new methods for ponding analysis of open web steel joist roofs · aisc appendix 2 “this appendix...
TRANSCRIPT
Presentedby:
Copyright©2018SteelJoistInstitute.AllRightsReserved.
F E B R U A R Y 2 1 , 2 0 1 8
MarkD.Denavit,P.E.,Ph.D.JamesM.Fisher,Ph.D.,P.E.,Dist.M.ASCE
NewMethodsforPondingAnalysisofOpenWebSteelJoistRoofs
PollingQuestion
2
• NewrequirementtoearnPDHcredits
• Twoquestionswillbeaskedduringthedurationoftoday’spresentation
• ThequestionwillappearwithinthepollingsectionofyourGoToWebinarControlPaneltorespond
Disclaimer
3
Theinformationpresentedhereinisdesignedtobeusedbylicensedprofessionalengineersandarchitectswhoarecompetenttomakeaprofessionalassessmentofitsaccuracy,suitabilityandapplicability.TheinformationpresentedhereinhasbeendevelopedbytheSteelJoistInstituteandisproducedinaccordancewithrecognizedengineeringprinciples.TheSJIanditscommitteeshavemadeaconcertedefforttopresentaccurate,reliable,andusefulinformationonthedesignofsteeljoistsandJoistGirders.ThepresentationofthematerialcontainedhereinisnotintendedasarepresentationorwarrantyonthepartoftheSteelJoistInstitute.Anypersonmakinguseofthisinformationdoessoatone’sownriskandassumesallliabilityarisingfromsuchuse.
LearningObjectives
4
1. RecalltheroofpondingrequirementswithinASCE7,IBC,andFMGlobal.
2. DescribethelimitationsofthemethodofpondinganalysisgiveninAppendix2oftheAISCSpecification.
3. InvestigatethestabilityofsimpleroofsystemsforpondingusingtheSJIRoofBayAnalysisTool.
4. Identifythemainfactorsinfluencingthepondingstabilityofopen-websteeljoistroofs.
NewMethodsforPondingAnalysisofOpenWebSteelJoistRoofs
• ReviewofroofpondingrequirementsandintroductiontotheSJIRoofBayAnalysisTool
– PresentedbyJimFisher
• ThedirectanalysismethodforpondingandusingtheSJIRoofBayAnalysisTooltoevaluatesusceptiblebays
– PresentedbyMarkDenavit
5
SJITechnicalDigestNo.3
7
STRUCTURALDESIGNOFSTEELJOISTROOFSTORESISTPONDINGLOADSORDERFROMsteeljoist.org$25.00
RoofPonding
• Commentson:
– IBC2015– ASCE7-2016– FMGlobal1-54,2016
– ANSI/AISC360-16– ANSI/SJI100-2015
8
InternationalBuildingCode1503.4RoofDrainage.
“DesignandinstallationofroofdrainagesystemsshallcomplywithSection1503ofthiscodeandSections1106and1108,asapplicable,oftheInternationalPlumbingCode.”
1503.4.1Secondary(emergencyoverflow)drainsorscuppers.
“Whereroofdrainsarerequired,secondary(emergencyoverflow)roofdrainsorscuppersshallbeprovidedwheretheroofperimeterconstructionextendsabovetheroofinsuchamannerthatwaterwillbeentrappediftheprimarydrainsallowbuildupforanyreason.Theinstallationandsizingofsecondaryemergencyoverflowdrains,leadersandconductorsshallcomplywithSections1106and1108,asapplicable,oftheInternationalPlumbingCode.”
9
InternationalBuildingCode
1503.4.2Scuppers.
“Whenscuppersareusedforsecondary(emergencyoverflow)roofdrainage,thequantity,size,locationandinletelevationofthescuppersshallbesizedtopreventthedepthofpondingwaterfromexceedingthatforwhichtheroofwasdesignedasdeterminedbySection1611.1.Scuppersshallnothaveanopeningdimensionoflessthan4inches(102mm).Theflowthroughtheprimarysystemshallnotbeconsideredwhenlocatingandsizingscuppers.”
10
InternationalBuildingCode
1507.10Built-uproofs.
“Theinstallationofbuilt-uproofsshallcomplywiththeprovisionsofthissection.”
1507.10.1Slope.
“Built-uproofsshallhaveadesignslopeofaminimumofnotlessthanone-fourthunitverticalin12unitshorizontal(2-percentslope)fordrainage,exceptforcoal-tarbuilt-uproofsthatshallhaveadesignslopeofaminimumnotlessthanone-eighthunitverticalin12unitshorizontal(1-percentslope).”
11
InternationalBuildingCode
1608.3“SusceptiblebaysofroofsshallbeevaluatedforpondinginstabilityinaccordancewithSection7.11ofASCE7.”
12
InternationalBuildingCode
1611.1Designrainloads.
“Eachportionofaroofshallbedesignedtosustaintheloadofrainwaterthatwillaccumulateonitiftheprimarydrainagesystemforthatportionisblockedplustheuniformloadcausedbywaterthatrisesabovetheinletofthesecondarydrainagesystematitsdesignflow.Thedesignrainfallshallbebasedonthe100-yearhourlyrainfallrateindicatedinFigure1611.1oronotherrainfallratesdeterminedfromapprovedlocalweatherdata.
R=5.2(ds+dh) (Equation16-36)”
13
InternationalBuildingCode
where:
dh=Additionaldepthofwaterontheundeflectedroofabovetheinletofsecondarydrainagesystematitsdesignflow(i.e.,thehydraulichead),ininches.
ds=Depthofwaterontheundeflectedroofuptotheinletofsecondarydrainagesystemwhentheprimarydrainagesystemisblocked(i.e.,thestatichead),ininches.
R=Rainloadontheundeflectedroof,inpsf.Whenthephrase"undeflectedroof"isused,deflectionsfromloads(includingdeadloads)shallnotbeconsideredwhendeterminingtheamountofrainontheroof.”
