newwtx2[1].4 02 digital microwave system
TRANSCRIPT
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 1/125
WTX2.4-02Digital Microwave System
Dec. 8, 06
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 2/125
Table of contents
A. Foreword .. .................................................................................................................. 6
1 - Structure of manual.. .................................................................................................... 7
2 - Safety instructions.. ...................................................................................................... 7
3 - List of abbreviations .. ................................................................................................... 9
B. Description ... ............................................................................................................ 10
1 - General description... .................................................................................................. 11
2 - Feature ... .................................................................................................................... 11
3 - System Configuration... .............................................................................................. 12
3.1 - RF channel frequency arrangement ... ................................................ 12
3.2 - Unprotected Configuration... ............................................................... 12
4 - Description of units ... ................................................................................................. 13
4.1 - The Modem Unit ... .............................................................................. 13
4.2 - The Transceiver Unit... ........................................................................ 16
5 - Technical Parameters... .............................................................................................. 19
5.1 - System Transmitter... .......................................................................... 19
5.2 - System Receiver... .............................................................................. 19
5.3 - Radio branch system... ....................................................................... 19
5.4 - Base-band Interface ... ........................................................................ 20
5.5 - Auxiliary interface (optional)... ............................................................. 20
5.6 - Alarm And Remote Alarm... ................................................................. 20
5.7 - Power ... .............................................................................................. 20
5.8 - Environmental Condition... .................................................................. 21
5.9 - Dimension... ........................................................................................ 21
5.10 - MTBF... ............................................................................................. 21
C. Installation... ............................................................................................................. 24
1 - Delivery... ................................................................................................................... 25
1.1 - Checking the configuration ... .............................................................. 25
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 3/125
1.2 - Labels on the boxes... ......................................................................... 25
1.3 - Storage ... ............................................................................................ 26
1.4 - Before Installation Task List ... ............................................................. 26
2 - Indoor part installation... ............................................................................................. 30
2.1 - Installation ... ....................................................................................... 30
2.2 - Unpacking... ........................................................................................ 31
2.3 - Installation The Equipment ... .............................................................. 32
2.4 -Signal lines ... ....................................................................................... 36
3 - Outdoor part installation ... .......................................................................................... 42
3.1 - Antenna installation... .......................................................................... 42
3.2 - Antenna connection ... ......................................................................... 44
3.3 - Transmission Line Installation... .......................................................... 45
3.4 - Equipment grounding... ....................................................................... 47
4 - System testing ... ........................................................................................................ 48
4.1 - Testing ... ............................................................................................. 48
4.2 - BER (Bit Error Rate) testing... ............................................................. 51
D. Operation and configuration... .................................................................................. 52
1 - Instruction ... ............................................................................................................... 53
1.1 - Note... ................................................................................................. 53
1.2 - Equipment front panel Instruction ... .................................................... 54
1.3 - Standby page... ................................................................................... 56
2 - Menu operation... ....................................................................................................... 57
2.1 - Introduction... ...................................................................................... 57
2.2 - State Menu ... ...................................................................................... 58
2.3 - Setup Menu ... ..................................................................................... 73
3 - Menu structure ... ........................................................................................................ 85
E. Maintenance... .......................................................................................................... 86
1 - Preventive Maintenance ... ......................................................................................... 87
1.1 - Routine Maintenance... ....................................................................... 87
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 4/125
1.2 - Routine Checking Of Operation Conditions ... ..................................... 87
1.3 -Test on the measurement point ... ........................................................ 87
1.4 -The supervision ... ................................................................................ 87
1.5 - Keeping maintenance log ... ................................................................ 88
2 - Corrective maintenance ... .......................................................................................... 88
3 - Analyzing Modem Unit alarm indicators ... .................................................................. 88
3.1 - Using the LCD on Modem Unit to trace alarms ... ............................... 89
3.2 - Using the LCD on MODEM Unit to trace alarms... .............................. 91
4 - System Troubleshooting and maintenance ... ............................................................. 94
4.1- Tx Troubleshooting and maintenance:... .............................................. 94
4.2 - RX troubleshooting and maintenance... .............................................. 97
4.2 - RX troubleshooting and maintenance... .............................................. 98
4.3 - E1 I/O interface troubleshooting and maintenance:.... ...................... 101
4.4 - Troubleshooting and maintenance of monitor and display keyboard 102
4.4 - Troubleshooting and maintenance of monitor and display keyboard 102
5 - 2.4GHz Transceiver Unit troubleshooting and maintenance ..................... ............... 105
5.1 - Power troubleshooting and maintenance..........................................105
5.2 - Troubleshooting and maintenance of display and inspection............ 106
5.3 - Tx troubleshooting and maintenance................................................109
5.4 - Troubleshooting and maintenance of no Rx gain.............................. 110
5.5 - Troubleshooting and maintenance of LO in trouble .......................... 112
6 - Troubleshooting and maintenance of Modem Unit....................................................113
6.1 - ALM analysis .................................................................................... 113
6.2 - Troubleshooting and maintenance of IF Tx alarm (TIF [ALM]).......... 115
6.3 - Troubleshooting and maintenance of 2M code input alarm IN1~4
[ ALM] .................................................................................................... 116
6.4 - Troubleshooting and maintenance of Rx IF alarm (RIF [ALM]) ...... 116
6.5 - Troubleshooting and maintenance of Rx de-modulation alarm (SYN
[ALM] / FLS [ALM])................................................................................. 117
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 5/125
6.6 - Troubleshooting and maintenance of EOW ...................................... 119
6.7 - Troubleshooting and maintenance of display and monitoring........... 120
F. Service ................................................................................................................... 121
1 - TECHNICAL SUPPORT......................... ..................... ...................... ..................... .. 122
2 - WARRANTY ............................................................................................................ 123
Appendix 1 - List of application alarms...................... ..................... ...................... ......... 124
Appendix 2 - RX/TX level and Voltage corresponding graph ..................... ................... 125
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 6/125
A. Foreword
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 7/125
1 - Structure of manual
This manual provides for users a sound knowledge of how to operate and install
microwave links.
With it, you should quickly be able to operate the equipment. It is not intended to replace
the training services that we provide for your particular needs.
The manual is divided into seven sections followed by appendixes and index.
Foreword
Description
Installation
Operation and configuration
Maintenance
Service
Appendixes
2 - Safety instructions
2.1 - General rules
The following general safety precautions must be observed by the installer and the
operator. We assume no liability for the customer’s failure to comply with these
requirements.
Ground the equipment: for safety equipment, ground the equipment by joining the
station ground wire to the equipment ground terminal.
Do not operation the equipment in an explosive, dusty, dankish and heavy airflow
atmosphere or in presence of flammable gasses or fumes.For protection against fire: make use of fuse of the same current rating and type.
Dangerous voltages: users must not remove equipment covers or shields. The
installation and maintenance procedures described in this manual are for use by
service-trained personnel only.
Do not operate equipment in the way which may make the equipment damaged:
Ensure to return back to the standby page after completion of operation.
User’s operation is limited to [1.T/R State] and [2.M/D State]. Other items are set
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 8/125
by the technician or the manufacture. To ensure normal operation of the
equipment, please do not do any change.
Whenever it is possible that the safety protection features built into this equipment
have been impaired, isolate from the power supply and do not use the
equipment until safe operation will be verified by service-trained personnel. If
necessary, return the equipment to the manufacturer for service or repair.
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 9/125
3 - List of abbreviations
MNEMONIC ENGLISH MNEMONIC ENGLISH
AGC Automatic Gain Control HDB3High Density Binary 3
Code
ALC Automatic Level Control
FEC Forward Error Correction LED Light Emitting Diode
BER Bit Error Rate IF Intermediate frequency
QPSKQuadrature Phase Shift
KeyingRF Radio Frequency
LO Local Oscillator TX Transmitter
RX Receiver FD Frequency Diversity
SD Space Diversity T/R State Transceiver Unit state
EOW Engineering Order Wire Rx State Receiver state
M/D State Modem Unit state
TX State Transmitter state
EOW SetupEngineering order wire
number SetupH High power
CAP Setup Capacity Setup L Low power
M Medium power T Capacity 3E1
Q Capacity 4E1 S Capacity 1E1
D Capacity 2E1
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 10/125
B. Description
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 11/125
1 - General description
WTX2.4-02 is a family of digital point-to-point microwave radio system, designed to
satisfy various digital transmission needs of public and private networks for a large range
of applications.
WTX2.4-02 family covers the frequency range from 2300 2500MHz
It covers the following capacity:
1×2Mb/s 2×2Mb/s 4×2Mb/s
It is today used worldwide in:
Cellular networks
Fixed access networks for Public Telecom, including:
Infrastructure of Wireless IP networks
Direct complementary point-to–point access in LMDS networks
Private networks
Utility networks. Security/Defense networks
2 - Feature
QPSK Modulation and coherent demodulation.
The spectrum efficiency is optimized with the use of QPSK modulation with
digital filtering.
The modulation-demodulation (Modem Unit) with forward error correction (FEC)
to improve the availability and quality of the radio link.
A comprehensive supervision is also available to monitor the radio link
operation and its maintenance.
Transceiver unit is divided into several separated modules. such as frequency
synthesize oscillator, power amplifier, high quality LNA (low noise amplifier) andTX-Rx mixer, etc.
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 12/125
The Modem Unit is designed with the use of a large number of large-scale
integrated circuits and FPGA devices. The performance and reliability is
furthermore increased by it.
WTX2.4-02 is fully compliant with the international requirements (ITU-R) and
national regulations. Including 2Mb/s interface, spurious emissions, etc.
Small dimensions of the 19´–1U for Transceiver Unit and Modem Unit allows for
easy installation and maintenance in standard 19´racks, and save a lot of
space.
A 64kbit/s digital service telephone channel, interface as RJ11 (two-wire)
3 - System Configuration
3.1 - RF channel frequency arrangement
RF channel frequency arrangement of WTX2.4-02 is compliant with the international
requirements (CCIR, REC.933), the frequency arrangement list is hereafter. Please
consult factory for other frequency arrangement requested.
Frequency
Range
(MHz)
Max.
Capacity
(Mb/s)
Central
frequency
(MHz)
Channel
numbersTX/Rx separations (MHz)
2300~2500 4×2.048 2394 20 94
f t =f 0-90+4n
f r =f 0+4+4n
f t /f r :RF transmitter frequency/RF receiver frequency
f 0: central frequency 2394MHz
n: channel
3.2 - Unprotected Configuration
WTX2.4-02 unprotected (1+0) radio terminal is made up of the following elements.
