net vision - socomec : control and safety of low voltage …€¦ · · 2015-02-258 net vision...
TRANSCRIPT
Net VisionV e r s i o n 6 . 2 0
安装及操作手册 CN
Installations- und bedienungsanleitung DE
Manual de instalación y uso ES
Manuel d’installation et d’utilisation FR
Installation and operating manual GB
Manuale di installazione e uso IT
Installatie– en bedieningshandleiding NL
Dokumentacja Techniczno-Ruchowa PL
Manual de instalação e funcionamento PT
Manual de instalare şi utilizare RO
Руководство по установке и эксплуатации RU
Navodila za priključitev in uporabo SI
Kurulum ve kullanım kılavuzu TR
3
EN
GL
ISH
Net Vision Version 6.20 - Ref.: IOMNETVIXX01-GB 02
SUMMARY
EN
GL
ISH
1. INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.1. NET VISION PACKAGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.2. NET VISION FUNCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.3. NET VISION RESOURCES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2. SAFETY INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.1. FOR NET VISION CARD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.2. FOR NET VISION BOX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3. GENERAL SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.1. ETHERNET PROTOCOL COMPLIANCY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.2. BROWSER COMPLIANCY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
4. INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
4.1. CARD VERSION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
4.2. BOX VERSION (FOR UPS MODEL WITHOUT COM-SLOTS) . . . . . . . . . . . . . . 9
4.3. NET VISION BOOT SEQUENCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
5. IP ADDRESS CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
5.1. PREPARING NET VISION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
5.2. DEFAULT IP ADDRESS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
5.3. NET VISION ACCESS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
5.4. IP SETTINGS USING NETWORK AND SUPGRADE UTILITY FOR WINDOWS PC . 10
5.5. IP SETTINGS USING NETWORK IF DHCP NOT PRESENT . . . . . . . . . . . . . . 11
5.6. IP SETTINGS USING A TERMINAL AND RS232 CONNECTION . . . . . . . . . . . 13
6. RESET NET VISION WITH FACTORY SETTINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
7. USER INTERFACE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
7.1. INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
7.2. NET VISION MENU GENERAL OVERVIEW . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
7.3. EXTERNAL LINK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
8. UPS MONITORING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
8.1. COMPREHENSIVE VIEW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
8.2. UPS SYNOPTIC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
8.3. RECTIFIER INPUT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
8.4. BATTERY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
8.5. BYPASS INPUT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
8.6. OUTPUT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
8.7. ALERT LIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
8.8. CLIENT LIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
9. UPS MANAGEMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
9.1. UPS CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
9.2. UPS CONTROL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
9.3. BATTERY TEST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
9.4. POWERSHARE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
9.5. ECO MODE SCHEDULE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
9.6. WEEKLY SCHEDULE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
9.7. SPECIAL DAY SCHEDULE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
9.8. SHUTDOWN PARAMETERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
9.9. EMD CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
10. NET VISION CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
10.1. QUICK OVERVIEW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
10.2. DATE & TIME . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
10.3. NET VISION CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
10.4. NET VISION CONTROL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
10.5. EMAIL RECIPIENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
10.6. WOL (WAKE-ON-LAN) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
4 Net Vision Version 6.20 - Ref.: IOMNETVIXX01-GB 02
11. LOG FILES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
11.1. HISTORY LOG . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
11.2. EXTENDED HISTORY LOG . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
11.3. UPS EVENT LOG . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
11.4. NET VISION EVENT LOG . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
12. APPENDIX 1: LIST OF ALERTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
12.1. JBUSP ALERT LIST (NETYS - ITYS - MASTERYS - DELPHYS RANGES) . . . . 31
13. MODULYS GP / ITYS PRO ALERTS LIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
14. APPENDIX 2: LIST OF UPS EVENTS STORED IN THE LOG FILE . . . . . . . . . . . . . . . . . . . 33
15. APPENDIX 3: LIST OF MEASUREMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
16. APPENDIX 4: LIST OF NETVISION EVENTS STORED IN AGENT LOG. . . . . . . . . . . . . . . . 35
17. APPENDIX 5: SNMP OID TABLE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
17.1. NET VISION MIB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
17.2. RFC1628 UPS MIB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
18. TRAP LIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
18.1. SNMP V3 CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
19. APPENDIX 6: RADIUS CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
19.1. AUTHENTIFICATION CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
19.3. LOGIN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
19.2. DOMAIN USER TABLE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
20. NET VISION TECHNICAL SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
20.1. TECHNICAL SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
20.2. PIN ASSIGNMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
SUMMARY
5Net Vision Version 6.20 - Ref.: IOMNETVIXX01-GB 02
EN
GL
ISH
Net Vision is a network adapter for the professional monitoring and remote control of a single UPS or parallel UPS system.
The Net Vision network adaptor allows a UPS to connected directly the Ethernet network allowing secure management of the UPS
over the network using a web browser, a TELNET interface or NMS application via SNMP. The protocols used for connection are
independent of the platform and operating system, therefore Net Vision is extremely flexible and suitable for all systems.
In addition to monitoring and control, the Net Vision interface is able to provide a high level of protection for servers powered by the UPS.
In critical conditions, up to 250 devices powered by the UPS can be switched off in an orderly sequence whilst ensuring data integrity.
The remote shutdown is provided by a client shutdown to be installed on all computers that require this automatic function. Some clients
for Net Vision are native to certain operating systems, otherwise a universal shutdown client (JNC) can be used.
Net Vision is compatible with the following Socomec UPS products:
• ITYS (all ranges)
• Netys PR and RT
• MASTERYS MC, BC, IP, IP +, EM and Green Power
• DELPHYS BC, MP, MX, EM and Green Power
• MODULYS GP 2.0
1.1. NET VISION PACKAGE
Card / BOX
• Cable
- RJ45 to DB9 Female serial cable for console operation (HyperTerminal session for example)
- RJ45 to DB9 Male UPS serial cable (BOX version only)
- Power supply (BOX version only)
• CD
- User manual
- MIB file
- Supgrade utility
- Last SOCOMEC Net Vision FW version
- Quickstart
- Link to SOCOMEC website download page.
