  • NFPA 88AStandard for

    ParkingStructures

    1998 Edition

    National Fire Protection Association, 1 Batterymarch Park, PO Box 9101, Quincy, MA 02269-9101An International Codes and Standards Organization

  • Copyright

    National Fire Protection Association, Inc.

    One Batterymarch Park

    Quincy, Massachusetts 02269

    IMPORTANT NOTICE ABOUT THIS DOCUMENT

    NFPA codes and standards, of which the document contained herein is one, are developed through a consensus stan-

    dards development process approved by the American National Standards Institute. This process brings together volunteers

    representing varied viewpoints and interests to achieve consensus on fire and other safety issues. While the NFPA admin-

    isters the process and establishes rules to promote fairness in the development of consensus, it does not independently test,

    evaluate, or verify the accuracy of any information or the soundness of any judgments contained in its codes and standards.

    The NFPA disclaims liability for any personal injury, property or other damages of any nature whatsoever, whether

    special, indirect, consequential or compensatory, directly or indirectly resulting from the publication, use of, or reliance on

    this document. The NFPA also makes no guaranty or warranty as to the accuracy or completeness of any information pub-

    lished herein.

    In issuing and making this document available, the NFPA is not undertaking to render professional or other services

    for or on behalf of any person or entity. Nor is the NFPA undertaking to perform any duty owed by any person or entity to

    someone else. Anyone using this document should rely on his or her own independent judgment or, as appropriate, seek the

    advice of a competent professional in determining the exercise of reasonable care in any given circumstances.

    The NFPA has no power, nor does it undertake, to police or enforce compliance with the contents of this document.

    Nor does the NFPA list, certify, test or inspect products, designs, or installations for compliance with this document. Any

    certification or other statement of compliance with the requirements of this document shall not be attributable to the NFPA

    and is solely the responsibility of the certifier or maker of the statement.

    NOTICES

    All questions or other communications relating to this document and all requests for information on NFPA procedures

    governing its codes and standards development process, including information on the procedures for requesting Formal

    Interpretations, for proposing Tentative Interim Amendments, and for proposing revisions to NFPA documents during

    regular revision cycles, should be sent to NFPA headquarters, addressed to the attention of the Secretary, Standards Coun-

    cil, National Fire Protection Association, 1 Batterymarch Park, P.O. Box 9101, Quincy, MA 02269-9101.

    Users of this document should be aware that this document may be amended from time to time through the issuance of

    Tentative Interim Amendments, and that an official NFPA document at any point in time consists of the current edition of

    the document together with any Tentative Interim Amendments then in effect. In order to determine whether this document

    is the current edition and whether it has been amended through the issuance of Tentative Interim Amendments, consult ap-

    propriate NFPA publications such as the National Fire Codes Subscription Service, visit the NFPA website at

    www.nfpa.org, or contact the NFPA at the address listed above.

    A statement, written or oral, that is not processed in accordance with Section 16 of the Regulations Governing Com-

    mittee Projects shall not be considered the official position of NFPA or any of its Committees and shall not be considered

    to be, nor be relied upon as, a Formal Interpretation.

    The NFPA does not take any position with respect to the validity of any patent rights asserted in connection with any

    items which are mentioned in or are the subject of this document, and the NFPA disclaims liability of the infringement of

    any patent resulting from the use of or reliance on this document. Users of this document are expressly advised that deter-

    mination of the validity of any such patent rights, and the risk of infringement of such rights, is entirely their own responsi-

    bility.

    Users of this document should consult applicable federal, state, and local laws and regulations. NFPA does not, by the

    publication of this document, intend to urge action that is not in compliance with applicable laws, and this document may

    not be construed as doing so.

  • Licensing Policy

    This document is copyrighted by the National Fire Protection Association (NFPA). By making this document avail-

    able for use and adoption by public authorities and others, the NFPA does not waive any rights in copyright to this docu-

    ment.

    1. Adoption by Reference Public authorities and others are urged to reference this document in laws, ordinances,

    regulations, administrative orders, or similar instruments. Any deletions, additions, and changes desired by the adopting

    authority must be noted separately. Those using this method are requested to notify the NFPA (Attention: Secretary, Stan-

    dards Council) in writing of such use. The term adoption by reference means the citing of title and publishing information

    only.

