1 Hour Floor Ceiling Assembly: Existing 32" wood and steel bar joist truss with top andbottom cords constructed from 3" x 1.875'~laminated Douglas Fir. 2"x4" wood blocking, onelayer of 0.75" plywood and 1.5" of light weight concrete .
..,_ ...... ...-r--~-~"""¥'-~......-~ _,..•• ./ 1128 LIGHTWEIGHT CONCRETE
~~~t::ZZz:Zz~Ztz;;!Z!:t:Zz~2;2~:t2I. _-XN PLYWOOD SUB FLOOR
-- 2" x 4" WOOD BLOCKING
3" X 1.875"LAMINATED DOUGLAS FIR
~t---3· X1.875-LAMINATED DOUGLAS FIR
To achieve 1 hour fire rating for the above floor ceiling assembly:Apply 30 ml dry thickness of FireGuard E-84® Intumescent Coating to all exposed plywood deckingand 45 ml dry thickness of FireGuard E-84® Intumescent Coating to all exposed wood blocking andexposed steel bar joist truss.
STEEL BAR JOIST TRUSS
112" LIGHTWEIGHT CONCRETE
~~~~ZZZ~%22~~~pZ~~:~· ~::::::=-~n~t:~~~I~~~~~~O~FFIRE GUARD E-84®INTUMESCENT COATING2" x 4" WOOD BLOCKING38 X 1.875"LAMINATED DOUGLAS FIR
..... - ........ - STEEL BAR JOIST TRUSS----+-- 45 ML DRY THICKNESS OFFIRE GUARO E-84®INTUMESCENT COATING3" X 1.875·LAMINATED DOUGLAS FIR
STANDARD TESTED TO:
FIRST TEST ENDURANCE RATING: 1 HOUR
ASTM E-119-10B, UL 263. NFPA 251.ULC-S-1 Building Construction andMaterials
FIRE TESTED LABORATORY: GUARDIAN FIRE TESTINGLABORATORIES, INC.480 Hinman Ave.Buffalo, NY 14216
REPORT TO: GL 58812 Rev & GL 115411, EER-38193
PRODUCT: FireGuard E-84® Intumescent Coating
MANUFACTURER: SHIELD INDUSTRIES, INC.131 SmokehiIJ LaneWoodstock GA 30188
*SEE MANUFACTURER APPLICATION INSTRUCTIONS AND SPECIFICATIONSFOR SURFACE PREPARATION AND APPLICATION PROCESS