Asset: ACADEMY OF AMERICAN STUD HS AX - Q, 28-04 41ST AVENUE, New York, 11101
Inspection Id Inspection Type Time In Last Edited
SA : Q451 Architectural - Senior 2020-07-14 11:18 AM 2020-09-11 10:39 AM
AA : Q451 Architectural - Associate 2020-07-14 10:25 AM 2020-07-14 4:54 PM
Asset Data
Question Answer
Was the building fully accessible for inspection Yes
Principal(s) Information
Principal Name William Bassell
Organization Academy of American Studies High School - Annex - Queens
Did you meet with this Principal? No
Did this Principal provide feedback? Yes
Summary of Principal's Feedback A Principal questionnaire form was returned with no commentsregarding the physical conditions of the building.
Custodian Danial Danvers
Fireman Was not present
Building Square Footage 12000
Comments on the Area Entire Building Leased
Comments on the Stories (Floors) plus Basements 2+B
Comments on the Number of Classrooms 7
Comments on the Year Built 1935
Student Population 287
Staff Population 21
Weather Fair
Facade Photo
Corner of 41st Avenue and 28th Street -South view
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q451
PB/A&W Print Date: 9/13/2020Page 1 of 39
Main Entrance Photo
Facade A - 41st Avenue
Roof Photo
Roof 1 - Northeast view
Have any Systems/Major Building Components been upgraded? Yes
Systems: Vault Doors - replacement; Columns/Beams - repairs
Year: 2020
Systems: Exterior Walls, Windows - repairs
Year: 2017
Systems: Exterior Walls, Bulkhead Exterior Walls - repairs
Year: 2014
Systems: Coping, Roof Drains - replacement; Parapet, Roofing -repairs
Year: 2010
Systems: Exterior Guards, Windows - replacement
Year: 2008
Systems: Roofing - replacement
Year: 1985
Have there been any New Building Additions? No
Tandem Schools? No
Leased Space? Yes
Year Leased 1974
Inspection Full Inspection
Priority Condition
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q451
PB/A&W Print Date: 9/13/2020Page 2 of 39
PriorityCondition ExistLast Year?
PriorityCategory
ConditionDescription
ComponentAffected
LocationDescription
Person(s)Notified
Person(s) Title PhotoImage
Yes Potential FallingDebris
Deterioratedexterior concretewall is apotential fallingdebris hazard
EXTERIOR |EXTERIORWALLS
East corner ofthe 28th Streetfaçade at the2nd Floor level.
Daniel Danvers Custodian
Structural Engineer Required
StructuralCondition Type
ConditionDescription
ComponentAffected
LocationDescription
Person(s)Notified
Person(s) Title PhotoImage
No condition recorded
Accessibility
Accessibility Status Question Response
Is the primary or secondary entrance on an accessible route? No
Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem
FireAlarmStrobe
FUNCTIONAL ACCESSIBILITY
Exterior Routes
Exterior Entrances & Exits No Distance between opendoors < 4'
Exterior H/C Lifts No No
Exterior Ramps and Railings No Yes
Interior Routes
Corridor and Lobby H/C Lifts No No
Interior Corridor Doors and Hardware Yes Yes
Interior Corridors and Lobbies Yes
Interior Elevators No
Interior Lobby Doors and Hardware Yes
Interior Ramps No
Rooms & Spaces
Art Rooms No
Auditorium No
Cafeteria No
Classrooms None on Accessible Route Yes No Not on Accessible Route
Computer Rooms No
Gymnasium No
Library No
Main Office Room A101 Yes No Not on Accessible Route
Multi-purpose Room No
Nurse's Room No
Pool No
Science Lab No
Toilet Rooms (Boys) None on Accessible Route Yes No Not on Accessible Route
Toilet Rooms (Girls) None on Accessible Route Yes No Not on Accessible Route
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q451
PB/A&W Print Date: 9/13/2020Page 3 of 39
Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem
FireAlarmStrobe
Rooms & Spaces
Toilet Rooms (Staff) None on Accessible Route Yes No Not on Accessible Route
Building Template
Inspection
Question Response
Architectural
EXTERIOR Inspected
AREAWAY Does not Exist
AWNINGS AND CANOPIES Inspected
Condition 3 - Fair
Deficiency CONCRETE: MAJOR CRACKS/SPALLING
Roof Plan reference
Deficiency Quantity 15
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q451
PB/A&W Print Date: 9/13/2020Page 4 of 39
Question Response
EXTERIOR
AWNINGS AND CANOPIES
Deficiency Photo1
Facade A
Violations No violations recorded.
