Shown not to scale D C B A DESCRIPTION The nVent RAYCHEM NGC-40-BRIDGE module provides the interface between a panel's internal CAN-based network and upstream devices. Multiple communications ports are supported, allowing serial and Ethernet connections to be used with external devices. TOOLS REQUIRED • Small flat-blade screwdriver ADDITIONAL MATERIALS REQUIRED • Power supply 24 Vdc @150 mA per NGC-40-BRIDGE • Custom built CAN cables with RJ-45 connections KIT CONTENTS Item Qty Description A 1 NGC-40-BRIDGE module B 2 CAN bus termination block PTM# 10392-043 C 2 RS-485 termination resistors 120 Ω – 1% - 1/4 watt D 1 NGC-40-BRIDGE serial cable TTC# 10332-005 This component is an electrical device that must be installed correctly to ensure proper operation and to prevent shock or fire. For technical support, call nVent at (800) 545-6258. WARNING: APPROVALS Class I, Div. 2, Groups A,B,C,D T4 Class I, Zone 2, AEx nC IIC T4 IP20 Ex nL IIC T4 X –40˚C ≤ Ta ≤ +65˚C Conforms to: FM Class Number 3600 (11/98) FM Class Number 3611 (10/99) ANSI/UL STD. 60079-15-2009 UL STD. 61010-1 Hazardous Locations Certified to: CAN/CSA STD. C22.2 No. 213-M1987 (R2004) CAN/CSA STD. C22.2 No. 61010-1:2004 EN 61010-1 (2001) CAN/CSA STD. E60079-15:02 (R2006) (Russia, Kazakhstan, Belarus) For other countries contact your local nVent representative. NGC-40-BRIDGE Control and Monitoring Modules for use with the nVent RAYCHEM NGC-40 System Installation Instructions IECEx Marking: IECEx ETL 17.0062X Ex ec IIC T4 Gc ATEX Markings: ITS17ATEX402833X II 3 G Ex ec IIC T4 Gc Special conditions of use: The overall equipment is evaluated to type of protection "ec" For full connection details see these installation instructions The equipment shall only be used in an area of not more than pollution degree 2, as defined in IEC/EN 60664-1 The equipment shall be installed an enclosure that provides a minimum ingress protection of IP54 in accordance with IEC/EN 60079-0 Transient protection shall be provided that is set at a level not exceeding 140% of the peak rated voltage value at the supply terminals to the equipment 4008 717 nVent.com | 1

Upload: others

Post on 14-Oct-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: NGC-40-BRIDGE - nVent · 2020. 3. 10. · E60079-15:02 (R2006) (Russia, Kazakhstan, Belarus) For other countries contact your local nVent representative. NGC-40-BRIDGE ... A slide

Shownnot to scale

D

C

B

A

DESCRIPTIONThe nVent RAYCHEM NGC-40-BRIDGE module provides the interface between a panel's internal CAN-based network and upstream devices. Multiple communications ports are supported, allowing serial and Ethernet connections to be used with external devices.

TOOLS REQUIRED• Small flat-blade screwdriver

ADDITIONAL MATERIALS REQUIRED• Power supply 24 Vdc @150 mA per NGC-40-BRIDGE• Custom built CAN cables with RJ-45 connections

KIT CONTENTS

Item Qty Description

A 1 NGC-40-BRIDGE moduleB 2 CAN bus termination block PTM# 10392-043C 2 RS-485 termination resistors 120 Ω – 1% - 1/4 wattD 1 NGC-40-BRIDGE serial cable TTC# 10332-005

This component is an electrical device that must be installed correctly to ensure proper operation and to prevent shock or fire. For technical support, call nVent at (800) 545-6258.

WARNING:

APPROVALS

Class I, Div. 2, Groups A,B,C,D T4Class I, Zone 2, AEx nC IIC T4 IP20Ex nL IIC T4 X–40˚C ≤ Ta ≤ +65˚C

Conforms to: FM Class Number 3600 (11/98)FM Class Number 3611 (10/99)ANSI/UL STD. 60079-15-2009UL STD. 61010-1

Hazardous Locations

Certified to:CAN/CSA STD. C22.2 No. 213-M1987 (R2004)CAN/CSA STD. C22.2 No. 61010-1:2004EN 61010-1 (2001)CAN/CSA STD. E60079-15:02 (R2006)

(Russia, Kazakhstan, Belarus) For other countries contact your local nVent representative.

