note t r-410a h p r s · attention to note 8 of table 310 regarding ampacity adjustment factors...
TRANSCRIPT
Manual 2100-455A
Page 1 of 25
INSTALLATION INSTRUCTIONS
WALL MOUNTED
PACKAGE HEAT PUMPS
Models:
CH3S1
CH4S1
CH5S1
Manual : 2100-455A
Supersedes: 2100-455
File: Volume III Tab 17
Date: 08-18-06
Bard Manufacturing Company, Inc.
Bryan, Ohio 43506
Since 1914...Moving ahead just as planned.
© Copyright 2004
NOTE
THIS IS AN R-410A
HIGH PRESSURE
REFRIGERANT SYSTEM
Manual 2100-455A
Page 2 of 25
CONTENTS
Figures
Figure 1 Unit Dimensions CH3S1 ...................... 5
Figure 2 Unit Dimensions CH4S1 & CH5S1 ...... 6
Figure 3 Mounting Instructions CH3S1 ............ 10
Figure 4 Mounting Instructions CH4S1/CH5S1 . 11
Figure 5 Electric Heat Clearance ..................... 12
Figure 6 Wall Mounting Instructions ................. 13
Figure 7 Wall Mounting Instructions ................. 13
Figure 8 Common Wall Mounting Installations . 14
Figure 9 Common Wall Mounting Installations . 15
Figure 10 Unit 24V Terminal Board .................... 15
Figure 11 Low Pressure Control Bypass Timer . 17
Figure 12 Defrost Control Board ........................ 19
Figure 13 Fan Blade Setting .............................. 22
Tables
Table 1 Electric Heat Table ................................ 4
Table 2 Electrical Specifications ........................ 7
Table 3 Thermostat Wire Size ......................... 15
Table 4 Wall Thermostat .................................. 16
Table 5 Troubleshooting .................................. 20
Table 6 Fan Blade Dimensions........................ 22
Table 7 Refrigerant Charge ............................. 23
Table 8 Indoor Blower Performance ................ 23
Table 9 Maximum ESP of Operation ............... 23
Table 10 Pressure Table - High Cooling ............ 24
Table 11 Pressure Table - Low Cooling ............. 24
Table 12 Pressure Table - High Heating ............ 25
Table 13 Pressure Table - Low Heating ............. 25
Getting Other Information and Publications
For More Information ............................................... 3
Wall Mount General
Heat Pump Wall Mount Model Nomenclature ....... 4
Shipping Damage ................................................. 8
General .............................................................. 8
Duct Work ............................................................. 8
Filters .............................................................. 8
Condensate Drain – Evaporator ........................... 8
Installation Instructions
Wall Mounting Information .................................... 9
Mounting the Unit .................................................. 9
Wiring – Main Power ........................................... 15
Wiring – Low Voltage Wiring ............................... 15
Low Voltage Connections ................................... 16
Start Up
Application .......................................................... 16
Safety Practices .................................................. 17
Important Installer Note....................................... 17
Pressure Service Ports ....................................... 17
High & Low Pressure Switch .............................. 17
Three Phase Scroll Compressor Start Up ... 17 & 18
Phase Monitor ..................................................... 18
Service Hints ....................................................... 18
Sequence of Operation ....................................... 18
Compressor Current & Pressure
Control Module ................................................... 18
Defrost Cycle ...................................................... 19
Troubleshooting
Solid State Heat Pump Control
Troubleshooting Procedure................................. 20
Checking Temperature Sensor
Outside Unit Circuit ............................................. 21
Temperature vs. Resistance of Temperature ...... 21
Compressor Solenoid ......................................... 22
Fan Blade Setting Dimensions ........................... 22
Removal of Fan Shroud ...................................... 22
Refrigerant Charge R-410A ................................ 22
Pressure Tables ............................................. 24-25
Manual 2100-455APage 3 of 25
Getting Other Information and Publications
These publications can help you install the air
conditioner or heat pump. You can usually find these at
your local library or purchase them directly from the
publisher. Be sure to consult current edition of each
standard.
National Electrical Code ...................... ANSI/NFPA 70
Standard for the Installation .............. ANSI/NFPA 90A
of Air Conditioning and Ventilating Systems
Standard for Warm Air ...................... ANSI/NFPA 90B
Heating and Air Conditioning Systems
Load Calculation for ............................ ACCA Manual J
Residential Winter and Summer Air Conditioning
Duct Design for Residential .............. ACCA Manual D
Winter and Summer Air Conditioning and Equipment
Selection
FOR MORE INFORMATION, CONTACTTHESE PUBLISHERS:
ACCA Air Conditioning Contractors of America
1712 New Hampshire Ave. N.W.
Washington, DC 20009
Telephone: (202) 483-9370
Fax: (202) 234-4721
ANSI American National Standards Institute
11 West Street, 13th Floor
New York, NY 10036
Telephone: (212) 642-4900
Fax: (212) 302-1286
ASHRAE American Society of Heating, Refrigerating,
and Air Conditioning Engineers, Inc.
1791 Tullie Circle, N.E.
Atlanta, GA 30329-2305
Telephone: (404) 636-8400
Fax: (404) 321-5478
NFPA National Fire Protection Association
Batterymarch Park
P.O. Box 9101
Quincy, MA 02269-9901
Telephone: (800) 344-3555
Fax: (617) 984-7057
Manual 2100-455APage 4 of 25
WALL MOUNT GENERAL INFORMATION
HEAT PUMP WALL MOUNT MODEL NOMENCLATURE
CH 4S 1 – A 05 B P X X X X
TABLE 1
ELECTRIC HEAT TABLE
sledoMA-1S3HC B-1S3HC C-1S3HC
A-1S4HCA-1S5HC
B-1S4HCB-1S5HC
C-1S4HCC-1S5HC
1-042 1-802 3-042 3-802 3-064 1-042 1-802 3-042 3-802 3-064
WK A UTB A UTB A UTB A UTB A UTB A UTB A UTB A UTB A UTB A UTB
4 7.61 05631 4.41 04201
5 8.02 56071 1.81 00821 8.02 56071 1.81 00821
6 4.41 00502 5.21 06351 2.7 08402 4.41 00502 5.21 06351 2.7 08402
9 7.12 00603 7.81 03032 8.01 00703 7.12 00603 7.81 03032 8.01 00703
01 6.14 03143 2.63 00652 6.14 03143 2.63 00652
51 5.26 00215 1.45 00483 2.63 00215 2.13 00483 0.81 00215 5.26 00215 1.45 00483 2.63 00215 2.13 00483 0.81 00215
81 3.34 00416 5.73 05064 6.12 00416
02 2.38 05286 1.27 00215
MODEL NUMBER CONTROL MODULES
CAPACITY
3S - 3 ton
4S - 4 ton
5S - 5 ton VOLTS & PHASE
A - 230/208/60/1
B - 230/208/60/3
C - 460/60/3
REVISIONS
KW
VENTILATION OPTIONS
B - Blank-off Plate
R - Energy Recovery
V - Commercial Ventilator -
Motorized with Exhaust
FILTER OPTIONS
P - 2-Inch Pleated
COLOR OPTIONS
X - Beige (Standard)
4 - Buckeye Gray
5 - Desert Brown
8 - Dark Bronze
COIL OPTIONS
X - Standard
OUTLET OPTIONS
X - Front (Standard)
T - Top Outlet
Manual 2100-455APage 5 of 25
FIG
UR
E 1
UN
IT D
IME
NS
ION
S
16"
16"
16"
16"
16"
31 5
/8"
32 3
/4"
84 1
1/16
"
43 7
/8"
42 3
/16"
13 3
/8"
48 1
/16"
5 13
/16"
"31
"
6 7/
8"
39 7
/8"
9 13
/16"
15 7
/8"
29 7
/8"
6 1/
8"
1 3/
8"
43"
6 9/
16"
7/8"
2 1/
4"8
9/16
"
Left
Sid
e V
iew
(12)
Wal
l
Rig
ht S
ide
Vie
wB
ack
Vie
w
Ent
ranc
es
Top
Rai
n
Out
let
Gril
le
Con
d.
