new new 4000a continuous current frame rating for standard … · 2020. 5. 22. · new 4000a...

2
New 4000A continuous current frame rating for standard Magnum frame Product characteristics and performance Meets IEC 60947-2 standards Three- and four-pole configurations available Available only in drawout option 4000A rating plug and current sensors Width and height dimensions consistent with Magnum 3200A IEC drawout breaker 100% rated at full continuous current Up to 690 Vac 65 kA to 105 kA interrupting ratings Short-time withstand up to 85 kA (1 sec) / 65 kA (3 sec) Eaton’s MagnumE IEC low voltage power breaker offers a comprehensive portfolio of breaker frame sizes and ratings up to 6300A in four basic frame sizes to meet customer needs. With an on-going need to improve rating performance and product size, Eaton now offers a 4000A frame rating option in the standard Magnum frame. This allows for maximum configuration flexibility when selecting a power breaker to meet 4000A application needs. Magnum air circuit breakers meet the needs for IEC 60947-2 control and switchgear applications. The new 4000A frame rating of Magnum is available in a standard frame drawout configuration. Ratings and Capacities Magnum IEC Catalog (first 10 digits) Three-pole MWI6413LEA MWI8413LEA MWIC413LEA Four-pole MWI6414LEA MWI8414LEA MWIC414LEA Switching Capacity Rated short-circuit making capacity Up to 440V 50/60 Hz Up to 690V 50/60 Hz Icm kA kA 137 137 179 179 210 179 Rated short-time withstand current 50/60 Hz t = 1s t = 3s Icw kA kA 65 50 85 65 85 65 Rated Short-Circuit Breaker Capacity I cm IEC/EN 60947 operating sequence Icu O-t-CO Up to 240V 50/60 Hz Up to 440V 50/60 Hz Up to 690V 50/60 Hz Icu kA kA kA 65 65 65 85 85 85 105 105 85 IEC/EN 60947 operating sequence Ics O-t-CO-t-CO Up to 240V 50/60 Hz Up to 440V 50/60 Hz Up to 690V 50/60 Hz Ics kA kA kA 65 65 65 85 85 85 105 105 85 Protection, coordination, infor- mation and diagnostics with the DigitripE trip unit family Microprocessor-based rms sensing Basic to programmable over- current protection and alarms Ampere and power metering, power quality Local display for information and diagnostics Communicates with transla- tors to common protocols, such as ModbusT, INCOME and PROFIBUST Zone selective interlocking for improved coordination Arcflash Reduction Maintenance SystemE tech- nologies for arc flash reduction Breaker health monitoring Safety Third-party certifications and approvals: KEMA/CCC Arc flash reduction solutions Through-the-door design for interface with the breaker compartment door closed Maintenance, modification and service Internationally approved factory-installed and field-installable accessories Accessories common to all frame sizes Easy to add or replace accessories and renewal parts at the point of use Primary disconnecting contacts are mounted on the breaker for ease of inspection and replacement Eaton Electrical Services & Systems is available for startup and support Magnum IEC low voltage power circuit breakers

Upload: others

Post on 14-Oct-2020

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: New New 4000A continuous current frame rating for standard … · 2020. 5. 22. · New 4000A continuous current frame rating for standard Magnum frame Product characteristics and

New 4000A continuous current frame rating for standard Magnum frame

Product characteristics and performance

• MeetsIEC60947-2standards

• Three-andfour-poleconfigurationsavailable

• Availableonlyindrawoutoption

• 4000Aratingplugandcurrentsensors

• WidthandheightdimensionsconsistentwithMagnum3200AIECdrawoutbreaker

• 100%ratedatfullcontinuouscurrent

• Upto690Vac

• 65kAto105kAinterruptingratings

• Short-timewithstandupto85kA(1sec)/65kA(3sec)

Eaton’s MagnumE IEC low voltage power breaker offers a comprehensive portfolio of breaker frame sizes and ratings up to 6300A in four basic frame sizes to meet customer needs. With an on-going need to improve rating performance and product size, Eaton now offers a 4000A frame rating option in the standard Magnum frame. This allows for maximum configuration flexibility when selecting a power breaker to meet 4000A application needs. Magnum air circuit breakers meet the needs for IEC 60947-2 control and switchgear applications. The new 4000A frame rating of Magnum is available in a standard frame drawout configuration.

