PG&E-owned Photovoltaic Sites Information Appendix E2 2014 ES RFO Site Nominal Voltage At Connection Point (See note 1 below) Guaranteed Dmax (MW) at Year 1- 10 (See note 2 below) Guaranteed Discharge Duration (hours) Guaranteed Site Specific Required Duty Cycle Gates 17115 W. Gale Ave Huron, CA 93234 12.47kVAC 4MW 4 1 full discharge and charge per day, for 365 days per year for minimum of 10 years Huron (see note 3) Corner of West Gale Avenue and South Lassen Ave (Hwy 269), Huron, CA 93234 12.47kVAC 4MW 4 1 full discharge and charge per day, for 365 days per year for minimum of 10 years Stroud W. Kamm Ave west of S. Lassen Ave (Hwy 145), Helm, CA 93627 12.47kVAC 4MW 4 1 full discharge and charge per day, for 365 days per year for minimum of 10 years Notes: 1. The voltages listed are nominal only. A. The equipment connected to the 12.47kVAC bus shall be at least 15kV class equipment, typical voltage range is from 0VAC to 13.8kVAC. 2. These values are minimum total output power for the Energy Storage Systems (ESS) at each site. Dmax of 4 MW is the minimum output for duration of 4 hours. This system should a modular system made up of smaller units (say 500kW or 1 MW) in parallel to give the total of 4 MW. 3. Huron is on the west side of South Lassen Ave (Hwy 269) on West Gale Ave. Date: 1-28-15

Upload: others

Post on 19-Mar-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: No minal Voltage At Guaranteed Dmax (MW) Guaranteed … · 2017-03-24 · output (dmax) is 4mw minimum for 4 hours 2. items within the clouded areas are new scope of work. 12.47kv

PG&E-owned Photovoltaic Sites Information Appendix E2 2014 ES RFO

Site

Nominal Voltage At Connection Point (See

note 1 below)

Guaranteed Dmax (MW)

at Year 1- 10 (See note 2 below)

Guaranteed Discharge Duration (hours)

Guaranteed Site Specific Required Duty Cycle

Gates 17115 W. Gale Ave Huron, CA 93234

12.47kVAC

4MW

4

1 full discharge and charge per day, for 365 days per year for minimum of 10 years

Huron (see note 3) Corner of West Gale Avenue and South Lassen Ave (Hwy 269), Huron, CA 93234

12.47kVAC

4MW

4

1 full discharge and charge per day, for 365 days per year for minimum of 10 years

Stroud W. Kamm Ave west of S. Lassen Ave (Hwy 145), Helm, CA 93627

12.47kVAC

4MW

4

1 full discharge and charge per day,

for 365 days per year for minimum of 10 years

Notes: 1. The voltages listed are nominal only.

A. The equipment connected to the 12.47kVAC bus shall be at least 15kV class equipment, typical voltage range is from 0VAC to 13.8kVAC. 2. These values are minimum total output power for the Energy Storage Systems (ESS) at each site. Dmax of 4 MW is the minimum output for duration of 4 hours. This system should a modular system made up of smaller units (say 500kW or 1 MW) in parallel to give the total of 4 MW. 3. Huron is on the west side of South Lassen Ave (Hwy 269) on West Gale Ave.

Date: 1-28-15

Page 2: No minal Voltage At Guaranteed Dmax (MW) Guaranteed … · 2017-03-24 · output (dmax) is 4mw minimum for 4 hours 2. items within the clouded areas are new scope of work. 12.47kv

AT HURON AND GUERNSEY1 of 10 EXISTING STEP-UP TRANSFORMERS

12,470VAC-420VAC SIZE IS 2MVA ONAN.

