FIRE ALARM CONTROL PANEL ELECTRICAL CONTRACTOR EQUIPMENT GROUND EMERGENCY FACP E.G. EM EC WP 3+ UON SHALL BE DETERMINED FROM THE ARCHITECTURAL DRAWINGS. AND THE OWNER PRIOR TO SUBMISSION OF BID TO DETERMINE WHAT WORK MUST BE AND WORK. CONTRACTOR SHALL FURNISH ALL NECESSARY OUTLETS, SUPPORTS, FITTINGS AND ACCESSORIES TO FULFILL APPLICABLE CODES, REGULATIONS, BUILDING GENERAL ELECTRICAL NOTES STANDARDS AND THE BEST PRACTICES OF THE TRADE FOR INSTALLATION OF PERFORMED AFTER NORMAL BUSINESS HOURS. UNLESS OTHERWISE DIRECTED ANY NOISY WORK (CHOPPING, CORE DRILLING, HAMMERING, ETC.) AND BUILDING POWER ALL OUTDOOR WIRING SHALL BE INSTALLED IN NOT DIPPED GALVANIZED RIGID STEEL CONFIRM NORMAL BUSINESS HOURS WITH BUILDING MANAGEMENT. ARMORED CABLE MAY BE USED CONCEALED IN HANG CEILINGS AND PARTITIONS. VOLT CIRCUITS OVER 100' IN LENGTH SHALL BE NO. 10 AWG. INTERRUPTIONS SHALL BE PERFORMED OUTSIDE OF NORMAL BUSINESS HOURS. PARTITIONS, FLOORS, OR CEILINGS SHALL BE FIRE STOPPED USING APPROVED METHODS. ALL SLEEVES MUST HAVE BUSHINGS. SEALANT SHALL BE 3 HOUR FIRE BARRIER #CP-25 (NO LESS THAN 3" THICK BACKED UP WITH MINERAL WOOL). ROUTING, EQUIPMENT LOCATIONS AND ELECTRICAL WORK AS ACTUALLY INSTALLED. 2. THE EXACT LOCATION AND ELEVATION OF ALL LIGHTING FIXTURES, RECEPTACLES, ETC. 3. THE CONTRACTOR SHALL COORDINATE WITH THE GENERAL CONTRACTOR, THE ARCHITECT 4. ALL INDOOR WIRING SHALL BE INSTALLED IN ELECTRICAL METALLIC TUBING (EMT). 5. THE MINIMUM WIRE SIZE FOR BRANCH CIRCUITS SHALL BE NO. 12 AWG EXCEPT 120 7. OPENINGS AROUND ELECTRICAL PENETRATIONS THROUGH FIRE RESISTANCE RATED WALLS, 8. PREPARE "AS-BUILT" DRAWINGS SHOWING WIRE SIZE, CIRCUIT NUMBERING, CIRCUIT 6. ALL CONTROL WIRING ASSOCIATED WITH MECHANICAL EQUIPMENT IS THE RESPONSIBILITY 1. DRAWINGS ARE DIAGRAMMATIC AND INDICATE THE GENERAL ARRANGEMENT OF SYSTEMS OF THE MECHANICAL CONTRACTOR. CONDUIT. ELECTRICAL WORK. AMERICAN WIRE GAUGE CIRCUIT BREAKER CONDUIT CIRCUIT CB CKT. C AWG ELECTRICAL ABBREVIATIONS PNL TYP P N.T.S. WITH APPLICABLE LAWS AND ENVIRONMENTAL REGULATIONS. EQUIPMENT REQUIRED TO BE TURNED OVER PROVIDE ADDITIONAL SUPPORT FOR ALL EXISTING CONDUITS, LOW VOLTAGE CABLING AND DEVICES TO REMAIN WHICH ARE AFFECTED BY DEMOLITION OF EXISTING CEILINGS AND PARTITIONS. ALL WORK SHALL BE PROPERLY IDENTIFIED AFTER DEMOLITION. UPDATE ALL PANEL SCHEDULES TO AVOID CONFLICTS WITH NEW WORK. INSTALL JUNCTION BOXES, TAPE OFF CONDUCTORS AND IDENTIFY WITH ARE REMOVED FROM ENCLOSURES OR SURFACES NOT INDICATED TO BE REPAIRED OR REFINISHED. PROVIDE BLANK COVER PLATES AT OPEN BOXES WHERE EXISTING RECEPTACLES OR ELECTRICAL DEVICES FIRE ALARM SYSTEM SHALL REMAIN IN OPERATION DURING BOTH DEMOLITION AND CONSTRUCTION STAGES FEEDERS AND BRANCH CIRCUITS TO BE RE-USED - REMOVE CONDUIT AND WIRING TO LOCATIONS WHICH THE PANEL OF ORIGIN. WIRING SHALL BE REMOVED TO THE PANEL OF ORIGIN. WHERE EMPTY CONDUITS FEEDERS AND BRANCH CIRCUITS TO BE REMOVED - CONDUIT AND SUPPORTS SHALL BE REMOVED TO TO THE OWNER SHALL BE PLACED IN A MUTUALLY ACCEPTABLE LOCATION. REMAIN, INSTALL A PULLSTRING AND IDENTIFY AT BOTH ENDS. REFLECT EQUIPMENT AND CIRCUIT REMOVALS. OF THIS PROJECT. PROVIDE FIRE WATCH IF REQUIRED. 9. 12. 11. 10. PANEL AND CIRCUIT NUMBER. 8. 7. ELECTRICAL DEMOLITION NOTES NOTES AND GRAPHIC REPRESENTATIONS SHALL NOT LIMIT THE EXTENT OF DEMOLITION REQUIRED. CONTRACTOR SHALL VISIT THE SITE, CAREFULLY EXAMINE EXISTING CONDITIONS AND SHALL PERFORM DOCUMENTS. EXTENT OF ALL DEMOLITION WORK SHALL INCLUDE, BUT NOT LIMITED TO, ELECTRICAL WORK ASSOCIATED WITH THE REMOVAL OF LIGHTING FIXTURES, WIRING DEVICES, AND ALL ASSOCIATED ALL DEMOLITION REQUIRED TO ACHIEVE THE FINAL DESIGN INTENT AS REQUIRED BY THE CONTRACT ELECTRICAL CONTRACTOR SHALL MAINTAIN CONTINUITY OF CIRCUITRY FOR EXISTING EQUIPMENT AND DEVICES THAT ARE TO REMAIN. WHERE OUTLETS ARE REMOVED AND ARE NOT AT THE CIRCUIT DEAD-END, EQUIPMENT AND WIRING TO BE REMOVED SHALL BE DE-ENERGIZED PRIOR TO ANY DEMOLITION WORK. EQUIPMENT INDICATED TO BE REMOVED SHALL BE TAKEN FROM THE SITE AND DISPOSED OF IN ACCORDANCE RELOCATED AND RECONNECTED USING MATERIALS AND STANDARDS OF THIS CONTRACT. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE TO TRACE AND RELOCATE ALL EXISTING FEEDERS AND BRANCH CIRCUIT WIRING WHICH PASSES THROUGH THE DEMOLITION AREA THAT SERVE EXISTING ALL WORK REQUIRED TO REMAIN IN SERVICE BUT INTERFERING WITH THE ALTERATIONS SHALL BE RACEWAY AND WIRING. EXTENT OF ALL DEMOLITION SHALL BE COORDINATED WITH THE ARCHITECT. EXTEND CIRCUITRY AS REQUIRED TO MAINTAIN INTEGRITY OF ORIGINAL CIRCUIT. SPACES TO REMAIN. 5. 6. 4. 3. 2. 1. UNLESS OTHERWISE NOTED WEATHERPROOF PHASE POLES PANEL TYPICAL NOT TO SCALE ELECTRICAL DRAWING LIST SHEET # DWG # TRADE DESCRIPTION E-101.00 GROUND LEVEL: ELECTRICAL - SYMBOLS & NOTES E-201.00 GROUND LEVEL: ELECTRICAL - SPECIFICATIONS I E-202.00 GROUND LEVEL: ELECTRICAL - SPECIFICATIONS II E-302.00 GROUND LEVEL: ELECTRICAL - LIGHTING PLAN & NOTES 1 2 3 5 6 LIGHTING FIXTURE SCHEDULE (REFER TO ARCHITECT DRAWINGS FOR EXACT FIXTURE DETAILS) POWER LEGEND SECTION DESIGNATION ON DRAWING WHERE SECTION IS CUT A-SECTION DESIGNATION B-DRAWING NO. LIGHTING ARRESTOR (RISER DIAGRAM) GROUNDING RESISTOR (RISER DIAGRAM) GROUND CONNECTION (RISER DIAGRAM) AUTOMATIC TRANSFER SWITCH (RISER DIAGRAM) METER AND CURRENT TRANSFORMER (RISER DIAGRAM) DRAWOUT TYPE CIRCUIT BREAKER (RISER DIAGRAM) CIRCUIT BREAKER (RISER DIAGRAM) DISCONNECT SWITCH (RISER DIAGRAM) FUSED DISCONNECT SWITCH (RISER DIAGRAM) SUSPENDED NON-LINEAR RATED TRANSFORMER (RISER DIAGRAM) FLOOR MOUNTED TRANSFORMER (RISER DIAGRAM) EXISTING EQUIPMENT TO BE REMOVED EXISTING EQUIPMENT TO BE RELOCATED RELOCATED POSITION OF EXISTING EQUIPMENT DRAWING NOTATIONS RE ER 1 A HA 1 B # REVISION SYMBOL FEEDER DESIGNATION TAG DRAWING NOTE TAG EXISTING EQUIPMENT TO REMAIN LINE REPRESENTATION ~ ~ ~ ~ T TRANSFORMER (RISER DIAGRAM) EXISTING WIRING TO REMAIN EXISTING WIRING BE REMOVED NEW EQUIPMENT NEW WIRING FUSE (RISER DIAGRAM) ~ ~ TRANSFORMER MANUAL MOTOR SWITCH WITH THERMAL OVERLOAD PROTECTION COMBINATION MOTOR STARTER/DISCONNECT SWITCH TRANSIENT VOLTAGE SURGE SUPPRESSION DEVICE NEW FLUSH MOUNTED PANELBOARD NEW SURFACE MOUNTED PANELBOARD EXISTING PANELBOARD OR DISTRIBUTION BOARD HWH ECH VAV FCU ELECTRICAL SYMBOL FOR MECHANICAL EQUIPMENT CONNECTION-GREATER THAN i" HORSE POWER. PJ SEC ELECTRICAL SYMBOL FOR MISCELLANEOUS CONNECTION: PULL/TAP BOX. "CSB"-CABLE SUPPORT BOX CONCEALED (IN WALL OR CEILING) CIRCUIT OR WIRING AHU- TVSS AHU- VAV- S T T S PS AHU AIR HANDLING UNIT MAGNETIC DOOR CONTROLLER FUSED DISCONNECT SWITCH UNFUSED DISCONNECT SWITCH VARIABLE FREQUENCY DRIVE AUTOMATIC TRANSFER SWITCH CONDENSATE PUMP ELECTRIC HEAT COIL AIR CONDITIONING UNIT EHC CP AC - - - - PROJECTION SCREEN MOTORIZED DRAPE FINAL EQUIPMENT CONNECTION SLAB MOUNTED JUNCTION BOX WALL MOUNTED JUNCTION BOX CEILING MOUNTED JUNCTION BOX MD PS - - MOTOR WIREWAY PNL-1 ELECTRICAL LEGEND 1 - - - - FVAV FAN COIL UNIT HOT WATER HEATER ELECTRIC CABINET HEATER VARIABLE AIR VOLUME - - - - MD EWC UH SECURITY EQUIPMENT PROJECTION EQUIPMENT - - FA - MS - FAN POWERED VAV BOX MOTORIZED DAMPER ELECTRIC WATER COOLER UNIT HEATER FIRE ALARM MOTORIZED SHADE ATS VFD S T T T LINE VOLTAGE POWER OR LIGHTING CIRCUITRY HOMERUN WITH PANEL DESIGNATION. NUMERAL WHERE USED INDICATES CIRCUIT NUMBER. IT SHALL CONSIST OF 2#12-s"C, UNLESS OTHERWISE NOTED. E L N SECTION DESIGNATION ON DRAWING WHERE SECTION IS CUT A-SECTION DESIGNATION B-DRAWING NO. EXISTING EQUIPMENT TO BE REMOVED EXISTING EQUIPMENT TO BE RELOCATED RELOCATED POSITION OF EXISTING EQUIPMENT ELECTRICAL DRAWING NOTATIONS RE ER 1 A HA 1 B # REVISION SYMBOL FEEDER DESIGNATION TAG DRAWING NOTE TAG EXISTING EQUIPMENT TO REMAIN ELECTRICAL LINE REPRESENTATION EXISTING WIRING TO REMAIN EXISTING WIRING BE REMOVED NEW EQUIPMENT NEW WIRING NL MLO MTD MAIN LUGS ONLY NIGHT LIGHT MOUNTED I.G. MCB GFI EOL GROUND FAULT INTERRUPTER MAIN CIRCUIT BREAKER ISOLATED GROUND END OF LINE DEVICE NEW FLUSH FLOOR MOUNTED DUPLEX OUTLET NEW JUNCTION BOX - WALL MOUNTED POWER DATA-TELEPHONE HOOK-UP NEW FLUSH CEILING MOUNTED DATA OUTLET NEW FLUSH FLOOR MOUNTED COMBINATION VOICE/DATA OUTLET INDICATES EXISTING OUTLET TO REMAIN NEW FLUSH CEILING MOUNTED QUAD OUTLET WALL MOUNTED DOOR RELEASE BUTTON ELECTROMAGNETIC STRIKE FOR SECURE DOOR WALL MOUNTED DOOR ACCESS KEYPAD DR EX WALL MOUNTED SPEAKER 96" AFF S ES K J ELECTRIFIED FURNITURE SYSTEM. WIRELESS ACCESS POINT WAP NEW FAX OUTLET, # INDICATES DROPS. NEW DATA OUTLET, # INDICATES DROPS. NEW DUPLEX CONVENIENCE WALL OUTLET MOUNTED @15" A.F.F. (U.O.N.) AS MFG. (FURNITURE MOUNT AS REQUIRED) NEW DUPLEX OUTLET ON DEDICATED CIRCUIT MTD. @ 15" AFF (UON) WALL OUTLET MOUNTED @15" A.F.F. (U.O.N.) NEW DOUBLE DUPLEX (QUAD) ELECTRICAL CONVENIENCE IP WALL PHONE MTD @ 54" AFF 2 2 E-301.00 4 E-401.00 GROUND LEVEL: ELECTRICAL - DETAILS NORTH LEGEND DESCRIPTION 2'x2' SUPENDED LAY-IN CEILING @ 9'-0" TYP. GROUND LEVEL: ELECTRICAL - LIGHTING PLAN & NOTES SITE PLAN: 375 BEACH 92ND STREET, QUEENS , NY BLOCK #: 16109 LOT #: 43 92SN STREET BEACH CHANNEL DR 375 JAMAICA BAY 7 E-601.00 GROUND LEVEL: ELECTRICAL - ELECTRICAL PANEL SCHEDULES DESCRIPTION MANUFACTURER MODEL LAMP QTY NOTES USE W/ PENDANT MOUNTED, TRACK , TYPE "L" LV106, TRACK HEAD WHITE TRACK FIXTURE 1 MR-16, 50W 38 EMERGENCY LIGHT W/ BATTERY PACK WAC LIGHTING RECESSED FIXTURE, ADJUSTABLE TRIM: HR-D-417, WHITE HOUSING , HR-8402E 1, 35W PENDANT MOUNTED EX. SURFACE MOUNTED FLUORESCENT LIGHTOLIER SLB2SFSVA232120SO (2) T-8 11 EX. PENDANT MOUNTED FIXTURE 1 CF, 13W EX. TRACK FIXTURE 1 MR-16, 35W 21 EX. SURFACE MOUNTED FLUORESCENT LIGHTOLIER SLB2SFSVA232120SO (2) T-8 9 EX. WALL MOUNTED SCONCE EXIST EX. PENDANT MTD CEILING FAN ELK LIGHTING ELK-17042-1 1 CF, 13W 14 12 EX. SURFACE MOUNTED FLUORESCENT LIGHTOLIER SLB2SFSVA232120SO (2) T-8 11 6 1 CF, 13W EXIST JESCO 3 LIGHTING SCHEDULE seal & signature dwg title twig cadd checked by issue date AS NOTED drawn by 02/11/2011 project no. dwg. no. scale cad file t10-12-0230 375 Beach 92nd Street Queens, NY 11693 SUBMISSIONS DATE rev no issue project project 375 Beach 92nd Street Queens, NY 11693 architect 231 West 29th Street - Suite 606, New York, NY 10001 Tel: 212 . 967 . TWIG / Fax: 212 . 967 . 8945 [email protected] www.twigcon.com A Division of The Wall Consulting Group, Inc. All Rights Reserved. 2007- 2010 375 Beach 92nd Street E-101.00.dwg NYC dob# sheet THESE PLANS ARE APPROVED ONLY FOR THE WORK ON THE BEING APPROVED OR IN ACCORDANCE WITH APPLICABLE CODES. APPLICATION SPECIFICATION SHEET. ALL OTHER MATTERS SHOWN ARE NOT TO BE RELIED UPON OR TO BE CONSIDERED AS EITHER $OO 'UDZLQJV $QG :ULWWHQ 0DWHULDO +HUHLQ &RQVWLWXWH 7KH 2ULJLQDO $QG 8QSXEOLVKHG :RUN 2I 7KH :DOO &RQVXOWLQJ *URXS ,QF DQGRU 7:,* &RQVXOWLQJ (QJLQHHUV 3& $QG 7KH 6DPH 0D\ 1RW %H 'XSOLFDWHG 8VHG 2U 'LVFORVHG :LWKRXW 7KH :ULWWHQ &RQVHQW 2I 7KH :DOO &RQVXOWLQJ *URXS ,QF DQGRU 7:,* &RQVXOWLQJ (QJLQHHUV 3& NYCECC NOTES: TO THE BEST OF MY KNOWLEDGE, BELIEF AND PROFESSIONAL JUDGMENT, THESE PLANS AND SPECIFICATIONS ARE IN COMPLIANCE WITH THE NEW YORK CITY ENERGY CONSERVATION CODE. 02.14.11 1 FILING & PRICING GROUND FLOOR ELECTRICAL SYMBOLS & NOTES 1 of 7