CHIMNEY Inspected
Material Type(s) Masonry
Condition 3 - Fair
Deficiency BRICK: MINOR CRACKS AND SPALLING
Roof Plan reference
Deficiency Quantity 40
Quantity Uom S.F.
Potential Action RESTITCH
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 1
Violations No violations recorded.
Deficiency BRICK: MAJOR / THRU CRACKS
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q451
PB/A&W Print Date: 9/13/2020Page 5 of 39
Question Response
EXTERIOR
CHIMNEY
Roof Plan reference
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REMOVE AND REBUILD
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 1
Violations No violations recorded.
COPING Inspected
Condition 2 - Between Good and Fair
Deficiency METAL: OPEN TRANSVERSE JOINTS WITH DAMAGEDCAULKING
Roof Plan reference
Deficiency Quantity 20
Quantity Uom L.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q451
PB/A&W Print Date: 9/13/2020Page 6 of 39
Question Response
EXTERIOR
COPING
Deficiency Photo1
Facade A
Violations No violations recorded.
CORNICE Inspected
Condition 2 - Between Good and Fair
Deficiency PRE-CAST CONCRETE: MINOR CRACKS, SPALLING
Roof Plan reference
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade D
Violations No violations recorded.
DOORS Inspected
DOORS AND FRAMES Inspected
Condition 5 - Poor
Deficiency METAL CLAD: DETERIORATED DOOR AND FRAME - MAJORDETERIORATION
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q451
PB/A&W Print Date: 9/13/2020Page 7 of 39
Question Response
EXTERIOR
DOORS
DOORS AND FRAMES
Roof Plan reference
Deficiency Quantity 3
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade A
Violations No violations recorded.
DOOR HARDWARE Inspected
Condition 3 - Fair
Deficiency No deficiencies recorded
LINTELS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
TRANSOM/SIDE LIGHT Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
EXTERIOR WALLS Inspected
Material Type(s) Masonry, Concrete
Replacement Quantity 8,000
Replacement Uom S.F.
InspectedInstance on All Facades
Instance Condition 5 - Poor
Instance Quantity 8,000
Instance Quantity Uom S.F.
Deficiency BRICK: OPEN JOINTS
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q451
PB/A&W Print Date: 9/13/2020Page 8 of 39
Question Response
EXTERIOR
EXTERIOR WALLS
Roof Plan reference
Elevation
Deficiency Quantity 1,000
Quantity Uom S.F.
Potential Action REPOINT
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade A
Violations No violations recorded.
Deficiency CAST IN PLACE / PRE-CAST CONCRETE: MAJORCRACKS/SPALLING
Roof Plan reference
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q451
PB/A&W Print Date: 9/13/2020Page 9 of 39
Question Response
EXTERIOR
EXTERIOR WALLS
Elevation
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 6
Deficiency Photo1
Facade D
Violations No violations recorded.
Deficiency BRICK: DETERIORATED MASONRY SILLS
Roof Plan reference
Elevation
Deficiency Quantity 30
Quantity Uom L.F.
Potential Action REMOVE AND REPLACE
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q451
PB/A&W Print Date: 9/13/2020Page 10 of 39
Question Response
EXTERIOR
EXTERIOR WALLS
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade B
Violations No violations recorded.
Deficiency CAST IN PLACE / PRE-CAST CONCRETE: MAJORCRACKS/SPALLING
Roof Plan reference
Elevation
Deficiency Quantity 40
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q451
PB/A&W Print Date: 9/13/2020Page 11 of 39
Question Response
EXTERIOR
EXTERIOR WALLS
Facade A
Violations No violations recorded.
Deficiency STUCCO CEMENT SURFACE: CRACKS, SPALLING
Roof Plan reference
Elevation
Deficiency Quantity 300
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade B
Violations No violations recorded.
Deficiency CAST IN PLACE / PRE-CAST CONCRETE: MINOR CRACKS,SPALLED, DETERIORATED REBAR
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q451
PB/A&W Print Date: 9/13/2020Page 12 of 39
Question Response
EXTERIOR
EXTERIOR WALLS
Roof Plan reference
Elevation
Deficiency Quantity 40
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade B
Violations No violations recorded.
