I-E96-610AAPPENDIX A - NTCL01 TERMINATION UNIT CONFIGURATION
INTRODUCTION
The INNIS01 Network Interface Slave Module (NIS) can use theNTCL01 Communication Termination Unit (TCL) for termina-tion. Jumpers on the TCL unit select the type of cable used toconnect the NIS module to an INFI-NET system. Refer to theNTCL01 instruction for complete information. Figure A-1shows the location of jumpers and connectors. Figures A-2 andA-3 show the coaxial and twinaxial cable connections. TableA-1 lists the jumper settings used on TCL unit circuit boardrevision levels D and E. Table A-2 lists the jumper settingsused on TCL unit circuit board revision levels F or higher.
Figure A-1. NTCL01 Connector and JumperLocations (Revision F or Greater)
NTCL01 TB2 TB1J1
J2
J4
J3
J10 J6J9
F1
P1
E2
COMM
E1
+24 V
J5J8 J7
LOOP 2 LOOP 1
1 1IN+ IN+
2 2IN IN
7 7SHLD SHLD
6 6OUT OUT
5 5OUT+ OUT+
4 4NC NC
3 3SHLD SHLD
8 8PSS2 PSS1
3
12
3
12
3
12
3
12
3
12
3
12
CHASSIS GROUND T00205AINTRODUCTION A - 1
-
NTCL01 TERMINATION UNIT CONFIGURATION
TP85180D
NKCL01NKCL11
T00384A
NKPL01NKPL02
IN FROMLOOPFigure A-2. NTCL01 Coaxial Cable Connections to INNIS01 Modules
Figure A-3. NTCL01 Twinaxial Cable Connections to INNIS01 Modules
NKTL01-3
NTCL01
8 7 6 5 4 3 2 1
8 7 6 5 4 3 2 1TB1
TB2
LOOP2
LOOP1
P1
NTCL01
8 7 6 5 4 3 2 1
8 7 6 5 4 3 2 1TB1
TB2
LOOP2
LOOP1
P1
NTCL01
8 7 6 5 4 3 2 1
8 7 6 5 4 3 2 1TB1
TB2
LOOP2
LOOP1J2
J2
J2
J1
J1
J1
E2
E1
P1
COM
+24 V
E2
E1
COM
+24 V
E2
E1
COM
+24 V
IN FROM LOOP
NKTL01-3
TO OTHER NODES
J3J4
J3J4
J3J4
P3
P1
P2
INNIS01
P3
P1
P2
INNIS01
NKLS01NKLS11
NKLS01NKLS11
NKTT01NKTT11
P3
P1
P2
NTCL01
8 7 6 5 4 3 2 1
8 7 6 5 4 3 2 1TB1
TB2
LOOP2
LOOP1
NTCL01
8 7 6 5 4 3 2 1
8 7 6 5 4 3 2 1TB1
TB2
LOOP2
LOOP1
IN
IN
SH
SHP1
P1
INNIS01
COME2
E1 +24V
COME2
E1 +24V
P3
P1
P2
INNIS01
OUT TOOTHER NODES
J3J4
J3J4
J2
J2
J1
J1
NKLS01NKLS11
NKLS01NKLS11INTRODUCTIONA - 2 I-E96-610A
-
NTCL01 TERMINATION UNIT CONFIGURATION
I-E96-610ATable A-1. NTCL01 Jumper Settings for Revision D and E
Jumper Number Twinaxial Cable Jumper SettingsCoaxial Cable Jumper
SettingsJ5 - J12 2 - 3 2 - 3
J13 - J18 1 - 2 2 - 3
Table A-2. NTCL01 Jumper Settings for Revision F or Greater
Jumper Number Twinaxial Cable Jumper SettingsCoaxial Cable Jumper
SettingsJ5 - J10 1 - 2 2 - 3INTRODUCTION A - 3
-
Document SummaryAPPENDIX A - NTCL01 TERMINATION UNIT CONFIGURATIONINTRODUCTIONFiguresA-1. NTCL01 Connector and Jumper Locations (Revision F or Greater)A-2. NTCL01 Coaxial Cable Connections to INNIS01 ModulesA-3. NTCL01 Twinaxial Cable Connections to INNIS01 Modules
TablesA-1. NTCL01 Jumper Settings for Revision D and EA-2. NTCL01 Jumper Settings for Revision F or Greater