Upload: others

Post on 08-Aug-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: NORTH - Thai Rock · battery pack recessed wac lighting fixture, adjustable trim: hr-d-417, white housing , hr-8402e1, 35w pendant mounted ex. surface mounted fluorescent lightolier

FIRE ALARM CONTROL PANEL

ELECTRICAL CONTRACTOR

EQUIPMENT GROUND

EMERGENCY

FACP

E.G.

EM

EC

WP

Ø/PH

UON

SHALL BE DETERMINED FROM THE ARCHITECTURAL DRAWINGS.

AND THE OWNER PRIOR TO SUBMISSION OF BID TO DETERMINE WHAT WORK MUST BE

AND WORK. CONTRACTOR SHALL FURNISH ALL NECESSARY OUTLETS, SUPPORTS,

FITTINGS AND ACCESSORIES TO FULFILL APPLICABLE CODES, REGULATIONS, BUILDING

GENERAL ELECTRICAL NOTES

STANDARDS AND THE BEST PRACTICES OF THE TRADE FOR INSTALLATION OF

PERFORMED AFTER NORMAL BUSINESS HOURS. UNLESS OTHERWISE DIRECTED ANY

NOISY WORK (CHOPPING, CORE DRILLING, HAMMERING, ETC.) AND BUILDING POWER

ALL OUTDOOR WIRING SHALL BE INSTALLED IN NOT DIPPED GALVANIZED RIGID STEEL

CONFIRM NORMAL BUSINESS HOURS WITH BUILDING MANAGEMENT.

ARMORED CABLE MAY BE USED CONCEALED IN HANG CEILINGS AND PARTITIONS.

VOLT CIRCUITS OVER 100' IN LENGTH SHALL BE NO. 10 AWG.

INTERRUPTIONS SHALL BE PERFORMED OUTSIDE OF NORMAL BUSINESS HOURS.

PARTITIONS, FLOORS, OR CEILINGS SHALL BE FIRE STOPPED USING APPROVED METHODS.

ALL SLEEVES MUST HAVE BUSHINGS. SEALANT SHALL BE 3 HOUR FIRE BARRIER

#CP-25 (NO LESS THAN 3" THICK BACKED UP WITH MINERAL WOOL).

ROUTING, EQUIPMENT LOCATIONS AND ELECTRICAL WORK AS ACTUALLY INSTALLED.

2. THE EXACT LOCATION AND ELEVATION OF ALL LIGHTING FIXTURES, RECEPTACLES, ETC.

3. THE CONTRACTOR SHALL COORDINATE WITH THE GENERAL CONTRACTOR, THE ARCHITECT

4. ALL INDOOR WIRING SHALL BE INSTALLED IN ELECTRICAL METALLIC TUBING (EMT).

5. THE MINIMUM WIRE SIZE FOR BRANCH CIRCUITS SHALL BE NO. 12 AWG EXCEPT 120

7. OPENINGS AROUND ELECTRICAL PENETRATIONS THROUGH FIRE RESISTANCE RATED WALLS,

8. PREPARE "AS-BUILT" DRAWINGS SHOWING WIRE SIZE, CIRCUIT NUMBERING, CIRCUIT

6. ALL CONTROL WIRING ASSOCIATED WITH MECHANICAL EQUIPMENT IS THE RESPONSIBILITY

1. DRAWINGS ARE DIAGRAMMATIC AND INDICATE THE GENERAL ARRANGEMENT OF SYSTEMS

OF THE MECHANICAL CONTRACTOR.

CONDUIT.

ELECTRICAL WORK.

AMERICAN WIRE GAUGE

CIRCUIT BREAKER

CONDUIT

CIRCUIT

CB

CKT.

C

AWG

ELECTRICAL ABBREVIATIONS

PNL

TYP

P

N.T.S.

WITH APPLICABLE LAWS AND ENVIRONMENTAL REGULATIONS. EQUIPMENT REQUIRED TO BE TURNED OVER

PROVIDE ADDITIONAL SUPPORT FOR ALL EXISTING CONDUITS, LOW VOLTAGE CABLING AND DEVICES TO

REMAIN WHICH ARE AFFECTED BY DEMOLITION OF EXISTING CEILINGS AND PARTITIONS.

ALL WORK SHALL BE PROPERLY IDENTIFIED AFTER DEMOLITION. UPDATE ALL PANEL SCHEDULES TO

AVOID CONFLICTS WITH NEW WORK. INSTALL JUNCTION BOXES, TAPE OFF CONDUCTORS AND IDENTIFY WITH

ARE REMOVED FROM ENCLOSURES OR SURFACES NOT INDICATED TO BE REPAIRED OR REFINISHED.

PROVIDE BLANK COVER PLATES AT OPEN BOXES WHERE EXISTING RECEPTACLES OR ELECTRICAL DEVICES

FIRE ALARM SYSTEM SHALL REMAIN IN OPERATION DURING BOTH DEMOLITION AND CONSTRUCTION STAGES

FEEDERS AND BRANCH CIRCUITS TO BE RE-USED - REMOVE CONDUIT AND WIRING TO LOCATIONS WHICH

THE PANEL OF ORIGIN. WIRING SHALL BE REMOVED TO THE PANEL OF ORIGIN. WHERE EMPTY CONDUITS

FEEDERS AND BRANCH CIRCUITS TO BE REMOVED - CONDUIT AND SUPPORTS SHALL BE REMOVED TO

TO THE OWNER SHALL BE PLACED IN A MUTUALLY ACCEPTABLE LOCATION.

REMAIN, INSTALL A PULLSTRING AND IDENTIFY AT BOTH ENDS.

REFLECT EQUIPMENT AND CIRCUIT REMOVALS.

OF THIS PROJECT. PROVIDE FIRE WATCH IF REQUIRED.

9.

12.

11.

10.

PANEL AND CIRCUIT NUMBER.

8.

7.

ELECTRICAL DEMOLITION NOTES

NOTES AND GRAPHIC REPRESENTATIONS SHALL NOT LIMIT THE EXTENT OF DEMOLITION REQUIRED.

CONTRACTOR SHALL VISIT THE SITE, CAREFULLY EXAMINE EXISTING CONDITIONS AND SHALL PERFORM

DOCUMENTS. EXTENT OF ALL DEMOLITION WORK SHALL INCLUDE, BUT NOT LIMITED TO, ELECTRICAL

WORK ASSOCIATED WITH THE REMOVAL OF LIGHTING FIXTURES, WIRING DEVICES, AND ALL ASSOCIATED

ALL DEMOLITION REQUIRED TO ACHIEVE THE FINAL DESIGN INTENT AS REQUIRED BY THE CONTRACT

ELECTRICAL CONTRACTOR SHALL MAINTAIN CONTINUITY OF CIRCUITRY FOR EXISTING EQUIPMENT AND

DEVICES THAT ARE TO REMAIN. WHERE OUTLETS ARE REMOVED AND ARE NOT AT THE CIRCUIT DEAD-END,

EQUIPMENT AND WIRING TO BE REMOVED SHALL BE DE-ENERGIZED PRIOR TO ANY DEMOLITION WORK.

EQUIPMENT INDICATED TO BE REMOVED SHALL BE TAKEN FROM THE SITE AND DISPOSED OF IN ACCORDANCE

RELOCATED AND RECONNECTED USING MATERIALS AND STANDARDS OF THIS CONTRACT.

THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE TO TRACE AND RELOCATE ALL EXISTING FEEDERS

AND BRANCH CIRCUIT WIRING WHICH PASSES THROUGH THE DEMOLITION AREA THAT SERVE EXISTING

ALL WORK REQUIRED TO REMAIN IN SERVICE BUT INTERFERING WITH THE ALTERATIONS SHALL BE

RACEWAY AND WIRING. EXTENT OF ALL DEMOLITION SHALL BE COORDINATED WITH THE ARCHITECT.

EXTEND CIRCUITRY AS REQUIRED TO MAINTAIN INTEGRITY OF ORIGINAL CIRCUIT.

SPACES TO REMAIN.

5.

6.

4.

3.

2.

1.

UNLESS OTHERWISE NOTED

WEATHERPROOF

PHASE

POLES

PANEL

TYPICAL

NOT TO SCALE

ELECTRICAL DRAWING LIST

SHEET # DWG # TRADE DESCRIPTION

E-101.00 GROUND LEVEL: ELECTRICAL - SYMBOLS & NOTES

E-201.00 GROUND LEVEL: ELECTRICAL - SPECIFICATIONS I

E-202.00 GROUND LEVEL: ELECTRICAL - SPECIFICATIONS II

E-302.00

GROUND LEVEL: ELECTRICAL - LIGHTING PLAN & NOTES

1

2

3

5

6

LIGHTING FIXTURE SCHEDULE

(REFER TO ARCHITECT DRAWINGS FOR EXACT FIXTURE DETAILS)

POWER LEGEND

SECTION DESIGNATION ON DRAWING WHERE SECTION IS CUT

A-SECTION DESIGNATION

B-DRAWING NO.

LIGHTING ARRESTOR (RISER DIAGRAM)

GROUNDING RESISTOR (RISER DIAGRAM)

GROUND CONNECTION (RISER DIAGRAM)

AUTOMATIC TRANSFER SWITCH (RISER DIAGRAM)

METER AND CURRENT TRANSFORMER (RISER DIAGRAM)

DRAWOUT TYPE CIRCUIT BREAKER (RISER DIAGRAM)

CIRCUIT BREAKER (RISER DIAGRAM)

DISCONNECT SWITCH (RISER DIAGRAM)

FUSED DISCONNECT SWITCH (RISER DIAGRAM)

SUSPENDED NON-LINEAR RATED TRANSFORMER (RISER DIAGRAM)

FLOOR MOUNTED TRANSFORMER (RISER DIAGRAM)

EXISTING EQUIPMENT TO BE REMOVED

EXISTING EQUIPMENT TO BE RELOCATED

RELOCATED POSITION OF EXISTING EQUIPMENT

DRAWING NOTATIONS

RE

ER

1

A

HA

1

B

#

REVISION SYMBOL

FEEDER DESIGNATION TAG

DRAWING NOTE TAG

EXISTING EQUIPMENT TO REMAIN

LINE REPRESENTATION

~

~

~~

T

TRANSFORMER (RISER DIAGRAM)

EXISTING WIRING TO REMAIN

EXISTING WIRING BE REMOVED

NEW EQUIPMENT

NEW WIRING

FUSE (RISER DIAGRAM)

~~

TRANSFORMER

MANUAL MOTOR SWITCH WITH THERMAL OVERLOAD PROTECTION

COMBINATION MOTOR STARTER/DISCONNECT SWITCH

TRANSIENT VOLTAGE SURGE SUPPRESSION DEVICE

NEW FLUSH MOUNTED PANELBOARD

NEW SURFACE MOUNTED PANELBOARD

EXISTING PANELBOARD OR DISTRIBUTION BOARD

HWH

ECH

VAV

FCU

ELECTRICAL SYMBOL FOR MECHANICAL EQUIPMENT CONNECTION-GREATER THAN i" HORSE

POWER.

PJ

SEC

ELECTRICAL SYMBOL FOR MISCELLANEOUS CONNECTION:

PULL/TAP BOX. "CSB"-CABLE SUPPORT BOX

CONCEALED (IN WALL OR CEILING) CIRCUIT OR WIRING

AHU-

TVSS

AHU-

VAV-

S

T

T

S

PS

AHU AIR HANDLING UNIT

MAGNETIC DOOR CONTROLLER

FUSED DISCONNECT SWITCH

UNFUSED DISCONNECT SWITCH

VARIABLE FREQUENCY DRIVE

AUTOMATIC TRANSFER SWITCH

CONDENSATE PUMP

ELECTRIC HEAT COIL

AIR CONDITIONING UNIT

EHC

CP

AC

-

-

-

-

PROJECTION SCREEN

MOTORIZED DRAPE

FINAL EQUIPMENT CONNECTION

SLAB MOUNTED JUNCTION BOX

WALL MOUNTED JUNCTION BOX

CEILING MOUNTED JUNCTION BOX

MD

PS

-

-

MOTOR

WIREWAY

PNL-1

ELECTRICAL LEGEND

1

-

-

-

-

FVAVFAN COIL UNIT

HOT WATER HEATER

ELECTRIC CABINET HEATER

VARIABLE AIR VOLUME

-

-

-

-

MD

EWC

UH

SECURITY EQUIPMENT

PROJECTION EQUIPMENT

-

-

FA -

MS -

FAN POWERED VAV BOX

MOTORIZED DAMPER

ELECTRIC WATER COOLER

UNIT HEATER

FIRE ALARM

MOTORIZED SHADE

ATS

VFD

S

T

T

T

LINE VOLTAGE POWER OR LIGHTING CIRCUITRY HOMERUN WITH PANEL

DESIGNATION. NUMERAL WHERE USED INDICATES CIRCUIT NUMBER. IT SHALL

CONSIST OF 2#12-s"C, UNLESS OTHERWISE NOTED.

E

L

N

SECTION DESIGNATION ON DRAWING WHERE SECTION IS CUT

A-SECTION DESIGNATION

B-DRAWING NO.

EXISTING EQUIPMENT TO BE REMOVED

EXISTING EQUIPMENT TO BE RELOCATED

RELOCATED POSITION OF EXISTING EQUIPMENT

ELECTRICAL DRAWING NOTATIONS

RE

ER

1

A

HA

1

B

#

REVISION SYMBOL

FEEDER DESIGNATION TAG

DRAWING NOTE TAG

EXISTING EQUIPMENT TO REMAIN

ELECTRICAL LINE REPRESENTATION

EXISTING WIRING TO REMAIN

EXISTING WIRING BE REMOVED

NEW EQUIPMENT

NEW WIRING

NL

MLO

MTD

MAIN LUGS ONLY

NIGHT LIGHT

MOUNTED

I.G.

MCB

GFI

EOL

GROUND FAULT INTERRUPTER

MAIN CIRCUIT BREAKER

ISOLATED GROUND

END OF LINE DEVICE

NEW FLUSH FLOOR MOUNTED DUPLEX OUTLET

NEW JUNCTION BOX - WALL MOUNTED

POWER DATA-TELEPHONE HOOK-UP

NEW FLUSH CEILING MOUNTED DATA OUTLET

NEW FLUSH FLOOR MOUNTED COMBINATION VOICE/DATA OUTLET

INDICATES EXISTING OUTLET TO REMAIN

NEW FLUSH CEILING MOUNTED QUAD OUTLET

WALL MOUNTED DOOR RELEASE BUTTON

ELECTROMAGNETIC STRIKE FOR SECURE DOOR

WALL MOUNTED DOOR ACCESS KEYPAD

DR

EX

WALL MOUNTED SPEAKER 96" AFFS

ES

K

J

ELECTRIFIED FURNITURE SYSTEM.

