Technical and Specifi cation Information Greenstar Danesmoor regular series

Greenstar Danesmoor System series

Greenstar Danesmoor wall-mountedregular series

Greenstar Danesmoor Utility series

Greenstar regular and system oil-fi red condensing boiler range

NEW

Page 2: NEW - Oil Tanks | Steel, Fuel Dispensing & Bunded Oil Tanks › wp-content › uploads › ... · Oilfit flexible flue liner 57 - 58 Accessories 59 - 62 Worcester training 63 - 65

2

Worcester and you. Making a difference.

As part of the Bosch Group, Worcester

products are designed and manufactured to

provide customers with the highest levels of

quality and reliability which are synonymous

with the Bosch name.

Worcester is a part of Europe’s largest

supplier of heating products and with our

UK-based resources as well as the Bosch

Group's global infrastructure, we can offer

you the value-added solutions you deserve.

Worcester employs a nationwide network of

Service Engineers and technically trained

Field Sales Managers, supported by an

experienced technical services team which

is able to provide comprehensive support

and advice from designing system layouts

through to installation.

Worcester is dedicated to providing high

performance, energy effi cient heating

and hot water systems for a wide range

of installations. Our oil manufacturing

heritage stretches back to the foundation of

the company in 1962 and during this period

we have built a reputation for manufacturing

products which offer the end user the

highest levels of quality and reliability.

2

Page 3: NEW - Oil Tanks | Steel, Fuel Dispensing & Bunded Oil Tanks › wp-content › uploads › ... · Oilfit flexible flue liner 57 - 58 Accessories 59 - 62 Worcester training 63 - 65

3

Contents PageThe Greenstar regular and system boiler range 4 - 5

Key features of the range 6 - 9

Inside story 10 - 25

Site preparations and guidance 26 - 32

Installation requirements 33 - 36

The Worcester Greenstar System Filter 37

Condensate pipework 38 - 39

The Worcester CondenseSure auxiliary siphon 40 - 41

Horizontal and vertical flue terminal positioning 42 - 43

Horizontal fluing options (internal models) 44 - 45

Vertical fluing options (internal models) 46 - 47

Greenstar Danesmoor wall mounted internal boiler range

horizontal fluing options 48 - 49

Greenstar Danesmoor wall mounted internal boiler range

vertical fluing options 50 - 51

Fluing options (external models) 52

Plume management positioning and system options 53 - 55

Conventional flue 56

Oilfit flexible flue liner 57 - 58

Accessories 59 - 62

Worcester training 63 - 65

After-sales 66

“At Worcester we recognise the vital role you

play in the specification and installation of

energy efficient appliances in homes across

the UK. We will continue to invest in our

products, people, facilities and added value

services to ensure you have all you require in

order to deliver only the best solutions to your

customers’ requirements.”

Carl Arntzen,

Managing Director,

Bosch Thermotechnology Ltd.

The reception and main entrance at our Worcester headquarters

3

Page 4: NEW - Oil Tanks | Steel, Fuel Dispensing & Bunded Oil Tanks › wp-content › uploads › ... · Oilfit flexible flue liner 57 - 58 Accessories 59 - 62 Worcester training 63 - 65

4

The Greenstar regular and system oil-fi red condensing boiler rangeThe Greenstar Danesmoor regular and Danesmoor System

series are part of a market-leading range of high effi ciency

boilers which is good news for the environment and

excellent news for specifi ers, installers and consumers.

They are ideal for customers who are looking to minimise

fuel consumption, without sacrifi cing heating and hot

water performance.

Greenstar oil-fi red regular and system boilers offer outputs

between 12 to 70kW and are specifi cally designed for use

with either a vented or sealed system. The range includes

fl oor standing internal and external models and a wall

mounted internal appliance (WM). They are ideally suited

to our range of Greenstore hot water cylinders which allow

your customers to benefi t from mains pressure hot water,

rapid re-heat times and excellent heat retention.

Every appliance is operationally tested before it leaves

the factory as part of Worcester’s rigorous quality

control procedure. When you install a Worcester

oil-fi red boiler, you can rest assured that your customer

is receiving the best quality components and highest

levels of workmanship.

Highly effi cient condensing technology

The secondary heat exchanger of the Greenstar range

extracts more energy from the oil and, when compared with

a non-condensing boiler, can cut heating and hot water bills

by over £400 a year†. All Greenstar condensing boilers are

able to deliver this energy-saving performance by extracting

additional latent heat from the exhaust gases – a highly

effi cient use of energy which signifi cantly reduces carbon

dioxide emissions into the atmosphere.

Greenstar Danesmoor regular and Danesmoor System

condensing boilers have a seasonal effi ciency of over 90%

(SEDBUK 2009 value), effi ciently producing heat for both

your customers' heating and hot water demands. This is in

comparison to standard effi ciency boilers which achieve

around 78% effi ciency, highlighting how a Greenstar boiler

can reduce heating and hot water bills.

†Source: Energy Saving Trust: Based on replacing a G-rated oil-fired boiler with an A-rated oil-fired condensing boiler and a full set of controls in a typical 3 bedroom semi-detached home with an average oil price of 6.02p/kWh.

Page 5: NEW - Oil Tanks | Steel, Fuel Dispensing & Bunded Oil Tanks › wp-content › uploads › ... · Oilfit flexible flue liner 57 - 58 Accessories 59 - 62 Worcester training 63 - 65

55

Greenstar Danesmoor regular model.Kitchen courtesy of Alno Kitchens.

The Greenstar regular and system oil-fired range at a glance

Greenstar model Utility regular 32/50 Utility regular 50/70 Danesmoor WM 12/18 Danesmoor WM 18/25

Part No. 7 716 100 103 7 716 100 104 7 716 100 124 7 716 100 125

SEDBUK 2005 93.0% 92.5% 92.6% 92.8%

Model Utility regular Utility regular Wall mount regular Wall mount regular

Dimensions (h x w x d) 1012x520x815mm 1012x520x815mm 880x600x410mm 880x600x410mm

Output kW to central heating (CH)

Min 32kW 50kW 12kW 18kW

Max 50kW 70kW 18kW 25kW

Conventional CF or RS room-sealed from one appliance

RS only RS only

Greenstar model 12/18 models 18/25 models 25/32 models

Danesmoor regular 7 716 100 132 7 716 100 133 7 716 100 134

Danesmoor regular Utility 7 716 100 141 7 716 100 142 7 716 100 143

Danesmoor System 7 716 100 135 7 716 100 136 7 716 100 137

Danesmoor System Utility 7 716 100 147 7 716 100 148 7 716 100 149

SEDBUK 2005 93.2% 93.0% 92.8%

Dimensions (h x w x d) All Kitchen/Utility models

855x370x600mm 855x370x600mm 855x370x600mm

Output kW to central heating (CH)

Min 12kW 18kW 25kW

Max 18kW 25kW 32kW

Conventional CF or RS room-sealed from one appliance

NEW

NEW

NEW

NEW

Greenstar model 12/18 External models 18/25 External models 25/32 External models

Danesmoor regular External 7 716 100 144 7 716 100 145 7 716 100 146

Danesmoor System External 7 716 100 126 7 716 100 127 7 716 100 128

SEDBUK 2005 93.2% 93.0% 92.8%

Dimensions (h x w x d) 950x565x780mm 950x565x780mm 950x565x780mm

Output kW to central heating (CH)

Min 12kW 18kW 25kW

Max 18kW 25kW 32kW

Balanced flue

NEW

NEW

Page 6: NEW - Oil Tanks | Steel, Fuel Dispensing & Bunded Oil Tanks › wp-content › uploads › ... · Oilfit flexible flue liner 57 - 58 Accessories 59 - 62 Worcester training 63 - 65

6

Greenstar Danesmoor regular and

Danesmoor System internal boiler ranges

Greenstar internal models are ideally suited for installation

in a kitchen or a utility room.

Greenstar internal regular and system boilers feature:

• The same footprint as previous models, creating less

disturbance for replacement installations

• An annual effi ciency of over 90% (SEDBUK 2009 value),

ensuring optimum effi ciency

• A 5mm steel inner primary heat exchanger surface as

well as a 3mm outer, increasing effi ciency and reliability

• Years of Worcester innovation have developed the

optimum match between the burner and the boiler,

ensuring maximum effi ciency and an exceptionally clean

and quiet operation

• A full 2 year guarantee, as well as a 5 year* guarantee on

the primary heat exchanger and a 10 year* guarantee on

the secondary heat exchanger.

Greenstar Danesmoor regular and

Danesmoor System External boiler ranges

Where space in the home is at a premium, a Greenstar

External boiler is the ideal solution.

Whilst offering many of the features of the internal

models, Greenstar External models also feature:

• A robust, durable external cabinet that blends in with

the garden and protects the appliance from the elements

• IP45 Ingress Protection – protecting the boiler from

water, dust and the environment

• A built-in frost thermostat which protects the appliance

from freezing

• Balanced fl ue system ensures that the fl ame is

maintained even in exposed environments.

Key features of the range

*Terms and conditions apply.

On the secondary heat exchanger*.

Special features of our Greenstar Danesmoor internal

and external models

Worcester's return to the Danesmoor heritage has brought

a new range of regular boilers that deliver the following

installer-focused features.

• Cross-fi ring burner with easy access to principle

components enabling annual service from the front

of the boiler

• Easy to remove one-piece primary baffl es made from

special high temperature resistant stainless steel

• Optimised hydraulic connections based on installer

feedback – all connections fi t on the inside of the boiler,

providing a fl ush fi nish to the exterior. A blanking plug is

provided for the fl ow tapping with the regular appliances

• An annual effi ciency of over 90% (SEDBUK 2009 value),

ensuring optimum effi ciency

• Rigid cabinet with a cross brace that provides a

convenient tray for nuts and bolts

• The new Greenstar Danesmoor boilers are

up to 17kg lighter than the previous Greenstar Camray.

NEW

NEW

Page 7: NEW - Oil Tanks | Steel, Fuel Dispensing & Bunded Oil Tanks › wp-content › uploads › ... · Oilfit flexible flue liner 57 - 58 Accessories 59 - 62 Worcester training 63 - 65

77

Operation

Greenstar Danesmoor System boilers are supplied ready for

use with sealed primary water systems, and can be installed

with the Worcester Greenstore range of twin and single coil

unvented cylinders.

Greenstar Danesmoor regular boilers are suitable for open

vented systems, requiring a minimum head of 1m. They

too can be installed with our Worcester Greenstore

unvented cylinders.

All models operate on 28 sec kerosene oil and feature a

Riello burner.

Applications

The outputs offered within the range makes our Greenstar

oil-fi red boilers suitable for a wide range of domestic

properties, as well as providing installation fl exibility.

All models are solar compatible and are ideally matched

to our range of Greenskies solar thermal panels and

Greenstore TC twin coil cylinders.

Fluing

Floor standing indoor appliances can

be used with either a room-sealed

concentric fl ue or conventional (open)

fl ue. A fl exi-fl ue liner kit is available to enable the appliance

to be fl ued via a chimney. The room-sealed fl ue ensures

extremely quiet operation. The Greenstar Danesmoor WM is

only for use with room-sealed fl ues.

The external appliances utilise a balanced fl ue system

in order to minimise the risk of lockouts caused by

strong winds.

A plume management kit is available for both internal and

external boilers.

Greenstar Oilfi t – the easy-fi t fl uing solution

• Multiple fl uing options with the ability to fl ue internal

fl oor standing boilers from the top, rear or side and

external boilers from the rear and side

• Conventional fl ue via the adaptor kit or fl exi-fl ue chimney

liner kit

• Room-sealed fl ue lengths up to 8m vertically and

6m horizontally

• Quick-to-install push-fi t connections and telescopic

options which form a gas-tight seal and in most cases

eliminate the need to cut the fl ue

• Easy-fi t installation that requires no special tools when

fi tting fl ue extensions, elbows and adaptors.

Greenstar Danesmoor regular External

Greenstar Danesmoor regular Utility

Greenskies Solar-Lux, Solar-Lifestyle, Solar-Lito, Solar-Lito Mini and Greenstore TC series

Page 8: NEW - Oil Tanks | Steel, Fuel Dispensing & Bunded Oil Tanks › wp-content › uploads › ... · Oilfit flexible flue liner 57 - 58 Accessories 59 - 62 Worcester training 63 - 65

8 *Source: Worcester Customer Satisfaction Index 2011

Given the competitive nature of the heating industry, Worcester

know that installers have an important decision to make when it

comes to selecting the best product for their customers. Many

installers are loyal to the Worcester brand and recognise the

importance of the technical support and training Worcester offers.

At Worcester, we pride ourselves on the hard work that goes on

behind the scenes to make sure you and your customers benefi t

from much more than the best in high-effi ciency boilers and

renewable technologies.

For example, within the product reliability department, every

Worcester Greenstar oil-fi red boiler is tested. The testing procedure

certifi es that every boiler has been put through its paces in the

most extreme of conditions to ensure they are robust enough to

stand up to the highest of demands and toughest of environments.

We collect information on each individual component when we

fi eld trial our appliances, whilst also systematically noting any

feedback from the service engineer who worked on the boilers.

This information, along with responses from installers, is constantly

processed to ensure all technical observations can be acted upon

as a matter of urgency. It is this commitment that ultimately

ensures that Worcester products remain the best they can be.

“ 9 out of 10 professional installers would choose

Worcester for their own home”*

Andy Rose, ACR Heating Services

Why choose Worcester oil?

Did you know?

• For testing purposes Worcester has its own formula to

replicate contaminated heating system water. This mix

contains iron dust, quartz sand, hemp fi bre and other

impurities which are commonly found in system

water samples.

• Test boilers are positioned on a shaker table for 3 hours

before being set to vibrate across a range of frequencies

to simulate 3,000 miles of worldwide transport.

• Parts in the hydraulic circuit complete 300,000 water

pressure cycles to ensure optimum performance

is achieved.

• We have received a Royal Warrant in recognition of

supplying goods to Her Majesty, the Queen, an honour

we have held since 2003.

• With over 100 people in the quality control team

on-site, Worcester has more quality control engineers

than salesmen.

• As part of the global Bosch Group, Worcester has access

to world leading resources, including a corporate research

department and access to the very latest manufacturing

and product development processes.

• Each new Worcester appliance design is ‘fi eld trialled’ for

at least 1 winter period. To benefi t from winter conditions

all year round, outside of the British winter, products are

tested overseas.

• Every boiler receives an end of line full functional test

before it leaves the factory.

By appointment to Her Majesty The Queen

Boiler Manufacturer Worcester, Bosch Group T/A

Bosch Thermotechnology Ltd.

Page 9: NEW - Oil Tanks | Steel, Fuel Dispensing & Bunded Oil Tanks › wp-content › uploads › ... · Oilfit flexible flue liner 57 - 58 Accessories 59 - 62 Worcester training 63 - 65

9

In addition to our own extensive testing and research, we

also listen and respond to installers as part of our product

development programme.

As a result of such feedback, we have brought about the

following distinct features that benefi t the installer.

Easy installation

The fi rst thing that you will notice is that the new Greenstar

Danesmoor models are between 13 and 17kg lighter than

the previous Greenstar Camray.

The hydraulic connections have been optimised based

on the feedback received from our customers during the

development process. This new plumbing arrangement

allows the installer to make all the connections within the

cabinet at the back of the boiler, saving time and hassle.

Further improvements include an oil line which is run

through the cabinet, as well as an oil isolation valve which

mounts on an easy-to-access bracket on the right hand side

of the primary heat exchanger. There is also space on the

bracket for the installation of a second oil isolation valve if

you are utilizing a twin pipe system.

Finally, the new Greenstar Danesmoor boilers retain the

internal condensate trap from the previous models, which

utilises a simple condensate pipe connection. The height

of the trap removes the need for a condensate pump in

most instances.

Simple servicing

The new Greenstar Danesmoor range has increased

serviceability at its heart.

Based on installer feedback, the Greenstar Danesmoor

has been created to make servicing as simple and quick as

possible, with the new layout enabling an annual service to

take place completely from the front of the boiler.

Cleaning the primary heat exchanger is now made easy

due to the one piece primary baffl es which can be quickly

removed for cleaning via the combustion chamber door.

