Asset: P.S. 110 - BROOKLYN, 124 MONITOR STREET, New York, 11222 Inspection Id Inspection Type Time In Last Edited SA : K110 Architectural - Senior 2019-10-31 7:01 AM 2020-09-01 5:00 PM AA : K110 Architectural - Associate 2019-10-31 7:38 AM 2020-01-28 5:03 PM Asset Data Question Answer Was the building fully accessible for inspection Yes Principal(s) Information Principal Name Dana Raciunas (Acting Principal) Organization P.S. 110 – Brooklyn Did you meet with this Principal? Yes Did this Principal provide feedback? Yes Summary of Principal's Feedback The Principal's comments are as follows: 1. The floors in the corridors and classrooms are deteriorated and require an upgrade. 2. The toilets rooms are antiquated and require an upgrade. Custodian James Carbonaro Fireman Alex Enriquez Building Square Footage 67,000 Comments on the Area None Comments on the Stories (Floors) plus Basements 4+B+Attic Comments on the Number of Classrooms 38 Comments on the Year Built 1895 Student Population 594 Staff Population 73 Weather Fair Facade Photo Corner of Monitor Street at Driggs Avenue - Northeast View NYC Department of Education Architectural Inspection Building Condition Assessment Survey 2019 - 2020 K110 PB/A&W Print Date: 9/14/2020 Page 1 of 44

Upload: others

Post on 22-Aug-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: NYC Department of EducationFireman Alex Enriquez Building Square Footage 67000 Comments on the Area None Comments on the Stories (Floors) plus Basements 4 + B + Attic Comments on the

Asset: P.S. 110 - BROOKLYN, 124 MONITOR STREET, New York, 11222

Inspection Id Inspection Type Time In Last Edited

SA : K110 Architectural - Senior 2019-10-31 7:01 AM 2020-09-01 5:00 PM

AA : K110 Architectural - Associate 2019-10-31 7:38 AM 2020-01-28 5:03 PM

Asset Data

Question Answer

Was the building fully accessible for inspection Yes

Principal(s) Information

Principal Name Dana Raciunas (Acting Principal)

Organization P.S. 110 – Brooklyn

Did you meet with this Principal? Yes

Did this Principal provide feedback? Yes

Summary of Principal's Feedback The Principal's comments are as follows: 1. The floors in the corridorsand classrooms are deteriorated and require an upgrade. 2. The toiletsrooms are antiquated and require an upgrade.

Custodian James Carbonaro

Fireman Alex Enriquez

Building Square Footage 67,000

Comments on the Area None

Comments on the Stories (Floors) plus Basements 4+B+Attic

Comments on the Number of Classrooms 38

Comments on the Year Built 1895

Student Population 594

Staff Population 73

Weather Fair

Facade Photo

Corner of Monitor Street at Driggs Avenue -Northeast View

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K110

PB/A&W Print Date: 9/14/2020Page 1 of 44

Page 2: NYC Department of EducationFireman Alex Enriquez Building Square Footage 67000 Comments on the Area None Comments on the Stories (Floors) plus Basements 4 + B + Attic Comments on the

Main Entrance Photo

Facade A - Monitor Street

Roof Photo

Roof 3 - Northeast View

Have any Systems/Major Building Components been upgraded? Yes

Systems: New Windows, repairs to Metal Roofing; New Built UpRoofing and Modified Bitumen Roofing; New Flashing;New Roof Hatches; Interior upgrades

Year: 2014

Systems: New Elevator

Year: 2010

Systems: Limited Window repairs; Foundation Waterproofing;Exterior Masonry repairs; Limited Roof repairs; LimitedDoor replacement; Boys and Girls Toilet Room upgradeson 2nd and 3rd Floors.

Year: 2002

Have there been any New Building Additions? Yes

Comments on New Building Additions 2010 (+4500 SF)

Tandem Schools? No

Leased Space? No

Priority Condition

PriorityCondition ExistLast Year?

PriorityCategory

ConditionDescription

ComponentAffected

LocationDescription

Person(s)Notified

Person(s) Title PhotoImage

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K110

PB/A&W Print Date: 9/14/2020Page 2 of 44

Page 3: NYC Department of EducationFireman Alex Enriquez Building Square Footage 67000 Comments on the Area None Comments on the Stories (Floors) plus Basements 4 + B + Attic Comments on the

No condition recorded

Structural Engineer Required

StructuralCondition Type

ConditionDescription

ComponentAffected

LocationDescription

Person(s)Notified

Person(s) Title PhotoImage

No condition recorded

Accessibility

Accessibility Status Question Response

Is the primary or secondary entrance on an accessible route? Yes

Is the building a multi-story building? Yes

Are all floors of the building accessible through compliant means? Yes

Accessible classrooms exists on each floor? Yes

Boys and Girls or Unisex accessible toilets exist on at least every other floor? No

Is there at least one Boys and Girls or Unisex toilet accessible in the building? Yes

If the following spaces exist, are SOME accessible? Art Room, Auditorium,Cafeteria, Computer, Gymnasiums, Library, Multipurpose Room, Science Labs