"C
H3
S1
" U
nit
Dim
en
sio
ns
Gril
leO
utle
tO
pt. H
igh
Vol
tage
Con
d.In
let
Sup
ply
Gril
le
Fla
shin
g
Ope
ning
Ope
ning
Slo
pe T
op
Con
d.
Ret
urn
Opt
iona
l Top
Out
let
Blo
wer
Acc
ess
Doo
r
Filt
er A
cces
sD
oor
Ven
t Opt
ion
Acc
ess
Doo
r
Hea
ter
Acc
ess
Doo
r
Con
trol
Pan
el
Acc
ess
Doo
r
Doo
r
C. B
reak
er
Low
Vol
tage
Ent
ranc
e
Ent
ranc
e
Hig
h V
olta
ge
Top
Vie
w
MIS
-214
6
Mou
ntin
g H
oles
Acc
ess
Doo
rE
vap.
Dra
inH
ose
Fro
nt V
iewDra
in fo
r op
tiona
ldr
ain
pan
Manual 2100-455APage 6 of 25
FIG
UR
E 2
UN
IT D
IME
NS
ION
S
42 3
/4"
39 7
/8"
1 3/
8"6
7/8"
Rig
ht S
ide
Vie
wF
ront
Vie
w
MIS
-202
0 A
Left
Sid
e V
iew
"CH
4S1
and
CH
5S1"
Uni
t Dim
ensi
ons
Bac
k V
iew
Doo
rF
ilter
Acc
ess
Sup
ply
Ope
ning
Mou
ntin
g(1
2) W
all
Ret
urn
Ope
ning
Top
Rai
nF
lash
ing
Eva
p. D
rain
Hos
e
Hol
es
Opt
. Hig
hV
olta
geE
ntra
nces
16"
6 9/
16"
48 1
/16"
9 13
/16"
15 7
/8"
29 7
/8"
6 1/
8"
43"
16"
16"
16"
7/8" 16
"2
1/4"
8 9/
16"
Con
d.
Gril
leO
utle
t
Ent
ranc
e
Ent
ranc
e
Low
Vol
tage
Hea
ter
Acc
ess
Doo
r
Con
trol
Pan
elD
oor
C. B
reak
erA
cces
s D
oor
Hig
h V
olta
ge
Acc
ess
Doo
r
22 3
/16"31
"
Blo
wer
Acc
ess
Doo
r
Inle
t Gril
leC
onde
nser
Ven
t Opt
ion
Acc
ess
Doo
r
94 1
1/16
"
43 7
/8"
42 3
/16"
13 3
/8"
41 5
/8"
5 13
/16"
Dra
in fo
r op
tiona
ldr
ain
pan
Gril
le
Con
d.O
utle
t
Slo
pe T
op
Opt
iona
l Top
Out
let
Top
Vie
w
Manual 2100-455APage 7 of 25
TABLE 2
ELECTRICAL SPECIFICATIONS
1 Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors.
2 Based on 75°C copper wire. All wiring must conform to NEC and all local codes.
3 These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electric Code
(latest revision), Article 310 for power conductor sizing.
CAUTION: When more than one field power conductor circuit is run through one conduit, the conductors must be derated. Pay special
attention to note 8 of table 310 regarding Ampacity Adjustment Factors when more than 3 conductors are in a raceway.
ledoM
TIUCRICELGNIS TIUCRICLAUD
detaR&stloVesahP
.oNdleiF
rewoPstiuriC
3
muminiMtiucriCyticapmA
1
mumixaMlanretxE
roesuFtiucriCrekaerB
2
dleiFrewoP
eriWeziS
2
dnuorGeriWeziS
3
tiucriCmuminiMyticapmA
1
mumixaMesuFlanretxE
tiucriCrorekaerB
2
rewoPdleiFeziSeriW
2
dnuorGeziSeriW
.tkCA
.tkCB
.tkCC
.tkCA
.tkCB
.tkCC
.tkCA
.tkCB
.tkCC
.tkCA
.tkCB
.tkCC
Z0A-1S3HC50A01A51A
1-802/0321-802/0321-802/0321-802/032
11
2ro12ro1
92551858
54060909
8644
0101
88
------9233
------2525
------------
------5454
------0606
------------
------01
8
------
66
------------
------0101
------0101
------------
Z0B-1S3HC60B90B51B
3-802/0323-802/0323-802/0323-802/032
1111
32140505
03540505
01888
01010101
------------
------------
------------
------------
------------
------------
------------
------------
------------
------------
------------
------------
Z0C-1S3HC60C90C51C
3-0643-0643-0643-064
1111
11024242
51025252
41210101
41210101
------------
------------
------------
------------
------------
------------
------------
------------
------------
------------
------------
------------
Z0A-1S4HC40A50A01A51A02A
1-802/0321-802/0321-802/0321-802/0321-802/0321-802/032
11
2ro12ro12ro13ro1
7375369898311
0506070909021
866332
0101
8886
------73737325
------62252525
---------------62
------05050505
------03060606
---------------03
------
8886
------01
666
---------------01
------01010101
------01010101
---------------01
Z0B-1S4HC60B90B51B81B
3-802/0323-802/0323-802/0323-802/0323-802/032
11111
7254454555
5305060606
88666
0101010101
---------------
---------------
---------------
---------------
---------------
---------------
---------------
---------------
---------------
---------------
---------------
---------------
Z0C-1S4HC60C90C51C81C
3-0643-0643-0643-0643-064
11111
4132828282
0252030303
2101010101
2101010101
---------------
---------------
---------------
---------------
---------------
---------------
---------------
---------------
---------------
---------------
---------------
---------------
Z0A-1S5HC40A50A01A51A02A
1-802/0321-802/0321-802/0321-802/0321-802/0321-802/032
12ro12ro12ro12ro13ro1
4456076969411
060708001001021
644332
0188886
---4444444444
---1262252525
---------------62
---0606060606
---5203060606
---------------03
---88888
---0101
666
---------------01
---0101010101
---0101010101
---------------01
Z0B-1S5HC60B90B51B81B
3-802/0323-802/0323-802/0323-802/0323-802/032
11222
6345363646
0506070707
86444
0101
666
------636373
------828282
---------------
------050505
------030303
---------------
------
888
------010101
---------------
------010101
------010101
---------------
Z0C-1S5HC60C90C51C81C
3-0643-0643-0643-0643-064
11111
9182232333
5253535353
018888
0101010101
---------------
---------------
---------------
---------------
---------------
---------------
---------------
---------------
---------------
---------------
---------------
---------------
Manual 2100-455APage 8 of 25
SHIPPING DAMAGE
Upon receipt of equipment, the carton should be
checked for external signs of shipping damage. If
damage is found, the receiving party must contact the
last carrier immediately, preferably in writing,
requesting inspection by the carrier’s agent.
GENERAL
The equipment covered in this manual is to be installed
by trained, experienced service and installation
technicians.
The refrigerant system is completely assembled and
charged. All internal wiring is complete.
The unit is designed for use with or without duct work.
Flanges are provided for attaching the supply and return
ducts.
These instructions explain the recommended method to
install the air cooled self-contained unit and the
electrical wiring connections to the unit.
These instructions and any instructions packaged with
any separate equipment, required to make up the entire
air conditioning system should be carefully read before
beginning the installation. Note particularly “Starting
Procedure” and any tags and/or labels attached to the
equipment.