Ratings and Capacities

Magnum IEC Catalog (first 10 digits) Three-pole MWI6413LEA MWI8413LEA MWIC413LEA

Four-pole MWI6414LEA MWI8414LEA MWIC414LEA

Switching Capacity

Rated short-circuit making capacity

Up to 440V 50/60 HzUp to 690V 50/60 Hz

Icm kAkA

137137

179179

210179

Rated short-time withstand current 50/60 Hz

t = 1st = 3s

Icw kAkA

6550

8565

8565

Rated Short-Circuit Breaker Capacity Icm

IEC/EN 60947 operating sequence Icu O-t-CO

Up to 240V 50/60 HzUp to 440V 50/60 HzUp to 690V 50/60 Hz

Icu kAkAkA

656565

858585

10510585

IEC/EN 60947 operating sequence Ics O-t-CO-t-CO

Up to 240V 50/60 HzUp to 440V 50/60 HzUp to 690V 50/60 Hz

Ics kAkAkA

656565

858585

10510585

Protection, coordination, infor-mation and diagnostics with the DigitripE trip unit family

• Microprocessor-basedrmssensing

• Basictoprogrammableover-currentprotectionandalarms

• Ampereandpowermetering,powerquality

• Localdisplayforinformationanddiagnostics

• Communicateswithtransla-torstocommonprotocols,suchasModbusT,INCOMEandPROFIBUST

• Zoneselectiveinterlockingforimprovedcoordination

• ArcflashReductionMaintenanceSystemEtech-nologiesforarcflashreduction

• Breakerhealthmonitoring

Safety

• Third-partycertificationsandapprovals:KEMA/CCC

• Arcflashreductionsolutions

• Through-the-doordesignforinterfacewiththebreakercompartmentdoorclosed

Maintenance, modification and service

• Internationallyapprovedfactory-installedandfield-installableaccessories

• Accessoriescommontoallframesizes

• Easytoaddorreplaceaccessoriesandrenewalpartsatthepointofuse

• Primarydisconnectingcontactsaremountedonthebreakerforeaseofinspectionandreplacement

• EatonElectricalServices&Systemsisavailableforstartupandsupport

Magnum IEC low voltage power circuit breakers

Page 2: New New 4000A continuous current frame rating for standard … · 2020. 5. 22. · New 4000A continuous current frame rating for standard Magnum frame Product characteristics and

Technical Data—Magnum IEC Standard Frame 4000A Ratings

General

Standards IEC/EN 60947

Ambient temperature Storage –40º to +70ºC (device with LCD display –20º to +70ºC)

Operating (open)

–25º to +70ºC (device with LCD display –20º to +70ºC)

Mounting position 30º 30º 30º 30º

Utilization category B

Protection type IP20, IP55 with protective cover

Direction of incoming supply As required

Weight—drawout unit Three-pole 138.8 kg

Four-pole 166.0 kg

Lifespan

Mechanical, without maintenance 5000 operations

Mechanical, with maintenance 8000 operations

Electrical, without maintenance 3000 operations

Electrical, with maintenance 3000 operations

Maximum operating frequency 60 operations/h

Heat dissipation at rated current In

with three-phase symmetrical loadWithdrawable units

750W

Main Conducting Paths

Rated current = rated uninterrupted current In = Iu 4000A

Rated uninterrupted current at 50ºC Iu 3815A

Rated uninterrupted current at 60ºC Iu 3318A

Rated uninterrupted current at 70ºC Iu 2752A

Rated impulse withstand voltage Uimp 12,000 Vac

Rated operational voltage Ue 690 Vac

Use in IT electrical power networks up U = 440V

IIT 40.0 kA

Use in IT electrical power networks up U = 690V

IIT —

Overvoltage category/pollution degree III/3

Rated insulation voltage Ui 1000V

Permissible continuous current for circuit breakers in switchboards at various internal ambient temperatures. The switchboard’s internal ambient temperature should be estimated using calculation methods of IEC regulation.

66.1

30.5

123.2

14.5

101.6

83.3

410.9 138.9

100.8

161.3Typical right side view for both three- and four-pole. For additional dimensional drawings and CAD block files, please go to www.eaton.com and www.eaton.com/magnum.

365.2

10.7

52.1

33.5

33.5

127.0 127.0

33.2

33.2

491.4

10.8

33.8

33.8

33.4

33.4

Rear View Three-Pole Rear View Four-Pole

Top View Three-Pole Top View Four-Pole

4X 127.0 127.0

6X

For additional information on Eaton’s Magnum and Series NRXE power breakers, please go to www.eaton.com and www.eaton.com/magnum.

Dimensions in mm

Eaton CorporationElectricalSector1111SuperiorAve.Cleveland,OH44114UnitedStates877-ETN-CARE(877-386-2273)Eaton.com

©2010EatonCorporationAllRightsReservedPrintedinUSAPublicationNo.PA01301022E/Z9567March2010

PowerChainManagementisaregisteredtrademarkofEatonCorporation.

Allothertrademarksarepropertyoftheirrespectiveowners.