01-01 COMBINER

BOX

EXISTING PV PANEL STRINGS

APPROXIMATE PEAK STRING VOLTAGE AT

HURON IS 730VDCGUERNSEY IS

718VDC

EXISTING MAIN 12.47KV NOMINAL VOLTAGE SWITCHGEAR

DC

AC

01-13 COMBINER

BOX

EXISTING PV PANEL STRINGS

APPROXIMATE PEAK STRING VOLTAGE AT

HURON IS 730VDCGUERNSEY IS

718VDC

EXISTING THERE ARE FROM 6 TO

13 COMBINER BOXES PER INVERTER

EXISTING INVERTERS ARE ADVANCE ENERGY (AE) PV INVERTERS

RATING: OUTPUT POWER 500KWNOMINAL VOLTAGE OUTPUT 420VAC

OUTPUT VOLTAGE RANGE 378VAC TO 462VACRATED DC INPUT VOLTAGE IS 1000VDC

DC VOLTAGE INPUT OPERATIONAL RANGE (MPPT WINDOW) IS 600VDC TO 850VDC

WITH TURN ON AT 700VDC MAXIMUM INPUT CURRENT 850 AMPS DC

01-01 INVERTER

1 of 40 TOTAL

DC

AC

01-02 INVERTEREXISTING

2 of 40 TOTAL

THIS INVERTER CIRCUIT IS THE

SAME AS INVERTER

01-01

DC

AC

01-03 INVERTEREXISTING

3 of 40 TOTAL

THIS INVERTER CIRCUIT IS THE

SAME AS INVERTER

01-01

DC

AC

01-04 INVERTEREXISTING

4 of 40 TOTAL

THIS INVERTER CIRCUIT IS THE

SAME AS INVERTER

01-01

EXISTING EQUIPMENT

POSSIBLE CONNECTION POINT FOR ESS

EXHIBIT F ATTACHMENT 3 ENERGY STORAGE SYSTEM (ESS) PROJECTS

AT HURON 20MW PV SITES

(1 OF 10) 480VAC BUS.BUS VOLTAGE RANGE IS 378VAC TO 462VAC

WITH A NOMINAL VOLTAGE OF 420VAC

2-4-15 REV. ASheet 1 of 3

NOTES:1. THE ENERGY STORAGE SYSTEM (ESS) SYSTEM TOTAL POWER OUTPUT (Dmax) IS 4MW MINIMUM FOR 4 HOURS

2. ITEMS WITHIN THE CLOUDED AREAS ARE NEW SCOPE OF WORK.

12.47KV SWITCHGEAR TO ADD THE ENERGY

STORAGE SYSTEM (ESS)

POSSIBLE CONNECTION POINT FOR ENERGY STORAGE SYSTEM ON 12.47KV BUS

THE DESIGN SHOWN HERE IS CONCEPTUAL ONLY.BIDDER WILL ENGINEER THE ENERGY STORAGE SYSTEM.

MINIMUM GUARANTEED POWER OUTPUT (DMAX) IS 4 MW.

Page 3: No minal Voltage At Guaranteed Dmax (MW) Guaranteed … · 2017-03-24 · output (dmax) is 4mw minimum for 4 hours 2. items within the clouded areas are new scope of work. 12.47kv

AT STROUD 1 OF 20 EXISTING STEP-UP TRANSFORMERS

12,470VAC-420VAC SIZE IS 1MVA ONAN.

01-01 COMBINER

BOX

EXISTING PV PANEL STRINGS

APPROXIMATE PEAK STRING VOLTAGE AT

STROUD IS 704VDC

EXISTING MAIN 12.47KV NOMINAL VOLTAGE SWITCHGEAR

DC

AC

01-10 COMBINER

BOX

EXISTING PV PANEL STRINGS

APPROXIMATE PEAK STRING VOLTAGE AT

STROUD IS 704VDC

EXISTING THERE ARE

10 COMBINER BOXES PER INVERTER

01-01 INVERTER

1 OF 40 TOTAL

DC

AC

01-02 INVERTER

2 OF 40TOTAL

THIS INVERTER CIRCUIT IS THE

SAME AS INVERTER

01-01

(1 OF 20) 480VAC BUS .BUS VOLTAGE RANGE IS 378VAC TO 462VAC

WITH A NOMINAL VOLTAGE OF 420VAC

EXHIBIT F ATTACHMENT 3 ENERGY STORAGE SYSTEM (ESS) PROJECTS

AT STROUD 20MW PV SITEEXISTING EQUIPMENT

POSSIBLE CONNECTION POINT FOR ESS

EXISTING INVERTERS ARE ADVANCE ENERGY (AE) PV INVERTERS

RATING: OUTPUT POWER 500KWNOMINAL VOLTAGE OUTPUT 420VAC

OUTPUT VOLTAGE RANGE 378VAC TO 462VACRATED DC INPUT VOLTAGE IS 1000VDC

DC VOLTAGE INPUT OPERATIONAL RANGE (MPPT WINDOW) IS 600VDC TO 850VDC

WITH TURN ON AT 700VDC MAXIMUM INPUT CURRENT 850 AMPS DC

02-04-15 REV. ASheet 2 of 3

NOTES:1. THE ENERGY STORAGE SYSTEM (ESS) SYSTEM TOTAL POWER OUTPUT (Dmax) IS 4MW MINIMUM FOR 4 HOURS

2. ITEMS WITHIN THE CLOUDED AREAS ARE NEW SCOPE OF WORK.

12.47KV SWITCHGEAR TO ADD THE ENERGY

STORAGE SYSTEM (ESS)

