Asset: P.S. 110 - BROOKLYN, 124 MONITOR STREET, New York, 11222
Inspection Id Inspection Type Time In Last Edited
SA : K110 Architectural - Senior 2019-10-31 7:01 AM 2020-09-01 5:00 PM
AA : K110 Architectural - Associate 2019-10-31 7:38 AM 2020-01-28 5:03 PM
Asset Data
Question Answer
Was the building fully accessible for inspection Yes
Principal(s) Information
Principal Name Dana Raciunas (Acting Principal)
Organization P.S. 110 – Brooklyn
Did you meet with this Principal? Yes
Did this Principal provide feedback? Yes
Summary of Principal's Feedback The Principal's comments are as follows: 1. The floors in the corridorsand classrooms are deteriorated and require an upgrade. 2. The toiletsrooms are antiquated and require an upgrade.
Custodian James Carbonaro
Fireman Alex Enriquez
Building Square Footage 67,000
Comments on the Area None
Comments on the Stories (Floors) plus Basements 4+B+Attic
Comments on the Number of Classrooms 38
Comments on the Year Built 1895
Student Population 594
Staff Population 73
Weather Fair
Facade Photo
Corner of Monitor Street at Driggs Avenue -Northeast View
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K110
PB/A&W Print Date: 9/14/2020Page 1 of 44
Main Entrance Photo
Facade A - Monitor Street
Roof Photo
Roof 3 - Northeast View
Have any Systems/Major Building Components been upgraded? Yes
Systems: New Windows, repairs to Metal Roofing; New Built UpRoofing and Modified Bitumen Roofing; New Flashing;New Roof Hatches; Interior upgrades
Year: 2014
Systems: New Elevator
Year: 2010
Systems: Limited Window repairs; Foundation Waterproofing;Exterior Masonry repairs; Limited Roof repairs; LimitedDoor replacement; Boys and Girls Toilet Room upgradeson 2nd and 3rd Floors.
Year: 2002
Have there been any New Building Additions? Yes
Comments on New Building Additions 2010 (+4500 SF)
Tandem Schools? No
Leased Space? No
Priority Condition
PriorityCondition ExistLast Year?
PriorityCategory
ConditionDescription
ComponentAffected
LocationDescription
Person(s)Notified
Person(s) Title PhotoImage
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K110
PB/A&W Print Date: 9/14/2020Page 2 of 44
No condition recorded
Structural Engineer Required
StructuralCondition Type
ConditionDescription
ComponentAffected
LocationDescription
Person(s)Notified
Person(s) Title PhotoImage
No condition recorded
Accessibility
Accessibility Status Question Response
Is the primary or secondary entrance on an accessible route? Yes
Is the building a multi-story building? Yes
Are all floors of the building accessible through compliant means? Yes
Accessible classrooms exists on each floor? Yes
Boys and Girls or Unisex accessible toilets exist on at least every other floor? No
Is there at least one Boys and Girls or Unisex toilet accessible in the building? Yes
If the following spaces exist, are SOME accessible? Art Room, Auditorium,Cafeteria, Computer, Gymnasiums, Library, Multipurpose Room, Science Labs
Yes
Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem
FireAlarmStrobe
FUNCTIONAL ACCESSIBILITY
Exterior Routes
Exterior Entrances & Exits Yes
Exterior H/C Lifts No No
Exterior Ramps and Railings Yes Yes
Interior Routes
Corridor and Lobby H/C Lifts No No
Interior Corridor Doors and Hardware No No
Interior Corridors and Lobbies Yes
Interior Elevators Yes Yes
Interior Lobby Doors and Hardware Yes
Interior Ramps No
Rooms & Spaces
Art Rooms Room 303 Yes Yes
Auditorium 4th Floor Yes Yes Yes Yes
Cafeteria 1st Floor Yes Yes No Yes
Classrooms 1st - 4th Floors Yes Yes
Computer Rooms Room 209 Yes Yes
Gymnasium 3rd Floor Yes Yes Yes Yes
Library Room 207/208 Yes Yes
Main Office Room 106A Yes Yes
Multi-purpose Room Basement - North Yes Yes No No
Basement - South Yes No Not on Accessible Route No No
Nurse's Room Room 109 Yes Yes
Pool No
Science Lab No
Toilet Rooms (Boys) 1st and 3rd Floor Yes Yes
Toilet Rooms (Girls) 1st and 2nd Floor Yes Yes
Toilet Rooms (Staff) 1st - 4th Floors Yes Yes
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K110
PB/A&W Print Date: 9/14/2020Page 3 of 44
Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem
FireAlarmStrobe
Building Template
Inspection
Question Response
Architectural
EXTERIOR Inspected
AREAWAY Inspected
InspectedInstance on AW1-AW2
Instance Condition 3 - Fair
Instance Quantity 2
Instance Quantity Uom EACH
Deficiency AREAWAY GRATINGS: MINOR RUSTING
Roof Plan reference
Deficiency Quantity 100
Quantity Uom S.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K110
PB/A&W Print Date: 9/14/2020Page 4 of 44
Question Response
EXTERIOR
AREAWAY
Deficiency Photo1
AW2
Violations No violations recorded.