WIRELESS ACCESS POINT

WAP

NEW FAX OUTLET, # INDICATES DROPS.

NEW DATA OUTLET, # INDICATES DROPS.

NEW DUPLEX CONVENIENCE WALL OUTLET MOUNTED

@15" A.F.F. (U.O.N.) AS MFG. (FURNITURE MOUNT AS REQUIRED)

NEW DUPLEX OUTLET ON DEDICATED CIRCUIT MTD. @ 15" AFF (UON)

WALL OUTLET MOUNTED @15" A.F.F. (U.O.N.)

NEW DOUBLE DUPLEX (QUAD) ELECTRICAL CONVENIENCE

IP WALL PHONE MTD @ 54" AFF

2

2

E-301.004

E-401.00 GROUND LEVEL: ELECTRICAL - DETAILS

NO

RTH

LEGENDDESCRIPTION

2'x2' SUPENDED LAY-IN

CEILING @ 9'-0" TYP.

GROUND LEVEL: ELECTRICAL - LIGHTING PLAN & NOTES

SITE PLAN: 375 BEACH 92ND STREET, QUEENS , NY

BLOCK #: 16109

LOT #: 43

9

2

S

N

S

T

R

E

E

T

B

E

A

C

H

C

H

A

N

N

E

L

D

R

3

7

5

J

A

M

A

I

C

A

B

A

Y

7 E-601.00 GROUND LEVEL: ELECTRICAL - ELECTRICAL PANEL SCHEDULES

DESCRIPTION MANUFACTURER MODEL LAMP QTY NOTES

USE W/ PENDANT

MOUNTED, TRACK ,

TYPE "L"

LV106, TRACK HEAD

WHITE

TRACK FIXTURE

1 MR-16, 50W 38

EMERGENCY

LIGHT W/

BATTERY PACK

WAC LIGHTING

RECESSED

FIXTURE,

ADJUSTABLE

TRIM: HR-D-417, WHITE

HOUSING , HR-8402E

1, 35W

PENDANT

MOUNTED

EX. SURFACE

MOUNTED

FLUORESCENT

LIGHTOLIER SLB2SFSVA232120SO (2) T-8

11

EX. PENDANT

MOUNTED

FIXTURE

1 CF, 13W

EX. TRACK

FIXTURE

1 MR-16, 35W 21

EX. SURFACE

MOUNTED

FLUORESCENT

LIGHTOLIER SLB2SFSVA232120SO (2) T-8

9

EX. WALL

MOUNTED

SCONCE

EXIST

EX. PENDANT

MTD CEILING

FAN

ELK LIGHTING ELK-17042-1

1 CF, 13W 14

12

EX. SURFACE

MOUNTED

FLUORESCENT

LIGHTOLIER SLB2SFSVA232120SO (2) T-8

11

6

1 CF, 13W

EXIST

JESCO

3

LIGHTING SCHEDULE

seal & signature

dwg title

twig

cadd

checked by

issue date

AS NOTED

drawn by

02/11/2011

project no.

dwg. no.

scale

cad file

t10-12-0230

375 Beach 92nd StreetQueens, NY 11693

SUBMISSIONS

DATE rev no issue

project

project

375 Beach 92nd StreetQueens, NY 11693

architect

231 West 29th Street - Suite 606, New York, NY 10001

Tel: 212 . 967 . TWIG / Fax: 212 . 967 . 8945

[email protected] www.twigcon.com

A Division of The Wall Consulting Group, Inc. All Rights Reserved. 2007- 2010©

375 Beach 92nd Street E-101.00.dwg

NYC dob#

sheetTHESE PLANS ARE APPROVED ONLY FOR THE WORK ON THE

BEING APPROVED OR IN ACCORDANCE WITH APPLICABLE CODES.

APPLICATION SPECIFICATION SHEET. ALL OTHER MATTERS SHOWN

ARE NOT TO BE RELIED UPON OR TO BE CONSIDERED AS EITHER

All Drawings And Written Material Herein Constitute The Original And Unpublished Work Of The Wall Consulting Group, Inc. and/or TWIG Consulting Engineers, P.C., And The Same May Not Be Duplicated, Used, Or Disclosed Without The Written Consent Of The Wall Consulting Group, Inc. and/or TWIG Consulting Engineers, P.C. © 2011.

NYCECC NOTES:

TO THE BEST OF MY KNOWLEDGE, BELIEF AND

PROFESSIONAL JUDGMENT, THESE PLANS AND

SPECIFICATIONS ARE IN COMPLIANCE WITH THE

NEW YORK CITY ENERGY CONSERVATION CODE.

02.14.11 1 FILING & PRICING

GROUND FLOORELECTRICALSYMBOLS & NOTES

1 of 7

Page 2: NORTH - Thai Rock · battery pack recessed wac lighting fixture, adjustable trim: hr-d-417, white housing , hr-8402e1, 35w pendant mounted ex. surface mounted fluorescent lightolier

ELECTRICAL SPECIFICATIONS - I

AND CONTROL OF THE OWNER. ENGAGE THE SERVICES OF VARIOUS MANUFAC

PROPER OPERATION AND SERVICING OF THE EQUIPMENT.

ALL SYSTEMS UNTIL THE FINAL ACCEPTANCE OF THE WORK.

RESPONSIBLE FOR THE ELECTRICAL WORK AS DESCRIBED HEREIN.

TO BE PERFORMED BY "THIS CONTRACTOR".

ON THE PERFORMANCE UNDER THIS CONTRACT.

9. "PROVIDE" - "FURNISH" AND "INSTALL".

CIRCUIT/CONDUCTORS/WIRING AS REQUIRED.

THE STRUCTURAL ENGINEER'S DOCUMENTS, AS APPLICABLE, ARE PART OF THIS

A201, LATEST EDITION, OR AS REQUIRED BY THE ARCHITECT DOCUMENTS, AND/OR

F. THE "GENERAL CONDITIONS OF THE CONTRACT FOR CONSTRUCTION" AIA DOCUMENT

3. THIS CONTRACTOR IS RESPONSIBLE FOR THE MAINTENANCE AND OPERATION OF

1. "ELECTRICAL CONTRACTOR", "THIS CONTRACTOR" - THE PARTY OR PARTIES

HAVE BEEN DULY AWARDED THE CONTRACT FOR AND ARE THEREBY MADE

4. "THESE SPECIFICATIONS", "THIS SECTION, PART, DIVISION" (OF THE

SPECIFICATION)- THE DOCUMENT SPECIFYING THE WORK TO BE PERFORMED BY

7. "FURNISH" - PURCHASE AND DELIVER TO THE PROJECT SITE COMPLETE WITH

6. "ARCHITECT", "ENGINEER", "OWNER'S REPRESENTATIVE" - THE PARTY OR

5. THE ELECTRICAL WORK", "THIS WORK", - ALL LABOR MATERIALS, EQUIPMENT,

EVERY NECESSARY APPURTENANCE AND SUPPORT, ALL AS PART OF THE

PARTIES RESPONSIBLE FOR INTERPRETING, ACCEPTING AND OTHERWISE RULING

PROPER AND COMPLETE INSTALLATION BY THE ELECTRICAL CONTRACTOR.

APPARATUS, CONTROLS, ACCESSORIES, AND OTHER ITEMS REQUIRED FOR A

"EQUIVALENT" SUITABLE FOR USE ON THE PROJECT, AS DETERMINED BY THE

ENGINEER BASED ON DOCUMENTS PRESENTED FOR SUCH DETERMINATION.

2. "THIS CONTRACT", "THE CONTRACT" - THE AGREEMENT COVERING THE WORK

3. APPROVED", "EQUAL", "SATISFACTORY", "ACCEPTED", "ACCEPTABLE",

RIES AS REQUIRED, INCLUDING THE EXTENSION OF EXISTING OR PROVIDING NEW

11. "RELOCATE" - MOVE EXISTING EQUIPMENT/DEVICES/FIXTURE AND ALL ACCESSO

10. "NEW" - MANUFACTURED WITHIN THE PAST TWO YEARS AND NEVER BEFORE

8. "INSTALL" - UNLOAD AT THE DELIVERY POINT AT THE SITE AND PERFORM EVERY

CORRECT OPERATION AT THE PROPER LOCATION IN THE PROJECT, ALL AS PART

OPERATION NECESSARY TO ESTABLISH SECURE MOUNTING INSTALLATION AND

TURERS SUPPLYING THE EQUIPMENT FOR THE PROPER STARTUP AND OPERATION

OF ALL SYSTEMS INSTALLED. INSTRUCT THE OWNERS PERSONNEL IN THE

AND EQUIPMENT IN WHICH DEFECTS DEVELOP WITHIN THE GUARANTEE PERIOD.

REPAIRS OR REPLACEMENTS IN EQUIPMENT SUPPLIED BY THIS CONTRACTOR.

THIS WORK SHALL BE DONE AS DIRECTED BY THE OWNER. THIS GUARANTEE

REPAIRING AND REPLACING WORK OF OTHER TRADES AFFECTED BY DEFECTS,

SHALL INCLUDE RESPONSIBILITY TO PAY FOR ALL EXPENSES INCURRED IN

ASSUME RESPONSIBILITY FOR ALL EXPENSES INCURRED FOR ANY W0RKMANSHIP

2. THE CONTRACTOR SHALL GUARANTEE TO REPLACE OR REPAIR PROMPTLY AND

USED.

ELECTRICAL WORK.

OF THE ELECTRICAL WORK.

"THIS CONTRACTOR".

CONTRACT.

G. DEFINITIONS:

COORDINATION, BULLETINS, OR ADDENDA.

1.06 AS-BUILT DRAWINGS:

AS-BUILT DRAWINGS ARE TO BE SIGNED AND CERTIFIED BY INSTALLING CONTRACTOR

THAT THIS IS THE AS-BUILT CONDITION OF THE WORK.

INDEX AND INDEX TABS TO INCLUDE THE FOLLOWING:

A. CONTRACTOR SHALL MAINTAIN RECORD DRAWING PRINTS ON JOB SITE AND RECORD,

AT TIME OF OCCURRENCE, DEVIATIONS FROM CONTRACT DOCUMENTS DUE TO FIELD

B. CONTRACTOR SHALL REVISE SHOP DRAWINGS TO CONFORM TO RECORD DRAWINGS

AND SUBMIT AN AS-BUILT CONDITION (DEVICES, EQUIPMENT, CIRCUITRY, ETC.)

DRAWINGS UPON COMPLETION OF THE PROJECT. FINAL SUBMISSION OF REPRODUCIBLE

A. SUBMIT FOUR (4) LOOSE-LEAF BOUND OPERATING AND MAINTENANCE MANUALS WITH

3. ALL ITEMS SUBMITTED FOR REVIEW IN SHOP DRAWING SECTION.

1. OPERATING AND MAINTENANCE INSTRUCTIONS ON ALL SYSTEMS.

2. MANUFACTURERS' CATALOG CUTS ON ALL EQUIPMENT.

BUILDING MANAGEMENT.

EXISTING TENANTS ON OTHER FLOORS.

1.04 SHOP DRAWINGS

1. DISTRIBUTION EQUIPMENT

3. LIGHTING FIXTURES.

THE FOLLOWING:

ARCHITECT/ENGINEER FOR REVIEW, WITH BID SUBMISSION.

A MINIMUM OF TWO (2) DAYS PRIOR TO ANY WORK, WHICHEVER IS MORE STRINGENT.

C. COORDINATE WITH BUILDING OWNER FOR ANY SERVICE INTERRUPTION OF EXISTING

SYSTEMS AND GIVE NOTICE AS REQUIRED BY BUILDING RULES AND REGULATIONS OR

CONTRACTOR IS TO PERFORM WORK ON PREMIUM TIME, SO AS NOT TO DISTURB

B. THIS CONTRACTOR IS RESPONSIBLE FOR ADHERING TO THE BUILDING OWNER'S RULES

AND REGULATIONS. ANY DISCREPANCIES BETWEEN THE CONTRACT DOCUMENTS AND

THE BUILDING RULES AND REGULATIONS SHALL BE SUBMITTED IN WRITING TO THE

BUILDING SYSTEM INTERRUPTIONS ARE TO BE PERFORMED OUTSIDE NORMAL BUSINESS

2. OVERCURRENT PROTECTIVE DEVICES (FUSES AND BREAKERS).

DIAGRAMS. SHOP DRAWINGS SUBMISSION SHALL INCLUDE, BUT NOT BE LIMITED TO,

A. SUBMIT SHOP DRAWINGS CERTIFIED BY ALL TRADES THAT COORDINATION HAS BEEN

COMPLETED. SUBMIT ALL CERTIFIED EQUIPMENT CUTS WITH CONSTRUCTION WIRING

12. MODIFICATION OF EXISTING FIRE ALARM SYSTEM.

1.03 COORDINATION WITH BUILDING MANAGEMENT

A. THIS CONTRACTOR IS TO OBTAIN A COPY OF THE BUILDING RULES AND REGULATIONS

PRIOR TO BID SUBMISSION TO DETERMINE REQUIREMENTS AND THE EXTENT OF

PREMIUM TIME WORK REQUIRED BY BUILDING MANAGEMENT. FOR THE PURPOSE OF THE

BID ASSUME ANY NOISY WORK (E.G., CHOPPING, CORE DRILLING ETC.) AND BASE

11. GROUNDING OF ALL EQUIPMENT AS REQUIRED BY CODE AND AS SPECIFIED.

10. TEMPORARY LIGHT AND POWER DURING CONSTRUCTION.

1.05 MAINTENANCE MANUALS:

MAY BE MORE STRINGENT AND CONTRACTOR IS RESPONSIBLE TO OBTAIN REQUIRE

MENTS FROM CONSTRUCTION MANAGER, GENERAL CONTRACTOR OR ARCHITECT.

REPRODUCIBLE AND ONE (1)PRINT OF ALL DRAWINGS. SPECIFIC JOB REQUIREMENTS

B. PROVIDE A MINIMUM OF FOUR (4) COPIES OF 8-1/2"X 11" SUBMISSIONS AND ONE (1)

5. FIRE ALARM SYSTEM EQUIPMENT AND WIRING SCHEMATIC.

4. DEVICES.

HOURS.

OPERATION, MAINTENANCE AND REPAIR.

MORE STINGENT SITUATION SHALL APPLY.

WITH OTHER TRADES TO AVOID CONFLICTS.

AMENDMENTS, NYC BUILDING DEPARTMENT, BUILDING MANAGEMENT, AND

A. INSTALL ALL NEW WORK IN A NEAT WORKMANLIKE MANNER READILY ACCESSIBLE FOR

THESE SPECIFICATIONS. CONTRACTOR IS TO INFORM ENGINEER, OF ANY

EXISTING WORK OR MATERIALS WHICH VIOLATE ANY OF THE ABOVE LAWS AND

VIOLATION SHALL BE CORRECTED BY THIS CONTRACTOR AND AT NO EXPENSE

1. ALL WORK SHALL COMPLY WITH REQUIREMENTS OF THE 2002 NEC AND NYC

LOCAL CODES, LAWS AND REGULATIONS GOVERNING OR RELATING TO ANY

ALL AUTHORITIES HAVING JURISDICTION. APPLICABLE NATIONAL, STATE AND

PORTION OF THIS WORK SHALL BE INCORPORATED INTO AND MADE A PART OF

REGULATIONS. ANY WORK DONE BY THE CONTRACTOR CAUSING SUCH

WORK AND APPROXIMATE LOCATION OF EQUIPMENT. REFER TO ARCHITECTURAL

SWITCHES LIGHT FIXTURES, RECEPTACLES ETC. WORK SHALL BE COORDINATED

1. PRIOR TO SUBMISSION OF THE BID, THIS CONTRACTOR SHALL VISIT THE JOB

WORK INDICATED ON THE DRAWINGS AND DESCRIBED HEREIN. DISCREPANCIES,

SITE TO ASCERTAIN THE ACTUAL FIELD CONDITIONS AS THEY RELATE TO THE

1. PRIOR TO SUBMISSION OF A FORMAL BID, THIS CONTRACTOR SHALL REVIEW ALL

SHALL BE EVIDENCE THAT SITE VERIFICATION HAS BEEN PERFORMED AS

SUBMITTED AS A WRITTEN QUALIFICATION OF THE BID. SUBMISSION OF A BID

SUBMISSION OF THE BID, AND IF NOT RESOLVED TO SATISFACTION, SHALL BE

SHALL INCLUDE ANY WORK REQUIRED IN THE BID WHICH IS INDICATED OR

DEMOLITION, ARCHITECTURAL, MECHANICAL, PLUMBING AND SPRINKLER AND

DRAWINGS OF THE ENTIRE PROJECT INCLUDING GENERAL CONSTRUCTION,

2. DRAWINGS ARE DIAGRAMMATIC AND INDICATE GENERAL ARRANGEMENT OF

IMPLIED TO BE PERFORMED BY THIS TRADE IN FOTHER SECTIONS OF THE WORK.

