Revolution in Water Treatment…
A Fit & Forget System
NTPC NETRA's Conference on R&D for Energy Sustainability
Presentation on Non-chemical Technology for High COC Operation with Scale
Inhibition for achieving “ZLD” 31st March 2016
NETRA
SCALE-BANTM A Sustainable solution
for Zero Liquid Discharge (ZLD)
A Fit & Forget System…
Continuously improving the possibilities to Innovate the conservation of natural resources….
A Non Chemical Water Treatment…
Revolution in Water Treatment…
A Fit & Forget System
A FACT
Only 0.007% of total water available on earth is potable which is being shared by all types of
Industries, Agriculture & House holds.
Revolution in Water Treatment…
A Fit & Forget System
Vision
To provide a Self Sustainable, Efficient and Cost Effective Zero Liquid Discharge
(ZLD) solution for Industries.
Revolution in Water Treatment…
A Fit & Forget System
Optimizing Generation through Scale free operations
Maximizing Water Conservation
A Sustainable Zero Liquid Discharge (ZLD) Solution
MISSION
Revolution in Water Treatment…
A Fit & Forget System
SCALE-BANTM equipment has been developed by years of
hard researches & trials and in commercial production since
1999. The technology is proven and well tested. The
references of its successful running in more than 200
industries and applications have been established.
“SCALE-BANTM is an online non chemical static mechanical
equipment which reduces 30% to 40% water consumption in
thermal power plants besides total prevention of hard water
scale in condensers/heat exchangers in cooling water
services.”
Genesis
Revolution in Water Treatment…
A Fit & Forget System
Impacts of scaling:
Loss of Vacuum/Generation & Increased steam consumption
Increased water consumption and water pollution
Problems & Concerns
SCALING IN CONDENSER/HEAT EXCHANGER
To meet above guidelines, conventional systems like RO & Multi Effect Evaporator (MEE) are very costly to install & operate. RO & MEE operations are cumbersome.
Zero Liquid Discharge (ZLD) & Specific Water Consumption in Thermal Power Plants as per New Gazette Notification (7th Dec. 2015) issued by Government of India-MOEF to be mandatorily achieved
Revolution in Water Treatment…
A Fit & Forget System
“Scale of even 0.5 mm causes an energy loss of 7%”
Impact of Scale in Heat Exchangers
11 27 48 90
0.3
0.71
4.7
9.5
4
Efficiency Loss in %
Revolution in Water Treatment…
A Fit & Forget System
RO & MEE
Chemical Treatment
Online Ball Cleaning System
Softener Plant
Conventional SCALE-BAN
Non-Chemical Static Mechanical Equipment
Available methods for ZLD & Scale Prevention
Restricted level of hardness (300ppm) and TDS (1500ppm) in cooling water causing Heavy Blow Down from cooling tower.
Blow down water can be consumed only after treatment through
RO followed by MEE.
Recurring Expenses on RO+MEE operations, Online Ball Cleaning System, anti-scalant chemical dosing & softener operation in cooling tower.
No guarantee for zero scale (Generation losses).
Frequent de-scaling of condenser/heat exchanger.
Limitations of Conventional Systems for achieving ZLD & Scale free Operations
Cooling tower can be operated at very high hardness (10000ppm) and TDS (50000ppm), Unbelievable COC level of 15 to 20 already achieved.
Reduction in blow down by more than 80% to 90% (ZLD achieved with zero recurring expenses).
Elimination of RO+MEE system for achieving ZLD.
Complete elimination of Online Ball Cleaning System, Softener & anti-scaling chemical.
Zero scale is guaranteed for 20 years.
De-scaling of Condensers/heat exchangers is not required.