Deficiency AREAWAY DRAINS: CLOGGED
Roof Plan reference
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
Deficiency Photo1
AW
Violations No violations recorded.
AWNINGS AND CANOPIES Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
CHIMNEY Inspected
Material Type(s) Masonry
Condition 3 - Fair
Deficiency BRICK: DETERIORATED CAP
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K110
PB/A&W Print Date: 9/14/2020Page 5 of 44
Question Response
EXTERIOR
CHIMNEY
Roof Plan reference
Deficiency Quantity 15
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Chimney
Violations No violations recorded.
COPING Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
CORNICE Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
DOORS Inspected
DOORS AND FRAMES Inspected
Condition 3 - Fair
Deficiency METAL: DETERIORATED DOOR AND FRAME - MINORDETERIORATION
Roof Plan reference
Deficiency Quantity 2
Quantity Uom EACH
Potential Action MAINTENANCE
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K110
PB/A&W Print Date: 9/14/2020Page 6 of 44
Question Response
EXTERIOR
DOORS
DOORS AND FRAMES
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade H
Violations No violations recorded.
DOOR HARDWARE Inspected
Condition 3 - Fair
Deficiency No deficiencies recorded
LINTELS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
TRANSOM/SIDE LIGHT Does not Exist
EXTERIOR WALLS Inspected
Material Type(s) Masonry, Concrete
Replacement Quantity 24,500
Replacement Uom S.F.
InspectedInstance on All Facades
Instance Condition 3 - Fair
Instance Quantity 24,500
Instance Quantity Uom S.F.
Deficiency BRICK: CRACKS/DISPLACED/SPALLED BRICK AT BUILDINGCORNERS
Roof Plan reference
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K110
PB/A&W Print Date: 9/14/2020Page 7 of 44
Question Response
EXTERIOR
EXTERIOR WALLS
Elevation
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REMOVE AND REBUILD
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade H
Violations No violations recorded.
Deficiency BRICK: MINOR CRACKS AND SPALLING
Roof Plan reference
Elevation
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action RESTITCH
Urgency of Action PRIORITY 3
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K110
PB/A&W Print Date: 9/14/2020Page 8 of 44
Question Response
EXTERIOR
EXTERIOR WALLS
Purpose of Action LEVEL 2
Deficiency Photo1
Facade H
Violations No violations recorded.
Deficiency CAST IN PLACE / PRE-CAST CONCRETE: MAJORCRACKS/SPALLING
Roof Plan reference
Elevation
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade H
Violations No violations recorded.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K110
PB/A&W Print Date: 9/14/2020Page 9 of 44
Question Response
EXTERIOR
EXTERIOR SOFFITS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LOADING DOCK Does not Exist
LOUVER Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
PARAPETS Inspected
Material Type(s) Masonry
Replacement Quantity 900
Replacement Uom C.F.
InspectedInstance on Facades D, E, F, G, H
Instance Condition 2 - Between Good and Fair
Instance Quantity 900
Instance Quantity Uom C.F.
Deficiency No deficiencies recorded
PLAZA DECK Does not Exist
ROOF Inspected
Roofing Inspected
Replacement Quantity 18,500
Replacement Uom S.F.
ROOF HATCH/SMOKE HATCH Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS Inspected
Condition 3 - Fair
Deficiency DAMAGED/MISSING
Roof Plan reference
Deficiency Quantity 50
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K110
PB/A&W Print Date: 9/14/2020Page 10 of 44
Question Response
EXTERIOR
ROOF
Roofing
LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS Inspected
Deficiency Photo1
Facade A
Violations No violations recorded.
