Aermec adheres to the EUROVENT Certification programme up to 600kW cooling. The products concerned appear in the EUROVENT Certified products guide. NRL R410A • Available in 9 sizes • Refrigerant R410A • 2 refrigerant circuits • High efficiency even at part load • Heat exchangers optimised to benefit from the excellent heat transfer characteristics of R410A • High efficiency scroll compressors • Axial fans with low sound level • Solid construction with polyester anti-corro- sion painted finish • Extended operating limits in heat pump oper- ation: - Maximum leaving water temperature 55° C - Maximum external air temperature 30° C (42° C with fan speed controller accessory DCPX) • Operating limits extended operation in heat pump. Version H ° - HL - Max water at 50 ° C produced - Max air temperature 30 ° C (42 ° C with acces- sory DCPX fan speed controller) Version. HA - HE - Max water at 55 ° C produced - Max air temperature 30 ° C (42 ° C with acces- sory DCPX fan speed controller) • Cooling mode Version. H ° - HL - Max 18 ° C water produced - Max air temperature 42 ° C Version. HA - HE - Max 18 ° C water produced - Max air temperature 46 ° C • Expansion valve (selected in unit configura- tor): - “°” standard thermostatic expansion valve - “X” electronic expansion valve, also for low fluid temperature (down to -6 °C) • Fan type (selected in unit configurator): - “°” Standard - “J” Inverter • Pump assembly and buffer tank options com- plete with water filter, flow switch, expansion tank, charging point, and anti-freeze electric heater • Microprocessor control system: - Control from the entering water tempera- ture, with the possibility of selecting control of the leaving water temperature. - Condensing control in summer with a 0-10 V modulating signal based on pressure and compensated for external air temperature (with DCPX accessory) - Evaporating control in summer for heat pump operation (with DCPX accessory) - Automatic rotation of compressors and pumps based on operating hours (manual rotation sizes 1400 to 1800) - Load limiting safety control - Low and high pressure transducers (standard for all units) - Automatic reset of alarms before tripping - Display in 4 languages - Alarm history • DCPX standard on all versions silenced Characteristics Accessories AERSET: The AERSET accessory allows the automatic compensation of the operating set- point of the unit to which it is connected, based on a 0-10V MODBUSinput signal. Mandatory accessory: AER485 or MODU- 485A AER485: RS-485 interface for supervision sys- tems with MODBUS protocol. AVX: spring anti-vibration mounts Select the AVX model from the compatibility table. DCPX: Low ambient device for cooling oper- ation below 10 °C down to -10 °C. Pressure transducers read the condensing pressure and the electronic controller varies fan speed to maintain adequate pressure for correct unit operation. Also permits correct unit operation in heating mode with external air tempera- tures above 30 °C and up to 42 °C. DRE: Soft starter (about 26% with two com- pressors, 22% with three compressors). Only available for 400V-3-phase power supply. Factory fitted only. GP: Protection grille protects the external coil from accidental damage. PGS: Daily/Weekly Programmer. Allows two daily time-clock programmes (two switch on/ off cycles) and different programmes for each day of the week. RIF: Power factor correction. Connected in parallel to the motor allowing about 10% reduction of input current. Must be requested at time of order and is available factory fitted only. AERWEB300: Accessory AERWEB allows remote control of a chiller through a com- mon PC and an ethernet connection over a common browser; 4 versions available: AERWEB300-6: Web server to monitor and remote control max. 6 units in RS485 net- work; AERWEB300-18: Web server to monitor and remote control max. 18 units in RS485 net- work; AERWEB300-6G: Web server to monitor and remote control max. 6 units in RS485 net- work with integrated GPRS modem; AERWEB300-18G: Web server to monitor and remote control max. 18 units in RS485 net- work with integrated GPRS modem; DUALCHILLER: Simplified control system to switch on/off and control two chillers in a sin- gle system (using Aermec GR3 command), as if they were a single unit. MULTICHILLER: Control system for multiple parallel installed constant flow chillers pro- viding individual chiller on/off and control capability. TRX1: Metal cap that replaces the plastic cap, mounted as shipping protection, for immer- sion heater holes in the buffer tank. • VT: anti-vibration mounts, to be fitted below the unit base. PRM1 and PRM2 : FACTORY FITTED ACCESSORY. A manual reset pressure switch wired in series with the existing high pressure switch installed on the compressor discharge line. COMPATIBILITY with the VMF SYSTEM For more information on the system refer to the manual. HIGH EFFICIENCY VERSION LOW NOISE HIGH EFFICIENCY VERSION COMPACT VERSION LOW NOISE COMPACT VERSION - 2 REFRIGERANT CIRCUITS - PUMP ASSEMBLY OPTION - PUMP ASSEMBLY AND BUFFER TANK OPTION 0750/1800 heat pump Reversible heat pumps Air/Water outdoor installation Axial fans and scroll compressor Cooling capacity 164kW÷470kW Heating capacity 203kW÷526kW