Yes

Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem

FireAlarmStrobe

FUNCTIONAL ACCESSIBILITY

Exterior Routes

Exterior Entrances & Exits Yes

Exterior H/C Lifts No No

Exterior Ramps and Railings Yes Yes

Interior Routes

Corridor and Lobby H/C Lifts No No

Interior Corridor Doors and Hardware No No

Interior Corridors and Lobbies Yes

Interior Elevators Yes Yes

Interior Lobby Doors and Hardware Yes

Interior Ramps No

Rooms & Spaces

Art Rooms Room 303 Yes Yes

Auditorium 4th Floor Yes Yes Yes Yes

Cafeteria 1st Floor Yes Yes No Yes

Classrooms 1st - 4th Floors Yes Yes

Computer Rooms Room 209 Yes Yes

Gymnasium 3rd Floor Yes Yes Yes Yes

Library Room 207/208 Yes Yes

Main Office Room 106A Yes Yes

Multi-purpose Room Basement - North Yes Yes No No

Basement - South Yes No Not on Accessible Route No No

Nurse's Room Room 109 Yes Yes

Pool No

Science Lab No

Toilet Rooms (Boys) 1st and 3rd Floor Yes Yes

Toilet Rooms (Girls) 1st and 2nd Floor Yes Yes

Toilet Rooms (Staff) 1st - 4th Floors Yes Yes

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K110

PB/A&W Print Date: 9/14/2020Page 3 of 44

Page 4: NYC Department of EducationFireman Alex Enriquez Building Square Footage 67000 Comments on the Area None Comments on the Stories (Floors) plus Basements 4 + B + Attic Comments on the

Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem

FireAlarmStrobe

Building Template

Inspection

Question Response

Architectural

EXTERIOR Inspected

AREAWAY Inspected

InspectedInstance on AW1-AW2

Instance Condition 3 - Fair

Instance Quantity 2

Instance Quantity Uom EACH

Deficiency AREAWAY GRATINGS: MINOR RUSTING

Roof Plan reference

Deficiency Quantity 100

Quantity Uom S.F.

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K110

PB/A&W Print Date: 9/14/2020Page 4 of 44

Page 5: NYC Department of EducationFireman Alex Enriquez Building Square Footage 67000 Comments on the Area None Comments on the Stories (Floors) plus Basements 4 + B + Attic Comments on the

Question Response

EXTERIOR

AREAWAY

Deficiency Photo1

AW2

Violations No violations recorded.

Deficiency AREAWAY DRAINS: CLOGGED

Roof Plan reference

Deficiency Quantity 1

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 2

Deficiency Photo1

AW

Violations No violations recorded.

AWNINGS AND CANOPIES Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

CHIMNEY Inspected

Material Type(s) Masonry

Condition 3 - Fair

Deficiency BRICK: DETERIORATED CAP

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K110

PB/A&W Print Date: 9/14/2020Page 5 of 44

Page 6: NYC Department of EducationFireman Alex Enriquez Building Square Footage 67000 Comments on the Area None Comments on the Stories (Floors) plus Basements 4 + B + Attic Comments on the

Question Response

EXTERIOR

CHIMNEY

Roof Plan reference

Deficiency Quantity 15

Quantity Uom L.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Chimney

Violations No violations recorded.

COPING Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

CORNICE Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

DOORS Inspected

DOORS AND FRAMES Inspected

Condition 3 - Fair

Deficiency METAL: DETERIORATED DOOR AND FRAME - MINORDETERIORATION

Roof Plan reference

Deficiency Quantity 2

Quantity Uom EACH

Potential Action MAINTENANCE

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K110

PB/A&W Print Date: 9/14/2020Page 6 of 44

Page 7: NYC Department of EducationFireman Alex Enriquez Building Square Footage 67000 Comments on the Area None Comments on the Stories (Floors) plus Basements 4 + B + Attic Comments on the

Question Response

EXTERIOR

DOORS

DOORS AND FRAMES

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Facade H

Violations No violations recorded.

DOOR HARDWARE Inspected

Condition 3 - Fair

Deficiency No deficiencies recorded

LINTELS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

TRANSOM/SIDE LIGHT Does not Exist

EXTERIOR WALLS Inspected

Material Type(s) Masonry, Concrete

Replacement Quantity 24,500

Replacement Uom S.F.

InspectedInstance on All Facades

Instance Condition 3 - Fair

Instance Quantity 24,500

Instance Quantity Uom S.F.

Deficiency BRICK: CRACKS/DISPLACED/SPALLED BRICK AT BUILDINGCORNERS

Roof Plan reference

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K110

PB/A&W Print Date: 9/14/2020Page 7 of 44

Page 8: NYC Department of EducationFireman Alex Enriquez Building Square Footage 67000 Comments on the Area None Comments on the Stories (Floors) plus Basements 4 + B + Attic Comments on the

Question Response

EXTERIOR

EXTERIOR WALLS

Elevation

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REMOVE AND REBUILD

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Facade H

Violations No violations recorded.

Deficiency BRICK: MINOR CRACKS AND SPALLING

Roof Plan reference

Elevation

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action RESTITCH

Urgency of Action PRIORITY 3

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K110

PB/A&W Print Date: 9/14/2020Page 8 of 44

Page 9: NYC Department of EducationFireman Alex Enriquez Building Square Footage 67000 Comments on the Area None Comments on the Stories (Floors) plus Basements 4 + B + Attic Comments on the

Question Response

EXTERIOR

EXTERIOR WALLS

Purpose of Action LEVEL 2

Deficiency Photo1

Facade H

Violations No violations recorded.

Deficiency CAST IN PLACE / PRE-CAST CONCRETE: MAJORCRACKS/SPALLING

Roof Plan reference

Elevation

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Facade H

Violations No violations recorded.

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K110

PB/A&W Print Date: 9/14/2020Page 9 of 44

Page 10: NYC Department of EducationFireman Alex Enriquez Building Square Footage 67000 Comments on the Area None Comments on the Stories (Floors) plus Basements 4 + B + Attic Comments on the

Question Response

EXTERIOR

EXTERIOR SOFFITS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

LOADING DOCK Does not Exist

LOUVER Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

PARAPETS Inspected

Material Type(s) Masonry

Replacement Quantity 900

Replacement Uom C.F.

InspectedInstance on Facades D, E, F, G, H

Instance Condition 2 - Between Good and Fair

Instance Quantity 900

Instance Quantity Uom C.F.