14
InternationalBuildingCode
1611.2Pondinginstability
“SusceptiblebaysofroofsshallbeevaluatedforpondinginstabilityinaccordancewithSection8.4ofASCE7.”
1611.3Controlleddrainage.
“Roofsequippedwithhardwaretocontroltherateofdrainageshallbeequippedwithasecondarydrainagesystematahigherelevationthatlimitsaccumulationofwaterontheroofabovethatelevation.SuchroofsshallbedesignedtosustaintheloadofrainwaterthatwillaccumulateonthemtotheelevationofthesecondarydrainagesystemplustheuniformloadcausedbywaterthatrisesabovetheinletofthesecondarydrainagesystematitsdesignflowdeterminedfromSection1611.1.SuchroofsshallalsobecheckedforpondinginstabilityinaccordancewithSection1611.2.”
15
ASCE7-16Criteria
• 7.11PondingInstability– Susceptiblebaysshallbedesignedtoprecludepondinginstability.Roofdeflectionscausedbythefullsnowloadsshallbeevaluatedwhendeterminingthelikelihoodofpondinginstability(seeSection8.4)
16
ASCE7-16Criteria• 8.4PONDINGINSTABILITYANDPONDINGLOADSusceptiblebaysshallbeinvestigatedbystructuralanalysistoassurethattheypossessadequatestiffnesstoprecludeprogressivedeflection(i.e.,instability)andadequatestrengthtoresisttheadditionalpondingloadAnyofthefollowingconditionsshallbedeemedtocreatesusceptiblebays:
• 1)Bayswitharoofslopelessthan1/4inchperfootwhenthesecondarymembersareperpendiculartothefreedrainingedge.
• 2)Bayswitharoofslopelessthan1inchperfootwhenthesecondarymembersareparalleltothefreedrainingedge.
• 3)Bayswitharoofslopeof1inchperfootandaspantospacingratioforthesecondarymembersgreaterthan16whenthesecondarymembersareparalleltothefreedrainingedge.
• 4)Baysonwhichwateraccumulates(inwholeorinpart)whentheprimarydrainsystemisblockedbutthesecondarydrainsystemisfunctional.Thelargerofthesnowloadortherainloadequaltothedesignconditionforablockedprimarydrainsystemshallbeusedinthisanalysis.
17
FMGlobal1-54
• SECTION2.5.4.1.6.5
• “A.Providesecondarydrainagetopreventanypossibilityofrainwateroverload.Theoverflowreliefprovisionestablishesthemaximumpossiblewaterlevelbasedonblockageoftheprimarydrainagesystem.Ensuretheprovisionisintheformofminimalheightroofedges,slotsinroofedges,overflowscuppersinparapetsoroverflowdrainsadjacenttoprimarydrains.
• B.Ensuretheoverflowreliefprotectionprovidespositiveanduniformdrainagereliefforeachroofsection.
• C.Whendesigningandsizingthesecondarydrainagesystem(overflowdrainsorscuppers),assumetheprimarydrainsare100%blockedandcannotflowwater.
• D.Ensuretheinletelevationofoverflowdrainsandtheinvertelevation(seesketchesinTable6aand8d)ofoverflowscuppersarenotlessthan2in.(50mm)normorethan3in.(75mm)abovethelowpointofthe(adjacent)roofsurfaceunlessasaferwaterdepthloading,includingtherequiredhydraulicheadtomaintainflow,hasbeendeterminedbytheroof-framingdesigner.”
19
AISCSpecifications-SectionB3DESIGNBASIS
B3.10.DesignforPonding
“Theroofsystemshallbeinvestigatedthroughstructuralanalysistoensurestrengthandstabilityunderpondingconditions,unlesstheroofsurfaceisconfiguredtopreventtheaccumulationofwater.MethodsofevaluatingstabilityandstrengthunderpondingconditionsareprovidedinAppendix2.”
20
AISCAppendix2
“Thisappendixprovidesmethodsfordeterminingwhetheraroofsystemhasadequatestrengthandstiffnesstoresistponding.Thesemethodsarevalidforflatroofswithrectangularbayswherethebeamsareuniformlyspacedandthegirdersareconsideredtobeuniformlyloaded.
Theappendixisorganizedasfollows:
– 2.1.SimplifiedDesignforPonding
– 2.2.ImprovedDesignforPonding
ThemembersofaroofsystemshallbeconsideredtohaveadequatestrengthandstiffnessagainstpondingbysatisfyingtherequirementsofSections2.1or2.2.”
21
AISCAppendix2
2.1.SIMPLIFIEDDESIGNFORPONDING
Theroofsystemshallbeconsideredstableforpondingandnofurtherinvestigationisneededifbothofthefollowingtwoconditionsaremet:
Cp+0.9Cs≤0.25 (A-2-1)
Id≥25(S4)10-6 (A-2-2)
Id≥3940S4 (A-2-2M)
22
AISCAppendix2
2.2.IMPROVEDDESIGNFORPONDING
ItispermittedtousetheprovisionsinthissectionwhenamoreaccurateevaluationofframingstiffnessisneededthanthatgivenbyEquationsA-2-1andA-2-2.
Definethestressindexes
23
0 8
0 8
. for primary member (A-2-5)
. for secondary member (A-2-
y op
o p
y os
o s
F fU
f
F fU
f
−⎛ ⎞= ⎜ ⎟⎝ ⎠
−⎛ ⎞= ⎜ ⎟⎝ ⎠
6)
AISCSPECIFICATION
24
ImprovedDesign:
Up,thestressindexfortheprimarymemberUs,thestressindexforthesecondarymemberCp,thestiffnessindexfortheprimarymemberCs,thestiffnessindexforthesecondarymemberfo,thestressatinitiationofponding
0.8 for the primary member (Eq. A-2-5)
0.8for the secondary member (Eq. A-2-6)
y op
o p
y os
o s
F fU
f
ffF
U
−⎛ ⎞= ⎜ ⎟⎝ ⎠
⎛ ⎞⎜ ⎟⎝ ⎠
−=
AISCAppendix2PondingAssumptions
• Framingisflat.
