    Grounding

    1.AccordingtoANSI/NEAMS-07,howotenshouldgroundsystemsbeelectricallytested?a.Onceayear c.Onceeverythreeyearsb.Onceeverytwoyears d.Onlyeveryouryears

    2.Temaximumgroundresistanceoanindustrialacilityshouldbea.1ohm c.4ohmsb.2ohms d.5ohms

    3.Temaximumgroundresistanceoageneratingstationshouldbea.1ohm c.4ohmsb.2ohms d.5ohms

    4.WhatIEEEstandardisusedasareerenceorall-o-potentialtesting?

    a.Standard71 c.Standard99b.Standard81 d.Stanardd101

    5. Foragroundsystemwithairlyuniormsoiland testelectrodesdrivenatsucientspacingrelativetothesizeothatgroundsystem,whatdistanceromthetestedelectrodeshouldthepotentialelectrodebeplacedtomeasurethetheoreticallycorrectgroundresistancewhenperormingaall-o-potentialtest?a.20eetb.100eetc.62percentothedistancebetweenthecurrentelec -trodeandthetestedelectrode

    d.57.7percentothedistancebetweenthecurrentelec-trodeandthetestedelectrode

    Answers

    1.Withaveragereliabilityandaveragecondition,thetableinAppendixBindicatesatestintervalo24months.Tistimerecommendationchangesaccordingtocriticalityandcondition.

    2.Section7.13givesamaximumo5ohmsoranindustrialacility.Ingrounding,though,thelowerthebetter.

    3.Section7.13shows1ohmmaximumorgeneratingandtransmissionacilities.4.TeANSI/IEEEStandard81,IEEEGuideorMeasuring

    EarthResistivity,GroundImpedance,andEarthSuracePotentialsoaGroundSystemisthereerence.

    5.Ithesoilisairlyhomogeneousincontent,thedistancethevoltageelectrode,P2,isdrivenisusually62percent.Otenthatmaynotprovidethetrueresistance,though.TebestprocedureistodriveP2inseverallocations,inlinewiththetestedelectrode,C1,andthetestcurrentelectrode,C2.ObtaintestdataorP2positionsbeginningabout50percentothedistanceromC1toC2untilabout70percentothatdistance.PlottheresultingearthresistancesrelativetotheP2distanceromC1.Wheretheplottedvalueslevelofisthetrueearth

    resistance.Itheplottedvaluesdonotlevelof,thatindicatesmoredistanceisneededbetweenC1andC2andthetestsneedtoberunagain.

    JimWhiteistherainingDirectororShermcoIndustriesandtheprincipalShermcorepresentativeontheNFPA70BCommittee.Jim

    isthealternateNEArepresentativeontheNFPA70ECommitteeandservesastheNEArepresentativeontheIEEE/NFPAArc-FlashHazardWorkGroup(RPC)AdHocCommittee.HeservedastheChairmanothe 2008 IEEEElectricalSaetyWorkshop. Jimis aNEACertifedLevelIVElectricalestingechnicianandamemberotheNEASaetyCommittee.