Deficiency No deficiencies recorded

PLAZA DECK Does not Exist

ROOF Inspected

Roofing Inspected

Replacement Quantity 18,500

Replacement Uom S.F.

ROOF HATCH/SMOKE HATCH Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS Inspected

Condition 3 - Fair

Deficiency DAMAGED/MISSING

Roof Plan reference

Deficiency Quantity 50

Quantity Uom L.F.

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K110

PB/A&W Print Date: 9/14/2020Page 10 of 44

Page 11: NYC Department of EducationFireman Alex Enriquez Building Square Footage 67000 Comments on the Area None Comments on the Stories (Floors) plus Basements 4 + B + Attic Comments on the

Question Response

EXTERIOR

ROOF

Roofing

LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS Inspected

Deficiency Photo1

Facade A

Violations No violations recorded.

ROOF BARRIER Inspected

Condition 3 - Fair

Deficiency RAILINGS/PANELS: DETERIORATED, MINOR RUSTING

Roof Plan reference

Deficiency Quantity 150

Quantity Uom S.F.

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Roof 2

Violations No violations recorded.

ROOF CAGE Does not Exist

ROOF FENCE Does not Exist

ROOFING Inspected

InspectedInstance on Metal: Roof 6

Instance Condition 1 - Good

Instance Quantity 1,200

Instance Quantity Uom S.F.

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K110

PB/A&W Print Date: 9/14/2020Page 11 of 44

Page 12: NYC Department of EducationFireman Alex Enriquez Building Square Footage 67000 Comments on the Area None Comments on the Stories (Floors) plus Basements 4 + B + Attic Comments on the

Question Response

EXTERIOR

ROOF

Roofing

ROOFING

Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?

No

Installation Year 2014

Source of Installation Custodial Staff

Deficiency No deficiencies recorded

InspectedInstance on Metal: Roofs 1, 3A and 5

Instance Condition 2 - Between Good and Fair

Instance Quantity 10,800

Instance Quantity Uom S.F.

Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?

No

Installation Year 1985

Source of Installation Custodial Staff

Deficiency No deficiencies recorded

InspectedInstance on Modified Bitumen: Roofs 2, 3, 4, 11, 12

Instance Condition 2 - Between Good and Fair

Instance Quantity 5,600

Instance Quantity Uom S.F.

Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?

No

Installation Year 2014

Source of Installation Custodial Staff

Deficiency No deficiencies recorded

InspectedInstance on Built-Up: Roofs 7, 8, 9

Instance Condition 2 - Between Good and Fair

Instance Quantity 900

Instance Quantity Uom S.F.

Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?

No

Installation Year 2014

Source of Installation Custodial Staff

Deficiency No deficiencies recorded

ROOFING DRAINS Does not Exist

Specialties Inspected

BULKHEAD/PENTHOUSE Does not Exist

CUPOLA/ SPIRES/ TOWERS Does not Exist

DORMER Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

DUNNAGE STEEL Does not Exist

SKYLIGHT/ROOF VENT Does not Exist

ROOF/GRAVITY TANK Does not Exist

STAIRS/RAMPS: EXTERIOR Inspected

BUILDING CHEEK/FLANK WALLS Inspected

Condition 2 - Between Good and Fair

Deficiency CAST IN PLACE CONCRETE: CRACKS/SPALLING - MINOR

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K110

PB/A&W Print Date: 9/14/2020Page 12 of 44

Page 13: NYC Department of EducationFireman Alex Enriquez Building Square Footage 67000 Comments on the Area None Comments on the Stories (Floors) plus Basements 4 + B + Attic Comments on the

Question Response

EXTERIOR

STAIRS/RAMPS: EXTERIOR

BUILDING CHEEK/FLANK WALLS

Roof Plan reference

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Facade A

Violations No violations recorded.

RAILINGS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

STAIRS/RAMPS Inspected

Condition 3 - Fair

Deficiency CONCRETE: WORN-OUT TREAD/RISER/NOSING

Roof Plan reference

Deficiency Quantity 15

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K110

PB/A&W Print Date: 9/14/2020Page 13 of 44

Page 14: NYC Department of EducationFireman Alex Enriquez Building Square Footage 67000 Comments on the Area None Comments on the Stories (Floors) plus Basements 4 + B + Attic Comments on the

Question Response

EXTERIOR

STAIRS/RAMPS: EXTERIOR

STAIRS/RAMPS

Deficiency Photo1

Main Entry - Facade A

Violations No violations recorded.

WINDOWS Inspected

Replacement Quantity 9,100

Replacement Uom S.F.

EXTERIOR GUARDS Inspected

Condition 3 - Fair

Deficiency RUST - MINOR

Roof Plan reference

Elevation

Deficiency Quantity 50

Quantity Uom S.F.

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K110

PB/A&W Print Date: 9/14/2020Page 14 of 44

Page 15: NYC Department of EducationFireman Alex Enriquez Building Square Footage 67000 Comments on the Area None Comments on the Stories (Floors) plus Basements 4 + B + Attic Comments on the

Question Response

EXTERIOR

WINDOWS

EXTERIOR GUARDS

Deficiency Photo1

Facade F / G

Violations No violations recorded.

LINTELS Inspected

Condition 2 - Between Good and Fair

Deficiency STEEL: MINOR RUSTING

Roof Plan reference

Elevation

Deficiency Quantity 20

Quantity Uom L.F.

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Facade F - Exit 4

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K110

PB/A&W Print Date: 9/14/2020Page 15 of 44

Page 16: NYC Department of EducationFireman Alex Enriquez Building Square Footage 67000 Comments on the Area None Comments on the Stories (Floors) plus Basements 4 + B + Attic Comments on the

Question Response

EXTERIOR

WINDOWS

LINTELS Inspected

Violations No violations recorded.