• Membersarenotcambered.
• Taperedinsulationnotconsidered.
• Baysarerectangular.
• Adjacentbaysareidentical.
• Beamsareuniformlyspaced.
• Allbeamshaveequalstiffness.
• Allmembersaresimplysupported.
• Axialloadsnotpresent.
• Waterloadcoverstheentirebay.
25
PondingLoadStrategiesbasedontheAISCprovisions:• Provideroofsystemstoavoidpondingbyslopingroofmembers,orbythe
useoftaperedinsulationorslopingfill.
• Stiffentheroof’sstructuralmembersbyselectingacombinationoflowflexibilityconstantswhichsatisfyEquationA-2-1oftheAISCSpecificationAppendix2(AISC2016).
• ConductamoreexactanalysisforpondingfollowingtheproceduresgivenintheAISCSpecificationAppendix2.
• Counteractthepondingmechanismbyprovidingupwardcamberinthejoists,providedthatdrainsareinstallednearcolumns(seeFMGlobal1-54FM(2016).
• Whendesigningroofswithlowslopes,parallelchordjoistswithendsupportsatdifferentelevationsaremoreeconomicalthanprovidingpitchintothejoisttopchords.Thewebsystemofanon-parallelchordjoistandthejoistasawholeismoreexpensivetomanufacture……”
26
ANSI/SJI100-2015
• StandardSpecificationforK-Series,LH-Series,andDLH-SeriesOpenWebSteelJoistsandforJoistGirders.
• TheSJISpecificationsinSection5.11containsthefollowingrequirementrelativetoponding:
– “Thepondinginvestigationshallbeperformedbythespecifyingprofessional.”
27
COMMENTSONTHECITEDDOCUMENTS:
• Allroofsrequireasecondarydrainagesystem.
• Allroofsmustbedesignedforimpoundedwaterbasedontheprimarydrainsbeingblocked.
• Impoundedwaterheightsaretoincludethehydraulicheadabovethesecondarydrainagesystem.
• Pondinginstabilitychecksaretobemadeusingthelargerofsnowloadorrainload(impoundedwater).
28
COMMENTSONTHECITEDDOCUMENTS:
• Forroofswithsnowloadsof20psforless,anadditional5psfofrainonsnowmustbeusedindesign.
• FollowIBCrequirementsinSection1507.10.1Slope.“Built-uproofsshallhaveadesignslopeofnotlessthanone-fourthunitverticalin12unitshorizontal(2-percentslope)fordrainage,exceptforcoal-tarbuilt-uproofsthatshallhaveadesignslopeofnotlessthanone-eighthunitverticalin12unitshorizontal(1-percentslope).”
29
GeneralInfoTab-Notes• GoverningcodeisIBC2012.
• BaysizesarelimitedtoJoistandJoistGirderLoadTables.
• Decksizeselectedbyminimumweightanddeflectionlimits,fromSDITables.
• DeckdeflectionisbasedonminimumofIporIn,perdirectionofSDI.
• SDIminimumbearinglengthsassumed.
• JoistsizeselectedbyminimumweightanddeflectionlimitsfromSJILoadTables.
• DLHjoistdataislimitedtospansgreaterthanthe“safeload”spansintheSJILoadTables.
39
Joist/JoistGirderDepths&DeflectionChecks
43
OPTIONAL INCREASED LOAD DATA Member I Ieff = I/1.15
Joist Load lb / ft 18K 3 85 74 in.4
JG Panel Point Load kips 60G10N4.6F 2484 2160 in.4 NEW
Suggestdoingthis.
PollingQuestion
WhichofthefollowingisNOToneoftheassumptionsmadeforthepondingprovisionsinAppendix2oftheAISCSpecification?
A. TheroofsatisfiestheIBCminimumsloperequirements.
B. Themembersarenotcambered.
C. Thebeamsareuniformlyspaced.
D. Thebeamshaveequalstiffness.
E. Waterloadcoverstheentirebay.
49
NewMethodsforPondingAnalysisofOpenWebSteelJoistRoofs
• ReviewofroofpondingrequirementsandintroductiontotheSJIRoofBayAnalysisTool
– PresentedbyJimFisher
• ThedirectanalysismethodforpondingandusingtheSJIRoofBayAnalysisTooltoevaluatesusceptiblebays
– PresentedbyMarkDenavit
50
LimitationsoftheAISCAppendix2Method
• Flatroofconstruction– ThemethodinAISCAppendix2assumesaperfectlyflatroof
• Noroofslopeandnocamber
• Momentandshearenvelopes– ThemethodinAISCAppendix2checksonlythemaximummoment
• Nocheckformomentandshearstrengththatvaryalongthelength• Nolocalchecks(e.g.,bendingbetweenpanelpoints)
• Levelofloading– ThemethodinAISCAppendix2isonlyintendedforusewithASD
• NoprovisionsforusewithLRFD
51
DirectAnalysisMethodforPonding
• Anewmethodtoevaluateroofsforponding
• SimilarinconcepttothedirectanalysismethoddescribedinChapterCoftheAISCSpecification,buttherearemanydifferences
• Load-effectsduetoimpoundedwaterarecomputeddirectlybasedonthedeformedshapeoftheroofsystem
• Checkperformedbycomparingrequiredstrengthstoavailablestrengths
52
RequiredStrengths
• Determinedfromananalysisthatcapturesthenonlinearloadingfromtheimpoundedwater
– Closed-formsolutionsavailableforsimplecases
– Iterativeanalysisforgeneralcases
• Geometricnonlinearity(second-ordereffects)andmaterialnonlinearity(inelasticity)neednotbecaptured
53
LoadCombinations
• ForthepondingcheckSJIrecommendsusing:
– D+0.75P+0.75S forASD
– 1.2D+1.2P+1.2S forLRFD
• NotethattheIBCstrengthcombinationsstillneedtobechecked
– D+(LrorSorR) forASD
– 1.2D+1.6(LrorSorR) forLRFD
54
D =DeadLoadP =ImpoundedWaterLoadS =SnowLoadLr =RoofLiveLoadR =RainLoad
ForceLevelAdjustmentFactor
• RequirementfromChapterCoftheAISCSpecification:
“Allload-dependenteffectsshallbecalculatedatalevelofloadingcorrespondingtoLRFDloadcombinationsor1.6
timesASDloadcombinations.”
