Asset: AUX. SERV.- JAM. LEARN CT TR - Q, 162-02 HILLSIDE AVENUE, New York, 11432 Inspection Id Inspection Type Time In Last Edited SA : Q969 Architectural - Senior 2019-12-20 7:38 AM 2020-01-15 12:31 PM AA : Q969 Architectural - Associate 2019-12-20 8:51 AM 2019-12-20 2:18 PM Asset Data Question Answer Was the building fully accessible for inspection No Inspection Access Comment Outdoor Electrical Enclosure (missing key) Principal(s) Information Principal Name Jeffrey Robins Organization Jamaica Auxiliary Service Learning Center - Queens Did you meet with this Principal? Yes Did this Principal provide feedback? Yes Summary of Principal's Feedback The Principal had no concerns regarding the physical condition of the building. Custodian Was not present Fireman Christopher Hoytt Building Square Footage 1300 Comments on the Area None Comments on the Stories (Floors) plus Basements 1 (No Basement) Comments on the Number of Classrooms 2 Comments on the Year Built 1997 Student Population 20 Staff Population 5 Weather Fair Facade Photo Corner of Facade A and Facade D - South View NYC Department of Education Architectural Inspection Building Condition Assessment Survey 2019 - 2020 Q969 PB/A&W Print Date: 9/14/2020 Page 1 of 10

Upload: others

Post on 14-Oct-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: NYC Department of EducationAsset: AUX. SERV.- JAM. LEARN CT TR - Q, 162-02 HILLSIDE AVENUE, New York, 11432 Inspection Id Inspection Type Time In Last Edited SA : Q969 Architectural

Asset: AUX. SERV.- JAM. LEARN CT TR - Q, 162-02 HILLSIDE AVENUE, New York, 11432

Inspection Id Inspection Type Time In Last Edited

SA : Q969 Architectural - Senior 2019-12-20 7:38 AM 2020-01-15 12:31 PM

AA : Q969 Architectural - Associate 2019-12-20 8:51 AM 2019-12-20 2:18 PM

Asset Data

Question Answer

Was the building fully accessible for inspection No

Inspection Access Comment Outdoor Electrical Enclosure (missing key)

Principal(s) Information

Principal Name Jeffrey Robins

Organization Jamaica Auxiliary Service Learning Center - Queens

Did you meet with this Principal? Yes

Did this Principal provide feedback? Yes

Summary of Principal's Feedback The Principal had no concerns regarding the physical condition of thebuilding.

Custodian Was not present

Fireman Christopher Hoytt

Building Square Footage 1300

Comments on the Area None

Comments on the Stories (Floors) plus Basements 1 (No Basement)

Comments on the Number of Classrooms 2

Comments on the Year Built 1997

Student Population 20

Staff Population 5

Weather Fair

Facade Photo

Corner of Facade A and Facade D - SouthView

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q969

PB/A&W Print Date: 9/14/2020Page 1 of 10

Page 2: NYC Department of EducationAsset: AUX. SERV.- JAM. LEARN CT TR - Q, 162-02 HILLSIDE AVENUE, New York, 11432 Inspection Id Inspection Type Time In Last Edited SA : Q969 Architectural

Main Entrance Photo

Facade A - Unit T1

Roof Photo

Roof 1

Have any Systems/Major Building Components been upgraded? Yes

Systems: Ramps/Stairs and Railings repaired

Year: 2018

Have there been any New Building Additions? No

Tandem Schools? No

Leased Space? No

Priority Condition

PriorityCondition ExistLast Year?

PriorityCategory

ConditionDescription

ComponentAffected

LocationDescription

Person(s)Notified

Person(s) Title PhotoImage

Yes ProtrudingElements

Damaged metalwall panel withexposed sharpedges is aprotrudingelements hazard.

EXTERIOR |EXTERIORWALLS

West side ofTransportableUnit T1

ChristopherHoytt

Fireman

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q969

PB/A&W Print Date: 9/14/2020Page 2 of 10

Page 3: NYC Department of EducationAsset: AUX. SERV.- JAM. LEARN CT TR - Q, 162-02 HILLSIDE AVENUE, New York, 11432 Inspection Id Inspection Type Time In Last Edited SA : Q969 Architectural

Structural Engineer Required

StructuralCondition Type

ConditionDescription

ComponentAffected

LocationDescription

Person(s)Notified

Person(s) Title PhotoImage

No condition recorded

Accessibility

Accessibility Status Question Response

Is the primary or secondary entrance on an accessible route? Yes

Is the building a multi-story building? No

Do any of the following spaces exist? Classroom, Art Room, Auditorium, Cafeteria,Computer, Gymnasiums, Library, Multipurpose Room, Science Labs