DRAWINGS FOR ALL DIMENSIONS AND COORDINATE FINAL LOCATIONS OF

IF ANY, SHALL BE BROUGHT TO THE ENGINEER'S ATTENTION PRIOR TO

3. IF A CONFLICT OCCURS IN THE SPECIFICATIONS AND/OR ON THE DRAWINGS, THE

4. ANY EQUIPMENT, PARTS, MATERIALS, ACCESSORIES , OR LABOR THAT IS

NOT SPECIFICALLY MENTIONED HEREIN OR SHOWN ON THE DRAWINGS, SHALL

NECESSARY FOR PROPER PERFORMANCE OF THE ELECTRICAL WORK, ALTHOUGH

BE FURNISHED AND INSTALLED WITHOUT ADDITIONAL COST.

ONE YEAR FROM DATE OF FINAL ACCEPTANCE OF THIS WORK. FINAL

IS TAKEN OVER AND ACCEPTED BY THE OWNER, AND IS UNDER CARE, CUSTODY,

ACCEPTANCE SHALL BE DEFINED AS THE TIME AT WHICH THE ELECTRICAL WORK

1. ALL MATERIALS AND WORKMANSHIP SHALL BE GUARANTEED FOR A PERIOD OF

E. GUARANTEE:

DESCRIBED ABOVE.

D. CONTRACT DOCUMENTS:

TO THE OWNER.

C. SITE VERIFICATION:

1.01 GENERAL REQUIREMENTS:

PART 1 GENERAL

B. CODES AND INSPECTIONS:

MOTORS.

EXAMINATIONS HAS BEEN MADE.

K. LIABILITY INSURANCE

J. EXISTING VIOLATIONS

OWNER AN SUBMIT DOCUMENT.

GENCY LIGHTING.

1.02 SCOPE OF WORK:

L. TEMPORARY LIGHT AND POWER

SCOPE OF WORK SHALL INCLUDE BUT NOT BE LIMITED TO THE FOLLOWING:

NECESSARY FOR COMPLETE, SAFE INSTALLATION OF ALL ELECTRICAL WORK. THE

A. PROVIDE ALL LABOR, MATERIALS, EQUIPMENT, AND CONTRACTOR'S SERVICES

ESTABLISHED BY O.S.H.A. ENERGY COSTS WILL BE BOURNE BY THE OWNER.

1. FURNISH ADEQUATE LIABILITY INSURANCE AND BONDING AS REQUIRED BY THE

1. ELECTRICAL CONTRACTOR SHALL PROVIDE TEMPORARY LIGHT AND POWER FOR

THE NEW CONSTRUCTION AREAS, IN ACCORDANCE WITH ACCEPTED STANDARDS

SUBMISSION OF A PROPOSAL; WILL BE CONSTRUCTED AS EVIDENCE THAT SUCH

2. INSTALLATION OF LIGHT FIXTURES AND LAMPS INCLUDING EXIT AND EMER

3. INSTALLATION OF WALL SWITCHES, RECEPTACLES, VOICE/DATA, OUTLETS, ETC.

4. INSTALLATION OF NEW RACEWAY AND CONDUCTORS FOR LIGHTING AND

5. CUTTING, CHANNELING AND CHASING REQUIRED TO ACCOMMODATE THE

ALL CONDUCTORS AND CONDUIT BACK TO THEIR SOURCE.

1. DEMOLITION AND REMOVAL OF ELECTRICAL EQUIPMENT AS REQUIRED INCLUDING

1. ALL PARTS IF THE EXISTING WORK AND ASSOCIATED EQUIPMENT SHALL BE

INSPECTED FOR COMPLIANCE WITH THE NEW YORK CITY ELECTRICAL CODE. ALL

VIOLATIONS MUST BE INCLUDED ON THE BID AS ADDITIONAL SERVICES.

EQUIPMENT.

THE AFOREMENTIONED EQUIPMENT.

ELECTRICAL INSTALLATION AND ROUGH PATCHING.

8. INSTALLATION OF CONDUIT, JUNCTION BOXES, PULL BOXES, ETC. REQUIRED FOR

9. MAINTENANCE AND PROPER OPERATION OF EXISTING BASE BUILDING SYSTEMS

WITHIN THE CONTRACT AREA IN ACCORDANCE WITH THE REQUIREMENTS OF

6. ADDITION OR MODIFICATION OF EXISTING ELECTRICAL DISTRIBUTION EQUIP

7. INSTALLATION OF HVAC POWER WIRING AND FINAL CONNECTIONS TO HVAC

MENT.

POWER.

ACCESSORIES. ALL OTHER EQUIPMENT AND OPERATIONS IN ANY WAY

AFFECTED BY THE REMOVAL IS TO REMAIN IN FULL OPERATION. PROVIDE ALL

NECESSARY COMPONENTS TO MAINTAIN SUCH OPERATION.

12. "REMOVE" - DISMANTLE AND CART AWAY FROM SITE INCLUDING ALL RELATED

I. CUTTING AND PATCHING

H. PERMITS AND FEES

CONCRETE FOUNDATIONS FOR EQUIPMENT, AND FURNISHING AND SETTING OF

1. DO ALL NECESSARY CUTTING AND ROUGH PATCHING. THE FOLLOWING WORK

WILL BE DONE BY OTHERS. FINISH PAINTING AND PATCHING. MASONRY BD

1. OBTAIN ALL PERMITS, FILE DOCUMENTS, PAY ALL FEES AND PERFORM ALL

TESTING AS REQUIRED BY ALL AUTHORITIES HAVING JURISDICTION.

PHONE OUTLET WITH 1" CONDUIT STUBBED INTO HUNG CEILING ($/OUT

A. FUSES SHALL BE CURRENT LIMITING TYPE WITH AN INTERRUPTING CAPACITY OF

C. ANY CIRCUIT BREAKERS MADE AVAILABLE DUE TO DEMOLITION SHALL BE

DESIGNATED AS SPARE ON PANELBOARD DIRECTORIES.

D. INSTALL CONDUIT EXPANSION FITTINGS IN EACH CONDUIT RUN WHEREVER IT

STRAIGHT RUN TERMINATED AT A BOX OR CABINET. WHERE RISER CONDUITS

INDICATE THE GENERAL LOCATION OF OUTLET BOXES AND CIRCUITING. THE

B. FOR ALL SIZES OF CONDUIT LARGER THAN 1-1/2", USE STANDARD ELBOW; IN

CONDUIT RUNS FOR THESE CIRCUITS MAY BE MODIFIED AT THE TIME OF

OF CONDUIT SHALL BEAR THE MAKER'S TRADEMARK OR STAMP. THE PLANS

COMBINED WEIGHTS OF CONDUIT, HANGER AND CABLES.

INSTALLATION TO ADAPT SAME TO BUILDING CONSTRUCTION.

FINAL CONNECTIONS TO MOTORS, LIGHT FIXTURES, ETC. MAY BE DONE WITH

CONCEALED IN CONCRETE SHALL BE RIGID THREADED REGARDLESS OF SIZE.

H. FEEDERS AND BRANCH CIRCUITRY ABOVE HUNG CEILING AND IN PARTITIONS

I. ALL CONDUIT IN MECHANICAL ROOMS, ELECTRICAL CLOSETS AND WHERE

E. RUNNING THREADS SHALL NOT BE USED. WHERE CONDUIT WITH TAPERED

CONCEALED IN CEILINGS, WALLS, SLABS, PIPE CHASES, AND FURRED SPACES

EXCEPT WHERE CROSSINGS ARE UNAVOIDABLE, THEN THE CONDUIT SHALL BE

G. UNLESS OTHERWISE INDICATED OR SPECIFIED, ALL WIRING SHALL BE INSTALLED

THREADS CANNOT BE COUPLED WITH STANDARD CONDUIT COUPLINGS UTILIZE

KEPT AT LEAST 1 INCH FROM THE COVERING OF THE PIPE CROSSING.

CROSSES AN EXPANSION JOINT AND WHEREVER THE CONDUIT LENGTH EXCEEDS

FLEXIBLE METALLIC CONDUIT (NO LONGER THAN SIX FEET).

O.Z./GEDNEY SPLIT COUPLING OR ERICKSON COUPLINGS.

FASTENINGS SHALL BE PROVIDED AT EACH ELBOW AND AT EACH END OF EACH

SHALL BE RUN IN ELECTRICAL METALLIC TUBING (EMT) UNLESS OTHERWISE NOTED.

HOT WATER PIPES. DO NOT RUN CONDUIT WITHIN THREE INCHES OF SUCH PIPES

F. LAY OUT AND INSTALL ALL CONDUIT RUNS TO AVOID PROXIMITY TO STEAM AND

CLAMPS, PIPE STRAPS OR HEAVY IRON TIES WIRED TO THE STRUCTURAL MEMBERS

SUPPORTING EQUIPMENT. SIZE AND TYPE OF ANCHOR SHALL BE BASED ON THE

PIERCE FLOOR SLABS, THEY SHALL REST ON EACH FLOOR WITH APPROVED BEAM

SMALLER SIZES, FIELD BENDS WILL BE PERMITTED INSTEAD OF USING MANUFAC-

TURED ELBOWS BUT CARE MUST BE TAKEN NOT TO DAMAGE THE CONDUIT. THE

C. CONDUIT SHALL BE SECURELY FASTENED IN PLACE AND HANGERS, SUPPORTS OR

RADIUS OF THE INNER CURVE OF ANY BEND SHALL NOT BE ANY LESS THAN THAT

A. ALL WIRES SHALL BE RUN IN CONDUIT AS SPECIFIED HEREINAFTER, EACH LENGTH

200,000 RMS AMPERES AND OF THE CONTINUOUS CURRENT RATINGS AS SHOWN

B. THEY SHALL HAVE AVERAGE MELTING TIME-CURRENT CHARACTERISTICS TO MEET

THE UNDERWRITERS' LABORATORIES REQUIREMENTS FOR "CLASS K" 0-600 AMP

FBO FURNISH BY OTHERS UON UNLESS OTHERWISE NOTED

EM EMERGENCY SWBD SWITCH BOARD

EC ELECTRICAL CONTRACTOR SD SMOKE DETECTOR

CO CONDUIT ONLY PB PULL BOX

E EXISTING Ø PHASE

DISC DISCONNECT PWR POWER

CU COPPER PNL PANEL

GFI GROUND FAULT INTERRUPTER WP WATERPROOF

FLUOR FLOURESCENT W WIRE

FA FIRE ALARM UF UNFUSED

ELEC ELECTRICAL SW SWITCH

GND GROUND

HR HOMERUN

HZ HERTZ

HC HUNG CEILING

IG ISOLATED GROUND

TYP TYPICAL

WHENEVER POSSIBLE.

HEIGHTS SHOWN ON ARCHITECTURAL DRAWINGS EXTRA COMPENSATION WILL NOT BE

CONSTRUCTION CONTRACTOR TO COORDINATE ALL WORK TO MAINTAIN CEILING

PLUMBING CONTRACTORS AND MAKE THOROUGH ARRANGEMENTS WITH THE

A. ELECTRICAL CONTRACTOR SHALL MEET WITH SPRINKLER, HVAC SHEETMETAL AND

CKT CIRCUIT NTS NOT TO SCALE

BB BASE BUILDING MLO MAIN LUGS ONLY

SHALL BE PROVIDED WITH SWAY BRACING FOR SEISMIC RESTRAINTS IN ACCOR

A AMP/AMPERE KVA KILOVOLTAMPERE

AWG AMERICAN WIRE GAUGE KCM THOUSAND CIRCULAR MILLS

ATS AUTOMATIC TRANSFER SWITCH MCB MAIN CIRCUIT BREAKER

A. ALL RACEWAYS AND EQUIPMENT SUSPENDED FROM THE BUILDING STRUCTURE

GRANTED FOR MIS-COORDINATED WORK.

CB CIRCUIT BREAKER N NEUTRAL

CDT CONDUIT MTD MOUNTED

ADA AMERICANS WITH DISABILITIES ACT KW KILOWATT

AHC ABOVE HUNG CEILING LTG LIGHTING

AFF ABOVE FINISH FLOOR Y WYE

DANCE WITH NEW YORK CITY LOCAL LAW 17/950

1.12 ABBREVIATIONS:

1.11 SEISMIC COMPLIANCE

1.10 COORDINATION WITH OTHER TRADES

(H) 3 1/2" EMT # 2

(J) 3/4" FLEXIBLE #1/0

(M) 1 1/2" FLEXIBLE

(L) 11/4" FLEXIBLE

(I) 4" EMT # 1

(4) RACEWAY ($/LIN. FT.) CONDUCTORS ($/LIN./FT)

(A) 3/4" EMT #14

(D) 1 1/2" EMT # 8

(E) 2" EMT # 6

(F) 2 1/2" EMT # 4

(G) 3" EMT # 3

(C) 1 1/4" EMT #10

(B) 1" EMT #12

(K) 1" FLEXIBLE

LET).

PERMITTED BY CODE.

200 FEET.

ON THE DRAWINGS.

FUSES AND "CLASS L" OVER 600 AMP FUSES.

2 .05 RACEWAYS:

2 .04 FUSES:

PART 2 - PRODUCTS/APPLICATION

E. A TYPEWRITTEN LIST OF CIRCUITS SHOWING CLEARLY THE LOADS SUPPLIED BY

B. PROVIDE CODE GAUGE STEEL DOORS FOR ALL PANELBOARD BOXES. FRONT

COVER SHALL BE A "DOOR WITHIN A DOOR" TYPE. THE OUTER DOOR (TRIM)

1000 AMPERES PER SQUARE INCH OF CROSS-SECTIONAL AREA. PROVIDE A

PIANO HINGE. THE INNER DOOR SHALL ALLOW ACCESS TO CIRCUIT BREAKERS

BOLTED TOGETHER WITH EXTERIOR ANGLE IRON FRAME. BOX SHALL BE OF

DRAWINGS. PANEL BOX AND COVER SHALL BE GIVEN TWO COATS OF GREY

SUFFICIENT SIZE TO ALLOW A GUTTER AT LEAST 5-3/4" IN WIDTH ENTIRELY

BUS BARS AS CALLED FOR ON PANEL SCHEDULES.

ONLY. PROVIDE LOCK AND KEY FOR INNER DOOR.

A. UNLESS OTHERWISE NOTED, DISCONNECT SWITCHES SHALL BE "QUICK-MAKE,

FOUND WITH UNBALANCED LOADS SHALL HAVE ITS CIRCUITS REARRANGED AS

THIS LIST SHALL BE MOUNTED IN A STEEL FRAME UNDER A PLASTIC WINDOW.

PANELBOARD BREAKERS SHALL BE OF THE SAME MANUFACTURER ANDBE

WEATHERPROOF DISCONNECT SWITCHES WHERE INSTALLED OUTDOORS OR AS

REQUIRED TO BALANCE PHASE LEGS WITHIN 10%.

INDICATING PANEL IDENTIFICATION AND VOLTAGE.

AS INDICATED ON THE DRAWINGS. PROVIDE ALL FUSES AS REQUIRED. PROVIDE

QUICK-BREAK," HEAVY DUTY TYPE IN NEMA 1 ENCLOSURES FUSED OR UNFUSED

D. PANELS SHALL BE PROVIDED WITH NEUTRAL BARS SIZED AT 200% OF THE PHASE

EACH CIRCUIT SHALL BE INSTALLED ON THE INSIDE OF EACH PANEL BOARD DOOR.