The baffl es have been made from a specially selected

grade of temperature-resistant stainless steel. Testing has

shown that the baffl e design should not stick allowing

hassle-free removal.

The secondary heat exchanger baffl es continue to use the

folded mesh design that has been a marked success in

previous Greenstar oil-fi red boilers.

Designed with installation and servicing in mind

Greenstar Danesmoor regular

Page 10: NEW - Oil Tanks | Steel, Fuel Dispensing & Bunded Oil Tanks › wp-content › uploads › ... · Oilfit flexible flue liner 57 - 58 Accessories 59 - 62 Worcester training 63 - 65

10

Burner lead

Flue overheat reset button

Temperature control

Demand indicator

Lock-out indicator

Primary heat exchanger access door

Internal condensate trap

Oil supply isolating valve

Flue gas analyser test point (behind control box)

Boiler overheat reset button

Optional digital plug-in programmer

Flue manifold and secondary heat exchanger access door

Burner

Primary heat exchanger

Inside story – Greenstar Danesmoor regular condensing boiler

NEW

Flow 1" BSP

Secondary heat exchanger

Flue connection

Flue gas analyser test point

Return 22mm (12/18, 18/25)

28mm (25/32)

Page 11: NEW - Oil Tanks | Steel, Fuel Dispensing & Bunded Oil Tanks › wp-content › uploads › ... · Oilfit flexible flue liner 57 - 58 Accessories 59 - 62 Worcester training 63 - 65

11

Technical data

BoilerGreenstar Danesmoor

regular 12/18Greenstar Danesmoor

regular 18/25Greenstar Danesmoor

regular 25/32

Height 855mm 855mm 855mm

Width 370mm 370mm 370mm

Depth 600mm 600mm 600mm

Weight – lift 86kg 89kg 93kg

2005 SEDBUK value 93.2% / A rated 93.0% / A rated 92.8% / A rated

2009 SEDBUK value 91.1% 90.9% 90.7%

Solar compatible

Heating flow / return connections 1 inch BSP, 22mm 1 inch BSP, 22mm 1 inch BSP, 28mm

Condensate connection (polypropylene) 21.5mm 21.5mm 21.5mm

Oil connection 10mm 10mm 10mm

Primary water content 20 ltr 21 ltr 22 ltr

Output to central heating 12 - 18kW 18 - 25kW 25 - 32kW

Oil burner Riello RDB 2.2 Riello RDB 2.2 Riello RDB 2.2

Optional plug-in twin channel digital controls

Maximum primary static head 30m 30m 30m

Minimum primary static head 1m 1m 1m

Water side resistance 20ºC 20mbar 30mbar 56mbar

Exhaust flue gas mass flow 29kg/hr 40kg/hr 51kg/hr

Control thermostat range 55/81ºC 55/81ºC 55/81ºC

Power supply 230V, 50Hz 230V, 50Hz 230V, 50Hz

Maximum power consumption 150W 150W 150W

Flue reset overheat thermostat (cut out) 110ºC 110ºC 110ºC

Boiler manual reset overheat thermostat (cut out) 105ºC 105ºC 105ºC

Boiler high limit thermostat (cut out) 95ºC 95ºC 95ºC

Minimum diameter flue (CF) 100mm 100mm 100mm

Flue diameter (RS) 80/125mm 80/125mm 80/125mm

Maximum horizontal flue RS 6,000mm 6,000mm 6,000mm

Maximum vertical flue RS 8,000mm 8,000mm 8,000mm

Maximum hearth temperature <100ºC <100ºC <100ºC

Page 12: NEW - Oil Tanks | Steel, Fuel Dispensing & Bunded Oil Tanks › wp-content › uploads › ... · Oilfit flexible flue liner 57 - 58 Accessories 59 - 62 Worcester training 63 - 65

12

Inside story – Greenstar Danesmoor regular Utility condensing boiler

NEW

Boiler overheat reset button

Burner lead

Flue overheat reset button

Temperature control

Primary heat exchanger access door

Internal condensate trap

Oil supply isolating valve

Burner

Primary heat exchanger

Flue manifold and secondary heat exchanger access door

Flow 1" BSP

Secondary heat exchanger

Flue connection

Flue gas analyser test point

Return 22mm (12/18, 18/25)

28mm (25/32)

Page 13: NEW - Oil Tanks | Steel, Fuel Dispensing & Bunded Oil Tanks › wp-content › uploads › ... · Oilfit flexible flue liner 57 - 58 Accessories 59 - 62 Worcester training 63 - 65

13

Technical data

BoilerGreenstar Danesmoor regular Utility 12/18

Greenstar Danesmoor regular Utility 18/25

Greenstar Danesmoor regular Utility 25/32

Height 855mm 855mm 855mm

Width 370mm 370mm 370mm

Depth 600mm 600mm 600mm

Weight – lift 86kg 89kg 93kg

2005 SEDBUK value 93.2% / A rated 93.0% / A rated 92.8% / A rated

2009 SEDBUK value 91.1% 90.9% 90.7%

Solar compatible

Heating flow / return connections 1 inch BSP, 22mm 1 inch BSP, 22mm 1 inch BSP, 28mm

Condensate connection (polypropylene) 21.5mm 21.5mm 21.5mm

Oil connection 10mm 10mm 10mm

Primary water content 20 ltr 21 ltr 22 ltr

Output to central heating 12 - 18kW 18 - 25kW 25 - 32kW

Oil burner Riello RDB 2.2 Riello RDB 2.2 Riello RDB 2.2

Optional plug-in twin channel digital controls N/A N/A N/A

Maximum primary static head 30m 30m 30m

Minimum primary static head 1m 1m 1m

Water side resistance 20ºC 20mbar 30mbar 56mbar

Exhaust flue gas mass flow 29kg/hr 40kg/hr 51kg/hr

Control thermostat range 55/81ºC 55/81ºC 55/81ºC

Power supply 230V, 50Hz 230V, 50Hz 230V, 50Hz

Maximum power consumption 150W 150W 150W

Flue reset overheat thermostat (cut out) 110ºC 110ºC 110ºC

Boiler manual reset overheat thermostat (cut out) 105ºC 105ºC 105ºC

Boiler high limit thermostat (cut out) 95ºC 95ºC 95ºC

Minimum diameter flue (CF) 100mm 100mm 100mm

Flue diameter (RS) 80/125mm 80/125mm 80/125mm

Maximum horizontal flue RS 6,000mm 6,000mm 6,000mm

Maximum vertical flue RS 8,000mm 8,000mm 8,000mm

Maximum hearth temperature <100ºC <100ºC <100ºC

Page 14: NEW - Oil Tanks | Steel, Fuel Dispensing & Bunded Oil Tanks › wp-content › uploads › ... · Oilfit flexible flue liner 57 - 58 Accessories 59 - 62 Worcester training 63 - 65

14

Inside story – Greenstar Danesmoor regular External condensing boiler

Flue gas analyser test point

Temperature control

Flue overheat reset button

Primary heat exchanger access door

Primary heat exchanger

Burner

Burner lead

Flue manifold and secondary heat exchanger access

Internal condensate trap

Oil supply isolating valve

Boiler overheat reset button

Service mode switch

NEW

Flow 1" BSP

Secondary heat exchanger

Flue connection

Flue gas analyser test point

Return 22mm (12/18, 18/25)

28mm (25/32)

Page 15: NEW - Oil Tanks | Steel, Fuel Dispensing & Bunded Oil Tanks › wp-content › uploads › ... · Oilfit flexible flue liner 57 - 58 Accessories 59 - 62 Worcester training 63 - 65

15

Technical data

BoilerGreenstar Danesmoor regular External 12/18

Greenstar Danesmoor regular External 18/25

Greenstar Danesmoor regular External 25/32

Height 950mm 950mm 950mm

Width 565mm 565mm 565mm

Depth 780mm 780mm 780mm

Weight – lift 99kg 102kg 106kg

2005 SEDBUK value 93.2% / A rated 93.0% / A rated 92.8% / A rated

2009 SEDBUK value 91.1% 90.9% 90.7%

Solar compatible

Heating flow / return connections 1 inch BSP, 22mm 1 inch BSP, 22mm 1 inch BSP, 28mm

Condensate connection (polypropylene) 21.5mm 21.5mm 21.5mm

Oil connection 10mm 10mm 10mm

Primary water content 20 ltr 21 ltr 22 ltr

Output to central heating 12 - 18kW 18 - 25kW 25 - 32kW

Oil burner Riello RDB 1 Riello RDB 2.2 Riello RDB 2.2

Optional plug-in twin channel digital controls N/A N/A N/A

Maximum primary static head 30m 30m 30m

Minimum primary static head 1m 1m 1m

Water side resistance 20ºC 20mbar 30mbar 56mbar

Exhaust flue gas mass flow 29kg/hr 40kg/hr 51kg/hr

Control thermostat range 55/81ºC 55/81ºC 55/81ºC

Power supply 230V, 50Hz 230V, 50Hz 230V, 50Hz

Maximum power consumption 150W 150W 150W

Flue reset overheat thermostat (cut out) 110ºC 110ºC 110ºC

Boiler manual reset overheat thermostat (cut out) 105ºC 105ºC 105ºC

Boiler high limit thermostat (cut out) 95ºC 95ºC 95ºC

Balanced flue kit Supplied in boiler case Supplied in boiler case Supplied in boiler case

Flue diameter 80/125mm 80/125mm 80/125mm

Maximum hearth temperature <100ºC <100ºC <100ºC

Ingress protection rating IP45 IP45 IP45

Page 16: NEW - Oil Tanks | Steel, Fuel Dispensing & Bunded Oil Tanks › wp-content › uploads › ... · Oilfit flexible flue liner 57 - 58 Accessories 59 - 62 Worcester training 63 - 65

16

Inside story – Greenstar Danesmoor WM regular condensing boiler series

Secondary heat exchanger

Flue cowl

Burnerservice hook

Primary heat exchanger

Temperature control

Thermostat phial pockets

Drip tray

Condense trap

Push fit flow and return burner air duct pipework connections

Riello RDB burner

Optional digital plug-in programmer

Control panel

Page 17: NEW - Oil Tanks | Steel, Fuel Dispensing & Bunded Oil Tanks › wp-content › uploads › ... · Oilfit flexible flue liner 57 - 58 Accessories 59 - 62 Worcester training 63 - 65

17

Technical data

BoilerGreenstar Danesmoor

WM 12/18Greenstar Danesmoor

WM 18/25

Height 880mm 880mm

Width 600mm 600mm

Depth 410mm 410mm

Weight – lift 72kg 72kg

2005 SEDBUK value 92.6% / A rated 92.8% / A rated

2009 SEDBUK value 90.7% 90.7%

Solar compatible

Heating flow / return connections 22mm copper 22mm copper

Condensate connection (polypropylene) 21.5mm plastic pipe 21.5mm plastic pipe

Oil connection 10mm 10mm

Primary water content 23 ltr 23 ltr

Output to central heating 12 - 18kW 18 - 25kW

Oil burner Riello RDB 1 Riello RDB 2.2

Optional plug-in twin channel digital controls

Maximum primary static head 30m 30m

Minimum primary static head 1m 1m

Water side resistance 20ºC 30mbar 69mbar

Exhaust flue gas mass flow 29kg/hr 40kg/hr

Control thermostat range 55/81ºC 55/81ºC

Power supply 230V, 50Hz 230V, 50Hz

Maximum power consumption 150W 160W

Flue reset overheat thermostat (cut out) 110ºC 110ºC

Boiler manual reset overheat thermostat (cut out) 105ºC 105ºC

Boiler high limit thermostat (cut out) 95ºC 95ºC

Minimum diameter flue (RS) 80/125mm 80/125mm

Maximum horizontal flue RS (125mm dia.) 4,000mm 4,000mm

Maximum vertical flue RS (125mm dia.) 6,000mm 6,000mm

Ingress protection rating IP20 IP20

Page 18: NEW - Oil Tanks | Steel, Fuel Dispensing & Bunded Oil Tanks › wp-content › uploads › ... · Oilfit flexible flue liner 57 - 58 Accessories 59 - 62 Worcester training 63 - 65

18

Inside story – Greenstar Utility regular condensing boiler series

Burner leadBurner

Primary heat exchanger service

access door

Flue gas analysis point

Service access door to secondary heat exchanger

Burner combustion air hose (RS only)

Multi-directional flue outlet box (RS only)

Burner control box

Thermostat pocket

Data label

Lock out reset button

Return

Flue gas overheat thermostat

Air vent to secondary heat exchanger

Flow

Flue gasreset button

Overheat thermostat reset button

Temperature control

Greenstar Utility regular fascia

Page 19: NEW - Oil Tanks | Steel, Fuel Dispensing & Bunded Oil Tanks › wp-content › uploads › ... · Oilfit flexible flue liner 57 - 58 Accessories 59 - 62 Worcester training 63 - 65

1919

BoilerGreenstar

Utility regular 32/50Greenstar

Utility regular 50/70

Height 1,012mm 1,012mm

Width 520mm 520mm

Depth 815mm 815mm

Weight – lift 270kg 280kg

2005 SEDBUK value 93.0% / A rated 92.5% / A rated

2009 SEDBUK value 90.0% 90.5%

Solar compatible

Heating flow / return connections 1½ inch BSP/28mm 1½ inch BSP/28mm

Condensate connection (polypropylene) 21.5mm plastic pipe 21.5mm plastic pipe

Oil connection 10mm 10mm

Primary water content 50 ltr 51 ltr

Output to central heating 32 - 50kW 50 - 70kW

Oil burner Riello RDB 3.2 Riello RDB 4.2

Open primary vent 1½ inch BSP 1½ inch BSP

Primary cold feed 1½ inch BSP 1½ inch BSP

Maximum primary static head 30m 30m

Minimum primary static head 1m 1m

Water side resistance 20ºC 26mbar 40mbar

Exhaust flue gas mass flow 76kg/hr 106kg/hr

Power supply 230V, 50Hz 230V, 50Hz

Maximum power consumption 190W 220W

Flue reset overheat thermostat (cut out) 120ºC 120ºC

Boiler manual reset overheat thermostat (cut out) 110ºC 110ºC

Boiler high limit thermostat (cut out) 100ºC 100ºC

Minimum diameter flue (CF) 130mm 130mm

Minimum diameter flue (RS) 100/150mm 100/150mm

Maximum horizontal flue RS (150mm dia.) 3,000mm 3,000mm

Maximum vertical flue RS (150mm dia.) 6,000mm 6,000mm

Maximum hearth temperature <100ºC <100ºC

Ingress protection rating IP20 IP20

Technical data

Page 20: NEW - Oil Tanks | Steel, Fuel Dispensing & Bunded Oil Tanks › wp-content › uploads › ... · Oilfit flexible flue liner 57 - 58 Accessories 59 - 62 Worcester training 63 - 65

20

Inside story – Greenstar Danesmoor System condensing boiler series

Boiler overheat reset button

Temperature control

Demand indicator

Pressure gauge

Flue overheat reset button (under control box)

Expansion vessel

Circulating pump

Expansion vessel bracket

Burner

Flue gas analyser test point (behind control box)

Primary heat exchanger access door

Internal condensate trap

Lock-out indicator

Optional digital plug-in programmer

NEW

Flow 1" BSP

Pressure relief valve

Secondary heat exchanger

Flue connection

Flue gas analyser test point

Return 22mm (12/18, 18/25)

28mm (25/32)

Page 21: NEW - Oil Tanks | Steel, Fuel Dispensing & Bunded Oil Tanks › wp-content › uploads › ... · Oilfit flexible flue liner 57 - 58 Accessories 59 - 62 Worcester training 63 - 65