Yes

For the spaces that do exist, are they ALL accessible? Yes

Is there at least one Boys and Girls or Unisex toilet accessible in the building Yes

Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem

FireAlarmStrobe

FUNCTIONAL ACCESSIBILITY

Exterior Routes

Exterior Entrances & Exits Yes

Exterior H/C Lifts No No

Exterior Ramps and Railings Yes Yes

Interior Routes

Corridor and Lobby H/C Lifts No No

Interior Corridor Doors and Hardware Yes Yes

Interior Corridors and Lobbies Yes

Interior Elevators No

Interior Lobby Doors and Hardware Yes

Interior Ramps No

Rooms & Spaces

Art Rooms No

Auditorium No

Cafeteria No

Classrooms 1st Floor Yes Yes

Computer Rooms No

Gymnasium No

Library No

Main Office No

Multi-purpose Room No

Nurse's Room No

Pool No

Science Lab No

Toilet Rooms (Boys) 1st Floor - Unisex Yes Yes

Toilet Rooms (Girls) 1st Floor - Unisex Yes Yes

Toilet Rooms (Staff) 1st Floor - Unisex Yes Yes

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q969

PB/A&W Print Date: 9/14/2020Page 3 of 10

Page 4: NYC Department of EducationAsset: AUX. SERV.- JAM. LEARN CT TR - Q, 162-02 HILLSIDE AVENUE, New York, 11432 Inspection Id Inspection Type Time In Last Edited SA : Q969 Architectural

Building Template

Inspection

Question Response

Architectural

EXTERIOR Inspected

AREAWAY Does not Exist

AWNINGS AND CANOPIES Does not Exist

CHIMNEY Does not Exist

COPING Does not Exist

CORNICE Does not Exist

DOORS Inspected

DOORS AND FRAMES Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

DOOR HARDWARE Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

LINTELS Does not Exist

TRANSOM/SIDE LIGHT Does not Exist

EXTERIOR WALLS Inspected

Material Type(s) Steel

Replacement Quantity 1,700

Replacement Uom S.F.

InspectedInstance on All Facades

Instance Condition 5 - Poor

Instance Quantity 1,700

Instance Quantity Uom S.F.

Deficiency METAL PANEL: SEVERE DENTS

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q969

PB/A&W Print Date: 9/14/2020Page 4 of 10

Page 5: NYC Department of EducationAsset: AUX. SERV.- JAM. LEARN CT TR - Q, 162-02 HILLSIDE AVENUE, New York, 11432 Inspection Id Inspection Type Time In Last Edited SA : Q969 Architectural

Question Response

EXTERIOR

EXTERIOR WALLS

Roof Plan reference

Elevation

Deficiency Quantity 500

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Facade C

Violations No violations recorded.

Deficiency METAL PANEL: DAMAGED TRIM

Roof Plan reference

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q969

PB/A&W Print Date: 9/14/2020Page 5 of 10

Page 6: NYC Department of EducationAsset: AUX. SERV.- JAM. LEARN CT TR - Q, 162-02 HILLSIDE AVENUE, New York, 11432 Inspection Id Inspection Type Time In Last Edited SA : Q969 Architectural

Question Response

EXTERIOR

EXTERIOR WALLS

Elevation

Deficiency Quantity 200

Quantity Uom L.F.

Potential Action REPLACE

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 6

Deficiency Photo1

Facade C

Violations No violations recorded.

EXTERIOR SOFFITS Does not Exist

LOADING DOCK Does not Exist

LOUVER Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

PARAPETS Does not Exist

PLAZA DECK Does not Exist

ROOF Inspected

Roofing Inspected

Replacement Quantity 1,300

Replacement Uom S.F.

ROOF HATCH/SMOKE HATCH Does not Exist

LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS Does not Exist

ROOF BARRIER Does not Exist

ROOF CAGE Does not Exist

ROOF FENCE Does not Exist

ROOFING Inspected

InspectedInstance on Single Ply, Mechanically Fastened Roof: Roof 1

Instance Condition 3 - Fair

Instance Quantity 1,300

Instance Quantity Uom S.F.

Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?

No

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q969

PB/A&W Print Date: 9/14/2020Page 6 of 10

Page 7: NYC Department of EducationAsset: AUX. SERV.- JAM. LEARN CT TR - Q, 162-02 HILLSIDE AVENUE, New York, 11432 Inspection Id Inspection Type Time In Last Edited SA : Q969 Architectural

Question Response

EXTERIOR

ROOF

Roofing

ROOFING

Dunnage Steel less than 18" above the Roofing?

