night covers on open vertical cases
DESCRIPTION
Night Covers on Open Vertical Cases. Provisional UES Proposal Presentation to the Regional Technical Forum August 30, 2011. Thanks to All Participants. Measure Summary. Retrofitting night covers to existing medium temperature open multi-deck cases - PowerPoint PPT PresentationTRANSCRIPT
![Page 1: Night Covers on Open Vertical Cases](https://reader036.vdocuments.us/reader036/viewer/2022081604/56816752550346895ddc024e/html5/thumbnails/1.jpg)
Night Covers on Open Vertical Cases
Provisional UES Proposal Presentation to the Regional Technical Forum
August 30, 2011
1
![Page 2: Night Covers on Open Vertical Cases](https://reader036.vdocuments.us/reader036/viewer/2022081604/56816752550346895ddc024e/html5/thumbnails/2.jpg)
Thanks to All Participants
2
![Page 3: Night Covers on Open Vertical Cases](https://reader036.vdocuments.us/reader036/viewer/2022081604/56816752550346895ddc024e/html5/thumbnails/3.jpg)
Measure Summary
• Retrofitting night covers to existing medium temperature open multi-deck cases
• Provisional savings estimate 44 kWh/lin ft and 5 therms/lin ft
• Based on a calibrated DOE2.2r simulation
• Requesting Provisional UES Status
3
![Page 4: Night Covers on Open Vertical Cases](https://reader036.vdocuments.us/reader036/viewer/2022081604/56816752550346895ddc024e/html5/thumbnails/4.jpg)
4
Measure History• Night Covers (first version):
– Previously RTF-approved: March 2, 2009– Includes separate savings values for applying night
covers to vertical and horizontal refrigerated display cases
– Calculation methodology: uncalibrated engineering calculations
• Vertical Night Covers– Updated UES to replace existing value, which is out-of-
compliance
![Page 5: Night Covers on Open Vertical Cases](https://reader036.vdocuments.us/reader036/viewer/2022081604/56816752550346895ddc024e/html5/thumbnails/5.jpg)
5
UES Analysis Summary
![Page 6: Night Covers on Open Vertical Cases](https://reader036.vdocuments.us/reader036/viewer/2022081604/56816752550346895ddc024e/html5/thumbnails/6.jpg)
Appendix A: Provisional UES Checklist
6
![Page 7: Night Covers on Open Vertical Cases](https://reader036.vdocuments.us/reader036/viewer/2022081604/56816752550346895ddc024e/html5/thumbnails/7.jpg)
7
Appendix B: UES Measure Summary
![Page 8: Night Covers on Open Vertical Cases](https://reader036.vdocuments.us/reader036/viewer/2022081604/56816752550346895ddc024e/html5/thumbnails/8.jpg)
8
![Page 9: Night Covers on Open Vertical Cases](https://reader036.vdocuments.us/reader036/viewer/2022081604/56816752550346895ddc024e/html5/thumbnails/9.jpg)
9
![Page 10: Night Covers on Open Vertical Cases](https://reader036.vdocuments.us/reader036/viewer/2022081604/56816752550346895ddc024e/html5/thumbnails/10.jpg)
10
![Page 11: Night Covers on Open Vertical Cases](https://reader036.vdocuments.us/reader036/viewer/2022081604/56816752550346895ddc024e/html5/thumbnails/11.jpg)
11
![Page 12: Night Covers on Open Vertical Cases](https://reader036.vdocuments.us/reader036/viewer/2022081604/56816752550346895ddc024e/html5/thumbnails/12.jpg)
Implementation and Product Standards
12
• No night cover may be present in baseline
• Minimum 1 year manufacturer’s warranty
• Minimum application of 6 hours/ 24 hour period
![Page 13: Night Covers on Open Vertical Cases](https://reader036.vdocuments.us/reader036/viewer/2022081604/56816752550346895ddc024e/html5/thumbnails/13.jpg)
Estimation Procedure
13
• Modeled using DOE 2.2R to capture interactive effects
• “Typical” store was built using GrocerSmart Audit Data
• Multiplex Baseline assumes Floating Head Pressure, T8 lamps, and EC motors are in place.
• Stand-alone system baseline assumes T8 lamps and EC motors.