WINDOWS Inspected

Material Type(s) Aluminum

InspectedInstance on Aluminum - Double Hung: All Facades

Instance Condition 1 - Good

Instance Quantity 9,100

Instance Quantity Uom S.F.

Installation Year 2014

Source of Installation Custodial Staff

Deficiency No deficiencies recorded

INTERIOR Inspected

POOLS Does not Exist

STRUCTURAL Inspected

COLUMNS/BEAMS/BEARING WALLS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

FLOOR STRUCTURE Inspected

Condition 4 - Between Fair and Poor

Deficiency CONCRETE SLAB ON GRADE: THRU CRACKS

Deficiency Location/Instance Basement- Tool Room, Gas Meter Room

Deficiency Quantity 350

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 5

Deficiency Photo1

Tool Room

Violations No violations recorded.

Deficiency CONCRETE SLAB ON GRADE: MINOR CRACKS

Deficiency Location/Instance Basement - Multipurpose Rooms, Oil Tank Room, Tool Room

Deficiency Quantity 1,000

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 5

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K110

PB/A&W Print Date: 9/14/2020Page 16 of 44

Page 17: NYC Department of EducationFireman Alex Enriquez Building Square Footage 67000 Comments on the Area None Comments on the Stories (Floors) plus Basements 4 + B + Attic Comments on the

Question Response

INTERIOR

STRUCTURAL

FLOOR STRUCTURE

Deficiency Photo1

Multipurpose Room

Violations No violations recorded.

FOUNDATION WALLS Inspected

Material Type(s) Masonry

Condition 3 - Fair

Deficiency BRICK: OPEN JOINTS

Deficiency Location/Instance Basement - Gas Meter Room, Electrical Panel Room

Deficiency Quantity 200

Quantity Uom S.F.

Potential Action REPOINT

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 5

Deficiency Photo1

Gas Meter Room

Violations No violations recorded.

ROOF STRUCTURE Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

VAULTS-BUNKERS Does not Exist

AUDITORIUM Inspected

InspectedInstance on 4th Floor (300 Seats)

Ceiling

InspectedInstance on 4th Floor (300 Seats)

Condition 2 - Between Good and Fair

Deficiency METAL PAN: DAMAGED/MISSING

Deficiency Location/Instance Rear of Room, Center

Deficiency Quantity 100

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 4

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K110

PB/A&W Print Date: 9/14/2020Page 17 of 44

Page 18: NYC Department of EducationFireman Alex Enriquez Building Square Footage 67000 Comments on the Area None Comments on the Stories (Floors) plus Basements 4 + B + Attic Comments on the

Question Response

INTERIOR

AUDITORIUM

Ceiling

Purpose of Action LEVEL 4

Deficiency Photo1

Rear

Violations 35311988P

Door(s)

InspectedInstance on 4th Floor (300 Seats)

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Fixed H/C Lift

Does not ExistInstance on 4th Floor (300 Seats)

Fixed Seating

InspectedInstance on 4th Floor (300 Seats)

Condition 2 - Between Good and Fair

Deficiency DAMAGED/BROKEN/INOPERABLE

Deficiency Location/Instance Seats I/2, J/2

Deficiency Quantity 2

Quantity Uom EACH

Potential Action REPLACE

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 6

Deficiency Photo1

Seats I/2, J/2

Violations No violations recorded.

Deficiency DAMAGED/BROKEN/INOPERABLE

Deficiency Location/Instance Seat I/5

Deficiency Quantity 1

Quantity Uom EACH

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K110

PB/A&W Print Date: 9/14/2020Page 18 of 44

Page 19: NYC Department of EducationFireman Alex Enriquez Building Square Footage 67000 Comments on the Area None Comments on the Stories (Floors) plus Basements 4 + B + Attic Comments on the

Question Response

INTERIOR

AUDITORIUM

Fixed Seating

Deficiency Photo1

Seat I/5

Violations No violations recorded.

Floor Finish

InspectedInstance on 4th Floor (300 Seats)

Condition 4 - Between Fair and Poor

Deficiency VINYL TILES: TRIPPING HAZARD - ELECTRICAL OUTLET

Deficiency Location/Instance Center

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 6

Deficiency Photo1

Center

Violations No violations recorded.

Deficiency VINYL TILES: DETERIORATED SUBSTRATE

Deficiency Location/Instance Near Stage, Center, Rear of Room, East side, West side, North side,South side

Deficiency Quantity 300

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K110

PB/A&W Print Date: 9/14/2020Page 19 of 44

Page 20: NYC Department of EducationFireman Alex Enriquez Building Square Footage 67000 Comments on the Area None Comments on the Stories (Floors) plus Basements 4 + B + Attic Comments on the

Question Response

INTERIOR

AUDITORIUM

Floor Finish

Deficiency Photo1

Near Stage

Violations No violations recorded.

Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES

Deficiency Location/Instance North side, South side Near Entrance

Deficiency Quantity 100

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

North side

Violations No violations recorded.

Sliding-folding Partition

Does not ExistInstance on 4th Floor (300 Seats)

Stage

InspectedInstance on 4th Floor (300 Seats)

Stage Inspected

InspectedInstance on 4th Floor (300 Seats)

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Stage Curtain Rigging Does not Exist

Does not ExistInstance on 4th Floor (300 Seats)

Stage Curtains Does not Exist

Does not ExistInstance on 4th Floor (300 Seats)

Walls

InspectedInstance on 4th Floor (300 Seats)

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Window Curtains/Shades/Blinds

InspectedInstance on 4th Floor (300 Seats)

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K110

PB/A&W Print Date: 9/14/2020Page 20 of 44

Page 21: NYC Department of EducationFireman Alex Enriquez Building Square Footage 67000 Comments on the Area None Comments on the Stories (Floors) plus Basements 4 + B + Attic Comments on the

Question Response

INTERIOR

AUDITORIUM

Window Curtains/Shades/Blinds

Condition 3 - Fair

Deficiency WORN/DAMAGED CURTAINS

Deficiency Location/Instance Rear of stage, Rear of Room

Deficiency Quantity 80

Quantity Uom S.F.