ROOF BARRIER Inspected
Condition 3 - Fair
Deficiency RAILINGS/PANELS: DETERIORATED, MINOR RUSTING
Roof Plan reference
Deficiency Quantity 150
Quantity Uom S.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 2
Violations No violations recorded.
ROOF CAGE Does not Exist
ROOF FENCE Does not Exist
ROOFING Inspected
InspectedInstance on Metal: Roof 6
Instance Condition 1 - Good
Instance Quantity 1,200
Instance Quantity Uom S.F.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K110
PB/A&W Print Date: 9/14/2020Page 11 of 44
Question Response
EXTERIOR
ROOF
Roofing
ROOFING
Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?
No
Installation Year 2014
Source of Installation Custodial Staff
Deficiency No deficiencies recorded
InspectedInstance on Metal: Roofs 1, 3A and 5
Instance Condition 2 - Between Good and Fair
Instance Quantity 10,800
Instance Quantity Uom S.F.
Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?
No
Installation Year 1985
Source of Installation Custodial Staff
Deficiency No deficiencies recorded
InspectedInstance on Modified Bitumen: Roofs 2, 3, 4, 11, 12
Instance Condition 2 - Between Good and Fair
Instance Quantity 5,600
Instance Quantity Uom S.F.
Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?
No
Installation Year 2014
Source of Installation Custodial Staff
Deficiency No deficiencies recorded
InspectedInstance on Built-Up: Roofs 7, 8, 9
Instance Condition 2 - Between Good and Fair
Instance Quantity 900
Instance Quantity Uom S.F.
Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?
No
Installation Year 2014
Source of Installation Custodial Staff
Deficiency No deficiencies recorded
ROOFING DRAINS Does not Exist
Specialties Inspected
BULKHEAD/PENTHOUSE Does not Exist
CUPOLA/ SPIRES/ TOWERS Does not Exist
DORMER Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
DUNNAGE STEEL Does not Exist
SKYLIGHT/ROOF VENT Does not Exist
ROOF/GRAVITY TANK Does not Exist
STAIRS/RAMPS: EXTERIOR Inspected
BUILDING CHEEK/FLANK WALLS Inspected
Condition 2 - Between Good and Fair
Deficiency CAST IN PLACE CONCRETE: CRACKS/SPALLING - MINOR
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K110
PB/A&W Print Date: 9/14/2020Page 12 of 44
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
BUILDING CHEEK/FLANK WALLS
Roof Plan reference
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade A
Violations No violations recorded.
RAILINGS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
STAIRS/RAMPS Inspected
Condition 3 - Fair
Deficiency CONCRETE: WORN-OUT TREAD/RISER/NOSING
Roof Plan reference
Deficiency Quantity 15
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K110
PB/A&W Print Date: 9/14/2020Page 13 of 44
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
STAIRS/RAMPS
Deficiency Photo1
Main Entry - Facade A
Violations No violations recorded.
WINDOWS Inspected
Replacement Quantity 9,100
Replacement Uom S.F.
EXTERIOR GUARDS Inspected
Condition 3 - Fair
Deficiency RUST - MINOR
Roof Plan reference
Elevation
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K110
PB/A&W Print Date: 9/14/2020Page 14 of 44
Question Response
EXTERIOR
WINDOWS
EXTERIOR GUARDS
Deficiency Photo1
Facade F / G
Violations No violations recorded.
LINTELS Inspected
Condition 2 - Between Good and Fair
Deficiency STEEL: MINOR RUSTING
Roof Plan reference
Elevation
Deficiency Quantity 20
Quantity Uom L.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade F - Exit 4
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K110
PB/A&W Print Date: 9/14/2020Page 15 of 44
Question Response
EXTERIOR
WINDOWS
LINTELS Inspected
Violations No violations recorded.
WINDOWS Inspected
Material Type(s) Aluminum
InspectedInstance on Aluminum - Double Hung: All Facades
Instance Condition 1 - Good
Instance Quantity 9,100
Instance Quantity Uom S.F.
Installation Year 2014
Source of Installation Custodial Staff
Deficiency No deficiencies recorded
INTERIOR Inspected
POOLS Does not Exist
STRUCTURAL Inspected
COLUMNS/BEAMS/BEARING WALLS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
FLOOR STRUCTURE Inspected
Condition 4 - Between Fair and Poor
Deficiency CONCRETE SLAB ON GRADE: THRU CRACKS
Deficiency Location/Instance Basement- Tool Room, Gas Meter Room
Deficiency Quantity 350
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 5
Deficiency Photo1
Tool Room
Violations No violations recorded.