EACH PANEL SHALL BE EXTERNALLY TAGGED WITH PERMANENT LAMACOID PLATE

F. PHASE LEGS OF ALL PANELS SHALL BE BALANCED AT SUPPLY POINT. ANY PANEL

SHALL ALLOW ACCESS TO ENTIRE PANELBOARD BOX INCLUDING GUTTER SPACES.

C. PANEL BUS BARS SHALL BE COPPER PROPORTIONED FOR A CURRENT DENSITY OF

COPPER GROUND BAR IN EACH PANEL. PROVIDE AN ISOLATED GROUND BAR IN

OUTER DOOR (TRIM) SHALL BE ATTACHED DIRECTLY TO BOX BY A FULL LENGTH

SURROUNDING EACH SECTION OF BOARD. INCREASE GUTTER SIZE TO ACCOMMO

DATE FEEDER SIZE.BOARDS SHALL BE SURFACE OR FLUSH TYPE AS NOTED ON THE

A. PANELBOARD BOXES SHALL BE MADE OF SHEET STEEL "BENT-UP" OR RIVETED OR

A. FOR PANELBOARD APPLICATIONS, CIRCUIT BREAKERS SHALL BE BOLTED TO THE

PANELBOARD BUS BARS. WHERE CIRCUIT BREAKERS ARE INSTALLED IN EXISTING

BREAK WITH NON-WELDING CONTACTS COMPENSATED FOR AMBIENT TEMPERA

COMPATIBLE WITH EXISTING PANELBOARD. FOR STAND ALONE APPLICATIONS,

CIRCUIT BREAKERS SHALL BE IN A NEMA 1 ENCLOSURE.

TURES AND SHALL HAVE A MINIMUM SHORT CIRCUIT RATING OF 10,000 AMPERES

SYMMETRICAL FOR 120/280V PANELS AND 14,000 AMPERES SYMMETRICAL FOR

B. CIRCUIT BREAKERS SHALL BE "THERMAL MAGNETIC" TYPE, QUICK-MAKE, QUICK-

OWN EXPENSE. ANY MODIFICATIONS TO ASSOCIATED SYSTEMS OR ADDITIONAL COSTS

ATTRIBUTED TO THIS SUBSTITUTION SHALL BE AT THIS CONTRACTOR'S EXPENSE.

PERFORMANCE REQUIREMENTS SHOWN ON CONTRACT DOCUMENTS. CONTRACTOR

SHALL REPLACE ANY EQUIPMENT THAT DOES NOT MEET THESE REQUIREMENTS AT HIS

B. ALL SUBSTITUTED EQUIPMENT SHALL CONFORM TO SPACE REQUIREMENTS AND

1. AMOUNTS INDICATED SHALL BE FOR WORK FULLY INSTALLED COMPLETE WITH

INDICATING THE SIZE AND LOCATION OF ALL ACCESS DOORS REQUIRED FOR

OPERATION AND MAINTENANCE OF ALL CONCEALED EQUIPMENT, DEVICES, JUNCTION

BOXES, PULL BOXES ETC. THIS CONTRACTOR SHALL ARRANGE FOR THE FURNISHING

AND INSTALLATION OF ALL ACCESS DOORS IN FINISHED CONSTRUCTION AND INCLUDE

COSTS IN THE BID. ACCESS DOORS SHALL BE OF ADEQUATE SIZE TO PROVIDE ACCESS

A. THIS CONTRACTOR SHALL SUBMIT TO THE ARCHITECT FOR APPROVAL A PLAN

C. CONTRACTOR SHALL SUBMIT BID BASED ON SPECIFIED ITEMS AND SHALL SUPPLY AS

3. UNIT PRICES ARE TO BE A MAXIMUM PRICE, NOT TO EXCEED COST UNDER ANY

2. UNIT PRICES SHALL INCLUDE ALL RELATED GENERAL CONDITIONS, OVER-HEAD,

(2) RECEPTACLE - ADD/DEDUCT PRICE FOR EACH TYPE SPECIFIED ON

(3) DATA/TELEPHONE OUTLET -ADD/DEDUCT PRICE FOR WALL MOUNTED TELE

(1) LIGHT FIXTURES -FOR EACH TYPE SPECIFIED ON DRAWINGS ($/FIXTURE)

ALL ASSOCIATED COMPONENTS. AMOUNTS INDICATED SHALL BE BINDING FOR

FRINGES REQUIRED. UNIT PRICES TO BE TAKEN EQUALLY FOR ALL ADDS AND

PROFIT, INSURANCES, LABOR, ENGINEERING MATERIALS, SUPERVISION AND

A. GENERAL

DRAWINGS ($/RECEPTACLE).

THE DURATION OF THE PROJECT.

DEDUCTS TO THE CONTRACT DOCUMENTS.

1. ELECTRICAL

B. LIST OF UNIT PRICES:

CIRCUMSTANCES.

AN ALTERNATE PRICE ANY SUBSTITUTIONS.

1.08 ACCESS DOORS IN GENERAL CONSTRUCTION:

TO CONCEALED ITEMS FOR OPERATION AND MAINTENANCE.

1.09 UNIT PRICES:

INDICATED ON DRAWINGS.

2 .02 DISCONNECT SWITCHES:

2 .03 CIRCUIT BREAKERS:

277/480V PANELS OR HIGHER WHERE NOTED.

PANELS AS INDICATED ON PANEL SCHEDULES.

SPECIFIED ITEM, THOSE DEVIATIONS ARE TO BE IDENTIFIED ON A LINE BY LINE BASIS.

IF THE SUBSTITUTE IS BEING UTILIZED FOR FINANCIAL REASONS, THE ASSOCIATED

WITHOUT A FORMAL WRITTEN SUBMITTAL TO THE ENGINEER WHICH INCLUDES ALL

DIMENSIONAL, PERFORMANCE AND MATERIAL SPECIFICATIONS. ANY CHANGES IN

LAYOUT, MECHANICAL CHARACTERISTICS, STRUCTURAL REQUIREMENTS, OR DESIGN

A. NO SUBSTITUTE MATERIAL OR MANUFACTURER OF EQUIPMENT SHALL BE PERMITTED

DUE TO THE USE OF A SUBSTITUTION SHALL BE SUBMITTED TO THE ENGINEER AS PART

OF THIS PROPOSAL. THE CONTRACTOR TAKES FULL RESPONSIBILITY FOR THE

SUBSTITUTION AND ALL CHANGES RESULTING FROM SUBSTITUTION. ALL ITEMS SHALL

BE SUBMITTED FOR REVIEW IN CONJUNCTION WITH THE SUBMITTAL OF THE

ALTERNATE. ANY SUBSTITUTION MUST BE SUBMITTED WITH AN EXPLANATION WHY

A SUBSTITUTION IS BEING UTILIZED. IF THE SUBSTITUTED ITEM DEVIATES FROM THE

CREDIT MUST BE SIMULTANEOUSLY SUBMITTED.

1.07 SUBSTITUTIONS:

2 .01 PANELBOARDS:

ENAMEL PAINT.

seal & signature

dwg title

twig

cadd

checked by

issue date

AS NOTED

drawn by

02/11/2011

project no.

dwg. no.

scale

cad file

t10-12-0230

375 Beach 92nd StreetQueens, NY 11693

SUBMISSIONS

DATE rev no issue

project

project

375 Beach 92nd StreetQueens, NY 11693

architect

231 West 29th Street - Suite 606, New York, NY 10001

Tel: 212 . 967 . TWIG / Fax: 212 . 967 . 8945

[email protected] www.twigcon.com

A Division of The Wall Consulting Group, Inc. All Rights Reserved. 2007- 2010©

375 Beach 92nd Street E-201.00.dwg

NYC dob#

sheetTHESE PLANS ARE APPROVED ONLY FOR THE WORK ON THE

BEING APPROVED OR IN ACCORDANCE WITH APPLICABLE CODES.

APPLICATION SPECIFICATION SHEET. ALL OTHER MATTERS SHOWN

ARE NOT TO BE RELIED UPON OR TO BE CONSIDERED AS EITHER

All Drawings And Written Material Herein Constitute The Original And Unpublished Work Of The Wall Consulting Group, Inc. and/or TWIG Consulting Engineers, P.C., And The Same May Not Be Duplicated, Used, Or Disclosed Without The Written Consent Of The Wall Consulting Group, Inc. and/or TWIG Consulting Engineers, P.C. © 2011.

NYCECC NOTES:

TO THE BEST OF MY KNOWLEDGE, BELIEF AND

PROFESSIONAL JUDGMENT, THESE PLANS AND

SPECIFICATIONS ARE IN COMPLIANCE WITH THE

NEW YORK CITY ENERGY CONSERVATION CODE.

02.14.11 1 FILING & PRICING

GROUND FLOORELECTRICALSPECIFICATIONSSHEET I

2 of 7

Page 3: NORTH - Thai Rock · battery pack recessed wac lighting fixture, adjustable trim: hr-d-417, white housing , hr-8402e1, 35w pendant mounted ex. surface mounted fluorescent lightolier

ELECTRICAL SPECIFICATIONS - II

A. PULLBOXES, JUNCTION BOXES AND OUTLET BOXES SHALL BE MANUFACTURED

GREY, EQUIPMENT GROUND - GREEN. 277/480 VOLT SYSTEM: PHASE 'A' - BROWN, PHASE

H. INSTALL AND CONNECT UP COMPLETE CONDUCTORS FOR ALL CIRCUITS AND

J. TAG ALL FEEDERS IN ALL PULL BOXES, GUTTER SPACES, AND WIREWAYS

M. SPLICES IN BRANCH WIRING (#8 AWG AND SMALLER) SHALL BE TWISTED AND

IN DATA PROCESSING/COMMUNICATION ROOM RAISED FLOOR CAVITIES.

TRANSFORMERS, UPS SYSTEMS WITH COMPRESSION TYPE CONNECTORS. AT

PANELBOARDS TERMINATE WITH MECHANICAL LUGS.

TYPE. FINISH OF TOGGLE AND DEVICE PLATE AS DIRECTED BY ARCHITECT.

SPEED SWITCHES SHALL MATCH THE DIMMING SWITCH STYLE.

MANUFACTURER'S REQUIREMENTS WHEN GANGED.

L. JOIN OR TAP STRANDED CONDUCTORS (#6 AWG AND LARGER) WITH PRESSURE

INDENT TYPE CONNECTORS BURNDY, NEPCO, OR O.Z./GEDNEY WITH COMPOSITION

TYPE CONNECTORS SHALL NOT BE USED. UTILIZE UL LISTED "SILICON FILLED"

MADE MECHANICALLY TIGHT; THEN SECURED WITH PIGTAIL CONNECTORS, CRIMP

N. SUPPORT CONDUCTORS IN VERTICAL RACEWAYS AT THE TOP OF ANY RACEWAY

PIGTAIL CONNECTORS WHERE LOCATED IN WET ENVIRONMENTS, OUTDOORS OR

DEVICES AND PLATES SHALL BE PLUMB AND FLUSH MOUNTED UNLESS OTHER

A. WIRING DEVICES SHALL BE SPECIFICATION GRADE UNLESS OTHERWISE NOTED. ALL

WHICH ARE NOT GREATER THAN 40 FEET. SUPPORT SHALL BE O.Z./ GEDNEY TYPE R.

LONGER THAN 20 FEET. INCLUDE ADDITIONAL SUPPORTS SPACED AT INTERVALS

E. MULTIPLE DEVICES AT A COMMON LOCATION SHALL BE INSTALLED IN A COMMON

SINGLE POLE OR VARIABLE SPEED TYPE SWITCHES, THE SINGLE POLE/ VARIABLE

AS DIRECTED BY ARCHITECT. WHERE DIMMER SWITCHES ARE LOCATED NEXT TO

C. DIMMERS SHALL BE RATED AT 120 VOLT, WATTAGE SIZE AS REQUIRED. FINISH

D. STANDARD RECEPTACLES SHALL BE 120 VOLT, 15 AMP, 2 POLE GROUNDING TYPE.

B. SWITCHES SHALL BE 120/277 VOLTS, RATED AT 20 AMPERES, QUIET OPERATION

B. ALL FIXTURES THAT ARE EXISTING TO BE REUSED SHALL BE CLEANED, RELAMPED

MULTIGANG BOX WITH A COMMON FACEPLATE. DERATE DIMMER SWITCHES PER

WITH THE NEW OR EXISTING CEILING SYSTEM TYPE. ALL FIXTURES SHALL BE

A. ALL LIGHT FIXTURE MOUNTING HARDWARE SHALL MATCH AND BE COORDINATED

AND REBALLASTED. ANY DEFECTIVE OR DAMAGED PARTS SHALL BE REPAIRED OR

I. NO CONDUCTORS SHALL BE PULLED INTO ANY CONDUIT RUN BEFORE ALL CONDUIT

WIRING SYSTEMS UNLESS OTHERWISE NOTED. UP TO 3 SINGLE CIRCUITS MAY BE

K. TERMINATE STRANDED CONDUCTORS #6 AWG AND LARGER AT SWITCHBOARDS,

SOAPSTONE, MINERALLAC #100 OR APPROVED EQUAL BY THOMAS AND BETTS.

WHEN REQUIRED TO EASE THE PULLING OF WIRES INTO CONDUIT, USE POWDERED

JOINTS ARE MADE UP TIGHTLY, AND THE ENTIRE RUN IS SECURED IN PLACE.

2 .08 LIGHT FIXTURES:

EQUIPPED WITH "EARTHQUAKE" CLIPS.

REPLACED.

2 .07 WIRING DEVICES:

WISE NOTED. REFER TO SYMBOL LIST.

THROUGH WHICH THEY PASS.

INSULATING COVERS.

RUN IN A CONDUIT.

I. BARRIERS IN JUNCTION AND PULL BOXES SHALL BE OF CONDUCTIVE MATERIAL OF

2 .11 SUPPORTS AND FASTENINGS:

AS SPECIFIED HEREIN.

INSTALLATION OF ELECTRIC EQUIPMENT.

J. ALL EQUIPMENT, DEVICE BOXES, JUNCTION BOXES, PULLBOXES AND OUTLET

BOXES SHALL BE INSTALLED SO AS TO ALLOW ACCESS TO THE BOX. IF

ADEQUATE THICKNESS FOR MECHANICAL STRENGTH BUT IN NO CASE LESS THAN

1/8". EACH BARRIER SHALL HAVE AN ANGLE IRON FRAMING SUPPORT ALL

A. ALL SUPPORTS AND FASTENINGS NECESSARY FOR THE SUPPORT OF ELECTRICAL

B. FURNISH AND INSTALL ALL STEEL SUPPORTING MEMBERS, HANGERS, BRACKETS

COVERPLATES IN AREAS WHERE UNOBSTRUCTED ACCESS IS NOT POSSIBLE.

EQUIPMENT SHALL BE IN ACCORDANCE WITH THE BEST INDUSTRY PRACTICE AND

OR OTHER SPECIAL DETAILS REQUIRED AND NECESSARY FOR THE PROPER

NECESSARY AND APPROVED BY ARCHITECT, PROVIDE ACCESS DOOR OR

AROUND.

REMOVABLE BACKPLATE WHERE REQUIRED.

LENGTH TO SUIT CONDITIONS.

E. LIGHTING FIXTURE BOXES SHALL BE 4 INCH OCTAGON WITH 3/8 INCH FIXTURE

F. INCLUDE ALL REQUIRED JUNCTION/PULL BOXES AND OUTLET BOXES REGARDLESS

G. WHERE BOXES HAVE ANY SINGLE HORIZONTAL DIMENSION LARGER THAN 36",

NOTATION, MAY NOT SHOW ALL THAT ARE ACTUALLY REQUIRED).

STUD. FOR SUSPENDED CEILING WORK, PROVIDE A 4 INCH OCTAGON BOX WITH

OF INDICATIONS ON THE DRAWINGS WHICH DUE TO SYMBOLIC METHODS OF

THEY SHALL BE FITTED WITH CABLE SUPPORT RACKS CONSISTING OF 3/4"

PIPE SUPPORT RACKS SHALL BE INCLUDED WITH THE PULLBOX SO THAT NO CABLE

REMAINS UNSUPPORTED FOR A HORIZONTAL DISTANCE GREATER THAN 36". IN

NO CASE SHALL CABLE SUPPORT PIPE RACKS BE MOUNTED SO THAT THEY

INTERFERE WITH THE REMOVAL OF SCREW COVERS.