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Rear of stage

Rear of Room

Violations No violations recorded.

CAFETERIA Inspected

InspectedInstance on 1st Floor (2,000SF)

Ceiling

InspectedInstance on 1st Floor (2,000SF)

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s)

InspectedInstance on 1st Floor (2,000SF)

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Fixed Equipment

Does not ExistInstance on 1st Floor (2,000SF)

Floor Finish

InspectedInstance on 1st Floor (2,000SF)

Condition 4 - Between Fair and Poor

Deficiency VINYL TILES: DETERIORATED SUBSTRATE

Deficiency Location/Instance Near windows, Near Kitchen

Deficiency Quantity 150

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K110

PB/A&W Print Date: 9/14/2020Page 21 of 44

Page 22: NYC Department of EducationFireman Alex Enriquez Building Square Footage 67000 Comments on the Area None Comments on the Stories (Floors) plus Basements 4 + B + Attic Comments on the

Question Response

INTERIOR

CAFETERIA

Floor Finish

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Near windows

Violations No violations recorded.

Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES

Deficiency Location/Instance Center , Near Entrance

Deficiency Quantity 15

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Center

Violations No violations recorded.

Sliding-folding Partition

Does not ExistInstance on 1st Floor (2,000SF)

Stage

Does not ExistInstance on 1st Floor (2,000SF)

Walls

InspectedInstance on 1st Floor (2,000SF)

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Window Curtains/Shades/Blinds

Does not ExistInstance on 1st Floor (2,000SF)

CLASSROOMS/CORRIDORS/ADMIN SPACES Inspected

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency GYPSUM BOARD: DAMAGED/DETERIORATED

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K110

PB/A&W Print Date: 9/14/2020Page 22 of 44

Page 23: NYC Department of EducationFireman Alex Enriquez Building Square Footage 67000 Comments on the Area None Comments on the Stories (Floors) plus Basements 4 + B + Attic Comments on the

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Ceiling

Deficiency Location/Instance 2nd Floor Near Elevator, 3rd Floor Near Elevator, 4th Floor NearElevator

Deficiency Quantity 60

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

4th Floor Near Elevator

Violations No violations recorded.

Deficiency PLASTER: CRACKS/SPALLING

Deficiency Location/Instance Room 403

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room 403

Violations No violations recorded.

Deficiency METAL PAN: DAMAGED/MISSING

Deficiency Location/Instance Room 306

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K110

PB/A&W Print Date: 9/14/2020Page 23 of 44

Page 24: NYC Department of EducationFireman Alex Enriquez Building Square Footage 67000 Comments on the Area None Comments on the Stories (Floors) plus Basements 4 + B + Attic Comments on the

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Ceiling

Deficiency Photo1

Room 306

Violations No violations recorded.

Door(s) Inspected

Condition 5 - Poor

Deficiency WOOD: DETERIORATED DOOR

Deficiency Location/Instance Rooms 200 (Original Building), 306, 312, 403, 406, and others

Deficiency Quantity 20

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room 406

Violations No violations recorded.

Floor Finish Inspected

Condition 5 - Poor

Deficiency CONCRETE: CRACKS

Deficiency Location/Instance North Basement Room, South Basement Room

Deficiency Quantity 800

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K110

PB/A&W Print Date: 9/14/2020Page 24 of 44

Page 25: NYC Department of EducationFireman Alex Enriquez Building Square Footage 67000 Comments on the Area None Comments on the Stories (Floors) plus Basements 4 + B + Attic Comments on the

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Floor Finish

Deficiency Photo1

Basement Room

Violations No violations recorded.

Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES

Deficiency Location/Instance Rooms 104, 206, 312, 403, 406, and others

Deficiency Quantity 7,000

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room 403

Violations No violations recorded.

Deficiency VINYL TILES: DETERIORATED SUBSTRATE

Deficiency Location/Instance Corridor near Rooms 101, 102, 106, 403, Corridor near Cafeteria, andothers

Deficiency Quantity 2,500

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Corridor near Room 403

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K110

PB/A&W Print Date: 9/14/2020Page 25 of 44

Page 26: NYC Department of EducationFireman Alex Enriquez Building Square Footage 67000 Comments on the Area None Comments on the Stories (Floors) plus Basements 4 + B + Attic Comments on the

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Floor Finish Inspected

Violations No violations recorded.

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency GYPSUM BOARD: DETERIORATED

Deficiency Location/Instance 2nd Floor Near Elevator, 3rd Floor Near Elevator, 4th Floor NearElevator

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

4th Floor Near Elevator

Violations No violations recorded.

Deficiency PLASTER: CRACKS/SPALLING

Deficiency Location/Instance Rooms 103, 104, 306, Corridor near Room 103

Deficiency Quantity 60

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room 306

Violations No violations recorded.