POSSIBLE CONNECTION POINT FOR ENERGY STORAGE SYSTEM ON 12.47KV BUS

THE DESIGN SHOWN HERE IS CONCEPTUAL ONLY.BIDDER WILL ENGINEER THE ENERGY STORAGE SYSTEM.

MINIMUM GUARANTEED POWER OUTPUT (DMAX) IS 4 MW.

Page 4: No minal Voltage At Guaranteed Dmax (MW) Guaranteed … · 2017-03-24 · output (dmax) is 4mw minimum for 4 hours 2. items within the clouded areas are new scope of work. 12.47kv

AT GATES 1 OF 28 EXISTING STEP-UP TRANSFORMERS

12,000VAC-324VAC SIZE IS 750/840kVA ONAN.

01-01 COMBINER

BOX

EXISTING PV PANEL STRINGS

APPROXIMATE PEAK STRING VOLTAGE AT IS 722VDC

EXISTING MAIN 12.47KV NOMINAL VOLTAGE SWITCHGEAR

DC

AC

01-10 COMBINER

BOX

EXISTING PV PANEL STRINGS

APPROXIMATE PEAK STRING VOLTAGE AT

STROUD IS 722VDC

EXISTING THERE ARE

14 COMBINER BOXES PER INVERTER

01-01 INVERTER

1 OF 28 TOTAL

(1 OF 28) 324VAC BUS .BUS VOLTAGE RANGE IS 292VAC TO 356VAC

WITH A NOMINAL VOLTAGE OF 324VAC

EXHIBIT F ATTACHMENT 3 ENERGY STORAGE SYSTEM (ESS) PROJECTS

AT GATES 20MW PV SITEEXISTING EQUIPMENT

POSSIBLE CONNECTION POINT FOR ESS

EXISTING INVERTERS ARE SMA PV INVERTERS

RATING: OUTPUT POWER 720KWNOMINAL VOLTAGE OUTPUT 324VAC

OUTPUT VOLTAGE RANGE 292VAC TO 356VACRATED DC INPUT VOLTAGE IS 1000VDC

DC VOLTAGE INPUT OPERATIONAL RANGE (MPPT WINDOW) IS 525VDC TO 820VDC

MAXIMUM INPUT CURRENT 1600 AMPS DC

02-04-15 REV. ASheet 3 of 3

NOTES:1. THE ENERGY STORAGE SYSTEM (ESS) SYSTEM TOTAL POWER OUTPUT (Dmax) IS 4MW MINIMUM FOR 4 HOURS

2. ITEMS WITHIN THE CLOUDED AREAS ARE NEW SCOPE OF WORK.

12.47KV SWITCHGEAR TO ADD THE ENERGY

STORAGE SYSTEM (ESS)

POSSIBLE CONNECTION POINT FOR ENERGY STORAGE SYSTEM ON 12.47KV BUS

THE DESIGN SHOWN HERE IS CONCEPTUAL ONLY.BIDDER WILL ENGINEER THE ENERGY STORAGE SYSTEM.

MINIMUM GUARANTEED POWER OUTPUT (DMAX) IS 4 MW.

Page 5: No minal Voltage At Guaranteed Dmax (MW) Guaranteed … · 2017-03-24 · output (dmax) is 4mw minimum for 4 hours 2. items within the clouded areas are new scope of work. 12.47kv

Gates

Alice
Stamp
Page 6: No minal Voltage At Guaranteed Dmax (MW) Guaranteed … · 2017-03-24 · output (dmax) is 4mw minimum for 4 hours 2. items within the clouded areas are new scope of work. 12.47kv
Page 7: No minal Voltage At Guaranteed Dmax (MW) Guaranteed … · 2017-03-24 · output (dmax) is 4mw minimum for 4 hours 2. items within the clouded areas are new scope of work. 12.47kv

Stroud