• FordesignbyASD,theanalysisisconductedunder1.6timestheASDloadcombination,andtheresultinginternalforcesaredividedby1.6toobtaintherequiredstrengthsofcomponents
55
Loads
• Waterandsnowactatthesametime,butaccountforthephysicaloverlapofmaterial– Densityofwateronly=62.4lb/ft3– Densityofsnowonly=γ (14-30lb/ft3,ASCE7-16Equation7.7-1)– Densityofwaterandsnow=62.4lb/ft3
56
Water Level
Water Only
AvailableStrengths
• MomentandshearenvelopespertheSJISpecification
57
0
wL2/8
0
wL/2
-wL/2
wL/8 (25% of end reaction, per SJI Specification)
wL/16 (12.5% of end reaction,assumed)
Shear diagram for simply supported beam under uniformly
distributed load
JoistMomentEnvelope JoistShearEnvelope
NotethattheSJISpecificationdoesnotrequireanystrengthforshearreversals.12.5%ofendreactionisassumedandactionmustbetakentoensurethatcapacity
AvailableStrengths
• MomentandshearenvelopespertheSJISpecification
58
JoistGirderMomentEnvelope JoistGirderShearEnvelope
0
Mmax
0
R
R
R/4 (25% of end reaction, per SJI Specification)
Shear diagram for simply supported beam with equal point loads
25% of shear envelope in reverse direction per SJI Specification
GeneralInput
• GeneraldatareferencedfromRoofBayAnalysissheet
60
General Input (Defined in Roof Bay Analysis Spreadsheet)
Design Methodology ASD40.00 ft40.00 ft24K 7253 lb/ft
36G8N6.2K6.2 k8
18.00 psf36.00 lb/ft12.00 psf
Joist SpanJoist Girder SpanJoist Size
Dead Load on Joists
Snow Load
Joist Girder Size
Number of Joist Spaces
Joist Girder Self Weight
Joist Allowable Load
Joist Girder Allowable Load
PondingSpecificInput
• Additionaldatabeyondwhatisdefinedonthe“RoofBayAnalysis”sheet
• Defines:– Waterload– Loadfactors– Undeformedshapeof
theroof(slopeandcamber)
– Adjacentbays– etc.
61
Ponding Specific Input
-3.00 inCompute load on deformed roof: Y (Y or N)
15.30 lb/ft3
Force level adjustment factor (α ): 1.60override:
Load factors:1.00
override:0.75
override:0.75
override:
0.000 in0.000 in
-10.000 in-10.000 in
Camber:0.625 in
override: in0.000 in
override: in0.625 in
override: inBay is mirrored:
Y (Y or N)Y (Y or N)N (Y or N)Y (Y or N)
Joist support is wall:Y (Y or N)N (Y or N)
N (Y or N)N (Y or N)
Effective moment of inertia:215.1 in4
(Values include override: in4
1.15 factor for 1,677 in4
shear deformations) override: in4
Joist is rigid:
Bottom Joist Girder
Top Joist Girder
Top
Joist Girder
Joist 1 (Leftmost)Joist 9 (Rightmost)
Snow
Dead
Top of roof elevation:
Bottom Right
Snow density:
BottomTop
Bottom
Right
Joist
Left
Bottom LeftTop RightTop Left
Water level relative to zero datum:
Joist
Ponded Water
AnalysisProcedure
• Readinputandsetupanalysis(e.g.,computejoistandjoistgirderstiffnessmatrices)
• Loopuntilconvergence:– Computepondedwaterloads
– Analyzeeachjoist
– Analyzejoistgirders(ifnecessary)
– Checkforconvergencebasedonpondedwaterloadvector
• Computeanddisplayandmoments,shears,andequivalentloads
62
RUN ANALYSIS
Convergence!
Iteration ΣW# (kips)1 14.7852 30.3473 34.1714 35.1135 35.3486 35.4077 35.4218 35.4259 35.42610 35.4261112131415
ComputingPondingLoads
• Thebaydiscretizedintoagridofcellstocomputepondingloads.
– Furthersubdivisionintoa4x4girdwithineachcell– Colombi,P.(2006).“ThePondingProblemonFlatSteelRoofGrids.”JournalofConstructionalSteelResearch,62(7),647–655.
63
JoistOutput
64
Joist Output
Joist Max Shear Equiv. Load Max Moment Equiv. Load Strength StrengthNumber kips lb/ft kip-ft lb/ft Ratio Check
1 4.29 214.3 39.10 212.9 0.85 OKAY2 4.44 222.0 40.32 220.3 0.88 OKAY3 4.64 232.2 41.97 230.3 0.92 OKAY4 4.78 239.2 43.10 237.2 0.95 OKAY5 4.83 241.7 43.49 239.7 0.96 OKAY6 4.78 239.2 43.10 237.2 0.95 OKAY7 4.64 232.2 41.97 230.3 0.92 OKAY8 4.44 222.0 40.32 220.3 0.88 OKAY9 4.29 214.3 39.10 212.9 0.85 OKAY
NOTES: 1. Loads and load effects correspond to ASD load combinations.2. Strength ratio computed assuming shear capacity equal to 12.5% of the end reaction for shear reversals, see Note 14 on the Ponding Instructions spreadsheet.