Specialties Does not Exist

GYMNASIUM Inspected

InspectedInstance on 3rd Floor

Ceiling

InspectedInstance on 3rd Floor

Condition 2 - Between Good and Fair

Deficiency PLASTER: CRACKS/SPALLING

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K110

PB/A&W Print Date: 9/14/2020Page 26 of 44

Page 27: NYC Department of EducationFireman Alex Enriquez Building Square Footage 67000 Comments on the Area None Comments on the Stories (Floors) plus Basements 4 + B + Attic Comments on the

Question Response

INTERIOR

GYMNASIUM

Ceiling

Deficiency Location/Instance Near windows

Deficiency Quantity 25

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 4

Deficiency Photo1

Near windows

Violations 35311988P

Door(s)

InspectedInstance on 3rd Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Fixed Equipment

InspectedInstance on 3rd Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Floor Finish

InspectedInstance on 3rd Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Seating

Does not ExistInstance on 3rd Floor

Sliding-folding Partition

Does not ExistInstance on 3rd Floor

Stage

Does not ExistInstance on 3rd Floor

Walls

InspectedInstance on 3rd Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Window Curtains/Shades/Blinds

Does not ExistInstance on 3rd Floor

INTERIOR DOOR HARDWARE Inspected

Condition 3 - Fair

Deficiency No deficiencies recorded

INTERIOR GUARDS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K110

PB/A&W Print Date: 9/14/2020Page 27 of 44

Page 28: NYC Department of EducationFireman Alex Enriquez Building Square Footage 67000 Comments on the Area None Comments on the Stories (Floors) plus Basements 4 + B + Attic Comments on the

Question Response

INTERIOR

KITCHEN Inspected

InspectedInstance on 1st Floor

Ceiling

Not RequiredInstance on 1st Floor

Door(s)

Does not ExistInstance on 1st Floor

Floor Finish

Not RequiredInstance on 1st Floor

Walls

Not RequiredInstance on 1st Floor

LIBRARY Inspected

InspectedInstance on Room 207/208

Built-in Furnishing

InspectedInstance on Room 207/208

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Ceiling

InspectedInstance on Room 207/208

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s)

InspectedInstance on Room 207/208

Condition 3 - Fair

Deficiency WOOD: DETERIORATED DOOR

Deficiency Location/Instance Entrance

Deficiency Quantity 1

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Entrance

Violations No violations recorded.

Floor Finish

InspectedInstance on Room 207/208

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Walls

InspectedInstance on Room 207/208

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K110

PB/A&W Print Date: 9/14/2020Page 28 of 44

Page 29: NYC Department of EducationFireman Alex Enriquez Building Square Footage 67000 Comments on the Area None Comments on the Stories (Floors) plus Basements 4 + B + Attic Comments on the

Question Response

INTERIOR

LOCKER ROOM Does not Exist

MULTI-PURPOSE ROOM Inspected

InspectedInstance on Basement - North (2,000SF)

InspectedInstance on Basement - South (1,000)

Ceiling

InspectedInstance on Basement - North (2,000SF)

Condition 2 - Between Good and Fair

Deficiency PLASTER: CRACKS/SPALLING

Deficiency Location/Instance West side

Deficiency Quantity 25

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

West side

Violations No violations recorded.

Door(s)

InspectedInstance on Basement - North (2,000SF)

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

InspectedInstance on Basement - South (1,000)

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Fixed Equipment

Does not ExistInstance on Basement - North (2,000SF)

Does not ExistInstance on Basement - South (1,000)

Floor Finish

InspectedInstance on Basement - North (2,000SF)

Condition 5 - Poor

Deficiency CONCRETE: CRACKS

Deficiency Location/Instance Center

Deficiency Quantity 25

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K110

PB/A&W Print Date: 9/14/2020Page 29 of 44

Page 30: NYC Department of EducationFireman Alex Enriquez Building Square Footage 67000 Comments on the Area None Comments on the Stories (Floors) plus Basements 4 + B + Attic Comments on the

Question Response

INTERIOR

MULTI-PURPOSE ROOM

Floor Finish

Deficiency Photo1

Center

Violations No violations recorded.

Deficiency ROLLED ASPHALT: CRACKS

Deficiency Location/Instance West side, East side

Deficiency Quantity 1,500

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

West side

Violations No violations recorded.

Sliding-folding Partition

Does not ExistInstance on Basement - North (2,000SF)

Does not ExistInstance on Basement - South (1,000)

Stage

Does not ExistInstance on Basement - North (2,000SF)

Does not ExistInstance on Basement - South (1,000)

Walls

InspectedInstance on Basement - South (1,000)

Condition 2 - Between Good and Fair

Deficiency BRICK: CRACKS/SPALLING

Deficiency Location/Instance West wall

Deficiency Quantity 100

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K110

PB/A&W Print Date: 9/14/2020Page 30 of 44

Page 31: NYC Department of EducationFireman Alex Enriquez Building Square Footage 67000 Comments on the Area None Comments on the Stories (Floors) plus Basements 4 + B + Attic Comments on the

Question Response

INTERIOR

MULTI-PURPOSE ROOM

Walls

Deficiency Photo1

Near windows

Violations No violations recorded.

InspectedInstance on Basement - North (2,000SF)

Condition 2 - Between Good and Fair

Deficiency BRICK: CRACKS/SPALLING

Deficiency Location/Instance Near windows

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Near windows

Violations No violations recorded.

Window Curtains/Shades/Blinds

Does not ExistInstance on Basement - North (2,000SF)

Does not ExistInstance on Basement - South (1,000)

SCIENCE DEMO ROOM Does not Exist

SCIENCE LAB Does not Exist

SCIENCE PREP ROOM Does not Exist

SHOWER ROOM Does not Exist

STAIRS/RAMPS: INTERIOR Inspected

Do Letter Stair Signs Exist? Partially

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s) Inspected

Condition 4 - Between Fair and Poor

Deficiency METAL CLAD WOOD: DETERIORATED DOOR

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K110

PB/A&W Print Date: 9/14/2020Page 31 of 44

Page 32: NYC Department of EducationFireman Alex Enriquez Building Square Footage 67000 Comments on the Area None Comments on the Stories (Floors) plus Basements 4 + B + Attic Comments on the

Question Response

INTERIOR

STAIRS/RAMPS: INTERIOR

Door(s)

Deficiency Location/Instance Stairs AB/4, CD/Basement, EF/Basement

Deficiency Quantity 3

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Stair AB/4

Violations No violations recorded.