Deficiency CONCRETE SLAB ON GRADE: MINOR CRACKS
Deficiency Location/Instance Basement - Multipurpose Rooms, Oil Tank Room, Tool Room
Deficiency Quantity 1,000
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K110
PB/A&W Print Date: 9/14/2020Page 16 of 44
Question Response
INTERIOR
STRUCTURAL
FLOOR STRUCTURE
Deficiency Photo1
Multipurpose Room
Violations No violations recorded.
FOUNDATION WALLS Inspected
Material Type(s) Masonry
Condition 3 - Fair
Deficiency BRICK: OPEN JOINTS
Deficiency Location/Instance Basement - Gas Meter Room, Electrical Panel Room
Deficiency Quantity 200
Quantity Uom S.F.
Potential Action REPOINT
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
Deficiency Photo1
Gas Meter Room
Violations No violations recorded.
ROOF STRUCTURE Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
VAULTS-BUNKERS Does not Exist
AUDITORIUM Inspected
InspectedInstance on 4th Floor (300 Seats)
Ceiling
InspectedInstance on 4th Floor (300 Seats)
Condition 2 - Between Good and Fair
Deficiency METAL PAN: DAMAGED/MISSING
Deficiency Location/Instance Rear of Room, Center
Deficiency Quantity 100
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K110
PB/A&W Print Date: 9/14/2020Page 17 of 44
Question Response
INTERIOR
AUDITORIUM
Ceiling
Purpose of Action LEVEL 4
Deficiency Photo1
Rear
Violations 35311988P
Door(s)
InspectedInstance on 4th Floor (300 Seats)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Fixed H/C Lift
Does not ExistInstance on 4th Floor (300 Seats)
Fixed Seating
InspectedInstance on 4th Floor (300 Seats)
Condition 2 - Between Good and Fair
Deficiency DAMAGED/BROKEN/INOPERABLE
Deficiency Location/Instance Seats I/2, J/2
Deficiency Quantity 2
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 6
Deficiency Photo1
Seats I/2, J/2
Violations No violations recorded.
Deficiency DAMAGED/BROKEN/INOPERABLE
Deficiency Location/Instance Seat I/5
Deficiency Quantity 1
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K110
PB/A&W Print Date: 9/14/2020Page 18 of 44
Question Response
INTERIOR
AUDITORIUM
Fixed Seating
Deficiency Photo1
Seat I/5
Violations No violations recorded.
Floor Finish
InspectedInstance on 4th Floor (300 Seats)
Condition 4 - Between Fair and Poor
Deficiency VINYL TILES: TRIPPING HAZARD - ELECTRICAL OUTLET
Deficiency Location/Instance Center
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 6
Deficiency Photo1
Center
Violations No violations recorded.
Deficiency VINYL TILES: DETERIORATED SUBSTRATE
Deficiency Location/Instance Near Stage, Center, Rear of Room, East side, West side, North side,South side
Deficiency Quantity 300
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K110
PB/A&W Print Date: 9/14/2020Page 19 of 44
Question Response
INTERIOR
AUDITORIUM
Floor Finish
Deficiency Photo1
Near Stage
Violations No violations recorded.
Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES
Deficiency Location/Instance North side, South side Near Entrance
Deficiency Quantity 100
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
North side
Violations No violations recorded.
Sliding-folding Partition
Does not ExistInstance on 4th Floor (300 Seats)
Stage
InspectedInstance on 4th Floor (300 Seats)
Stage Inspected
InspectedInstance on 4th Floor (300 Seats)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stage Curtain Rigging Does not Exist
Does not ExistInstance on 4th Floor (300 Seats)
Stage Curtains Does not Exist
Does not ExistInstance on 4th Floor (300 Seats)
Walls
InspectedInstance on 4th Floor (300 Seats)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Window Curtains/Shades/Blinds
InspectedInstance on 4th Floor (300 Seats)
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K110
PB/A&W Print Date: 9/14/2020Page 20 of 44
Question Response
INTERIOR
AUDITORIUM
Window Curtains/Shades/Blinds
Condition 3 - Fair
Deficiency WORN/DAMAGED CURTAINS
Deficiency Location/Instance Rear of stage, Rear of Room
Deficiency Quantity 80
Quantity Uom S.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Rear of stage
Rear of Room
Violations No violations recorded.