CORRESPONDING TO THE CABLES ENTERING AND LEAVING THE BOX. SUFFICIENT

OF THE PULL BOXES. EACH PIPE SUPPORT SHALL BE FITTED WITH A CONTINUOUS

FIBER INSULATING SLEEVE. THE PIPE SUPPORTS SHALL BE ARRANGED IN TIERS

DIAMETER STEEL PIPES WITH FLANGED ENDS BOLTED TO THE SIDES OR FRAME

B. PROVIDE PULL BOXES AND JUNCTION BOXES IN LONG STRAIGHT RUNS OF

WAY BETWEEN CABLE ACCESS POINTS, THE ACCESSIBILITY OF CABLE JOINTS AND

TO FULFILL REQUIREMENTS AS TO THE NUMBER OF BENDS PERMITTED IN RACE

RACEWAY TO ASSURE THAT CABLES ARE NOT DAMAGED WHEN THEY ARE PULLED,

FROM GALVANIZED INDUSTRY STANDARD GAUGE SHEET STEEL.

SPLICES, AND THE APPLICATION OF CABLE SUPPORTS.

C. PULLBOXES AND JUNCTION BOXES SHALL BE SIZED SO THAT THE MINIMUM

D. SWITCH RECEPTACLE AND WALL OUTLET BOXES SHALL BE A NOMINAL 4 INCH

FIXTURE STUD AS REQUIRED. GANGED OUTLET BOXES SHALL BE SUFFICIENT

COVER, UNLESS OTHERWISE INDICATED ON THE DRAWING. PROVIDE 3/8 INCH

SQUARE, 1-1/2 INCH OR 2-1/8 INCH DEEP AS REQUIRED BY CODE WITH A RAISED

BENDING RADIUS CRITERIA SPECIFIED FOR THE WIRES AND CABLE ARE MAIN

2. BETWEEN 277/480V WIRING CONNECTED TO DIFFERENT SERVICES.

1. BETWEEN NORMAL AND EMERGENCY WIRING.

H. PULL/JUNCTION BOX BARRIERS SHALL BE PROVIDED FOR SYSTEMS AS FOLLOWS:

TAINED.

K. FLEXIBLE METALLIC CONDUIT SHALL BE OF THE GROUNDING TYPE. IT SHALL

M. THREADED FITTINGS SHALL BE USED WITH RIGID CONDUIT. SET SCREW OR

O. ALL METAL CONDUIT TERMINATING IN A METAL ENCLOSURE SHALL HAVE AN

COMMUNICATION/DATA ROOM OR CLOSET. FURNISH DRAG LINE.

COMPRESSION FITTINGS SHALL BE USED WITH EMT.

INTO ACCESSIBLE HUNG CEILING AND DIRECTED TOWARDS PARTICULAR

D. RECESSED LIGHTING FIXTURES FOR HUNG CEILING APPLICATIONS SHALL BE

B. ALL CONDUCTORS SHALL BE SOFT 98% MINIMUM CONDUCTIVITY PROPERLY

SINGLE OUTLET BOX. NO FIXTURE SHALL BE SUPPLIED FROM AN OUTLET IN

IT SHALL ONLY BE INSTALLED WHERE PERMITTED BY CODE.

LENGTHS NOT TO EXCEED 6 FEET FROM ADJACENT JUNCTION BOXES.

120 VOLT CIRCUITS OVER 100' IN LENGTH SHALL BE NO. 10 AWG.

600 VOLT RATED INSULATION UNLESS OTHERWISE NOTED.

CONSIST OF GALVANIZED STEEL TAPE FORMED INTO AN INDUSTRY STANDARD

L. RIGID METAL CONDUIT SHALL BE INDUSTRY STANDARD STEEL CONDUIT. IT SHALL

INTERLOCKING COIL. IT SHALL NOT BE LESS THAN 3/4" TRADE SIZE UNLESS

EMT SHALL BE HOT DIPPED GALVANIZED STEEL ONLY. IT SHALL NOT BE LESS

THAN 3/4" TRADE SIZE UNLESS OTHERWISE NOTED. IT SHALL BE USED FOR TRADE

THAN 4" UNLESS OTHERWISE NOTED. ALUMINUM SHALL BE ACCEPTABLE EXCEPT

SHALL BE HOT DIPPED GALVANIZED. IT SHALL BE USED FOR TRADE SIZE GREATER

SHALL BE 1" THIN WALL RUN CONCEALED WALLS, TERMINATED AND BUSHED 6"

N. EMPTY CONDUIT FOR NEW COMMUNICATION AND DATA OUTLETS IN PARTITIONS

NOT BE LESS THAN 3/4" TRADE SIZE UNLESS OTHERWISE NOTED. STEEL CONDUIT

WRITTEN APPROVAL IS GIVEN TO THE CONTRACTOR FROM THE BUILDING OWNER.

A. METAL CLAD (TYPE MC) FOR CONCEALED BRANCH CIRCUITRY MAYBE USED WHEN

INSULATED BUSHING. PROVIDE "GROUNDING" TYPE BUSHING WHERE REQUIRED.

SUPPLIED WITH TYPE THHN INSULATED WIRE IN FLEXIBLE METALLIC CONDUIT, IN

C. THE MINIMUM WIRE SIZE FOR BRANCH CIRCUITS SHALL BE NO. 12 AWG EXCEPT

REFINED COPPER, TYPE THHN/THWN INSULATED. ALL CONDUCTORS SHALL HAVE

J. ELECTRIC METALLIC TUBING SHALL BE INDUSTRY STANDARD THIN WALL CONDUIT,

ARRANGED SO THAT UP TO FOUR SUCH FIXTURES MAY BE CONNECTED INTO A

E. CONNECTION TO RECESSED CEILING FIXTURES SUPPLIED WITH PIGTAILS SHALL BE

F. UNLESS SPECIFIED OTHERWISE, ALL WIRES #10 AWG AND SMALLER SHALL BE

SOLID, CONDUCTORS #8 AWG AND LARGER SHALL BE STRANDED.

EXISTS, FACTORY COLOR CODING SHALL BE AS FOLLOWS:

G. COLOR CODING SHALL BE BUILDING STANDARD. WHERE NO BUILDING STANDARD

120/208 VOLT SYSTEM: PHASE 'A' - BLACK, PHASE 'B' - RED, PHASE 'C' - BLUE, NEUTRAL -

ANOTHER ROOM.

2. 06 WIRE AND CABLE:

FOR CONCRETE ENCASEMENT.

SIZE UP TO 4" UNLESS OTHERWISE NOTED.

OTHERWISE NOTED.

2 .09 FIRE ALARM SYSTEM:

RELOCATE AT OWNER'S DIRECTION.

DEVICES IN OPERATION AT ALL TIMES.

G. PROVIDE LAMPS SUITABLE FOR LIGHTING FIXTURES IN WHICH THEY ARE USED AND

A. THE ELECTRICAL CONTRACTOR SHALL FURNISH NEW FIRE ALARM EQUIPMENT AS

FROSTED AND RATED AT 120 VOLTS UNLESS OTHERWISE SPECIFIED.

AS INDICATED ON THE DRAWINGS. FLUORESCENT LAMPS SHALL BE "RAPID START"

AND SHALL DELIVER NOT LESS THAN 3150 LUMENS. COLOR SHALL BE WARM

WHITE UNLESS OTHERWISE NOTED. INCANDESCENT LAMPS SHALL BE INSIDE

RESPONSIBILITY OF THIS CONTRACTOR TO NOTIFY THE BUILDING OWNER AND

C. IT IS THIS CONTRACTOR'S RESPONSIBILITY TO MAINTAIN FIRE ALARM SPEAKERS,

B. WHERE CONSTRUCTION INTERFERES WITH EXISTING FIRE ALARM EQUIPMENT, OR

IT IS LOCATED ON EXISTING WALLS TO BE DEMOLISHED, IT SHALL BE THE

ALARM VENDOR'S COST FOR TIE-IN'S, PROGRAMMING, PARTS, ETC.

ANY WORK. THE ELECTRICAL CONTRACTOR'S BID SHALL INCLUDE ANY FIRE

COORDINATE WITH THE BASE BUILDING FIRE ALARM SYSTEM VENDOR PRIOR TO

SHOWN AND CONNECT TO THE EXISTING FIRE ALARM SYSTEM. RETAIN AND

D. ELECTRICAL CONTRACTOR SHALL FILE FORM A-433, "APPLICATION FOR ELECTRI

CAL INSPECTION" WITH THE BUREAU OF FIRE PREVENTION AT 9 METROTECH

STROBES, SMOKE DETECTORS, FIRE WARDEN STATIONS AND OTHER FIRE SAFETY

ACCOMPANY THE FIRE DEPARTMENT INSPECTOR DURING HIS INSPECTION OF THE

CENTER, BROOKLYN, NEW YORK. ELECTRICAL CONTRACTOR SHALL THEN

F. WHERE DIMMING OF FLUORESCENT FIXTURES IS REQUIRED, THE ELECTRONIC

REQUIRED TO ACCOMMODATE THE FIXTURE DESCRIBED IN THE FIXTURE SCHED

REGULATIONS PART 18. ELECTRONIC BALLASTS FOR 1, 2, 3, OR 4 LAMP

COMBINATIONS AS WELL AS COMPACT FLUORESCENT LAMPS SHALL BE USED AS

BY LUTRON. THE CONTRACTOR MUST COORDINATE THIS WITH THE LIGHTING

BALLAST INSTALLED MUST BE COMPATIBLE WITH THE DIMMING SWITCH. IF

LUTRON DIMMING PRODUCTS ARE USED THE BALLAST MUST BE MANUFACTURED

MANUFACTURER AND LUTRON PRIOR TO PLACING FIXTURE ORDER.

RELATING TO THIS INSPECTION.

SYSTEM, MAKE ALL MODIFICATIONS REQUIRED BY THE INSPECTOR RESULTING

AFFIDAVIT. ELECTRICAL CONTRACTOR SHALL PAY ALL FIRE DEPARTMENT FEES

FROM ISSUANCE OF "NOTICE OF DEFECTS" AND FILE A SELF CERTIFICATION

2 .10 PULLBOXES, JUNCTION BOXES AND OUTLET BOXES:

ULE.

D. FLUORESCENT BALLASTS SHALL BE UL'S CLASS "P" AND SHALL CONFORM TO

C. ALL FIXTURES SHALL BE FREE OF LIGHT LEAKS ABOVE OR BELOW CEILING.

BALLAST FACTOR (0.95 MINIMUM).

E. ELECTRONIC BALLASTS SHALL BE HIGH-FREQUENCY, FULL OUTPUT TYPE FOR USE

LOW HEAT DESIGN WITH HIGH POWER FACTOR (0.9 MINIMUM) AND A HIGH

WITH 265 MA RAPID START T-8 LAMPS. THEY SHALL HAVE A 'A' SOUND RATING

BALLASTS FOR FLUORESCENT LAMPS SHALL BE OF THE ENERGY SAVING SUPER

TION BY C.B.M. BALLASTS SHALL COMPLY WITH THE STATE ENERGY CODE.

HARMONIC CURRENT DISTORTION (THD). BALLASTS SHALL MEET OR EXCEED FCC

OR BETTER. ALL ELECTRONIC BALLASTS SHALL HAVE LESS THAN 20% TOTAL

ANSI AND UL SPECIFICATION WITH LABELS OF APPROVAL BY UL AND CERTIFICA

7. JUNCTION/PULL BOXES: APPLETOWN ELECTRIC, CROUSE HINDS OR O.Z./

WIRING AND COMPONENTS SHALL BE INSTALLED AS DIRECTED BY VENDOR.

TASK LIGHTING FIXTURES, WIRING HARNESSES, CONNECTORS AND FITTINGS TO

THE ELECTRICAL CONTRACTOR FOR THE COMPLETE WIRING INSTALLATION. ALL

CONDUIT CONNECTIONS WITH REQUIRED PHASE CONDUCTORS, NEUTRAL

WIRING, RECEPTACLES. COVERPLATES, FITTINGS ETC. IN TABLE .

THIS FURNITURE IS FURNISHED WITH OPENINGS ONLY.

EXISTING TO BE REUSED THE CONTRACTOR SHALL CLEAN AND REFURBISH THE

EQUIPMENT. THIS SHALL INCLUDE TIGHTENING ALL CONNECTIONS, PLACING

DEFECTIVE MECHANISMS, EXERCISING MECHANISMS AND PROVIDING ANY

A. AT THE COMPLETION OF THE LIFE SAFETY SYSTEM INSTALLATION THE

3 .04 EXISTING EQUIPMENT REFURBISHMENT

ADHESIVE ('P' TOUCH TYPE) LABELS IN EXPOSED LOCATIONS. EMERGENCY

C. EMPTY CONDUITS SHALL BE IDENTIFIED WITH TAGS AT BOTH ENDS INDICATING

SHALL BE BY WHITE ON BLACK PLASTIC NAMEPLATE WITH 1/2" MINIMUM

CONTROL PANELS SHALL BE IDENTIFIED WITH SYSTEM NAME. IDENTIFICATION

AMPERE RATING, EQUIPMENT SERVED AND ORIGIN OF THE INCOMING FEED.

BE CLEARLY IDENTIFIED WITH THE EQUIPMENT DESIGNATION, VOLTAGE AND

B. JUNCTION BOXES, SPLICE BOXES, ETC., SHALL BE IDENTIFIED WITH PANEL AND

DEVICES SHALL BE IDENTIFIED IN RED AND UPS DEVICES IN BLUE.

THE LOCATION OF TERMINATION OF THE OPPOSITE END.

SHALL BE IDENTIFIED WITH THE NAME OF THE DEVICE CONTROLLED.

A. WHERE PANELBOARDS, SWITCHES, CIRCUIT BEAKERS, TRANSFORMERS, ETC. ARE

MISCELLANEOUS COMPONENTS SO THE EQUIPMENT IS IN FIRST CLASS WORKING

D. FIRE ALARM SYSTEM JUNCTION BOXES SHALL BE PAINTED FIRE DEPARTMENT RED.

DEVICES AND SUBMIT A REPORT TO THE ENGINEER VERIFYING THAT THE SYSTEMS

A. ALL PANELBOARDS, CONTROL PANELS, AND CABINETS SPECIFIED HEREIN SHALL

IDENTIFICATION SHALL BE BY INDELIBLE MARKER IN CONCEALED LOCATIONS AND

FOR EQUIPMENT SUCH AS PANTRY EXHAUST FANS, MOTORIZED SCREENS, ETC.

CIRCUIT NUMBERS, FOR CIRCUITS CONTAINED THEREIN. FACEPLATE OF SWITCHES

CONTRACTOR SHALL TEST ALL FIRE ALARM DEVICES AND EMERGENCY LIGHTING

ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL BACK BOXES, CONDUIT,

ELECTRICAL CONTRACTOR SHALL FURNISH 18" MAXIMUM LIQUID TIGHT FLEXIBLE

CONDUCTORS AND GROUND CONDUCTORS AS INDICATED FROM WALL ON FLOOR

A. THE ELECTRIFIED FURNITURE VENDOR WILL SUPPLY ALL RECEPTACLES, FURNITURE

F. ALL PANELBOARD COVERS SHALL BE REPLACED AT THE COMPLETION OF EACH

REQUIRED BY OTHER TRADES. COORDINATE WITH OTHER TRADES PRIOR TO

I. PRIOR TO ANY CHASING, CHOPPING, OR CORE DRILLING BEING PERFORMED, THE

REQUIRED. THIS WORK MUST BE APPROVED BY BUILDING MANAGEMENT PRIOR TO

WORK AND NOT AFFECTED ANY EXISTING BUILDING SYSTEMS. X-RAY SLABS IF

APPROPRIATE TRADES TO ENSURE THAT WORK WILL BE IN HARMONY WITH OTHER

CONTRACTOR SHALL FIELD INVESTIGATE CONDITIONS AND COORDINATE WITH ALL

H. MEGGER TEST TEMPERATURE MAINTENANCE CABLE AND HEAT TRACING CABLE AS

G. MAINTAIN GROUND CONTINUITY THROUGHOUT ALL SYSTEMS.

PROCEEDING.

DAYS WORK.

SUBMISSION OF BID.

APPROVED IDENTIFICATION.

