new new 4000a continuous current frame rating for standard … · 2020. 5. 22. · new 4000a...
TRANSCRIPT
New 4000A continuous current frame rating for standard Magnum frame
Product characteristics and performance
• MeetsIEC60947-2standards
• Three-andfour-poleconfigurationsavailable
• Availableonlyindrawoutoption
• 4000Aratingplugandcurrentsensors
• WidthandheightdimensionsconsistentwithMagnum3200AIECdrawoutbreaker
• 100%ratedatfullcontinuouscurrent
• Upto690Vac
• 65kAto105kAinterruptingratings
• Short-timewithstandupto85kA(1sec)/65kA(3sec)
Eaton’s MagnumE IEC low voltage power breaker offers a comprehensive portfolio of breaker frame sizes and ratings up to 6300A in four basic frame sizes to meet customer needs. With an on-going need to improve rating performance and product size, Eaton now offers a 4000A frame rating option in the standard Magnum frame. This allows for maximum configuration flexibility when selecting a power breaker to meet 4000A application needs. Magnum air circuit breakers meet the needs for IEC 60947-2 control and switchgear applications. The new 4000A frame rating of Magnum is available in a standard frame drawout configuration.
Ratings and Capacities
Magnum IEC Catalog (first 10 digits) Three-pole MWI6413LEA MWI8413LEA MWIC413LEA
Four-pole MWI6414LEA MWI8414LEA MWIC414LEA
Switching Capacity
Rated short-circuit making capacity
Up to 440V 50/60 HzUp to 690V 50/60 Hz
Icm kAkA
137137
179179
210179
Rated short-time withstand current 50/60 Hz
t = 1st = 3s
Icw kAkA
6550
8565
8565
Rated Short-Circuit Breaker Capacity Icm
IEC/EN 60947 operating sequence Icu O-t-CO
Up to 240V 50/60 HzUp to 440V 50/60 HzUp to 690V 50/60 Hz
Icu kAkAkA
656565
858585
10510585
IEC/EN 60947 operating sequence Ics O-t-CO-t-CO
Up to 240V 50/60 HzUp to 440V 50/60 HzUp to 690V 50/60 Hz
Ics kAkAkA
656565
858585
10510585
Protection, coordination, infor-mation and diagnostics with the DigitripE trip unit family
• Microprocessor-basedrmssensing
• Basictoprogrammableover-currentprotectionandalarms
• Ampereandpowermetering,powerquality
• Localdisplayforinformationanddiagnostics
• Communicateswithtransla-torstocommonprotocols,suchasModbusT,INCOMEandPROFIBUST
• Zoneselectiveinterlockingforimprovedcoordination
• ArcflashReductionMaintenanceSystemEtech-nologiesforarcflashreduction
• Breakerhealthmonitoring
Safety
• Third-partycertificationsandapprovals:KEMA/CCC
• Arcflashreductionsolutions
• Through-the-doordesignforinterfacewiththebreakercompartmentdoorclosed
Maintenance, modification and service
• Internationallyapprovedfactory-installedandfield-installableaccessories
• Accessoriescommontoallframesizes
• Easytoaddorreplaceaccessoriesandrenewalpartsatthepointofuse
• Primarydisconnectingcontactsaremountedonthebreakerforeaseofinspectionandreplacement
• EatonElectricalServices&Systemsisavailableforstartupandsupport
Magnum IEC low voltage power circuit breakers
Technical Data—Magnum IEC Standard Frame 4000A Ratings
General
Standards IEC/EN 60947
Ambient temperature Storage –40º to +70ºC (device with LCD display –20º to +70ºC)
Operating (open)
–25º to +70ºC (device with LCD display –20º to +70ºC)
Mounting position 30º 30º 30º 30º
Utilization category B
Protection type IP20, IP55 with protective cover
Direction of incoming supply As required
Weight—drawout unit Three-pole 138.8 kg
Four-pole 166.0 kg
Lifespan
Mechanical, without maintenance 5000 operations
Mechanical, with maintenance 8000 operations
Electrical, without maintenance 3000 operations
Electrical, with maintenance 3000 operations
Maximum operating frequency 60 operations/h
Heat dissipation at rated current In
with three-phase symmetrical loadWithdrawable units
750W
Main Conducting Paths
Rated current = rated uninterrupted current In = Iu 4000A
Rated uninterrupted current at 50ºC Iu 3815A
Rated uninterrupted current at 60ºC Iu 3318A
Rated uninterrupted current at 70ºC Iu 2752A
Rated impulse withstand voltage Uimp 12,000 Vac
Rated operational voltage Ue 690 Vac
Use in IT electrical power networks up U = 440V
IIT 40.0 kA
Use in IT electrical power networks up U = 690V
IIT —
Overvoltage category/pollution degree III/3
Rated insulation voltage Ui 1000V
Permissible continuous current for circuit breakers in switchboards at various internal ambient temperatures. The switchboard’s internal ambient temperature should be estimated using calculation methods of IEC regulation.
66.1
30.5
123.2
14.5
101.6
83.3
410.9 138.9
100.8
161.3Typical right side view for both three- and four-pole. For additional dimensional drawings and CAD block files, please go to www.eaton.com and www.eaton.com/magnum.
365.2
10.7
52.1
33.5
33.5
127.0 127.0
33.2
33.2
491.4
10.8
33.8
33.8
33.4
33.4
Rear View Three-Pole Rear View Four-Pole
Top View Three-Pole Top View Four-Pole
4X 127.0 127.0
6X
For additional information on Eaton’s Magnum and Series NRXE power breakers, please go to www.eaton.com and www.eaton.com/magnum.
Dimensions in mm
Eaton CorporationElectricalSector1111SuperiorAve.Cleveland,OH44114UnitedStates877-ETN-CARE(877-386-2273)Eaton.com
©2010EatonCorporationAllRightsReservedPrintedinUSAPublicationNo.PA01301022E/Z9567March2010
PowerChainManagementisaregisteredtrademarkofEatonCorporation.
Allothertrademarksarepropertyoftheirrespectiveowners.