CAFETERIA Inspected
InspectedInstance on 1st Floor (2,000SF)
Ceiling
InspectedInstance on 1st Floor (2,000SF)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
InspectedInstance on 1st Floor (2,000SF)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Fixed Equipment
Does not ExistInstance on 1st Floor (2,000SF)
Floor Finish
InspectedInstance on 1st Floor (2,000SF)
Condition 4 - Between Fair and Poor
Deficiency VINYL TILES: DETERIORATED SUBSTRATE
Deficiency Location/Instance Near windows, Near Kitchen
Deficiency Quantity 150
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K110
PB/A&W Print Date: 9/14/2020Page 21 of 44
Question Response
INTERIOR
CAFETERIA
Floor Finish
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near windows
Violations No violations recorded.
Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES
Deficiency Location/Instance Center , Near Entrance
Deficiency Quantity 15
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Center
Violations No violations recorded.
Sliding-folding Partition
Does not ExistInstance on 1st Floor (2,000SF)
Stage
Does not ExistInstance on 1st Floor (2,000SF)
Walls
InspectedInstance on 1st Floor (2,000SF)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Window Curtains/Shades/Blinds
Does not ExistInstance on 1st Floor (2,000SF)
CLASSROOMS/CORRIDORS/ADMIN SPACES Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency GYPSUM BOARD: DAMAGED/DETERIORATED
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K110
PB/A&W Print Date: 9/14/2020Page 22 of 44
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Ceiling
Deficiency Location/Instance 2nd Floor Near Elevator, 3rd Floor Near Elevator, 4th Floor NearElevator
Deficiency Quantity 60
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
4th Floor Near Elevator
Violations No violations recorded.
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Room 403
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 403
Violations No violations recorded.
Deficiency METAL PAN: DAMAGED/MISSING
Deficiency Location/Instance Room 306
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K110
PB/A&W Print Date: 9/14/2020Page 23 of 44
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Ceiling
Deficiency Photo1
Room 306
Violations No violations recorded.
Door(s) Inspected
Condition 5 - Poor
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance Rooms 200 (Original Building), 306, 312, 403, 406, and others
Deficiency Quantity 20
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 406
Violations No violations recorded.
Floor Finish Inspected
Condition 5 - Poor
Deficiency CONCRETE: CRACKS
Deficiency Location/Instance North Basement Room, South Basement Room
Deficiency Quantity 800
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K110
PB/A&W Print Date: 9/14/2020Page 24 of 44
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Floor Finish
Deficiency Photo1
Basement Room
Violations No violations recorded.
Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES
Deficiency Location/Instance Rooms 104, 206, 312, 403, 406, and others
Deficiency Quantity 7,000
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 403
Violations No violations recorded.
Deficiency VINYL TILES: DETERIORATED SUBSTRATE
Deficiency Location/Instance Corridor near Rooms 101, 102, 106, 403, Corridor near Cafeteria, andothers
Deficiency Quantity 2,500
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Corridor near Room 403
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K110
PB/A&W Print Date: 9/14/2020Page 25 of 44
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Floor Finish Inspected
Violations No violations recorded.
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency GYPSUM BOARD: DETERIORATED
Deficiency Location/Instance 2nd Floor Near Elevator, 3rd Floor Near Elevator, 4th Floor NearElevator
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
4th Floor Near Elevator
Violations No violations recorded.
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Rooms 103, 104, 306, Corridor near Room 103
Deficiency Quantity 60
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 306
Violations No violations recorded.