1.2. NET VISION FUNCTIONS
• UPS monitoring via HTML pages and synoptic
• UPS control
• UPS event notification via email
• SNMP TRAP notification to NMS system (NET VISION and RFC1628 TRAP from version 6.1 and above)
• Server Shutdown (using JNC and VIRTUAL-JNC software agent on servers)
• Events and measurements log files
• Multi-language capabilities
1.3. NET VISION RESOURCES
NETWORK – Ethernet connection
• Internal card version with 10/100 auto-sense fast Ethernet.
COM - RS232 serial link
• For Terminal session to configure the Net Vision without Network connection
• Or to connect EMD external sensor with a standard Ethernet CAT5 cable.
DIP SWITCH
• Special functioning mode
• Reset Net Vision with factory settings (see special procedure to be followed)
• RESET button
1. INTRODUCTION
6 Net Vision Version 6.20 - Ref.: IOMNETVIXX01-GB 02
2. SAFETY INFORMATION
2.1. FOR NET VISION CARD
• All servicing of this equipment must be performed by qualified service personnel. Remove rings, watches and other jewellery
before servicing the unit.
• Before plugging in/pulling out the Net Vision card to/from the UPS, please make sure that the power supplying the UPS has been
switched off. Hot swap of the Net Vision in UPS is inhibited.
2.2. FOR NET VISION BOX
• To reduce the risk of fire or electric shock, install the unit in a temperature-controlled indoor area free of conductive objects. Do
not place the unit near liquids or in an excessively humid environment.
• Do not allow liquids or foreign objects to enter the unit
• The unit does not contain any user-serviceable parts. Do not open the unit.
• All servicing of this equipment must be performed by qualified service personnel. Remove rings, watches and other jewellery
before servicing the unit.
• Before maintenance, repair or shipment, the unit must be switched off completely and unplugged and all connections removed.
• Before plugging in the Net Vision power adaptor, please make sure the power source rating matches the Net Vision power adaptor rating.
7
EN
GL
ISH
EN
GL
ISH
Net Vision Version 6.20 - Ref.: IOMNETVIXX01-GB 02
3. GENERAL SPECIFICATIONS
3.1. ETHERNET PROTOCOL COMPLIANCY
• IPv4 / v6
• DHCP
• SNMP v1 / v3
• SSH – SSL 3.0 512b RSA key
• WOL
• HTTP
• SMTP (without SRA key encryption)
• NTP – ICMP
• SNTP - ICMP / DNS
• RADIUS
3.2. BROWSER COMPLIANCY
• Internet Explorer v9 and later
• SAFARI v4 – v5
• CHROME /chromium v16.0.9 (32/64bits)
• FIREFOX V4.0
8 Net Vision Version 6.20 - Ref.: IOMNETVIXX01-GB 02
4. INSTALLATION
4.1. CARD VERSION
4.1-1
4.1-2
NETYS – ITYS UPS
ITYS & NETYS UPS Serial link settings are preconfigured and cannot be changed:
Speed 9600* / bits 8 / parity NONE / Stop bit=1 / flow control NONE, JBUS/MODBUS slave = 1
(*) ITYS 6-10kVA has a speed of 2400. Change the speed on the Net Vision configuration page
MASTERYS MC / BC / GP / IP / IP+ / GREEN POWER 2.0
Insert Net Vision in Slot 1
UPS Serial link settings:
- Serial link settings: 9600, without parity
- Slave number = 1
Selection of serial port > 9600 / 8 / NONE
JBUS/MODBUS slave = 1
RESETCOM
ON
2 1
NETWORK
100 10 StatusPower
NetworkPC
OFF
9Net Vision Version 6.20 - Ref.: IOMNETVIXX01-GB 02
EN
GL
ISH
4. INSTALLATION
DELPHYS MP/MX RANGE
Insert in Slot 5 or Slot 6
UPS Serial link settings
Select the right COM port: Slot 5 = COM1 and Slot 6 = COM2
COM port settings: 9600 / 8 / NONE
JBUS/MODBUS slave = 1
DELPHYS BC / GREEN POWER 2.0 RANGE
Insert Net Vision in upper slot 2
UPS Serial link settings
COM 2 selection on the mimic panel: 9600 / 8 / NONE
JBUS/MODBUS slave = 1
4.2. BOX VERSION (FOR UPS MODEL WITHOUT COM-SLOTS)
4.2-1
Poweradapter
SerialUPS cable
Network
PCOFF
4.3. NET VISION BOOT SEQUENCE
During NET VISION's starting phase, the green light will flash till communication is established.
NET VISION automatically detects the protocol and UPS type. Once the communication is established, the status light is continuous;
the MODBUS polling with UPS is running.
NET VISION manages 2 types of UPS mapping. APPENDIX 1 gives the lists of alert managed for both mappings.
'JBUSP' mapping for NETYS - ITYS - MASTERYS - DELPHYS: acronym with 2 numbers (A00 - A64)
'VU-MAP' mapping for MODULYS GP Green Power 2.0 range : acronym with 3 numbers (A000 - A127)
10 Net Vision Version 6.20 - Ref.: IOMNETVIXX01-GB 02
5.3-1
5.4-1
5. IP ADDRESS CONFIGURATION
5.1. PREPARING NET VISION
Once the UPS power is on and Net Vision has been installed in the slot and connected to the Network, the Net Vision's IP address
must be programmed.
5.2. DEFAULT IP ADDRESS
If a DHCP server is available on the same Network as Net Vision, the Net Vision will request a valid IP address from the server.If the
DHCP server is not available, Net Vision switches to this default IP address: 192.168.7.18
IPv6 is not activated by default. The default IP address is set to IPv4 format
5.3. NET VISION ACCESS
When the Net Vision has a valid IP address, open the web brow-
ser and enter the IP address set manually or given by the DHCP
server. IP address can be checked with Supgrade software
utility.
By default Net Vision requests the login and password to open
web pages.
This login and password remain the same for all connections
by default.
TELNET and Terminal session only request the password to
access the settings pages.
5.4. IP SETTINGS USING NETWORK AND SUPGRADE UTILITY FOR
WINDOWS PC
1. Connect Net Vision to the NETWORK
2. Make sure Net Vision is powered by the UPS
3. Copy the Supgrade.exe utility from the CD to your PC (no installation required)
4. Run Supgrade.exe:
5. Click on
6. The Net Vision appears in the UPS list with its IP address.
Password: publicLogin: admin
11Net Vision Version 6.20 - Ref.: IOMNETVIXX01-GB 02
EN
GL
ISH
5. IP ADDRESS CONFIGURATION
If the default address 192.168.7.18 is displayed, and DHCP is enabled, this means that Net Vision did not receive a valid address.