Upload: others

Post on 02-Aug-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: NRL - AerSA 0750-1800.pdfHA - HE 62,69/62,39 75,33 84,49 94,63 112,03 125,79 141,02 155,41 165,57 Water flow rate (l/h) H - HL 34572 39044 44032 50396 58480 66048 73444 80496 86516

Aermec adheres to the EUROVENT Certification programme up to 600kW cooling. The products concerned appear in the EUROVENT Certified products guide.

NRL

R410A

• Available in 9 sizes• Refrigerant R410A• 2 refrigerant circuits• High efficiency even at part load• Heat exchangers optimised to benefit from

the excellent heat transfer characteristics of R410A

• High efficiency scroll compressors• Axial fans with low sound level• Solid construction with polyester anti-corro-

sion painted finish• Extended operating limits in heat pump oper-

ation: - Maximum leaving water temperature 55° C - Maximum external air temperature 30° C (42° C with fan speed controller accessory DCPX)• Operating limits extended operation in heat

pump.Version H ° - HL- Max water at 50 ° C produced- Max air temperature 30 ° C (42 ° C with acces-

sory DCPX fan speed controller)Version. HA - HE- Max water at 55 ° C produced- Max air temperature 30 ° C (42 ° C with acces-

sory DCPX fan speed controller)• Cooling modeVersion. H ° - HL - Max 18 ° C water produced - Max air temperature 42 ° CVersion. HA - HE- Max 18 ° C water produced- Max air temperature 46 ° C• Expansion valve (selected in unit configura-

tor): - “°” standard thermostatic expansion valve - “X” electronic expansion valve, also for low

fluid temperature (down to -6 °C)• Fan type (selected in unit configurator): - “°” Standard - “J” Inverter• Pump assembly and buffer tank options com-

plete with water filter, flow switch, expansion

tank, charging point, and anti-freeze electric heater

• Microprocessor control system: - Control from the entering water tempera-

ture, with the possibility of selecting control of the leaving water temperature.

- Condensing control in summer with a 0-10 V modulating signal based on pressure and compensated for external air temperature (with DCPX accessory)

- Evaporating control in summer for heat pump operation (with DCPX accessory)

- Automatic rotation of compressors and pumps based on operating hours (manual rotation sizes 1400 to 1800)

- Load limiting safety control - Low and high pressure transducers (standard

for all units) - Automatic reset of alarms before tripping - Display in 4 languages - Alarm history• DCPX standard on all versions silenced

Characteristics

Accessories• AERSET: The AERSET accessory allows the

automatic compensation of the operating set-point of the unit to which it is connected, based on a 0-10V MODBUSinput signal. Mandatory accessory: AER485 or MODU-485A

• AER485: RS-485 interface for supervision sys-tems with MODBUS protocol.

• AVX: spring anti-vibration mounts Select the AVX model from the compatibility table.

• DCPX: Low ambient device for cooling oper-ation below 10 °C down to -10 °C. Pressure transducers read the condensing pressure and the electronic controller varies fan speed to maintain adequate pressure for correct unit operation. Also permits correct unit operation in heating mode with external air tempera-tures above 30 °C and up to 42 °C.