Operations with SCALEBAN
Working Principle of
SCALE-BANTM “Innovation
evolved from problem”
SOLUBILITY CHARACTERISTICS OF WATER S O
L U
B I
L I
T Y
Temperature
S1
S2
T1 T2
Ca++
Mg++
Relationship of pH & Solubility of Ca2+ and Mg2+in Liquid
Relationship of Temperature & Solubility of Ca2+ and Mg2+ in Liquid
S O
L U
B I
L I
T Y
pH Value
S1
S2
P1 P2
Ca++
Mg++
SCALEBAN
IN HEAT
EXCHANGER IN SCALEBAN
GALVANIC PRINCIPLE
Revolution in Water Treatment…
A Fit & Forget System
Working process of SCALE-BANTM
Revolution in Water Treatment…
A Fit & Forget System
VIDEO ON SCALEBAN AT NTPC DADRI
Revolution in Water Treatment…
A Fit & Forget System
SCALE-BAN Installation In a Power Plant
Revolution in Water Treatment…
A Fit & Forget System
DESIGN OF A SELF SUSTAINABLE, EFFICIENT AND COST EFFECTIVE ZERO LIQUID
DISCHARGE MODEL
ZERO LIQUID DISCHARGE (ZLD) WITHOUT SCALEBAN
COOLING TOWER --------------------------------
-------------------------------------------------------------
CONDENSER/ COOLERS
CONDENSER/ COOLERS
Make up water CLARIFIED WATER
EFFLUENT TREATMENT PLANT
CT Blow Down water
RO PLANT
COOLING TOWER/PROCESS
APPLICATIONS
RO PERMEATE
ETP TREATED WATER
MULTI EFFECT EVAPORATOR
(MEE)
2-3 COC
ZERO LIQUID DISCHARGE (ZLD) WITH SCALEBAN
COOLING TOWER ----------------------------------------------------------------
-----------------------------
CONDENSER/ COOLERS
CONDENSER/ COOLERS
Make up water CLARIFIED WATER
EFFLUENT TREATMENT PLANT
RO PLANT
COOLING TOWER/PROCESS
APPLICATIONS
RO PERMEATE
ETP TREATED WATER
MULTI EFFECT EVAPORATOR
Negligible Blow Down due to high COC. Hence can be directly taken
for ash handling/ coal handling
15-20 COC
COOLING TOWER ---------------------------------------------------------------------------------------------
CONDENSER/ COOLERS
CONDENSER/ COOLERS
SCALEBAN
SCALEBAN
Make up water
FINAL SCHEME WITH SCALEBAN FOR ACHIEVING ZERO LIQUID DISCHARGE (ZLD)
Negligible Blow Down due to high COC. Hence can be directly taken for ash
handling/coal handling
CLARIFIED WATER
15-20 COC
Revolution in Water Treatment…
A Fit & Forget System
SCALEBAN V/S CONVENTIONAL SYSTEM FOR ZLD AND SCALE PREVENTION
SCALEBAN SOLUTION CONVENTIONAL SYSTEM
It can handle very high hardness (10,000 PPM) & very high TDS (50,000 PPM).
Restricted low level of hardness (300 PPM) & TDS (1500 PPM).
No effect of seasonal or annual variation of water quality.
Chemical treatment and RO are water quality dependent.
Life time zero recurring cost for operation and maintenance.
Daily recurring expenses, Heavy opex for MEE & life of RO Membrane maximum 3 years.
Zero Scale Guarantee in Condensers. No Guarantee of Zero Scale.
Better life of Condenser Tubes. Acid and High Pressure jet cleaning shorten the life of tubes.
Additional Plant availability of 10-15 days enhancing PLF by 3% to 4%.
Downtime required for condenser/heat exchanger de-scaling.
Minimum 1% steam saving as condenser vacuum maintained at higher side.
Vacuum deteriorate over time leading to plant shutdown.
No land space for installation. Large shed required for RO & MEE Plant.
No power Consumption. Minimum 2 MWH power consumption.
ROI Maximum 2 years. Only Expenses, No ROI
No need of EVAPORATORS for achieving ZLD EVAPORATORS are required for achieving ZLD
Revolution in Water Treatment…
A Fit & Forget System
• pH value of re-circulating water should be maintained
between 7.0 to 8.5
Working Parameters of SCALE-BANTM
Revolution in Water Treatment…
A Fit & Forget System
Started as a concept in late 90’s - Now a proven technology and continuously proving the potential as the most efficient, cost effective & sustainable solution for Zero Liquid Discharge (ZLD) with Zero Scaling.
Year 2000: SEP
200 Plus Satisfied Clients
Year 2014: NTPC 1000MW power plant
Revolution in Water Treatment…
A Fit & Forget System
SCALEBAN CASE STUDY AT NTPC, DADRI 2X490MW TPP
Revolution in Water Treatment…
A Fit & Forget System
The ground work for the implementation of Scaleban at NTPC power plants started in 2012 by approaching to the then RED Mr. A. K. Jha (Director Technical), who advised to demonstrate Scaleban technology to NETRA.