While these instructions are intended as a generalrecommended guide, they do not supersede any nationaland/or local codes in any way. Authorities havingjurisdiction should be consulted before the installation ismade. See Page 3 for information on codes andstandards.
Size of unit for a proposed installation should be basedon heat loss calculation made according to methods ofAir Conditioning Contractors of America (ACCA). Theair duct should be installed in accordance with theStandards of the National Fire Protection Associationfor the Installation of Air Conditioning and VentilatingSystems of Other Than Residence Type, NFPA No.90A, and Residence Type Warm Air Heating and AirConditioning Systems, NFPA No. 90B. Where localregulations are at a variance with instructions, installershould adhere to local codes.
DUCT WORK
Any heat pump is more critical of proper operatingcharge and an adequate duct system than a straight airconditioning unit. All duct work, supply and return,must be properly sized for the design airflowrequirement of the equipment. Air ConditioningContractors of America (ACCA) is an excellent guide toproper sizing. All duct work or portions thereof not inthe conditioned space should be properly insulated inorder to both conserve energy and prevent condensationor moisture damage.
Design the duct work according to methods given by theAir Conditioning Contractors of America (ACCA).When duct runs through unheated spaces, it should beinsulated with a minimum of one inch of insulation.Use insulation with a vapor barrier on the outside of theinsulation. Flexible joints should be used to connect theduct work to the equipment in order to keep the noisetransmission to a minimum.
These units are suitable for 0 inch clearance tocombustible material. See Wall Mounting Instructionsand Figures 3, 4, 5, 6 & 7 for further details.
Ducts through the walls must be insulated and all jointstaped or sealed to prevent air or moisture entering thewall cavity.
Some installations may not require any return air duct.A metallic return air grille is required with installationsnot requiring a return air duct. The spacing betweenlouvers on the grille shall not be larger than 5/8 inch.
NOTE: If no return air duct is used, applicableinstallation codes may limit this cabinet toinstallation only in a single story structure.
Any grille that meets with 5/8 inch louver criteria maybe used. It is recommended that Bard Return Air GrilleKit RG2 through RG5 or RFG2 through RFG5 beinstalled when no return duct is used. Contactdistributor or factory for ordering information. If usinga return air filter grille, filters must be of sufficient sizeto allow a maximum velocity of 400 fpm.
FILTERS
A 2-inch pleated filter is supplied with each unit. Thefilter slides into position making it easy to service. Thisfilter can be serviced from the outside by removing the
filter access door.
CONDENSATE DRAIN – EVAPORATOR
A plastic drain hose extends from the drain pan at the
top of the unit down to the unit base. There are
openings in the unit base for the drain hose to pass
through. In the event the drain hose is connected to a
drain system of some type, it must be an open or vented
type system to assure proper drainage.
Manual 2100-455APage 9 of 25
INSTALLATION INSTRUCTIONS
WALL MOUNTING INFORMATION
1. Two holes for the supply and return air openings
must be cut through the wall as shown in Figure 3.
2. On wood frame walls, the wall construction must be
strong and rigid enough to carry the weight of the
unit without transmitting any unit vibration.
3. Concrete block walls must be thoroughly inspected
to insure that they are capable of carrying the weight
of the installed unit.
MOUNTING THE UNIT
1. These units are secured by wall mounting brackets
which secure the unit to the outside wall surface at
both sides. A bottom mounting bracket is provided
for ease of installation, but is not required.
2. The unit itself is suitable for 0 inch clearance. If a
combustible wall use a minimum of 30" x 10"
dimensions for sizing. However, it is generally
recommended that a 1-inch clearance is used for
ease of installation. The supply air opening would
then be 32" x 12". See Figures 3 and 4 for details.
3. Locate and mark lag bolt locations and bottom
mounting bracket location. See Figure 3.
4. Mount bottom mounting bracket.
5. Hook top rain flashing under back bend of top. Top
rain flashing is shipped with unit attached to back of
unit on the right side.
6. Position unit in opening and secure with 5/16 lag
bolts; use 3/4 inch diameter flat washers on the lag
bolts.
7. Secure rain flashing to wall and caulk across entire
length of top. See Figure 3.
8. For additional mounting rigidity, the return air and
supply air frames or collars can be drilled and
screwed or welded to the structural wall itself
(depending upon wall construction). Be sure to
observe required clearance if combustible wall.
9. On side-by-side installations, maintain a minimum
of 20 inches clearance on right side to allow access
to control panel and heat strips, and to allow proper
airflow to the outdoor coil. Additional clearance
may be required to meet local or national codes.
Manual 2100-455APage 10 of 25
7
0" m
in.
0" m
in.
"6
8
13 8
"
Uni
t Mou
ntin
g
Ret
urn
Ope
ning
Sup
ply
Ope
ning
Hol
es, 1
2 pl
aces
(Ins
tall
befo
re u
nit)
Bot
tom
Wal
l Bra
cket
Wal
l
B
43"
3
E
8
30"
16"
16"
16"
16"
16"
16"
C
8"
16"
C
16"
16"
16"
16"
"
D
A
16
5
D
Wall Section
MIS
-220
9
Ope
ning
Sup
ply
Duc
t
Acc
ess
Pan
elR
etur
n A
ir
Hea
ter
Opt
iona
lT
op O
utle
t
Rai
n F
lash
ing
(sup
plie
d)
flang
es Top
App
ly a
bea
d of
cau
lkal
ong
entir
e le
ngth
of t
opan
d be
hind
sid
e m
ount
ing
Foa
m
"CH
3S1"
Wal
l Mou
ntin
g In
stru
ctio
nsA
BC
DE
RE
QU
IRE
D D
IM. T
O M
AIN
TA
IN 0
"M
IN. C
LEA
RA
NC
E F
RO
MC
OM
BU
ST
IBLE
MA
TE
RIA
LS30
106
1/2
16
RE
QU
IRE
D D
IM. T
O M
AIN
TA
INO
PT
ION
AL
1" C
LEA
RA
NC
E F
RO
MC
OM
BU
ST
IBLE
MA
TE
RIA
LS32
125
1/2
25
FIG
UR
E 3
MO
UN
TIN
G IN
ST
RU
CT
ION
S
Manual 2100-455APage 11 of 25
FIG
UR
E 4
MO
UN
TIN
G IN
ST
RU
CT
ION
S
Manual 2100-455APage 12 of 25
FIGURE 5
ELECTRIC HEAT CLEARANCE
RECOMMENDED1" OPTIONAL CLEARANCE
Duct
Outside Sheeting
Unit
Inside Sheeting
Wall Frame
Supply Air
Typical Building
Supply Air DuctFlange of Wall
MIS-2210
Side section view of supply airduct for wall mounted unit showing
0" clearance to combustible surfaces.
Note: This unit is approved for 0" clearance, but the optional 1" clearance is recommended. See Figures 3 & 4.
Manual 2100-455APage 13 of 25
FIGURE 6
WALL MOUNTING INSTRUCTIONS
FIGURE 7
WALL MOUNTING INSTRUCTIONS
MIS-2024
steel siding wall
Interior finished wall
Return opening
structural steel2x4's, 2x6's, and/orFraming material:
unit before installing.
"CH" Unit
flashing. Attach toFactory supplied rain
before installing unit.bracket. Mount on wall
when framing wall to support unit.
Supply opening
Exterior wood or
Bottom mounting
Follow all local building codes!
1" clearance
1" clearance
9 13/16"
6 1/8"
15 7/8"
29 7/8"
51 1/4"
44 7/8"
Supply Opening
Return Opening
These structuralmembers must beable to support theentire weight of theunit.
Locate stud to matchspacing for rest of wall.A second member maybe required for somewalls.
!Follow all local building codeswhen framing wall to support unit.