• DRE: Soft starter (about 26% with two com-pressors, 22% with three compressors). Only available for 400V-3-phase power supply. Factory fitted only.

• GP: Protection grille protects the external coil

from accidental damage.• PGS: Daily/Weekly Programmer. Allows two

daily time-clock programmes (two switch on/off cycles) and different programmes for each day of the week.

• RIF: Power factor correction. Connected in parallel to the motor allowing about 10% reduction of input current. Must be requested at time of order and is available factory fitted only.

• AERWEB300: Accessory AERWEB allows remote control of a chiller through a com-mon PC and an ethernet connection over a common browser; 4 versions available:

AERWEB300-6: Web server to monitor and remote control max. 6 units in RS485 net-work;

AERWEB300-18: Web server to monitor and remote control max. 18 units in RS485 net-work;

AERWEB300-6G: Web server to monitor and remote control max. 6 units in RS485 net-work with integrated GPRS modem;

AERWEB300-18G: Web server to monitor and remote control max. 18 units in RS485 net-work with integrated GPRS modem;

• DUALCHILLER: Simplified control system to switch on/off and control two chillers in a sin-gle system (using Aermec GR3 command), as if they were a single unit.

• MULTICHILLER: Control system for multiple parallel installed constant flow chillers pro-viding individual chiller on/off and control capability.

• TRX1: Metal cap that replaces the plastic cap, mounted as shipping protection, for immer-sion heater holes in the buffer tank.

• VT: anti-vibration mounts, to be fitted below the unit base.

• PRM1 and PRM2 : FACTORY FITTED ACCESSORY. A manual reset pressure switch wired in series with the existing high pressure switch installed on the compressor discharge line.

• COMPATIBILITY with the VMF SYSTEM For more information on the system refer to the manual.

• HIGH EFFICIENCY VERSION • LOW NOISE HIGH EFFICIENCY

VERSION • COMPACT VERSION• LOW NOISE COMPACT VERSION

- 2 REFRIGERANT CIRCUITS- PUMP ASSEMBLY OPTION- PUMP ASSEMBLY AND BUFFER

TANK OPTION

0750/1800heat pump

Reversible heat pumpsAir/Water outdoor installationAxial fans and scroll compressorCooling capacity 164kW÷470kWHeating capacity 203kW÷526kW

Page 2: NRL - AerSA 0750-1800.pdfHA - HE 62,69/62,39 75,33 84,49 94,63 112,03 125,79 141,02 155,41 165,57 Water flow rate (l/h) H - HL 34572 39044 44032 50396 58480 66048 73444 80496 86516

Attention:– the standard options are shown by the symbol °– the configurations XD are not available (only for liquid temperatures below +4°C )Example of configuration code: NRL1000°H°E°°°04This is an NRL unit of size 1000, with standard thermostatic expansion valve, heat pump model, without heat recovery, high efficiency, with aluminium condenser coils, standard fans, and electrical panel for compressor motors 400V 3~ 50Hz, and single and standby high head pump and buffer tank.

By suitably combining the numerous options available it is possible to configure each model in such a way as to meet even the most demanding of system requirements.

Unit Configurator

Configuration fields:

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 | | | | | | | | | | Code | | Model | Version | Fan | Hydronic | | | | | Kit Size Expansion valve Heat recovery Coil Power supply

Code:NRL

Size:0750, 0800, 0900, 1000, 1250, 1404, 1504, 1655, 1800Expansion valve:

° - Standard thermostatic expansion valve for water temperature down to +4 °C

X - Electronic thermostatic valve, max. temp. of water produced: +4°C (for lower temperatures please contact us)Model:H - Heat pump

Heat recovery° - Without heat recoveryD - With partial heat recovery (desuperheater)

Version:° - Standard compact L - Compact low noise A - High efficiency E - High efficiency low noise