RUN ANALYSIS
JoistOutput
65
JoistNumber 0' 0" 2' 0" 4' 0" 6' 0" 8' 0" 10' 0" 12' 0" 14' 0" 16' 0" 18' 0" 20' 0" 22' 0" 24' 0" 26' 0" 28' 0" 30' 0" 32' 0" 34' 0" 36' 0" 38' 0" 40' 0"
1 243 241 239 236 233 229 225 220 214 208 200 192 183 173 163 152 141 135 135 135 1352 253 251 248 245 242 238 233 228 222 215 207 198 188 178 167 155 143 136 135 135 1353 267 265 261 258 254 249 244 238 231 224 215 206 195 184 172 160 147 137 135 135 1354 277 274 270 266 262 257 252 245 238 230 221 211 200 188 176 163 149 137 135 135 1355 281 278 273 269 265 260 254 248 241 232 223 213 202 190 177 164 150 138 135 135 1356 277 274 270 266 262 257 252 245 238 230 221 211 200 188 176 163 149 137 135 135 1357 267 265 261 258 254 249 244 238 231 224 215 206 195 184 172 160 147 137 135 135 1358 253 251 248 245 242 238 233 228 222 215 207 198 188 178 167 155 143 136 135 135 1359 243 241 239 236 233 229 225 220 214 208 200 192 183 173 163 152 141 135 135 135 135
NOTES: 1. Loads correspond to ASD load combinations.2. Highlighted distributed loads may cause a local overstress, see notes on Ponding Instructions spreadsheet.
Total Distributed Load on Joist as a Function of Distance from Bottom Support (lb/ft)
JoistOutput
66
JoistNumber 0' 0" 2' 0" 4' 0" 6' 0" 8' 0" 10' 0" 12' 0" 14' 0" 16' 0" 18' 0" 20' 0" 22' 0" 24' 0" 26' 0" 28' 0" 30' 0" 32' 0" 34' 0" 36' 0" 38' 0" 40' 0"
12 03 14 12 8 5 14 24 21 17 13 9 45 28 25 20 16 12 7 16 24 21 17 13 9 47 14 12 8 5 18 09
Total Distributed Load in Excess of Allowable Load on Joist as a Function of Distance from Bottom Support (lb/ft)
JoistGirderOutput
67
Joist Girder Output
Joist Joist React. Joist React.Number kips kips
2 3.48 4.443 3.58 4.644 3.65 4.785 3.68 4.836 3.65 4.787 3.58 4.648 3.48 4.44
N/A (WALL) 9.78N/A (WALL) 9.62N/A (WALL) 1.58N/A (WALL) NO GOOD
NOTES: 1. Loads and load effects correspond to ASD load combinations.2. Highlighted panel point loads may cause a local overstress, see notes in Ponding Instructions.
Joist Girder size can be revised by inputting larger loads in the ''optional increased load data'' section of the Roof Bay Analysis spreadsheet
Top Joist GirderPanel Point Load
kips
Strength Check:
Bottom Joist GirderPanel Point Load
kips9.069.479.75
Strength Ratio:Strength Check:
Equiv. Load for Shear (kips):
Strength Ratio:
Equiv. Load for Shear (kips):Equiv. Load for Moment (kips): Equiv. Load for Moment (kips):
9.859.759.479.06
Procedure
1.CompleteinitialdesignofroofsystemforprimarydesignloadsandidentifysusceptiblebaysinaccordancewithSection8.4ofASCE7-16.
• Theremainingstepswillneedtobecompletedforeachuniquesusceptiblebay.
2.DeterminethejoistandJoistGirderpreliminarydesignusingtheroofbayanalysisspreadsheet.
3.Determinethehydraulicheadbasedontheflowrate,Q,andthedrainagesystem.
• TheflowratecanbedeterminedusingASCE7-16EquationC8-1.
• ThehydraulicheadcanbedeterminedbasedonASCE7-16TableC8.3-1(overflowdamsorstandpipes),C8.3-3(scuppers),orC8.3-5(circularscuppers)
68
Procedure
4.Determinethewaterlevelabovetheprimarydrain(dh+ds).
• ChecktheBuildingCodetoseeifaminimumheightforsecondarydrainsisprovided.ASCE7-16providesnominimumheightexceptthattheheightshouldbehigherthantheprimarydrain.Aminimumof2inchesabovetheprimarydrainisoftenusedandisrequiredbyFMGlobal.
• Somecodesrequirethatscuppersbeaminimumof2inchesabovetherooflevel,butshouldnotexceed4inchesabovetherooflevel.
5.Inputtherequireddataintothepondinganalysisspreadsheet.Thedatafromtheroofbayanalysisisautomaticallytransferredtothepondinganalysis.
69
Procedure6.Runthepondinganalysis.
• Ifstabilityisachieved,theanalysisiscomplete.PondingstabilityisachievedwhentheshearandmomentenvelopesforthejoistsandJoistGirdersarenotexceeded.
• Ifstabilityisnotachieved,returntotheroofbayanalysisandselectalargerjoist,JoistGirder,orbothbyinputtingincreasedloadsinthe“optionalincreasedloaddata”section(ordecreasethejoistspacing).Rerunthepondinganalysisuntilstabilityisachieved.
• Iflocalloadeffectsareindicated(loadshighlightedwithredfont)determinebasedonanalysisorjudgementwhethertheindicatedappliedloadswillcausealocalizedoverstress.Iftheloadsaredeterminedtocauseoverstress,reruntheanalysiswithlargerjoistsorJoistGirders.
70
Procedure
7.Determineifloadingonthejoistsissymmetricorcouldcauseshearreversals.IfthereispotentialforshearreversalinthejoistsandshearreversalisnotaddressedviaotherdesignloadingcriteriasuchasNetUpliftorSnowDrift,specifythatjoistmanufacturerisrequiredto“designjoistsandJoistGirderwebsforaminimumverticalshearequalto12.5%oftheendreactionincompression.”
71
0
wL/2
-wL/2
wL/8 (25% of end reaction, per SJI Specification)
wL/16 (12.5% of end reaction,assumed)
Shear diagram for simply supported beam under uniformly
distributed load
Example
• Example2fromSJITechnicalDigest3
• StructurelocatedinMemphis,TN
• DrainElevation=-10in.
