npf910 - cee relays

2
Our energy at your service GENERATION & NETWORK Feeder Protection IED NPF910 • Cable end differential protection • Low-impedance REF protection • Harmonics protection and control • 5-shot scheme controlled autorecloser The optimal management of electrical power systems is based in particular on the reliability, availability and communication skills of protection, measurement and automation devices. The NPF910 offers a modular feeder protection and control solution for non-directional overcurrent and earth-fault protection with automatic reclosing. Optional cards (I/O, communication...) are available for more comprehensive monitoring and control applications. The NPF910 communicates using various protocols including IEC 61850 substation communication standard. ANSI CODES

Upload: others

Post on 25-Nov-2021

0 views

Category:

Documents


0 download

TRANSCRIPT

Our energy at your service

GENERATION & NETWORKFeeder Protection IED

NPF910

• Cableenddifferentialprotection

• Low-impedanceREFprotection

• Harmonicsprotectionandcontrol

• 5-shotschemecontrolledautorecloser

The optimal management of electrical power systems is based inparticular on the reliability, availability and communication skills ofprotection,measurementandautomationdevices.

TheNPF910offersamodularfeederprotectionandcontrolsolutionfornon-directionalovercurrentandearth-faultprotectionwithautomaticreclosing.Optionalcards(I/O,communication...)areavailableformorecomprehensivemonitoringandcontrolapplications.

TheNPF910communicatesusingvariousprotocolsincludingIEC61850substationcommunicationstandard.

ANSI CODES

A928B

CHARACTERISTICSProtection functions

• Three-phaseovercurrent,4stagesINST,DTorIDMT[50/51]

• Earth-fault(sensitive),4stagesINST,DTorIDMT[50N/51N(S)]

• Harmonicovercurrent/inrushblocking,4stagesINST,DTorIDMT[50H/51H/68H]

• Currentunbalance/brokenconductor,4stagesINST,DTorIDMT[46/46R/46L]

• Cablethermaloverloadprotection[49L]• Lowimpedancerestrictedearthfault/cableenddifferential[87N]

• Breakerfailureprotection[50BF/52BF]• Arcprotection(option)[50ARC]

Measuring and monitoring• Phaseandresidualcurrents(IL1,IL2,IL3,I01,I02)• CurrentTHDandharmonics(upto31st)• Circuitbreakerwear(CBW)• Disturbancerecorder(3.2kHz)• Currenttransformersupervision(CTS)• Tripcircuitsupervision[74TC]

Control• Controllableobjects:5• Autorecloser[79]• Cold-loadpick-upblock[68]• Switchontofaultlogic• 8settinggroups

Hardware• Currentinputs:5• Digitalinputs:3(standard)• Outputrelays:5+1(standard)

Options (4 slots)• Digitalinputsoptional:+8percard• Digitaloutputsoptional:+5percard(2cardsmax.)• Arcprotection(12sensors+2xHSO+BI)• 2xmAinput+6-8xRTDinput(2cardsmax.)• Communicationmedia(specifiedbelow)

Event recording• Non-volatiledisturbancerecords:100• Non-volatileeventrecords:10000

Communication media• RJ45Ethernet100Mb(frontstandard)• DoubleLCEthernet100Mb(option)• RS232+serialfibrePP/PG/GP/GG(option)

Communication protocols standard• IEC61850• IEC60870-5-103/101/104• ModbusRTU,ModbusTCP/IP• DNP3.0,DNP3.0overTCP/IP• SPA

Case• H,W,Dwithoutterminal177x127x174mm• H,W,Dwithterminal177x127x189mm(casingheight4U,width¼rack,depth210mm)

• H,Woffrontplate177x127mm• H,Wofcutout160x106mm

SMART9 - integrated softwareOur user friendly SMART9 (Setting, Measurement,Analysis,Recording,Time-saving)configurationsoftwarehelpstheusergetthebestfromNP900seriesrelays.