Coil:° - AluminiumR - CopperS - Tinned copperV - Coated aluminium

Fan:° - StandardJ - Inverter

Power supply:° - 400V 3~ 50Hz with circuit breakers (only for NRL 800 up to 1800) - 400V 3N~ 50Hz with circuit breakers (only NRL 0750)Hdronic kit:00 - without pump or buffer tank01 - single low head pump and buffer tank 02 - single and standby low head pump and buffer tank03 - single high head pump and buffer tank04 - single and standby high head pump and buffer tank05 - single low head pump and buffer tank (with holes for immersion

heaters)06 - single and standby low head pump and buffer tank (with holes

for immersion heaters)07 - single high head pump and buffer tank (with holes for immersion

heaters)08 - single and standby high head pump and buffer tank (with holes

for immersion heaters)09 - double hydraulic circuit10 - double hydraulic circuit (with holes for immersion heaters)P1 - single low head pump without buffer tankP2 - single and standby low head pump without buffer tankP3 - single high head pump without buffer tankP4 - single and standby high head pump without buffer tank

Accessory Compatibility

Mod. NRL Vers. 0750 0800 0900 1000 1250 1404 1504 1655 1800AERSET All ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔

AER485 All ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔

DUALCHILLER All ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔

MULTICHILLER All ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔

PGS All ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔

AERWEB300 All ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔

TRX1 All ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔

AVX "00"H - HL - 701 707 713 713 722 722 733 730

HA - HE - 704 710 716 719 725 730 734 737

AVX "01...04"H - HL - 702 708 714 717 723 728 728 728

HA - HE - 705 711 711 720 726 731 735 738

AVX (P1-P2-P3-P4)H - HL - 703 709 715 718 724 729 729 732

HA - HE - 706 712 712 721 727 732 736 736

VTAll 23 - - - - - - - -H 64 65 65 65 65 66 66 68 68

DCPXHL standard standard standard standard standard standard standard standard standardHA 65 66 66 66 68 68 68 68 68HE standard standard standard standard standard standard standard standard standard

DCPX vers. with fans "J" All NOTE: DCPX not necessary. The fans are already fitted with speed controller.DRE All 751 801 901 1001 1251 1404 1504 1655 1801

GPH - HL 10 (x3) 10 (x3) 10 (x3) 10 (x4) 10 (x4) 350 350 350 350

HA - HE 10 (x3) 260 260 260 350 350 350 500 500

RIFH -HL 53 87 89 91 91 92 92 93 94

HA -HE 53 88 90 92 92 92 92 93 94PRM1/PRM2 All ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔

Page 3: NRL - AerSA 0750-1800.pdfHA - HE 62,69/62,39 75,33 84,49 94,63 112,03 125,79 141,02 155,41 165,57 Water flow rate (l/h) H - HL 34572 39044 44032 50396 58480 66048 73444 80496 86516

(*) For size 075 has the power: 400V-3N-50Hz.

Technical data

Mod. NRL Vers. 0750 0800 0900 1000 1250 1404 1504 1655 1800

Cooling capacity (kW)

H 175 200 221 261 299 332 366 421 452HL 164 183 199 236 264 301 331 372 396HA 179 210 238 260 313 350 386 435 470HE 174 193 212 230 283 318 354 397 424

Total power input (kW)

H 71,23 81,88 94,93 102,13 121,42 141,15 160,25 167,61 180,68HL 78,36 90,74 105,76 112,91 137,05 154,93 175,00 188,18 205,22HA 64,22 74,02 83,15 95,20 110,56 127,40 144,55 152,86 163,99HE 69,84 81,87 94,90 107,93 123,23 141,11 159,24 169,47 183,53

Water flow rate (l/h)

H 30272 34572 38184 45064 51600 57276 63124 72756 78088HL 28380 31648 34400 40764 45580 51944 57104 64156 68284HA 30960 36292 41108 44892 54180 60372 66736 75164 81184HE 30100 33368 36636 39732 48848 54868 61060 68456 73272

Pressure drop (kPa)

H 74 46 45 50 57 40 40 47 46HL 65 39 37 41 45 33 34 37 36HA 64 55 56 54 61 48 49 54 54HE 60 47 45 43 51 40 41 45 44

Heating capacity (kW)H 203 228 257 295 342 386 429 470 505

HA - HE 205 234 264 295 346 390 435 486 526

Total power input (kW)H - HL 66,77 76,19 86,33 97,55 113,05 127,67 142,85 157,13 168,23