Click again on to refresh the list of devices.
If the default address remains after 2 or 3 minutes, you will need to set the IP address via Terminal or TELNET. If more than one
Net Vision is present in the list, they must be distinguishable with their own MAC address.
Supgrade cannot change the IP address.
7. Net Vision access: Click on to open the web page with your default internet browser. By default Net Vision requests
the login and password.
WARNING!
If using other operating systems check the IP address via Terminal session.
WARNING!
If the DCHP setting has been changed from ‘disable’ (fixed IP address) to ‘enable’, RESTART Net Vision. Alternatively, start communication with the DHCP server via the Net Vision control menu or the RESET button.
5.5. IP SETTINGS USING NETWORK IF DHCP NOT PRESENT
1. You need a computer with Terminal application connected to the same Network as Net Vision.
2. Check the IP address of your terminal
3. Run a terminal session (a DOS session for example)
4. Execute the following command:
ROUTE ADD 192.168.7.18 computer.IP.address
5.5-1
5.5-2
5. Test the connection to Net Vision
Ping 192.168.7.18
6. If the Net Vision responds to ping open a web session or TelNet session to modify IP parameters.
7. Run Telnet with default address
12 Net Vision Version 6.20 - Ref.: IOMNETVIXX01-GB 02
5. IP ADDRESS CONFIGURATION
5.5-3
5.5-4
Password: public.
Access to Net Vision IP Address configuration: Select 1 to enter the new IP address.
WARNING!
After modifying the IP address you will need to open a new session again with the new IP address given to Net Vision to
continue updating the settings.
If Telnet is not allowed due to security restrictions, it is also possible to use specific tools via SSHv1 or SSHv2. In this case Telnet should be disabled.
13
EN
GL
ISH
EN
GL
ISH
Net Vision Version 6.20 - Ref.: IOMNETVIXX01-GB 02
5. IP ADDRESS CONFIGURATION
5.6. IP SETTINGS USING A TERMINAL AND RS232 CONNECTION
1. Connect the RS232/RJ45 PC cable from Net Vision to your computer
2. Open a Terminal session with the parameters assigned to the right COM port:
- 9600 bauds
- Parity none
- 8 bits data
- No control
3. Press ‘space’ to open the communication.
4. Enter the password: public (by default)
5.6-1
5.6-2
The Terminal menus are the same as in the Telnet session. (See chapter above)
When the IP is set, open your web browser and enter the login and password to access the web pages.
14 Net Vision Version 6.20 - Ref.: IOMNETVIXX01-GB 02
6. RESET NET VISION WITH FACTORY SETTINGS
The following procedure describes the steps to RESET all Net Vision settings and password to factory values.
NB: this procedure does not affect the data stored in the log files.
Step 1: Remove Network and COM cables
Step 2: Remove the 2 screws
Step 3: Remove Net Vision from the slot
Step 4: Change the position of both DIP switches to ON (A)
Step 5: Put Net Vision back in the slot
Step 6: Initialisation process starts, Status and Power LEDs flash. When initialisation process is completed (after 40 seconds)
Status and Power LEDs switch to ON (B).
Step 7: Remove Net Vision from the Slot
Step 8: Change the position of both DIP switches from ON to OFF (A)
Step 9: Put Net Vision back in the slot. Net Vision will restart with factory settings.
Step 10: Fix Net Vision with both screws.
Step 11: Connect the Network and COM (if present) cables.
Step 12: Check that the DHCP server has kept the same IP address, or modify the IP address manually following the procedure
in the previous chapter.
If some Net Vision functions have been used before this procedure (eMail, SNMP, Shutdown, …), those functions will need to reconfigured.
The RESET button does not affect the Net Vision settings, it only restarts Net Vision. Make sure that the IP given by DHCP server remains the same as before the Net Vision RESET.
6-1
AB
RESETCOM
ON
2 1
NETWORK
100 10 StatusPower
15
EN
GL
ISH
EN
GL
ISH
Net Vision Version 6.20 - Ref.: IOMNETVIXX01-GB 02
7. USER INTERFACE
7.1. INTRODUCTION
7.1-1
7.2. NET VISION MENU GENERAL OVERVIEW
UPS Monitoring
Gives access to all UPS parameters available in Net Vision.
Each page describes a specific part of the UPS.
A dedicated page gives the list of current active alerts.
Client Table page lists all servers connected to Net Vision for Shutdown procedure.
UPS management
This menu contains specific sub-menus to control the behaviour of specific UPS functions. Not all menus are available for all UPS
models (consult the UPS user manual for the available functions).
UPS FUNCTIONS Condition Super-user account necessary
UPS Controls The remote controls have to be enabled by the UPS.
The controls enabled by the UPS are present in the list.
YES
To send commands to the UPS
Battery Test The Battery Test function is enabled by the UPS. YES to send the Battery Test
control to the UPS
Power Share The Power Share has to be managed by the UPS. YES
Weekly Schedule The UPS Standby Schedule is managed by the UPS. YES
Special day Schedule The UPS Standby Schedule is managed by the UPS. YES
Eco mode Schedule The eco mode management has to be managed by the UPS. YES
Shutdown Parameters Always present.
Weekly and Special Day Server shutdown schedules are present
if the UPS standby mode is managed by the UPS.
EMD events present only if the device is activated.
YES to modify the config
EMD Configuration Always present YES to activate the EMD if connec-
ted to Net Vision
SOCOMEC website link
Net Vision menu
UPS reference
Page title
Net Vision reference UPS model Synoptic access
Language access
HELP page
16 Net Vision Version 6.20 - Ref.: IOMNETVIXX01-GB 02
7. USER INTERFACE
Net Vision management
• Protocol configuration
• Net Visions control
History Log
• Measurements log file
• UPS and Agent events log.
7.3. EXTERNAL LINK
An extra menu is present if devices have been activated. These links give direct access to other devices. It automatically opens a
new page in the web browser with the selected link.
17
EN
GL
ISH
EN
GL
ISH
Net Vision Version 6.20 - Ref.: IOMNETVIXX01-GB 02
8.1-1
8. UPS MONITOR
8.1. COMPREHENSIVE VIEW
UPS STATUS DETAILS
Unknown If no communication with UPS Check the communication settings in the UPS or modify
communication settings in Net Vision configuration page
Imminent Stop Inverter in Imminent Stop for over-
load, over temperature or battery
low detection.