CL
MIS-2025
Manual 2100-455APage 14 of 25
FIGURE 8
COMMON WALL MOUNTING INSTALLATIONS
Isolation CurbWM1CF5-X
Supply Air
Return AirSilencer WAPR11-X
RETURN AIR
Free Blow Supply Plenum WAFB51-X
Out
side
Wal
l
Unit (outside)
Note: duct maybe in attic or below rafters as shown.
Note: direction of return
Rafters
Supply Air
Return Air
Out
side
Wal
l
Unit (outside)
Rafters
Supply Air
Return Air
Unit (outside)
Finished Ceiling
Finished Ceiling
Finished Ceiling
Supply Air
Rafters
Out
side
Wal
l
False Wall Installation
Fal
se W
all
Return Air
Ret
urn
Air
for lowest sound level as shown.
Grille
Grille
below rafters as shown.Note: duct maybe in attic or
grille louvers is pointed down
Grille
Duct
Free Air Flow - No Duct
Ducted Supply - Return At Unit
Duct
MIS-2027
Wall Sleeve
Free Air Flow - No DuctLow Sound With Acoustical Plenums
And Isolation Curbs
Manual 2100-455APage 15 of 25
Nine (9) wires should be run from thermostat subbase tothe 24V terminal board in the unit. A nine conductor,18 gauge copper color-coded thermostat cable isrecommended. The connection points are shown inFigure 10.
TABLE 3
THERMOSTAT WIRE SIZE
remrofsnarTAV ALF eguaGeriW
mumixaMecnatsiDteeFnI
55 3.2
eguag02eguag81eguag61egaug41egaug21
5406001061052
IMPORTANT
Only the thermostat combinations as shownabove will work with this equipment.
C
G Y2
G
E
Rc
TERMINAL BLOCK
L
UNIT LOW VOLTAGE
L
Y1 W1
RC
A1
Y1
Y B
BARD PART #8403-052
W1 W3W2 DH
W1
G O1
BC
Y2
T7652H1000 THERMOSTAT
B
Y1
W3/A1
Rh
Factory Jumper
1F93-380 THERMOSTATBARD PART #8403-049
MIS-2026 A
R W2 E
FIGURE 10
UNIT 24V TERMINAL BOARD
WIRING – MAIN POWER
Refer to the unit rating plate for wire sizing informationand maximum fuse or “HACR” type circuit breakersize. Each outdoor unit is marked with a “MinimumCircuit Ampacity”. This means that the field wiringused must be sized to carry that amount of current.Depending on the installed KW of electric heat, theremay be two field power circuits required. If this is thecase, the unit serial plate will so indicate. All modelsare suitable only for connection with copper wire. Eachunit and/or wiring diagram will be marked “Use CopperConductors Only”. These instructions must be adheredto. Refer to the National Electrical Code (NEC) forcomplete current carrying capacity data on the variousinsulation grades of wiring material. All wiring mustconform to NEC and all local codes.
The electrical data lists fuse and wire sizes (75° Ccopper) for all models including the most commonlyused heater sizes. Also shown are the number of fieldpower circuits required for the various models withheaters.
The unit rating plate lists a “Maximum Time DelayRelay Fuse” or “HACR” type circuit breaker that is tobe used with the equipment. The correct size must beused for proper circuit protection and also to assure thatthere will be no nuisance tripping due to the momentaryhigh starting current of the compressor motor.
The disconnect access door on this unit may be lockedto prevent unauthorized access to the disconnect. Toconvert for the locking capability, bend the tab locatedin the bottom left hand corner of the disconnect openingunder the disconnect access panel straight out. This tabwill now line up with the slot in the door. When shut, apadlock may be placed through the hole in the tabpreventing entry.
See “Start Up” section for important information onthree phase scroll compressor start ups.
WIRING – LOW VOLTAGE WIRING
230 / 208V, 1 phase and 3 phase equipment dualprimary voltage transformers. All equipment leaves thefactory wired on 240V tap. For 208V operation,reconnect from 240V to 208V tap. The acceptableoperating voltage range for the 240 and 208V taps are:
TAP RANGE
240 253 – 216
208 220 – 187
NOTE: The voltage should be measured at the fieldpower connection point in the unit and whilethe unit is operating at full load (maximumamperage operating condition).
FIGURE 9
COMMON WALL MOUNTING INSTALLATIONS
Out
side
Wal
l
Clo
set W
all
Clo
set W
all
Grille
Return Air
Ret
urn
Air
Supply Air Duct
Finished Ceiling
Raised Closet Floor
Rafters
Wall Sleeve
Closet Installation
Unit (outside)
Note: duct maybe in attic or below rafters as shown.
MIS-2240
Grille
Manual 2100-455APage 16 of 25
LOW VOLTAGE CONNECTIONS
FOR DDC CONTROL
Fan Only Energize G
Cooling Mode 1st Stage Energize Y, G
Cooling Mode 2nd Stage Energize Y, Y1, G
Heat Pump Heating 1st Stage Energize Y, G, B
Heat Pump Heating 2nd Stage Energize Y, Y1, G, B
3rd Stage Heating Energize G, W2, Y, B, Y1
w/Heat Pump (if employed)
Ventilation Energize G, O1
Emergency Heat Energize B, W2, E, G
LOW VOLTAGE CONNECTIONS
These units use a grounded 24 volt AC low voltage
circuit and require at least a 2 stage heating and a 2
stage cooling thermostat.
The “R” terminal is the hot terminal and the “C”
terminal is grounded.
“G” terminal is the fan input.
“Y” terminal is the compressor Stage 1 input.
“Y1” terminal is the compressor Stage 2 input.
“B” terminal is the reversing valve input. The reversing
valve must be energized for heating mode.
“R” terminal is 24 VAC hot.
“C” terminal is 24 VAC grounded.
“L” terminal is compressor lockout output. This
terminal is activated on a high or low pressure trip by
the electronic heat pump control. This is a 24 VAC
output.
“W2” terminal is second stage heat (if equipped).
“O1” terminal is the ventilation input. This terminal
energizes any factory installed ventilation option.
“E” terminal is the emergency heat input. This terminal
energizes the emergency heat relay if equipped.
NOTE: For total and proper control using DDC, a
total of 7 controlled outputs are required (6 if
no ventilation system is installed). For proper
system operation under Emergency Heat
conditions where the compressor needs to be
deactivated, the B-W2-E outputs need to be
energized. Removing the Y (compressor) signal
alone turns the compressor off, but does not
activate the additional circuitry embedded in
the heat pump for proper and complete
operation.
TABLE 4
WALL THERMOSTAT
tatsomrehT serutaeFtnanimoderP
940-3048)083-39F1(
taeh.gts2;looc.gts2cinortcelEelbammargorP
revoegnahclaunaMrootuA
250-3048taeh.gts3;looc.gts2cinortcelEelbammargorP
revoegnahclaunaMrootuA
START UP
These units require R-410A refrigerant & Polyol Ester oil.
APPLICATION:
1. Use separate service and manufacturing equipment
to avoid cross contamination of oil and refrigerants.
2. Use recovery equipment rated for R-410A
refrigerant.
3. Use manifold gauges rated for R-410A (800 psi/250
psi low).
4. R-410A is a binary blend of HFC-32 and HFC-125.
5. R-410A is nearly azeotropic - similar to R-22 and
R-12. Although nearly azeotropic, charge with
liquid refrigerant.
6. R-410A operates at 40-70% higher pressure than
R-22, and systems designed for R-22 cannot
withstand this higher pressure.
7. R-410A has an ozone depletion potential of zero,
but must be reclaimed due to its global warming
potential.
8. R-410A compressors use Polyol Ester oil.
9. Polyol Ester oil is hygroscopic; it will rapidly
absorb moisture and strongly hold this moisture in
the oil.