HA - HE 62,69/62,39 75,33 84,49 94,63 112,03 125,79 141,02 155,41 165,57

Water flow rate (l/h)H - HL 34572 39044 44032 50396 58480 66048 73444 80496 86516

HA - HE 35088 40076 45236 50396 59168 66736 74476 83248 89956

Pressure drop (kPa)H - HL 96 61 62 65 78 54 55 59 58

HA - HE 82 68 69 69 76 58 60 66 66ENERGY INDICES

EER (W/W)

H 2,46 2,44 2,33 2,55 2,46 2,35 2,28 2,51 2,50HL 2,09 2,02 1,88 2,09 1,93 1,94 1,89 1,98 1,93HA 2,79 2,84 2,86 2,73 2,83 2,74 2,67 2,85 2,87HE 2,49 2,36 2,23 2,13 2,29 2,25 2,22 2,34 2,31

ESEER (W/W)

H 3,66 3,85 3,66 3,67 3,63 3,50 3,44 3,45 3,53HL 3,67 3,79 3,66 3,66 3,56 3,42 3,39 3,39 3,37HA 3,98 4,01 3,90 3,82 3,96 3,80 3,72 3,74 3,71HE 3,87 3,92 3,87 3,78 3,93 3,77 3,66 3,72 3,74

COP (W/W)H - HL 3,03 3,00 2,98 3,02 3,03 3,02 3,00 2,99 3,00

HA - HE 3,28/3,29 3,11 3,13 3,11 3,09 3,10 3,08 3,13 3,17ELECTRICAL DATASupply All 400V-3-50Hz (*)

Total input current in cooling mode

(A)

H 122 142 166 189 208 249 286 305 319HL 132 153 177 200 226 269 308 328 348HA 113 136 158 180 196 235 273 286 304HE 120 145 169 192 211 251 292 306 324

Total input current in heating mode

(A)

H 113 136 156 179 193 227 261 279 290HL 113 136 156 179 193 227 261 279 290HA 113 138 157 177 197 231 265 282 293HE 113 138 157 177 197 231 282 282 293

Maximum current (FLA) (A)H - HL 144 173 195 221 265 282 312 349 398

HA - HE 144 177 199 221 274 290 320 357 406

Starting current (LRA) (A)H - HL 320 348 404 430 533 616 646 683 666

HA - HE 320 352 408 430 542 624 654 691 674Type of compressors All ScrollCompressors/circuits (n°) All 4/2 4/2 4/2 4/2 4/2 4/2 4/2 5/2 6/2Type of fans All Axial

Fan air flow rate (m3/h)

H 50200 64500 63750 85600 80800 87400 86800 124200 122400HL 41700 45200 44600 59900 56600 65500 69400 86900 85700HA 48000 85600 84600 83600 126000 124200 122400 168000 165600HE 34600 59920 59220 60610 88200 90000 91800 117600 115920

Number of fans (n°)

H 3 3 3 4 4 4 4 6 6HL 3 3 3 4 4 4 4 6 6HA 3 4 4 4 6 6 6 8 8HE 3 4 4 4 6 6 6 8 8

Evaporator All PlatesType of hydraulic connection All VictaulicHydraulic connections "00" version (Ø) All 3" 3" 3" 3" 3" 4" 4" 4" 4"

Page 4: NRL - AerSA 0750-1800.pdfHA - HE 62,69/62,39 75,33 84,49 94,63 112,03 125,79 141,02 155,41 165,57 Water flow rate (l/h) H - HL 34572 39044 44032 50396 58480 66048 73444 80496 86516

Aermec S.p.A.Via Roma, 996 - 37040 Bevilacqua (VR) - ItalyTel. 0442633111 - Telefax 044293577www.aermec.com

Aermec reserves the right to make all modification deemed necessary for improving the product at any time with any modification of technical data.

Warning: the weights refer to versions without pump or buffer tank.