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 13/125
Elements Quantity
Transceiver Unit 1
Modem Unit 1
4 - Description of units
4.1 - The Modem Unit
4.1.1 - The Modem Unit consists of the following sub unit (refer to Figure 2 )
Multiplex/demultiplex
Bit insertion/extractor
FEC code/decode
QPSK modulator/demodulator
Display, control and communication
Power supply
4.1.2 - Service bit including
One 64kbit/s signal for EOW
One 64kbit/s signal provides users with low speed data channel (optional).
4.1.3 - Description of Function
Modem Unit change base band signals and auxiliary data signals from exchanger or
digital terminal into combined serial signals by multiplex, these combined signals forms
Modem
UnitE1 I/O
Transceiver
Unit
Figure 1 Block diagram of 1+0
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 14/125
I,Q parallel signals and clocks after FEC coded and thus to complete QPSK modulation.
Transceiver Unit converts the microwave signals back to QPSK signals. QPSK signals
are sent to Modem Unit through IF cable and then are demodulated into I, Q signals, the
clock is also recovered. The IF Modem Unit recovers serial combined signals after
finishing decoding these signals respectively into 1×2Mb/s, 2×2Mb/s, 4×2Mb/s
base-band signals and auxiliary data according different signals, and changes them back
again into standard base-band signals to output.
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 15/125
Figure 2 Block diagram of Modem Unit
Multiplex Bit Insertion FEC code QPSKModulator
IF
Demultiplex Bit Extractor FEC decode
n×E1input...
Powersupply
12V
5V
48V LCD Display and Control
3× 64kb/s service bit n×E1 output...
12V
QPDe
I
Q
I
Q
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 16/125
4.2 - The Transceiver Unit
4.2.1 - The Transceiver Unit consists of the following sub unit (refer to Fig 7)
Transmitter:
TX amplifier
TX local oscillator
Up-converter(mixed)
Single-band filter
Power amplifier
TX channel filter
Receiver
RX channel filter
LNA
Single-band filter
Down-converter(mixed)
Rx IF Amplifier
AGC
Rx local oscillator
4.2.2 – function description
The TX IF from the Modem Unit is up –converted in order to provide the final transmission
frequency. The output power is continuously monitored through the control and fed to the
modem Unit.
The microwave signal from the modem Unit is amplified at first, through a LNA and then is
down-converted. The resulting IF is amplified and is finally fed to the Modem Unit.
When the TX IF signal from the Modem Unit loses, the centre frequency of RF will export
from RF port.
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 17/125
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 18/125
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 19/125
19
5 - Technical Parameters
5.1 - System Transmitter
Output power: +17 +26dBm adjustable (accuracy ±1dBm)
IF frequency: 70MHz ± 7KHz
IF input signal level: 0dBm ±1dBm
Modulation mode: QPSK
Error correction coding: k=7 3/4 mode
Tx local oscillator frequency stability ≤ ±10 ppm
Spurious emission: ≤ -30 dBm
5.2 - System Receiver
Noise figure: ≤ 3dB (from Receiver input)
Normal receiver signal level: -40dBm
Threshold: ≤ -86 dBm (error rate 1×10 -6)
IF frequency: 70MHz
IF output level: 0 dBm±1dBm AGC dynamic range:>50dB( -35 -86dBm)
Modulation mode: DCQPSK
Error correction coding: FEC coding
Rx local oscillator stability: ≤ ±10 ppm
5.3 - Radio branch system
Antenna, feeder interface: N type (female)
Impedance: 50 Ω
Return loss:>17dB
Direction insertion loss: ≤ 3dB (f o ± 8.5MHz)
Branch filter: 7-resonator ceramic filter
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 20/125
20
5.4 - Base-band Interface
Capacity: 1×2048kb/s, 2×2048kb/s, 4×2048kb/s
Frequency tolerance: ± 50 ppm
Line code shape: HDB3
Interface characteristics: impedance, level, code type compliance with
ITU-TG.703
Jitter characteristics compliance with ITU-TG.823 G.921
Cable length allowed: 0 150m
Socket: DB25 or BNC
5.5 - Auxiliary interface (optional)
Data interface: RS232
Data rate: 2.4kb/s, 4.8kb/s, 9.6kb/s, 19.2kb/s
EOW(Engineering Order Wire) interface: RJ11
EOW: 64kb/s PCM mode
EOW: dialing for sel-call mode
Subscriber line extension interface
Center order terminal is connected directly to with exchanger
Subscriber terminal is connected to telephone
Ethernet data interface: 10 BASE, rate 1.92Mbps
Operational mode: occupies an E1 interface (selectable from 1 to 4 E1)
5.6 - Alarm And Remote Alarm
Alarm led
Alarm led illuminating indicates local equipment generating alarm signals.
Remote alarm led
Illuminating indicates remote equipment generating alarm signals.
5.7 - Power Input voltage: -48V DC (allowed variation range -36 -72 V DC )
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 21/125
21
Modem Unit output voltage: +5V, +12V, -12V
Transceiver Unit output voltage: +12V, -12V
Switching output voltage: +12V, +5V, -5V
Consumption: 35W
5.8 - Environmental Condition
Working temperature:
5 40ºC : All technical index are guaranteed
0 45ºC : Normal operation is guaranteed.
Storage temperature: -40 +55ºC
Relative humidity: no more than 85%
Note: Storage area must be well ventilated, dry, without erosion gas
5.9 - Dimension
Modem Unit, Transceiver Unit dimension:
Width × high × length =482.6mm (19’) × 44.45mm × 320mm
5.10 - MTBF
MTBF ≥ 100000 hours
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 22/125
22
Digital Microwave Radio System Hs
No Item Specs
1 operation frequency range 2300 to 2500MHz
2 Tx/Rx local frequency stability ±10ppm3 output power typical >25 dBm
4 system gain 111dB5 RF input level typical -40dBm6 AGC dynamic range More than 50dB -35~-86 dBm 7 transmission capacity 4×2.048mbps8 Demodulation Coherent demodulation
9
base-band interfacebit rate
interface codesignal levelimpedance
ITU-T G.7032.048mbps ±50ppm
HDB3VO-P =2.37V75 ohm unbalanced
10 service channel 1 EOW 2-WIRE
11
voice frequency channelfrequency bandoutput leveloutput impedance
ITU-T G7120.3 to 3.4KHz-6dBm~-35.5dBm600 ohm, balanced
12 measurement points
Tx powerRX level (Indication range: -35dBm~-86dBm)Tx local oscillatorRx local oscillatorIntermediate Frequency 70MHz±20ppm(BNC)
13 channel space 8MHz14 Branch filter parameters refer to Figure 4 15 Intermediate Frequency 70MHz16 IF level 0dBm±1dB17 Threshold -86dBm BER ≤ 1×10 -6
18 power supply -48VDC(-36 to -72VDC)
19 power consumption Approx 100w (1 station HS configuration)
20
temperature rangeguaranteed operationworkable operationtransport and storage
5 +40 -5 +45 -25 +55
21
relative humidityguaranteed operation
workable operationtransport and storage
Less than 90% at +45
Less than 90% at +50 Less than 90% at +50
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 23/125
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 24/125
24
C. Installation
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 25/125
25
1 - Delivery
When you receive the equipment in its packaging:
Check the condition of the packaging.
If damaged, make your reservations known to the carrier as quickly as possible.
1.1 - Checking the configuration
As a rule, the packaging of equipment is
The hop equipment is enclosed in the wooden boxes, in other words, two paper
boxes enclosed; one end equipment is enclosed in each paper box. The materialness is
as following:
No. Item Quantity
1 Modem 1
2 Transceiver 1
3 E1 I/O cable kit 1
4 Power connector kit 15 Fuse 3 6 IF connection 2 7 50 Ω cable (N) 18 Telephone Set 19 Technical handbook 1
10 Test report 1
1.2 - Labels on the boxes
TRANSCEIVER UNIT
TX 2418MHz RX 2324MHz
CHANNEL 09 NO. R
(2)(1)
(3) (4)
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 26/125
26
(1) TX Frequency of the Transceiver Unit
(2) RX Frequency of the Transceiver Unit
(3) Channel of the Transceiver Unit
(4) Serial number of the equipment
1.3 - Storage
If installation is to be deferred, the type of packaging will define the equipment storage
conditions:
Cardboard boxes should be warehoused indoors, in a dry, well aired room.
Wooden or plywood boxes may be stored outdoors, provided that they are protected
from rain and the sun’s rays.
1.4 - Before Installation Task List
There are several tasks that should be accomplished prior to installing the system. This
section briefly describes the following:
- Site selection
- Line-of-sight and path clearance determination
- Anticipated RSL calculation
- Fade margin calculation
- Availability calculation
- Frequency plan determination
- Power supply planning- Antenna purchase
DESCRIPTION No. QTY
Modem M 1
Transceiver R 1
Appendix 1
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 27/125
27
NOTE:
Only directional antennas should be used with the system. These can be grid or solid
parabolic antennas (minimum 2 foot – 0.6 meter). Flat panel antennas are also acceptable
if the beam width is kept to a minimum.
1.4.1 –Site Selection Requirements
The system site must have:
- Access to the appropriate power
- Close proximity to the telephone you wish to interconnect
- Line-of-sight to the other location with adequate clearance
- Location for mounting the antennas
1.4.2 – line-of –sight and path clearance guidelines
The system will not operate properly unless they have line-of-sight between their
corresponding antennas. The transmission will not pass through trees or other obstacles.
Factors to consider include:
- Earth curvature
- Future growth of trees
- Height of building
In addition to the line-of-sight requirement, a well-engineered path will also have
additional path clearance to allow for signal loss due to patial obstructions, atmospheric
ducting and ground reflections. To maximize radio reception, 0.6 times the first Fresnel
zone should be calculated and this distance added to the path clearance (in addition to or
buildings).