    2. Adoption by Transcription A. Public authorities with lawmaking or rule-making powers only, upon written no-

    tice to the NFPA (Attention: Secretary, Standards Council), will be granted a royalty-free license to print and republish this

    document in whole or in part, with changes and additions, if any, noted separately, in laws, ordinances, regulations, admin-

    istrative orders, or similar instruments having the force of law, provided that: (1) due notice of NFPAs copyright is con-

    tained in each law and in each copy thereof; and (2) that such printing and republication is limited to numbers sufficient to

    satisfy the jurisdictions lawmaking or rule-making process. B. Once this NFPA Code or Standard has been adopted into

    law, all printings of this document by public authorities with lawmaking or rule-making powers or any other persons desir-

    ing to reproduce this document or its contents as adopted by the jurisdiction in whole or in part, in any form, upon written

    request to NFPA (Attention: Secretary, Standards Council), will be granted a nonexclusive license to print, republish, and

    vend this document in whole or in part, with changes and additions, if any, noted separately, provided that due notice of

    NFPAs copyright is contained in each copy. Such license shall be granted only upon agreement to pay NFPA a royalty.

    This royalty is required to provide funds for the research and development necessary to continue the work of NFPA and its

    volunteers in continually updating and revising NFPA standards. Under certain circumstances, public authorities with law-

    making or rule-making powers may apply for and may receive a special royalty where the public interest will be served

    thereby.

    3. Scope of License Grant The terms and conditions set forth above do not extend to the index of this document.

    (For further explanation, see the Policy Concerning the Adoption, Printing, and Publication of NFPA Documents,

    which is available upon request from the NFPA.)

  • 88A1Copyright 1998 NFPA, All Rights Reserved

    NFPA 88A

    Standard for

    Parking Structures

    1998 Edition

    This edition of NFPA 88A, Standard for Parking Structures, was prepared by the TechnicalCommittee on Garages and Parking Structures and acted on by the National Fire ProtectionAssociation, Inc., at its Annual Meeting held May 1821, 1998, in Cincinnati, OH. It was issuedby the Standards Council on July 16, 1998, with an effective date of August 5, 1998, and super-sedes all previous editions.

    This edition of NFPA 88A was approved as an American National Standard on August 6,1998.

    Changes other than editorial are indicated by a vertical rule in the margin of the pages onwhich they appear. These lines are included as an aid to the user in identifying changes fromthe previous edition.

    Origin and Development of NFPA 88AWork on fire protection safeguards for garages was initiated by the NFPA in 1927 with the

    appointment of a committee. After extensive deliberations and the publication of successivedrafts, the standard was adopted in 1932. Subsequently, the committee was discharged as itappeared that no further activity was needed in this field. In 1952 the present committee wascreated. This committee prepared a number of redrafts of the 1932 text, and in 1957 a revisedNFPA 88, Standard for Garages, was adopted. Revisions were made in 1962, 1968, 1979, 1985,and 1995.

    Prior to 1973, the subject of this standard was included in NFPA 88, Standard for Garages.In order to treat separately the occupancies of repair garages and parking structures, this stan-dard and NFPA 88B, Standard for Repair Garages, were published separately in 1973.

    In 1991 partial revisions were made, and the 1995 edition contained editorial changes.The 1998 edition contains definitions clarifying the various configurations of parking struc-tures. It further contains changes increasing the area of office space related to the parkingstructure and further clarifies the requirements for vertical opening protection and auto-matic sprinkler installation. This edition also includes new requirements for natural gas pow-ered vehicles.

  • 88A2 PARKING STRUCTURES

    1998Technical Committee on Garages and Parking Structures

    Michael Crowley, Chair Rolf Jensen & Assoc., Inc., TX [SE]

    Michael D. Cato, Delray Beach Fire Dept., FL [E]Rep. Fire Marshals Assn. of North America

    Allan Davis, Hunnicutt Davis and Assoc., CT [U]Rep. International Parking Institute

    Thomas J. Forsythe, Gage-Babcock & Assoc., CA [SE]Richard G. Gewain, Hughes Assoc., Inc., MD [SE]Marshall A. Klein, Marshall A. Klein & Assoc., Inc., MD [U]

    Rep. TC Automotive/Marine Service Station

    Hank Martin, American Iron and Steel Inst., CA [M]Howard R. May, Desman Assoc., IL [U]

    Rep. National Parking Assn.Joseph J. Messersmith, Jr., Portland Cement Assn., VA [M]Robert L. Ruyle, Ruyle & Assoc., NE [SE]Domenick A. Serrano, Jr., S&S Fire Suppression Systems Inc., NY [M]

    Rep. Natl Fire Sprinkler Assn.

    Alternates

    James Golinveaux, Central Sprinkler Corp., PA [M](Alt to D. A. Serrano, Jr.)

    James M. Hunnicutt, Hunnicutt Davis and Assoc., MD [U](Alt. to A. Davis)

    Stephen V. Skalko, Portland Cement Assn., GA [M](Alt. to J. J. Messersmith, Jr.)