21

BoilerGreenstar Danesmoor

System 12/18Greenstar Danesmoor

System 18/25Greenstar Danesmoor

System 25/32

Height 855mm 855mm 855mm

Width 370mm 370mm 370mm

Depth 600mm 600mm 600mm

Weight – lift 95kg 98kg 102kg

2005 SEDBUK value 93.2% / A rated 93.0% / A rated 92.8% / A rated

2009 SEDBUK value 91.1% 90.9% 90.7%

Solar compatible

Heating flow / return connections 22mm 22mm 28mm

Condensate connection (polypropylene) 21.5mm 21.5mm 21.5mm

Oil connection 10mm 10mm 10mm

Primary water content 20 ltr 21 ltr 22 ltr

Output to central heating 12 - 18kW 18 - 25kW 25 - 32kW

Oil burner Riello RDB 2.2 Riello RDB 2.2 Riello RDB 2.2

Optional plug-in twin channel digital controls

Water side resistance 20ºC 20mbar 30mbar 56mbar

Available pump head 20ºC 5.2 mH2O 4.3 mH2O 4.1 mH2O

Exhaust flue gas mass flow 29kg/hr 40kg/hr 51kg/hr

Control thermostat range 55/81ºC 55/81ºC 55/81ºC

Power supply 230V, 50Hz 230V, 50Hz 230V, 50Hz

Maximum power consumption 208W 208W 208W

Flue reset overheat thermostat (cut out) 110ºC 110ºC 110ºC

Boiler manual reset overheat thermostat (cut out) 105ºC 105ºC 105ºC

Boiler high limit thermostat (cut out) 95ºC 95ºC 95ºC

Minimum diameter flue (CF) 100mm 100mm 100mm

Flue diameter (RS) 80/125mm 80/125mm 80/125mm

Maximum horizontal flue RS 6,000mm 6,000mm 6,000mm

Maximum vertical flue RS 8,000mm 8,000mm 8,000mm

Maximum hearth temperature <100ºC <100ºC <100ºC

Ingress protection rating IP20 IP20 IP20

Technical data

Page 22: NEW - Oil Tanks | Steel, Fuel Dispensing & Bunded Oil Tanks › wp-content › uploads › ... · Oilfit flexible flue liner 57 - 58 Accessories 59 - 62 Worcester training 63 - 65

22

Inside story – Greenstar Danesmoor System Utility condensing boiler series

Flue overheat reset button (under control box)

Boiler overheat reset button

Burner lead

Temperature control

Expansion vessel

System pressure gauge

Circulating pump

Expansion vessel bracket

Burner

Flue gas analyser test point (behind control box)

Primary heat exchanger access door

Internal condensate trap

NEW

Flow 1" BSP

Pressure relief valve

Secondary heat exchanger

Flue connection

Flue gas analyser test point

Return 22mm (12/18, 18/25)

28mm (25/32)

Page 23: NEW - Oil Tanks | Steel, Fuel Dispensing & Bunded Oil Tanks › wp-content › uploads › ... · Oilfit flexible flue liner 57 - 58 Accessories 59 - 62 Worcester training 63 - 65

23

BoilerGreenstar Danesmoor System Utility 12/18

Greenstar Danesmoor System Utility 18/25

Greenstar Danesmoor System Utility 25/32

Height 855mm 855mm 855mm

Width 370mm 370mm 370mm

Depth 600mm 600mm 600mm

Weight – lift 95kg 98kg 102kg

2005 SEDBUK value 93.2% / A rated 93.0% / A rated 92.8% / A rated

2009 SEDBUK value 91.1% 90.9% 90.7%

Solar compatible

Heating flow / return connections 22mm 22mm 28mm

Condensate connection (polypropylene) 21.5mm 21.5mm 21.5mm

Oil connection 10mm 10mm 10mm

Primary water content 20 ltr 21 ltr 22 ltr

Output to central heating 12 - 18kW 18 - 25kW 25 - 32kW

Oil burner Riello RDB 2.2 Riello RDB 2.2 Riello RDB 2.2

Optional plug-in twin channel digital controls N/A N/A N/A

Water side resistance 20ºC 20mbar 30mbar 56mbar

Available pump head 20ºC 5.2 mH2O 4.3 mH2O 4.1 mH2O

Exhaust flue gas mass flow 29kg/hr 40kg/hr 51kg/hr

Control thermostat range 55/81ºC 55/81ºC 55/81ºC

Power supply 230V, 50Hz 230V, 50Hz 230V, 50Hz

Maximum power consumption 208W 208W 208W

Flue reset overheat thermostat (cut out) 110ºC 110ºC 110ºC

Boiler manual reset overheat thermostat (cut out) 105ºC 105ºC 105ºC

Boiler high limit thermostat (cut out) 95ºC 95ºC 95ºC

Minimum diameter flue (CF) 100mm 100mm 100mm

Flue diameter (RS) 80/125mm 80/125mm 80/125mm

Maximum horizontal flue RS 6,000mm 6,000mm 6,000mm

Maximum vertical flue RS 8,000mm 8,000mm 8,000mm

Maximum hearth temperature <100ºC <100ºC <100ºC

Ingress protection rating IP20 IP20 IP20

Technical data

Page 24: NEW - Oil Tanks | Steel, Fuel Dispensing & Bunded Oil Tanks › wp-content › uploads › ... · Oilfit flexible flue liner 57 - 58 Accessories 59 - 62 Worcester training 63 - 65

24

Inside story – Greenstar Danesmoor System External condensing boiler series

Expansion vessel

Flue gas analyser test point

Temperature control

Primary heat exchanger access door

Burner

Burner lead

Service mode switchPressure gauge

Combustion air inlet tube

Circulation pump

Internal condensate trap

NEW

Flow 1" BSP

Pressure relief valve

Secondary heat exchanger

Flue connection

Flue gas analyser test point

Return 22mm (12/18, 18/25)

28mm (25/32)

Page 25: NEW - Oil Tanks | Steel, Fuel Dispensing & Bunded Oil Tanks › wp-content › uploads › ... · Oilfit flexible flue liner 57 - 58 Accessories 59 - 62 Worcester training 63 - 65

25

BoilerGreenstar Danesmoor System External 12/18

Greenstar Danesmoor System External 18/25

Greenstar Danesmoor System External 25/32

Height 950mm 950mm 950mm

Width 565mm 565mm 565mm

Depth 780mm 780mm 780mm

Weight – lift 108kg 111kg 115kg

2005 SEDBUK value 93.2% / A rated 93.0% / A rated 92.8% / A rated

2009 SEDBUK value 91.1% 90.9% 90.7%

Solar compatible

Heating flow / return connections 22mm 22mm 28mm

Condensate connection (polypropylene) 21.5mm 21.5mm 21.5mm

Oil connection 10mm 10mm 10mm

Primary water content 20 ltr 21 ltr 22 ltr

Output to central heating 12 - 18kW 18 - 25kW 25 - 32kW

Oil burner Riello RDB 2.2 Riello RDB 2.2 Riello RDB 2.2

Optional plug-in twin channel digital controls N/A N/A N/A

Condensate trap

Available pump head 20ºC 5.2 mH2O 4.3 mH2O 4.1 mH2O

Exhaust flue gas mass flow 29kg/hr 40kg/hr 51kg/hr

Control thermostat range 55/81ºC 55/81ºC 55/81ºC

Power supply 230V, 50Hz 230V, 50Hz 230V, 50Hz

Maximum power consumption 208W 208W 208W

Flue reset overheat thermostat (cut out) 110ºC 110ºC 110ºC

Boiler manual reset overheat thermostat (cut out) 105ºC 105ºC 105ºC

Boiler high limit thermostat (cut out) 95ºC 95ºC 95ºC

Balanced flue kit Supplied in boiler case Supplied in boiler case Supplied in boiler case

Maximum hearth temperature <100ºC <100ºC <100ºC

Ingress protection rating IP45 IP45 IP45

Technical data

Page 26: NEW - Oil Tanks | Steel, Fuel Dispensing & Bunded Oil Tanks › wp-content › uploads › ... · Oilfit flexible flue liner 57 - 58 Accessories 59 - 62 Worcester training 63 - 65

26

Site preparations and guidance (internal models)

All materials used on open fl ue systems must be able to

sustain the corrosive elements present within the fl ue

gases from condensing boilers. Worcester’s Oilfi t fl exible

fl ue liner is available in a variety of lengths from 8m to 15m

and is suitable for the Greenstar range† (see installation

manual for further details or contact our Technical Support

Department). Guidance on the suitability of appropriate

materials should be sought from the fl ue manufacturer, if a

non-Worcester fl ue is to be installed. Worcester can supply

a fl exible fl ue liner suitable for CF chimney installations.

Siting of appliance

Greenstar Danesmoor regular, Danesmoor regular Utility,

Danesmoor System, Danesmoor System Utility and Utility

regular oil-fi red appliances are not suitable for external

installation unless a suffi cient enclosure is provided. The

fl oor must be fi rm and level.

The fl oor on which the boiler is to be mounted should be

capable of supporting an overall weight of approximately

140kg (Danesmoor) or 300kg (Utility regular). All models

have a hearth temperature of below 100°C removing the

need for a constructional hearth.

The appliances should be positioned on a non-combustible

solid base as near to the fl ue location point as possible.

Care should be taken to ensure that the appliance is level.

Siting of appliance (wall mounted models)

Wall mounted models are supplied with a wall mounting

frame and the primary pipework can be installed prior to

the installation of the appliance. The wall must be capable

of supporting the weight of the appliance, accessories and

water content, approximately 135kg. The appliance is not

suitable for external installation unless a suitable enclosure

is provided.

Flue system

The Greenstar Danesmoor regular, Danesmoor regular

Utility, Danesmoor System, Danesmoor System Utility and

Utility regular appliances can be connected to either a

conventional fl ue system or a multi-directional, room-sealed

balanced fl ue. In either case, the conventional fl ue adaptor

or the appropriate RS fl ue kit needs to be specifi ed. The

Greenstar Danesmoor WM is only suitable for use with a

room-sealed fl ue.

†Excluding external models

Installation of a Greenstar Oilfit RS flue system

The Greenstar Oilfit flexible flue liner

Page 27: NEW - Oil Tanks | Steel, Fuel Dispensing & Bunded Oil Tanks › wp-content › uploads › ... · Oilfit flexible flue liner 57 - 58 Accessories 59 - 62 Worcester training 63 - 65

27

600mm

1,200mm 570mm

300mm

100mm

100mm

1,155mm

DANESMOOR 18/25

max

min

!

Installation clearances

600mm

1,200mm 380mm

10mm or 300mm**

5mm*

5mm*

1,155mm

DANESMOOR 18/25

max

min

!

Service clearances

Note: *Remove the flue ‘knock-out’ panel sections if this clearance is less than 75mm. **Top: 300mm for maintenance and repair. Top: 10mm for annual service check.

600mm

1,415mm 540mm

300mm

10mm

10mm

1,312mm

Service clearances

600mm

1,415mm 720mm

300mm

100mm

100mm

1,297mm

Installation clearances

Greenstar Utility regular

600mm

1,010mm 620mm

300mm

10mm

10mm

1,380mm

200mm

Installation clearances

Greenstar Danesmoor WM

Installation and service clearances

The minimum clearances shown below should be allowed

for installation and servicing.

Greenstar Danesmoor regular, Danesmoor regular Utility,

Danesmoor System and Danesmoor System Utility

Page 28: NEW - Oil Tanks | Steel, Fuel Dispensing & Bunded Oil Tanks › wp-content › uploads › ... · Oilfit flexible flue liner 57 - 58 Accessories 59 - 62 Worcester training 63 - 65

28

Internal ventilation External ventilation

Compartment ventilationA Compartment

B Boiler

C Low level vent

D High level vent

E Air supply

Conventional flue† – minimum air vent area (cm2) for appliances installed in a compartment

Internal ventilation* External ventilation**

kW High level (D)

Low Level (C)

High level (D)

Low Level (C)

12/18 198 297 99 198

18/25 275 413 138 275

25/32 330 495 165 330

32/50 495 743 248 495

50/70 715 1,073 358 715

WM 12/18 198 297 99 198

WM 18/25 275 413 138 275

*Internal air to and from a space/room inside the building.**External air to and from directly outside the building.† Due to changes to BS 5410 and modern building design, these figures no longer incorporate the adventitious ventilation allowance.

Room-sealed flue† – minimum air vent area (cm2) for appliances installed in a compartment

Internal ventilation* External ventilation**

kW High level (D)

Low Level (C)

High level (D)

Low Level (C)

12/18 198 198 99 99

18/25 275 275 138 138

25/32 330 330 165 165

32/50 495 495 248 248

50/70 715 715 358 358

WM 12/18 198 198 99 99

WM 18/25 275 275 138 138

Air supply

Conventional Flue (CF)

An adequate supply of free air must be delivered to the boiler

for combustion purposes through a permanent inlet, such as

an air brick, into the area where the boiler is situated.

Combustion air must not be taken from bathroom or

bedroom areas.

Minimum area of air inlet for combustion*

kW Area

12/18 99cm2

18/25 138cm2

25/32 165cm2

32/50 248cm2

50/70 258cm2

WM 12/18 99cm2

WM 18/25 138cm2

* Due to changes to BS 5410 and modern building design, these figures no longer incorporate the adventitious ventilation allowance.

Compartment installation

Follow the requirements of BS 5410 and note:

• Minimum clearances must be maintained

• An access door is required to install, service and

maintain the boiler as well as any ancillary equipment,

i.e. condensate trap

• If fi tting the boiler into an airing cupboard use a non-

combustible material to separate the boiler from the airing

space. If the material is perforated, the holes must not

exceed 13mm.

Compartment ventilation

• Ventilation must be provided for boilers fi tted into

compartments as described in BS 5410

• Referring to the diagram below, a minimum of 2 air

vents must be fi tted, one at low level (C) and another

at high level (D) onto the same wall using the same

air (E) for circulation

• Free air must not be taken from a room or internal space

containing a bath or shower and must not communicate

with a protected area such as a hall, stairway, landing,

corridor, lobby, shaft, etc.

• Air vents must allow access for clean, free air and

must be sited to comply with the fl ue terminal

position requirements

• Air ducting runs must not exceed 3 metres.

• Low level air vents must be within 450mm from the fl oor

• A warning label must be added to the vents with a

statement to the effect: “Do not block this vent.

Do not use for storage”.

Page 29: NEW - Oil Tanks | Steel, Fuel Dispensing & Bunded Oil Tanks › wp-content › uploads › ... · Oilfit flexible flue liner 57 - 58 Accessories 59 - 62 Worcester training 63 - 65

29

600mm

600mm

2,250mm

600mm

600mm radius

750mm

750mm

2,250mm

2,250mm12 21

11 22 2,250mm

0

0

Conventional flued boilers must not be fitted in

a bathroom.

Important: bathroom locations and clearances

• The boiler must not be installed in zones 0, 1 or 2

• Any switch or appliance control which uses mains

electricity must not be within reach of a person using

the bath or shower

• Electrical switches, fused spurs and socket outlets must

not be situated in the bathroom.

Refer to the latest IEE wiring regulations.

855mm

600mm 370mm

DANESMOOR 18/25

max

min

!

Casing dimensions

Greenstar Danesmoor regular, Danesmoor regular Utility,

Danesmoor System and Danesmoor System Utility

1,012mm

815mm 520mm

Casing dimensions

Greenstar Utility regular

880mm

380mm

600mm410mm

30mm

Casing dimensions

Greenstar Danesmoor WM

Page 30: NEW - Oil Tanks | Steel, Fuel Dispensing & Bunded Oil Tanks › wp-content › uploads › ... · Oilfit flexible flue liner 57 - 58 Accessories 59 - 62 Worcester training 63 - 65

30

Pipework connections

The diagrams below show the fl ue and pipe outlets (mm):

Note: For servicing purposes, keep the condensate and pressure relief discharge pipes away from components and pipework connections.

Flue and pipe connections

Key Description 12/18 & 18/25

A Flow 22mm dia. copper

B Return 22mm dia. copper

C Primary drain hose connection ½" BSP

D Condensate outlet 21.5mm dia.

E Flue outlet 80/125mm dia.

Greenstar Danesmoor regular & Danesmoor regular Utility models

Flue and pipe connections

Key Description 12/18 & 18/25 25/32

A CH flow 1" dia. BSP 1" dia. BSP

B CH return 22mm dia. plain copper

28mm dia. plain copper

C Condensate outlet 21.5mm dia. 21.5mm dia.

D Flue outlet 80/125mm 80/125mm

Flue and pipe connections

Key Description 12/18 & 18/25 25/32

A CH flow 22mm dia. 28mm dia.

B CH return 22mm dia. plain copper

28mm dia. plain copper

C Condensate outlet 21.5mm dia. 21.5mm dia.

D Flue outlet 80/125mm 80/125mm

E Oil pipe isolating valve 10mm 10mm

FOptional oil line return line connection

10mm 10mm

G Pressure relief pipe 15mm dia. 15mm dia.