Depends on UPS model
On Maintenance UPS in maintenance mode Depends on UPS model
On maintenance
bypass
Load supplied by maintenance
bypass (internal or external)Only if the maintenance bypass breaker is present in the UPS
Battery discharging UPS on battery Occurs if the Input supply is absent, or during the Battery Test.
Battery Test running Displayed during the test
UPS on Standby UPS on, load not supplied Depends on UPS model
Load on bypass Load on mains The load is not protected by UPS
Eco mode Eco mode activated If eco mode enabled
Normal mode Load on mains Only for Off line UPS
On Inverter Load protected by Inverter Normal mode for ON LINE UPS
UPS Off Load not supplied
EMD input 2 (free text)
Only if 3-phase UPS
Only if 3-phase input UPS
Only if managed by UPS
Only if the EMD is connected and activated
EMD input 1 (free text)
NOTE! Output kVA is added to this table if this measurement is available on UPS.
18 Net Vision Version 6.20 - Ref.: IOMNETVIXX01-GB 02
HELP MENU
Click on the icon to open the HELP page.
8.1-2
8.2-1
From HELP page click on the icon to go back to the web page.
This function is available for all Net Vision pages.
8.2. UPS SYNOPTIC
Click on the icon to open the synoptic page.
From synoptic page click on the icon 10 to go back to the comprehensive view.
8. UPS MONITOR
19Net Vision Version 6.20 - Ref.: IOMNETVIXX01-GB 02
EN
GL
ISH
SINGLE UNIT
8.2-2
8.2-3
8.2-4
FLOW DISPLAY
GREY: means not powered
BLUE: means under power.
BATTERY DISPLAY
Green lines: indicate the battery level:
4th line: > 95 %
3rd line: > 90 %
2nd line: > 85 %
1st line: <=85 %
Yellow lines: indicate the battery discharging.
Yellow Battery means battery alert flagged, or battery low / discharged.
LOAD DSIPLAY
The lines inside the tank represent the level of UPS load rate.
Above 100% the lines are yellow. 1 line = 10 % from 30% to 120 %
Above 120% the lines are red.
SUBSET DISPLAY
Green sinusoid symbol (Inverter/Bypass) or DC (Rectifier) symbol means the subset is ON
Yellow sinusoid symbol (Inverter/Bypass) or DC (Rectifier) symbol means the subset is ON and an alert has been flagged.
STATUS BAR DISPLAY
The colour of the bar indicates the status of the UPS.
GREEN: Normal mode / eco mode. Load protected by UPS
YELLOW: On bypass / maintenance bypass / preventive maintenance requested
RED: Load OFF / Imminent Stop
GREY: UPS on standby. Load not supplied.
8. UPS MONITOR
20 Net Vision Version 6.20 - Ref.: IOMNETVIXX01-GB 02
8.2-6
8.2-7
8.2-5
ADDITIONAL ICONS
Bypass impossible Alert present
PARALLEL SYSTEM
Click on the UNIT button (1 to 6) to switch to UNIT VIEW
Click on the SYS button to go back to SYSTEM VIEW.
The colour of the button indicates the status of the unit:
GREEN: Unit working (On inverter / On bypass)
YELLOW: Unit alert flagged (General unit alert flagged)
RED: Unit OFF (Unit output off)
GREY: Unit on Standby
8. UPS MONITOR
21Net Vision Version 6.20 - Ref.: IOMNETVIXX01-GB 02
EN
GL
ISH
UPS WITHOUT BYPASS – CONVERTER MODE
The Bypass path is not displayed in this configuration.
The Bypass monitor page is empty, no data is available.
Measurements not managed are not displayed. The line of values is removed.
MODULAR UNIT
In the case of modular unit UPS architecture, it is possible to see the module's comprehensive view.
Click on the 'module page' button to open the module tables window. These tables are the same as the unit's comprehensive view.
The page only displays the modules or subunits present in the unit.
8.3. RECTIFIER INPUT
See help page for more info
The min and max values are stored in the UPS Extend Log
8.4. BATTERY
Battery Status:
- Unknown (no communication with UPS)
- Battery discharged
- Battery disconnected
- Battery low
- Battery not OK
- Battery discharging
- Battery OK
See help page for more info
8.5. BYPASS INPUT
See help page for more info
In the case of a UPS without Bypass or converter mode, the page is empty.
8.6. OUTPUT
Output Status:
- Unknown (no communication with UPS)
- On maintenance Bypass
- On standby
- On Bypass
- Eco mode
- Normal mode (Only for OFF LINE UPS)
- On Inverter
- UPS OFF
See help page for more info
8.7. ALARM TABLE
See help page for more info
See Appendix for alert list managed by Net Vision
8.8. CLIENT TABLE
See help page for more info
The severity column is not managed.
8. UPS MONITOR
22 Net Vision Version 6.20 - Ref.: IOMNETVIXX01-GB 02
9. UPS MANAGEMENT
9.1. UPS CONFIGURATION
See help page for more info
9.2. UPS CONTROL
Menu present if remote controls are set on UPS and Super-user account session open.
Example: Only controls enabled by UPS are present on the page.
9.2-1
9.2-2
Select one control option and confirm.
If Power Share plugs are managed by UPS, the output plug controls are displayed on the same page.
List of possible control options (depending on UPS capabilities)
• Standby ON
• Standby OFF
• Eco Mode
• Normal Mode
• On Bypass
• On Inverter
• Alarm Reset
• Buzzer OFF
WARNING!Some controls are not available with some UPS units.
After sending a command to the UPS, the page is not refreshed with new data. It is advisable to refresh the page
manually with the latest list of commands available.
9.3. BATTERY TEST
Present only if the Battery Test is enabled by UPS.
The Administrator account is needed to send the Battery Test command.
The Battery Status is notified and the last Battery Test result displayed:
• Processing
• Failed
• Waiting (Battery Test schedule enabled by the UPS)
• Not active (test never performed or Battery Test disabled by the UPS)
• OK
See help page for more details.
23Net Vision Version 6.20 - Ref.: IOMNETVIXX01-GB 02
EN
GL
ISH
9.4. POWERSHARE
Present only if Power Share is managed by UPS.