9. FIRE STOP MATERIAL: HILTI, 3M (NOTE: MATERIAL MUST BE ACCEPTABLE TO

B. ALL DATA/VOICE/COMMUNICATION WIRING SHALL BE INSTALLED BY OTHERS.

RATED WALLS, PARTITIONS, FLOORS, OR CEILINGS SHALL BE FIRE STOPPED USING

D. PROVIDE DANGER LABELING AT ALL EQUIPMENT AND JUNCTION/PULL BOXES PER

E. AT COMPLETION OF ELECTRICAL WORK ALL "IN SLAB" TRENCH DUCT COVERS

A. ALL CONTROL WIRING ASSOCIATED WITH MECHANICAL EQUIPMENT IS THE

APPROVED METHODS. SEALANT SHALL BE RATED FOR 3 HOURS.

C. OPENINGS AROUND ELECTRICAL PENETRATIONS THROUGH FIRE RESISTANCE

RESPONSIBILITY OF THE MECHANICAL CONTRACTOR.

COORDINATE WITH THE RESPECTIVE INSTALLER.

SHALL BE REPLACED.

CODE.

3 .01 GENERAL:

PART 3 - EXECUTION

8. TRANSFORMERS: ITE, WESTINGHOUSE, GE OR SQUARE "D

14. LIGHT SWITCHES: HUBBELL, LEVITON

15. DIMMER SWITCHES: LUTRON T-STAR (NT/NTLV SERIES)

16. RECEPTACLES: HUBBELL, LEVITON�

13. OCCUPANCY SENSORS: NOVITAS, WATT STOPPER

12. BALLASTS: MOTOROLA, ESB, UNIVERSAL

11. LAMPS: GE, SYLVANIA, PHILLIPS

10. FITTINGS, COUPLINGS, BUSHINGS,CONNECTORS: OZ GEDNEY, BURNDY,

GEDNEY CO.

LOCAL AHJ)

NEPCO,THOMAS AND BETTS

ORDER.

ARE FULLY OPERATIONAL.

3 .06 IDENTIFICATION OF EQUIPMENT

3 .05 LIFE SAFETY TESTING

LETTERING ATTACHED BY SCREWS.

OUTLET.

B. CONFERENCE TABLE:

3 .03 ELECTRIFIED FURNITURE SYSTEMS

J. FURNISH AND INSTALL WIRING FOR ADEQUATE LIGHT AND SMALL TOOLS POWER

HANDLE. PANELBOARDS - 6'-6" TO MCB OR TOP CIRCUIT BREAKER (IF NO

STEEL MEMBERS, INSERTS, ANCHORS, WIRES AND THE REQUIRED ASSEMBLY

ACCORDANCE WITH ALL LOCAL CODES AND ORDINANCES HAVING JURISDICTION.

K. MOUNTING HEIGHTS: DISCONNECT SWITCHES OR ENCLOSED CB'S -6'-6" TO

WHETHER THEY ARE REPRESENTED ON THE DRAWINGS OR NOT. ALL BRANCH

BOXES SPLICE BOXES, ETC. IN DEMOLITION AREA SHALL BE COMPLETELY

B. ALL BRANCH CIRCUIT WIRING, COMMUNICATION/DATA CABLING CONDUIT, PULL

A. ALL WALL AND FLOOR MOUNTED RECEPTACLES, OUTLETS, DEVICES JUNCTION

BUT NO LESS THAN MANUFACTURERS CLEARANCE REQUIREMENTS.

ARE REPRESENTED ON THE DRAWINGS OR NOT.

E. CLEAN OUT EXISTING CELLULAR DECK SYSTEM AND REMOVE ALL CONDUCTORS

ALL MOTOR STARTERS, DISCONNECT SWITCHES, CONTROL DEVICES, ETC. SHALL

COMPLETELY REMOVED BACK TO THE SOURCE OF POWER AND DISCONNECTED.

FOR REMOVAL ON THE HVAC AND PLUMBING DEMOLITION DRAWINGS SHALL BE

ABANDONED CONDUIT AND WIRING SHALL BE REMOVED. THE CONTRACTOR

CORE AREAS SUCH AS THE RESTROOMS, ELECTRICAL/TELEPHONE CLOSETS,

F. ELECTRICAL CONTRACTOR SHALL MAINTAIN CONTINUITY OF CIRCUITRY FOR

ING AND REPLACING ALL COVER PLATES, GASKETS, SCREWS AND RELATED

WORK WHICH INTERFERES WITH THE NEW INSTALLATION. ALL EXPOSED

AND CABLING THAT IS NOT IN USE. CONTRACTOR IS RESPONSIBLE FOR MAINTAIN

SHALL CUT BACK ALL ABANDONED CONDUIT AND WIRING TO FLOOR, OR DEMISING

WALL OF THE SPACE. THIS WORK MAY NOT BE REPRESENTED ON THE DRAWINGS,

BUT SHOULD BE TAKEN INTO ACCOUNT BY THE CONTRACTOR IN HIS PROPOSAL.

MCB)TRANSFORMERS (WHERE HUNG) - AS CLOSE AS POSSIBLE TO SLAB ABOVE

THEREOF. ALL SEISMIC RESTRAINTS SHALL BE DESIGNED AND CONSTRUCTED IN

L. PROVIDE SEISMIC RESTRAINTS FOR ALL EQUIPMENT, INCLUDING ALL STRUCTURAL

FOR THE PROJECT. THIS SHALL INCLUDE STRINGERS, LAMPS, OUTLETS, BREAKERS,

BE REMOVED. REFER TO MECHANICAL AND PLUMBING DRAWINGS FOR ADDITIONAL

EQUIPMENT SUCH AS FANS, AIR CONDITIONING UNITS, PUMPS, ETC. DESIGNATED

CIRCUITRY SHALL BE DISCONNECTED FROM THEIR RESPECTIVE CIRCUIT BREAKERS.

REMOVED BACK TO THEIR SOURCE FROM THEIR RESPECTIVE CIRCUIT BREAKERS

BOXERS IN DEMOLITION AREA SHALL BE COMPLETELY REMOVED WHETHER THEY

D. THE CONTRACTOR SHALL REMOVE AND/OR RELOCATE ANY EXISTING ELECTRICAL

C. ALL POWER AND CONTROL WIRING AND CONDUIT ASSOCIATED WITH MECHANICAL

COMPONENTS. ALL REMOVED AFTERSETS SHALL BE CAPPED WITH COVERPLATES.

EXISTING EQUIPMENT AND DEVICES THAT ARE TO REMAIN. THIS SHALL INCLUDE

STAIRS, ELEVATOR LOBBIES ETC. WHERE OUTLETS ARE REMOVED AND ARE NOT

INTEGRITY OF ORIGINAL CIRCUIT. WHERE A WIRING DEVICE IS TO BE REMOVED

AND THAT WALL IS TO REMAIN THE ELECTRICAL CONTRACTOR SHALL REMOVE

G. CIRCUIT BREAKERS IN ELECTRICAL CLOSETS MADE SPARE DUE TO DEMOLITION

AT THE CIRCUIT DEAD END, EXTEND CIRCUITRY AS REQUIRED TO MAINTAIN

SHALL BE DESIGNATED AS SUCH ON THE PANELBOARD SCHEDULE.

BRANCH CIRCUITRY FROM ITS SOURCE AND FILL-IN OUTLET BOX. BLANK PLATES

ON ACCEPTABLE HANGERS AND INSERTS. CONDUIT OR MC CABLE FOR BRANCH

CIRCUITRY SHALL BE SUPPORTED BY CLAMPS OR PIPE STRAPS SECURED TO THE

G. EXCEPT FOR BRANCH CIRCUITRY INSTALL ALL CONDUIT IN HUNG CEILING SPACE

A. PANELBOARDS: NYC-METROPOLITAN,LINCOLN ELECTRIC, ELECTRO-TECH OR ATLAS,

D. PROVIDE ISOLATED GROUND BUS BAR AND CONDUCTORS WHERE INDICATED ON

THE DECK. SUPPORT FROM CEILING TEES, CROSS TEES OR SUPPORT WIRES IS

C. ALL GROUND WIRES SHALL BE SUITABLY PROTECTED FROM MECHANICAL INJURY.

CEILING SUPPORT SYSTEM (BLACK IRON), FROM STRUCTURAL MEMBERS OR FROM

2 .13 ACCEPTABLE MANUFACTURERS:

OUTSIDE NYC - ITE, WESTINGHOUSE, GE OR SQUARE "D"

2. CIRCUIT BREAKERS: ITE, WESTINGHOUSE, GE OR SQUARE "D

5. WIRE/CABLE: ROME PHELPS DOGGE, GENERAL CABLE, SIMPLEX

4. RACEWAY: NATIONAL WIRE PRODUCTS, TRIANGLE OR REPUBLIC

1. DISCONNECT SWITCHES: ITE, WESTINGHOUSE, GE OR SQUARE "D"

3. FUSES: BUSSMAN, GOULD SHAWMUTT

6. METAL CLAD CABLE: AFC

DRAWINGS.

VERTICAL SURFACE MOUNTING, WHICH IS REQUIRED IN A FREE STANDING

F. INCLUDE SUPPORTING FRAMES OR RACKS FOR EQUIPMENT, INTENDED FOR

B. PROVIDE SUPPLEMENTARY GROUND BONDING WHERE METALLIC CONDUITS

A. PROVIDE A GREEN GROUND CONDUCTOR IN CIRCUIT CONDUITS AS INDICATED.

TERMINATE AT METAL CLAD EQUIPMENT (OR AT THE METAL PULL BOX OF

EQUIPMENT) FOR WHICH A GROUND BUS IS SPECIFIED WITH USHING OF THE

GROUNDING TYPE CONNECTED INDIVIDUALLY TO GROUND BUS.

2 .12 GROUNDING:

PROHIBITED.

POSITION.

WILL NOT BE PERMITTED.

INFORMATION.

3 .02 DEMOLITION

E. INCLUDE SUPPORTING FRAMES OR RACKS EXTENDING FROM SLAB TO SLAB FOR

AT INTERVALS NO GREATER THAN THE STORY HEIGHT, OR 15 T. WHICHEVER IS

D. WHERE THEY ARE NOT EMBEDDED IN CONCRETE, SUPPORT LESS THAN 1" TRADE

NO GREATER THAN 8 FEET. SUPPORT SUCH CONDUITS 2" TRADE SIZE OR LARGER,

C. SUPPORT LESS THAN 2" TRADE SIZE, VERTICALLY RUN CONDUIT AT INTERVALS

SIZE, HORIZONTALLY RUN CONDUITS AT INTERVALS NO GREATER THAN 7 FT.

WORK INDICATED AS BEING SUPPORTED FROM WALLS UNLESS WALLS OF

SUPPORT SUCH CONDUITS, 1" TRADE SIZE OR LARGER, AT INTERVALS NO

CONCRETE BLOCK OR SIMILAR STRUCTURAL CONSTRUCTION.

GREATER THAN 10 FT.

SMALLER.

AND FUSING, AS IS NECESSARY.

seal & signature

dwg title

twig

cadd

checked by

issue date

AS NOTED

drawn by

02/11/2011

project no.

dwg. no.

scale

cad file

t10-12-0230

375 Beach 92nd StreetQueens, NY 11693

SUBMISSIONS

DATE rev no issue

project

project

375 Beach 92nd StreetQueens, NY 11693

architect

231 West 29th Street - Suite 606, New York, NY 10001

Tel: 212 . 967 . TWIG / Fax: 212 . 967 . 8945

[email protected] www.twigcon.com

A Division of The Wall Consulting Group, Inc. All Rights Reserved. 2007- 2010©

375 Beach 92nd Street E-202.00.dwg

NYC dob#

sheetTHESE PLANS ARE APPROVED ONLY FOR THE WORK ON THE

BEING APPROVED OR IN ACCORDANCE WITH APPLICABLE CODES.

APPLICATION SPECIFICATION SHEET. ALL OTHER MATTERS SHOWN

ARE NOT TO BE RELIED UPON OR TO BE CONSIDERED AS EITHER

All Drawings And Written Material Herein Constitute The Original And Unpublished Work Of The Wall Consulting Group, Inc. and/or TWIG Consulting Engineers, P.C., And The Same May Not Be Duplicated, Used, Or Disclosed Without The Written Consent Of The Wall Consulting Group, Inc. and/or TWIG Consulting Engineers, P.C. © 2011.

NYCECC NOTES:

TO THE BEST OF MY KNOWLEDGE, BELIEF AND

PROFESSIONAL JUDGMENT, THESE PLANS AND

SPECIFICATIONS ARE IN COMPLIANCE WITH THE

NEW YORK CITY ENERGY CONSERVATION CODE.

02.14.11 1 FILING & PRICING

GROUND FLOORELECTRICALSPECIFICATIONSSHEET II

3 of 7

Page 4: NORTH - Thai Rock · battery pack recessed wac lighting fixture, adjustable trim: hr-d-417, white housing , hr-8402e1, 35w pendant mounted ex. surface mounted fluorescent lightolier

GROUND FLOOR: ELECTRICAL LIGHTING PLAN

SCALE: 3/16" - 1'-0"

5. ALL WORK WITHIN THE ELECTRICAL CLOSETS REQUIRES

PERMISSION FROM BUILDING MANAGEMENT. ANY WORK WITHIN THE

CLOSET REQUIRES AN ELECTRICAL SHUTDOWN OF ALL POWER IN

THE CLOSET. ALL SHUTDOWNS REQUIRE MINIMUM 48 HOUR NOTICE

TO BUILDING MANAGEMENT AND THEIR APPROVAL BEFORE WORK

6. ANY ELECTRICAL SHUTDOWNS THAT MAY AFFECT OTHER

TENANTS, THE CONTRACTOR MUST NOTIFY BUILDING MANAGEMENT A

MINIMUM OF TWO (2) WEEKS PRIOR TO THE SHUTDOWN IN WRITING.

SHUTDOWNS SHALL BE PERFORMED ONLY AT THE DIRECTION OF

THE OWNER'S REPRESENTATIVE. ALL COSTS ASSOCOCIATED WITH

SHUTDOWNS ARE THE RESPONSIBILITY OF THIS CONTRACTOR.

CAN PROCEED.

2. THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING AND PROVIDING

CIRCUIT WIRING TO SERVE THE INTENDED FUNCTION.

AMONG ALL THREE PHASES.

3. THE CONTRACTOR IS RESPONSIBLE FOR PROPERLY BLANCING LOADS

4. ALL CIRCUIT BREAKER SERVING MECHANICAL LOADS SHALL BE TYPE

THE ACTUAL NUMBER OF CONDUCTORS REQUIRED FOR ALL BRANCH

"HACR".

GENERAL ELECTRICAL NOTES

1. CIRCUIT NUMBERS INDICATED FOR CIRCUITING INTENDED AND CIRCUIT

LOAD CALCULATION. ACTUAL AVALABLE CIRCUIT NUMBERS SHALL

BE VERIFIED IN THE FIELD AFTER DEMOLITION, BY THIS CONTRACTOR.

ELECTRICAL LIGHTING NOTES

MANUFACTURER'S CATALOG CUT SHEETS ACCOMPANYING THIS

DRAWING ARE CONSIDERED PART OF SPECIFICATIONS AND INCLUDE ALL

PHOTOMETRIC INFORMATION WHERE APPLICABLE. ALL CUT SHEETS

SHOULD BE ISSUED WITH SCHEDULE TO REDUCE POSSIBLE NON EQUAL

SUBSTITUTIONS.

LIGHTING EQUIPMENT SUBSTITUTIONS ARE NOT PERMITTED UNLESS

APPROVED BY LIGHTING CONSULTANT / ARCHITECT PRIOR TO BID

SUBMISSION.

ALL LIGHTING EQUIPMENT PRICING TO BE PROVIDED AS LINE ITEMS. ALL

ALTERNATES AND SUBSTITUTIONS MUST INCLUDE DEDUCTS FROM

SPECIFIED EQUIPMENT.

LIGHTING EQUIPMENT TO BE ORDERED BY WRITTEN DESCRIPTION.

CATALOG NUMBERS ARE PROVIDED FOR REFERENCE, U.O.N.

ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR VERIFICATION OF ALL

DIMENSIONS AND LOCATIONS OF LIGHTING EQUIPMENT ON DRAWINGS.

CONTACT LIGHTING CONSULTANT/ARCHITECT IF LIGHTING PLANS CAN

NOT BE IMPLEMENTED AS INDICATED.

THE SPECIFIED LAMP TYPE IS BASED ON ANTICIPATED PERFORMANCE.