WEIV EDISWEIV TNORF

67

417

RS 155CF 170

712

747

825

50

A

C

A

B

C

D D

23

Pipework connections TOP VIEW

6935 67

21.5

100

A

C

D

GB

825

412

E

F

321

40

FRONT VIEW

Pipework connections

Greenstar Danesmoor System & Danesmoor System Utility models

Flue and pipe connections

Key Description 32/50 & 50/70

A CH flow/open vent 1½" dia. BSP

B Primary feed/drain 1½" dia. BSP

C CH return 28mm dia. plain ended copper

D Flue outlet 100/150mm

Pipework connections

Greenstar Utility regular models

188.5mm

191mm

C

108mm (B)153.5mm (D)

74.5mm (A)

FRONT VIEW SIDE VIEW

E

96.5mm

503.5mm

Pipework connections

Greenstar Danesmoor WM models

35

69

48 19

67

48

B

370

TOP VIEW

GA

Page 31: NEW - Oil Tanks | Steel, Fuel Dispensing & Bunded Oil Tanks › wp-content › uploads › ... · Oilfit flexible flue liner 57 - 58 Accessories 59 - 62 Worcester training 63 - 65

3131**Rear clearance flue outlet on side *Rear clearance flue outlet on rear

Site preparations and guidance (external models)

600mm

2,500mm600mm

BASE

FR

ON

T

600mm min.

FRONT

2,500mm*

45mm85mm

600mm

Planview

50mm**

10mm

600mm

2,500mm

FRONT

Plan view

FRONT

2,500mm10mm

600mm

Plan view

50mm**

Siting of appliance

The Greenstar Danesmoor External appliances are suitable

for external installation only. Appliances should be installed

at a suitable location onto a fi xed, permanent and rigid

surface. There must be suffi cient hard-standing around

the appliance to allow for servicing. Appliances must be

installed on a fl at, level surface to ensure that condensation

does not enter the primary heat exchanger. Appliances

should not be installed where there is a potential for

excessive ground water coverage. Tarmac and wood hard-

standings are not recommended.

Flue system

For all external boilers, consideration should be given to

the location of the appliance and its fl ue outlet in relation

to windows, doors and air vents. The Greenstar Danesmoor

regular and Danesmoor System External appliances can

be connected to the Greenstar Oilfi t External fl ue system

(supplied with the Danesmoor regular External) providing

balanced fl uing options at low level, high level or vertical

outlets (see page 52).

Installation and service clearances

The minimum clearances shown below should be allowed

for installation and servicing. It is strongly recommended

that the fl ue terminal faces away from walls to reduce the

possibility of “wetting” occurring. Care should be taken to

ensure that pipework leaving the appliance and entering

the building should not be exposed. The appliance should

be sited as close to the dwelling as possible.

565mm

950mm

780mm

Casing dimensions

Greenstar Danesmoor regular External and Greenstar Danesmoor System External

Side view Bird's eye view

Bird's eye viewBird's eye view

Page 32: NEW - Oil Tanks | Steel, Fuel Dispensing & Bunded Oil Tanks › wp-content › uploads › ... · Oilfit flexible flue liner 57 - 58 Accessories 59 - 62 Worcester training 63 - 65

32

Pipework connections Danesmoor System External

The diagrams below show the fl ue and pipe outlets (mm):

Note: For servicing purposes, keep the condensate and pressure relief discharge pipes away from components and pipework connections.

Rear

Right side

Danesmoor regular External flue and pipe connections

Description 12/18 & 18/25 25/32

CH flow/open vent 1" dia. BSP 1" dia. BSP

CH return 22mm dia. plain copper

28mm dia. plain copper

Flue outlet 80/125mm dia. 80/125mm dia.

Condensate outlet 21.5mm dia. 21.5mm dia.

Left side

Pipework connections Danesmoor regular External

The diagrams below show the fl ue and pipe outlets (mm):

Note: For servicing purposes, keep the condensate and pressure relief discharge pipes away from components and pipework connections.

Condensate

Flue

Services

PRV

Fire valve capillary& drain access

REAR

Rear

Right side

Left side

Flue

Services

Condensate

PRV

Oil

RIGHT HAND SIDE

Fire valve capillary& drain access

Flue

Services

Condensate

Oil

PRV

LEFT HAND SIDE

Danesmoor System External flue and pipe connections

Description 12/18 & 18/25 25/32

CH flow 22mm 28mm

CH return 22mm dia. plain copper

28mm dia. plain copper

Flue outlet 80/125mm dia. 80/125mm dia.

Condensate outlet 21.5mm dia. 21.5mm dia.

93

Flue Services

Condensate

Fire valve & drain access

Pressure relief valve

91

269

171

105

330

784 794

152

559

715

704

5594105

784

659

669

624.5

437

224

794

Flue Services

Condensate

Pressure relief valve

Fire valve & drain access

Oil

491.5

659679

699

625

492

327

784 794

Services

Condensate

Pressure relief valve

Oil

5590

715

124

Flue

Page 33: NEW - Oil Tanks | Steel, Fuel Dispensing & Bunded Oil Tanks › wp-content › uploads › ... · Oilfit flexible flue liner 57 - 58 Accessories 59 - 62 Worcester training 63 - 65

33

Installation requirements

Installation regulations

The appliance should be installed by a competent person

who is aware of the Health and Safety at Work Act. They

should take appropriate action to ensure that the regulations

are adhered to. In order to give optimum effi ciency and

trouble-free operation, the appliance must be commissioned

by a qualifi ed OFTEC engineer.

In particular, the installation of this appliance must be in

accordance with the relevant requirements of the following

British Standards and regulations in respect of the safe

installation of equipment:

The compliance with a British Standard does not, of itself,

confer immunity from legal obligations.

BS 5410: part 1 & 2: Code of Practice for Oil Fired Boilers.

BS 799: part 5: Specifi cation for Oil Storage Tanks.

BS 7593: Code of Practice for treatment of water in

domestic hot water central heating systems.

BS 5449: part 1: Specifi cation for forced circulation hot

water central heating for domestic premises.

BS 5955: part 8: Specifi cation for the installation of

thermoplastic pipes and associated fi ttings for use in

domestic hot and cold water services and heating systems.

BS 7291: Thermoplastic pipes and associated fi ttings for

hot and cold water for domestic purposes and heating

installations in buildings.

BS 7074: part 1: Application, selection and installation

of expansion vessels and ancillary equipment for sealed

water systems.

BS 7671: IEE Wiring Regulations, current edition.

Full British Standards requirements can be found on

the British Standards website.

The Building Regulations England and Wales, Scotland and

Northern Ireland.

Local water company bye-laws.

The Control of Pollution (Oil) Regulations.

OFTEC Standards

Sealed system installation

The Greenstar system oil-fi red appliances are designed for

sealed systems, incorporating a pre-plumbed expansion

vessel, pressure relief valve set to 3bar, automatic air

vent and pressure gauge. The expansion vessel fi tted to

the appliance will accommodate differing system volumes

depending on initial charge pressure and system pre-

pressurisation. Under certain circumstances the system

volume may be in excess of that catered for by the

expansion vessel provided. In this instance, an additional

vessel should be fi tted as close as possible to the return

connection of the appliance. Filling of the system can take

place from a make-up vessel, which should be fi tted with

a non-return valve above the highest point in the system.

Alternatively, and to comply with the new Water Authority

requirements, the system may be fi lled through a temporary

hose connection to the mains water supply, provided that a

double check valve assembly and test point are fi tted on the

system side of the temporary connection. Greenstar regular

boilers can be installed on a sealed system subject to an

appropriately sized expansion vessel, a 3bar pressure relief

valve and a fi lling link with pressure gauge being added.

Open vented primary systems

The feed and expansion cistern (E) must be positioned

to provide a static head (S) of at least 1 metre above the

highest point in the heating system to the water level in the

expansion tank (E).

The open vent pipe (H), feed and expansion pipe (F) must

rise continuously from the appliance.

The open vent pipe (H) must be at least 22mm dia.

A Appliance

C Automatic bypass valve

D Drain cock

E Feed and expansion cistern

F Feed and expansion 15mm dia. min

H Open vent 22mm dia. min

J Circulating pump

K Zone valve

L Lockshield valve

M Hot water cylinder

R Radiators

S Static head

T TRV

Typical open vent system

F

E

H

A

M

JC

K

K D D

T T

T TL L

L L

R

R

R

R

S1,000mm min.

150mm max.

Page 34: NEW - Oil Tanks | Steel, Fuel Dispensing & Bunded Oil Tanks › wp-content › uploads › ... · Oilfit flexible flue liner 57 - 58 Accessories 59 - 62 Worcester training 63 - 65

34

Radiator valves

Underfloor heating

• Plastic pipework used for underfloor heating must be

correctly controlled with a thermostatic blending valve,

limiting the temperature of the circuits to approximately

50ºC. A 20ºC temperature differential must also be

maintained at the appliance.

Primary system/connections/valves

• Do not use galvanised pipes or radiators.

• All system connections must be capable of sustaining a

pressure up to 3bar

• Radiator valves should conform to BS 2767:10

• All other valves should conform to BS 1010

• An automatic bypass valve must be connected between

the heating fl ow and return where TRVs are used on all

radiators. It should be fi tted to give at least a 3 metre

circuit when activated.

• Drain cocks are required at all of the lowest points on

the system

• Air vents are required at all of the high points on

the system.

Guarantee

Worcester oil-fi red appliances are offered with a 2 year*

guarantee on parts and labour from the date of installation

providing the appliance is commissioned upon installation

and the regular service requirements are met. The primary

heat exchanger comes with a

5 year* guarantee and the

secondary heat exchanger is

guaranteed for 10 years*.

Ongoing service and maintenance contracts can be

arranged through the Worcester Customer Service

Department if you do not wish to service or maintain

your customer's boiler.

*Terms and conditions apply.

Oil storage tank

4m

max

.

Full base (plastic tanks)

30

0m

mm

in.

Oil burner

Externalwall

Isolatingvalve

Isolatingvalve

Oil strainer& waterseparator

Oilsupplypipe

Fire valveto BS 5410

Oil pump

Isolatingvalve

Oil filter

Fire valvesensor

Fig. 10 Single pipe system

Oil storage tank

Full base (plastic tanks)

3.5

m m

ax.

Oil supply pipe

150mm

Oil burner

Isolatingvalve

Fire valvesensor

Oil filter

Oilpump

Externalwall

Fire valve to BS 5410

Non-return valveIsolatingvalve

Isolatingvalve

Oil strainer &water separator

Fig. 11 Two pipe system

Oil supply

**

Page 35: NEW - Oil Tanks | Steel, Fuel Dispensing & Bunded Oil Tanks › wp-content › uploads › ... · Oilfit flexible flue liner 57 - 58 Accessories 59 - 62 Worcester training 63 - 65

35

The oil burner on the Greenstar regular and system

oil-fi red appliances is supplied with a single fl exible fuel

line from the oil pump, which is connected to the main

oil supply line (via the oil isolation valve), within the

appliance. This enables the burner to be removed without

the need for disconnection of the fuel line.

The maximum permissible head is 4 metres. If the head is

greater, then a head breaking device must be incorporated

into the oil supply line.

The oil pump’s primary job is to pressurise the oil once in

the pump and force it out of the nozzle at high pressure to

atomise the fuel, ensuring clean and effi cient combustion.

This same pump can also be converted to ‘draw’ up the

fuel line in cases where the oil tank is lower than the

appliance’s burner. This conversion should be undertaken

by the installing engineer.

All oil pumps on Worcester appliances can easily be

converted to work on a two pipe system (details of

this operation are within the Installation and Servicing

instructions which come with the appliance).

More advice on fuel lines can be sought from OFTEC Book

Three as well as Technical sheet TI/134.

De-aeration devices

A de-aeration device is a container of oil, about the size of

a pint glass, with an automatic air vent on top as well as

three connections on the bottom. It removes the need to

run a return oil pipe back to the tank from the burner as

in Fig. 11. Its function is to provide a reservoir of oil from

which the oil pump draws. It also acts to vent any air in the

oil out to the atmosphere preventing a nuisance ‘lockout’

of the burner. Not all the oil drawn is consumed and any

excess is returned to the de-aeration device meaning that

whilst the burner is fi ring, there is a continuous fl ow and

return of oil. The third connection is for the main fuel line

from the oil tank. There is usually a non-return valve located

in this connection to prevent oil draining back towards the

oil tank under gravity which can create a vacuum. When

the burner is fi ring, the whole fuel supply system is under

negative pressure, i.e. suction, therefore it is imperative

that all joints on the fuel supply system are correct. Whilst

there may be no obvious signs of an oil leak externally,

when the burner is fi ring it may be possible for air to

be drawn in through a bad joint, reducing the pump’s

capabilities, resulting in a lack of fuel to the oil pump and

a nuisance ‘lockout’. This may manifest itself as a very low

level of oil or ‘foaming’ of the oil inside the de-aeration

device whilst the burner is trying to fi re.

Most de-aeration devices are made of plastic and vent

to the atmosphere. For this reason, they must always be

located externally. Metal types do exist which do not emit

vapour. These can be located internally or externally.

Top outlet oil tanks should have the non-return valve

removed from the end of the oil feed pipe within the

tank if installed in conjunction with a de-aeration device.

Supply pipe

The oil supply pipe itself would normally be annealed

copper tube with a protective plastic coating which is easily

manipulated around bends and usually enables the fuel line

to be run in a continuous length without joints. If joints

must be used, they must be accessible, even if underground

(via an access duct) and should be of the manipulative

type. Plastic pipe specifi cally for oil lines does exist and is

acceptable but must only be used underground.

Galvanised pipe, fi ttings and soldered joints must not be

used in oil lines.

More advice on fuel lines can be sought from OFTEC Book

Three as well as Technical sheet TI/134.

Oil burner

Oil pump

Full base (plastic tanks)

3.5

m m

ax.

Oil storage tank

Isolatingvalve Isolating

valve

Fire valve sensor

External wall

Fire valveto BS 5410

De-aerator

Oil supply pipe

Oil strainer & waterseparator

Fig. 12 Single pipe lift system with de-aerator

Page 36: NEW - Oil Tanks | Steel, Fuel Dispensing & Bunded Oil Tanks › wp-content › uploads › ... · Oilfit flexible flue liner 57 - 58 Accessories 59 - 62 Worcester training 63 - 65

36

Maximum allowable pipe run

Head 8mm inside dia. pipe (10mm OD copper)

10mm inside dia. pipe (12mm OD copper)

0m 50m 100m

-0.5m 44m 100m

-1.0m 38m 95m

-1.5m 32m 80m

-2.0m 26m 66m

-2.5m 20m 50m

-3.0m 14m 37m

-3.5m 8m 22m

Table 2: Double pipe sub-gravity feed system

Maximum allowable pipe run

Head 8mm inside dia. pipe (10mm OD copper)

10mm inside dia. pipe (12mm OD copper)

0.5m 12m 30m

1.0m 25m 69m

1.5m 37m 91m

2.0m 49m 100m

2.5m 62m 100m

3.0m 74m 100m

3.4m 87m 100m

4.0m 99m 100m

Table 1: Single pipe gravity feed system

Table 3: Single pipe suction lift with de-aerator

Maximum allowable run from tank to de-aerator

Fuel flow rate 2.5 (kg/h) 5 (kg/h) 10 (kg/h) 10 (kg/h)

Head 8mm dia. 8mm dia. 8mm dia. 10mm dia.

0m 100m 55m 26m 100m

0.5m 95m 45m 23m 100m

1.0m 80m 40m 20m 90m

1.5m 70m 35m 17m 75m

2.0m 60m 30m 14m 65m

2.5m 45m 25m 11m 50m

3.0m 35m 15m 8m 35m

3.5m 25m 10m 5m 20m

Supply pipe sizing

The diameter of the oil supply pipe itself is determined by

the distance from the oil tank to the appliance and the head

of oil whether it be positive or negative.

Tables 1 and 2 give the required diameter of supply pipe

when cross referenced with the head. Table 3 gives the

diameter of the supply pipe when the use of a de-aeration

device is made.

Oil tanks

For further information on oil tank location, please consult

the tank supplier.