Net Vision allows you to control the Power Share plugs according to the UPS events or measurements.
9. UPS MANAGEMENT
9.4-1
MODE SETTINGS
Battery Capacity: switches the output plug to OFF when the value is reached.
Remaining Backup time: switches the output plug to OFF when the value is reached.
Time on Battery: switches the output plug to OFF when the value is reached.
Emergency lighting: switches the output plug to ON when the UPS is on battery.
See help page for more details.
9.5. ECO MODE SCHEDULE
Present only if eco mode is enabled by UPS. See help page for more details.
9.6. WEEKLY SCHEDULE
Present only if the standby schedule is enabled. See help page for more details.
9.7. SPECIAL DAY SCHEDULE
Present only if the standby schedule is enabled. See help page for more details.
9.8. SHUTDOWN PARAMETERS
Net Vision allows you to send notification and shutdown commands to servers. The shutdown agent has to be installed on each
server. The Net Vision IP address should be set in the agent configuration. If the server is recognised by NET VISON, it will be present
in the Client Table page of the UPS monitor menu.
UPS SHUT OFF
This function is available if the Standby Schedule is managed by the UPS. Otherwise this function is not displayed.
The UPS shut-off command is sent to the UPS when the Net Vision sends the shutdown command to the server. This command is
sent with the time period set for this function. The UPS will turns off the output at the end of the time period.
The restart delay defines the time period after which the UPS should restart automatically after mains power resumes. A restart time
set to 0 means that the UPS will not restart.
WARNING!Make sure that the UPS shut-off time period is longer than the total time period for the shutdown procedure for the
servers and workstations supplied by the UPS. See shutdown process paragraph for more details
24 Net Vision Version 6.20 - Ref.: IOMNETVIXX01-GB 02
9. UPS MANAGEMENT
9.8-1
SHUTDOWN EVENT SELECTION
• AC Failed (UPS on battery)
• Battery Low
• UPS Overload
• UPS over Temperature
• On By-pass
• Imminent Stop
• Level of battery capacity (the value of the level has to be set in the Net Vision configuration page)
Additional events if EMD device present:
• EMD Temperature
• EMD Humidity
• EMD IN1 Abnormal
• EMD IN2 Abnormal
SHUTDOWN TEST PROCEDURE
Net Vision allows you to simulate an AC fail event. After a 2nd validation the Shutdown procedure starts, with the settings of ‘AC fail’ event.
Net Vision sends the notification and the shutdown command to the server.
At the end of the procedure, after sending the shutdown command, Net Vision waits around 2 minutes before sending a shutdown cancel
command. This command permits the agent to recover normal UPS status. The agent is then ready for the shutdown procedure again.
During the test the button is disabled and switches to 'enabled' when the ‘shutdown cancel’ command is sent to servers.
WARNING!
If the time period = 0, the server shutdown command is sent immediately.
Example of the sequence stored in the Agent log file. 1 minute time period and warning every 10 seconds.
25Net Vision Version 6.20 - Ref.: IOMNETVIXX01-GB 02
EN
GL
ISH
9. UPS MANAGEMENT
SHUTDOWN PROCESS
Principle: When a shutdown event occurs, Net Vision sends a first notification to all servers at the end of the 1st warning period. A
time period set to 0 means immediately.
While the event is present Net Vision sends notification regularly, defined by ‘Warning interval’. At the end of the ‘event delay’ period
Net Vision sends the shutdown command to the servers.
9.8-2
9.9-1
9.9. EMD CONFIGURATION
If an EMD device (environment and temperature sensor) is connected to Net Vision, you will need to activate it.
The EMD should be connected to Net Vision COM port. EMD values are not transferred to the UPS.
CUSTOMISATION
Temperature and humidity measurements and two inputs can be assigned as required.
THRESHOLDS
The MIN and MAX thresholds define the tolerances. If the value is out of tolerance, Net Vision will send an email, SNMP TRAP or
server shutdown command, depending on the Net Vision settings. The offset can compensate the value with a reference value.
ALERT MODE
Defines whether or not the EMD inputs are flagged as an alert in ‘Normally Open’ or ‘Normally Closed’ position.
For more details refer to HELP page.
26 Net Vision Version 6.20 - Ref.: IOMNETVIXX01-GB 02
10. NET VISION CONFIGURATION
10.1. QUICK OVERVIEW
Net Vision confi guration Functions Settings
Date & Time Manages the Net Vision real time clock. Net Vision is also able to synchronise the UPS clock.
- Manual
- NTP server
- Synchronise with computer
- Synchronise UPS
Net Vision Confi g Includes all NETWORK configuration needed for Net Vision.
- IP v4 or v6
- SMTP server
- SMTP port (25 by default) from 6.1 version only
- email account authentication
- Super-user account
- Log file samples
- UPS serial link
- System identification
Net Vision Control Enable or disable protocols.
Log file managements
- DHCP
- Telnet
- FTP (upgrade)
- SNMP
- SSH
- HTTP
- Log file reset
- Log file download
- MIB access
eMail Receivers withSuper-user account only
Defines the events, and outlines the addresses of eMail recipients.
- Event Selection
- Free text field
- eMail address table
- send Test
SNMPv3 USM Table Defines the user name and password for SNMP encryption
Only present if SNMP v3 enabled
SNMP TRAP Receivers List of NMS, up to 8 maximum - IP address
- TRAP TYPE : NET VISION TRAP or RFC1628 TRAP (from version 6.1 and above)
SNMP/HTTP Control Defines the access with specific computer, read or read/write
Also includes the User domain for specific use.
- IP address
- Community
- Access
Home page Refresh Makes it possible to change the refresh period for UPS monitoring web pages
WakeOnLan Targets Describes the list of servers to wake when the UPS output is powered.
- Server MAC address (32 max)
- Delay
- Retry number
RADIUS Confi guration This function allows user access management via RADIUS server.
See APPENDIX.
- RADIUS Server
- Privacy policy
- Packet management
External Link Allows the addition of hyperlinks to other devices in the NET VISON page.
- Hyperlink (up to 4)
- Description
- Enabled/disabled
The following chapters give additional info about Net Vision configurations.
For more details see the HELP pages.