NGC-40-BRIDGEControl and Monitoring Modules for use with the nVent RAYCHEM NGC-40 System Installation Instructions

IECEx Marking:IECEx ETL 17.0062XEx ec IIC T4 Gc

ATEX Markings:ITS17ATEX402833X

II 3 G Ex ec IIC T4 Gc

Special conditions of use:• The overall equipment is evaluated to type of protection "ec"• For full connection details see these installation instructions• The equipment shall only be used in an area of not more than

pollution degree 2, as defined in IEC/EN 60664-1• The equipment shall be installed an enclosure that provides a

minimum ingress protection of IP54 in accordance with IEC/EN 60079-0

• Transient protection shall be provided that is set at a level not exceeding 140% of the peak rated voltage value at the supply terminals to the equipment

4008 717

nVent.com | 1

Page 2: NGC-40-BRIDGE - nVent · 2020. 3. 10. · E60079-15:02 (R2006) (Russia, Kazakhstan, Belarus) For other countries contact your local nVent representative. NGC-40-BRIDGE ... A slide

2 | nVent.com

GENERALSupply voltage 24 Vdc ± 10%Internal power consumption < 3.6 W per NGC-40-BRIDGEAmbient operating temperature –40ºC to 65ºC (–40ºF to 149ºF)Ambient storage temperature –40ºC to 75ºC (–40ºF to 167ºF)Environment PD2, CAT IIIMax. altitude 2,000 m (6,562 ft)Humidity 5 – 90% noncondensingMounting Din Rail – 35 mm

ELECTROMAGNETIC COMPATIBILITYEmissions EN 61000-6-3   Emission standard for residential, commercial and light industrial environmentsImmunity EN 61000-6-2   Immunity standard for industrial environments

COMMUNICATIONS COM1, COM2Type 2-wire RS-485Cable One shielded twisted pairLength 1,200 m (4,000 ft) maximumQuantity Up to 255 devices per portData rate 9600, 19.2K, 38.4K, 57.6K, 115.2K baudData bits 7 or 8Parity None, even, oddStop bits 0, 1, 2Tx delay 0 – 5 sec.Protocol Modbus RTU or ASCIIConnection terminals Wago cage clamp terminals

COMMUNICATIONS COM3Type RS-232Cable Custom TTC# 10332-005Length 15 m (50 ft) maximumData rate 9600, 19.2K, 38.4K, 57.6K, 115.2K baudData bits 7 or 8Parity None, even, oddStop bits 0, 1, 2Tx delay 0 – 5 sec.Protocol Modbus RTU or ASCIIConnection terminals RJ-11

CAN NETWORKING PORTType 2-wire isolated CAN-based peer-peer network. Isolated to 300 V.Connection Two 8-pin RJ-45 connectors (both may be used for Input or Output connections)Protocol Proprietary NGC-40Topology Daisy chainLength 10 m (33 ft) maximumQuantity Up to 80 CAN nodes per network segmentAddress Unique, factory assigned

ETHERNETType 10/100 BaseT Ethernet networkLength 100 m (328 ft)Data rates 10 or 100 MB/sProtocol Modbus/TCPConnection terminals Shielded 8-pin RJ-45 connector on front of module

PROGRAMMING AND SETTINGLED indicatorsAlarm conditions RESET, Configuration lost, CAN communications failConfiguration switch SET/RUN slide switch on front of module

CONNECTION TERMINALSWiring terminals Cage clamp, 0.5 to 2.5 mm² (24 to 12 AWG)CAN networking and module power Two RJ-45s, one each IN and OUT. Provides CAN bus signals and +24 Vdc power.

HOUSINGSize 45.1 mm (1.78 in) wide x 87 mm (3.43 in) high x 106.4 mm (4.2 in) deep

Page 3: NGC-40-BRIDGE - nVent · 2020. 3. 10. · E60079-15:02 (R2006) (Russia, Kazakhstan, Belarus) For other countries contact your local nVent representative. NGC-40-BRIDGE ... A slide

nVent.com | 3

Front Top Bottom Back

RESET

NGC-40 BRIDGE MODULE

45.1 mm (1.78 in)

45.1 mm (1.78 in) 45.1 mm (1.78 in)

45.1 mm (1.78 in)

87 m

m (3

.43

in)

87 m

m (3

.43

in)

106.