Specialties Does not Exist
GYMNASIUM Inspected
InspectedInstance on 3rd Floor
Ceiling
InspectedInstance on 3rd Floor
Condition 2 - Between Good and Fair
Deficiency PLASTER: CRACKS/SPALLING
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K110
PB/A&W Print Date: 9/14/2020Page 26 of 44
Question Response
INTERIOR
GYMNASIUM
Ceiling
Deficiency Location/Instance Near windows
Deficiency Quantity 25
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 4
Deficiency Photo1
Near windows
Violations 35311988P
Door(s)
InspectedInstance on 3rd Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Fixed Equipment
InspectedInstance on 3rd Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish
InspectedInstance on 3rd Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Seating
Does not ExistInstance on 3rd Floor
Sliding-folding Partition
Does not ExistInstance on 3rd Floor
Stage
Does not ExistInstance on 3rd Floor
Walls
InspectedInstance on 3rd Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Window Curtains/Shades/Blinds
Does not ExistInstance on 3rd Floor
INTERIOR DOOR HARDWARE Inspected
Condition 3 - Fair
Deficiency No deficiencies recorded
INTERIOR GUARDS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K110
PB/A&W Print Date: 9/14/2020Page 27 of 44
Question Response
INTERIOR
KITCHEN Inspected
InspectedInstance on 1st Floor
Ceiling
Not RequiredInstance on 1st Floor
Door(s)
Does not ExistInstance on 1st Floor
Floor Finish
Not RequiredInstance on 1st Floor
Walls
Not RequiredInstance on 1st Floor
LIBRARY Inspected
InspectedInstance on Room 207/208
Built-in Furnishing
InspectedInstance on Room 207/208
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Ceiling
InspectedInstance on Room 207/208
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
InspectedInstance on Room 207/208
Condition 3 - Fair
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance Entrance
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Entrance
Violations No violations recorded.
Floor Finish
InspectedInstance on Room 207/208
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Walls
InspectedInstance on Room 207/208
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K110
PB/A&W Print Date: 9/14/2020Page 28 of 44
Question Response
INTERIOR
LOCKER ROOM Does not Exist
MULTI-PURPOSE ROOM Inspected
InspectedInstance on Basement - North (2,000SF)
InspectedInstance on Basement - South (1,000)
Ceiling
InspectedInstance on Basement - North (2,000SF)
Condition 2 - Between Good and Fair
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance West side
Deficiency Quantity 25
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
West side
Violations No violations recorded.
Door(s)
InspectedInstance on Basement - North (2,000SF)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
InspectedInstance on Basement - South (1,000)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Fixed Equipment
Does not ExistInstance on Basement - North (2,000SF)
Does not ExistInstance on Basement - South (1,000)
Floor Finish
InspectedInstance on Basement - North (2,000SF)
Condition 5 - Poor
Deficiency CONCRETE: CRACKS
Deficiency Location/Instance Center
Deficiency Quantity 25
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K110
PB/A&W Print Date: 9/14/2020Page 29 of 44
Question Response
INTERIOR
MULTI-PURPOSE ROOM
Floor Finish
Deficiency Photo1
Center
Violations No violations recorded.
Deficiency ROLLED ASPHALT: CRACKS
Deficiency Location/Instance West side, East side
Deficiency Quantity 1,500
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
West side
Violations No violations recorded.
Sliding-folding Partition
Does not ExistInstance on Basement - North (2,000SF)
Does not ExistInstance on Basement - South (1,000)
Stage
Does not ExistInstance on Basement - North (2,000SF)
Does not ExistInstance on Basement - South (1,000)
Walls
InspectedInstance on Basement - South (1,000)
Condition 2 - Between Good and Fair
Deficiency BRICK: CRACKS/SPALLING
Deficiency Location/Instance West wall
Deficiency Quantity 100
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K110
PB/A&W Print Date: 9/14/2020Page 30 of 44
Question Response
INTERIOR
MULTI-PURPOSE ROOM
Walls
Deficiency Photo1
Near windows
Violations No violations recorded.
InspectedInstance on Basement - North (2,000SF)
Condition 2 - Between Good and Fair
Deficiency BRICK: CRACKS/SPALLING
Deficiency Location/Instance Near windows
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near windows
Violations No violations recorded.
Window Curtains/Shades/Blinds
Does not ExistInstance on Basement - North (2,000SF)
Does not ExistInstance on Basement - South (1,000)
SCIENCE DEMO ROOM Does not Exist
SCIENCE LAB Does not Exist
SCIENCE PREP ROOM Does not Exist
SHOWER ROOM Does not Exist
STAIRS/RAMPS: INTERIOR Inspected
Do Letter Stair Signs Exist? Partially
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s) Inspected
Condition 4 - Between Fair and Poor
Deficiency METAL CLAD WOOD: DETERIORATED DOOR
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K110
PB/A&W Print Date: 9/14/2020Page 31 of 44
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Door(s)
Deficiency Location/Instance Stairs AB/4, CD/Basement, EF/Basement
Deficiency Quantity 3
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stair AB/4
Violations No violations recorded.
