good

Deficiency No deficiencies recorded

InspectedInstance on Schoolyard- Southwest

Condition 1 - Good

Deficiency No deficiencies recorded

InspectedInstance on Schoolyard- East

Condition 1 - Good

Deficiency No deficiencies recorded

InspectedInstance on Schoolyard- Northwest

Condition 1 - Good

Deficiency No deficiencies recorded

Unpaved Area

Does not ExistInstance on Schoolyard- Southwest

Does not ExistInstance on Schoolyard- Center West

Does not ExistInstance on Schoolyard- East

Does not ExistInstance on Schoolyard- Northwest

PLAYING SURFACE Inspected

Playing Field Inspected

InaccessibleInstance on Schoolyard- South

Running Track Does not Exist

RETAINING WALLS Inspected

Are there any Retaining Walls 6' OR higher facing publicstreet/sidewalk?

No

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2017 - 2018

K192

PB/A&W Print Date: 6/26/2018Page 31 of 32

Page 32: NYC Department of Education · Fireman Larry Guarinello Building Square Footage 76000 Comments on the Area None Comments on the Stories (Floors) plus Basements 5+B+PH

Question Response

SITE

RETAINING WALLS

Condition 3 - Fair

Deficiency CAST IN PLACE CONCRETE: CRACKS/SPALLING - MAJOR

Deficiency Location/Instance Along 48th Street, Along 47th Street

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Along 48th Street

Violations No violations recorded.

SEATING Inspected

Benches Inspected

Concrete Does not Exist

Metal/Wood/Plastic Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Bleachers Does not Exist

SITE WALLS (NOT RETAINING WALLS) Does not Exist

STAIRS/RAMPS: EXTERIOR Does not Exist

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2017 - 2018

K192

PB/A&W Print Date: 6/26/2018Page 32 of 32