4 m

m (4

.2 in

)

A. Wiring Terminals

Terminals Function1 COM 1 (485) + in2 COM 1 (485) + out3 COM 2 (485) + in4 COM 2 (485) + out5 COM 1 (485) – in6 COM 1 (485) – out7 COM 2 (485) – in8 COM 2 (485) – out9 – 12 Not used

B. Status LEDs

Status: Indicates status of the moduleOff No powerGreen OK/NormalYellow (flashing) Configuration modeRed (flashing) Internal fault

Network: Indicates CAN network activityOff No link detectedGreen Link OK, receive data packetsYellow Transmit data packetsRed (flashing) Network error

COM: Indicates COM1 & 2 (RS-485) activityOff No activityGreen (flashing) Receipt of data packetYellow (flashing) Transmit of data packet

C. Communication Slide Switch

D. RS-232 Port

Status: Indicates status of RS-232 portTop LED

Off No activityGreen (flashing) Receipt of data packet

Bottom LEDOff No activityYellow (flashing) Transmit of data packet

E. Ethernet Port

Status: Indicates status of the LANTop LED

Off No LAN detectedGreen ON, LAN detected

Bottom LEDOff No LAN activityYellow (flashing) LAN activity (data packet)

F. CAN Bus/Module Power

G. Reset Button

System Components

Page 4: NGC-40-BRIDGE - nVent · 2020. 3. 10. · E60079-15:02 (R2006) (Russia, Kazakhstan, Belarus) For other countries contact your local nVent representative. NGC-40-BRIDGE ... A slide

4 | nVent.com

COM 1 OutCOM 1 Out

22 66 1010

++ ––

RESET

NGC-40 BRIDGE MODULE

COM 2 OutCOM 2 Out

44 88 1212

++ ––

120 ohm termination

resistor

120 ohm termination

resistor

Fieldterminal

block

Fieldterminal

block

120 ohm termination

resistor

120 ohm termination

resistor

COM 1 InCOM 1 In

11 55 99

++ ––

RESET

NGC-40 BRIDGE MODULE

To upstreamdevice

To upstreamdevice

Fieldterminal

block

Fieldterminal

block

COM 2 InCOM 2 In

33 77 1111

++ ––

++ –– ++ ––

To upstreamdevice

To upstreamdevice

Wiring for Com 1 & Com 2 must be terminated on a panel mounted terminal block. No ground wires should be terminated on terminals 9 & 11. Terminate Com shields at the panel mounted field terminal block chassis ground.

Wiring for Com 1 & Com 2 must be terminated on a panel mounted terminal block. No ground wires should be terminated on terminals 10 & 12. Terminate Com shields and 120 Ω termination resistors (included) at the panel mounted field terminal block as shown.

1

2

1

2

Each NGC-40-BRIDGE mounts on a DIN 35 rail. MOUNTING: Insert the rear bottom of the module into the DIN rail, then push up and inwards to engage the clip.

REMOVAL: Push the module upwards to disengage the clip, then rotate the module toward you.

Mounting the NGC-40-BRIDGE

RS-485 Connection Diagrams – North American Installation TechniqueCOM 1&2 Connections (In) COM 1&2 Connections (Out) and

RS-485 Termination Resistor

Page 5: NGC-40-BRIDGE - nVent · 2020. 3. 10. · E60079-15:02 (R2006) (Russia, Kazakhstan, Belarus) For other countries contact your local nVent representative. NGC-40-BRIDGE ... A slide

nVent.com | 5

RESET

NGC-40 BRIDGE MODULE

EthernetEthernetTo upstream

deviceTo upstream

device

RS-232RS-232Local RS-232

to LaptopLocal RS-232

to Laptop

Local RS-232 (COM 3) & Ethernet Switch Setting RS-232

User Interface – Configuration SwitchA slide switch is provided on the front of the module to allow the user to set the bridge into a known state for configuration of the communication ports, as shown in the following table:

Switch Position

Bridge Module Settings

SET Configuration mode

RUN Normal operating mode

Modbus address 1

Settings based on the user configuration parameters

Local RS-232

Protocol RTU

Data rate 9600 baud

Data bits 8

Stop bits 2

Parity No parity

COM 1 InCOM 1 In

11 55 99

++ ––RESET

NGC-40 BRIDGE MODULE

Fieldterminalblock

Fieldterminalblock

COM 2 InCOM 2 In

33 77 1111

++ ––

++ ––

++ ––

Earth groundingbar located at thebridge module

Earth groundingbar located at thebridge module

Earth groundingbar located at thebridge module

Earth groundingbar located at thebridge module

To upstreamdevice

To upstreamdevice

To upstreamdevice

To upstreamdevice

RESET

NGC-40 BRIDGE MODULE

COM 1 OutCOM 1 Out

22 66 1010

++ ––

COM 2 OutCOM 2 Out

44 88 1212

++ ––

120 ohm termination

resistor

120 ohm termination

resistor

120 ohm termination

resistor

120 ohm termination

resistor

Fieldterminalblock

Fieldterminalblock

Earth groundingbar located at thebridge module

Earth groundingbar located at thebridge module

Earth groundingbar located at thebridge module

Earth groundingbar located at thebridge module

Wiring for Com 1 & Com 2 must be terminated on a panel mounted terminal block. No ground wires should be terminated on terminals 9 & 11. Terminate Com shields at the panel mounted field terminal block chassis ground. The Com cable shield from the field terminal block to the Bridge should be terminated at the earth ground bar.

Wiring for Com 1 & Com 2 must be terminated on a panel mounted terminal block. No ground wires should be terminated on terminals 10 & 12. Terminate Com shields and 120 Ω termination resistors (included) at the panel mounted field terminal block as shown. The Com cable shield from the field terminal block to the Bridge should be terminated at the earth ground bar.

RS-485 Connection Diagrams – European Installation TechniqueCOM 1&2 Connections (In) COM 1&2 Connections (Out) and RS-485 Termination Resistor

Page 6: NGC-40-BRIDGE - nVent · 2020. 3. 10. · E60079-15:02 (R2006) (Russia, Kazakhstan, Belarus) For other countries contact your local nVent representative. NGC-40-BRIDGE ... A slide

6 | nVent.com

RS-485 ShieldedTwisted PairRS-485 ShieldedTwisted Pair

RESET

NGC-40 BRIDGE MODULE

COM 2 InCOM 2 In

33 77 1111

++ ––

++ ––

Earth groundingbar located at thebridge module

Earth groundingbar located at thebridge module

Panel Terminal BlockPanel Terminal Block

++ ––~~ ~~

PanelPanel

++ ––To nextRMM2To nextRMM2

FieldField~~~~

++ ––++ ––

When using the field mounted RMM2 for RTD input, it must be connected to the COM 2 In as shown below.

RMM2 Connection – Optional

Page 7: NGC-40-BRIDGE - nVent · 2020. 3. 10. · E60079-15:02 (R2006) (Russia, Kazakhstan, Belarus) For other countries contact your local nVent representative. NGC-40-BRIDGE ... A slide

nVent.com | 7

Power/Termination

Module

Power/Termination

Module

CAN/TermCAN/TermCAN / 24 VdcCAN / 24 Vdc

ININ OUT

CAN / 24 Vdc

HTC/HTC3orI/O

Module 10

ININ OUTOUT

CAN / 24 Vdc

HTC/HTC3orI/O

Module 4

ININ OUTOUT

CAN / 24 Vdc

HTC/HTC3orI/O

Module 3

ININ OUTOUT

CAN / 24 Vdc

HTC/HTC3orI/O

Module 2

ININ OUTOUT

CAN / 24 Vdc

BridgeModule

80 Modulesper Bridge

Module 1++––20 Modules

per Power Supply20 Modules

per Power Supply20 Modules

per Power Supply20 Modules

per Power Supply

TerminationBlock

TerminationBlock

100-240 Vac In100-240 Vac In

Optional redundant supplyOptional redundant supply

100-240 Vac In100-240 Vac In

++––

CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc

ININ OUT

CAN / 24 Vdc

HTC/HTC3orI/O

Module 20

ININ OUTOUT

CAN / 24 Vdc

HTC/HTC3orI/O

Module 14

ININ OUTOUT

CAN / 24 Vdc

HTC/HTC3orI/O

Module 13

ININ OUTOUT

CAN / 24 Vdc

HTC/HTC3orI/O

Module 12

ININ

CAN / 24 Vdc

HTC/HTC3orI/O

Module 11

OUTOUT

TerminationBlock

TerminationBlockCAN / 24 Vdc CAN / 24 Vdc

CAN / 24 Vdc

CAN / 24 Vdc CAN / 24 Vdc

Power/Termination

Module

Power/Termination

Module

CAN / 24 Vdc

Primary Supply*24 Vdc

Primary Supply*24 Vdc

* Power supply shall have a means for disconnect from line voltage* Power supply shall have a means for disconnect from line voltage