Partition Inspected
Condition 2 - Between Good and Fair
Deficiency GLASS PANEL: DAMAGED/DETERIORATED
Deficiency Location/Instance Stairs AB/1, EF/Basement, GH/Basement, 4
Deficiency Quantity 40
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stair GH/Basement
Violations No violations recorded.
Railings Inspected
Condition 4 - Between Fair and Poor
Deficiency METAL: MISSING
Deficiency Location/Instance Exits 4, 6, 7 Vestibules
Deficiency Quantity 18
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 6
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K110
PB/A&W Print Date: 9/14/2020Page 32 of 44
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Railings
Deficiency Photo1
Exit 7 Vestibule
Violations No violations recorded.
Stairs and Landings Inspected
Condition 5 - Poor
Deficiency STONE: BROKEN/MISSING
Deficiency Location/Instance Stairs CD/2, 3, EF/Basement, 2, 4, and others
Deficiency Quantity 100
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stair EF/Basement
Violations No violations recorded.
Deficiency CONCRETE: CRACKS/SPALLING - MAJOR
Deficiency Location/Instance Stairs CD/Basement, EF/Basement, Multi-Purpose Room - South
Deficiency Quantity 80
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K110
PB/A&W Print Date: 9/14/2020Page 33 of 44
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Stairs and Landings
Multi-Purpose Room - South
Stair CD/Basement
Violations No violations recorded.
Deficiency ROLLED ASPHALT: CRACKS
Deficiency Location/Instance Stairs CD/1, 3, 4, EF/1, 4, and others
Deficiency Quantity 3,000
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stair CD/1
Violations No violations recorded.
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Stairs CD/Basement, EF/1
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K110
PB/A&W Print Date: 9/14/2020Page 34 of 44
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Walls
Deficiency Photo1
Stair EF/1
Violations No violations recorded.
Deficiency CERAMIC TILE: BROKEN/ MISSING
Deficiency Location/Instance Stairs CD/Basement, 2, 3, 4, EF/1, and others
Deficiency Quantity 80
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stair CD/Basement
Violations No violations recorded.
TOILET ROOMS - STAFF Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s) Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish Inspected
Condition 3 - Fair
Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES
Deficiency Location/Instance Inside Room 108
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K110
PB/A&W Print Date: 9/14/2020Page 35 of 44
Question Response
INTERIOR
TOILET ROOMS - STAFF
Floor Finish
Deficiency Photo1
Inside Room 108
Violations No violations recorded.
Stalls Inspected
Condition 5 - Poor
Deficiency RUST - MAJOR
Deficiency Location/Instance Inside Room 108
Deficiency Quantity 1
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Inside Room 108
Violations No violations recorded.
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
TOILET ROOMS - STUDENTS Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s) Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stalls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K110
PB/A&W Print Date: 9/14/2020Page 36 of 44
Question Response
INTERIOR
TOILET ROOMS - STUDENTS
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Inside Room 103
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Inside Room 103
Violations No violations recorded.
LIFE SAFETY Inspected
F.D. HOLDING AREA Does not Exist
STEEL STAIRS Does not Exist
SITE Inspected
CONTAINERIZATION Does not Exist
Drainage System for Asphalt Inspected
Catch Basins/Manhole - Surrounded by asphalt Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Culverts - Asphalt Covering Does not Exist
Drainage System for Concrete Inspected
Catch Basins/Manhole - Surrounded by concrete Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Culverts - Concrete Covering Does not Exist
Drainage System for Soil Does not Exist
DRINKING FOUNTAINS Does not Exist
FENCES Inspected
Condition 3 - Fair
Deficiency CHAIN LINK: DAMAGED/DETERIORATED
Deficiency Location/Instance Monitor Street near gate to Schoolyard
Deficiency Quantity 100
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K110
PB/A&W Print Date: 9/14/2020Page 37 of 44
Question Response
SITE
FENCES
Violations No violations recorded.
Deficiency WROUGHT IRON: RUST - MAJOR
Deficiency Location/Instance Monitor Street
Deficiency Quantity 40
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Monitor Street
Violations No violations recorded.
Deficiency WROUGHT IRON: DAMAGED/DETERIORATED
Deficiency Location/Instance Driggs Avenue, Monitor Street
Deficiency Quantity 80
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Monitor Street
Violations No violations recorded.