1.4.3 – RSL calculation and link budget
The received signal level (RSL) can be estimated using the following formula:RSL(dBm) = P out – FL 1+G 1+G 2 – FL 2 - Lp
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 28/125
28
Where: P out is the transmitter output power ( in dBm)
FL1 is the feeder loss of the transmit side ( in dB)
G1 is the gain of the transmit antenna ( in dB)
G2 is the gain of the receive antenna ( in dB)
FL2 is the feeder loss of the receive side ( in dB)
Lp is the path loss, defined by:
Lp(dB)=96.6 + 20log 10 F + 20 log 10 D
Where: F = frequency in GHz
D = distance of path in miles
The link budget is very important for determining any potential problems during
installations. If you have calculated the expected RSL, you can see if it has been achieved
during installation, and troubleshoot if necessary.
1.4.4 – Fade Margin Calculation
The fade margin is the difference between the actual received signal and the system’s
threshold. Using the formula provided in section 1.4.3, the anticipated RSL can be
calculated. Compare this RSL to the specified threshold of the system and calculate the
fade margin as the difference between the two signal levels.
Dispersive fade margin is another factor that many microwave path engineers may use to
plan their link budget. For the system, the dispersive fade margin is in excess of 45dB and
therefore is not a determining factor in path planning. This excellent dispersive fade
margin performance is important because the RF signal has considerably wide bandwidth.
1.4.5 – Availability Calculation
Availability of the microwave path is the measure of the time that the link will operate
without producing an excessive BER due to multipath fading. In the absence of direct
interference, availability is affected by the following:- Path length
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 29/125
29
- Fade margin
- Frequency
- Terrain (smooth, average, mountainous)
- Climate (dry, temperate, hot/humid)
Depending on the type of traffic carried over the link, the system designer may wish to
design for a specific availability. For example, if the data or voice traffic that is carried by
the radio is critical then it may be designed for a very high availability. To improve
availability, for example, the fade margin can be increased by making the path shorter, or
by using higher gain antennas in conjunction with lower loss feeders(by using high quality
transmission line or shortening feed length).
1.4.6 – Frequency plan determination
When configuring system in a hub or repeater configuration, careful engineering of the
system frequency plans and antenna locations should be performed in order to minimize
potential interference between the nearby systems. As a rule of thumb, do not place
identical frequency plan system (e.g. two “A” channel systems) at the same site. In most
cases, it is desirable to use a different frequency plan (e.g. A versus B). However, with
careful engineering, placing more than one system of the same frequency channel plan at
the same site can be accomplished. In fact, the frequency plan is designed to allow
complex hub configurations that may require reusing the same frequency plan. When
designing these types of configurations, antenna size and antenna location are critical. If
Identical channel plans must be used at the same site, the system channel (e.g. A1 and
A2) should be used at a site to minimize interference. Using alternate channels (e.g. A1
and A2) is less likely to be successful (and therefore not recommended) due to the high
level of transmitter to receiver isolation required from the antenna system.
1.4.7 – Power Supply Planning
The system must have access to a supply of appropriate power. Typically negative ground48 volt supply is used. For DC, be sure the cable is of sufficient gauge to carry the
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 30/125
30
necessary current.
Before installing the system, plan for the continuous power consumption needs in
accordance with the specifications. It is also wise to plan for backup power for critical
communication circuits (including the system). Backup power allows the system and
associated equipment to continue operation when primary power is interrupted.
1.4.8 – Antenna Planning
Using the path planning tools, proper antenna size can be determined which will yield the
desired path performance. In general, the larger the antenna that is used with the system,
the better the link will perform. Larger antennas have narrower beamwidth and higher gain,
which will yield better link performance (higher fade margin, better availability) and
improve immunity to interference (due to the smaller beamwidths). However, larger
antennas are more costly to purchase and difficultly install than smaller antennas, in some
cases requiring special equipment for installation. All of these factors should be taken into
consideration when selecting antennas.
2 - Indoor part installation
The following tools may be required for the installation:- Cross tip screwdriver- Small spanner- Big spanner
- Digital Voltmeter
2.1 - Installation
Installation work begins with unpacking and should follow the steps blow.
Step 1. Unpacking
Step 2. Installing the equipment
Step 3. Connecting the cables
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 31/125
31
2.2 - Unpacking
2.2.1 -Check the shipment container for damage, if not, put up unpacking, pay
attention not to damage the contents or the container.
2.2.2 -Checking The Contents
When unpacking, check each of the contents against the packing list to find missing or
damaged components, keep shipment container for possible re-use until all the contents
are checked to be in satisfactory conditions.
2.2.3 - Labels on the equipment
2.2.3.1 - Labels on the Transceiver Unit
(1) Name of the equipment
(2) TX Frequency of the Transceiver Unit
(3) RX Frequency of the Transceiver Unit
(4) Channel of the Transceiver Unit
(5) Serial number of the equipment
R 009
R: Transceiver Serial number of
the equipment
TRANSCEIVER UNIT
TX 2418MHz RX 2324MHz
CHANNEL 09 NO. R009
(1)
(4)
(2) (3)
(5)
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 32/125
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 33/125
33
rack-mount-brackets on both side of the main body cabinet, using the cabinet mounting
bows, then, install the equipment on the rack.
2.3.2.1-Rack installation sketch: including M8 bolt, Ф 8 nut Ф 8 spring washer Ф 8 flat
washer( see the following figure), upper bracket lower bracket column
2.3.2.2 - The equipment mounting pole installation sketch
Mounting pole is installed on right and left side of equipment, see the following figure:
M8 bolt
Ф8 nutФ8 spring washerФ8 flat washer
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 34/125
34
Mounting pole is installed at the middle (or front) of right and left side of equipment
according to demand. Recommended installation methods are that it is installed at the
middle of the equipment with M3 bolt .
The equipment is installed on the rack.(see the following figure)
M3 bolt
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 35/125
35
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 36/125
36
2.4 -Signal lines
2.4.1 E1 I/O Cable kit
E1 signal I/O Cable kit is connected with E1 I/O interface on the modem Unit
(connection kit refer to the following page).
Serial number Name
1 Cable SYV-75-2-2
2 Cable socket BNC-KY32Y-1
3 DB25A/M
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 37/125
37
E1 I/O Cable kit DB25A/M Port Pin Assignments
DB25A/M Connector Pin Number Signal Name
1 E1out1
2 GND
3 E1out2
4 GND
5 E1out3
6 GND
7 E1out4
8 GND
9 NC
10 NC
11 NC
12 NC
13 NC
14 E1IN1
15 GND
16 E1IN2
17 GND
18 E1IN3
19 GND
20 E1IN4
21 GND
22 NC
23 NC
24 NC
25 NC
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 38/125
38
connecting with modem unit
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 39/125
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 40/125
40
2.4.3 IF connection: the cable which connects the Modem Unit with the Transceiver
Unit
Serial number Name
1 Cable socket BNC-75J4C
2 Cable SYV-75-2-1
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 41/125
41
2.4.9 EOW telephone handset connection
Note: telephone handset must be connected with the modem unit
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 42/125
42
3 - Outdoor part installation
3.1 - Antenna installation
The antenna installation consists of mounting the antenna on the tower, building roof or
other location that provides line –of sight path clearance to the far location. In general,
antennas smaller than 4 feet diameter are not recommended for urban areas due to their
higher interference susceptibility.
Antennas should be ordered with a suitable mounting kit specific to the site requirements,
for example specifying round or angle tower leg adaptors, or a roof tripod.
If wind-loading may be a problem for an outside mounted antenna, a grid antenna can
reduce the wind load compared to a solid dish, although the antenna discrimination
capability, for example at hub locations, will be degraded. However, vertical vs. horizontal
discrimination, if required, may be improved by using grid antennas.
The antenna must be very rigidly mounted, with adequate room for azimuth and elevation
adjustment.
The antenna polarization must be the same at both ends of the link, either vertical or
horizontal.
In general, antenna mountings require a support pipe to which upper and lower support
brackets are attached with U bolts. The antenna and optional elevation and azimuth
adjustment rods are then mounted onto the support brackets. The whole structure must
be adequately grounded, in case of lightning. The antenna system must always be
installed according to the manufacture’s instructions.
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 43/125
43
Mounting Pole dimension: 76mm or 114mm
76mmor
114mm
Figure 1 Mounting Pole dimension
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 44/125
44
Fitting the top “U bolt” on the 114 mm Ø tube
1) Offer the threaded “U” bolt (M10) item on the 114 mm Ø tube.
2) Fit casting on the bracket.
3) Fit the washers, item and nuts (HM10) item on the threaded bracket.
4) Tighten the nuts using a 17 mm flat wrench and the plate will be distorted.
3.2 - Antenna connection
The equipment is equipped with an N-type female connector at the antenna port,
“ANTENNA” at the rear of the shelf. A jumper cable (or “pigtail”) fitted with two N-type male
connectors should be used to connect the antenna port with the antenna transmission
line.
A low loss 50 ohms cable (for example 1/2 ″, 7/8 ″foam or air coax ) is recommended for the
antenna transmission line between the top of the rack and the antenna. The return loss
presented by the transmission line at the top of the rack should be as possible (20 dB,
minimum recommended). The length of the antenna transmission line should be kept as
short as possible (to minimize losses).
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 45/125
45
Antenna Installation sketch
3.3 - Transmission Line Installation
The co-axial transmission line (cable) may be prepared by first being cut to the
approximate length allowing some excess and an N-type male connector installed on the
antenna end (expect for large or high performance antennas with 7/8 ″EIA flange
U boltsGrid Antenna
Casting
antislip baffle
Plumb pull pole
Feed
Jumper cable
Feeder cable
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 46/125
46
connectors).
The cable is then pulled through the cable ducts, trays or conduit (as required) to the
antenna, while being careful not to kink or damage the cable in any way.
The cable should be supported in a tray on horizontal runs and by hangers on vertical
runs. Hangers should be spaced according to the manufacturer’s instructions.
The cable should be grounded using a special grounding kit that attaches to the outer
copper conductor. Grounds must be installed at the antenna, at the bottom of the tower (if
applicable) and where the transmission line enters the building. Long cable runs should be
grounded every 100 feet. In case of high lighting incidence, lightning dissipaters should be
attached to antennas. In addition, co-axial, in-line, spark-gap type, lightning suppressors
should be added at the bottom of the co-ax cable.
After installation, the cable is terminated with a second N-type male connector attached at
the equipment end.
Prior to operation, the electrical integrity of the cable and connectors can be checked with
a simple DC detector between the center conductor and outer conductor.
The transmission line should ideally be connected directly to the antenna at one end and
to the RF port of the equipment at the other end. However, a jumper cables may be
required to avoid sharp bends in the transmission line or undue stress on the connection.