BECAUSE FEW SITUATIONS ARE TRULY TYPICAL, THE CONSULTANT MAY

RECOMMEND THAT A LIMITED NUMBER OF LAMPS BE CHANGED TO ALTER

LAMP COLOR, LAMP WATTAGE, OR BEAM DISTRIBUTION. IT IS

RECOMMENDED THAT EXTRA REPLACEMENT STOCKS NOT BE ORDERED

UNTIL AFTER INSTALLATION IS APPROVED. DURING THE FOCUSING

PHASE, THE CONSULTANT MAY RECOMMEND THE ADDITIONAL PURCHASE

OF FILTERS, SPREAD LENS, COLOR GELS, LAMP SLEEVES AND OTHER

ACCESSORIES. THESE DEVISES ARE LOW BUDGET ITEMS AND ARE NOT

INCLUDED IN INITIAL COST ESTIMATES.

1.

2.

3.

4.

5.

6.

VOLTS208/120

PHASE3

WIRE4

BUS225A

MCB70A

MINIMUM

INTERRUPTING

RATING:14KAIC

MOUNTING SURFACE

PER PHASE(VA)

ELECTRICAL PANEL SCHEDULE: P-2B

RELOCATED

ELECTRICAL

PANEL

DS-1

P-1

P-2A/2B

P-3

P-1

seal & signature

dwg title

twig

cadd

checked by

issue date

AS NOTED

drawn by

02/11/2011

project no.

dwg. no.

scale

cad file

t10-12-0230

375 Beach 92nd StreetQueens, NY 11693

SUBMISSIONS

DATE rev no issue

project

project

375 Beach 92nd StreetQueens, NY 11693

architect

231 West 29th Street - Suite 606, New York, NY 10001

Tel: 212 . 967 . TWIG / Fax: 212 . 967 . 8945

[email protected] www.twigcon.com

A Division of The Wall Consulting Group, Inc. All Rights Reserved. 2007- 2010©

375 Beach 92nd Street E-301.00.dwg

NYC dob#

sheetTHESE PLANS ARE APPROVED ONLY FOR THE WORK ON THE

BEING APPROVED OR IN ACCORDANCE WITH APPLICABLE CODES.

APPLICATION SPECIFICATION SHEET. ALL OTHER MATTERS SHOWN

ARE NOT TO BE RELIED UPON OR TO BE CONSIDERED AS EITHER

All Drawings And Written Material Herein Constitute The Original And Unpublished Work Of The Wall Consulting Group, Inc. and/or TWIG Consulting Engineers, P.C., And The Same May Not Be Duplicated, Used, Or Disclosed Without The Written Consent Of The Wall Consulting Group, Inc. and/or TWIG Consulting Engineers, P.C. © 2011.

NYCECC NOTES:

TO THE BEST OF MY KNOWLEDGE, BELIEF AND

PROFESSIONAL JUDGMENT, THESE PLANS AND

SPECIFICATIONS ARE IN COMPLIANCE WITH THE

NEW YORK CITY ENERGY CONSERVATION CODE.

02.14.11 1 FILING & PRICING

GROUND FLOORELECTRICALLIGHTINGPLAN & NOTES

4 of 7

Page 5: NORTH - Thai Rock · battery pack recessed wac lighting fixture, adjustable trim: hr-d-417, white housing , hr-8402e1, 35w pendant mounted ex. surface mounted fluorescent lightolier

GROUND FLOOR: ELECTRICAL POWER PLAN

SCALE: 3/16" - 1'-0"

5. ALL WORK WITHIN THE ELECTRICAL CLOSETS REQUIRES

PERMISSION FROM BUILDING MANAGEMENT. ANY WORK WITHIN THE

CLOSET REQUIRES AN ELECTRICAL SHUTDOWN OF ALL POWER IN

THE CLOSET. ALL SHUTDOWNS REQUIRE MINIMUM 48 HOUR NOTICE

TO BUILDING MANAGEMENT AND THEIR APPROVAL BEFORE WORK

6. ANY ELECTRICAL SHUTDOWNS THAT MAY AFFECT OTHER

TENANTS, THE CONTRACTOR MUST NOTIFY BUILDING MANAGEMENT A

MINIMUM OF TWO (2) WEEKS PRIOR TO THE SHUTDOWN IN WRITING.

SHUTDOWNS SHALL BE PERFORMED ONLY AT THE DIRECTION OF

THE OWNER'S REPRESENTATIVE. ALL COSTS ASSOCOCIATED WITH

SHUTDOWNS ARE THE RESPONSIBILITY OF THIS CONTRACTOR.

CAN PROCEED.

2. THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING AND PROVIDING

CIRCUIT WIRING TO SERVE THE INTENDED FUNCTION.

AMONG ALL THREE PHASES.

3. THE CONTRACTOR IS RESPONSIBLE FOR PROPERLY BALANCING LOADS

4. ALL CIRCUIT BREAKER SERVING MECHANICAL LOADS SHALL BE TYPE

THE ACTUAL NUMBER OF CONDUCTORS REQUIRED FOR ALL BRANCH

"HVACR".

GENERAL ELECTRICAL NOTES

1. CIRCUIT NUMBERS INDICATED FOR CIRCUITING INTENDED AND CIRCUIT

LOAD CALCULATION. ACTUAL AVALABLE CIRCUIT NUMBERS SHALL

BE VERIFIED IN THE FIELD AFTER DEMOLITION, BY THIS CONTRACTOR.

RELOCATED

ELECTRICAL

PANEL

TO REMAIN

(100A) EXIST.

EXTEND AND RECONNECT

EXISTING ELECTRICAL CIRCUIT

TO RELOCATED BOILER

#6

#16

TX-1

2.

1. ELECTRICIAN SHALL PROVIDE CORD & PLUG.

PROVIDE ISOLATED GROUND & COMM CONDUIT.

COORDINATE RECEPTACLE WITH EQUIPMENT

SUPPLIER PRIOR TO INSTALLATION.

3.

REFER TO ARCHITECTURAL DRAWINGS FOR

ALL INFORMATION ON OUTLETS LOCATED IN

MILLWORK AND MOUNTING DETAILS.

4.

5. FED FROM FLOOR BELOW. REFER TO

ARCHITECTURAL DETAILS.

6.

LOCATE CEILING MOUNTED RECEPTACLE ABOVE

STAINLESS STEEL CEILING OF WINE ROOM.

7.

RELOCATE EXISTING POWER AND CONTROL WIRING

SERVING EXISTING FAN. SEE MECHANICAL DRAWINGS

FOR MORE INFORMATION, COORDINATE POWER SHUT

DOWN WITH THE TENANT.

ELECTRICAL POWER NOTES

P-1

DS-1

P-1

DISTRIBUTION

PANEL

P-2A/B

P-3

32-POLE

M

1

M

2

M

3

E

E

E

E

E E EE

E

E

E

E

E

E

#17 #19

#8

VOLTS208/120

PHASE3

WIRE4

BUS225A

MCB100A

MINIMUM

INTERRUPTING

RATING:14KAIC

MOUNTING SURFACE

PER PHASE(VA)

7900

1040

1040

380 77

380 1000

380 500

400 180

1325

1325

1380 1000

1380

380

400

180

3500 360

200

ELECTRICAL PANEL SCHEDULE: P-3

E

E

seal & signature

dwg title

twig

cadd

checked by

issue date

AS NOTED

drawn by

02/11/2011

project no.

dwg. no.

scale

cad file

t10-12-0230

375 Beach 92nd StreetQueens, NY 11693

SUBMISSIONS

DATE rev no issue

project

project

375 Beach 92nd StreetQueens, NY 11693

architect

231 West 29th Street - Suite 606, New York, NY 10001

Tel: 212 . 967 . TWIG / Fax: 212 . 967 . 8945

[email protected] www.twigcon.com

A Division of The Wall Consulting Group, Inc. All Rights Reserved. 2007- 2010©

375 Beach 92nd Street E-302.00.dwg

NYC dob#

sheetTHESE PLANS ARE APPROVED ONLY FOR THE WORK ON THE

BEING APPROVED OR IN ACCORDANCE WITH APPLICABLE CODES.

APPLICATION SPECIFICATION SHEET. ALL OTHER MATTERS SHOWN

ARE NOT TO BE RELIED UPON OR TO BE CONSIDERED AS EITHER

All Drawings And Written Material Herein Constitute The Original And Unpublished Work Of The Wall Consulting Group, Inc. and/or TWIG Consulting Engineers, P.C., And The Same May Not Be Duplicated, Used, Or Disclosed Without The Written Consent Of The Wall Consulting Group, Inc. and/or TWIG Consulting Engineers, P.C. © 2011.

NYCECC NOTES:

TO THE BEST OF MY KNOWLEDGE, BELIEF AND

PROFESSIONAL JUDGMENT, THESE PLANS AND

SPECIFICATIONS ARE IN COMPLIANCE WITH THE

NEW YORK CITY ENERGY CONSERVATION CODE.

02.14.11 1 FILING & PRICING

GROUND FLOORELECTRICALPOWERPLAN & NOTES

5 of 7

Page 6: NORTH - Thai Rock · battery pack recessed wac lighting fixture, adjustable trim: hr-d-417, white housing , hr-8402e1, 35w pendant mounted ex. surface mounted fluorescent lightolier

PANELBOARD IDENTIFICATION DETAIL

DOOR IN DOOR COVER DETAIL

LOCK

CIRCUIT BREAKERS

DOOR TO COVER

NOT TO SCALE

ONLY.

CONTINUOUS PIANO

HINGE

FEED THRU METHOD FOR MULTI-SECTION PANELBOARD

CONDUIT (TOP OR

BOTTOM ENTRANCE)

SEE NOTE #1

CONDUCTOR

(IF REQUIRED)

INCOMING FEEDER CABLES

MAIN CIRCUIT BREAKER

DOUBLE SIZE NEUTRAL

NOT TO SCALE

120/208V, 3PH

CONDUCTORS.

2. NEUTRAL SHALL PASS THROUGH SAME HOLE IN BARRIER AS PHASE

1. INCREASED GUTTERS MAY BE REQUIRED TO SUIT FEEDER CABLES.

NEUTRAL DOUBLE BUS

NOTES:

SECTION I

PANEL

N

SECTION II

PANEL

N

PIANO TYPE HINGE

(TYPICAL)

PH C:RED

PH B:BLUE

PH A:BLACK

UNIT PANEL

SOURCE:DP-7E

PANEL "RP-45E"

INSIDE COVER ABOVE SCHEDULE

IDENTIFICATION. MOUNT ON

CONDUCTOR COLOR CODE

PANEL SOURCE

PANEL SYSTEM

PANEL VOLTAGE & PHASE

PANEL NAME

WALL DEVICE LOCATION ELEVATION

THERMOSTATS AND STROBE ALARMS SHALL ALIGN ABOVE LIGHT SWITCHES.

ELEVATION PER ARCHITECTURAL DOCUMENTS

1.

NOTE:

2.

LIGHT SWITCHES

THERMOSTAT

STROBE ALARM

C

L

C

L

2.1.

3. 4.

NOT TO SCALE

NOT TO SCALE

seal & signature

dwg title

twig

cadd

checked by

issue date

AS NOTED

drawn by

02/11/2011

project no.

dwg. no.

scale

cad file

t10-12-0230

375 Beach 92nd StreetQueens, NY 11693

SUBMISSIONS

DATE rev no issue

project

project

375 Beach 92nd StreetQueens, NY 11693

architect

231 West 29th Street - Suite 606, New York, NY 10001

Tel: 212 . 967 . TWIG / Fax: 212 . 967 . 8945

[email protected] www.twigcon.com

A Division of The Wall Consulting Group, Inc. All Rights Reserved. 2007- 2010©

375 Beach 92nd Street E-401.00.dwg

NYC dob#

sheetTHESE PLANS ARE APPROVED ONLY FOR THE WORK ON THE

BEING APPROVED OR IN ACCORDANCE WITH APPLICABLE CODES.

APPLICATION SPECIFICATION SHEET. ALL OTHER MATTERS SHOWN

ARE NOT TO BE RELIED UPON OR TO BE CONSIDERED AS EITHER

All Drawings And Written Material Herein Constitute The Original And Unpublished Work Of The Wall Consulting Group, Inc. and/or TWIG Consulting Engineers, P.C., And The Same May Not Be Duplicated, Used, Or Disclosed Without The Written Consent Of The Wall Consulting Group, Inc. and/or TWIG Consulting Engineers, P.C. © 2011.

NYCECC NOTES:

TO THE BEST OF MY KNOWLEDGE, BELIEF AND

PROFESSIONAL JUDGMENT, THESE PLANS AND

SPECIFICATIONS ARE IN COMPLIANCE WITH THE

NEW YORK CITY ENERGY CONSERVATION CODE.

02.14.11 1 FILING & PRICING

GROUND FLOORELECTRICALDETAILS

6 of 7

Page 7: NORTH - Thai Rock · battery pack recessed wac lighting fixture, adjustable trim: hr-d-417, white housing , hr-8402e1, 35w pendant mounted ex. surface mounted fluorescent lightolier

P-3

(32-POLE)

P-2A

(16-POLE)

P-2B

(24-POLE)

(100A)

(70A)

(70A)

EXISTING KITCHEN

EXISTING

PANEL (60A)

DS-1

(60A)

P-1

DIST.

PANEL

(42-POLE)

M

M

M

M-3

M-2

M-1

EXISITING

PULL-BOX

EXISTING ELECTRIC CLOSET

BUILDING LINE

(200A)

1ST FLOOR

GROUND FLOOR

1

1

2

" ØC

1

1

4

" ØC

1

1

2

" ØC

1

1

4

" ØC

FROM SERVICE UTILITY

1

1

4

" ØC

1 " ØC

1

1

2

" ØC

ELECTRICAL RISER DIAGRAM

SCALE: NTS

VOLTS208/120

PHASE3

WIRE4

BUS225A

MCB70A

MINIMUM

INTERRUPTING

RATING:14KAIC

MOUNTING SURFACE

PER PHASE(VA)

ELECTRICAL PANEL SCHEDULE: P-2B

ELECTRICAL POWER PANEL SCHEDULE: P-1

VOLTS120/208

PHASE3

WIRE4

BUS125A

MCB100A

MINIMUM

INTERRUPTING

RATING:10KAIC

MOUNTING SURFACE

PER PHASE(VA)

VOLTS208/120

PHASE3

WIRE4

BUS225A

MCB100A

MINIMUM

INTERRUPTING

RATING:14KAIC

MOUNTING SURFACE

PER PHASE(VA)

7900

1040

1040

380 77

380 1000

380 500

400 180

1325

1325

1380 1000

1380

380

400

180

3500 360

200

ELECTRICAL PANEL SCHEDULE: P-3

seal & signature

dwg title

twig

cadd

checked by

issue date

AS NOTED

drawn by

02/11/2011

project no.

dwg. no.

scale

cad file

t10-12-0230

375 Beach 92nd StreetQueens, NY 11693

SUBMISSIONS

DATE rev no issue

project

project

375 Beach 92nd StreetQueens, NY 11693

architect

231 West 29th Street - Suite 606, New York, NY 10001

Tel: 212 . 967 . TWIG / Fax: 212 . 967 . 8945

[email protected] www.twigcon.com

A Division of The Wall Consulting Group, Inc. All Rights Reserved. 2007- 2010©

375 Beach 92nd Street E-601.00.dwg

NYC dob#

sheetTHESE PLANS ARE APPROVED ONLY FOR THE WORK ON THE

BEING APPROVED OR IN ACCORDANCE WITH APPLICABLE CODES.

APPLICATION SPECIFICATION SHEET. ALL OTHER MATTERS SHOWN

ARE NOT TO BE RELIED UPON OR TO BE CONSIDERED AS EITHER

All Drawings And Written Material Herein Constitute The Original And Unpublished Work Of The Wall Consulting Group, Inc. and/or TWIG Consulting Engineers, P.C., And The Same May Not Be Duplicated, Used, Or Disclosed Without The Written Consent Of The Wall Consulting Group, Inc. and/or TWIG Consulting Engineers, P.C. © 2011.

NYCECC NOTES:

TO THE BEST OF MY KNOWLEDGE, BELIEF AND

PROFESSIONAL JUDGMENT, THESE PLANS AND

SPECIFICATIONS ARE IN COMPLIANCE WITH THE

NEW YORK CITY ENERGY CONSERVATION CODE.

02.14.11 1 FILING & PRICING

GROUND FLOORELECTRICALRISER DIAGRAM

7 of 7