10. A liquid line dryer must be used - even a deep
vacuum will not separate moisture from the oil.
11. Limit atmospheric exposure to 15 minutes -
MAXIMUM.
12. If compressor removal is necessary, always plug
compressor immediately after removal. Purge with
small amount of nitrogen when inserting plugs.
Manual 2100-455APage 17 of 25
START UP CONT’D.
SAFETY PRACTICES:
1. Never mix R-410A with other refrigerants.
2. Use gloves and safety glasses, Polyol Ester oils can
be irritating to the skin, and liquid refrigerant will
freeze the skin.
3. Never use air and R-410A to leak check; the
mixture may become flammable.
4. Do not inhale R-410A – the vapor attacks the
nervous system, creating dizziness, loss of
coordination and slurred speech. Cardiac
irregularities, unconsciousness and ultimate death
can result from breathing this concentration.
5. Do not burn R-410A. This decomposition produces
hazardous vapors. Evacuate the area if exposed.
6. Use only cylinders rated DOT4BA/4BW 400.
7. Never fill cylinders over 80% of total capacity.
8. Store cylinders in a cool area, out of direct sunlight.
9. Never heat cylinders above 125°F.
10. Never trap liquid R-410A in manifold sets, gauge
lines or cylinders. R-410A expands significantly at
warmer temperatures. Once a cylinder or line is full
of liquid, any further rise in temperature will cause
it to burst.
IMPORTANT INSTALLER NOTEFor improved start-up performance, wash the indoor coil
with a dish washing detergent.
PRESSURE SERVICE PORTSR-410A requires high pressure hose connections and
gauges. High and Low pressure service ports are
installed on all units so that the system operating
pressures can be observed. Pressure tables can be found
later in the manual covering all models on both cooling
and heating cycles. It is imperative to match the correct
pressure table to the unit by model number.
HIGH & LOW PRESSURE SWITCHAll models are supplied with a remote reset high and low
pressure switch. If tripped, this pressure switch may be
reset by turning the thermostat off then back on again.
High/Low Pressure control provides protection for the
compressor. In the event system pressures go above 540
PSI or below 35 PSI, in either cooling or heating mode,
the compressor will be stopped. This will activate the
“L” terminal of the low voltage terminal strip. This
terminal can be used for remote indication of a pressure
lockout. The lockout circuit will hold compressor off
line. When the system problem is corrected, the unit
operation can be restored by turning the main power
supply off and then back on, or reset the room thermostat.
The low pressure control has a bypass to eliminate
nuisance lockout on cold start up.
The bypass timer should be set to 200 seconds, and this
is to assure there is no nuisance tripping of the low-
pressure control during startup in heating mode under
cold weather conditions. See Figure 10:
FIGURE 11
LOW PRESSURE CONTROL BYPASS TIMER
THREE PHASE SCROLL COMPRESSORSTART UP INFORMATIONScroll compressors, like several other types of
compressors, will only compress in one rotational
direction. Direction of rotation is not an issue with
single phase compressors since they will always start
and run in the proper direction.
However, three phase compressors will rotate in either
direction depending upon phasing of the power. Since
there is a 50-50 chance of connecting power in such a
way as to cause rotation in the reverse direction,
verification of proper rotation must be made. All three
phase units incorporate a phase monitor to ensure proper
field wiring. See the “Phase Monitor” section later in
this manual.
Verification of proper rotation must be made any time a
compressor is changed or rewired. If improper rotation
is corrected at this time there will be no negative impact
on the durability of the compressor. However, reverse
operation for over one hour may have a negative impact
on the bearing due to oil pump out.
NOTE: If compressor is allowed to run in reverse
rotation for several minutes, the compressor’s
internal protector will trip.
All three phase ZR3 compressors are wired identically
internally. As a result, once the correct phasing is
determined for a specific system or installation,
connecting properly phased power leads to the same
Fusite terminal should maintain proper rotation
direction.
Manual 2100-455APage 18 of 25
Verification of proper rotation direction is made by
observing that suction pressure drops and discharge
pressure rises when the compressor is energized. Reverse
rotation also results in an elevated sound level over that
with correct rotations, as well as, substantially reduced
current draw compared to tabulate values.
The direction of rotation of the compressor may be
changed by reversing any two line connections to the unit.
PHASE MONITORAll units with three phase compressors are equipped with
a 3 phase line monitor to prevent compressor damage due
to phase reversal.
The phase monitor in this unit is equipped with two
LEDs. If the Y signal is present at the phase monitor and
phases are correct, the green LED will light. If phases are
reversed, the red fault LED will be lit and compressor
operation is inhibited.
If a fault condition occurs, reverse two of the supply leads
to the unit. Do not reverse any of the unit factory wires
as damage may occur.
SERVICE HINTS1. Caution homeowner to maintain clean air filters at all
times. Also, not to needlessly close off supply and
return air registers. This reduces airflow through the
system, which shortens equipment service life as well
as increasing operating costs.
2. Switching to heating cycle at 75° F or higher outside
temperature may cause a nuisance trip of the remote
reset high pressure switch. Turn thermostat off then
on to reset the high pressure switch.
3. The heat pump wall thermostats perform multiple
functions. Be sure that all function switches are
correctly set for the desired operating mode before
trying to diagnose any reported service problems.
4. Check all power fuses or circuit breakers to be sure
they are the correct rating.
5. Periodic cleaning of the outdoor coil to permit full
and unrestricted airflow circulation is essential.
SEQUENCE OF OPERATION
COOLING STAGE 1 – Circuit R-Y makes at thermostat
pulling in compressor contactor, starting the compressor
and outdoor motor. The G (indoor motor) circuit is
automatically completed on any call for cooling operation
or can be energized by manual fan switch on subbase of
constant air circulation.
COOLING STAGE 2 – Circuit R-Y1 makes at the
thermostat energizing the 2nd stage solenoid in the
compressor. Default position is not energized.
Compressor will run at low capacity until this solenoid is
energized.
HEATING STAGE 1 – A 24V solenoid coil on reversing
valve controls heating cycle operation. Two thermostat
options, one allowing “Auto” changeover from cycle to
cycle and the other constantly energizing solenoid coil
during heating season and thus eliminating pressure
equalization noise except during defrost, are to be used.
On “Auto” option a circuit is completed from R-W1 and
R-Y on each heating “on” cycle, energizing reversing
valve solenoid and pulling in compressor contactor
starting compressor and outdoor motor. R-G also make
starting indoor blower motor. Heat pump heating cycle
now in operation. The second option has no “Auto”
changeover position, but instead energizes the reversing
valve solenoid constantly whenever the system switch on
subbase is placed in “Heat” position, the “B” terminal
being constantly energized from R. A thermostat demand
for Stage 1 heat completes R-Y circuit, pulling in
compressor contactor starting compressor and outdoor
motor. R-G also make starting indoor blower motor.
HEATING STAGE 2 – Circuit R-Y2 makes at the
thermostat energizing the 2nd stage solenoid in the
compressor.
COMPRESSOR CURRENT & PRESSURECONTROL MODULE
The compressor control module monitors compressor
current and pressure and prevents internal overload trips
due to low voltage or extremely high ambient
temperatures by de-energizing the full capacity
compressor solenoid. The control monitors current to the
compressor and discharge pressure. If current is sensed
that is in excess of 93% of the compressor, maximum
continuous current rating or pressure is sensed greater
than 525 PSI, the compressor control module de-
energizes for a time as determined by the time
potentiometer on the compressor control module. This
will drop the current draw and pressure and allow the
compressor to run at 75 percent of capacity rather than
not at all. Once the time period has elapsed the full
capacity compressor solenoid will re-energize and try
again to run at full capacity. If the pressure or current is
exceeded again, the coil will again de-energize. This
sequence will repeat until the ambient temperature drops
or the line voltage increases enough that the trip values
are not exceeded.