• OverflowScupperElevation=-8in.
– Secondarydrainsare24in.wideopenchannelscuppers
72
Controllingsusceptiblebay
ProjectDescriptionandLoading
• GirderLength,Lg=40ft• GirderDepth=36in.• NumberofGirderTopChordPanelPointSpaces,N=8• JoistLength,Lj=40ft• JoistSpacing,S=5ft• DeadLoad,wD=18psf• GirderDeadLoad,wD=1psf• LiveLoad,wL=20psf(reducible)• SnowLoad,ws=7psf(requires5psfrain-on-snowsurcharge
load;seeIBC1611.2andSection7.10ofASCE7-16)
73
PreliminaryDesign
• EntertherelevantdataintotheRoofBayAnalysissheet
– SetmaximumJoistGirderdepthto36in.
• DataautomaticallytransferredtothePondingAnalysissheet
• Designsatisfactoryfordead,live,andsnowloads
– Stillneedtocheckrainloadcombinationandpondingstability
74
General Input (Defined in Roof Bay Analysis Spreadsheet)
Design Methodology ASD40.00 ft40.00 ft24K 7253 lb/ft
36G8N6.2K6.2 k8
18.00 psf36.00 lb/ft12.00 psf
Dead Load on Joists
Snow Load
Joist Girder Size
Number of Joist Spaces
Joist Girder Self Weight
Joist Allowable Load
Joist Girder Allowable Load
Joist SpanJoist Girder SpanJoist Size
DetermineHydraulicHead
• Therearetwooverflowsuppers,eachhasatributaryareaofhalfthetotalareaoftheroof:
A=(60ft.)(80ft.)=4800ft.2
• The100-yearhourlyrainfallrateforMemphis,TNis3.75in./hr.asdeterminedfromFigure1611.1inthe2015IBC
i=3.75in./hr
75
DetermineHydraulicHead
• DeterminetheflowrateusingEquationC8-1inASCE7-16:
Q=0.0104Ai,gals/min.(ASCE7-16Eq.C8.3-1)
Q=(0.0104)(4800ft.2)(3.75in./hr)=187.2gals/min.
76
DetermineHydraulicHead
• Aflowrateof187.2gals/min.correspondstoahydraulicheadbetween1and2in.forthe24in.widescupperaccordingtoTableC8.3-3ofASCE7-16.
• Interpolatingyieldsdh=1.9in. Usedh=2in.
77
DetermineSnowDensity
• ThegroundsnowloadforMemphis,TNis10psfasdeterminedfromFigure7.2-1ofASCE7-16
pg=10psf
• DeterminethesnowdensityusingEquation7.7-1ofASCE7-16
γ=0.13pg+14≤30lb/ft3
γ=15.3lb/ft3
78
PondingSpecificInput
• Waterlevel2in.abovesecondarydrain
– -8in.+2in.=-6in.
• Computeloadondeformedroof:Yes
• SJIRecommendedLoadCombination
– D+0.75P+0.75S– α=1.6
79
Ponding Specific Input
-6.00 inCompute load on deformed roof: Y (Y or N)
15.30 lb/ft3
Force level adjustment factor (α ): 1.60override:
Load factors:1.00
override:0.75
override:0.75
override:
0.000 in0.000 in
-10.000 in-10.000 in
Camber:0.625 in
override: in0.000 in
override: in0.625 in
override: inBay is mirrored:
Y (Y or N)Y (Y or N)N (Y or N)Y (Y or N)
Joist support is wall:Y (Y or N)N (Y or N)
N (Y or N)N (Y or N)
Effective moment of inertia:215.1 in4
(Values include override: in4
1.15 factor for 1,677 in4
shear deformations) override: in4
Joist is rigid:
Bottom Joist Girder
Top Joist Girder
Top
Joist Girder
Joist 1 (Leftmost)Joist 9 (Rightmost)
Snow
Dead
Top of roof elevation:
Bottom Right
Snow density:
BottomTop
Bottom
Right
Joist
Left
Bottom LeftTop RightTop Left
Water level relative to zero datum:
Joist
Ponded Water
JoistOutput
80
Joist Output
Joist Max Shear Equiv. Load Max Moment Equiv. Load Strength StrengthNumber kips lb/ft kip-ft lb/ft Ratio Check
1 3.36 167.8 30.37 166.3 0.66 OKAY2 3.46 172.8 31.08 171.2 0.68 OKAY3 3.59 179.6 32.08 177.8 0.71 OKAY4 3.69 184.3 32.78 182.4 0.73 OKAY5 3.72 186.0 33.03 184.1 0.74 OKAY6 3.69 184.3 32.78 182.4 0.73 OKAY7 3.59 179.6 32.08 177.8 0.71 OKAY8 3.46 172.8 31.08 171.2 0.68 OKAY9 3.36 167.8 30.37 166.3 0.66 OKAY
NOTES: 1. Loads and load effects correspond to ASD load combinations.2. Strength ratio computed assuming shear capacity equal to 12.5% of the end reaction for shear reversals, see Note 14 on the Ponding Instructions spreadsheet.
RUN ANALYSIS
JoistOutput
81
JoistNumber 0' 0" 2' 0" 4' 0" 6' 0" 8' 0" 10' 0" 12' 0" 14' 0" 16' 0" 18' 0" 20' 0" 22' 0" 24' 0" 26' 0" 28' 0" 30' 0" 32' 0" 34' 0" 36' 0" 38' 0" 40' 0"
1 197 194 190 186 182 177 172 166 160 154 146 139 135 135 135 135 135 135 135 135 1352 204 201 197 193 188 183 178 172 165 158 151 142 136 135 135 135 135 135 135 135 1353 214 211 207 202 197 192 186 179 172 165 157 148 139 135 135 135 135 135 135 135 1354 221 218 213 208 203 197 191 184 177 169 161 151 142 136 135 135 135 135 135 135 1355 223 220 215 210 205 199 193 186 179 171 162 153 143 136 135 135 135 135 135 135 1356 221 218 213 208 203 197 191 184 177 169 161 151 142 136 135 135 135 135 135 135 1357 214 211 207 202 197 192 186 179 172 165 157 148 139 135 135 135 135 135 135 135 1358 204 201 197 193 188 183 178 172 165 158 151 142 136 135 135 135 135 135 135 135 1359 197 194 190 186 182 177 172 166 160 154 146 139 135 135 135 135 135 135 135 135 135
NOTES: 1. Loads correspond to ASD load combinations.