    Robert J. Wills, American Iron & Steel Inst., AL [M](Alt. to H. Martin)

    James D. Lake, Staff Liaison

    This list represents the membership at the time the Committee was balloted on the text of this edition. Since that time, chang-es in the membership may have occurred. A key to classifications is found at the back of this document.

    NOTE: Membership on a committee shall not in and of itself constitute an endorsement of the Associationor any document developed by the committee on which the member serves.

    Committee Scope: This Committee shall have primary responsibility for documents on construction, con-trol of fire hazards, ventilation, fire protection, and maintenance of garages and parking structures. Edition

  • CONTENTS 88A3

    1998 Edition

    Contents

    Chapter 1 General . . . . . . . . . . . . . . . . . . . . . . . . . . 88A 41-1 Scope. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88A 41-2 Purpose . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88A 41-3 Equivalency . . . . . . . . . . . . . . . . . . . . . . . . . . . 88A 41-4 Retroactivity . . . . . . . . . . . . . . . . . . . . . . . . . . 88A 4

    Chapter 2 Definitions . . . . . . . . . . . . . . . . . . . . . . . . 88A 42-1 Definitions. . . . . . . . . . . . . . . . . . . . . . . . . . . . 88A 4

    Chapter 3 Construction . . . . . . . . . . . . . . . . . . . . . . 88A 43-1 General Requirements . . . . . . . . . . . . . . . . . . 88A 43-2 Internal Subdivision . . . . . . . . . . . . . . . . . . . . 88A 53-3 Floors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88A 53-4 Means of Egress. . . . . . . . . . . . . . . . . . . . . . . . 88A 53-5 Openings in Fire Walls and Fire Partitions . . . 88A 53-6 Vertical Openings in Enclosed Parking

    Structures . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88A 53-7 Open Parking Structures . . . . . . . . . . . . . . . . 88A 5

    Chapter 4 Hazards . . . . . . . . . . . . . . . . . . . . . . . . . . 88A 54-1 Lighting and Power . . . . . . . . . . . . . . . . . . . . 88A 54-2 Heating. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88A 54-3 Ventilation . . . . . . . . . . . . . . . . . . . . . . . . . . . 88A 5

    4-4 Storage and Handling of FlammableLiquids and Liquefied Petroleum Gasand Natural Gas . . . . . . . . . . . . . . . . . . . . . . 88A 5

    4-5 Housekeeping . . . . . . . . . . . . . . . . . . . . . . . . 88A 6

    Chapter 5 Protection . . . . . . . . . . . . . . . . . . . . . . . . 88A 65-1 Automatic Sprinkler Systems, Fire Alarm

    Systems, and Signaling Systems. . . . . . . . . . . 88A 65-2 Automatic Sprinkler Systems or Fire

    Detection and Smoke Removal . . . . . . . . . . . 88A 65-3 Maintenance and Supervision of Fire

    Detection and Fire-ExtinguishingSystems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88A 6

    5-4 Standpipes . . . . . . . . . . . . . . . . . . . . . . . . . . . 88A 65-5 Employee Instruction . . . . . . . . . . . . . . . . . . 88A 6

    Chapter 6 Referenced Publications. . . . . . . . . . . . . 88A 6

    Appendix A Explanatory Material. . . . . . . . . . . . . . . 88A 7

    Appendix B Referenced Publications. . . . . . . . . . . . 88A 7

    Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88A 7

  • 88A4 PARKING STRUCTURESNFPA 88A

    Standard for

    Parking Structures

    1998 Edition

    NOTICE: An asterisk (*) following the number or letter des-ignating a paragraph indicates that explanatory material onthe paragraph can be found in Appendix A.

    Information on referenced publications can be found inChapter 6 and Appendix B.

    Chapter 1 General

    1-1 Scope. This standard shall cover the construction andprotection of, as well as the control of hazards in, open,enclosed, basement, and underground parking structures.This standard shall not apply to one- and two-family dwellings.

    1-2 Purpose. The purpose of this standard is to provide min-imum fire protection standards for parking structures.

    1-3 Equivalency. Nothing in this standard is intended to pre-vent the use of systems, methods, or devices of equivalent orsuperior quality, strength, fire resistance, effectiveness, dura-bility, and safety over those prescribed by this standard, pro-vided technical documentation is submitted to the authorityhaving jurisdiction to demonstrate equivalency and the sys-tem, method, or device is approved for the intended purpose.

    1-4 Retroactivity.

    1-4.1 The provisions of this document are considered neces-sary to provide a reasonable level of protection from loss of lifeand property from fire and explosion. They reflect situationsand the state of the art prevalent at the time the standard wasissued.