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 47/125
47
3.4 - Equipment grounding
Feeder grounding; cut the outer layer of the feeder cable about 10cm length, expose themetal part. Connect one end of the grounding kit to the metal part and seal with tape,connect the other end to protected ground.
Necessary only if
D>80m
D
In door
Grounding kit
10cm
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 48/125
48
4 - System testing
4.1 - Testing
4.1.1 –install station A with the antenna facing to station B.
4.1.2 –install station B with its antenna facing to station A.
Check the system is well grounded and the polar are correctly connected before
powering the system. The standby page is displayed as Fig 1
Fig 1
Fig 2 will be displayed on the screen seconds later.
Fig 2
Because the antenna is not fine adjusted, the screen may display ”RX: - LOW” in this
case, the antenna should be readjusted according to level graph.
Transceiver
Modem Unit
Transceiver
Modem Unit
Station A Station B
SYS Initialize
Loading……...
TX: + dBm [NOR]
RX: - dBm [NOR]
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 49/125
49
The procedure of adjustment is as following
1. Connect the red probes of multimeter (set in DC range) to pin 4 of the DB9 head
attached to the equipment. pin 9 is ground.
9
1
6Pin
Pin 1
Pin 6
(voltage) (voltage)
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 50/125
50
The best RX level of the equipment is –40dBm. Recommend to set normal RX
level between –55 ~ -40dBm. The respective RX level can be easily checked out
according to voltage graph.
2. Fix station B antenna, adjust station A antenna, slowly adjust elevation. Observe
AGC voltage while adjusting to make it be optimum. Then adjust azimuth make it
reach maximum. Adjust station B antenna the same way, after antennas are well
adjusted. Look at the LCD screen of the modem Unit and check that if TX power
and RX level indication are normal, if there is any warning on the Modem Unit
panel. When everything is normal, perform bit error test.(refer to Bit Error Test).
After adjusting the antenna, if AGC level is very low, on the LCD screen, RX Low
will be displayed. It may because too much loss of space or blocking space.
Increasing the antenna diameter and TX power may resolve the problem. If there
is blocking object, increase the height of the antenna or change the station
location to avoid to be blocked.
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 51/125
51
4.2 - BER (Bit Error Rate) testing
Bit error rate (BER) testing is the preferred way to evaluate a radio link’s performance. It
can be performed from point -to-point or in loopback mode (which tests both directions of
the radio path). Figure 1 illustrates a typical BER test configuration for loopback testing
(which may include the radio’s path instead of in-line attenuators).
When performing BER testing, make sure of the following step:
a) Connect BER tester to data input/output connector(s).
b) Connect data input/output of the remote equipment with the cable.
Remark: The BER tester pattern must be set up as 2 15-1, and test code must be set
up as HDB3.
Figure 1 Loopback BER Test Configuration
WTX2.4-02 WTX2.4-02
BER tester
RF RF
Antenna Antenna
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 52/125
52
D. Operation and configuration
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 53/125
53
1 - Instruction
1.1 - Note All operations are based on systems work normally without warning. If there is a
warning or abnormality on screen, please refer to the maintenance section.
All legends with under line are defaulted cursor position.
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 54/125
54
1.2 - Equipment front panel Instruction
1.2.1 - Modem Unit front panel
① Power LED: Indicates status of -48VDC on the circuit board. Power LED illuminating
indicates -48VDC is present on the board.
② Power switch: ON means power on the circuit board. OFF means no power.
③ LCD screen
④ EOW: Engineering order wire interface.
⑤ Alarm LED: Alarm LED illuminating indicates LOCAL equipment (including Modem
Unit and RF Transceiver Unit) generating alarm signals.
⑥ RMT Alarm LED: Lighting indicates remote equipment (including Modem Unit and RF
Transceiver Unit) generating alarm signals.
⑦ 70MHz: IF carrier wave (70 MHz±3KHz, 0dBm±1dB).
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 55/125
55
1.2.2 – Transceiver Unit front panel
① Power LED: Indicates status of -48VDC on the circuit board. Power LED illuminating
indicates -48VDC is present on the board.
② Power switch: ON means Power on the circuit board. OFF means no power.
③ TLO: TX local oscillator frequency measurement point (-6dBm±2dB).
④ RLO: RX local oscillator frequency measurement point (-6dBm±2dB).
⑤ DETECT: Detect interface (refer to Appendix 2 ).
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 56/125
56
1.3 - Standby page
After installation by technician, check the system is well grounded, power supply is
correctly connected, then power the system, standby page (Fig 1) will be displayed on the
LCD screen of Modem Unit.
Fig 1
The system is initializing, all system parameters are being loaded, please wait. The
standby page will be displayed seconds later. The following describes different standby
pages according to respective equipment.
1.3.1 - Modem Unit standby page
Fig 2
On this page, present TX value and alarm, RX value and alarm are displayed on the same
link equipment .
1.3.1.1 - Tx and Rx
Tx: Output power of Transceiver Unit.
the normal display range is 17 26 dBm.
If TX value is less than 15 dBm, “TX: loss” is displayed in the first line.
Rx: Receiver signal level of Transceiver Unit.
the normal display range is -35 -86 dBm.
If RX value is less than -88 dBm, “RX: low” is displayed in the second line.
SYS Initialize
Loading……...
Tx: + 25 dBm [NOR]
Rx: - 65 dBm [NOR]
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 57/125
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 58/125
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 59/125
59
Fig 6
Fig 6 indicates Unit has already communicated with the local equipment ( or link), the local
equipment (or link) status including Modem Unit and Transceiver Unit can be checked.
2.2.1 T/R State Menu
The T/R State Menu is used to check TX power, RX level, Tx power alarm and RX level
alarm of the Transceiver Unit, below is the different status of the local equipment (or link).
Put the cursor on “1” of the first line by moving “Right” keys. Then select the “Enter” key to
call up the T/R State Menu , Fig 7 is displayed on the screen.
Fig 7
1. T/R State
2. M/D State
1.1 Tx Level
1.2 Rx Level
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 60/125
60
The T/R State menu includes 4 sub-menus: TX power, RX level, Tx power alarm and RX
level alarm of the Transceiver Unit. Moving the “Up/Down” keys to get the following 4
menus
"1.1 Tx Level "
"1.2 Rx Level "
"1.3 Tx State "
"1.4 Rx State "
2.2.1.1 Tx Level
The menu is used to show the current TX power of the Transceiver Unit. Put the cursor on
the "1.1 Tx Level " by moving the “ Up/Down” keys, then select the “Enter” key to call
up "1.1 Tx Level " menu, Fig 8 is displayed on the screen.
Fig
Fig 8
The screen shows that the current TX power of the Transceiver Unit is 26dBm.
2.2.1.2 Rx Level
The menu shows the current RX level of the Transceiver Unit. Put the cursor on the "1.2
Rx Level " by moving the “ Up/Down” keys, then select the “Enter” key to call up "1.2
Rx Level” menu. Fig 9 is displayed on the screen.
Fig 9
The screen shows that the current RX level of the Transceiver Unit is 65dBm.
Tx Level
26 dBm
Rx Level
65 dBm
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 61/125
61
2.2.1.3 Tx State
The menu shows the current TX power alarm signal of the Transceiver Unit. Put the
cursor on the "1.3 Tx State " by moving the“ Up/Down” keys, then select the “Enter”
key to call up "1.3 Tx State " menu. Fig 10 is displayed on the screen.
Fig 10
The detailed signals see the following table.
The alarm signal may be switched off during test to avoid wrong decision and wrong
operation.
The alarm signals above both have “on” and “off” states. Put the cursor onto the alarm
signals required and press the “Enter” key to call up the page of Fig 12 (for example).
For a instance of “TLO” put the cursor on the first line, then press the “Enter” key to call
up the page of Fig 11.
Fig 11
Name Meaning State
NOR: normalTLO Tx local oscillator alarm
ALM: alarmNOR: normal
TPWTx power alarm, if Tx power is less than4dB of setup value, alarm appears. ALM: alarm
1.3.1 TLO [NOR]
1.3.2 TPW [NOR]
1.3.1 TLO [ On ]
Opt. [ On Off ]
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 62/125
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 63/125
63
2.2.1.4 Rx State
The menu is used to show the current RX level alarm signal of the Transceiver Unit. Put
the cursor on the "1.4 Rx State " by moving the “ Up/Down” keys, then select the
“Enter” key to call up "1.4 Rx State " menu. Fig 15 is displayed on the screen .
Fig 15
The details see the following table.
All signals above have “on” and “off” state. Put the cursor onto the alarm signals required
and press the “Enter” key to call up the page of Fig 16(for example).
Take “ RLO ” as an example put the cursor on the first line, then press the “Enter” key to
call up the page of Fig 17.
Fig 16
The cursor is defaulted on “ On ” of the second line “ Opt. [ On Off ] ”, It may be
selected on “on” or “off” by the “Right” key, and the cursor in the second line will move
accordingly. The brackets in the first line of the screen shows the current switch state of
selected signal, the picture shows the “ RLO ” is turned on, means the “ RLO ” switch is
enable. When signal alarm switch is enable, if signal alarms, the alarm LED willimmediately light on. Please revert back to previous menu, Fig 17 is displayed on the
Name Meaning State
NOR: normalRLO Rx local oscillator alarm
ALM: alarm
NOR: normalRSL
Rx level alarm, if Rx level is less than
-82dBm, alarm appears. ALM: alarm
1.4.1 RLO [NOR]
1.4.2 RSL [NOR]
1.4.1 RLO [ On ]
Opt. [ On Off ]
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 64/125
64
screen.
Fig 17
Now, put the cursor on “Off” by the “Right “key, then press the “Enter” key to close alarm
signal. Fig 18 is displayed on the screen.
Fig 18
Now, signal “ RLO ” is OFF, means the “ RLO ” alarm signal is inhibited,. If there is a “ RIF”
signal alarm, the alarm LED will not light on. Please revert back to previous menus; Fig 19
is displayed on the screen .
Fig 19
1.4.1 RLO [ Off ]
Opt. [ On Off ]
1.4.1 RLO [Off]
1.4.2 RSL [NOR]
1.4.1 RLO [ALM]1.4.2 RSL [NOR]
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 65/125
65
2.2.2 M/D State Menu
The M/D State Menu is used to check alarm signal of the Modem Unit (or link). This
example shows status of the Modem Unit (or link). Put the cursor on the first line by
selecting the “Up/Down” keys, then select the “Enter” key to call up M/D State Menu. Fig
21 is displayed on the screen.