Total Distributed Load on Joist as a Function of Distance from Bottom Support (lb/ft)
Appliedloadsgreatestatlocationofgreatest
deflection
Constantappliedloadwheretheroofis
abovethewaterlevel
JoistGirderOutput
82
Joist Girder Output
Joist Joist React. Joist React.Number kips kips
2 2.90 3.463 2.95 3.594 2.99 3.695 3.00 3.726 2.99 3.697 2.95 3.598 2.90 3.46
N/A (WALL) 7.58N/A (WALL) 7.47N/A (WALL) 1.22N/A (WALL) NO GOOD
NOTES: 1. Loads and load effects correspond to ASD load combinations.2. Highlighted panel point loads may cause a local overstress, see notes in Ponding Instructions.
Joist Girder size can be revised by inputting larger loads in the ''optional increased load data'' section of the Roof Bay Analysis spreadsheet
Top Joist GirderPanel Point Load
kips
Strength Check:
Bottom Joist GirderPanel Point Load
kips7.097.377.55
Strength Ratio:Strength Check:
Equiv. Load for Shear (kips):
Strength Ratio:
Equiv. Load for Shear (kips):Equiv. Load for Moment (kips): Equiv. Load for Moment (kips):
7.627.557.377.09
ReviseDesign
• The36G8N6.2Kwhichwasselectedbytheroofbayanalysissheetbasedondead,live,andsnowloadingisinsufficientforthepondingcondition.
– Itneedstobestrengthenedorstiffened.
• TheJoistGirderwillbebothstrengthenedandstiffenedifthepanelpointloadisincreased.
• Revisethedesignto36G8N7.5Kusingtheoptionalincreasedloaddataintheroofbayanalysissheet
83
OPTIONAL INCREASED LOAD DATA Member I Ieff = I/1.15Joist Load lb / ft 24K 7 247 215 in.4
JG Panel Point Load 7.5 kips 36G8N7.5K 2333 2029 in.4
JoistGirderOutput
84
Joist Girder Output
Joist Joist React. Joist React.Number kips kips
2 2.89 3.423 2.93 3.524 2.95 3.595 2.96 3.616 2.95 3.597 2.93 3.528 2.89 3.42
N/A (WALL) 7.37N/A (WALL) 7.29N/A (WALL) 0.98N/A (WALL) OKAY
NOTES: 1. Loads and load effects correspond to ASD load combinations.
Top Joist GirderPanel Point Load
kips
Strength Check:
Bottom Joist GirderPanel Point Load
kips7.017.227.36
Strength Ratio:Strength Check:
Equiv. Load for Shear (kips):
Strength Ratio:
Equiv. Load for Shear (kips):Equiv. Load for Moment (kips): Equiv. Load for Moment (kips):
7.417.367.227.01
CheckIBCStrengthLoadCombination
• Differencesinpondingspecificinput
– Computeloadondeformedroof:No
– Loadfactors(D+R)
• Bayfoundtobeadequate
85
Ponding Specific Input
-6.00 inCompute load on deformed roof: N (Y or N)
15.30 lb/ft3
Force level adjustment factor (α ): 1.60override:
Load factors:1.00
override:0.00
override:1.00
override:
0.000 in0.000 in
-10.000 in-10.000 in
Camber:0.625 in
override: in0.000 in
override: in0.625 in
override: inBay is mirrored:
Y (Y or N)Y (Y or N)N (Y or N)Y (Y or N)
Joist support is wall:Y (Y or N)N (Y or N)
N (Y or N)N (Y or N)
Effective moment of inertia:215.1 in4
(Values include override: in4
1.15 factor for 1,677 in4
shear deformations) override: in4
Joist is rigid:
Bottom Joist Girder
Top Joist Girder
Top
Joist Girder
Joist 1 (Leftmost)Joist 9 (Rightmost)
Snow
Dead
Top of roof elevation:
Bottom Right
Snow density:
BottomTop
Bottom
Right
Joist
Left
Bottom LeftTop RightTop Left
Water level relative to zero datum:
Joist
Ponded Water
Example
• Example4fromSJITechnicalDigest3
• Determineiftheroofisfreedrainingunderthetotalsuperimposedloads– DeadLoad=14psf– DeadLoad=1psf(JoistGirder)– SnowLoad=25psf
• Donotconsidercamber• Duetowallattachmentassume
theedgejoistdoesnotdeflect.• Theroofhasaslopeof1/4in./ft.
downwardtotheright.