    1-4.2 Unless otherwise noted, it is not intended that the pro-visions of this document be applied to facilities, equipment,structures, or installations that were existing or approved forconstruction or installation prior to the effective date of thedocument, except in those cases where it is determined by theauthority having jurisdiction that the existing situationinvolves a distinct hazard to life or adjacent property.

    Chapter 2 Definitions

    2-1 Definitions.

    Approved.* Acceptable to the authority having jurisdic-tion.

    Authority Having Jurisdiction.* The organization, office, orindividual responsible for approving equipment, an installa-tion, or a procedure.

    Basement and Underground Parking Structures. Parkingstructures that are located below grade. A basement parkingstructure has other occupancies above it; an undergroundparking structure has no occupancy other than parking aboveit. Basement and underground parking structures are consid-ered as specific cases of enclosed parking structures.

    Enclosed Parking Structure. Any parking structure that isnot an open parking structure.

    Labeled. Equipment or materials to which has beenattached a label, symbol, or other identifying mark of an orga-nization that is acceptable to the authority having jurisdictionand concerned with product evaluation, that maintains peri-odic inspection of production of labeled equipment or mate-rials, and by whose labeling the manufacturer indicatescompliance with appropriate standards or performance in aspecified manner.

    Listed.* Equipment, materials, or services included in a listpublished by an organization that is acceptable to the author-ity having jurisdiction and concerned with evaluation of prod-ucts or services, that maintains periodic inspection ofproduction of listed equipment or materials or periodic eval-uation of services, and whose listing states that either theequipment, material, or service meets identified standards orhas been tested and found suitable for a specified purpose.

    Open Parking Structures. A parking structure that, at eachparking level, has wall openings open to the atmosphere, foran area of not less than 1.4 ft2 (0.13 m2) for each linear foot(0.3 m) of its exterior perimeter. Such openings are distrib-uted over 40 percent of the building perimeter or uniformlyover two opposing sides. Interior walls lines and column linesare at least 20 percent open, with openings distributed to pro-vide ventilation.

    Parking Structure. A building, structure, or portion thereofused for the parking, or storage, or both, of motor vehicles. Aparking structure shall be permitted to be enclosed or open,shall be permitted to use ramps, and shall be permitted to usemechanical control push-button-type elevators to transfervehicles from one floor to another. Motor vehicles are permit-ted to be parked by the driver or an attendant, or are permit-ted to be parked mechanically by automatic facilities. Whereautomatic parking is provided, the operator of those facilitiesshall be permitted either to remain at the entry level or totravel to another level. Motor fuel shall be permitted to be dis-pensed, and motor vehicles shall be permitted to be servicedin a parking structure.

    Chapter 3 Construction

    3-1 General Requirements.

    3-1.1* Parking structures shall be built using one of the typesof construction defined in NFPA 220, Standard on Types ofBuilding Construction, except as otherwise amended in thisstandard.

    3-1.2 Those parts of parking structures located within, imme-diately below, attached to, or less than 10 ft (3.0 m) from abuilding used for any other purpose shall be separated bywalls, partitions, floors, or floor-ceiling assemblies having a fireresistance rating of not less than 2 hours.

    Exception: No fire-rated separation is required when parts of a park-ing structure and a building used for any other purpose, separated by10 ft (3.0 m) or more, are attached only via open pedestrian balconiesor bridges or open vehicle bridges.

    3-1.3* Those portions of an open parking structure locatedwithin or immediately below a building used for another pur-pose shall have the principal supporting members and bear-ing walls in all levels of the parking structure protected to1998 Edition

  • HAZARDS 88A5provide a fire-resistive rating equivalent to that required forthe other occupancy.

    3-2 Internal Subdivision. Offices or other similar spaces thatare related to the operation of the parking structure and areless than 3000 ft2 (279 m2) in area shall be separated fromparking areas by walls or partitions that resist the passage ofsmoke.

    Exception: Cashier or attendant booths shall be permitted to be open tothe parking structure.

    3-3 Floors.

    3-3.1 Floor surfaces shall be of noncombustible material.

    3-3.1.1 Where combustible construction is permitted, floorsurfaces shall be noncombustible and liquid tight.

    3-3.1.2* Asphalt shall be permitted on grade.

    3-3.2 Floors shall be graded and equipped with drains.

    3-3.3 Floors in areas of parking structures where motor fuelsare dispensed shall be designed in accordance with NFPA 30A,Automotive and Marine Service Station Code.

    3-4 Means of Egress. Means of egress shall conform with theprovisions set forth in NFPA 101, Life Safety Code.

    3-5 Openings in Fire Walls and Fire Partitions

    3-5.1 Doorways and other openings in fire walls and fire parti-tions shall be protected with approved fire doors installed inaccordance with NFPA 80, Standard for Fire Doors and Fire Win-dows.