Installation Year 1997

Source of Installation Custodial Staff

Deficiency SINGLE PLY, MECHANICALLY FASTENED ROOF: ROOFING:BEYOND USEFUL LIFE

Deficiency Location/Instance Single Ply, Mechanically Fastened Roof: Roof 1

Deficiency Quantity 1,300

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 1

Purpose of Action LEVEL 2

Deficiency Photo1 No photo recorded

Violations No violations recorded.

ROOFING DRAINS Does not Exist

Specialties Does not Exist

STAIRS/RAMPS: EXTERIOR Inspected

BUILDING CHEEK/FLANK WALLS Does not Exist

RAILINGS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

STAIRS/RAMPS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

WINDOWS Inspected

Replacement Quantity 100

Replacement Uom S.F.

EXTERIOR GUARDS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

LINTELS Does not Exist

WINDOWS Inspected

Material Type(s) Aluminum

InspectedInstance on Aluminum - Other: Facade A

Instance Condition 3 - Fair

Instance Quantity 100

Instance Quantity Uom S.F.

Installation Year 1997

Source of Installation Custodial Staff

Deficiency No deficiencies recorded

INTERIOR Inspected

POOLS Does not Exist

STRUCTURAL Inspected

COLUMNS/BEAMS/BEARING WALLS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q969

PB/A&W Print Date: 9/14/2020Page 7 of 10

Page 8: NYC Department of EducationAsset: AUX. SERV.- JAM. LEARN CT TR - Q, 162-02 HILLSIDE AVENUE, New York, 11432 Inspection Id Inspection Type Time In Last Edited SA : Q969 Architectural

Question Response

INTERIOR

STRUCTURAL

FLOOR STRUCTURE Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

FOUNDATION WALLS Does not Exist

ROOF STRUCTURE Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

VAULTS-BUNKERS Does not Exist

AUDITORIUM Does not Exist

CAFETERIA Does not Exist

CLASSROOMS/CORRIDORS/ADMIN SPACES Inspected

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s) Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Floor Finish Inspected

Condition 3 - Fair

Deficiency VINYL TILES: DETERIORATED SUBSTRATE

Deficiency Location/Instance Rooms T1, T2

Deficiency Quantity 300

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room T1

Violations No violations recorded.

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Specialties Does not Exist

GYMNASIUM Does not Exist

INTERIOR DOOR HARDWARE Inspected

Condition 3 - Fair

Deficiency No deficiencies recorded

INTERIOR GUARDS Does not Exist

KITCHEN Does not Exist

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q969

PB/A&W Print Date: 9/14/2020Page 8 of 10

Page 9: NYC Department of EducationAsset: AUX. SERV.- JAM. LEARN CT TR - Q, 162-02 HILLSIDE AVENUE, New York, 11432 Inspection Id Inspection Type Time In Last Edited SA : Q969 Architectural

Question Response

INTERIOR

LIBRARY Does not Exist

LOCKER ROOM Does not Exist

MULTI-PURPOSE ROOM Does not Exist

SCIENCE DEMO ROOM Does not Exist

SCIENCE LAB Does not Exist

SCIENCE PREP ROOM Does not Exist

SHOWER ROOM Does not Exist

STAIRS/RAMPS: INTERIOR Does not Exist

TOILET ROOMS - STAFF Inspected

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s) Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Floor Finish Inspected

Condition 5 - Poor

Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES

Deficiency Location/Instance Room T2

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room T2

Violations No violations recorded.

Stalls Does not Exist

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

TOILET ROOMS - STUDENTS Inspected

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s) Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Floor Finish Inspected

Condition 3 - Fair

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q969

PB/A&W Print Date: 9/14/2020Page 9 of 10

Page 10: NYC Department of EducationAsset: AUX. SERV.- JAM. LEARN CT TR - Q, 162-02 HILLSIDE AVENUE, New York, 11432 Inspection Id Inspection Type Time In Last Edited SA : Q969 Architectural

Question Response

INTERIOR

TOILET ROOMS - STUDENTS

Floor Finish

Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES

Deficiency Location/Instance Room T1

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room T1

Violations No violations recorded.

Stalls Does not Exist

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

LIFE SAFETY Inspected

F.D. HOLDING AREA Does not Exist

STEEL STAIRS Does not Exist

SITE Not Required

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q969

PB/A&W Print Date: 9/14/2020Page 10 of 10