The relay on the compressor control module is a single
pole double throw relay. The full capacity compressor
solenoid connects to the common terminal of the relay.
Once current is sensed by the compressor control module,
the relay closes and the second stage cooling call (if
present) is sent to the full capacity compressor solenoid.
This sequence prevents damage to the full capacity
compressor solenoid by ensuring that the solenoid is not
energized when the compressor is not running. A brief
time delay in this sequence also prevents locked rotor
amperage during start-up from tripping the device and
engaging the time delay period.
Manual 2100-455APage 19 of 25
DEFROST CYCLE
The defrost cycle is controlled by temperature and timeon the solid state heat pump control. See Figure 12.
When the outdoor temperature is in the lower 40° Ftemperature range or colder, the outdoor coiltemperature is 32° F or below. This coil temperature issensed by the coil temperature sensor mounted near thebottom of the outdoor coil. Once coil temperaturereaches 30° F or below, the coil temperature sensorsends a signal to the control logic of the heat pumpcontrol and the defrost timer will start.
After 60 minutes at 30° F or below, the heat pumpcontrol will place the system in the defrost mode.
During the defrost mode, the refrigerant cycle switchesback to the cooling cycle, the outdoor motor stops,electric heaters are energized, and hot gas passingthrough the outdoor coil melts any accumulated frost.When the temperature rises to approximately 57° F, thecoil temperature sensor will send a signal to the heatpump control which will return the system to heatingoperations automatically.
If some abnormal or temporary condition such as a highwind causes the heat pump to have a prolonged defrostcycle, the heat pump control will restore the system toheating operation automatically after 10 minutes.
The heat pump defrost control board has an option of30, 60 or 90-minute setting. All models are shippedfrom the factory on the 60-minute pin. If specialcircumstances require a change to another time, removethe wire from the 60-minute terminal and reconnect tothe desired terminal. The manufacturer'srecommendation is for 60-minute defrost cycles. Referto Figure 12.
There is a cycle speed up jumper on the control. Thiscan be used to reduce the time between defrost cycleoperation without waiting for time to elapse.
Use a small screwdriver or other metallic object, oranother 1/4 inch QC, to short between the SPEEDUPterminals to accelerate the HPC timer and initiatedefrost.
Be careful not to touch any other terminals with theinstrument used to short the SPEEDUP terminals. Itmay take up to 10 seconds with the SPEEDUP terminalsshorted for the speedup to be completed and the defrostcycle to start.
As soon as the defrost cycle kicks in remove theshorting instrument from the SPEEDUP terminals.Otherwise the timing will remain accelerated and runthrough the 1-minute minimum defrost length sequencein a matter of seconds and will automatically terminatethe defrost sequence.
There is an initiate defrost jumper (sen jump) on thecontrol that can be used at any outdoor ambient duringthe heating cycle to simulate a 0° coil temperature. Thiscan be used to check defrost operation of the unitwithout waiting for the outdoor ambient to fall into thedefrost region.
By placing a jumper across the SEN JMP terminals (a1/4 inch QC terminal works best) the defrost sensormounted on the outdoor coil is shunted out and willactivate the timing circuit. This permits the defrostcycle to be checked out in warmer weather conditionswithout the outdoor temperature having to fall into thedefrost region.
In order to terminate the defrost test the SEN JMPjumper must be removed. If left in place too long thecompressor could stop due to the high pressure controlopening because of high pressure condition created by
operating in the cooling mode withoutdoor fan off. Pressure will risefairly fast as there is likely noactual frost on the outdoor coil inthis artificial test condition.
There is also a 5-minute compressortime delay function built into theHPC. This is to protect thecompressor from short cyclingconditions. In some instances, it ishelpful to the service technician tooverride or speed up this timingperiod, and shorting out theSPEEDUP terminals for a fewseconds can do this.
FIGURE 12
DEFROST CONTROL BOARD
Manual 2100-455APage 20 of 25
TROUBLESHOOTING
SOLID STATE HEAT PUMP CONTROLTROUBLESHOOTING PROCEDURE
1. Turn on AC power supply to indoor and outdoor
units.
2. Turn thermostat blower switch to fan on. The indoor
blower should start. (If it doesn’t, troubleshoot
indoor unit and correct problem.)
3. Turn thermostat blower switch to auto position.
Indoor blower should stop.
4. Set system switch to heat or cool. Adjust thermostat
to call for heat or cool. The indoor blower,
compressor, and outdoor fan should start.
NOTE: If there was no power to 24 volt transformer,
the compressor and outdoor fan motor will not
start for 5 minutes. This is because of the
compressor short cycle protection.
TABLE 5
TROUBLESHOOTING
MOTPMYS SESUACELBISSOP KCEHCOTTAHW RIAPERROKCEHCOTWOH
rosserpmoCtonseodrotcatnoc
rognitaeh(ezigrene.)gnilooc
gniriwtiucriclortnoC tinutanoitcennocRrofkcehCC-Rneewtebtlov42dna
taehrewopottinuroodtuootnoitcennocRnuR.lortnocpmup
tuokcolrosserpmoC .1
.2
neewtebV42rofkcehC.lortnocpmuptaehnoC-1L
hgihssorcakcehChctiwserusserp
.1
.2
tatsomrehtnrut,C-1LneewtebegatlovonfIerusserphgihteserotniaganodnaffo
.hctiwstonlliwdnaneposihctiwserusserphgihfI
.hctiwserusserphgihecalper,teser
elcyctrohsrosserpmoCnoitcetorp
C-CCneewtebV42rofkcehC.lortnocpmuptaehnoC-Ydna
pudeepsrepmuj,C-CCneewtebegatlovonfIdluohsrewopsdnoces01nihtiwdna,lanimret
pudeepsevomeR.C-CCneewtebraeppa.sdnoces01retfarepmuj
lortnocpmuptaeHevitcefed
elbissoprehtollakcehC.560-0012launaM.sesuac
.lortnocpmuptaehecalpeR
evitcefedrotcatnoC liocdetrohsroneporofkcehC.gnidniw
.rotcatnocecalpeR
tongnisahprewoPtcerroc
esahpnoDELderrofkcehC.)ylnostinuesahp3(rotinom
.tinuehtotsdaelrewopowthctiwS
rotomroodtuonaFnurtonseod
gnitaehrognilooc(gnirudtpecxe
.)tsorfed
evitcefedrotoM detrohsroneporofkcehC.gnidniwrotom
.rotomecalpeR
roticapacrotoMevitcefed
kcehC.gnitarroticapackcehC.roticapacdetrohsroneporof
.roticapacecalpeR
lortnocpmuptaeHevitcefed
noyalernafssorcakcehC.)CN-moC(lortnocpmuptaeh
.lortnocpmuptaehecalpeR
evlavgnisreveRezigrenetonseod
.)ylnognitaeh(
dionelosevlavgnisreveRevitcefedlioc
.liocdetrohsroneporofkcehC .liocdionelosecalpeR
lortnocpmuptaeHevitcefed
C-VRneewtebV42rofkcehC.C-Bdna
.1
.2.gniriwtiucriclortnockcehC.lortnocpmuptaehecalpeR
otniogtonlliwtinUtsorfed
.)ylnognitaeh(
rorosneserutarepmeTlortnocpmuptaeh
evitcefed
erutarepmettcennocsiDrepmujdnadraobmorfrosnesdnaslanimretpudeepsssorca
sihT.slanimretpmujnesogottinuehtesuacdluohs
nihtiwelcyctsorfedahguorht.etunimeno
.1
.2
ecalper,elcyctsorfedhguorhtseogtinufI.rosneserutarepmet
,elcyctsorfedhguorhtogtonseodtinufI.lortnocpmuptaehecalper
emoctonlliwtinUtsorfedfotuo.)ylnognitaeh(
rorosneserutarepmeTlortnocpmuptaeh
evitcefed
pudeepsssorcarepmuJesuacdluohssihT.slanimret
tsorfedfotuoemocottinueht.etunimenonihtiw
.1
.2
ecalper,elcyctsorfedfotuosemoctinufI.rosneserutarepmet
,elcyctsorfedfotuoemoctonseodtinufI.lortnocpmuptaehecalper
Manual 2100-455APage 21 of 25
CHECKING TEMPERATURE SENSOROUTSIDE UNIT CIRCUIT
1. Disconnect temperature sensor from board and from
outdoor coil.
