GH
21P
BG
H21P
BG
H21P
B
GH21PB
APPLICATION
INSTALATION ON THE BOILER
R
HEATING CONTROLLERSCHŁODNICTWO
OGRZEWANIE
PROPERTIES
The controller for central heatingboilers with pellets burners
The GH21PB is a controller for central heating boilers with burners
prepared to burn wooden pellets. It feeds fuel precisely and controls air
flow into the process of burning.
With the inclusion of the heater device, flue gas sensor and flame sensor
the controller allows automatic flame ignition in case of a fuel burnout.
Controller supervises the process of preparing domestic hot water (DHW)
and allows to operate main heating circuit (central heating - CH cycle).
The GH21PB controller has been fitted for full communication with the
GA03HAroom panel (manufactured by GECO).
Functional visualisation of casing and large readable graphic LCD display.
Single-module construction enables comfortable installation on the boiler .
Possible to meassure flue gas temperature (PT 1000)
Possible of control over two screw feeders: the burner feeder and the container feeder
Anit-stagnation protection for the executive devices - ANTI STOP function
Desinfection of the DHW cycle (Anti Legionella), DHW priority, Summer mode function.
Co-operation with room panel GA03HA (full control of boiler operation from apartament).
Adaptation mode regulation which adjust fan rotation to individual boiler dynamics.
Control temperature in the burner feeder and flame sensor to ignition mode (option).
Sound and text alarm signals.
Built -in temperature limiter in standard (STB).
Many language versions.
Boiler operational parameters archiving function, among others alarm controller record.
Soft start of the fan.
Possibility of selecting type of controller regulation: ADAPTATION MODE, GRATE MODE.
Fan
STB
Temperaturelimiter
Feeder temp.sensor
°C
GA03HARoom panel
A
Flame movingback detection
Anti-Legionella
70°CLE
ANTY
STOP
Lighter
LE
Feeder container
Flame sensor
DHWPump
°C
FlueGasTemp.
°C
P.P.U.H. “GECO” Sp. z o.o.
Cholerzyn 376
32-060 Liszki, Poland
DIAGRAM OF CONNECTIONS
THE CONTROL AND HEATING SYSTEM
TECHNICAL DATA
GH
21P
BG
H21P
BG
H21P
B
Diagram of electric connections
Outputs Inputs
50,51
52,53
54,55
56,57
58
Flue gas temp. sensor
B-
Feeder temp. sensor/Thermostat
DHW/Return/Flame sensor/Reed relay
03
01
Lighter
Power supply 230V
04
02
05
06
07
08
09
11
12 15
14 16
Lighter
Power supply 230V
CH pump
CH pump
DHW Pump/Mix Pump
DHW Pump/Mix Pump
Burner feeder
Burner feeder
N
L
L
N
N
L
N
L
N
L
L
N
Fan Temp. limiter (STB)
Fan Temp. limiter (STB)
Boiler outlet temp. sensor
59
60
61 +12 V DC
RoompanelGA03HA
A+
GND
Controls
P1
P2
P4
P3
P5
CH Pump
HUW Pump
Container feeder
Fan
Lighter
Sensors
T1
T2
T4
T3
Boiler temperature
Flue gas temperature
HUW temp./Flame
Feeder temperature
Watercontainer
P5
T1
T3Boiler
cycle DHW cycle CH
T4
P2
P1
Fuelcontainer
P4M
P3
T2
230V AC +10%/ -15%
od +5°C do + 40°C
20% ÷ 80% RH
NTC - range: od 0°C do +100°C
3,15A
°C W
0
10
20
30
40
50
60
70
80
90
100
7174,89
4374,83
2747,10
1774,91
1172,09
795,08
547,95
384,62
275,86
202,37
149,16
1A
1A
1A
1A
3A
250W
250W
250W
250W
750W
Temp. sensor.(PT1000)
°C W
0
50
100
150
200
250
300
350
400
450
500
1000,00
1194,00
1385,10
1573,30
1758,60
1941,00
2120,50
2297,20
2470,90
2641,80
2809,80
550 2974,90
600 3137,10
650 3296,40
700 3452,80
750 3606,40
1000 - ran.:od 0°C do +750°CPT
1) boiler temperature sensor2) flue gas temperature
GH21PB equipment
Standard equipment:
Power supply voltage
Working temperature
Relative humidity
Sensor type
Fan and feeder protection
CH pump
DHW pump/Mix pump/Feeder Container
Burner feeder
Fan
Lighter
Optional equipment:
1) DHW temperature sensor/ Flame sensor2) GA03HA Room panel3) supplying wire4) burner feeder temperature sensor
Controls:
1) CH pump2) DHW pump/ Mix pump/ Container feeder3) fan4) lighter5) burner feeder
Temp. sensor
(NTC) 2,2 kW
Output Constatnt load
Temperaturelimiter
STB
PE stripGH21PB
5058
01
5159 5260 5361 54 55 56 57
02 0503 0604 07 08 1109 10 1312 14 15 16
230V AC
Fuse.
N LN LL N NN LL N L
NTCB- A+ +12VGND
F 3,15A/250V
Imax=10A
01-02 - Power03-04 - Lighter05-06 - C.H. Pump07-08 - D.H.W. Pump/
Mix Pump/Feeder
09-11 - Feeder/Container Feeder
12-14 - Fan15-16 - STB
50-51 - Boiler temp. sensor52-53 - Feeder temperature sensor/
Room thermostat54-55 -56-57 - D.H.W. temp./Return temp.
/Flame sensor/Reed relay58-59-60-61 - Room panel GA03HA
Flue gas temp. sensor
PT1000