Deficiency BRICK: OPEN JOINTS
Roof Plan reference
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q451
PB/A&W Print Date: 9/13/2020Page 13 of 39
Question Response
EXTERIOR
EXTERIOR WALLS
Elevation
Deficiency Quantity 400
Quantity Uom S.F.
Potential Action REPOINT
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade B
Violations No violations recorded.
Deficiency GLASS BLOCK: OPEN JOINTS
Roof Plan reference
Elevation
Deficiency Quantity 200
Quantity Uom S.F.
Potential Action REPOINT
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q451
PB/A&W Print Date: 9/13/2020Page 14 of 39
Question Response
EXTERIOR
EXTERIOR WALLS
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade A
Violations No violations recorded.
Deficiency GLASS BLOCK: RUSTED SUB-FRAME
Roof Plan reference
Elevation
Deficiency Quantity 200
Quantity Uom L.F.
Potential Action REPLACE-IN-KIND
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade B
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q451
PB/A&W Print Date: 9/13/2020Page 15 of 39
Question Response
EXTERIOR
EXTERIOR WALLS
Violations No violations recorded.
Deficiency GLASS BLOCK: CHIPPED/ BROKEN PIECES
Roof Plan reference
Elevation
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPLACE-IN-KIND
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade A
Violations No violations recorded.
Deficiency STUCCO CEMENT SURFACE: WATER INFILTRATION ININSTRUCTIONAL SPACE
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q451
PB/A&W Print Date: 9/13/2020Page 16 of 39
Question Response
EXTERIOR
EXTERIOR WALLS
Roof Plan reference
Elevation
Deficiency Quantity 200
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
Deficiency Photo1
Facade A - Room 20 shown, Facade B - 1st Floor Men's ToiletRoom similar
Violations No violations recorded.
Deficiency GLASS BLOCK: WATER INFILTRATION IN INSTRUCTIONALSPACE
Roof Plan reference
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q451
PB/A&W Print Date: 9/13/2020Page 17 of 39
Question Response
EXTERIOR
EXTERIOR WALLS
Elevation
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
Deficiency Photo1
Facade A - Stair A/2
Violations No violations recorded.
EXTERIOR SOFFITS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LOADING DOCK Does not Exist
LOUVER Inspected
Condition 3 - Fair
Deficiency BROKEN/ DENTED BLADES
Roof Plan reference
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q451
PB/A&W Print Date: 9/13/2020Page 18 of 39
Question Response
EXTERIOR
LOUVER
Elevation
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade D
Violations No violations recorded.
PARAPETS Inspected
Material Type(s) Masonry
Replacement Quantity 1,800
Replacement Uom C.F.
InspectedInstance on Roof 1
Instance Condition 5 - Poor
Instance Quantity 1,800
Instance Quantity Uom C.F.
Deficiency BRICK: OPEN JOINTS
Roof Plan reference
Deficiency Quantity 500
Quantity Uom S.F.
Potential Action REPOINT
Urgency of Action PRIORITY 3
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q451
PB/A&W Print Date: 9/13/2020Page 19 of 39
Question Response
EXTERIOR
PARAPETS
Purpose of Action LEVEL 2
Deficiency Photo1
Facade B
Violations No violations recorded.
Deficiency BRICK: MINOR CRACKS, SPALLING
Roof Plan reference
Deficiency Quantity 100
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 1 Facade B
Violations No violations recorded.
Deficiency BRICK: OUT OF PLUMB
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q451
PB/A&W Print Date: 9/13/2020Page 20 of 39
Question Response
EXTERIOR
PARAPETS
Roof Plan reference
Deficiency Quantity 500
Quantity Uom C.F.
Potential Action REMOVE AND REBUILD
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 1 Facade D
Violations No violations recorded.
PLAZA DECK Does not Exist
ROOF Inspected
Roofing Inspected
Replacement Quantity 5,000
Replacement Uom S.F.
ROOF HATCH/SMOKE HATCH Does not Exist
LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
ROOF BARRIER Does not Exist
ROOF CAGE Does not Exist
ROOF FENCE Does not Exist
ROOFING Inspected
InspectedInstance on Modified Bitumen: Roof 1
Instance Condition 3 - Fair
Instance Quantity 5,000
Instance Quantity Uom S.F.
Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?