2. Use an ohmmeter and measure the resistance of the
sensor. Also use ohmmeter to check for short or
open.
3. Check resistance reading to chart of resistance use
sensor ambient temperature. (Tolerance of part is
± 10%)
4. If sensor resistance reads very low, then sensor is
shorted and will not allow proper operation of the
heat pump control.
5. If sensor is out of tolerance, shorted, open, or reads
very low ohms then it should be replaced.
F R F R F R
-25.0
-24.0
-23.0
-22.0
-21.0
-20.0
-19.0
-18.0
-17.0
-16.0
-15.0
-14.0
-13.0
-12.0
-11.0
-10.0
-9.0
-8.0
-7.0
-6.0
-5.0
-4.0
-3.0
-2.0
-1.0
0.0
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
11.0
12.0
13.0
14.0
15.0
16.0
17.0
18.0
19.0
20.0
21.0
22.0
23.0
24.0
196871
190099
183585
177318
171289
165487
159904
154529
149355
144374
139576
134956
130506
126219
122089
118108
114272
110575
107010
103574
100260
97064
93981
91008
88139
85371
82699
80121
77632
75230
72910
70670
68507
66418
64399
62449
60565
58745
56985
55284
53640
52051
50514
49028
47590
46200
44855
43554
42295
41077
25.0
26.0
27.0
28.0
29.0
30.0
31.0
32.0
33.0
34.0
35.0
36.0
37.0
38.0
39.0
40.0
41.0
42.0
43.0
44.0
45.0
46.0
47.0
48.0
49.0
50.0
51.0
52.0
53.0
54.0
55.0
56.0
57.0
58.0
59.0
60.0
61.0
62.0
63.0
64.0
65.0
66.0
67.0
68.0
69.0
70.0
71.0
72.0
73.0
74.0
39898
38757
37652
36583
35548
34545
33574
32634
31723
30840
29986
29157
28355
27577
26823
26092
25383
24696
24030
23384
22758
22150
21561
20989
20435
19896
19374
18867
18375
17898
17434
16984
16547
16122
15710
15310
14921
14544
14177
13820
13474
13137
12810
12492
12183
11883
11591
11307
11031
10762
75.0
76.0
77.0
78.0
79.0
80.0
81.0
82.0
83.0
84.0
85.0
86.0
87.0
88.0
89.0
90.0
91.0
92.0
93.0
94.0
95.0
96.0
97.0
98.0
99.0
100.0
101.0
102.0
103.0
104.0
105.0
106.0
107.0
108.0
109.0
110.0
111.0
112.0
113.0
114.0
115.0
116.0
117.0
118.0
119.0
120.0
121.0
122.0
123.0
124.0
10501
10247
10000
9760
9526
9299
9077
8862
8653
8449
8250
8057
7869
7686
7507
7334
7165
7000
6840
6683
6531
6383
6239
6098
5961
5827
5697
5570
5446
5326
5208
5094
4982
4873
4767
4663
4562
4464
4367
4274
4182
4093
4006
3921
3838
3757
3678
3601
3526
3452
TEMPERATURE F VS RESISTANCE R OF TEMPERATURE
Manual 2100-455APage 22 of 25
REMOVAL OF FAN SHROUD
1. Disconnect all power to the unit.
2. Remove the screws holding both grilles, one on each
side of unit, and remove grilles.
3. Remove screws holding fan shroud to condenser and
bottom. Nine (9) screws.
4. Unwire condenser fan motor.
5. Slide complete motor, fan blade, and shroud
assembly out the left side of the unit.
6. Service motor/fan as needed.
7. Reverse steps to reinstall.
R-410A
REFRIGERANT CHARGE
The correct system R-410A charge is shown on the unit
rating plate. Optimum unit performance will occur with
a refrigerant charge shown on the unit serial plate.
If correct charge is in doubt, recover the refrigerant and
recharge per the charge on the unit rating plate. See
Table 7 for proper subcooling levels for evaluation of
proper charge.
TABLE 6
FAN BLADE DIMENSION
ledoM AnoisnemiD
LLA 0.1
COMPRESSOR SOLENOID
A nominal 24-volt direct current coil activates the
internal compressor solenoid. The input control circuit
voltage must be 18 to 28 volt ac. The coil power
requirement is 20 VA. The external electrical
connection is made with a molded plug assembly (PN
029-0311-00). This plug contains a full wave rectifier
to supply direct current to the unloader coil.
Compressor Solenoid Test Procedure – If it is
suspected that the unloader is not working, the
following methods may be used to verify operation.
1. Operate the system and measure compressor
amperage. Cycle the compressor solenoid on and
off at ten-second intervals. The compressor
amperage should go up or down at least 25 percent.
2. If step one does not give the expected results, shut
unit off. Apply 18 to 28 volt ac to the solenoid
molded plug leads and listen for a click as the
solenoid pulls in. Remove power and listen for
another click as the solenoid returns to its original
position.
3. If clicks can’t be heard, shut off power and remove
the control circuit molded plug from the compressor
and measure the solenoid coil resistance. The
resistance should be 32 to 60 ohms depending on
compressor temperature.
4. Next, check the molded plug.
Voltage check: Apply control voltage to the plug wires (18
to 28 volt ac). The measured dc voltage at the female
connectors in the plug should be around 15 to 27 vdc.
Resistance check: Measure the resistance from the end of
one molded plug lead to either of the two female
connectors in the plug. One of the connectors should read
close to zero ohms, while the other should read infinity.
Repeat with other wire. The same female connector as
before should read zero, while the other connector again
reads infinity. Reverse polarity on the ohmmeter leads and
repeat. The female connector that read infinity previously
should now read close to zero ohms.
Replace plug if either of these test methods does not
show the desired results.
FAN BLADE SETTING DIMENSIONS
Shown in Figure 13 are the correct fan blade setting
dimensions for proper air delivery across the outdoor
coil.
Any service work requiring removal or adjustment in
the fan and/or motor area will require that the
dimensions below be checked and blade adjusted in or
out on the motor shaft accordingly.
FIGURE 13
FAN BLADE SETTING
Manual 2100-455APage 23 of 25
TABLE 9
MAXIMUM ESP OF OPERATION
deepShgiH
LLA 5.
TABLE 7 1
REFRIGERANT CHARGE - SUBCOOLING LEVEL
GNILOOC GNITAEH
ledoMdetaRwolfriA
DO59erutarepmeT
DO08erutarepmeT
DO74erutarepmeT
DO53erutarepmeT
1S3HC 0011 02-61 91-51 23-82 03-62
1S4HC 0051 22-81 12-71 42-02 91-51
1S5HC 0071 03-62 42-02 53-13 13-72
NOTE: These units are equipped with a variable speed (ECM) indoor motor that automatically adjusts itself to maintainapproximately the same rate of indoor airflow in both heating and cooling, dry and wet coil conditions and at both 230/208 or 460 volts.
1 Maximum ESP (inches WC) shown is with 2" thick disposable filter.
2 Rated CFM for 2nd Stage Operation – required for maximum performance rating.
3 1st Stage – the CFM output on 1st Stage Heating or Cooling.