Oil fi lters

Oil fi lters must always be incorporated in the oil supply line.

One should be fi tted on the outlet from the oil tank to fi lter

deposits from within the tank or fuel, and one should be

fi tted near the appliance to fi lter deposits from within the

fuel line itself. They are supplied and fi tted by the installing

engineer and are not part of the boiler’s components. It

should be possible to service them without the need for

draining down the fuel supply line. There must be suffi cient

clearance below the fi lter to enable servicing operations

to be carried out easily. Filters must comply to OFTEC

standard OFS E104.

Fire valves

A fi re valve is an essential part of the oil supply system. It

must be supplied and fi tted by the installing engineer and

is not part of the boiler’s components. Its purpose is to cut

off the fl ow of oil outside the building in the event of fi re

within the boiler area. The valve should be located on the

fuel line at the point of entry into the building. It must be

activated by a remote sensor located over the burner. A clip

is provided within the appliance for the sensor. Fire valves

must comply with OFTEC standard OFS E101.

Page 37: NEW - Oil Tanks | Steel, Fuel Dispensing & Bunded Oil Tanks › wp-content › uploads › ... · Oilfit flexible flue liner 57 - 58 Accessories 59 - 62 Worcester training 63 - 65

37

At the centre of this innovative design is a highly powerful

magnet that removes the magnetic debris (magnetite) that

is present in the heating system water. The central location

of the magnet ensures that magnetite is collected quickly

and retained, maximising the overall protection, a proven

technology that offers a capacity to collect up to 200g of

magnetite a year. Any non-magnetic debris is caught by the

twin-action cyclonic trap.

The Greenstar System Filter has been extensively

tested in simulated systems, proving its effectiveness

in removing iron oxide, magnetite, limescale particles,

casting sand, welding debris, non-magnetic metal fl akes,

paint particles and other system pollutants.

The Worcester Greenstar System Filter

Modern condensing boilers are precision engineered

and designed to run with a clean water heating system.

Over time, dirty system water will damage a boiler and

its components, causing failures as well as potentially

shortening the life of the overall system.

Damaged boiler and

system components

• Blockages in primary

heat exchanger

• Increased wear on pumps

• Blocked valves.

Reduced effi ciency

• Energy effi ciency loss equivalent to a boiler being

reduced from A rated effi ciency to D rated, resulting

in fuel wastage*

• Blocked radiators can reduce effi ciency and

heating comfort.

A highly effective solution

from the brand you can trust

The Worcester Greenstar

System Filter has been

specifi cally designed to

combat the damaging

effects of system debris

and pollutants, allowing

homeowners to protect their

boiler or heat pump for a

fraction of its cost. The fi lter

is suitable for any 22mm piped heating systems.

Features Benefits

Highly effective filter

Safeguards the boiler against damage and protects the efficiency of the system. Saves up to 6% a year on energy bills*

Prevent blockages in radiators A warmer home and quieter system

High powered internal magnetProven technology that can capture up to 200g of magnetite

Cylindrical design Increased performance – better installation options

Twin-action – magnetic and non-magnetic filtration

Instantly effective against a wide range of system debris

No power consumption or moving parts

No electrical wiring connection or supply needed. Zero running costs and no failure of components

Can be installed under the boiler or away from the appliance

Flexibility

One-way valve for adding system chemicals

Removes the need to isolate a section of the system when carrying out servicing and maintenance

Worcester, Bosch Group specification and design

Reliability of components and filter

*Independent research carried out by GASTEC at CRE

The Greenstar System Filter is easy to install and service

A circulating pump damaged by system debris and pollutants

Installation

The fi lter can be installed almost anywhere in a heating

system. However, to maximise the effectiveness, it should

be placed before the boiler and after the last radiator.

Product infoPart number 7 716 192 609

NEW

Page 38: NEW - Oil Tanks | Steel, Fuel Dispensing & Bunded Oil Tanks › wp-content › uploads › ... · Oilfit flexible flue liner 57 - 58 Accessories 59 - 62 Worcester training 63 - 65

38

For full technical information on pipe size, insulation

and different condensate pipework methods, please

see Installation, Commissioning and Servicing

Instruction Manual.

Important points to consider when siting a condensate

drainage pipe:

• Where a new or replacement boiler is being installed,

access to an internal “gravity discharge” point should

be one of the factors considered in determining

boiler location

• The condensate pipe must be a minimum of 22mm dia.

plastic pipe

• The condensate pipework must fall at least 52mm per

metre towards the outlet and should take the shortest

practicable route

• Ensure there are no blockages in the pipe run.

Internal connections

In order to minimise risk of freezing during prolonged cold

spells, the following methods of installing a condensate

drainage pipe should be adopted, in order of priority.

Wherever possible, the condensate drainage pipe should be

routed and terminated so that the condensate drains away

from the boiler under gravity to a suitable internal foul water

discharge point such as an internal soil and vent stack.

A suitable permanent connection to the foul waste pipe

should be used. (see fi g. 1)

Condensate pipework

Condensatedischarge from boiler

Universalconnector

Soil andvent stack

22mm dia. Min. 450mmand up to three storeys

Fig. 1 Disposal to soil vent stack (internal and external models). For external models increase pipe size and insulate pipework.

Alternatively if the fi rst option is not possible, an internal

kitchen or bathroom waste pipe, washing machine waste

pipe, etc. can be used. (see fi g. 2)

22mm dia.

Condensatedischarge from boiler

Universalconnector

Visible air breakat plug hole

Sink or basin with integrated overflow

75mm sinkwaste trap

75mmmin.

Fig. 2 Disposal to a waste pipe (internal models)

Condensatedischarge from boiler

Universalconnector 22mm dia.

Visible air breakat plug hole Sink or

basin with integrated overflow

75mm sinkwaste trap

75mmmin.

Condensatepump

Fig. 3 Condensate pump disposal (internal models)

Condensate pump

Where “gravity discharge” to an internal termination is not

physically possible, or where very long internal runs would

be required to reach a suitable discharge point, condensate

should be removed using a proprietary condensate pump,

of a specifi cation recommended by the boiler or condensate

pump manufacturer.

The pump outlet pipe should discharge to a suitable

internal foul water discharge point such as an internal soil

and vent stack, internal kitchen or bathroom waste pipe,

washing machine waste pipe etc. A suitable permanent

connection to the foul waste pipe should be used.

(see fi g. 3 and 4)

Universalconnector

22mm dia.Condensatedischarge from boiler

Pipeworktransition Insulate &

increase pipe size to 32mm

25

mm

min

.

Condensatepump

Fig. 4 Condensate pump to external disposal (internal models)

Page 39: NEW - Oil Tanks | Steel, Fuel Dispensing & Bunded Oil Tanks › wp-content › uploads › ... · Oilfit flexible flue liner 57 - 58 Accessories 59 - 62 Worcester training 63 - 65

39

Condensatedischarge from boiler Universal

connector

Pipeworktransition

Insulate &increase pipe size to 32mm

Externalrain waterpipe intofoul water

External air break

Air gap

PVCu strapon fitting

43mm 90ºmale/female bend

22mm dia.

Fig. 6 Disposal into a rainwater down pipe (internal and external models). For external models increase pipe size and insulate pipework.

UNSUITABLE FOR CLAY SOIL TYPES

22mm dia. 400mm min.

25mm min.

500mm min.

25mm

25mm25mm

50mm

300mm

100mm dia.

Drainageholes12mm dia.

100mmdia. min.plasticpipe

Pipeworktransition

Condensatedischarge from boiler

Universalconnector

Insulate &increase pipesize to 32mm

100mm dia.min. plasticpipeLimestonechippings

Drainageholes

Bottom of sealed tube

Fig. 5 Soak away (internal and external models). For external models increase pipe size and insulate pipework.

In addition to the condensate discharge options illustrated

on these pages and in the Installation, Commissioning

and Servicing Instruction Manual, the new Worcester

CondenseSure auxiliary siphon provides an innovative

alternative for the prevention of freezing for externally run

discharge condensate (see pages 40-41 for details).

External connections

Freezing conditions

• Pipework length should be kept to a minimum and the

route should be as vertical as possible

• A Worcester CondenseSure auxiliary siphon may be

used to reduce the risk of freezing

• Where pipework is subjected to extreme cold or wind

chill, a form of weather-proof insulation should be used.

Condensate waste

• Care should be taken when siting a soak away to avoid

obstructing existing services.

If no other discharge method is possible, then the use of

an externally-run condensate drainage pipe terminating at

a suitable foul water discharge point, or purpose-designed

soak away, may be considered (see fi g. 5).

If this method is chosen, then the following measures

should be adopted:

• The external run should be kept as short as possible

and not exceed 3m

• A CondenseSure auxiliary siphon may be used to reduce

the risk of freezing

• The pipe should be run internally as far as possible

before going externally and the pipe diameter should be

increased to 32mm before it passes through the wall to

the exterior. The pipe should be insulated using suitable

waterproof and weather resistant insulation

• The external pipe should take the shortest and least

exposed route to the discharge point, and should “fall”

as steeply as possible away from the boiler, without

horizontal runs in which condensate might stand

• The use of fi ttings, elbows, etc., should be kept to a

minimum and any internal “burrs” on cut pipework

should be removed so that the internal pipe section is

as smooth as possible.

Fitting an external air break

• Refer to Fig 6. When a rainwater down pipe (which goes

directly into a sewer that carries both rain water and

foul water) is used to dispose of condensate, an air

break must be installed. It should be fi tted on the

43mm pipework, between the boiler condensate outlet

and the drainpipe. The installation should take place

outside the property to avoid fl ooding during adverse

weather conditions.

Page 40: NEW - Oil Tanks | Steel, Fuel Dispensing & Bunded Oil Tanks › wp-content › uploads › ... · Oilfit flexible flue liner 57 - 58 Accessories 59 - 62 Worcester training 63 - 65

40

With temperatures as low as -20ºC being experienced

in very cold winters, practices such as externally run

condensate discharge pipework are now being questioned.

In these conditions the condensate pipe on a condensing

oil-fi red boiler can freeze. This can lead to a blocked

condensate pipe, which will cause condensate to drain

back into the boiler leading to corrosion of mild steel

components and leakage of condensate. This can result

in premature component failure, damage to property and

burner failure.

The Worcester CondenseSure auxiliary siphon has been

designed to allow a more fl exible approach to boiler siting.

Tested to extreme temperatures

The Worcester CondenseSure auxiliary siphon has been

extensively tested under simulated extreme weather

conditions, proving its effectiveness in preventing frozen

condensate at -15ºC for a sustained period of 48 hours.

CondenseSure principle of operation

Most oil-fi red condensing boilers have a trap which

releases condensate as it is formed. A typical A-rated

condensing boiler will generate up to 2 litres of

condensate an hour (dependent on output and

temperature) which is discharged as a continuous

trickle. With this frequency of discharge, the condensate

pipework is never empty of condensate, consequently

increasing the potential for freezing of the pipework in

prolonged sub-zero temperatures.

The CondenseSure siphon connects to the boiler

condensate discharge outlet and collects the condensate

into a larger volume before releasing it into the

discharge pipe.

With this expanded siphonic operation, the discharge from

the CondenseSure increases to every 15 to 20 minutes,

resulting in:

• Increased velocity and fl ow rate

• Only 3 to 4 siphonic actions per hour, meaning the

condensate pipework is empty for longer

• Signifi cantly decreased or even eliminated

freezing potential.

The Worcester CondenseSure auxiliary siphon NEW

The CondenseSure insulating jacket helps to retain the temperature of the condensate.

Features Benefits

No power consumptionNo electrical wiring connection or supply needed, meaning zero running costs

No moving parts No failure of components

Can be installed on new or existing installations

Suitable for any gas- or oil-fired condensing boilers

Can be attached to 22mm heating flow pipework (gas-fired boiler)

Uses ‘free’ energy from the pipe to heat the condensate

Under boiler or remote installation

Flexibility

No electrical connections No electrician needed

No pipe insulation neededCost saving and aesthetically pleasing

A universal fi tting for new and existing installations

Although developed specifi cally for Worcester Greenstar

gas- and oil-fi red boilers, the Worcester CondenseSure

can also be fi tted to any make of condensing boiler for

both new and retrofi t installations. The CondenseSure

can provide a simple solution which eliminates the need

for re-siting both the new boiler and the system pipework

when replacing an existing non-condensing appliance.

CondenseSure can easily be fi tted to an existing

condensing boiler to provide peace of mind in extreme

weather conditions.

Page 41: NEW - Oil Tanks | Steel, Fuel Dispensing & Bunded Oil Tanks › wp-content › uploads › ... · Oilfit flexible flue liner 57 - 58 Accessories 59 - 62 Worcester training 63 - 65

41

FittingEase of installation

The CondenseSure has been designed for ease of

installation and is suitable for most boiler applications.

Although it can be clipped to a fl ow pipe under a wall

hung boiler, on fl oor standing boilers the CondenseSure

can be wall-mounted away from the boiler, whilst still

being connected to the condensate discharge pipe.

Additional installation considerations include:

• Keeping any external pipework as short as possible

• Minimising the number of bends and connections

• Removal of burrs after cutting any pipe

• Removal of surplus solvent from the

interior of the pipe.

There is no Part P requirement as the CondenseSure has

no working parts to break down, does not use any energy

and has no electrical connections.

1. Foam backing with double-sided tape

2. Siphon mounting screws

3. Siphon body

4. Foam insert (used with regular or system boilers)

5. Foam cover

1

2

2

3

4

5

A typical installation using CondenseSure

Condensatedischarge from boiler

Universalconnector

External pipework3000mm max.

CondenseSure

2.5º fall min.

32mm OD pipe

Product infoPart number 7 716 192 746

CondenseSure installation parameters

The CondenseSure will protect an externally run condensate

discharge pipe from freezing for 48 hours at -15°C providing

the following installation parameters are met:

• The externally run pipe length does not exceed 3 metres

• There is a fall on the discharge pipe of at least 2.5 degrees

• The discharge pipe diameter is not less than 32mm

in diameter.

Whilst it is not necessary to insulate the pipework, it may

be a consideration if longer lengths or lower external

temperatures are expected.

Page 42: NEW - Oil Tanks | Steel, Fuel Dispensing & Bunded Oil Tanks › wp-content › uploads › ... · Oilfit flexible flue liner 57 - 58 Accessories 59 - 62 Worcester training 63 - 65

42

Horizontal and vertical flue terminal positioning

All measurements in millimetres

Key to illustration

1. 600mm distance to a boundary, unless it will cause a

nuisance. BS 5410: Part 1 recommends that care is

taken when siting terminals in relation to boundaries.

2. 600mm below eaves and balconies, this can be reduced

to 75mm, as long as the fl ue terminal is extended to

clear any overhang.

3. 600mm horizontally or vertically to an opening, air brick

or opening window.

4. 1,500mm vertically from a terminal on the same wall.

5. 750mm horizontally from a fl ue on the same wall.

6. 300mm to an internal or external corner.

1,500

Boundary

Conventional flue

750

750

Velux dormer w

Window

300

600600

600

600

600

GREENSTAR DANESMOOR KITCHEN 12/18

32

4

5 6

71

8

Note• All measurements are the minimum clearances required.• Use suitable brackets and fi ttings to support the fl ue

at approximately one metre intervals and at a change of direction.

• Terminals must be positioned so as to avoid combustion products entering the building.

• In spite of the dimensions given here, the terminal must not be closer than 300mm to combustible material, in the case of a thatched roof, double this dimension.

• Terminals must be positioned so as to avoid products of combustion accumulating in stagnant pockets around or entering the building.

• Terminals must be at least 1.8m from an oil storage tank unless a wall with of at least 30 minutes fi re resistance which extends 300mm wider and higher than the tank is present between the tank and the terminal.

Page 43: NEW - Oil Tanks | Steel, Fuel Dispensing & Bunded Oil Tanks › wp-content › uploads › ... · Oilfit flexible flue liner 57 - 58 Accessories 59 - 62 Worcester training 63 - 65

43

2m

1m

52mm 104mm

2,500

Drainpipe

Externaloil boiler

750

or window

300

300

600

12

13

14

9

10

11

7. Minimum 600mm straight fl ue before any bend on a

conventional fl ue.

8. 750mm between a vertical structure and a fl ue terminal.