Deficiency CONCRETE CURB: DAMAGED/DETERIORATED
Deficiency Location/Instance Driggs Avenue, Monitor Street
Deficiency Quantity 175
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K110
PB/A&W Print Date: 9/14/2020Page 38 of 44
Question Response
SITE
FENCES
Deficiency Photo1
Monitor Street
Violations No violations recorded.
IRRIGATION SYSTEM Does not Exist
PAVING Inspected
Student Non-Use Inspected
Gravel Exists? No
Asphalt Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Concrete Inspected
Condition 3 - Fair
Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS
Deficiency Location/Instance Driggs Avenue, Monitor Street
Deficiency Quantity 300
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Monitor Street
Violations No violations recorded.
Pavers Does not Exist
Student Use Inspected
Gravel Exists? No
Asphalt Inspected
Condition 4 - Between Fair and Poor
Deficiency POTHOLES
Deficiency Location/Instance South Schoolyard
Deficiency Quantity 15
Quantity Uom S.F.
Potential Action REPAIR
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K110
PB/A&W Print Date: 9/14/2020Page 39 of 44
Question Response
SITE
PAVING
Student Use
Asphalt
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
South Schoolyard
Violations No violations recorded.
Deficiency CRACKS - MINOR
Deficiency Location/Instance South Schoolyard
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
Deficiency CRACKS - MAJOR
Deficiency Location/Instance South Schoolyard
Deficiency Quantity 600
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
South Schoolyard
Violations No violations recorded.
Concrete Inspected
Condition 3 - Fair
Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS
Deficiency Location/Instance North Schoolyard
Deficiency Quantity 75
Quantity Uom S.F.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K110
PB/A&W Print Date: 9/14/2020Page 40 of 44
Question Response
SITE
PAVING
Student Use
Concrete
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
North Schoolyard
Violations No violations recorded.
Pavers Does not Exist
Site Sidewalks & Walkways Inspected
Asphalt Does not Exist
Concrete Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Pavers Does not Exist
DOT Sidewalk Inspected
Asphalt Does not Exist
Concrete Inspected
Condition 4 - Between Fair and Poor
Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS
Deficiency Location/Instance Driggs Avenue, Monitor Street
Deficiency Quantity 1,000
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Monitor Street
Violations No violations recorded.
Deficiency DAMAGED CURBS
Deficiency Location/Instance Driggs Avenue, Monitor Street
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K110
PB/A&W Print Date: 9/14/2020Page 41 of 44
Question Response
SITE
PAVING
DOT Sidewalk
Concrete
Deficiency Quantity 50
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Monitor Street
Violations No violations recorded.
Pavers Does not Exist
PLAYGROUNDS Inspected
InspectedInstance on Schoolyard - South
Benches
Does not ExistInstance on Schoolyard - South
Fence
Does not ExistInstance on Schoolyard - South
Pavement
Does not ExistInstance on Schoolyard - South
Play Equipment
InspectedInstance on Schoolyard - South
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Safety Surfacing
InspectedInstance on Schoolyard - South
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Unpaved Area
Does not ExistInstance on Schoolyard - South
PLAYING SURFACE Does not Exist
RETAINING WALLS Does not Exist
SEATING Inspected
Benches Inspected
Concrete Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Metal/Wood/Plastic Inspected
Condition 3 - Fair
Deficiency DAMAGED/DETERIORATED
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K110
PB/A&W Print Date: 9/14/2020Page 42 of 44
Question Response
SITE
SEATING
Benches
Metal/Wood/Plastic
Deficiency Location/Instance South Schoolyard
Deficiency Quantity 1
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
South Schoolyard
Violations No violations recorded.
Bleachers Does not Exist
SITE WALLS (NOT RETAINING WALLS) Inspected
Condition 4 - Between Fair and Poor
Deficiency BRICK: DETERIORATED COPING STONE
Deficiency Location/Instance South Schoolyard
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
South Schoolyard
Violations No violations recorded.
Deficiency BRICK: CRACKS/SPALLING - MAJOR
Deficiency Location/Instance South Schoolyard
Deficiency Quantity 225
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K110
PB/A&W Print Date: 9/14/2020Page 43 of 44
Question Response
SITE
SITE WALLS (NOT RETAINING WALLS)
Deficiency Photo1
South Schoolyard
Violations No violations recorded.
STAIRS/RAMPS: EXTERIOR Does not Exist
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K110
PB/A&W Print Date: 9/14/2020Page 44 of 44