• Infiltration, conduction, and radiation load based on manufacturer data, the ASHRAE Refrigeration Handbook, and SCE lab test report
![Page 14: Night Covers on Open Vertical Cases](https://reader036.vdocuments.us/reader036/viewer/2022081604/56816752550346895ddc024e/html5/thumbnails/14.jpg)
Model Calibration: Whole Building
14
![Page 15: Night Covers on Open Vertical Cases](https://reader036.vdocuments.us/reader036/viewer/2022081604/56816752550346895ddc024e/html5/thumbnails/15.jpg)
Model Calibration:Compressor Energy Use
15
![Page 16: Night Covers on Open Vertical Cases](https://reader036.vdocuments.us/reader036/viewer/2022081604/56816752550346895ddc024e/html5/thumbnails/16.jpg)
Model Calibration- Baseline:Case Refrigeration Load
16
Total case load based on ANSI/ASHRAE 72 testing = 1600 btu/hr-ft
ASHRAE data used to disaggregate load components
![Page 17: Night Covers on Open Vertical Cases](https://reader036.vdocuments.us/reader036/viewer/2022081604/56816752550346895ddc024e/html5/thumbnails/17.jpg)
Model Calibration- Efficient Case: Case Refrigeration Load
17
![Page 18: Night Covers on Open Vertical Cases](https://reader036.vdocuments.us/reader036/viewer/2022081604/56816752550346895ddc024e/html5/thumbnails/18.jpg)
18
Cost Estimates
• Cost estimate: $36/ft
• Unchanged from previously accepted cost value
• Supported by invoice levels observed by program
![Page 19: Night Covers on Open Vertical Cases](https://reader036.vdocuments.us/reader036/viewer/2022081604/56816752550346895ddc024e/html5/thumbnails/19.jpg)
19
Measure Effective Useful Life
• EUL: 5 years
• Unchanged from previously accepted EUL
• Supported by 1 year warranty requirement
![Page 20: Night Covers on Open Vertical Cases](https://reader036.vdocuments.us/reader036/viewer/2022081604/56816752550346895ddc024e/html5/thumbnails/20.jpg)
20
Reliable Efficient Case Data
![Page 21: Night Covers on Open Vertical Cases](https://reader036.vdocuments.us/reader036/viewer/2022081604/56816752550346895ddc024e/html5/thumbnails/21.jpg)
Calibration Plan• Collect Metered Data
– Rack: Volts, Amps, PF– Condenser: Volts, Amps, PF– Hourly Natural Gas via Utility Interval Meter– Hourly Outside Air Temperature
• Minimum 3 weeks baseline • Minimum 3-weeks post
– This is a direct load measure. We expect less seasonal interaction than system measures like floating head pressure.
21
![Page 22: Night Covers on Open Vertical Cases](https://reader036.vdocuments.us/reader036/viewer/2022081604/56816752550346895ddc024e/html5/thumbnails/22.jpg)
Calibration Plan• Develop regressions for daily or hourly
refrigeration use correlated to ambient temperature
• Annualize using TMY data– Pre, Post and Savings (Pre minus Post)
22
![Page 23: Night Covers on Open Vertical Cases](https://reader036.vdocuments.us/reader036/viewer/2022081604/56816752550346895ddc024e/html5/thumbnails/23.jpg)
Calibration Plan
• Collect DOE2.2r inputs per data collection specifications• Use inputs to run DOE2.2r for Baseline & Post estimates
of total refrigeration energy• Compare estimates of Baseline, Post & Savings
estimates of refrigeration energy to best-practice estimates
• Modify DOE2.2r models and iterate tests until both baseline energy use, post energy use and energy savings at all sites are reasonable and there is no significant bias.
23
![Page 24: Night Covers on Open Vertical Cases](https://reader036.vdocuments.us/reader036/viewer/2022081604/56816752550346895ddc024e/html5/thumbnails/24.jpg)
Proposed Provisional UES Value
Measure
Site Savings (kWh)
Site Savings (therms)
Measure Life
(years)
Capital Cost
($/unit)
TRC B/C
RatioNight Covers- Retrofit to Open Vertical Case on Multiplex - Seattle, WA 42.0 5.5 5 $36 1.5Night Covers- Retrofit to Open Vertical Case on Stand-alone - Seattle, WA 44.7 5.5 5 $36 1.6Night Covers- Retrofit to Open Vertical Case on Multiplex - Spokane, WA 41.6 5.2 5 $36 1.5Night Covers- Retrofit to Open Vertical Case on Stand-alone - Spokane, WA 44.0 5.2 5 $36 1.5Night Covers- Retrofit to Open Vertical Case on Multiplex - Billings, MT 45.7 4.9 5 $36 1.5Night Covers- Retrofit to Open Vertical Case on Stand-alone - Billings, MT 47.8 4.9 5 $36 1.6
Night Covers- Retrofit to Open Vertical Case - Average 44.3 5.2 5 $36 1.6
![Page 25: Night Covers on Open Vertical Cases](https://reader036.vdocuments.us/reader036/viewer/2022081604/56816752550346895ddc024e/html5/thumbnails/25.jpg)
RTF Proposed Motion:
“I _________ move that the RTF approve the UES for Night covers on Open Vertical Refrigerated Display Cases under provisional status with a sunset date of August 31st, 2013.