Fig 21
M/D State menu includes two sub-menus: modulate state and demodulate state. See
the following figure.
"2.1 MOD State "
"2.2 DEM State "
2.2.2.1 MOD State
The menu is used to show the current modulation alarm of the Modem Unit.
Put the cursor on the "2.1 MOD State " by moving the “ Up/Down” keys, then select
the “Enter” key to call up "2.1 MOD State " Fig 22 is displayed on the screen.
Fig 22
The details see the following table.
2.1 MOD State
2.2 DEM State
2.1.1 TIF [NOR]
2.1.2 TSL [NOR]
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 66/125
66
All signals above have “on” and “off” states. Put the cursor onto the alarm signals required
and press the “Enter” key to call up the page of Fig 22 (for example).
Take “ TIF” as an example put the cursor on the first line, then press the “Enter” key to
call up the page of Fig 23( for example).
Fig 23
The cursor is defaulted on “ On ” of the second line “ Opt. [ On Off ] ”, It may be
selected “on” or “off” by the “Right” key, and the cursor in the second line will move
accordingly. The brackets in the first line of the screen are showing the current switch
state of the selected signal. On the picture the TIF” is turned on, meaning the switch is
available. When signal alarm switch is enable, if signal alarms, the alarm LED willimmediately light on. Please revert back to previous menu, Fig 24 is displayed on the
Name Meaning State
NOR: normalTIF Tx IF alarm ALM: alarm as described in
section 3.2NOR: normal
TSL Transmitting signal loss ALM: alarm as described insection 3.2
NOR: normal
IN1The first E1 loss alarm. When
capacity is 1E1, the alarm appears ALM: alarm as described in
section 3.2NOR: normal
IN2The second E1 loss alarm. When
capacity is 2E1, the alarm appears ALM: alarm as described in
section 3.2NOR: normal
IN3The third E1 loss alarm. When
capacity is 3E1, the alarm appears ALM: alarm as described in
section 3.2NOR: normal
IN4The fourth E1 loss alarm. When
capacity is 4E1, the alarm appears ALM: alarm as described in
section 3.2
2.1.1 TIF [ On ]
Opt. [ On Off ]
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 67/125
67
screen.
Fig 24
Now, put the cursor on “Off” by the “Right “key, then press the “Enter” key to close alarm
signal. Fig 25 is displayed on the screen.
Fig 25
Now, signal “ TIF” is OFF, means “ TIF” signal alarm is inhibited. If there is a “ TIF” signal
alarm, the LED will not light on. Please revert back to previous menu; Fig 26 is displayed
on the screen.
Fig 26
2.1.1 TIF [ Off ]
Opt. [ On Off ]
2.1.1 TIF [Off]
2.1.2 TSL [NOR]
2.1.1 TIF [ALM]
2.1.2 TSL [NOR]
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 68/125
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 69/125
69
All signals above have “on” and “off” state. Put the cursor onto the alarm signals required
and press the “Enter” key to call up the page of Fig 28( for example).Take “ RIF” as an
example put the cursor on the first line, then press the “Enter” key. Fig 28 is displayed on
the screen.
Fig 28
The cursor is defaulted on “ On ” of the second line “ Opt. [ On Off ] ”, It may be
selected “on” or “off” by the “Right” key, and the cursor in the second line will move
accordingly. The brackets in the first line of the screen shows the current switch state of
the selected signal, on this picture, the “ RIF” is turning on, means the switch is available.
When signal alarm switch is available, if signal alarms, the alarm LED will
immediately light on. Please revert back to previous menu, Fig 29 is displayed on the
screen.
Fig 29
Code Name Meaning State
NOR normal2.2.1 RIF Rx IF alarm ALM: alarm
See maintenance sectionNOR normal
2.2.2 ERR Bit error alarm ALM: alarmSee maintenance section
NOR normal
2.2.3 FLSFrame synchronization loss
alarm ALM: alarm
See maintenance sectionNOR normal
2.2.4 RMTRemote terminal alarm
ALM: alarm
See maintenance section
2.2.1 RIF [ On ]
Opt. [ On Off ]
2.2.1 RIF [ALM]
2.2.2 ERR [NOR]
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 70/125
70
Now, put the cursor on “Off” by the “Right “key, then press the “Enter” key to close alarm
signal. Fig 30 is displayed on the screen.
Fig 30
Signal “ RIF” is OFF, at present means signal “ RIF” alarm is inhibited, If there is a alarm,
the alarm LED will not light on. Please revert back to previous menu; Fig 31 is displayed
on the screen.
Fig 31
2.2.1 RIF [ Off ]
Opt. [ On Off ]
2.2.1 RIF [Off]
2.2.2 ERR [NOR]
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 71/125
71
2.2.3 Remote state operation
If the user wants to select the remote equipment (or link), he can put the cursor on the
second line by moving the “Right” keys and press the “Enter” key to call up the menu.
Please refer to 2.2.3.1 for the detailed operation see the following figure 32.
“>Remote [ ] ”
Fig 32
2.2.3.1 – Requests remote equipment (or link) state.
Put the cursor on the second line by moving the “Right” keys, then press the “Enter” key.
Fig 33 is displayed on the screen.
Fig 33
Fig 33 indicates Unit is communicating with the remote equipment (or link),
Please wait for few seconds, one of the following two figures will be displayed on the
screen.
Fig 34
Fig 34 indicates Unit has already communicated with the remote equipment (or link), the
remote equipment state (including Modem Unit and Transceiver Unit) can be checked.
Refer to section 2.2.1 and 2.2.2 for the rest operation.
>Local [ ]
>Remote [ ]
Remote state
Waiting ………
1. T/R State
2. M/D State
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 72/125
72
Users may select operation after careful consideration. If users want to keep on operation,
then select the “Enter” key (the cursor is defaulted on”Yes”) to response to the local
request. Fig 35 is displayed on the screen.
Fig 35
Please wait for a few seconds, one of the following three figures will be displayed on the
screen.
Fig 36
Fig 36 indicates Unit has already communicated with the remote equipment (or link), the
remote equipment state (including Modem Unit and Transceiver Unit) can be checked.
Refer to section 2.2.1 and 2.2.2 for the rest operation.
Note: If user wants to exit, reverts back to the previous menu by selecting
the“Left” keys.
Remote state
Waiting ………
1. T/R State
2. M/D State
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 73/125
73
2.3 - Setup Menu
Setup Menu is used to setup local EOW, TX power of local Transceiver Unit, capacity of
local Modem Unit. Put the cursor on "B. Setup " by moving the “Up/Down” keys,
then press the “Enter” key to call up "B. Setup ". Fig 37 is displayed on the
screen.
Fig 37
Setup Menu includes 3 sub-menu: local EOW, TX power of local Transceiver Unit,
capacity of local Modem Unit. Moving the “Up/Down” keys to get the following 3 menus.
"1. EOW Number "
"2. PWR Setup "
"3. CAP Setup "
2.3.1 EOW Number
EOW Number menu is mainly used to setup local EOW number. Put the cursor on "1.
EOW Number " by moving the “Up/Down” keys, then presses the “Enter” key to call up
"1. EOW Number " . Fig 38 is displayed on the screen.
Fig 38
The cursor is defaulted on the first “ 0” of the second line. The first line on the screen
shows the local EOW number, the second line shows adjustable range (from 00 to 15) of
EOW number. Only when the Local EOW number should be consistent with the remoteEOW number, EOW function comes true.
1. EOW Number
2. PWR Setup
EOW: 0000
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 74/125
74
On the “ EOW Setup ” page, the first line refers to the EOW number of the local equipment.
The second line refers to the EOW numbers that user can select by the “Right” key. The
EOW number is increased by one by selecting the “Up” key, and decreased by one by
selecting the “Down” key. Then press the “Enter” key to confirm. With the EOW number
increasing or decreasing, the EOW number in the first line changes accordingly.
For example, the current EOW number of local equipment is “ 00 ”, users want that EOW
number is “ 06 ”. put cursor on the second character “ 0” of the second line by moving the
“Right” key, users continuously press “Up” until the second “ 0” of the second line is “ 6”and
press the “Enter” key. Fig 39 is displayed on the screen.
Fig 39
By then the local EOW is successfully changed. If the current EOW number of remote
equipment also is “ 06 ”, EOW function is achieved between local equipment and remote
equipment, otherwise EOW function is invalidated.
Caution: please do not change the EOW number randomly. And dialing number in
fact is ‘#’+ EOW number.
EOW: 06
06
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 75/125
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 76/125
76
Fig 43
Fig 44
Fig 43 indicates the input password is wrong, Please contact with the technician and gets
technical support.
Fig 44 indicates the input password is correct and getting into PWR Setup menu. On this
page, the first line is current TX power of the local equipment; the second line is the
optional operation to the TX power of local Transceiver Unit as described in the following
table.
Note: 1 Sometimes, it might push “+” several times to increase local
Transceiver Unit TX power by 1 dBm. This is the normal reaction of the system.
2 The adjustable range of the local Transceiver Unit TX power is 17 ~ 26 dBm.
For example, if the users want to make TX power of the local equipment to be
maximal, should be according to the following operation step
Operation Meaning
The local Transceiver Unit TX power increased
The local Transceiver Unit TX power decreased
Error
Try Again
Tx Level [ 25 dBm ]
Opt. [ + , - ]
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 77/125
77
On the “ PWR Setup ” page, select one of [+ , - ] by the “right” key, and then press the
“Enter” key to increase or decrease the preset Tx power. The current Tx value is displayed
in the first line.
For example, if users want to reach maximum TX power of the local Transceiver Unit.
Please apply to following steps.
Step 1 Put the cursor on the "B. Setup " by moving the “Up/Down” keys, then
press the “Enter” key to call up "B. Setup " . Fig 45 is displayed on the screen.
Fig 45
Step 2 Put the cursor on the "2. PWR Setup " by moving the “Up/Down” keys,
then press the “Enter” key to call up “2. PWR Setup " . Fig 46 is displayed on the
screen.
Fig 46
Step 3 Put the cursor on "1" by moving the “Right” keys, then press the “Enter” key . Fig
47 is displayed on the screen.