Partition Inspected

Condition 2 - Between Good and Fair

Deficiency GLASS PANEL: DAMAGED/DETERIORATED

Deficiency Location/Instance Stairs AB/1, EF/Basement, GH/Basement, 4

Deficiency Quantity 40

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Stair GH/Basement

Violations No violations recorded.

Railings Inspected

Condition 4 - Between Fair and Poor

Deficiency METAL: MISSING

Deficiency Location/Instance Exits 4, 6, 7 Vestibules

Deficiency Quantity 18

Quantity Uom L.F.

Potential Action REPLACE

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 6

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K110

PB/A&W Print Date: 9/14/2020Page 32 of 44

Page 33: NYC Department of EducationFireman Alex Enriquez Building Square Footage 67000 Comments on the Area None Comments on the Stories (Floors) plus Basements 4 + B + Attic Comments on the

Question Response

INTERIOR

STAIRS/RAMPS: INTERIOR

Railings

Deficiency Photo1

Exit 7 Vestibule

Violations No violations recorded.

Stairs and Landings Inspected

Condition 5 - Poor

Deficiency STONE: BROKEN/MISSING

Deficiency Location/Instance Stairs CD/2, 3, EF/Basement, 2, 4, and others

Deficiency Quantity 100

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Stair EF/Basement

Violations No violations recorded.

Deficiency CONCRETE: CRACKS/SPALLING - MAJOR

Deficiency Location/Instance Stairs CD/Basement, EF/Basement, Multi-Purpose Room - South

Deficiency Quantity 80

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K110

PB/A&W Print Date: 9/14/2020Page 33 of 44

Page 34: NYC Department of EducationFireman Alex Enriquez Building Square Footage 67000 Comments on the Area None Comments on the Stories (Floors) plus Basements 4 + B + Attic Comments on the

Question Response

INTERIOR

STAIRS/RAMPS: INTERIOR

Stairs and Landings

Multi-Purpose Room - South

Stair CD/Basement

Violations No violations recorded.

Deficiency ROLLED ASPHALT: CRACKS

Deficiency Location/Instance Stairs CD/1, 3, 4, EF/1, 4, and others

Deficiency Quantity 3,000

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Stair CD/1

Violations No violations recorded.

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency PLASTER: CRACKS/SPALLING

Deficiency Location/Instance Stairs CD/Basement, EF/1

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K110

PB/A&W Print Date: 9/14/2020Page 34 of 44

Page 35: NYC Department of EducationFireman Alex Enriquez Building Square Footage 67000 Comments on the Area None Comments on the Stories (Floors) plus Basements 4 + B + Attic Comments on the

Question Response

INTERIOR

STAIRS/RAMPS: INTERIOR

Walls

Deficiency Photo1

Stair EF/1

Violations No violations recorded.

Deficiency CERAMIC TILE: BROKEN/ MISSING

Deficiency Location/Instance Stairs CD/Basement, 2, 3, 4, EF/1, and others

Deficiency Quantity 80

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Stair CD/Basement

Violations No violations recorded.

TOILET ROOMS - STAFF Inspected

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s) Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Floor Finish Inspected

Condition 3 - Fair

Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES

Deficiency Location/Instance Inside Room 108

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K110

PB/A&W Print Date: 9/14/2020Page 35 of 44

Page 36: NYC Department of EducationFireman Alex Enriquez Building Square Footage 67000 Comments on the Area None Comments on the Stories (Floors) plus Basements 4 + B + Attic Comments on the

Question Response

INTERIOR

TOILET ROOMS - STAFF

Floor Finish

Deficiency Photo1

Inside Room 108

Violations No violations recorded.

Stalls Inspected

Condition 5 - Poor

Deficiency RUST - MAJOR

Deficiency Location/Instance Inside Room 108

Deficiency Quantity 1

Quantity Uom EACH

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Inside Room 108

Violations No violations recorded.

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

TOILET ROOMS - STUDENTS Inspected

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s) Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Floor Finish Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Stalls Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K110

PB/A&W Print Date: 9/14/2020Page 36 of 44

Page 37: NYC Department of EducationFireman Alex Enriquez Building Square Footage 67000 Comments on the Area None Comments on the Stories (Floors) plus Basements 4 + B + Attic Comments on the

Question Response

INTERIOR

TOILET ROOMS - STUDENTS

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency PLASTER: CRACKS/SPALLING

Deficiency Location/Instance Inside Room 103

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Inside Room 103

Violations No violations recorded.

LIFE SAFETY Inspected

F.D. HOLDING AREA Does not Exist

STEEL STAIRS Does not Exist

SITE Inspected

CONTAINERIZATION Does not Exist

Drainage System for Asphalt Inspected

Catch Basins/Manhole - Surrounded by asphalt Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Culverts - Asphalt Covering Does not Exist

Drainage System for Concrete Inspected

Catch Basins/Manhole - Surrounded by concrete Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Culverts - Concrete Covering Does not Exist

Drainage System for Soil Does not Exist

DRINKING FOUNTAINS Does not Exist

FENCES Inspected

Condition 3 - Fair

Deficiency CHAIN LINK: DAMAGED/DETERIORATED

Deficiency Location/Instance Monitor Street near gate to Schoolyard

Deficiency Quantity 100

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1 No photo recorded

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K110

PB/A&W Print Date: 9/14/2020Page 37 of 44

Page 38: NYC Department of EducationFireman Alex Enriquez Building Square Footage 67000 Comments on the Area None Comments on the Stories (Floors) plus Basements 4 + B + Attic Comments on the

Question Response

SITE

FENCES

Violations No violations recorded.

Deficiency WROUGHT IRON: RUST - MAJOR

Deficiency Location/Instance Monitor Street

Deficiency Quantity 40

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Monitor Street

Violations No violations recorded.

Deficiency WROUGHT IRON: DAMAGED/DETERIORATED

Deficiency Location/Instance Driggs Avenue, Monitor Street

Deficiency Quantity 80

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Monitor Street

Violations No violations recorded.