9. 1,000mm below a Velux or dormer window, 300mm

above or to either side of the Velux or dormer window

or any opening on a sloping roof.

10. 600mm above the highest point of an intersection with

a roof.

11. Any fl ue must fall back towards the boiler by 3° or

52mm for every metre of fl ue so that the condensate

drains back to the boiler for disposal.

12. 300mm to any vertical sanitary pipework or drain pipe.

13. Flue clearance must be at least 300mm above ground

or balcony level. Terminal guards must be fi tted if the

fl ue is less than 2 metres from the ground or if a person

could come into contact with the fl ue terminal.

14. 2,500mm between terminals facing each other.

Page 44: NEW - Oil Tanks | Steel, Fuel Dispensing & Bunded Oil Tanks › wp-content › uploads › ... · Oilfit flexible flue liner 57 - 58 Accessories 59 - 62 Worcester training 63 - 65

Part No. Description

125mm diameter

7 716 190 064Standard telescopic flue kit (460 - 670mm)

7 716 190 062Short telescopic flue kit (350 - 460mm)

7 716 190 033 1,000mm flue extension

7 716 190 097 600mm short flue extension

7 716 190 034 90º bend

7 716 190 035 45º bends (pair)

7 716 190 101 Flue damper

7 716 190 050 Flue terminal guard

7 716 190 105Infill plate for high level horizontal flues (Danesmoor)

Greenstar Utility regular components

Part No. Description

150mm diameter

7 716 190 043 Standard flue kit

7 716 190 045 1,000mm extension flue kit

7 716 190 046 90º bend

7 716 190 047 45º bends (pair)

7 716 190 051 Flue terminal guard

44

Greenstar fl oor standing boiler range horizontal fl uing options (internal models)The Greenstar regular and system boiler range has a

125mm diameter telescopic horizontal room-sealed fl ue

system including a plume management kit.

Horizontal room-sealed fl ue

Greenstar Danesmoor regular and Danesmoor System components

Flue diameter 125mm 150mm

Maximum flue length Danesmoor 12/18, 18/25 & 25/32

6,000mm N/A

Utility regular 32/50 N/A 3,000mm

Utility regular 50/70 N/A 3,000mm

The following criteria should be noted when planning

the installation:

• The concentric fl ue system must be inclined at

3º (52mm per metre) from the appliance, to allow

condensate to drain back into the boiler

• A white plume of condensation will be emitted from

the terminal because the appliance operates at high

effi ciency. Care must be taken when selecting the fl ue

terminal position

• To achieve a maximum fl ue length, one of the extension

fl ue kits will need to be cut so that the permitted

maximum fl ue length is not exceeded

• Note: The short fl ue extension (600mm) may be used

as an alternative to the standard 1,000mm extension

on 80/125mm fl ue installations as required up to the

maximum fl ue lengths stated (Part No. 7 716 190 097).

Notes: Flue length is measured from the side/top of the boiler to the outside wall for the Greenstar Oilfit flue kits 125mm and 150mm.All components for the left horizontal and right horizontal outlet come within the Greenstar Oilfit horizontal flue kit (150mm) for the Greenstar Utility regular 32/50 and 50/70 models.

Note: The maximum fl ue length must be reduced by the

following amounts for each bend used.

45º bend 90º bend

80/125mm fl ues 500mm 1,000mm

100/150mm fl ues 500mm 1,000mm

Page 45: NEW - Oil Tanks | Steel, Fuel Dispensing & Bunded Oil Tanks › wp-content › uploads › ... · Oilfit flexible flue liner 57 - 58 Accessories 59 - 62 Worcester training 63 - 65

4545

Option 1: Standard rear flue assembly

Components

Maximum lengths (mm) & no. of components required

Greenstar Danesmoor regular & Danesmoor System series

Part No. 125mm 7 716 190 064

125mm 670 1

Greenstar Utility regular series

Part No. 150mm 7 716 190 043

150mm 880 1

Option 3: Side flue extension

Components

Maximum lengths (mm) & no. of components required

Greenstar Danesmoor regular & Danesmoor System series

Part No. 125mm 7 716 190 064 7 716 190 033 7 716 190 034

125mm 5,000 1 up to 5 1

Greenstar Utility regular series

Part No. 150mm 7 716 190 043 7 716 190 045 7 716 190 046

150mm 3,000 1 up to 2 1

Option 2: Extended rear flue assembly

Components

Maximum lengths (mm) & no. of components required

Greenstar Danesmoor regular & Danesmoor System series

Part No. 125mm 7 716 190 064 7 716 190 033

125mm 6,000 1 up to 6

Greenstar Utility regular series

Part No. 150mm 7 716 190 043 7 716 190 045

150mm 3,000 1 up to 3

Option 4: High level horizontal discharge

Components

Maximum lengths (mm) & no. of components required

Greenstar Danesmoor regular & Danesmoor System series

Part No. 125mm 7 716 190 064 7 716 190 033 7 716 190 034

125mm 5,000 1 up to 5 2

Greenstar Utility regular series

Part No. 150mm 7 716 190 043 7 716 190 045 7 716 190 046

150mm 2,000 1 up to 2 2

Note: The maximum fl ue length must be reduced by the

following amounts for each bend used.

45º bend 90º bend

80/125mm fl ues 500mm 1,000mm

100/150mm fl ues 500mm 1,000mm

Horizontal fl ue options 1-4 illustrate common fl ue installations. Other confi gurations of the fl ue system are possible up

to, and not exceeding, the stated maximum fl ue lengths.

Page 46: NEW - Oil Tanks | Steel, Fuel Dispensing & Bunded Oil Tanks › wp-content › uploads › ... · Oilfit flexible flue liner 57 - 58 Accessories 59 - 62 Worcester training 63 - 65

46

Greenstar fl oor standing boiler range vertical fl uing options (internal models) The Greenstar regular and system boiler range has the

choice of 2 differently sized vertical room-sealed fl ue

systems, 125mm and 150mm. Both systems have different

maximum lengths.

Vertical room-sealed fl ue

Flue diameter 125mm 150mm

Maximum flue length (inc. terminal) Danesmoor 12/18, 18/25 & 25/32 8,000mm† N/A

Utility regular 32/50 N/A 6,000mm

Utility regular 50/70 N/A 6,000mm

Flue terminal assembly diameter 138mm 163mm†Flue damper (Part No 7 716 190 101) required at effective flue lengths >6m

Greenstar Danesmoor regular, Danesmoor System & Danesmoor System Utility components

Part No. Description

125mm diameter

7 716 190 103Vertical balanced flue kit (Danesmoor regular)

7 716 190 033 1,000mm flue extension

7 716 190 097 600mm short flue extension

7 716 190 034 90º bend

7 716 190 035 45º bends (pair)

7 716 190 101 Flue damper

7 716 191 090 Flashing – flat roof

7 716 191 091 Flashing – pitched roof

Greenstar Utility regular components

Part No. Description

150mm diameter

7 716 190 044Vertical balanced flue kit (Greenstar Utility regular)

7 716 190 045 1,000mm flue extension

7 716 190 046 90º bend

7 716 190 047 45º bends (pair)

The following criteria should be noted when planning

the installation:

• To achieve a maximum fl ue length, one of the extension

fl ue kits will need to be cut so that the permitted

maximum fl ue length is not exceeded

• The concentric fl ue system must be inclined at

3º (52mm per metre) from the appliance, to allow

condensate to drain back into the boiler

• Because the appliance operates at high effi ciency, a

white plume of condensation will be emitted from the

terminal. Care must be taken when selecting the fl ue

terminal position

• Note: The short fl ue extension (600mm) may be used

as an alternative to the standard 1,000mm extension

on 80/125mm fl ue installations as required up to the

maximum fl ue lengths stated (Part No. 7 716 190 097).

Note: The maximum fl ue length must be reduced by the

following amounts for each bend used.

45º bend 90º bend

80/125mm fl ues 500mm 1,000mm

100/150mm fl ues 500mm 1,000mm

Notes: Flue length is measured from the side/top of the boiler to the outside wall for the Greenstar Oilfit flue kits 125mm and 150mm.All components for the left horizontal and right horizontal outlet come within the Greenstar Oilfit horizontal flue kit (150mm) for the Greenstar Utility regular 32/50 and 50/70 models.

Page 47: NEW - Oil Tanks | Steel, Fuel Dispensing & Bunded Oil Tanks › wp-content › uploads › ... · Oilfit flexible flue liner 57 - 58 Accessories 59 - 62 Worcester training 63 - 65

47

Option 1: Vertical balanced flue system minimum height

Components

Maximum lengths (mm) & no. of components required

Greenstar Danesmoor regular & Danesmoor System series

Part No. 125mm 7 716 190 103

125mm 1,080 1

Greenstar Utility regular series

Part No. 150mm 7 716 190 044

150mm 1,290 1

Note: The maximum fl ue length must be reduced by the

following amounts for each bend used.

45º bend 90º bend

80/125mm fl ues 500mm 1,000mm

100/150mm fl ues 500mm 1,000mm

Vertical fl ue options 1-2 illustrate common fl ue installations. Other confi gurations of the fl ue system are possible up to,

and not exceeding, the stated maximum fl ue lengths.

Option 2: Vertical balanced flue system with two 90º bends

Components

Maximum lengths (mm) & no. of components required

Greenstar Danesmoor regular & Danesmoor System series

Part No. 125mm 7 716 190 103 7 716 190 033 7 716 190 034

125mm 6,000† 1 up to 6 2

Greenstar Utility regular series

Part No. 150mm 7 716 190 044 7 716 190 045 7 716 190 046

150mm 4,000 1 up to 4 2

†Flue damper (Part No 7 716 190 101) required at effective flue lengths >6m

Page 48: NEW - Oil Tanks | Steel, Fuel Dispensing & Bunded Oil Tanks › wp-content › uploads › ... · Oilfit flexible flue liner 57 - 58 Accessories 59 - 62 Worcester training 63 - 65

48

Greenstar Danesmoor Wall Mounted Internal boiler range horizontal fl uing optionsThe Greenstar Danesmoor WM regular boiler range has a

125mm diameter telescopic horizontal room-sealed fl ue

system including a plume management kit.

Horizontal room-sealed fl ue

Flue diameter 125mm

Minimum flue length 160mm

Maximum flue length 4,000mm

Greenstar Danesmoor Wall Mounted components

Note: The telescopic fl ue kit does not include 90° bend

required for horizontal fl uing.

The following criteria should be noted when planning

the installation:

• The concentric fl ue system must be inclined at

3º (52mm per metre) from the appliance, to allow

condensate to drain back into the boiler

• A white plume of condensation will be emitted from

the terminal because the appliance operates at high

effi ciency. Care must be taken when selecting the fl ue

terminal position

• To achieve a maximum fl ue length, one of the extension

fl ue kits will need to be cut so that the permitted

maximum fl ue length is not exceeded

• Note: The short fl ue extension (600mm) may be used

as an alternative to the standard 1,000mm extension

on 80/125mm fl ue installations as required up to the

maximum fl ue lengths stated (Part No. 7 716 190 097).

Part No. Description

125mm diameter

7 716 190 064Standard telescopic flue kit (460 - 670mm)

7 716 190 062Short telescopic flue kit (350 - 460mm)

7 716 190 033 1,000mm flue extension

7 716 190 097 600mm short flue extension

7 716 190 034 90º bend

7 716 190 035 45º bends (pair)

Note: The maximum fl ue length must be reduced by the

following amounts for each bend used.

45º bend 90º bend

80/125mm fl ues 500mm 1,000mm

Page 49: NEW - Oil Tanks | Steel, Fuel Dispensing & Bunded Oil Tanks › wp-content › uploads › ... · Oilfit flexible flue liner 57 - 58 Accessories 59 - 62 Worcester training 63 - 65

49

Option 1: Standard horizontal flue assembly

Components

Maximum lengths (mm) & no. of components required

Greenstar Danesmoor WM series

Part No. 125mm 7 716 190 064 7 716 190 034

125mm 670 1 1

Option 3: Extended flue assembly horizontal and upwards

Components

Maximum lengths (mm) & no. of components required

Greenstar Danesmoor WM series

Part No. 125mm 7 716 190 064 7 716 190 033 7 716 190 034

125mm 4,000 1 up to 4 1

Option 2: Extended horizontal flue assembly

Components

Maximum lengths (mm) & no. of components required

Greenstar Danesmoor WM series

Part No. 125mm 7 716 190 064 7 716 190 033 7 716 190 034

125mm 4,000 1 up to 4 1

Option 4: Extended flue assembly horizontal and upwardsusing a second 90º bend

Components

Maximum lengths (mm) & no. of components required

Greenstar Danesmoor WM series

Part No. 125mm 7 716 190 064 7 716 190 033 7 716 190 034

125mm 3,000 1 up to 3 2

Option 5: Extended horizontal flue assembly with a second 90º bend

Components

Maximum lengths (mm) & no. of components required

Greenstar Danesmoor WM series

Part No. 125mm 7 716 190 064 7 716 190 033 7 716 190 034

125mm 3,000 1 up to 3 2

Note: The maximum fl ue length must be reduced by the

following amounts for each bend used.

45º bend 90º bend

80/125mm fl ues 500mm 1,000mm

Horizontal fl ue options 1-5 illustrate common fl ue installations. Other confi gurations of the fl ue system are possible up

to, and not exceeding, the stated maximum fl ue lengths.

Page 50: NEW - Oil Tanks | Steel, Fuel Dispensing & Bunded Oil Tanks › wp-content › uploads › ... · Oilfit flexible flue liner 57 - 58 Accessories 59 - 62 Worcester training 63 - 65

50

Greenstar Danesmoor Wall Mounted Internal boiler range vertical fl uing options The Greenstar Danesmoor WM boiler range has a 125mm

diameter vertical room-sealed fl ue system.

Vertical room-sealed fl ue Part No. Description

125mm diameter

7 716 190 103 Vertical balanced flue kit

7 716 190 033 1,000mm flue extension

7 716 190 097 600mm short flue extension

7 716 190 034 90º bend

7 716 190 035 45º bends (pair)

7 716 191 090 Flashing – flat roof

7 716 191 091 Flashing – pitched roof

Greenstar Danesmoor Wall Mounted components

The following criteria should be noted when planning

the installation:

• To achieve a maximum fl ue length, one of the extension

fl ue kits will need to be cut so that the permitted

maximum fl ue length is not exceeded

• The concentric fl ue system must be inclined at

3º (52mm per metre) from the appliance, to allow

condensate to drain back into the boiler

• Because the appliance operates at high effi ciency, a

white plume of condensation will be emitted from the

terminal. Care must be taken when selecting the fl ue

terminal position

• Note: The short fl ue extension (600mm) may be used

as an alternative to the standard 1,000mm extension

on 80/125mm fl ue installations as required up to the

maximum fl ue lengths stated (Part No. 7 716 190 097).

Flue diameter 125mm

Minimum flue length 1,080mm

Maximum flue length (inc. terminal) 6,000mm

Flue terminal assembly diameter 125mm

Flue terminal assembly length 1,080mm

Note: The maximum fl ue length must be reduced by the

following amounts for each bend used.

45º bend 90º bend

80/125mm fl ues 500mm 1,000mm

Page 51: NEW - Oil Tanks | Steel, Fuel Dispensing & Bunded Oil Tanks › wp-content › uploads › ... · Oilfit flexible flue liner 57 - 58 Accessories 59 - 62 Worcester training 63 - 65

51

Option 1: Vertical balanced flue system minimum height

Components

Maximum lengths (mm) & no. of components required

Greenstar Danesmoor WM series

Part No. 125mm 7 716 190 103

125mm 1,080 1

Option 4: Vertical balanced flue system with two 45º bends

Components

Maximum lengths (mm) & no. of components required

Greenstar Danesmoor WM series

Part No. 125mm 7 716 190 103 7 716 190 033 7 716 190 035

125mm 5,000 1 up to 5 2

Option 2: Vertical balanced flue system maximum height

Components

Maximum lengths (mm) & no. of components required

Greenstar Danesmoor WM series

Part No. 125mm 7 716 190 103 7 716 190 033

125mm 6,000 1 up to 6

Option 3: Vertical balanced flue system with two 90º bends

Components

Maximum lengths (mm) & no. of components required

Greenstar Danesmoor WM series

Part No. 125mm 7 716 190 103 7 716 190 033 7 716 190 034

125mm 4,000 1 up to 4 1*

*Only order 1 additional 90º bend – vertical kit includes a 90º bend

Note: The maximum fl ue length must be reduced by the

following amounts for each bend used.