Fig 47
Step 4 Put the cursor on "0" by moving the “Right” keys, then press the “Enter” key.Fig48 is displayed on the screen.
1. EOW Number
2. PWR Setup
>Local [ ]
Password:
0123456789
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 78/125
78
Fig 48
Step 5 Repeat step 4 to finish input of the password.
Step 6 After finishing password input, one of the following two figure will be displayed
on the screen.
Fig 49
Fig 50
Fig 49 shows that the user input password is incorrect, please contact with the technician
and get support.
Fig 50 shows that the user input password is correct and successfully get into Power
Setup menu.
Step 7 Put the cursor on "+" by moving the “Right” keys, press the “Enter” key until Fig
51 is displayed on the screen.
Fig 51
This page shows that the current local equipment’s TX Power reaches the maximumvalue. It will automatically revert back to the Power Setup menu as Fig 52.
Password: *
0123456789
Error
Try Again
Tx Level [ 25 dBm ]
Opt. [ + , - ]
Tx Level [ 26 dBm ]
MAX Value: DOWN
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 79/125
79
Fig 52
Step 8 The operation is completed.
CAUTION: The defaulted password is 0000000
only changing of the local Transceiver Unit TX Power is allowed
on the“PWR Setup”.
changing of the Transceiver Unit Power may result in link
instability. Only the technicians are authorized to do it.
Tx Level [ 26 dBm ]
Opt. [ + , - ]
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 80/125
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 81/125
81
Fig 56
Fig 57
Fig 56 indicates the input password is wrong, Please contact with the technician and get
technical support.
Fig 57 indicates the input password is correct and getting into CAP Setup menu. In the
example, the first line indicates the current capacity of the local Modem Unit is 2E1, the
second line is the optional operation to the capacity of local Modem Unit as described in
the following table
.
Optional capacity Meaning
1 The local Modem Unit capacity is 1E1
2 The local Modem Unit capacity is 2E1
3 The local Modem Unit capacity is 3E1
4 The local Modem Unit capacity is 4E1
Error
Try Again
CAP [ 2 * E1 ]
Opt. [ 1 2 3 4 ]
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 82/125
82
As a function of the local Modem Unit capacity change, parameters on the standby page
will change as detailed in the following table.
Capacity parameters Capacity meaning
Q 4E1
D 2E1
S 1E1
On the “CAP Setup” page, select any of the [1 2 3 4] by the “Right” key to change the
preset capacity value. The capacity value on the standby page will change accordingly.
For example, if the user wants the local Modem Unit is 1E1, proceed as follows
Step 1 Put the cursor on "B. Setup " by the “Up/Down” keys and then press the
“Enter” key. Fig 58is displayed on the screen.
Fig 58
Step 2 Put the cursor on "3. CAP Setup " by the “Up/Down” keys and then press
the “Enter” key. Fig 59 is displayed on the screen.
Fig 59
Step 3 Put the cursor on "1" by the “Right” keys and then press the “Enter”key. Fig 60 is
displayed on the screen.
1. EOW Number
2. PWR Setup
>Local [ ]
Password :
0123456789
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 83/125
83
Fig 60
Step 4 Put the cursor on "8" by the “Right” keys and then press the “Enter”key. Fig 61 is
displayed on the screen.
Fig 61
Step 5 Repeat step 4 to finish the input of password: 8320830.
Step 6 after inputting the password, one of the following two figure is displayed.
Fig 62
Fig 63
Fig 62 shows that the user input password is incorrect, please contact with the technician
and get support.
Fig 63 shows that the user input password is correct and successfully get into CAP Setup
menu.
Password : *
0123456789
Error
Try Again
CAP [ 2 * E1 ]
Opt. [ 1 2 3 4 ]
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 84/125
84
Step 7 Put the cursor on "1" by the “Right /Left” keys and then press the “Enter”key. Fig
64 is displayed on the screen.
Fig 64
This page shows CAP Setup of the local Modem Unit has been completed.
Step 8 Reverting back to the standby page. The local Unit standby page changes to as Fig
65.
Fig 65
Step 9 The operation is completed.
CAUTION
The defaulted password is 8320830
only changing of the local Modem Unit capacity is allowed on the“ CAP
Setup ”.
changing of the capacity of Modem Unit may result in link instability. Only
the technicians are authorized to do it.
CAP [ 1 * E1 ]Opt. [ 1 2 3 4 ]
WTX-2.4-02SV4.3
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 85/125
85
3 - Menu structure
1.1Tx Level
1.2 Rx Level
1 .T/R Sta te
>local [ ]
2.M/D State 2.1 MOD State
2.2 DEM State
A . St a t e
1 .1Tx Level
1 .T/R Sta te 1.2 Rx Level
>Remote [ ]
2.M/D State 2.1 MOD State
2.2 DEM State
WTX2.4- 02D
V4.3
1.EOW Number
B. Setup 2.PWR Setup local [ ]
3.CAP Setup local [ ]
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 86/125
86
E. Maintenance
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 87/125
87
On detecting a failure, the operator must go to one of the stations on the failed hop,
analyze the fault and determine which element has failed.
1 - Preventive Maintenance
It involves inspecting the units and their interconnections (connectors, cables, sockets,
etc), as well as all the equipment involved in the operation of the station (power generation
equipment, compressor if appropriate, solar panels if appropriate, earthing, etc) and, in
case of doubt, checking the suspect parts, taking all the necessary precautions to avoid
disrupting data transmission through the link.
1.1 - Routine Maintenance
Since the performance of component parts such as, IC’s transistors, resistors tend to
change under influence of heat and time, it is recommended that routine maintenance is
carried out at a regular interval to find out any changes of condition, which may cause
unexpected system break Down some time later.
1.2 - Routine Checking Of Operation Conditions
1.2.1 -Equipment should be kept from dust.
1.2.2 -Check the condition of the cables connectors and connections.
1.3 -Test on the measurement pointThe Transceiver Unit output power, Received signal level; Tx/Rx local oscillator frequency
is measurable at the measurement points of the Transceiver Unit.
1.4 -The supervision
Performance status of both local and remote equipment can be displayed on the LCD
screen which built in MODEM unit. The operator analyzes the alarm and initiates
appropriate corrective maintenance operations
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 88/125
88
1.5 - Keeping maintenance log
Maintenance log should be kept for each station. All maintenance operation check results,
date of the occurrences of failures, remedial action taken, and other necessary things
should be logged for reference.
2 - Corrective maintenance
- Check the condition of the cables, connectors and connections, and of all the
components that are involved in the operation at the station (power supply, battery,
earthing, etc),
- Analyze the IDU alarm indicators,
- If alarms are indicated, locate them using LCD of the MODEM Unit and analyze them
and carry out the necessary corrective procedures (change of unit, module, cable, etc).
3 - Analyzing Modem Unit alarm indicators
The alarm indicators on the Modem Units provide an indication of network elements
affected:
The ALM LED lighting: the local equipment alarm
The RMT LED lighting: the remote equipment alarm
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 89/125
89
3.1 - Using the LCD on Modem Unit to trace alarms
If the following figures appear on the LCD of the Modem Unit
Fig 1
Fig 2
TRL: TX power alarm
TX power low or fading
① Check whether the IF connection is normal or not
② If IF connection is normal, disconnect the IF connector, connect Transceiver Unit
to the other Modem Unit, check whether TPW is normal or not.
③ If not, change Transceiver Unit.
RX: RX level alarm
RX level low
① Check the antenna, if the antenna is not accurately pointed, repoint and check
that the alarm disappears. Abnormal conditions are hampering propagation:
presence of a sheet of water or waterlogged ground along the path of the link,
reflections from one or more layers of the troposphere caused by abnormal
stratification of the atmosphere, a fairly frequent condition in tropical climates,
natural screen or construction strongly masking the first “Fresnel ellipsoid”, rain
storms, etc.
② Check RF cable③ Check RF connection
Tx: [ALM]
Rx: [NOR]
Tx: [NOR]
Rx: [ALM]
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 90/125
90
④ If not, change Transceiver Unit.
If the following message appears on the LCD of Modem Unit.
Fig 3
① RUM connection problem: disconnected, incorrectly fastened, cut,
short-circuited or bad contact inside a connector. Repair the connection, check
its connectors, and change the defective items or the connection.② Do not power Transceiver Unit: check whether the power supply LCD of
Transceiver Unit is normal or not.
③ Change Modem Unit
④ After use the new Modem Unit, the alarm persists, change Transceiver Unit.
If Fig 4 appears on the LCD.
Fig 4
① connection problem.
② Change Modem Unit
Caution!
T/R COMM Fault
TX: + dBm
RX: - dBm
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 91/125
91
3.2 - Using the LCD on MODEM Unit to trace alarms
Modem Unit1 Block diagram
On installation, any channel interference will cause some alarms to be generated, so,
make sure the channel hasn’t been interfered.
NºAlarm
messageMost probable case and corrective methods
1 TIFTX IF alarm: Modulation IF lossCheck the power supply of Modem Unit, otherwise, change theModem Unit
2 TSLTransmitter signal loss: the output of coding signal lossCheck the power supply of Modem Unit, otherwise, change ModemUnit
3 IN1 The first E1 loss alarm: the first 2Mb/s data input lossCheck the 2Mb/s data input against the installation sheet;
Signal rate Adjust andFEC
ModulatorI
Q
Q
I
70MHz
70MHz
To Transmitter 1
From Receiver 1
21
ALC
5DEM678910
2Mb/s
2Mb/s
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 92/125
92
Check the 2Mb/s data input short circuit or open of the line;Check cable loss;Check the E1 I/O connection;Otherwise, change Modem Unit.
4 IN2 The second E1 loss alarm: the first 2Mbits input lossCheck methods is as same as IN1
5 RIF
Receiver signal loss alarmDisconnect IF connector on IF_OUT of Modem Unit and IF_IN ofModem Unit, connect IF_IN to IF_OUT of Modem Unit by IFconnection;Check whether RIF on the MODEM Unit LCD is normal; if RIF isnormal, check the IF_connector on the RX of Modem Unit; changeTransceiver Unit;Otherwise, change Modem Unit.
6 ERR
Error alarm, error bit has been in communication.Disconnect IF connector on IF_OUT of Modem Unit and IF_IN ofModem Unit, connect IF_IN to IF_OUT of Modem Unit by IFconnection; Check whether ERR is normal; If ERR is normal, theinterference in communication exist: otherwise, change Modem Unit.