No
Installation Year 1985
Source of Installation Custodial Staff
Deficiency MODIFIED BITUMEN: ROOFING: BEYOND USEFUL LIFE
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q451
PB/A&W Print Date: 9/13/2020Page 21 of 39
Question Response
EXTERIOR
ROOF
Roofing
ROOFING
Deficiency Location/Instance Modified Bitumen: Roof 1
Deficiency Quantity 5,000
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 1
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
ROOFING DRAINS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Specialties Inspected
BULKHEAD/PENTHOUSE Inspected
Condition 4 - Between Fair and Poor
Deficiency BULKHEAD/PENTHOUSE DOORS: DETERIORATED DOORAND FRAME
Roof Plan reference
Deficiency Quantity 1
Quantity Uom EACH
Potential Action REPLACE DOOR AND FRAME
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 1
Violations No violations recorded.
Deficiency BULKHEAD/PENTHOUSE DOORS: DETERIORATED LINTELS
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q451
PB/A&W Print Date: 9/13/2020Page 22 of 39
Question Response
EXTERIOR
ROOF
Specialties
BULKHEAD/PENTHOUSE
Roof Plan reference
Deficiency Quantity 10
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 1
Violations No violations recorded.
Deficiency BULKHEAD/PENTHOUSE WALLS/INTERIOR: BRICKCRACKS/SPALLING
Roof Plan reference
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q451
PB/A&W Print Date: 9/13/2020Page 23 of 39
Question Response
EXTERIOR
ROOF
Specialties
BULKHEAD/PENTHOUSE
Deficiency Photo1
Roof 1
Violations No violations recorded.
Deficiency BULKHEAD/PENTHOUSE CEILING: PLASTERDAMAGED/DETERIORATED
Roof Plan reference
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 1
Violations No violations recorded.
CUPOLA/ SPIRES/ TOWERS Does not Exist
DORMER Does not Exist
DUNNAGE STEEL Does not Exist
SKYLIGHT/ROOF VENT Does not Exist
ROOF/GRAVITY TANK Does not Exist
STAIRS/RAMPS: EXTERIOR Inspected
BUILDING CHEEK/FLANK WALLS Does not Exist
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q451
PB/A&W Print Date: 9/13/2020Page 24 of 39
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
RAILINGS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
STAIRS/RAMPS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
WINDOWS Inspected
Replacement Quantity 2,000
Replacement Uom S.F.
EXTERIOR GUARDS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LINTELS Inspected
Condition 4 - Between Fair and Poor
Deficiency STEEL: MAJOR RUSTING
Roof Plan reference
Elevation
Deficiency Quantity 400
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q451
PB/A&W Print Date: 9/13/2020Page 25 of 39
Question Response
EXTERIOR
WINDOWS
LINTELS Inspected
Facade D
Violations No violations recorded.
WINDOWS Inspected
Material Type(s) Aluminum
InspectedInstance on Aluminum - Double Hung: Facades A, B, D
Instance Condition 3 - Fair
Instance Quantity 2,000
Instance Quantity Uom S.F.
Installation Year 2008
Source of Installation Custodial Staff
Deficiency ALUMINUM - DOUBLE HUNG: INOPERABLE BALANCE
Roof Plan reference
Elevation
Deficiency Quantity 60
Quantity Uom EACH
Potential Action REPLACE BALANCES
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
INTERIOR Inspected
POOLS Does not Exist
STRUCTURAL Inspected
COLUMNS/BEAMS/BEARING WALLS Inspected
Condition 3 - Fair
Deficiency STEEL COLUMNS/BEAMS: MINOR RUSTING
Deficiency Location/Instance Basement
Deficiency Quantity 10
Quantity Uom S.F.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q451
PB/A&W Print Date: 9/13/2020Page 26 of 39
Question Response
INTERIOR
STRUCTURAL
COLUMNS/BEAMS/BEARING WALLS
Potential Action REPAIR AND REPAINT
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
Deficiency Photo1
Boiler Room
Violations No violations recorded.
Deficiency STEEL COLUMNS/BEAMS: DETERIORATED CONCRETEFIREPROOFING
Deficiency Location/Instance Basement
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
Deficiency Photo1
Boiler Room
Violations No violations recorded.
