new product enhancements & version 6.06 firmware enhancements gv3000/segv3000/se
TRANSCRIPT
New Product Enhancements & New Product Enhancements & VERSION 6.06 Firmware VERSION 6.06 Firmware EnhancementsEnhancements
GV3000/SEGV3000/SEGV3000/SEGV3000/SE
Feature and Enhancement SummaryFeature and Enhancement SummaryFeature and Enhancement SummaryFeature and Enhancement Summary
1) NEW Expanded Bookshelf Drive Rating
2) NEW Enclosure Kits for Power Modules
3) VERSION 6.06 Firmware Enhancements
• “FAST FLUX” Added to Sensorless Vector
• NEW- Regulator Output Configurations
• NEW- RMI Output Configurations
• NEW- Analog Input Configurations
• Modified Parameter Ranges
• NEW- OCL Speed Control Features
NEW Model: 430ER4060
• Expanded Bookshelf family
• NEW Model No.: 430ER4060
• Up to 43A V/Hz @ 2kHz
• Up to 32A Vector @ 2kHz
• Same programming and
functionality
• Saves panel space
• Braking circuitry is standard,
just add appropriate resistor
• Offers the user more selections
to fit their installation needs
NEW - Expanded Bookshelf Drive RatingNEW - Expanded Bookshelf Drive RatingNEW - Expanded Bookshelf Drive RatingNEW - Expanded Bookshelf Drive Rating
NEW - Expanded Power Module RatingsNEW - Expanded Power Module RatingsNEW - Expanded Power Module RatingsNEW - Expanded Power Module Ratings
• Expanded Power Module family• 30-60HP @ 460VAC
• Available 6-01 (50-60HP), 8-01 (30-40HP)
• Complete power module line from 1-200HP
ModelNumber
House PowerRating
Input Volts(AC)
InputKVA(1)
Input Amps(Maximum)(1)
Output Amps(Maximum)(2)(3)
Power LossWatts(4)
30V406030HP
(22KW)380-460VAC
+/-10%35.0 45A 40A 660
40V406040HP
(30KW)380-460VAC
+/-10%46.2 60A 54A 900
50V406050HP
(37KW)380-460VAC
+/-10%57.3 80A 67A 1100
60V406060HP
(45KW)380-460VAC
+/-10%71.7 92A 78A 1350
(1) These values are when AC reactor installed in the AC input line.(2) With vector regulation, 150% output current capability for oneminute.(3) These values are for operation with 4KHz carrier frequency. Foroperation with 8KHz carrier frequency,
derating by 20% is required.(4) These values are at full load operation.
NEW - Expanded Power Module RatingsNEW - Expanded Power Module RatingsNEW - Expanded Power Module RatingsNEW - Expanded Power Module Ratings
GV3000/SE Drive
Dim. H1 Dim. H2 Dim. H3 Dim. H4 Dim. W Dim. DWeight
(1)
30V4060
40V406050V4060
60V4060
544 mm 21.4 "
564 mm 22.2 "
504 mm 19.8 "
606 mm 23.9 "
450 mm 17.7 "
460 mm 18.1 "
405 mm 15.9 "
455 mm 17.9 "
23 Kg 51 lbs
30 Kg 66 lbs
235 mm 9.3 "
354 mm
13.6 "
GV300/SE Drive Dim.A1 Dim.A2 Dim.A3 Dim.A4 Dim.B1 Dim.B2 Dim.C1 Dim.C2 Dim.C3 Dia.d
30V4060
40V406050V4060
60V4060
9 mm 0.35 "
9 mm 0.35 "
100 mm 3.9 "
100 mm 3.9 "
25 mm 1.0 "
25 mm 2.0 "
51 mm 2.0 "
51 mm 2.0 "
10 mm 0.4 "
30 mm 1.2 "
10 mm 0.4 "
30 mm 1.2 "
• UL Approved Packaging for Nema Type 1
• 3 different kits for 460VAC units• 2CK4100 ( for 60 to 100 Hp )• 2CK4125 ( for 125 Hp )• 2CK4200 ( for 150 to 200 Hp )
• Allows for Machine or Wall mounting
• Conduit connects to Top & Bottom covers
• The Drive must be a Rev. 0.7 or higher
version drive to accept this kit
NEW - Enclosure Kits for Power ModulesNEW - Enclosure Kits for Power ModulesNEW - Enclosure Kits for Power ModulesNEW - Enclosure Kits for Power Modules
• Improves Sensorless Vector Operability
• Provides a quick response to a RUN command by
eliminating motor “pre-magnetizing” delay
• Improves coordination of starting up multi-drive
systems operating in Sensorless Vector Control
• Setting U.21 to zero will activate this feature
““FAST FLUX” Added to Sensorless VectorFAST FLUX” Added to Sensorless Vector““FAST FLUX” Added to Sensorless VectorFAST FLUX” Added to Sensorless Vector
• “Drive Ready” relay output added
• Output is energized when there are no faults
active
• Output is de-energized when there are one or
more faults active
• Relay Output can be configured to be
energized or de-energized when a fault occurs
• Provides greater flexibility to user
NEW - Regulator Output ConfigurationsNEW - Regulator Output ConfigurationsNEW - Regulator Output ConfigurationsNEW - Regulator Output Configurations
• Two new Output selections• Output turns on based upon speed reference
• Tie output into machine logic to energize downstream equipment
• Output is energized when the Terminal Strip start & stop inputs are closed• Output is de-energized when when either one of the inputs are
open
• Tie into machine logic so downstream equipment doesn’t start unless this output is energized
on -s ta te
S e lec ted S peed R e fe renceo ff-s ta te
L
H L = Leve l (r.056 )H = H ys te res is (r.053 )
r.056 and r.053 adjust hysteresis and level
NEW - RMI Output ConfigurationsNEW - RMI Output ConfigurationsNEW - RMI Output ConfigurationsNEW - RMI Output Configurations
• Start and Stop the drive via Speed Reference level• P.011 = 12 will allow this mode of operation• P.000 must be rE ( Remote / Terminal Strip )• Allows operator to control the drive from only a pot• Works in V/HZ, SVC, FVC
on-s ta te
A na log Inpu t (0 - 10vdc)
o ff-s ta te
User configurable turn-on / turn-off levels !
NEW - Analog Input ConfigurationsNEW - Analog Input ConfigurationsNEW - Analog Input ConfigurationsNEW - Analog Input Configurations
• Trim Gain and Draw Gain
• Range is now +/- 100%
• Zero Speed Hold Time
• Keep the motor magnetized for a longer time period
• Increased from 20 sec to 655 sec
Modified Parameter RangesModified Parameter RangesModified Parameter RangesModified Parameter Ranges
• Now when RMI (Remote Meter Interface) card is
installed
• Outer Control Loop Speed Reference can come from RMI
analog input or Preset Speeds 1-8
• When no option is installed
• Outer Control Loop Speed Reference can come from Preset
Speeds 1-8
• Greater flexibility when using an outer control loop
• More options for using the OCL control without the
RMI board
NEW - OCL Speed Control Features NEW - OCL Speed Control Features NEW - OCL Speed Control Features NEW - OCL Speed Control Features