27Net Vision Version 6.20 - Ref.: IOMNETVIXX01-GB 02
EN
GL
ISH
10.2. DATE & TIME
UPS DATE AND TIME
Net Vision allows the synchronisation of the UPS date and time. When Net Vision detects a new date and time (set manually or via
NTP server), it sends the new values to the UPS if this function is enabled.
This function is enabled if the date and time are managed by the UPS. Otherwise this part is not displayed.
[Update Now] sends the current date and time to the UPS manually.
DATE AND TIME SETTINGS
Synchronise with computer where the web browser is open
Synchronise with NTP server
Set values manually.
Net Vision also manages the time zone; GMT + [x] hours.
For more details refer to HELP page.
10.3. NET VISION CONFIGURATION
SYSTEM IDENTIFICATION
3 free fields (Contact - Name - Location) to identify Net Vision. This info is not reported to the UPS or other functions.
EMAIL MANAGEMENT
Net Vision allows you to send eMails on specific events. ‘First send delay’ (in minutes) means that Net Vision waits until the end of
the delay to send the eMail if the event is still present. 0 = email sent immediately
‘eMail send interval’ (in minutes) defines Net Vision email resending after a period, if the event is still present. 0 = no repetition.
WARNING!
NET VISION is not able to manage email accounts with the 1024/2048 SRA encrypton key.
HISTORY LOG
Defines the sample period that Net Vision stores the measurements.
‘History Log Interval’ stores the measurements with a period defined in seconds
‘Extended History Log Interval’ stores measurements and statistics with a period defined in minutes.
UPS SERIAL LINK
Net Vision communicates via RS232 serial link with the UPS.
The UPS serial port settings should be the same as Net Vision.
WARNING!
If communication problems occur, it will be necessary to adapt the ‘Net Vision Polling Rate’ and ‘JBUS Timeout’.
10.4. NET VISION CONTROL
SNMP TRAP FILTER
It activates or deactivates the following TRAP (Enabled = RFC1628 compliant):
upsTrapOnBattery: send every minute with remaining backup time and time on battery
upsTrapAlarmEntryAdded: send with the WellKnownAlarms OID for the recognised alert
upsTrapAlarmEntryRemoved: send with the WellKnownAlarms OID for the recognised alert
10. NET VISION CONFIGURATION
28 Net Vision Version 6.20 - Ref.: IOMNETVIXX01-GB 02
10.5. EMAIL RECEIVERS
EVENT MANAGEMENT
10.5-1
Event 1: General Alert.
Events 5 to 8 are linked to the EMD device managed if the device is connected to Net Vision.
Events 7 and 8 Display the configured sensor name.
Event 11: Load on Bypass.
Event 13: Alert cancelled.
Events 2,3,4,9,10,12: UPS alerts.
SEND TEST
Tests e-mail configuration.
WARNING!
Before sending a test you will need to configure the SMTP server and account.
10. NET VISION CONFIGURATION
29Net Vision Version 6.20 - Ref.: IOMNETVIXX01-GB 02
EN
GL
ISH
MAIL FORMAT
10.5-2
10.6-1
10.6. WOL (WAKE-ON-LAN)
A pop-up window is opened to set the MAC address and the delay before sending the packet to server.
The WOL packets are sent to servers when Net Vision detects that UPS output is powered by the inverter or bypass again, and the UPS has no active alerts.
10. NET VISION CONFIGURATION
Net Vision account: UPS reference.
Event List: lists of active alerts.
Timestamp: time when Net Vision detects the event
and hyperlink for NET VISION's IP address.
30 Net Vision Version 6.20 - Ref.: IOMNETVIXX01-GB 02
11. HISTORY LOG
11.1. HISTORY LOG
Net Vision stores the following measurements:
• Input Voltage per phase
• Output Voltage per phase
• Global output load rate
• Battery capacity
• EMD temperature (if EMD device present)
• EMD humidity (if EMD device present)
The sample period (in seconds) is defined on the Net Vision configuration page.
Net Vision manages the log file by period. One page gives the measurement sample for the period.
11.2. UPS EXTENDED LOG
Net Vision stores the History log measurements plus statistics such as Min, Average and Max for each measurement.
The sample period (in minutes) is defined on the Net Vision configuration page.
Net Vision manages the log file by period. One page gives the measurement sample for the period.
11.3. UPS EVENT LOG
Net Vision stores the UPS events.
See Appendix.
11.4. AGENT EVENTS LOG
Net Vision stores the agent event and sending of UPS commands.
See Appendix.
31Net Vision Version 6.20 - Ref.: IOMNETVIXX01-GB 02
EN
GL
ISH
12. APPENDIX 1: LIST OF ALERTS
JBUSP code Mimic panel message
A01 Battery Alarm
S05 Load on Battery
S15 Low Battery
S16 Battery discharged/Battery end
A07 Inside over-temperature alarm
A05 Input voltage out of tolerance
A03 Output voltage out of tolerance
A02 UPS overload
S04 Load on Mains/Load on By-Pass
A29 By-Pass general alarm
Output Off as Requested
UPS Off as Requested
A26 Battery charger general alarm
S08 UPS in standby mode
UPS Off
A00 General Alarm
S14 Battery Test failed (interrupted)
Communication Lost
Awaiting Power
Shutdown Pending
Shutdown Imminent
S10 Battery Test in progress
A04 Digital Power Supply Fault
A06 Auxiliary mains out of tolerance
A08 Manual bypass closed
A09 Short-circuit detection on UPS output
A10 Battery charger fault
A11 Inverter over-current
A12 Excessive Inverter distortion
A13 Precharge voltage out of tolerance
A14 Boost output voltage too low
A15 Boost output voltage too high
A16 Battery voltage too high
A17 Improper condition of use
A18 Blocking Inverter for overload
A19 Microprocessor control system failure
A20 Wrong configuration
A21 Pll Fault
A22 Input mains general alarm