FLOOR STRUCTURE Inspected
Condition 3 - Fair
Deficiency CONCRETE: CRACKS/SPALLED/REINFORCEMENT EXPOSED
Deficiency Location/Instance Basement
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q451
PB/A&W Print Date: 9/13/2020Page 27 of 39
Question Response
INTERIOR
STRUCTURAL
FLOOR STRUCTURE
Deficiency Photo1
Boiler Room
Violations No violations recorded.
Deficiency CONCRETE SLAB ON GRADE: MINOR CRACKS
Deficiency Location/Instance Basement
Deficiency Quantity 100
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
Deficiency Photo1
Boiler Room
Violations No violations recorded.
FOUNDATION WALLS Inspected
Material Type(s) Concrete
Condition 2 - Between Good and Fair
Deficiency CONCRETE: CRACKED/SPALLED/REINFORCEMENTEXPOSED
Deficiency Location/Instance Basement
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q451
PB/A&W Print Date: 9/13/2020Page 28 of 39
Question Response
INTERIOR
STRUCTURAL
FOUNDATION WALLS Inspected
Deficiency Photo1
Boiler Room
Violations No violations recorded.
ROOF STRUCTURE Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
VAULTS-BUNKERS Inspected
Foundation Walls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Slab Structure Inspected
Condition 3 - Fair
Deficiency METAL DECK AND CONCRETE: DETERIORATED
Deficiency Location/Instance Basement
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 5
Deficiency Photo1
Boiler Room
Violations No violations recorded.
Vault/Ash Hoist Doors and Framing Inspected
Condition 3 - Fair
Deficiency MINOR RUSTING
Deficiency Location/Instance Basement Storage Room egress doors
Deficiency Quantity 2
Quantity Uom EACH
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q451
PB/A&W Print Date: 9/13/2020Page 29 of 39
Question Response
INTERIOR
STRUCTURAL
VAULTS-BUNKERS
Vault/Ash Hoist Doors and Framing
Deficiency Photo1
Facade D
Violations No violations recorded.
AUDITORIUM Does not Exist
CAFETERIA Does not Exist
CLASSROOMS/CORRIDORS/ADMIN SPACES Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency ACOUSTIC TILES: DAMAGED/MISSING - ACTIVE LEAK
Deficiency Location/Instance Room 20
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
Deficiency Photo1
Room 20
Violations No violations recorded.
Deficiency ACOUSTIC TILES: DAMAGED/MISSING
Deficiency Location/Instance Rooms 12, 14, 21, 22, Corridor near Stair B/1, and others
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q451
PB/A&W Print Date: 9/13/2020Page 30 of 39
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Ceiling
Deficiency Photo1
Room 12
Violations No violations recorded.
Door(s) Inspected
Condition 5 - Poor
Deficiency WOOD: DETERIORATED DOOR AND FRAME
Deficiency Location/Instance Room 11B
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 11B
Violations No violations recorded.
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance Main Entrance Vestibule, Rooms 11A, A101, 14, 15, 23, and others
Deficiency Quantity 9
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q451
PB/A&W Print Date: 9/13/2020Page 31 of 39
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Door(s) Inspected
Room 14
Violations No violations recorded.
Floor Finish Inspected
Condition 2 - Between Good and Fair
Deficiency VINYL TILES: DETERIORATED SUBSTRATE
Deficiency Location/Instance Corridor near Room 11B
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Corridor near Room 11B
Violations No violations recorded.
Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES
Deficiency Location/Instance Main Entrance Lobby
Deficiency Quantity 15
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Main Entrance Lobby
Violations No violations recorded.
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency PLASTER: CRACKS/SPALLING - ACTIVE LEAK
Deficiency Location/Instance Room 20
Deficiency Quantity 40
Quantity Uom S.F.
Potential Action REPLACE
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q451
PB/A&W Print Date: 9/13/2020Page 32 of 39
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Walls
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
Deficiency Photo1
Room 20
Violations No violations recorded.
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Rooms 14, 22
Deficiency Quantity 70
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 14
Violations No violations recorded.
Specialties Does not Exist
GYMNASIUM Does not Exist
INTERIOR DOOR HARDWARE Inspected
Condition 3 - Fair
Deficiency No deficiencies recorded
INTERIOR GUARDS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
KITCHEN Does not Exist
LIBRARY Does not Exist
LOCKER ROOM Does not Exist
MULTI-PURPOSE ROOM Does not Exist
SCIENCE DEMO ROOM Does not Exist
SCIENCE LAB Does not Exist
SCIENCE PREP ROOM Does not Exist
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q451
PB/A&W Print Date: 9/13/2020Page 33 of 39
Question Response
INTERIOR
SHOWER ROOM Does not Exist
STAIRS/RAMPS: INTERIOR Inspected
Do Letter Stair Signs Exist? No
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s) Inspected
Condition 5 - Poor
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance Stair A/2
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stair A/2
Violations No violations recorded.