7 FLS
Frame synchronization loss alarmDemodulator frame unlock. Electrical power must be switched offthen on.Otherwise, change Modem Unit
8 RMTRemote terminal alarmOn the remote menu of the MODEM Unit, check alarm information ofthe remote equipment.If necessary, the operator must go to the remote station.
Change Modem Unit:
① Disconnect all the connection connected to the equipment you are changing;
② Change Modem Unit after checking that the characteristics match; reconnect
all the connection to the Modem Unit;
③ Power the Modem Unit;
④ Wait for about four second for the terminal to be reconfigured, the alarm
LEDs should go off and the equipment LEDs should turn green;
⑤ Update the station’s installation form.(refer to installation manual).
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 93/125
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 94/125
94
4 - System Troubleshooting and maintenance
4.1- Tx Troubleshooting and maintenance:
4.1.1 When Tx is in trouble, there is Tx power alarm on the LCD of Modem Unit. It is
can be shown as follows:
According to the above, the trouble spot should be found.
TX XXdBm ALM
RX XXdBm NOR
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 95/125
95
Normal?
IF connection
is normal
Check whether IF connection
line is normal
Self-loop check of
Modem Unit
Modem Unit shows
TX 25dBm NOR
(Transceiver Unit is
normal)
Modem Unit shows
TX XXdBm ALM
(Transceiver Unit is in
trouble)
Repair power andconnection
Equipment gets right
Replace or link IF
connection
Equipment gets right
N
N
N
Y
Y
Y
Check Modem Unit
Modem Unit displays
TX 19dBm ALM
Check power supplyof equipment
N
Y
1 2
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 96/125
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 97/125
97
Connect power meter at the RF port
of unit or inspect Rx level on the
remote end from the local end
No output power
Check RF connection
Replace RF
connection in trouble
Equipment gets right
N
Y
Normal ?
Operate EP switch on the
switching unit
Switching Unit RF on-off box introuble
Replace Switching Unit or RF on-off
box in trouble see 7 about
maintenance of switch unit
Equipment gets right
Replace Transceiver
Unit or Tx filter with
the same frequency
one (see 6 about
maintenance of
Transceiver Unit)
Y
Normal ? N
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 98/125
98
4.2 - RX troubleshooting and maintenance
Rx trouble includes lower alarm of Rx level and alarm of no Rx level. The First step is to
check the antenna direction, installation of antenna and cable, Tx unit on the remote end.
If the check shows that all above is normal, then Rx troubleshooting and maintenance
should be done on the local equipments.
4.2.1 - Alarm of Rx level or no Rx level
Modem Unit show:
RX XXdBm ALM
XX 86dBm or LOW
Check RF connection and connector
normal
Check RF N-type cable
Normal
If RF on-off and subbranch box of
switching unit are in trouble, replace
switching unit or them see 7 about
maintenance of switch unit
Equipment gets right
Turn to check
Transceiver Unit(see 5 about
maintenance of
Transceiver Unit)
Replace RF cable
Equipment gets right
If N-type connector is loose
Screw down N-type connector
Equipment gets right
N
N
Y
Y
Normal?N
Y
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 99/125
99
4.2.2 - No Rx level on the Transceiver Unit:
Modem Unit show:
RX XXdBm ALM
XX 86dBm or LOW
Check RF connection and connector
RLO ALM
normal
unit alarm state of the local Transceiver Unit
will be shown as following:
1.4.1 RLO ALM or NOR
1.4.2 RSL ALM
Equipment gets right
Replace RF connection
Equipment gets right
N
Y
LNA of Rx unit on the Transceiver
Unit is in trouble replace Rx unit or
Transceiver Unit
with the same frequency ones
Y N
If LO of Rx unit on the Transceiver
Unit gives an alarm replace Rx unit or
Transceiver Unit with the same
frequency ones
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 100/125
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 101/125
101
4.3 - E1 I/O interface troubleshooting and maintenance:
If trouble occurs connecting between equipment and others through E1 interface, please
analyze and maintain as the following method.
Trouble in E1 I/O connection
Re lace E1 I/O connection
Equipment gets right
no signal at each E1interface ?
N
Normal ?
Y
Connect again
Equipment gets right
N
Checking whether some
channel is broken
broken?N
No signal at E1 interface
Checking whether four E1
channels connection are normal
Check E1 I/O connection
Y
Seal again
Equipment gets right
Y
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 102/125
102
4.4 - Troubleshooting and maintenance of monitor and display keyboard
4.4.1 - Troubleshooting and maintenance should be done as follows when Modem Unit
does not display parameter of the corresponding Transceiver Unit:
a When Modem Unit displays “Caution T/R com Fault”
Please check whether RUM connection is connected correctly and work
normally. If broken or have some trouble, RUM connection needs to be sealed
again or replaced. As Soon as equipment gets right, it will display :
b. when Modem Unit does not display alarm state of the corresponding Transceiver
Unit, it will show:
This fault means turn-off of Tx or Rx alarm indicator. please operate as follows:
Operate MODEM Unit and choose corresponding state display of Tx or Rx.
Choosing alarm state “ON”, it will show as follows:
1.3.1 TLO [ON]
1.3.2 TPW [ON]
1.4.1 RLO [ON]
1.4.2 RSL [ON]
Quitting operation, it will show:1.3.1 TLO [NOR]
1.3.2 TPW [NOR]
1.4.1 RLO [NOR]
1.4.2 RSL [NOR]
TX 25dBm
RX XXdBm
TX 25dBm [NOR]
RX XXdBm [NOR]
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 103/125
103
Exiting from operation of state display, Modem Unit will display as follows:
c. If the Modem Unit does not show the parameter of Transceiver Unit, it will show:
To check the corresponding OAM connection and insure that it is normal. If
the connection is broken, please weld it or replace a new one. The equipment
gets right.
4.4.3 - Display trouble:
a. If there is no display trouble on the LCD of Modem Unit Unit, check the power
supply and insure that power switch is normal. Turning on the power switch, its
display gets right.
b. Open Modem Unit to check if the LCD connection is plugged correctly. Line
connecting, the display gets right.
4.4.4 - Trouble of keyboard operation:
a. If there is no reaction operating keyboard, please restart the Unit and reset the
keyboard control to make it gets right.
b. If one key on the keyboard is insensitive or unresponsive, it is key trouble. Please
replace the Unit. If problem can not be solved as indicated above, please replace the
TX 25dBm NOR
RX XXdBm NOR
TX dBm
RX dBm
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 104/125
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 105/125
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 106/125
106
5.2 - Troubleshooting and maintenance of display and inspection
5.2.1 - troubleshooting and maintenance of Tx and Rx display:
Trouble phenomenon: the front panel LCD of IF demodulation displays
+26dBm can’t be changed,
-34 dBm can’t be changed.RX -××dBm
TX +××dBm
Reading on the LCD does not
change
Check whether U10 MX584 pin 2
on the power board of 2.4GHzTransceiver Unit is +5V
Check whether U11 MAX840 pin
6 on the power board of2.4GHz Transceiver Unit is -5V
Check whether U9 MX5160 pin 5
or 6 on the power board of
2.4GHz Transceiver Unit is 2.4V
Replace U3 MAX114 on the
power board of 2.4GHzTransceiver Unit
replace
chip
Equipment
gets right
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 107/125
107
5.2.2 - Troubleshooting and maintenance of Tx and Rx measurement point
Trouble phenomenon: the voltage of DB9 pin 2 on the front panel of Transceiver Unit is
zero; the voltage of DB9 pin 4 on the front panel of Transceiver Unit is zero. Above both
are measured with multimeter.
a. check the RF connection 5 if it isn’t inserted correctly.
b. If reading on the front panel LCD of Modem Unit shows that Tx is normal, test
whether it is lined correctly between S5 pin 5 and DB9 pin 2 on the front panel of
Transceiver Unit or short circuit occurs, then repair it. The trouble of Tx power
inspection can be removed.
c. If reading on the front panel LCD of Modem Unit shows that Rx is normal, test
whether it is lined correctly between U7(LM1458)pin 1 on the 2.4GHz Transceiver
Unit power board and DB9 pin 4 on the front panel of Transceiver Unit or short circuit
occurs, then repair it. The trouble of Rx power inspection can be removed.
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 108/125
108
5.2.3 - Troubleshooting and maintenance of Rx and Tx local oscillation inspection:
Trouble phenomenon: to connect the microwave frequency meter (with N-SMA
conversion connector) with RLO and TLO on the front panel of Transceiver Unit, no
frequency is shown.
Testing the LO inspection port of Rx and Tx unit, if the frequency can be found, then
check SMA-JB3/ SMA-JB3 connection lines. If there is no frequency, analyse should
be done according to the flow chart.
Adjust or replace connection
Abnormality phenomenon of LO power inspection can
be divided into
a. reduction b. nonexistence
Check whether SMA-KF3-80 connection line is broken
or links to GND
Check coupling board of LO power inspection
Check LO
LO power inspection is normal
Repair LO if in trouble
Normal?
Adjust or replace
cou lin board Normal?
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 109/125
109
5.3 - Tx troubleshooting and maintenance
5.3.1 - No power output troubleshooting and maintenance
Trouble phenomenon: to connect the microwave power meter (with N-SMA conversion
connector) with Tx port on the rear panel of Transceiver Unit, there is no power output or
below the nominal.
No power output or below the nominal
Check whether IF signal exists on the connection
test whether power signal exists on the Tx unit
Turn to section 5.1
to handle LO
Check 70MHz IF signalCheck whether two
class amplification of
power IF amplifier is
normal and insure that
70MHz output signal
is normal
Up-convertor is normal ?test mixer and check
whether class1
amplification is normal
Check single-band filter
Turn to single
filter repairment
Power amplifier isnormal
Repair power supplyand insure it works
normally
Power amplifier doesn’t work
Replace PA module and test it again to make it works normally
Normal power output of Tx unit
It’snormal ?
Above is
normal
LO power inspection isnormal
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 110/125
110
5.3.2 - troubleshooting and maintenance if Tx unit power can not be tuned
5.4 - Troubleshooting and maintenance of no Rx gain
5.4.1 - troubleshooting and maintenance of no Rx gain
Tx unit power can not be tuned
Check whether P-MON detector
voltage is normal at the power IF
amplifier spot measured with
multimeter
Check detectordiode and feed
through capacitoron the power
amplifier moduleand insure thatthey are normal
Check whether PIN is normal on
the power IF amplifier module
Replace changeableattenuator
Check changeable resistance
Replace it if in trouble
Tuning of Tx unit power is normal
LNA doesn’t
work?