A23 Rectifier general alarm
JBUSP code Mimic panel message
A24 Boost general alarm
A25 Inverter general alarm
A26 Battery charger general alarm
A27 Output voltage over limits
A28 Output voltage under limits
A29 By-Pass general alarm
A30 UPS stopped for overload
A31 Imminent Stop
A32 Unit 1 general alarm
A33 Unit 2 general alarm
A34 Unit 3 general alarm
A35 Unit 4 general alarm
A36 Unit 5 general alarm
A37 Unit 6 general alarm
A38 External Alarm 1
A39 External Alarm 2
A40 External Alarm 3
A41 External Alarm 4
A42 Remote service alarm
A43 Redundancy lost
A44 Periodic service check up
A45 Automatic and manual transfer disabled
A46 Automatic transfer disabled
A47 Battery room alarm
A48 Manual bypass alarm
A49 Battery Discharged
A50 Insufficient resources
A51 Optional boards general alarm
A52 Rectifier fault
A53 Boost fault
A54 Inverter fault
A55 Parallel module fault
A56 Gen-set general alarm
A57 Gen-set fault
A58 Emergency stop active
A59 Battery circuit open
A60 Fans failure
A61 Phase rotation fault
A62 Bypass fault
S04 Load on Bypass
S08 UPS in standby
S14 Battery Test fault
S15 Battery low
S16 Battery discharged
Additional Status on the alert monitoring page:
NOTE! Alerts and status without acronym are managed by NET VISION itself
12.1. JBUSP ALERT LIST (NETYS - ITYS - MASTERYS - DELPHYS RANGES)
32 Net Vision Version 6.20 - Ref.: IOMNETVIXX01-GB 02
13. MODULYS GP / ITYS PRO ALERTS LIST
Code Mimic panel message
A027 Battery Alarm
A019 Load on Battery
A018 Low Battery
A017 Battery discharged/Battery end
A002 Inside over-temperature alarm
A035 Input voltage out of tolerance
A001 UPS overload
S002 Load on Mains/Load on By-Pass
A049 By-Pass general alarm
Output Off as Requested
UPS Off as Requested
A037 Battery charger general alarm
S013 UPS in standby mode
S004 UPS Off
A015 General Alarm
A034 Battery test failed (interrupted)
Communication Lost
Awaiting Power
Shutdown Pending
Shutdown Imminent
S034 Battery test in progress
A050 Auxiliary mains out of tolerance
S003 Manual bypass closed
A007 Short-circuit detection on UPS output
A036 Battery charger fault
A061 Microprocessor control system failure
A060 Wrong configuration
A035 Input mains general alarm
A033 Rectifier general alarm
A020 Battery temperature
A102 Unit 7 General Alarm
A034 Rectifier redundancy alarm
A041 Inverter general alarm
A037 Battery charger general alarm
Code Mimic panel message
A049 By-Pass general alarm
A000 Imminent Stop
A096 Unit 1 general alarm
A097 Unit 2 general alarm
A098 Unit 3 general alarm
A099 Unit 4 general alarm
A100 Unit 5 general alarm
A101 Unit 6 general alarm
A064 External Alarm 1
A065 External Alarm 2
A066 External Alarm 3
A067 External Alarm 4
A013 Remote service alarm
A006 Redundancy lost
A012 Periodic service check up
A003 Automatic and manual transfer disabled
A004 Automatic transfer disabled
A021 Battery room alarm
A056 Manual bypass alarm
A017 Battery Discharged
A005 Insufficient resources
A062 Optional boards general alarm
A032 Rectifier fault
A040 Inverter fault
A036 Gen-set general alarm
A059 Emergency stop active
A016 Battery circuit open
A051 Phase rotation fault
A048 Bypass fault
A022 Battery test failed
A103 Unit 8 General alarm
A042 Inverter redundancy alarm
33
EN
GL
ISH
EN
GL
ISH
Net Vision Version 6.20 - Ref.: IOMNETVIXX01-GB 02
14. APPENDIX 2: LIST OF UPS EVENTS STORED IN THE
LOG FILE
Mains Failure
Mains Restored
Inverter ON
Inverter OFF
Rectifier ON
Rectifier OFF
Load On Inverter
Load On Mains
Load Not Supplied
Battery Discharging
Battery Charging
eco mode ON
eco mode OFF
Standby Mode ON
Standby Mode OFF
Battery Test in progress
Battery Test finish
Low Battery
Battery discharged
Battery failure
Boost ON
Boost OFF
Auxiliary Mains Failure
Auxiliary Mains Restored
External Status 1 ON
External Status 1 OFF
External Status 2 ON
External Status 2 OFF
External Status 3 ON
External Status 3 OFF
External Status 4 ON
External Status 4 OFF
PLL fault
Recitifier Alarm
Boost Alarm
Inverter Alarm
Battery Charger Alarm
By-Pass Alarm
External Alarm 1 ON
External Alarm 1 OFF
External Alarm 2 ON
External Alarm 2 OFF
External Alarm 3 ON
External Alarm 3 OFF
External Alarm 4 ON
External Alarm 4 OFF
Unknown
JBUS Error: Bad function code
JBUS Error: Bad Address
JBUS Error: Bad CRC
JBUS Error: Function not supported
JBUS Error: Unknow
Power Plugs 1 ON
Power Plugs 2 ON
Power Plugs 3 ON
Power Plugs 4 ON
Power Plugs 1 OFF
Power Plugs 2 OFF
Power Plugs 3 OFF
Power Plugs 4 OFF
EMD Sensor detected high temperature
EMD Sensor detected normal temperature
EMD Sensor detected low temperature
EMD Sensor detected high humidity
EMD Sensor detected normal humidity
EMD Sensor detected low humidity
EMD %s input is active
EMD %s input is restored
Gen Set Running
Gen Set Stopped
34 Net Vision Version 6.20 - Ref.: IOMNETVIXX01-GB 02
15. APPENDIX 3: LIST OF MEASUREMENTS
HTML page Measurements Unit
Comprehensive view Output Load Rate %
Output kVA
Output Voltage V *10
Battery Capacity %
Battery Voltage V * 10
Rectifier Input Voltage V * 10
Temperature °C
Rectifier Input Rectifier input Voltage V * 10
Rectifier Input Frequency Hz * 10
Battery Battery Volatge V * 10
Battery Capacity Ah * 10
Battery Capacity %
Remaining backup time mn
Time since on Battery Power s
UPS Output UPS load rate %
Ouput Voltage V * 10
Output Frequency Hz * 10
Output Current A * 10
Bypass Input Bypass Voltage V* 10
Bypass Frequency Hz * 10
NOTE!If measurements are not present in NET VISION pages, it means that the measurments are not managed by the UPS.