Deficiency CONCRETE CURB: DAMAGED/DETERIORATED

Deficiency Location/Instance Driggs Avenue, Monitor Street

Deficiency Quantity 175

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K110

PB/A&W Print Date: 9/14/2020Page 38 of 44

Page 39: NYC Department of EducationFireman Alex Enriquez Building Square Footage 67000 Comments on the Area None Comments on the Stories (Floors) plus Basements 4 + B + Attic Comments on the

Question Response

SITE

FENCES

Deficiency Photo1

Monitor Street

Violations No violations recorded.

IRRIGATION SYSTEM Does not Exist

PAVING Inspected

Student Non-Use Inspected

Gravel Exists? No

Asphalt Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Concrete Inspected

Condition 3 - Fair

Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS

Deficiency Location/Instance Driggs Avenue, Monitor Street

Deficiency Quantity 300

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Monitor Street

Violations No violations recorded.

Pavers Does not Exist

Student Use Inspected

Gravel Exists? No

Asphalt Inspected

Condition 4 - Between Fair and Poor

Deficiency POTHOLES

Deficiency Location/Instance South Schoolyard

Deficiency Quantity 15

Quantity Uom S.F.

Potential Action REPAIR

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K110

PB/A&W Print Date: 9/14/2020Page 39 of 44

Page 40: NYC Department of EducationFireman Alex Enriquez Building Square Footage 67000 Comments on the Area None Comments on the Stories (Floors) plus Basements 4 + B + Attic Comments on the

Question Response

SITE

PAVING

Student Use

Asphalt

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

South Schoolyard

Violations No violations recorded.

Deficiency CRACKS - MINOR

Deficiency Location/Instance South Schoolyard

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1 No photo recorded

Violations No violations recorded.

Deficiency CRACKS - MAJOR

Deficiency Location/Instance South Schoolyard

Deficiency Quantity 600

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

South Schoolyard

Violations No violations recorded.

Concrete Inspected

Condition 3 - Fair

Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS

Deficiency Location/Instance North Schoolyard

Deficiency Quantity 75

Quantity Uom S.F.

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K110

PB/A&W Print Date: 9/14/2020Page 40 of 44

Page 41: NYC Department of EducationFireman Alex Enriquez Building Square Footage 67000 Comments on the Area None Comments on the Stories (Floors) plus Basements 4 + B + Attic Comments on the

Question Response

SITE

PAVING

Student Use

Concrete

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

North Schoolyard

Violations No violations recorded.

Pavers Does not Exist

Site Sidewalks & Walkways Inspected

Asphalt Does not Exist

Concrete Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Pavers Does not Exist

DOT Sidewalk Inspected

Asphalt Does not Exist

Concrete Inspected

Condition 4 - Between Fair and Poor

Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS

Deficiency Location/Instance Driggs Avenue, Monitor Street

Deficiency Quantity 1,000

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Monitor Street

Violations No violations recorded.

Deficiency DAMAGED CURBS

Deficiency Location/Instance Driggs Avenue, Monitor Street

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K110

PB/A&W Print Date: 9/14/2020Page 41 of 44

Page 42: NYC Department of EducationFireman Alex Enriquez Building Square Footage 67000 Comments on the Area None Comments on the Stories (Floors) plus Basements 4 + B + Attic Comments on the

Question Response

SITE

PAVING

DOT Sidewalk

Concrete

Deficiency Quantity 50

Quantity Uom L.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Monitor Street

Violations No violations recorded.

Pavers Does not Exist

PLAYGROUNDS Inspected

InspectedInstance on Schoolyard - South

Benches

Does not ExistInstance on Schoolyard - South

Fence

Does not ExistInstance on Schoolyard - South

Pavement

Does not ExistInstance on Schoolyard - South

Play Equipment

InspectedInstance on Schoolyard - South

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Safety Surfacing

InspectedInstance on Schoolyard - South

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Unpaved Area

Does not ExistInstance on Schoolyard - South

PLAYING SURFACE Does not Exist

RETAINING WALLS Does not Exist

SEATING Inspected

Benches Inspected

Concrete Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Metal/Wood/Plastic Inspected

Condition 3 - Fair

Deficiency DAMAGED/DETERIORATED

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K110

PB/A&W Print Date: 9/14/2020Page 42 of 44

Page 43: NYC Department of EducationFireman Alex Enriquez Building Square Footage 67000 Comments on the Area None Comments on the Stories (Floors) plus Basements 4 + B + Attic Comments on the

Question Response

SITE

SEATING

Benches

Metal/Wood/Plastic

Deficiency Location/Instance South Schoolyard

Deficiency Quantity 1

Quantity Uom EACH

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

South Schoolyard

Violations No violations recorded.

Bleachers Does not Exist

SITE WALLS (NOT RETAINING WALLS) Inspected

Condition 4 - Between Fair and Poor

Deficiency BRICK: DETERIORATED COPING STONE

Deficiency Location/Instance South Schoolyard

Deficiency Quantity 50

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

South Schoolyard

Violations No violations recorded.

Deficiency BRICK: CRACKS/SPALLING - MAJOR

Deficiency Location/Instance South Schoolyard

Deficiency Quantity 225

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K110

PB/A&W Print Date: 9/14/2020Page 43 of 44

Page 44: NYC Department of EducationFireman Alex Enriquez Building Square Footage 67000 Comments on the Area None Comments on the Stories (Floors) plus Basements 4 + B + Attic Comments on the

Question Response

SITE

SITE WALLS (NOT RETAINING WALLS)

Deficiency Photo1

South Schoolyard

Violations No violations recorded.

STAIRS/RAMPS: EXTERIOR Does not Exist

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K110

PB/A&W Print Date: 9/14/2020Page 44 of 44