    3-5.2 Where ducts pass through fire walls or fire partitions,the openings shall be protected in accordance with NFPA90A, Standard for the Installation of Air Conditioning and Venti-lating Systems.

    3-6 Vertical Openings in Enclosed Parking Structures. Verti-cal openings through floors in buildings four stories or morein height shall be enclosed with walls or partitions having a fireresistance rating of not less than 2 hours. For buildings lessthan four stories, such walls or partitions shall have a fire resis-tance rating of not less than 1 hour.

    Ramps in enclosed parking structures, shall not be required to be en-closed when either of the following safeguards is provided:

    (a) An approved, automatic sprinkler system fully protecting theparking structure

    (b) An approved, automatic, supervised fire detection system in-stalled throughout the parking structure using detectors sensing prod-ucts of combustion other than heat and a mechanical ventilationsystem in accordance with 4-3.2.

    3-7 Open Parking Structures.

    3-7.1 Open parking structures shall be of Type I or Type IIconstruction as defined in NFPA 220, Standard on Types ofBuilding Construction.

    3-7.2 Heights and floor areas of open parking structures ofType I, Type II (222), or Type II (111) construction shall bepermitted to be unlimited.

    3-7.3 Open parking structures of Type II (000) constructionshall be permitted to be of unlimited area where the followingconditions are met:(a) The height does not exceed 75 ft (22.9 m).

    (b) The horizontal distance from any point on any parkinglevel to an exterior wall opening on a street, an alley, acourtyard, or other similar permanent open space doesnot exceed 200 ft (61 m).

    Chapter 4 Hazards

    4-1 Lighting and Power.

    4-1.1 Electric wiring for light, power, heat, and signal or con-trol circuits and for electrically operated tools, portable appli-ances, and devices shall be in accordance with the provisionsof NFPA 70, National Electrical Code.

    4-1.2 Areas where flammable liquids are stored, handled, ordispensed shall be delineated and classified for the installationof electrical equipment in accordance with NFPA 30A, Automo-tive and Marine Service Station Code.

    4-2 Heating.

    4-2.1 Heating equipment shall conform with NFPA 90A, Stan-dard for the Installation of Air Conditioning and Ventilating Systems;NFPA 31, Standard for the Installation of Oil-Burning Equipment;NFPA 54, National Fuel Gas Code; and NFPA 211, Standard forChimneys, Fireplaces, Vents, and Solid Fuel-Burning Appliances, asapplicable.

    4-2.2 All flames associated with heating equipment shall belocated a minimum of 18 in. (457.2 mm) below the floor-ceiling assembly or 18 in. (457.2 mm) above the floor.

    Exception: Heating equipment located in such a manner that it is pro-tected by a partition not less than 18 in. (457.2 mm) above the floor.

    4-2.3 Improvised furnaces, salamanders, or space heatersshall not be used.

    4-3 Ventilation.

    4-3.1 A mechanical ventilation system shall not be required inan open parking structure.

    4-3.2* All enclosed parking structures shall be ventilated by amechanical system capable of providing a minimum of 1.0 cfmper sq ft of floor area (0.3 m3 per minute per m2) per hourduring hours of normal operation.

    4-3.3 Mechanical ventilating systems shall be installed inaccordance with NFPA 90A, Standard for the Installation of AirConditioning and Ventilating Systems. Ductwork shall be con-structed of noncombustible material.

    4-4 Storage and Handling of Flammable Liquids and Lique-fied Petroleum Gas and Natural Gas.

    4-4.1 The storage and handling of flammable liquids shallconform with NFPA 30, Flammable and Combustible Liquids Code.The storage and handling of liquefied petroleum gas shallconform with NFPA 58, Liquefied Petroleum Gas Code. The stor-age and handling of natural gas fuels shall conform with NFPA52, Compressed Natural Gas (CNG) Vehicular Fuel Systems Code, orNFPA 57, Standard for Liquefied Natural Gas (LNG) Vehicular FuelSystems.

    4-4.2 Dispensing Equipment. The design and installation ofequipment and storage tanks used for the dispensing of flam-mable liquids shall conform with the requirements for servicestations in NFPA 30A, Automotive and Marine Service StationCode. The equipment and storage tanks used for the dispens-1998 Edition

  • 88A6 PARKING STRUCTURESing of natural gas fuels shall conform with NFPA 52, CompressedNatural Gas (CNG) Vehicular Fuel Systems Code, or NFPA 57, Stan-dard for Liquefied Natural Gas (LNG) Vehicular Fuel Systems. Theequipment and storage tanks used for the dispensing of lique-fied petroleum gas shall conform with NFPA 58, Liquefied Petro-leum Gas Code.

    4-5 Housekeeping.