Redundant Supply*24 Vdc

Redundant Supply*24 Vdc

ININ OUT

CAN / 24 Vdc

HTC/HTC3orI/O

Module 10

ININ OUTOUT

CAN / 24 Vdc

HTC/HTC3orI/O

Module 4

ININ OUTOUT

CAN / 24 Vdc

HTC/HTC3orI/O

Module 3

ININ OUTOUT

CAN / 24 Vdc

HTC/HTC3orI/O

Module 2

ININ OUTOUT

CAN / 24 Vdc

BridgeModule

80 Modulesper Bridge

Module 1

TerminationBlock

TerminationBlock

++––

Power/Termination

Module

Power/Termination

Module

Primary Supply*24 Vdc

Primary Supply*24 Vdc

20 Modulesper Power Supply

20 Modulesper Power Supply

TerminationBlock

TerminationBlock

CAN/TermCAN/TermCAN / 24 VdcCAN / 24 Vdc

100-240 Vac In100-240 Vac In

Optional redundant supplyOptional redundant supply

100-240 Vac In100-240 Vac In

++––

CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc

Redundant Supply*24 Vdc

Redundant Supply*24 Vdc

20 Modulesper Power Supply

20 Modulesper Power Supply

* Power supply shall have a means for disconnect from line voltage* Power supply shall have a means for disconnect from line voltage

NGC-40 CAN Bus Connections for Up to 10 Modules

NGC-40 CAN Bus Connections for Up to 20 Modules

Page 8: NGC-40-BRIDGE - nVent · 2020. 3. 10. · E60079-15:02 (R2006) (Russia, Kazakhstan, Belarus) For other countries contact your local nVent representative. NGC-40-BRIDGE ... A slide

8 | nVent.com

HTC/HTC3/IO

HTC/HTC3/IO

PTM

PTM

CAN / TERM

CAN /

24 VDC

Termination

block

CAN / TERM CAN / 24 VDC

Termination

block

A termination block (included) is required at each end of the CAN/24 Vdc bus. See NGC-40 CAN bus connection wiring diagram for more details.

CAN Bus Termination Block

1. Provide suitable panel enclosure

The NGC-40-BRIDGE must be mounted in an enclosure to protect its electronic components. For indoor applications, use a minimum NEMA 1 enclosure (NEMA 12 recommended). For outdoor applications, use a NEMA 4 or NEMA 4X enclosure depending on the requirements.

Note: The nVent RAYCHEM NGC-40-BRIDGE is designed for operation in ambient temperatures from –40°C to 65°C (–40°F to 149°F ). If the ambient temperature is outside this range, a space heater and/or cooling fan will be required in the panel.

2. Determine locations for the NGC-40-BRIDGE assembly in the electrical panel.

The NGC-40-BRIDGE should be located in the rear of the panel. The NGC-40-BRIDGE assembly is an electronic unit and must not be located where it will be exposed to strong magnetic fields or excessive vibration.

*North American panel installation techniques

PS1

PTM

1

CBM

I/O

1

I/O

2

I/O

3

I/O

4

I/O

5

PS2

PTM

2

HTC

1

HTC

2

HTC

3

HTC

4

HTC

5

HTC

6

HTC

7

HTC

8

HTC

9

HTC

10

C1 C2 C3 C4 C5 C6 C7 C8 C9 C10

PS3

PTM

3

HTC

11

HTC

12

HTC

13

HTC

14

HTC

15

HTC

16

HTC

17

HTC

18

HTC

19

HTC

20

C11

C12

C113 C4 C5 C16

C17

C18

C19

C20

PS4

PTM

4

HTC

21

HTC

22

HTC

23

HTC

24

HTC

25

HTC

26

HTC

27

HTC

28

HTC

29

HTC

30

C21

C22

C23

C24

C25

TB

C26

C27

C28

C29

C30

PanelPaneldoor

Alarmlight

Provide Suitable Panel Enclosure and Determine Locations for NGC-40-BRIDGE Assembly in Panel*