LO is in lock loss? Isolator doesn’t
work?Rx mixer doesn’t
work?
Repair it Replace it Repair it, Adjust
every parameter
again according to
adjustment method
Repair it, Adjust
every parameter
again according to
adjustment method
Normal Rx gain
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 111/125
111
5.4.2 - troubleshooting and maintenance of Rx IF amplifier
a. Output level is not normal and tune RP3 in no effect.
To test MAX840 pin 6 with multimeter, If the voltage isn’t -5V ,then MAX840 does
not work and replace it or V5/V6 detector diode may be soldered not correctly or
broken.
b. AGC range not enough
A 10UF capacitor should be soldered between the +12V spot of the signal input
and GND. To test the N1~N6 integration amplifier with the multimeter ,the voltage
of output pin is in the range of 4.9V to 5.2V. If the voltage is not in the range , the
capacitors from C4 to C14 should be checked to see whether they are soldered
and work correctly and the V1 through V4 diodes are normal.
c. AGC shows voltage not normal
To test the diode D1, it should be replaced If the diode D1 does not work.
Otherwise the feedback resistance should be tested between pin 6 and pin 7 of
LM1458 in order to see whether it is 24K.
5.4.3 - LNA troubleshooting and maintenance
When the gain is very small and can not be tuned up, first check whether the line on the
transition board has been cut off, second check whether the isolator may be installed not
correctly or does not work, third check R1 voltage. If R1 voltage is 5V , then N2 is broken
and N1 broken if not.
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 112/125
112
5.5 - Troubleshooting and maintenance of LO in trouble
Trouble phenomenon: LO phase loss,locked level is 0V
Y NCheck soldering of 8MHz crystaloscillator and whether it works
Check pin setting of
MC145152 and whether
it is soldered correctly?
Check soldering of
MB510 and whether it
workes correctly?
Finally set LO with required
frequency
Change resistance
value of R10
Repair it and itworks correctly?
Finally check loop filter and whether
its output level of LM1458 is in
the range of 6V—8V?
Repair it and
it works
correctly?
Repair it
and it
works
LO output is normal
Y
Y N
Y N N
N
Y
N Y
Y
N
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 113/125
113
6 - Troubleshooting and maintenance of Modem Unit
6.1 - ALM analysis
When ALM of Modem Unit shines, connector links of external cable and cable are
checked to see if they are normal. Alarm information shown by system should be
analyzed in detail if they are normal.
6.1.1 - Tx alarm state:
6.1.2 - Rx alarm state:
2.2.1 RIF[NOR] /[ALM] IF Rx alarm2.2.2 ERR[NOR]/ [ALM] Rx error-code alarm2.2.3 SYN[NOR]/ [ALM] RPD Synchronization loss alarm2.2.4 HSW[NOR]/ [ALM] hitless switching alarm
2.2.5 FLS[NOR]/ [ALM] frame synchronization loss alarm2.2.6 RMT[NOR]/ [ALM] remote equipment alarm
Operate unit into state display
LOCAL[ ]
M/R STATE
MOD STATE
2.1.1 TIF[NOR]/ [ALM] IF Tx alarm2.1.2 TSL[NOR]/ [ALM] IF signal alarm2.1.3 IN1[NOR]/ [ALM] no input alarm of subbranch 12.1.4 IN2[NOR]/ [ALM] no input alarm of subbranch 22.1.5 IN3[NOR]/ [ALM] no input alarm of subbranch 32.1.6 IN4[NOR]/ [ALM] no input alarm of subbranch 4
DEM STATE
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 114/125
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 115/125
115
6.2 - Troubleshooting and maintenance of IF Tx alarm (TIF [ALM])
trouble phenomenon no IF Tx output alarm on the Modem Unit
N Replace it if 70Mcrystal oscillator 3JZ1 is
in trouble
Y
Check whether output of 90 power
splitters/combiners is normal
Y
N
N
Y
N
Y
Check whether output of
amplifier 3N3 is normal
N
Check whether output of
amplifier 3N2 is normal
Y
N
Y
Check whether output of diode
3V1 and 3V2 is normal
N
Replace comparator 3N1
Y
Alarm disappears? Y
N
Alarm disappears and Modem
Unit is normal
N
N
N
N
N
N
Y
Y
Y
Y
Y
Y
Check whether input signal exists atthe pin 1 of amplifier 3N4
Check whether output of mixer 3N9and 3N8 are normal
Check whether output of 0 ˚ power
splitters/combiners 3N7 is normal
Replace it if 90 ˚ power
splitters/combiners is in
trouble
Replace it if mixer is
in trouble
Replace it if 0 ˚ power
splitters/combiners is in
trouble
Replace it if amplifier
is in trouble
Replace it if amplifier is
in trouble
Replace it if diode isin trouble
Alarm disappears?
Alarm disappears?
Alarm disappears?
Alarm disappears?
Alarm disappears?
Alarm disappears?
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 116/125
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 117/125
117
6.5 - Troubleshooting and maintenance of Rx de-modulation alarm (SYN
[ALM] / FLS [ALM])
trouble phenomenon Self-loop lock loss on the Modem Unit
6.5.1 - Using IF connection to link IFIN and IFOUT of Modem Unit in the way of
self-loop.
6.5.2 - Measure base voltage of transistor (V5-8). replace them in trouble.
6.5.3 - Troubleshooting and maintenance
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 118/125
118
Note: The following analysis demands that Tx must be in no trouble.
N
Check whether output of
70MVCO5JT1 pin 8 is normal
Replace 5U1
Alarm disappears and Modem Unitis normal
YAlarm disappears?
Check whether output of
amplifier 5N5 pin 4 is normal
Replace it if amplifier
is in trouble
Replace it if VCO is
in trouble
Check whether output of 90 ˚
power splitters /combiners5N4 pin 3 and pin 6 are
normal
Replace it if 90 ˚
power splitters is in
trouble
Check whether output of mixer
5N2 pin 2 and 5N3 pin 2 are
normal
Replace it if mixer is
in trouble
Check whether pin 7 and pin 8
of comparator5U3 and 5U4
work correctly?
Replace it if
comparator is in
trouble
Check whether pin 4 and pin 9
of comparator 5U6 and 5U7
work correctly?
Replace it if
comparator is in
trouble
YAlarm disappears?
YAlarm disappears?
YAlarm disappears?
YAlarm disappears?
YAlarm disappears?
N
N
N
N
N
N
Y
Y
Y
Y
Y
Y
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 119/125
119
6.6 - Troubleshooting and maintenance of EOW
Check whether
output at the pin 5
of 8N9 is normal
EOW in trouble
Can not dial out Can not dial in
Replace 8N12
NCheck whether
output at the pin 5
of 8N10 is normal
N
Y
Replace 8N11
Y
Replace it if audio
amplifier 8N10
is in trouble
Alarm disappears
N
Modem Unit is normal
normal
N
YY
Y
Check if there is 64k signal input
at the pin 1 and pin 9 of 8N17.
Please confirm
that ModemUnit is
in no trouble again
N
Check if output at the pin 3 and
pin 8 of NAND gate 8N17 is
normal.
N
Check if output of PCM 8N15
is normal
N
Y
Y
Normal
Replace it if 8N17
is in troublenormal
N
Replace it if it’s in
trouble normal
N
Y
Y
Y
Replace it if audio
amplifier 8N9 is
in trouble
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 120/125
120
6.7 - Troubleshooting and maintenance of display and monitoring
6.7.1 - Troubleshooting and maintenance in this case like no display on LCD
Replace LCD
9U3 is in trouble9U1 is in trouble
Replace 9U1 Replace 9U3
LCD display is normal
YLCD is in trouble?
Pin 6 of LCD 9JP1is 0V?
N
NY
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 121/125
121
F. Service
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 122/125
122
1 - TECHNICAL SUPPORT
Manufacturer Support and General Inquires
Manufacturer provides service and support in the following ways:
Telephone
Hours of operation are from Monday to Friday 9:00AM - 5:30 PM.
To ensure the equipment normal operation, manufacturer provides route selection
and design.
Manufacturer provides necessary training on installation and operation.
Manufacture may provide installation and technical supervision on actual
requirement.
We promise we receive FAX, telephone about quality problem, after analyzing
problem; our technician will get to the site as soon as for domestic customers.
Return the defective equipment back to manufacture for prepare for overseas
customers.
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 123/125
123
2 - WARRANTY
2.1 - General terms
2.1.1 - All definitions contained in Manufacturer apply to the warranty.
2.1.2 - Manufacturer warrants that for a period of 1 year from the date of purchase from
Manufacturer or an authorized reseller, the product will be free from defects in material
and workmanship under normal use. If this product is not in good working order as
warranted, the sole and exclusive remedy shall be, at Manufacturer's option and
expense, to repair the defective product or to provide an equivalent replacement product.
All products that are replaced will become the property of Manufacturer. Replacement
products may be new or products reconditioned to a like-new condition.
2.1.3 - this warranty dose not applies to Antenna and feeder system and rack, which
non-manufacturer provided.
2.2 - Restrictions
This warranty does not apply if the product has been altered, except by Manufacturer
has not been installed, operated, repaired, or maintained in accordance with
instructions supplied by Manufacturer
has been subjected to abnormal physical or electrical stress, misuse, negligence, or
accident, or used in ultra hazardous activities.
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 124/125
124
Appendix 1 - List of application alarms
Alarmmnemonic
MEANING
TLO Tx local oscillator alarm
TPW Tx power alarm
RLO Rx local oscillator alarm
RSL Rx signal alarm
TIF Tx IF alarm
TSL Transmitting signal loss
IN1 The first E1 loss alarm
IN2 The second E1 loss alarm
IN3 The third E1 loss alarm
IN4 The four E1 loss alarm
RIF Rx IF alarm
ERR Error alarm
FLS Frame synchronization loss alarm
RMT Remote terminal alarm
8/13/2019 NEWWtx2[1].4 02 Digital Microwave System
http://slidepdf.com/reader/full/newwtx214-02-digital-microwave-system 125/125
Appendix 2 - RX/TX level and Voltage corresponding graph