    4-5.1 Daily inspections of the parking structure shall be madefor the removal or repair of any hazardous condition. Equip-ment and safety devices shall be maintained, and hazardousaccumulations of combustible material shall be removed fromthe structure.

    4-5.2 Clear aisle space shall be maintained to permit readyaccess to, and the use of, fire-fighting equipment.

    4-5.3 Metal lockers shall be provided for employees clothes.

    4-5.4 Approved metal receptacles with self-closing covers shallbe provided for the storage or disposal of oil-soaked waste orcloths.

    4-5.5 Covered metal containers shall be used for combustibletrash.

    Exception: Containers of 55 gal (208 L) or less capacity.

    4-5.6 Floors shall be kept clean and free of oil and grease.

    Chapter 5 Protection

    5-1 Automatic Sprinkler Systems, Fire Alarm Systems, and Signaling Systems.

    5-1.1 Automatic sprinkler systems, where required, shallconform with NFPA 13, Standard for the Installation of Sprin-kler Systems.

    5-1.2 Fire alarm systems, where required, shall conform withNFPA 72, National Fire Alarm Code.

    5-1.3 Automatic sprinklers and fire alarm systems shall not berequired in open parking structures.

    5-1.4 Automatic sprinkler systems shall be installed in base-ment and underground parking structures, the ceilings ofwhich are less than 2 ft (1.7 m) above grade, and in enclosedparking structures of Type III or Type IV construction over 50 ft(15.2 m) in height.

    5-2 Automatic Sprinkler Systems or Fire Detection and SmokeRemoval. Enclosed parking structures located at or abovegrade, within or immediately below a building used foranother occupancy, shall have one of the following systems:(a) An approved, automatic sprinkler system fully protecting

    the parking area(b) An approved, automatic, supervised fire detection system

    installed throughout the parking areas using detectorssensing products of combustion other than heat, and amechanical ventilation system in accordance with 4-3.2

    5-3 Maintenance and Supervision of Fire Detection and Fire-Extinguishing Systems.

    5-3.1 Where an automatic fire alarm or automatic fire-extin-guishing system is installed as a requirement of this standard,the system shall be supervised adequately to ensure reliable

    operation in accordance with 5-3.1.1 through 5-3.1.3 as appro-priate.

    5-3.1.1 The extinguishing or alarm system shall be electricallyconnected, either directly or through a central station facilityor by another approved method, to the fire department legallycommitted to serve the area where the building is located. Sys-tem actuation shall initiate the alarm sequence.

    5-3.1.2 Where a system might become inoperable due to clos-ing of valves, interruption of power, or other reasons, ade-quate supervision shall be provided to sound at least a localtrouble alarm when the system is disabled.

    5-3.1.3 Where building fire alarm facilities are provided, actu-ation of the fire detection or fire extinguishing system shallcause the building alarm to sound.

    5-3.2 Every automatic fire alarm or fire extinguishing systemrequired by this standard shall be continuously maintained inreliable operating condition at all times.

    5-3.3 Automatic fire sprinkler systems and standpipe systemsshall be inspected, tested, and maintained in accordance withNFPA 25, Standard for the Inspection, Testing, and Maintenance ofWater-Based Fire Protection Systems.

    5-4 Standpipes. Structures exceeding a height of 50 ft (15.2m) or having parking levels below grade shall have Class Istandpipes conforming to the provisions of NFPA 14, Standardfor the Installation of Standpipe and Hose Systems.

    Exception: In open parking structures of any height, Class I standpipesystems of the manual dry type shall be permitted.

    5-5* Employee Instruction. Employees of all parking struc-tures shall be instructed with respect to the importance oftransmitting fire alarms promptly and shall be trained in theuse of available private fire-fighting equipment.

    Chapter 6 Referenced Publications

    6-1 The following documents or portions thereof are refer-enced within this standard as mandatory requirements andshall be considered part of the requirements of this standard.The edition indicated for each referenced mandatory docu-ment is the current edition as of the date of the NFPA issuanceof this standard. Some of these mandatory documents mightalso be referenced in this standard for specific informationalpurposes and, therefore, are also listed in Appendix B.

    6-1.1 NFPA Publications. National Fire Protection Associa-tion, 1 Batterymarch Park, P.O. Box 9101, Quincy, MA 02269-9101.

    NFPA 13, Standard for the Installation of Sprinkler Systems,1996 edition.

    NFPA 14, Standard for the Installation of Standpipe and HoseSystems, 1996 edition.

    NFPA 25, Standard for the Inspection, Testing, and Maintenanceof Water-Based Fire Protection Systems, 1998 edition.

    NFPA 30, Flammable and Combustible Liquids Code, 1996 edi-tion.