Dimensions (mm)

Cod

.: SN

RLL

SHU

Y.11

/ 14

10

Mod. NRL U.M. Vers. 0750 0800 0900 1000 1250 1404 1504 1655 1800

Height (mm) AH - HL 1975 1975 1975 1975 1975 2450 2450 2450 2450

HA - HE 1975 2450 2450 2450 2450 2450 2450 2450 2450

Width (mm) BH - HL 1500 1500 1500 1500 1500 2200 2200 2200 2200HA -HE 1500 2200 2200 2200 2200 2200 2200 2200 2200

Depth (mm) CH - HL 4350 4355 4355 5355 5355 4250 4250 4250 4250

HA - HE 4350 3400 3400 3400 4250 4250 4250 5750 5750

Weight empty (kg)

H 1487 1800 1940 2170 2320 2930 3140 3220 3330HL 1487 1800 1950 2180 2320 2940 3150 3230 3340HA 1748 2150 2300 2460 2750 2990 3190 3680 3800HE 1748 2160 2310 2470 2760 3000 3200 3690 3810

Cooling- leaving water temperature 7 °C- external air temperature 35 °C- ∆t = 5 °C.

Heating- leaving water temperature 45 °C- external air temperature 7 °C db / 6 °C wb- ∆t = 5 °C.

DATA DECLARED IN ACCORDANCE WITHUNI EN 14511: 2011

Mod. NRL U.M. Vers. 0750 0800 0900 1000 1250 1404 1504 1655 1800HDRONIC KIT

Useful pump head low-headcooling mode

(kPa)

H 99 110 101 86 114 106 94 103 96HL 112 126 121 109 144 133 118 131 127HA 94 100 84 87 99 90 78 94 85HE 100 117 109 114 128 119 102 117 112

Useful pump head high-headcooling mode

(kPa)

H 216 226 216 199 253 243 209 239 234HL 229 243 237 223 286 272 245 266 264HA 211 216 198 200 238 225 186 231 223HE 217 233 225 228 269 257 222 253 249

Useful pump head low-headheating mode

(kPa)

H 75 90 73 63 83 65 57 82 73HL 105 116 107 91 119 101 101 112 104HA 71 84 66 63 78 61 52 71 60HE 71 84 66 63 78 61 52 71 60

Useful pump head high-headheating mode

(kPa)

H 192 205 186 173 219 197 148 219 211HL 187 200 177 163 204 176 137 210 200HA 187 199 178 173 214 193 141 209 198,86HE 187 199 178 173 214 193 141 209 199

Buffer tank capacity (l) All 700 700 700 700 700 700 700 700 700SOUND DATA

Sound power db(A)

H 85,0 88,5 88,5 90,5 93,5 91,0 90,5 92,0 94,0HL 80,0 85,5 85,5 87,5 90,5 88,0 87,5 89,0 91,0HA 85,0 88,5 88,5 88,5 91,5 91,0 91,5 92,0 94,0HE 77,0 83,0 83,0 83,5 86,0 85,5 85,0 86,5 88,5

Sound pressure db(A)

H 53,0 56,5 56,5 58,5 61,5 59,0 58,5 60,0 62,0HL 48,0 53,5 53,5 55,5 58,5 56,0 55,5 57,0 59,0HA 53,0 56,5 56,5 56,5 59,5 59,0 58,5 60,0 62,0HE 45,0 51,0 51,0 51,0 54,0 53,5 53,0 54,5 56,5

NRL_0750 HA-HENRL_0750/0800/0900 H-HL

B BC

B B

C

A

C

A

AA

C C

B

A

NRL_0800/0900/1000 HA-HENRL_1404/1504 H-HL

NRL_1250/1404/1504 HA-HE1655/1800 H-HL

NRL_1655/1800 HA-HENRL_1000/1250 H-HL

SOUND POWER:Aermec determines sound power values on the basis of measurements made in accordance with UNI EN ISO 9614-2, as required for Eurovent certification.

SOUND PRESSURE:Sound pressure in free field, at 10 m distance from the external surface of the unit (in accordance with UNI EN ISO 3744)