nwfall08 quiz85 grounding
TRANSCRIPT
-
8/3/2019 NWfall08 Quiz85 Grounding
1/1
www.netaworld.org Fall 2008 NETA WORLD
by Jim WhiteShermco Industries
Grounding
1.AccordingtoANSI/NEAMS-07,howotenshouldgroundsystemsbeelectricallytested?a.Onceayear c.Onceeverythreeyearsb.Onceeverytwoyears d.Onlyeveryouryears
2.Temaximumgroundresistanceoanindustrialacilityshouldbea.1ohm c.4ohmsb.2ohms d.5ohms
3.Temaximumgroundresistanceoageneratingstationshouldbea.1ohm c.4ohmsb.2ohms d.5ohms
4.WhatIEEEstandardisusedasareerenceorall-o-potentialtesting?
a.Standard71 c.Standard99b.Standard81 d.Stanardd101
5. Foragroundsystemwithairlyuniormsoiland testelectrodesdrivenatsucientspacingrelativetothesizeothatgroundsystem,whatdistanceromthetestedelectrodeshouldthepotentialelectrodebeplacedtomeasurethetheoreticallycorrectgroundresistancewhenperormingaall-o-potentialtest?a.20eetb.100eetc.62percentothedistancebetweenthecurrentelec -trodeandthetestedelectrode
d.57.7percentothedistancebetweenthecurrentelec-trodeandthetestedelectrode
Answers
1.Withaveragereliabilityandaveragecondition,thetableinAppendixBindicatesatestintervalo24months.Tistimerecommendationchangesaccordingtocriticalityandcondition.
2.Section7.13givesamaximumo5ohmsoranindustrialacility.Ingrounding,though,thelowerthebetter.
3.Section7.13shows1ohmmaximumorgeneratingandtransmissionacilities.4.TeANSI/IEEEStandard81,IEEEGuideorMeasuring
EarthResistivity,GroundImpedance,andEarthSuracePotentialsoaGroundSystemisthereerence.
5.Ithesoilisairlyhomogeneousincontent,thedistancethevoltageelectrode,P2,isdrivenisusually62percent.Otenthatmaynotprovidethetrueresistance,though.TebestprocedureistodriveP2inseverallocations,inlinewiththetestedelectrode,C1,andthetestcurrentelectrode,C2.ObtaintestdataorP2positionsbeginningabout50percentothedistanceromC1toC2untilabout70percentothatdistance.PlottheresultingearthresistancesrelativetotheP2distanceromC1.Wheretheplottedvalueslevelofisthetrueearth
resistance.Itheplottedvaluesdonotlevelof,thatindicatesmoredistanceisneededbetweenC1andC2andthetestsneedtoberunagain.
JimWhiteistherainingDirectororShermcoIndustriesandtheprincipalShermcorepresentativeontheNFPA70BCommittee.Jim
isthealternateNEArepresentativeontheNFPA70ECommitteeandservesastheNEArepresentativeontheIEEE/NFPAArc-FlashHazardWorkGroup(RPC)AdHocCommittee.HeservedastheChairmanothe 2008 IEEEElectricalSaetyWorkshop. Jimis aNEACertifedLevelIVElectricalestingechnicianandamemberotheNEASaetyCommittee.