    NFPA 30A, Automotive and Marine Service Station Code , 1996edition.

    NFPA 31, Standard for the Installation of Oil-Burning Equip-ment, 1997 edition.1998 Edition

  • INDEX 88A7NFPA 52, Compressed Natural Gas (CNG) Vehicular Fuel Sys-tems Code, 1998 edition.

    NFPA 54, National Fuel Gas Code, 1996 edition.NFPA 57, Standard for Liquefied Natural Gas (LNG) Vehicular

    Fuel Systems, 1996 edition.NFPA 58, Liquefied Petroleum Gas Code, 1998 edition.NFPA 70, National Electrical Code, 1999 edition.NFPA 72, National Fire Alarm Code, 1996 edition.NFPA 80, Standard for Fire Doors and Fire Windows, 1995 edi-

    tion.NFPA 90A, Standard for the Installation of Air Conditioning

    and Ventilating Systems, 1996 edition.NFPA 101, Life Safety Code, 1997 edition.NFPA 211, Standard for Chimneys, Fireplaces, Vents, and Solid

    Fuel-Burning Appliances, 1996 edition.NFPA 220, Standard on Types of Building Construction, 1995

    edition.

    Appendix A Explanatory Material

    Appendix A is not a part of the requirements of this NFPA docu-ment but is included for informational purposes only. This appendixcontains explanatory material, numbered to correspond with the appli-cable text paragraphs.

    A-2-1 Approved. The National Fire Protection Associationdoes not approve, inspect, or certify any installations, proce-dures, equipment, or materials; nor does it approve or evalu-ate testing laboratories. In determining the acceptability ofinstallations, procedures, equipment, or materials, the author-ity having jurisdiction may base acceptance on compliancewith NFPA or other appropriate standards. In the absence ofsuch standards, said authority may require evidence of properinstallation, procedure, or use. The authority having jurisdic-tion may also refer to the listings or labeling practices of anorganization that is concerned with product evaluations and isthus in a position to determine compliance with appropriatestandards for the current production of listed items.

    A-2-1 Authority Having Jurisdiction. The phrase authorityhaving jurisdiction is used in NFPA documents in a broadmanner, since jurisdictions and approval agencies vary, as dotheir responsibilities. Where public safety is primary, theauthority having jurisdiction may be a federal, state, local, orother regional department or individual such as a fire chief;fire marshal; chief of a fire prevention bureau, labor depart-ment, or health department; building official; electricalinspector; or others having statutory authority. For insurancepurposes, an insurance inspection department, rating bureau,

    or other insurance company representative may be the author-ity having jurisdiction. In many circumstances, the propertyowner or his or her designated agent assumes the role of theauthority having jurisdiction; at government installations, thecommanding officer or departmental official may be theauthority having jurisdiction.

    A-2-1 Listed. The means for identifying listed equipmentmay vary for each organization concerned with product evalu-ation; some organizations do not recognize equipment aslisted unless it is also labeled. The authority having jurisdictionshould utilize the system employed by the listing organizationto identify a listed product.

    A-3-1.1 Building codes generally contain provisions limitingthe heights and areas of parking structures of various types ofconstruction.

    A-3-1.3 See NFPA 220, Standard on Types of Building Construc-tion.

    A-3-3.1.2 Asphalt pavement applied over earth substrates is anacceptable method of surfacing.

    A-4-3.2 This ventilation requirement is also intended toaddress vehicles that use natural gas [compressed natural gas(CNG), or liquefied natural gas (LNG)]. A natural gas leakshould pose no greater risk than leaks of conventional motorfuels.

    A-5-5 Parking structures that are not within the protectionarea of an organized public fire department should have a firebrigade that is organized, equipped, and drilled in accordancewith NFPA 600, Standard on Industrial Fire Brigades.

    Appendix B Referenced Publications

    B-1 The following documents or portions thereof are refer-enced within this standard for informational purposes onlyand are thus not considered part of the requirements of thisstandard unless also listed in Chapter 6. The edition indicatedhere for each reference is the current edition as of the date ofthe NFPA issuance of this standard.

    B-1.1 NFPA Publications. National Fire Protection Associa-tion, 1 Batterymarch Park, P.O. Box 9101, Quincy, MA 02269-9101.

    NFPA 220, Standard on Types of Building Construction, 1995edition.

    NFPA 600, Standard on Industrial Fire Brigades, 1996 edition.

    Index

    1998 National Fire Protection Association. All Rights Reserved.

    The copyright in this index is separate and distinct from the copyright in the document which it indexes. The licensing provisio ns set forth forthe document are not applicable to this index. This index may not be reproduced in whole or in part by any means without the exp ress writtenpermission of the National Fire Protection Association, Inc.