Partition Does not Exist
Railings Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stairs and Landings Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Stair A/2
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q451
PB/A&W Print Date: 9/13/2020Page 34 of 39
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Walls
Deficiency Photo1
Stair A/2
Violations No violations recorded.
TOILET ROOMS - STAFF Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s) Inspected
Condition 5 - Poor
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance 2nd Floor Women’s Toilet Room
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
2nd Floor Women’s Toilet Room
Violations No violations recorded.
Floor Finish Inspected
Condition 5 - Poor
Deficiency VINYL TILES: DETERIORATED SUBSTRATE
Deficiency Location/Instance 1st Floor Men’s Toilet Room
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q451
PB/A&W Print Date: 9/13/2020Page 35 of 39
Question Response
INTERIOR
TOILET ROOMS - STAFF
Floor Finish
Deficiency Photo1
1st Floor Men’s Toilet Room
Violations No violations recorded.
Deficiency CERAMIC TILE: BROKEN/MISSING TILES
Deficiency Location/Instance 2nd Floor Women’s Toilet Room
Deficiency Quantity 40
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
2nd Floor Women’s Toilet Room
Violations No violations recorded.
Stalls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Walls Inspected
Condition 3 - Fair
Deficiency PLASTER: CRACKS/SPALLING - ACTIVE LEAK
Deficiency Location/Instance 1st Floor Men’s Toilet Room
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q451
PB/A&W Print Date: 9/13/2020Page 36 of 39
Question Response
INTERIOR
TOILET ROOMS - STAFF
Walls
Deficiency Photo1
1st Floor Men’s Toilet Room
Violations No violations recorded.
TOILET ROOMS - STUDENTS Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s) Inspected
Condition 5 - Poor
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance 1st Floor Boys Toilet Room, Girls Toilet Room
Deficiency Quantity 2
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
1st Floor Girls Toilet Room
Violations No violations recorded.
Floor Finish Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stalls Inspected
Condition 5 - Poor
Deficiency RUST - MAJOR
Deficiency Location/Instance 1st Floor Boys Toilet Room
Deficiency Quantity 1
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q451
PB/A&W Print Date: 9/13/2020Page 37 of 39
Question Response
INTERIOR
TOILET ROOMS - STUDENTS
Stalls
Deficiency Photo1
1st Floor Boys Toilet Room
Violations No violations recorded.
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LIFE SAFETY Inspected
F.D. HOLDING AREA Does not Exist
STEEL STAIRS Does not Exist
SITE Inspected
CONTAINERIZATION Does not Exist
Drainage System for Asphalt Does not Exist
Drainage System for Concrete Does not Exist
Drainage System for Soil Does not Exist
DRINKING FOUNTAINS Does not Exist
FENCES Does not Exist
IRRIGATION SYSTEM Does not Exist
PAVING Inspected
Student Non-Use Does not Exist
Student Use Does not Exist
Site Sidewalks & Walkways Does not Exist
DOT Sidewalk Inspected
Asphalt Does not Exist
Concrete Inspected
Condition 3 - Fair
Deficiency DAMAGED CURBS
Deficiency Location/Instance 28th Street, 41st Avenue
Deficiency Quantity 50
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q451
PB/A&W Print Date: 9/13/2020Page 38 of 39
Question Response
SITE
PAVING
DOT Sidewalk
Concrete
Deficiency Photo1
41st Avenue
Violations No violations recorded.
Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS
Deficiency Location/Instance 28th Street, 41st Avenue
Deficiency Quantity 425
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
41st Avenue
Violations No violations recorded.
Pavers Does not Exist
PLAYGROUNDS Does not Exist
PLAYING SURFACE Does not Exist
RETAINING WALLS Does not Exist
SEATING Does not Exist
SITE WALLS (NOT RETAINING WALLS) Does not Exist
STAIRS/RAMPS: EXTERIOR Does not Exist
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q451
PB/A&W Print Date: 9/13/2020Page 39 of 39