86
PreliminaryDesign
• Usetheroofbayanalysistabtodesignthebayfordeadandsnowload
– 26K6Joist– 56G8N10KJoistGirder
87
General Input (Defined in Roof Bay Analysis Spreadsheet)
Design Methodology ASD40.00 ft50.00 ft26K 6247 lb/ft
56G8N10K10 k8
14.00 psf42.00 lb/ft25.00 psf
Dead Load on Joists
Snow Load
Joist Girder Size
Number of Joist Spaces
Joist Girder Self Weight
Joist Allowable Load
Joist Girder Allowable Load
Joist SpanJoist Girder SpanJoist Size
PondingSpecificInput
• Setwaterlevelaselevationofedgejoist
• Overrideloadfactorstoanominalloadconditionforthisserviceabilitycheck
– D+P+S– α=1.0
• Overridecambertozero(perproblemstatement)
88
Ponding Specific Input
0.00 inCompute load on deformed roof: Y (Y or N)
0.00 lb/ft3
Force level adjustment factor (α ): 1.00override: 1.00
Load factors:1.00
override:1.00
override: 1.001.00
override: 1.00
12.500 in0.000 in12.500 in0.000 in
Camber:0.000 in
override: 0 in0.000 in
override: 0 in0.000 in
override: 0 inBay is mirrored:
Y (Y or N)N (Y or N)Y (Y or N)Y (Y or N)
Joist support is wall:N (Y or N)N (Y or N)
N (Y or N)Y (Y or N)
Effective moment of inertia:228.1 in4
(Values include override: in4
1.15 factor for 5,259 in4
shear deformations) override: in4
Joist is rigid:
Bottom Joist Girder
Top Joist Girder
Top
Joist Girder
Joist 1 (Leftmost)Joist 9 (Rightmost)
Snow
Dead
Top of roof elevation:
Bottom Right
Snow density:
BottomTop
Bottom
Right
Joist
Left
Bottom LeftTop RightTop Left
Water level relative to zero datum:
Joist
Ponded Water
Output
89
Iteration ΣW# (kips)1 0.0002 0.6013 0.6984 0.7135 0.7166 0.7167 0.7168 0.7169 0.716
JoistNumber 0' 0" 2' 0" 4' 0" 6' 0" 8' 0" 10' 0" 12' 0" 14' 0" 16' 0" 18' 0" 20' 0" 22' 0" 24' 0" 26' 0" 28' 0" 30' 0" 32' 0" 34' 0" 36' 0" 38' 0" 40' 0"
1 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 2442 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 2443 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 2444 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 2445 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 2446 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 2447 244 244 244 244 244 245 246 248 250 251 251 251 250 248 246 245 244 244 244 244 2448 244 244 244 245 249 255 260 265 269 271 271 271 269 265 260 255 249 245 244 244 2449 122 122 122 122 124 125 126 127 128 129 129 129 128 127 126 125 124 122 122 122 122
NOTES: 1. Loads correspond to ASD load combinations.2. Highlighted distributed loads may cause a local overstress, see notes on Ponding Instructions spreadsheet.
Total Distributed Load on Joist as a Function of Distance from Bottom Support (lb/ft)
Convergeswithwater
Waterpresentonfirsttwoupslopejoistsasindicated
byload>244lb/ftTHEROOFISNOTFREEDRAINING
Ponding Specific Input
0.00 inCompute load on deformed roof: Y (Y or N)
0.00 lb/ft3
Force level adjustment factor (α ): 1.00override: 1.00
Load factors:1.00
override:1.00
override: 1.001.00
override: 1.00
12.500 in0.000 in12.500 in0.000 in
Camber:0.000 in
override: 0 in0.000 in
override: 0 in0.000 in
override: 0 inBay is mirrored:
Y (Y or N)N (Y or N)Y (Y or N)Y (Y or N)
Joist support is wall:N (Y or N)N (Y or N)
N (Y or N)Y (Y or N)
Effective moment of inertia:485.0 in4
(Values include override: 485 in4
1.15 factor for 5,259 in4
shear deformations) override: in4
Joist is rigid:
Bottom Joist Girder
Top Joist Girder
Top
Joist Girder
Joist 1 (Leftmost)Joist 9 (Rightmost)
Snow
Dead
Top of roof elevation:
Bottom Right
Snow density:
BottomTop
Bottom
Right
Joist
Left
Bottom LeftTop RightTop Left
Water level relative to zero datum:
Joist
Ponded Water
PondingSpecificInput
• Revisedesignbyincreasingthesizeofthejoist
• Determinetherequiredmomentofinertiabytrialanderror
90
JoistNumber 0' 0" 2' 0" 4' 0" 6' 0" 8' 0" 10' 0" 12' 0" 14' 0" 16' 0" 18' 0" 20' 0" 22' 0" 24' 0" 26' 0" 28' 0" 30' 0" 32' 0" 34' 0" 36' 0" 38' 0" 40' 0"
1 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 2442 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 2443 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 2444 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 2445 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 2446 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 2447 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 2448 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 244 2449 122 122 122 122 122 122 122 122 122 122 122 122 122 122 122 122 122 122 122 122 122
NOTES: 1. Loads correspond to ASD load combinations.
Total Distributed Load on Joist as a Function of Distance from Bottom Support (lb/ft)
Output
91
Convergeswithoutwater
Uniformtotalloadindicatesnoimpounded
waterpresentTHEROOFISFREEDRAININGSelectajoistwithIe≥485in4
Iteration ΣW# (kips)1 0.0002 0.0003456789
SummaryandConclusions
• Provisionsrelatedtopondingexistinseveralcodes
• ThecommonlyusedAISCAppendix2methodforevaluatingpondinghasseverallimitations,especiallyforopen-websteeljoistroofs
• Anewmethod,directanalysisforponding,hasbeendevelopedandimplementedwithintheSJIRoofBayAnalysisTool
• TherecentlyupdatedSJITechnicalDigest3providesadditionalbackgroundinformationanddetails.
92
PollingQuestion
WhichofthefollowingstatementsisNOTtrueforpondingevaluationusingtheSJIRoofBayAnalysisTool?
A. JoistsandJoistGirderscanbesloped.B. JoistsandJoistGirderscanbecambered.
C. Spacingbetweenjoistsdoesnothavetobeequal.
D. LoadsonjoistsandJoistGirderscanbecalculatedonundeformedroofs.
E. ASDandLRFDsolutionsarepossible.
93
PollingQuestionAnswers
WhichofthefollowingisNOToneoftheassumptionsmadeforthepondingprovisionsinAppendix2oftheAISCSpecification?
A.Theroofisassumedtobeflat
WhichofthefollowingstatementsisNOTtrueforpondingevaluationusingtheSJIRoofBayAnalysisTool?TheroofsatisfiestheIBCminimumsloperequirements.
C.TheSJIRoofBayAnalysisToolcanonlymodeluniformlyspacedjoists.
94