45º bend 90º bend

80/125mm fl ues 500mm 1,000mm

Vertical fl ue options 1-4 illustrate common fl ue installations. Other confi gurations of the fl ue system are possible up to,

and not exceeding, the stated maximum fl ue lengths.

Page 52: NEW - Oil Tanks | Steel, Fuel Dispensing & Bunded Oil Tanks › wp-content › uploads › ... · Oilfit flexible flue liner 57 - 58 Accessories 59 - 62 Worcester training 63 - 65

52

Greenstar fl oor standing fl uing options (external models)

Greenstar Danesmoor regular External and Danesmoor System External components

Part No. Description

125mm diameter

Included with boiler

Low level horizontal balanced flue kit

7 716 190 03490º bend (internal) required for fluing to left or right

7 716 190 050 Flue terminal guard

Low-level rear

Components

Maximum lengths (mm) & no. of components required

Greenstar Danesmoor regular External & Greenstar Danesmoor System External series

Part No. 125mm 7 716 190 050

125mm 175Included

with boiler1

FRONT

TOPVIEW

240mm175mm

Low-level right

Components

Maximum lengths (mm) & no. of components required

Greenstar Danesmoor regular External & Greenstar Danesmoor System External series

Part No. 125mm 7 716 190 034 7 716 190 050

125mm 175Included

with boiler1 1

TOPVIEW

FRONT240mm

175mm

Top view Top view

Low-level left

Components

Maximum lengths (mm) & no. of components required

Greenstar Danesmoor regular External & Greenstar Danesmoor System External series

Part No. 125mm 7 716 190 034 7 716 190 050

125mm 175Included

with boiler1 1

TOPVIEW

FRONT

240mm

175mm

Top view

Greenstar Danesmoor regular External and Danesmoor System External boilers include a low level balanced fl ue kit.

Page 53: NEW - Oil Tanks | Steel, Fuel Dispensing & Bunded Oil Tanks › wp-content › uploads › ... · Oilfit flexible flue liner 57 - 58 Accessories 59 - 62 Worcester training 63 - 65

5353

Plume management terminal positioning

Door

Balcony

Boundary

Drainpipe

2

4

5

1

600

200

200

300

600600

300

150

150

150 150

600

Window Window

25

300Window

±45°

Flue exhaustoutlet

Air intake

6

100

2,500

7

3

Key to illustration

1. 600 mm distance to a boundary, unless it will cause

a nuisance. BS 5410: Part 1 recommends that care is

taken when siting terminals in relation to boundaries.

2. Internal/external corners the air intake can be reduced

to 150mm providing the fl ue exhaust outlet has a

300mm clearance.

3. Vertical sanitary pipe: 25mm to the fl ue air intake and

300mm to the fl ue exhaust outlet.

4. Clearance no less than 200mm from the lowest point of

the balcony or overhang, installations in car ports are

not recommended.

5. 1,200mm from an opening in a car port on the same wall

i.e. door or window leading into dwelling. 600mm to a

surface facing a terminal.

6. Using a plume management kit, the air intake

measurement can be reduced to 150mm providing the

fl ue exhaust outlet has a 600mm clearance. Plume kits

running horizontally must have a 10º fall back to the

boiler for proper disposal of condensate.

For details on specifi c lengths see relevant boiler

Technical & Specifi cation manual.

7. 2,500mm between air intake and facing terminal.

Note

• All measurements are the minimum clearances required

• Terminals must be positioned so as to avoid combustion

products entering the building

• Support the fl ue at approximately one metre intervals

and at a change of direction. Use suitable brackets

and fi ttings.

All measurements in millimetres

Page 54: NEW - Oil Tanks | Steel, Fuel Dispensing & Bunded Oil Tanks › wp-content › uploads › ... · Oilfit flexible flue liner 57 - 58 Accessories 59 - 62 Worcester training 63 - 65

54

Plume management system options (internal models)Greenstar Danesmoor regular, Danesmoor System & Danesmoor WM seriesCondensfi t II™ plume management system components

Part No. Description

80mm diameter

7 716 190 092 Plume management kit

7 716 190 093 1,000mm extension

7 716 190 095 90º bend

7 716 190 094 45º bend (pair)

Plume management system measuring

Note: All boilers have a maximum permissible

plume management length – see table below.

500mm (min) (M)

L (max)

5,000mm (max) (M)

L (max)

Flue length(L)

Max. number of bends

Plume length(M)

Max. number of bends

160 - 2,000mm 2 500 - 5,000mm 3

2,001 - 3,000mm 2 500 - 3,500mm 3

3,001 - 4,000mm 2 500 - 2,000mm 3

500mm (M)

Standard plume management system

The fl ue terminal outlet has built-in stops to limit rotation

for horizontal fl uing to allow condensate to run back into

the boiler for safe disposal. Do not attempt to force beyond

the limit stops.

All plume management sections must rise by at least

173mm per metre (10º) from the terminal to ensure that

condensate fl ows back into the boiler.

45°V

Direction of flue products, the angle of the terminal bend must be more than 45° fromthe wall or structure

Plume terminal

At least 1,500mm from any opening in the building

Opening in the building i.e. air brick, window.

Re-directing flue discharge from an 80mm dia. plume management outlet

Additional bends

Adding bends to the plume management system reduces

the actual plume management length. Each bend has an

equivalent straight length and must be factored into the

overall effective length.

• 90° bend is equivalent to 1,000mm

• 45° bend is equivalent to 500mm.

Page 55: NEW - Oil Tanks | Steel, Fuel Dispensing & Bunded Oil Tanks › wp-content › uploads › ... · Oilfit flexible flue liner 57 - 58 Accessories 59 - 62 Worcester training 63 - 65

55

Plume management system with extensions

Components

Maximum lengths (mm) & no. of components required

Greenstar Danesmoor regular, Danesmoor System, Danesmoor WM & Danesmoor regular External, Danesmoor System External series

Part No. 80mm 7 716 190 092 7 716 190 093

80mm 5,000 1 5

Plume management system with extensions and 45º bend

Components

Maximum lengths (mm) & no. of components required

Greenstar Danesmoor regular, Danesmoor System, Danesmoor WM & Danesmoor regular External, Danesmoor System External series

Part No. 80mm 7 716 190 092 7 716 190 093 7 716 190 094

80mm 5,000 1 5 1

Plume management system with extensions and two 45º bends

Components

Maximum lengths (mm) & no. of components required

Greenstar Danesmoor regular, Danesmoor System, Danesmoor WM & Danesmoor regular External, Danesmoor System External series

Part No. 80mm 7 716 190 092 7 716 190 093 7 716 190 094

80mm 5,000 1 5 1

±45°

M

Min. 150mm

Plume length (M) Max. number of bends

500 - 5,000mm 2

Greenstar Danesmoor regular External & Danesmoor System External series

The plume management kit can be used on the Greenstar

Danesmoor regular and System External models in

conjunction with the external low level horizontal fl ue kit.

Page 56: NEW - Oil Tanks | Steel, Fuel Dispensing & Bunded Oil Tanks › wp-content › uploads › ... · Oilfit flexible flue liner 57 - 58 Accessories 59 - 62 Worcester training 63 - 65

56

Open (conventional) fl ued appliances must not be installed

in a bedroom, bathroom or bedsitting room.

• The fl ue system must be in accordance with BS 5410 and

the current Building Regulations.

• The fl ue must be constructed of materials suitable for use

with condensing combustion products.

• External fl ue systems must be of the insulated type.

• Brick and masonry chimneys must be lined with a

suitable non-combustible material and properly jointed

to withstand the effects of the working temperature

(minimum rating of material 120°C) of the appliance and

any condensate which may form.

• All fl ue joints must be sealed to prevent the leakage of

condensate and combustion products.

• Ensure that joints are made so that the condensate runs

away and is not collected within the joint.

NOTE: The fl ue can be increased in size from the boiler

take off point providing the joint is correctly sealed. Never

reduce the fl ue diameter from the boiler take-off point.

• Because the fl ue operates at a lower temperature on a

condensing boiler compared to that of a conventional

appliance, the fl ue draught will be lower. Typically

the draught will be between 0.5mmwg and 4.4mmwg,

measured with the fl ue warm but the burner not fi ring.

The actual fi gure will vary depending on weather

conditions, fl ue height and position.

• The fl ue should be vertical and contain as few bends as

possible. A maximum of two 135° bends should be used.

• The fl ue outlet must be extended beyond the eaves of the

building and, where possible, above the apex.

• Fit a suitable anti down-draught terminal where down

draughts are experienced.

To convert the appliance to a conventional fl ue system the

vertical fl ue adaptor needs to be specifi ed:

Conventional flue sizing

Output Diameter

12/18 100/103mm

18/25 100/103mm

25/32 100/103mm

32/50 130mm

50/70 130mm

Conventional fl ue

C

B

A

D

E

A Boiler

B Flue

C Maximum 2 bends at 135º

D Anti down-draught terminal

E Chimney

Danesmoor WM is not suitable for CF.

The fl ue must be constructed of materials suitable for the

use of condensing combustion products.

Part No. Description

100mm diameter

7 716 190 104Greenstar Danesmoor CF flue adaptor kit

Part No. Description

130mm diameter

7 716 190 049Greenstar Utility regular CF flue adaptor kit

Page 57: NEW - Oil Tanks | Steel, Fuel Dispensing & Bunded Oil Tanks › wp-content › uploads › ... · Oilfit flexible flue liner 57 - 58 Accessories 59 - 62 Worcester training 63 - 65

57

Oilfit flexible flue liner

The Oilfi t fl exible fl ue liner allows installation into a position

where a standard effi ciency appliance had previously

been installed. It achieves this by enabling a Greenstar

condensing boiler to be open-fl ued up a chimney. The

continuous fl exible fl ue is installed from the roof, providing

a condensate-proof lining for the chimney.

A roof terminal, extension pieces and a fl ue adaptor are all

included within the kit.

Conventional flexible flue liner kit

100mm dia. Oilfit flexible flue liner kit

Greenstar Danesmoor regular & Danesmoor System

1 x chimney cowl

1 x terminal

1 x support collar

1 x support bracket assembly

1 x centralising spacer

1 x flexible to rigid adaptor kit (includes liner & seal)

1 x flexible liner

1 x rigid to flexible adaptor kit (includes liner & seal)

Part No. 7 716 190 076 (8m)

Part No. 7 716 190 077 (12m)

130mm dia. Oilfit flexible flue liner kit

Greenstar Utility regular 32/50 & 50/70 models

1 x chimney cowl

1 x terminal

1 x support bracket assembly

1 x centralising spacer

1 x fl exible to rigid adaptor kit (includes liner & seal)

1 x fl exible liner

1 x rigid to fl exible adaptor kit (includes liner & seal)

Part No. 7 716 190 079 (8m)

Part No. 7 716 190 080 (12m)

Part No. 7 716 190 081 (15m)

Part No. Description

100mm diameter

7 716 190 076 Oilfit flexible flue liner kit (8m)

7 716 190 077 Oilfit flexible flue liner kit (12m)

7 716 190 066 1,000mm extension kit*

7 716 190 067 500mm extension kit*

7 716 190 068 Telescopic extension*

7 716 190 069 45º bend*

7 716 190 104 Conventional vertical flue kit

7 716 190 074 Wall cover plate kit

Greenstar Utility regular fl exible fl ue liner components

Part No. Description

130mm diameter

7 716 190 079 Oilfit flexible flue liner kit (8m)

7 716 190 080 Oilfit flexible flue liner kit (12m)

7 716 190 081 Oilfit flexible flue liner kit (15m)

7 716 190 070 1,000mm extension kit*

7 716 190 071 500mm extension kit*

7 716 190 072 Telescopic extension*

7 716 190 073 45º bend*

7 716 190 049 Conventional vertical flue kit

7 716 190 075 Wall cover plate kit

*Stainless steel

Greenstar Danesmoor regular and Danesmoor System flexible flue liner components

Not for use with Greenstar Danesmoor WM boilers.

Model Flue diameter Maximum flue length

Greenstar Danesmoor regular and Danesmoor System series

12/18 100mm 12,000mm

18/25 100mm 12,000mm

25/32 100mm 12,000mm

Greenstar Utility regular series

32/50 130mm 15,000mm

50/70* 130mm 15,000mm *For 70kW adjust the first and second stage pump pressure to 125psi.

Page 58: NEW - Oil Tanks | Steel, Fuel Dispensing & Bunded Oil Tanks › wp-content › uploads › ... · Oilfit flexible flue liner 57 - 58 Accessories 59 - 62 Worcester training 63 - 65

58

Typical installations

Open (conventional) fl ued appliances must not be installed

in a bedroom, bathroom or bed-sitting room.

Before installation commences it must be checked that:

• The chimney is structurally sound and free of obstructions

• The chimney has been thoroughly swept to remove

deposits since it was last used.

The fl exible fl ue pipe is only suitable for lining chimneys

that conform to the Building Regulations and it should not

be used as a chimney on its own or outside a masonry or

fl ueblock chimney.

All the fl exible liner and adaptors must be within the

chimney with rigid stainless steel fl ue pipe connecting to

the boiler.

The fi rst 600mm of the stainless steel fl ue pipe off the

boiler must be vertical with no bends or restrictions.

There must be at least a 25mm clearance between the

stainless steel fl ue pipe and any combustible material.

The data label must be secured onto the chimney or

chimney hearth using the plate provided.

If it is not possible to attach the plate to the chimney,

the plate can be attached, in a visible position, next to

the electricity consumer unit.

Do not attach the data plate or label to the fl ue system.

The terminal should not be modifi ed and an extra cowl or

cover must not be fi tted. The boiler is designed so that

any rain that enters the fl ue will be directed down to the

condensate drain.

Calculating the length:

L maximum = boiler maximum minus 1m*.

(Each 45º bend has a 0.5m equivalent fl ue length)

*If the chimney has an additional offset, then L will be reduced by an extra metre.**The top 45º bend may not be required if there is sufficient room in the chimney to turn the flexible liner through 45º within the chimney. The stainless steel section must be adequately supported.

L max

A

B

C

E

G

F

D

**

A Boiler

B Stainless steel vertical section(min. 600mm)

C Maximum 2 bends at 45°

D Fire stop plate/inspection plate

E Centralising spacer

F Flexible liner

G Chimney cowl

Page 59: NEW - Oil Tanks | Steel, Fuel Dispensing & Bunded Oil Tanks › wp-content › uploads › ... · Oilfit flexible flue liner 57 - 58 Accessories 59 - 62 Worcester training 63 - 65

5959

Vertical flue kit(150mm dia.) –

Greenstar Utility regular

Worcester Part No. 7 716 190 044

1,000mm flue extension(125mm dia.)

Worcester Part No. 7 716 190 033

Greenstar Oilfi t internal fl ue system Greenstar Danesmoor regular, Greenstar Danesmoor System, Greenstar Danesmoor WM & Greenstar Utility regular internal series

Greenstar system & regular oil-fi red boiler accessories

Digital plug-in 7 day twin channel programmer (kitchen models only)

Worcester Part No. 7 716 192 033

CondenseSure auxiliary siphon

Worcester Part No. 7 716 192 746

Greenstar System Filter

Worcester Part No. 7 716 192 609

NEWNEW

Short telescopic flue kit (125mm dia.)

Worcester Part No. 7 716 190 062

Standard flue kit (150mm dia.)

Worcester Part No. 7 716 190 043

Standard telescopic flue kit (125mm dia.)

Worcester Part No. 7 716 190 064

Vertical flue kit (125mm dia.) – Greenstar

Danesmoor models

Worcester Part No. 7 716 190 103

600mm flue extension(125mm dia.)

Worcester Part No. 7 716 190 097

Infill plate kit for high level horizontal flues

Worcester Part No. 7 716 190 105

Page 60: NEW - Oil Tanks | Steel, Fuel Dispensing & Bunded Oil Tanks › wp-content › uploads › ... · Oilfit flexible flue liner 57 - 58 Accessories 59 - 62 Worcester training 63 - 65

60

Greenstar Oilfi t internal fl ue system continuedGreenstar Danesmoor regular, Greenstar Danesmoor System, Greenstar Danesmoor WM & Greenstar Utility regular internal series

Stainless steel flue terminal guard(150mm dia.)