    -A-

    Alarm systems . . . . . . . . . . . . . . . . . . . . . . . see Fire detection systems

    Approved (definition). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1, A-2-1

    Authority having jurisdiction (definition) . . . . . . . . . . . . . . . .2-1, A-2-1

    -B-

    Basement and underground parking structuresConstruction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-1.2Definition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1Sprinkler systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-1.4Standpipe systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-41998 Edition

  • 88A8 PARKING STRUCTURES

    -C-

    Construction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Chap. 3, A-3

    -D-

    Definitions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Chap. 2, A-2-1Dispensing equipment, flammable liquid . . . . . . . . . . . . . . . . . . . 4-4.2Doors, fire . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5.1

    -N-

    Natural gas, vehicles using . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-4-3.2

    -O-

    Oil-soaked waste and cloths . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-5.4Open parking structuresDrains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3.2Ducts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5.2

    -E-

    Electrical equipment and wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1Employees, fire instruction for . . . . . . . . . . . . . . . . . . . . . . . . 5-5, A-5-5Enclosed parking structures

    Construction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1.2Definition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-1Fire protection systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1.4, 5-2Ventilation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3.2, 5-2(b), A-4-3.2

    Equivalency to standard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3Exterior walls, openings in . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7.3(b)

    -F-

    Fire brigades . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-5-5Fire detection systems . . . . . . . . . . . . . . . . . . . . . . . . 3-6(b), 5-2 to 5-3Fire doors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5.1Fire protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Chap. 5, A-5-5Fire walls and partitions, openings in . . . . . . . . . . . . . . . . . . . . . . . . 3-5Flammable liquids, storage and handling of . . . . . . . . . . . . . . . . . . . 4-4Floors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-3, 4-5.6

    -H-

    Hazards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Chap. 4, A-4-3.2Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-2Height and area of structures . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7.2Housekeeping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-5

    -I-

    Internal subdivisions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2

    -L-

    Labeled (definition) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1Lighting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-1Listed (definition). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-1, A-2-1Lockers, employee . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5.3LP-Gas, storage and handling of . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4

    -M-

    Maintenance, fire detection and extinguishing systems . . . . . . . . . . 5-3Means of egress. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-4

    Construction . . . . . . . . . . . . . . . . . . . . . . . 3-1.2 to 3-1.3, 3-7, A-3-1.3Definition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1Standpipe systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4

    OpeningsFire walls and partitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5Open parking structures, walls of. . . . . . . . . . . . . . . . . . . . . 3-7.3(b)Vertical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6

    -P-

    Parking structures. . . . . . . . . . . . . . see also specific type such as Open parking structures

    Definition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1Purpose of standard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2

    -R-

    Ramps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6Referenced publications . . . . . . . . . . . . . . . . . . . . . . . .Chap. 6, App. BRetroactivity of standard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4

    -S-

    Scope of standard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1Smoke removal systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2Sprinkler systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6(a), 5-1 to 5-3Standpipes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-3.3Storage garages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-1.4Subdivisions, internal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2Supervision, fire detection and extinguishing systems . . . . . . . . . . 5-3

    -T-

    Trash, combustible. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-5.5

    -U-

    Underground parking structures . . . . see Basement and underground parking structures

    -V-

    Ventilation systems . . . . . . . . . . . . . . . . . . . . 3-6(b), 4-3, 5-2(b), A-4-3.2Vertical openings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-61998 Edition C-E

    Chapter1 General1-1 Scope.1-2 Purpose.1-3 Equivalency.1-4 Retroactivity.

    Chapter2 Definitions2-1 Definitions.

    Chapter3 Construction3-1 General Requirements.3-2 Internal Subdivision.3-3 Floors.3-4 Means of Egress.3-5 Openings in Fire Walls and Fire Partitions3-6 Vertical Openings in Enclosed Parking Structures.3-7 Open Parking Structures.

    Chapter4 Hazards4-1 Lighting and Power.4-2 Heating.4-3 Ventilation.4-4 Storage and Handling of Flammable Liquids and Liquefied Petroleum Gas and Natural Gas.4-5 Housekeeping.

    Chapter5 Protection5-1 Automatic Sprinkler Systems, Fire Alarm Systems, and Signaling Systems.5-2 Automatic Sprinkler Systems or Fire Detection and Smoke Removal.5-3 Maintenance and Supervision of Fire Detection and Fire- Extinguishing Systems.5-4 Standpipes.5-5 *Employee Instruction.

    Chapter6 Referenced Publications6-1 The following documents or portions thereof are referenced within this standard as mandatory...

    Appendix A Explanatory MaterialAppendix B Referenced PublicationsIndex