Page 9: NGC-40-BRIDGE - nVent · 2020. 3. 10. · E60079-15:02 (R2006) (Russia, Kazakhstan, Belarus) For other countries contact your local nVent representative. NGC-40-BRIDGE ... A slide

nVent.com | 9

Power/Termination

Module

Power/Termination

Module

CAN/TermCAN/TermCAN / 24 VdcCAN / 24 Vdc

Power/Termination

Board

Power/Termination

Board

CAN/TermCAN/TermCAN / 24 VdcCAN / 24 Vdc

Power/Termination

Module

Power/Termination

Module

CAN/TermCAN/TermCAN / 24 VdcCAN / 24 Vdc

Power/Termination

Modules

Power/Termination

Modules

CAN/TermCAN/TermCAN / 24 VdcCAN / 24 Vdc

ININ OUT

CAN / 24 Vdc

HTC/HTC3orI/O

Module 10

ININ OUTOUT

CAN / 24 Vdc

HTC/HTC3orI/O

Module 4

ININ OUTOUT

CAN / 24 Vdc

HTC/HTC3orI/O

Module 3

ININ OUTOUT

CAN / 24 Vdc

HTC/HTC3orI/O

Module 2

ININ OUTOUT

CAN / 24 Vdc

BridgeModule

80 Modulesper BridgeModule 1

CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc

ININ OUT

CAN / 24 Vdc

HTC/HTC3orI/O

Module 20

ININ OUTOUT

CAN / 24 Vdc

HTC/HTC3orI/O

Module 14

ININ OUTOUT

CAN / 24 Vdc

HTC/HTC3orI/O

Module 13

ININ OUTOUT

CAN / 24 Vdc

HTC/HTC3orI/O

Module 12

ININ OUTOUT

CAN / 24 Vdc

BridgeModule

80 Modulesper BridgeModule 11

CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc

ININ OUT

CAN / 24 Vdc

HTC/HTC3orI/O

Module 30

ININ OUTOUT

CAN / 24 Vdc

HTC/HTC3)orI/O

Module 24

ININ OUTOUT

CAN / 24 Vdc

HTC/HTC3orI/O

Module 23

ININ OUTOUT

CAN / 24 Vdc

HTC/HTC3orI/O

Module 22

ININ OUTOUT

CAN / 24 Vdc

HTC/HTC3orI/O

Module 21

++––20 Modules

per Power Supply20 Modules

per Power Supply

100-240 Vac In100-240 Vac In

20 Modulesper Power Supply

20 Modulesper Power Supply

100-240 Vac In100-240 Vac In

Optional redundant supplyOptional redundant supply

++––

CAN / 24 Vdc

CAN / 24 Vdc

CAN / 24 Vdc

CAN / 24 Vdc CAN / 24 Vdc

CAN / 24 Vdc

CAN / 24 Vdc

CAN / 24 Vdc CAN / 24 Vdc

ININ OUT

CAN / 24 Vdc

HTC/HTC3orI/O

Module 40

ININ OUTOUT

CAN / 24 Vdc

HTC/HTC3orI/O

Module 34

ININ OUTOUT

CAN / 24 Vdc

HTC/HTC3orI/O

Module 33

ININ OUTOUT

CAN / 24 Vdc

HTC/HTC3orI/O

Module 32

ININ OUTOUT

CAN / 24 Vdc

HTC/HTC3orI/O

Module 31

TerminationBlock

TerminationBlockCAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc

++––20 Modules

per Power Supply20 Modules

per Power Supply

TerminationBlock

TerminationBlock

100-240 Vac In100-240 Vac In

20 Modulesper Power Supply

20 Modulesper Power Supply

100-240 Vac In100-240 Vac In

Optional redundant supplyOptional redundant supply

++––

CAN / 24 Vdc

CAN / 24 Vdc

Primary Supply*24 Vdc

Primary Supply*24 Vdc

Redundant Supply*24 Vdc

Redundant Supply*24 Vdc

Primary Supply*24 Vdc

Primary Supply*24 Vdc

Redundant Supply*24 Vdc

Redundant Supply*24 Vdc

* Power supply shall have a means for disconnect from line voltage

NGC-40 CAN Bus Connections for Up to 40 Modules

Page 10: NGC-40-BRIDGE - nVent · 2020. 3. 10. · E60079-15:02 (R2006) (Russia, Kazakhstan, Belarus) For other countries contact your local nVent representative. NGC-40-BRIDGE ... A slide

North America Tel +1.800.545.6258Fax [email protected]

Europe, Middle East, AfricaTel +32.16.213.511Fax [email protected]

Asia PacificTel +86.21.2412.1688Fax [email protected]

Latin AmericaTel +1.713.868.4800Fax [email protected]

©2019 nVent. All nVent marks and logos are owned or licensed by nVent Services GmbH or its affiliates. All other trademarks are the property of their respective owners. nVent reserves the right to change specifications without notice.

RAYCHEM-IM-H58089-NGC40Bridge-EN-1910 PCN 1244-009547