Worcester Part No. 7 716 190 051

Stainless steel flue terminal guard(125mm dia.)

Worcester Part No. 7 716 190 050

Flat roof flashing kit(100mm & 125mm dia.)

Worcester Part No. 7 716 191 090

Pitched roof flashing kit(100mm & 125mm dia.)

Worcester Part No. 7 716 191 091

45º bend(125mm dia.)

Worcester Part No. 7 716 190 035

45º bend(150mm dia.)

Worcester Part No. 7 716 190 047

90º bend(125mm dia.)

Worcester Part No. 7 716 190 034

1,000mm flue extension(150mm dia.)

Worcester Part No. 7 716 190 045

90º bend(150mm dia.)

Worcester Part No. 7 716 190 046

Conventional vertical flue kit (130mm dia.) –

Greenstar Utility regular series

Worcester Part No. 7 716 190 049

Conventional vertical flue kit (100mm dia.) – Greenstar Danesmoor

regular & Danesmoor System

Worcester Part No. 7 716 190 104

Page 61: NEW - Oil Tanks | Steel, Fuel Dispensing & Bunded Oil Tanks › wp-content › uploads › ... · Oilfit flexible flue liner 57 - 58 Accessories 59 - 62 Worcester training 63 - 65

6161

Greenstar Oilfi t low level external fl ue systemGreenstar Danesmoor regular External & Greenstar Danesmoor System External series

Greenstar Oilfi t fl exible fl ue kit accessoriesGreenstar Danesmoor regular, Greenstar Danesmoor System & Greenstar Utility regular internal series

Stainless steel1,000mm extension kit

Worcester Part No. 100mm dia. 7 716 190 066130mm dia. 7 716 190 070

Stainless steel500mm extension kit

Worcester Part No. 100mm dia. 7 716 190 067130mm dia. 7 716 190 071

Oilfit flexible flue kit

Worcester Part No.100mm dia. 7 716 190 076 (8m) 7 716 190 077 (12m)

130mm dia. 7 716 190 079 (8m) 7 716 190 080 (12m) 7 716 190 081 (15m)

Stainless steel telescopic extension

Worcester Part No. 100mm dia.

7 716 190 068130mm dia.

7 716 190 072

Stainless steel 45º bend

Worcester Part No. 100mm dia.

7 716 190 069130mm dia.

7 716 190 073

Wall cover plate kit

Worcester Part No. 100mm dia. flue

7 716 190 074130mm dia. flue

7 716 190 075

Low level horizontal flue kit (125mm dia.)

Included with external boilers

90º bend*(125mm dia.)

Worcester Part No. 7 716 190 034

Stainless steel flue terminal guard

Worcester Part No. 7 716 190 050

* Used inside boiler when fluing to the side

Page 62: NEW - Oil Tanks | Steel, Fuel Dispensing & Bunded Oil Tanks › wp-content › uploads › ... · Oilfit flexible flue liner 57 - 58 Accessories 59 - 62 Worcester training 63 - 65

62

Plume management accessoriesGreenstar Danesmoor regular, Greenstar Danesmoor System, Greenstar Danesmoor WM, Greenstar Utility regular internal, Greenstar Danesmoor regular External & Greenstar Danesmoor System External series

Plume management kit(80mm dia.)

Worcester Part No. 7 716 190 092

1,000mm extension(80mm dia.)

Worcester Part No. 7 716 190 093

90º bend(80mm dia.)

Worcester Part No. 7 716 190 095

45º bend(80mm dia.)

Worcester Part No. 7 716 190 094

Page 63: NEW - Oil Tanks | Steel, Fuel Dispensing & Bunded Oil Tanks › wp-content › uploads › ... · Oilfit flexible flue liner 57 - 58 Accessories 59 - 62 Worcester training 63 - 65

6363

Belfast

Wakefield

Clay Cross

Worcester

West Thurrock

Dundee

Dublin

Burnley

Durham

Wiltshire

Tredegar

Cambridge

Wrexham

Camborne Paignton

Johnstone

Borders

Elgin

Ayr

WWWWWWWWWWWWWWWWWWW

Worcester has always placed great emphasis on technical

support and training for installers and service engineers.

Advances in heating technology, including the increasing use

of renewables, make the need for training greater than ever.

To ensure the highest levels of competence and expertise

in the installation of all Worcester products, we run

intensive training courses for installers, commissioning

engineers and operatives involved with servicing and

fault-fi nding.

Courses available

Our training facilities offer a number of courses suitable

for the installer and commissioning engineers, and more

in-depth courses for the servicing and fault-fi nding engineers.

Training centres throughout the UK

To enable us to meet the growing demand for training we

have invested in additional facilities at the award-winning

training academy at our Worcester headquarters. In addition

to the original academy there is now a new 400m2 unit, 25%

of which is devoted to an open-plan domestic training area

with life-size single-storey brick buildings. These feature

working Greenskies solar thermal systems which enable

installers to get up onto the roof of the building to get

more realistic training. There are bays full of all Greenstar

appliances, so installers can really get to grips with the

importance of system design. The additional space also

contains dedicated training areas for our renewable and

future products. The training centre also runs certifi ed

domestic and commercial ACS training and assessment.

Further academies are located at West Thurrock in Essex,

Wakefi eld and Clay Cross in Derbyshire, all offering our full

suite of courses. Please phone 0330 123 0166 for more

information about a course near you. Each course is run

by specialist trainers and is superbly equipped to deliver

a combination of classroom theory and practical hands-on

experience that’s second to none.

College-linked Learning

As well as offering training at our own centres, Worcester

has established close partnerships with many colleges

around the UK, equipping them with our latest products.

Call us on 0330 123 0166 to fi nd out when we will be

running the course of your choice at a college in your area.

Mobile training

To complement our training venues across the country,

we can also bring training to you.

We have mobile vehicles fully equipped with operational

Greenstar gas-fi red boilers, dry strip-down models and even

a Greensource air to air heat pump, ensuring that quality

training in a comfortable environment can be achieved on

your doorstep!

We have a 7.5 tonne mobile oil vehicle available

throughout the country for hands-on product training

and OFTEC assessments.

Distance learning/web based learning

Worcester has produced a selection of Distance Learning

CD ROMs/DVDs which are packed with information.

Call 0330 123 9119 for your copies, or visit

www.worcester-bosch.co.uk for information

on Web Based Learning.

Get on course for a more profi table future now.

Call now for more information 0330 123 0166

Training centresT

College links training centres

The total training experienceWorcester expertise that will build your skills

Page 64: NEW - Oil Tanks | Steel, Fuel Dispensing & Bunded Oil Tanks › wp-content › uploads › ... · Oilfit flexible flue liner 57 - 58 Accessories 59 - 62 Worcester training 63 - 65

64

Worcester’s oil manufacturing heritage stretches back to

the foundation of the company in 1962. Since then, we

have built a strong reputation for not only manufacturing

products at the highest levels of quality and reliability,

but also for training installers, commissioning engineers

and operatives.

Our oil-fi red boiler training courses are extensive, covering

areas such as dismantling a jet burner, setting oil pump

pressures, maintaining a condensate trap, the relationship

between air and oil supplies, as well as the detection

of intermittent faults. Our advanced fault-fi nding course

has been designed for installers and heating engineers

who are already knowledgeable on our range of oil-fi red

products. Our expert trainers will further increase your

experience, whilst also providing a strong understanding

of fault-fi nding techniques.

A requirement of Building Regulations 2001 - Part L

(England and Wales) and Part J (Scotland) is that every

boiler installation must be self-certifi ed by an installer

who is OFTEC registered. Worcester can offer this OFTEC

training, with a variety of courses to choose from.

Oil-fi red condensing boiler course

Greenstar Danesmoor and Heatslave II high effi ciency

condensing oil-fi red boiler training.

Oil advanced fault-fi nding.

OFTEC training and assessment courses

OFTEC 50.

OFTEC 101 & 105e, OFTEC 600a and

OFTEC 101/105e/600a.

Oil-fi red product courses

To complement the above courses, Worcester also runs unvented, water treatment, Domestic ACS training and

assessment, IDHEE domestic heating design, MCS Made Easy and Green Deal courses.

Please note: to attend OFTEC courses you must have a minimum of 12 months’ experience installing/servicing oil boilers or have attended an OFTEC 50 course. For candidates with limited oil experience, our Greenstar one day oil-fi red course offers pre-OFTEC training. Consult with the trainer at the end of the session to see if you are ready to undertake OFTEC assessment. For experienced oil technicians, training is not a pre-requisite for OFTEC assessment.

Oil-firedCourse

Oil Advanced Fault Finding OFTEC 50 OFTEC

101 & 105eOFTEC600a

OFTEC 101/ 105e/600a

Duration 1 Day 1 Day 5 Days 4 Days 1 Day 4 Days

Cost Free* £65 £600 £350 £175 £500

Training course covers

Specification A preparatory course for OFTEC

assessmentcourses.

(Price of course includes all

necessary OFTEC text books).

Domestic/light commercial pressure jet

commissioning, servicing and boiler

installation

Oil tank installation and associated

controls

Combined OFTEC 101, 105e and 600a courses

Installation

Commissioning

Servicing

Maintenance

Course locations

Worcester

Clay Cross

Wakefield

West Thurrock

College Links†

Mobile†

* A holding fee of £65 applies to free courses and is refunded on attendance of the course. If a booking is cancelled more than 10 working days before the course date, the fee will be fully refunded. The fee is non-refundable if a cancellation is made less than 10 working days before the course date.

†Please contact Worcester Training for specifi c colleges and mobile dates.

Page 65: NEW - Oil Tanks | Steel, Fuel Dispensing & Bunded Oil Tanks › wp-content › uploads › ... · Oilfit flexible flue liner 57 - 58 Accessories 59 - 62 Worcester training 63 - 65

Additional product and industry training courses The diversity of products in today’s heating industry gives

you the opportunity to expand your expertise, whilst

offering more choice to your customers. Worcester

provides comprehensive training from all its academies

on its entire range of technologies.

Gas-fi red condensing boiler courses

Greenstar CDi Classic gas-fi red condensing combi boilers.

Greenstar CDi Compact and NEW Greenstar Si Compact

gas-fi red condensing combi boilers.

Greenstar i Junior gas-fi red condensing combi boilers.

Greenstar system & regular gas-fi red condensing boilers

(covers NEW Greenstar 27Ri & 30Ri, Greenstar 12Ri-24Ri,

Greenstar CDi Classic Regular, Greenstar FS CDi Regular,

Greenstar 30CDi Classic System, NEW Greenstar 27i &

30i System and Greenstar 12i-24i System boilers).

Greenstar Highfl ow CDi & FS CDi Regular fl oor standing

gas-fi red condensing combi and regular boilers.

Renewable product courses

Renewables overview.

Greenskies solar.

Greenskies advanced solar.

Introduction to heat pumps.

Greenstore LECP ground source heat pumps.

Greensource air to air heat pumps.

Greensource air to water heat pumps.

Greensource split air to water heat pumps.

Greenstar Plus hybrid heat pumps.

Accessories training courses

Worcester controls.

We are here to provide you with training and assistance for

all areas of your business, not just product training. Call us

on 0330 123 0166 to order a full course training brochure

or to book yourself onto a training course, alternatively,

you can visit www.worcester-bosch.co.uk/training

Worcester commercial product courses

Greenspring CWi47 water heater.

GB162 overview.

GB162 domestic.

GB162 commercial.

Greenstar Heat Distribution Unit.

Commercial ACS training and assessment – CODNCO1.

Bosch commercial product courses

GB312 & GB402 overview.

Solar thermal product overview.

GWPL Gas Absorption Heat Pumps overview.

CHP overview.

Commercial controls overview.

Industry focused courses

Hot water systems & safety.

Chemical water treatment.

Construction skills F-Gas training/

assessment certifi cation.

IDHEE domestic heating design.

Domestic ACS training and assessment – reassessment.

CCN1 + 3 appliances.

MCS Made Easy.

Green Deal.

65

Page 66: NEW - Oil Tanks | Steel, Fuel Dispensing & Bunded Oil Tanks › wp-content › uploads › ... · Oilfit flexible flue liner 57 - 58 Accessories 59 - 62 Worcester training 63 - 65

A complete after-sales service

All the technical advice you needSpares

Genuine replacement parts for all supported

Worcester products are readily available from stock,

or on a next day delivery basis. Visit our website

www.worcester-bosch.co.uk/spares to fi nd your

local stockist.

Customer Technical Support

The Worcester Technical Helpline is a dedicated phone

line – committed to providing a comprehensive service to

complement the brand name and quality of our products.

Our experienced team of technical experts provides

answers to queries of a technical nature across the entire

Worcester range.

Worcester also has a pre-sales department, which provides

assistance in selecting a heating system to suit a particular

application, along with full guidance on installation. For

more information please contact the Technical Helpline

or alternatively visit our website where literature can be

downloaded www.worcester-bosch.co.uk.

Technical

Tel: 0330 123 3366

Fax: 01905 752 741

Email: [email protected]

Opening times

Monday – Friday: 7.00am – 8.00pm

Saturday: 8.30am – 4.00pm

Bank Holidays: 8.00am – 4.30pm

As part of the worldwide Bosch Group, Worcester strives to

maintain the highest possible standards of after-sales care.

In addition to the no-nonsense parts and labour

guarantee applicable to all Worcester products, you and

your customers have the assurance that every Worcester

product is manufactured to both the appropriate British

and European standards.

Worcester Contact Centre

Should you require support, our award winning Contact

Centre team, based at our head offi ce in Worcester, are

ready to take your calls. Whatever your query our contact

centre operators along with our nationwide team of

engineers are ready to help you.

Tel: 0330 123 9559

Opening times

Monday – Friday: 7.00am – 8.00pm

Saturday: 8.00am – 5.00pm

Sunday: 9.00am – 12 noon

Bank Holidays: 8.00am – 4.30pm

66

Page 67: NEW - Oil Tanks | Steel, Fuel Dispensing & Bunded Oil Tanks › wp-content › uploads › ... · Oilfit flexible flue liner 57 - 58 Accessories 59 - 62 Worcester training 63 - 65

6767

Notes

Page 68: NEW - Oil Tanks | Steel, Fuel Dispensing & Bunded Oil Tanks › wp-content › uploads › ... · Oilfit flexible flue liner 57 - 58 Accessories 59 - 62 Worcester training 63 - 65

Worcester, Bosch Group is a brand name of Bosch Thermotechnology Ltd.

This leafl et is accurate at the date of printing, but may be superseded and should be disregarded if specifi cation and/or appearances are changed in the interest of continued improvement. The statutory rights of the consumer are not affected.

Part No. 8 716 113 356 F 11/13 BB

T3140

PAPERS MADE WITH100% CHLORINE FREE

BLEACHED PULPTM

In partnership with

www.worcester-bosch.co.uk

Engineer Appointments

Email: [email protected]

or telephone 0330 123 9339

Enquiries

Email: [email protected]

or telephone 0330 123 9559

Guarantee Registration

To register your Worcester guarantee,

please visit our website

www.worcester-bosch.co.uk/registration

or telephone 0330 123 2552

Customer ServiceSales

Tel: 0330 123 9669

Fax: 01905 456445

[email protected]

Spare Parts

Tel: 0330 123 9779

Fax: 01905 754620

[email protected]

Technical Helpline (Pre & Post Sales)

Tel: 0330 123 3366

Fax: 01905 752741

[email protected]

Renewables Technical Helpline

Email: [email protected]

or telephone 0330 123 9229

Training

Tel: 0330 123 0166

Fax: 01905 752535

[email protected]

Literature

Email: [email protected]

or download instantly from our website

or telephone 0330 123 9119

Useful numbers

Calls to 03 numbers cost no more than a national rate call to an 01 or 02 number and must count towards any inclusive minutes in the same way as 01 and 02 calls.

These rules apply to calls from any type of line, including mobile, BT, other fi xed phone line or payphone. Calls from mobiles and some other networks may vary.

Calls to and from Bosch Thermotechnology Ltd may be recorded for training and quality assurance purposes.