BACKGROUND
Revolution in Water Treatment…
A Fit & Forget System
Presentation made to NETRA in May 2012 followed by NETRA’s visit to 3X130MW CPP of Bhushan Power and Steel ltd. Sambalpur (Orissa) to study Scaleban performance.
After satisfactory visit to BPSL Sambalpur, NTPC formed a team consisting of members from NETRA, OS & Dadri station.
Introducing Scaleban
Revolution in Water Treatment…
A Fit & Forget System
NTPC Dadri issued work order to Scaleban in November 2013.
Scaleban was commissioned in April 2014 on all the heat exchangers of Unit -5 and on Unit-6 in May 2015.
Project Implementation
Revolution in Water Treatment…
A Fit & Forget System
2X490MW NTPC, DADRI TPP
SCALEBAN INSTALLATION IN 490MW POWER PLANT CONDENSER (NTPC DADRI)
Revolution in Water Treatment…
A Fit & Forget System
“Scaleban offered all the equipment for unit-5 and unit-6 free of cost as a salute to our
Nation”
Revolution in Water Treatment…
A Fit & Forget System
From October 2014 Plant COC started increasing from average 2.5 to average 6 till December 2014 and passed bore well water circulation test.
Performance comparison was carried out by opening a Plate heat exchanger (PHE -5b) of Unit-5 which is fitted with Scaleban and a PHE of Unit-6 which was then operating without Scaleban.
Performance Evaluation
No scale
UNIT 5 PHE PLATE - After Scaleban
UNIT 6 PHE PLATE – Without Scaleban
Very hard Scale
Revolution in Water Treatment…
A Fit & Forget System
Impressed with the 10 months of performance, NTPC Dadri showcased the Scaleban Technology at their annual O&M conference during 13th to 15th February, 2015 and had presented a paper.
Revolution in Water Treatment…
A Fit & Forget System
NTPC DADRI STALL AT NTPC O&M CONFERENCE 13th-15th FEBRUARY 2015
Revolution in Water Treatment…
A Fit & Forget System
One pass of Unit 5 condenser opened on July 22, 2015 and found Scale free after
15 months.
Unit 5 condenser tube condition before installation of Scaleban
Revolution in Water Treatment…
A Fit & Forget System
1. Average 8 COC to be maintained during the month of December 2015 .
2. pH to be maintained beyond 8.3 during the entire month.
3. Vacuum loss due to dirty tube was recorded as 14.52 mm Hg on 28.11.2015.
4. The Criteria for success of Scaleban performance is if vacuum loss due to dirty tube remains within 3 mm of Hg.
Final Performance Test Parameters
Revolution in Water Treatment…
A Fit & Forget System
PHE 5b Opened for physical inspection
Before Concluding on 30.12.2015
Revolution in Water Treatment…
A Fit & Forget System
1. With Installation of Scaleban no scale has been observed during the complete test.
2. Calculated water saving of 31.44%, anti-scaling chemical saving of 100% and considerable reduction in sulfuric acid consumption and pumping power.
3. NTPC Dadri shall further increase COC to 10 in next 3 months for achieving ZLD.
SCALEBAN PERFORMANCE RESULTS
Revolution in Water Treatment…
A Fit & Forget System
In line with the environment (protection) amendment rule 2015 and the goal of National Water Mission for “Increasing water use efficiency by 20%” in existing and upcoming Power Plants, SCALE-BAN™ EQUIPMENT is the only technology available on self sustainable basis for achieving Zero Liquid Discharge along with ensuring Zero Scaling in Condensers/Heat Exchangers with lucrative ROI without any recurring cost.
With Scaleban, the cost of water can be reduced up to 40%, associated water treatment cost, electricity cost will be reduced & saving on chemical consumption. Scaleban is environmentally sustainable & helps achieving NATIONAL GOALS OF WATER CONSERVATION.
Conclusion
Revolution in Water Treatment…
A Fit & Forget System
BHUSHAN POWER & STEEL LTD., Sambalpur (Orissa)
Power Plant : P.O.Date : 01 May 2011 1. 130MW X 3 Nos. 2. 60MW X 1 No. 3. 40MW X 1 No. 4. 8MW X 2Nos.
CSP Plant : P.O.Date : 01 May 2011
Oxygen Plant : P.O. Date : 01 May 2011
Revolution in Water Treatment…
A Fit & Forget System
Bengal Energy Ltd., Kharagpur (WB) 40MW CPP (Installation in March 2014)
Condenser tubes at 15 COC
Revolution in Water Treatment…
A Fit & Forget System
Thank You!