4 Blower only CFM is the total air being circulated during continuous fan mode.
TABLE 8
INDOOR BLOWER PERFORMANCE
ledoMdetaR
PSE
1
xaMPSE
2
gnilooCegatSdn2gnitaeHegatSdn2
3
gnilooCegatSts1gnitaeHegatSts1
4
ylnOrewolBedoMtneVro
taeHcirtcelE
1S3HC 51. 5. 0011 008 008 0011
1S4HC 2. 5. 0051 0011 058 0071
1S5HC 2. 5. 0071 0031 058 0071
1 Expected subcooling levels during high capacity Stage 2 operation. Above subcooling levels are provided to troubleshoot low
charge or overcharged conditions. If charge is in doubt, evacuate and recharge the unit to the refrigerant charge listed on the
serial plate.
Manual 2100-455APage 24 of 25
TABLE 10
PRESSURE TABLE
TABLE 11
PRESSURE TABLE
GNILOOCYTICAPACHGIH
LEDOMRIANRUTER
ERUTAREPMETERUSSERP 57 oF 08 oF 58 oF 09 oF 59 oF 001 oF 501 oF 011 oF 511 oF
1S3HC
BD°57BW°26
EDISWOLEDISHGIH
431892
431813
431933
531363
731883
831514
041544
341674
641015
BD°08BW°76
EDISWOLEDISHGIH
341603
341623
341843
441273
641893
841624
051654
351884
651325
BD°58BW°27
EDISWOLEDISHGIH
841713
841733
841063
941583
151214
351144
551274
851505
161145
1S4HC
BD°57BW°26
EDISWOLEDISHGIH
131803
331233
531653
731083
831604
931134
931654
041384
041905
BD°08BW°76
EDISWOLEDISHGIH
041613
241043
441563
641093
841614
941244
941864
051594
051225
BD°58BW°27
EDISWOLEDISHGIH
541723
741253
941873
151404
351134
451754
451484
551215
551045
1S5HC
BD°57BW°26
EDISWOLEDISHGIH
031633
131953
131183
231604
431034
531554
731284
831015
041835
BD°08BW°76
EDISWOLEDISHGIH
931543
041863
041193
141614
341144
441764
641494
841325
051255
BD°58BW°27
EDISWOLEDISHGIH
441753
541183
541504
641134
841654
941384
151115
351145
551175
GNILOOCYTICAPACWOL FEERGEDLIOCROODTUOGNIRETNEERUTAREPMETRIA
LEDOMRIANRUTER
ERUTAREPMETERUSSERP 57 oF 08 oF 58 oF 09 oF 59 oF 001 oF 501 oF 011 oF 511 oF
1S3HC
BD°57BW°26
EDISWOLEDISHGIH
931952
041482
141803
241333
341953
541583
741014
941834
151464
BD°08BW°76
EDISWOLEDISHGIH
941662
051192
151613
251243
351863
551593
751124
951944
161674
BD°58BW°27
EDISWOLEDISHGIH
451572
551103
651723
751453
851183
061904
261634
561564
761394
1S4HC
BD°57BW°26
EDISWOLEDISHGIH
731182
731103
931323
041543
141073
341493
441914
641744
741574
BD°08BW°76
EDISWOLEDISHGIH
641882
741903
941133
051453
151973
351404
451034
651854
751784
BD°58BW°27
EDISWOLEDISHGIH
151892
251023
451343
551663
651293
851814
951544
161474
261405
1S5HC
BD°57BW°26
EDISWOLEDISHGIH
631392
731613
931043
141463
241983
341314
441934
541464
541984
BD°08BW°76
EDISWOLEDISHGIH
541003
741423
941943
151373
251993
351424
451054
551674
551205
BD°58BW°27
EDISWOLEDISHGIH
051113
251533
451163
651683
751314
851934
951664
061394
061025
Low side pressure ± 2 PSIG
High side pressure ± 5 PSIG
Tables are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating charge
being in the system, the charge should be removed, system evacuated and recharged to serial plate instruction.
Low side pressure ± 2 PSIG
High side pressure ± 5 PSIG
Tables are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating charge
being in the system, the charge should be removed, system evacuated and recharged to serial plate instruction.
Manual 2100-455APage 25 of 25
TA
BL
E 1
2
PR
ES
SU
RE
TA
BL
E
TA
BL
E 1
3
PR
ES
SU
RE
TA
BL
E
GNI
TA
EH
YTI
CA
PA
CH
GIH
FE
ER
GE
DLI
OC
RO
ODT
UO
GNI
RET
NE
ER
UTA
RE
PM
ETRI
A
LE
DO
MRI
AN
RUT
ER
ER
UTA
RE
PM
ETE
RU
SS
ER
P0o F
5o F01
o F51
o F02
o F52
o F03
o F53
o F04
o F54
o F05
o F55
o F06
o F56
o F
S3H
C°07
EDI
SW
OLE
DIS
HGI
H44092
64592
05003
45303
95403
46903
17813
87033
68643
59463
501783
611314
721244
931574
S4H
C°07
EDI
SW
OLE
DIS
HGI
H45082
55182
65382
65482
75882
16492
66403
47713
38433
49353
801673
321204
141134
061364
S5H
C°07
EDI
SW
OLE
DIS
HGI
H44272
64772
94482
35392
75403
36613
86033
57643
28463
09383
99404
801724
911254
921874
GNI
TA
EH
YTI
CA
PA
CW
OL
FE
ER
GE
DLI
OC
RO
ODT
UO
GNI
RET
NE
ER
UTA
RE
PM
ETRI
A
LE
DO
MRI
AN
RUT
ER
ER
UTA
RE
PM
ETE
RU
SS
ER
P0o F
5o F01
o F51
o F02
o F52
o F03
o F53
o F04
o F54
o F05
o F55
o F06
o F56
o F
S3H
C°07
EDI
SW
OLE
DIS
HGI
H64572
94082
35382
75382
26682
86192
57892
38803
19023
101433
111053
221963
431983
641214
S4H
C°07
EDI
SW
OLE
DIS
HGI
H06072
56172
36172
16372
26872
46482
07392
77303
78613
99133
311843
031763
941883
071114
S5H
C°07
EDI
SW
OLE
DIS
HGI
H85572
65472
65572
85972
06582
46492
07603
77123
58833
59853
601183
911604
331434
841564
Lo
w s
ide
pre
ssu
re ±
2 P
SIG
Hig
h s
ide
pre
ssu
re ±
5 P
SIG
Ta
ble
s a
re b
ase
d u
po
n r
ate
d C
FM
(a
irflo
w)
acro
ss t
he
eva
po
rato
r co
il.
If t
he
re is a
ny d
ou
bt
as t
o c
orr
ect
op
era
tin
g c
ha
rge
be
ing
in
th
e s
yste
m,
the
ch
arg
e s
ho
uld
be
re
mo
ve
d,
syste
m e
va
cu
ate
d a
nd
re
ch
arg
ed
to
se
ria
l p
late
in
str
uctio
n.
Lo
w s
ide
pre
ssu
re ±
2 P
SIG
Hig
h s
ide
pre
ssu
re ±
5 P
SIG
Ta
ble
s a
re b
ase
d u
po
n r
ate
d C
FM
(a
irflo
w)
acro
ss t
he
eva
po
rato
r co
il.
If t
he
re is a
ny d
ou
bt
as t
o c
orr
ect
op
era
tin
g c
ha
rge
be
ing
in
th
e s
yste
m,
the
ch
arg
e s
ho
uld
be
re
mo
ve
d,
syste
m e
va
cu
ate
d a
nd
re
ch
arg
ed
to
se
ria
l p
late
in
str
uctio
n.