35
EN
GL
ISH
EN
GL
ISH
Net Vision Version 6.20 - Ref.: IOMNETVIXX01-GB 02
16. APPENDIX 4: LIST OF NETVISION EVENTS STORED
IN AGENT LOG
Cold boot
Warm boot
Network link up
Network link down
Time Changed
Net Vision Restart
Parameters reset to default
Parameters chcecksum error
Clear history log
Firmware upgrade
History log cleared
Extent history log cleared
UPS event log cleared
Agent event log cleared
History log interval changed
Extent history log interval changed
Send shutdown warning to clients
Send shutdown request to clients
Send UPS shutdown command to UPS
Send shutdown cancel to clients
Send UPS output on command to UPS
UPS communication lost
UPS communication restored
Time changed by user
Time changed by server
Time changed by RTC
Enable Eco/Mode
Disable Eco/Mode
Enable Standby
Disable Standby
Reset ALarms
Reset Commands
Set Buzzer Off
eMail server or DNS fault
eMail retry to send
A email had been sent
eMail send error
eMail address error
SMTP authorization fail
The confi gured NTP server is not responding
Clear Customized Language
Enable By-Pass
Disable By-Pass
Wake On LAN packet sent to clients
36 Net Vision Version 6.20 - Ref.: IOMNETVIXX01-GB 02
17. APPENDIX 5: SNMP OID TABLE
17.1. NET VISION MIB
upsIdentModel [1.3.6.1.4.1.4555.1.1.1.1.1.1.0]
upsIdentUPSFirmwareVersion [1.3.6.1.4.1.4555.1.1.1.1.1.2.0]
upsIdentAgentSoftwareVersion [1.3.6.1.4.1.4555.1.1.1.1.1.3.0]
upsIdentUpsSerialNumber [1.3.6.1.4.1.4555.1.1.1.1.1.4.0]
upsBatteryStatus [1.3.6.1.4.1.4555.1.1.1.1.2.1.0]
upsSecondsOnBattery [1.3.6.1.4.1.4555.1.1.1.1.2.2.0]
upsEstimatedMinutesRemaining [1.3.6.1.4.1.4555.1.1.1.1.2.3.0]
upsEstimatedChargeRemaining [1.3.6.1.4.1.4555.1.1.1.1.2.4.0]
upsBatteryVoltage [1.3.6.1.4.1.4555.1.1.1.1.2.5.0]
upsInputNumLines [1.3.6.1.4.1.4555.1.1.1.1.3.1.0]
upsInputFrequency [1.3.6.1.4.1.4555.1.1.1.1.3.2.0]
upsInputLineIndex [1.3.6.1.4.1.4555.1.1.1.1.3.3.1.1.1]
upsInputLineIndex [1.3.6.1.4.1.4555.1.1.1.1.3.3.1.1.2]
upsInputLineIndex [1.3.6.1.4.1.4555.1.1.1.1.3.3.1.1.3]
upsInputVoltage [1.3.6.1.4.1.4555.1.1.1.1.3.3.1.2.1]
upsInputVoltage [1.3.6.1.4.1.4555.1.1.1.1.3.3.1.2.2]
upsInputVoltage [1.3.6.1.4.1.4555.1.1.1.1.3.3.1.2.3]
upsInputCurrent [1.3.6.1.4.1.4555.1.1.1.1.3.3.1.3.1]
upsInputCurrent [1.3.6.1.4.1.4555.1.1.1.1.3.3.1.3.2]
upsInputCurrent [1.3.6.1.4.1.4555.1.1.1.1.3.3.1.3.3]
upsInputVoltageMax [1.3.6.1.4.1.4555.1.1.1.1.3.3.1.4.1]
upsInputVoltageMax [1.3.6.1.4.1.4555.1.1.1.1.3.3.1.4.2]
upsInputVoltageMax [1.3.6.1.4.1.4555.1.1.1.1.3.3.1.4.3]
upsInputVoltageMin [1.3.6.1.4.1.4555.1.1.1.1.3.3.1.5.1]
upsInputVoltageMin [1.3.6.1.4.1.4555.1.1.1.1.3.3.1.5.2]
upsInputVoltageMin [1.3.6.1.4.1.4555.1.1.1.1.3.3.1.5.3]
upsOutputSource [1.3.6.1.4.1.4555.1.1.1.1.4.1.0]
upsOutputFrequency [1.3.6.1.4.1.4555.1.1.1.1.4.2.0]
upsOutputNumLines [1.3.6.1.4.1.4555.1.1.1.1.4.3.0]
upsOutputLineIndex [1.3.6.1.4.1.4555.1.1.1.1.4.4.1.1.1]
upsOutputLineIndex [1.3.6.1.4.1.4555.1.1.1.1.4.4.1.1.2]
upsOutputLineIndex [1.3.6.1.4.1.4555.1.1.1.1.4.4.1.1.3]
upsOutputVoltage [1.3.6.1.4.1.4555.1.1.1.1.4.4.1.2.1]
upsOutputVoltage [1.3.6.1.4.1.4555.1.1.1.1.4.4.1.2.2]
upsOutputVoltage [1.3.6.1.4.1.4555.1.1.1.1.4.4.1.2.3]
upsOutputCurrent [1.3.6.1.4.1.4555.1.1.1.1.4.4.1.3.1]
upsOutputCurrent [1.3.6.1.4.1.4555.1.1.1.1.4.4.1.3.2]
upsOutputCurrent [1.3.6.1.4.1.4555.1.1.1.1.4.4.1.3.3]
upsOutputPercentLoad [1.3.6.1.4.1.4555.1.1.1.1.4.4.1.4.1]
upsOutputPercentLoad [1.3.6.1.4.1.4555.1.1.1.1.4.4.1.4.2]
upsOutputPercentLoad [1.3.6.1.4.1.4555.1.1.1.1.4.4.1.4.3]
upsBypassFrequency [1.3.6.1.4.1.4555.1.1.1.1.5.1.0]
upsBypassNumLines [1.3.6.1.4.1.4555.1.1.1.1.5.2.0]
upsBypassLineIndex [1.3.6.1.4.1.4555.1.1.1.1.5.3.1.1.1]
upsBypassLineIndex [1.3.6.1.4.1.4555.1.1.1.1.5.3.1.1.2]
upsBypassLineIndex [1.3.6.1.4.1.4555.1.1.1.1.5.3.1.1.3]
upsBypassVoltage [1.3.6.1.4.1.4555.1.1.1.1.5.3.1.2.1]
upsBypassVoltage [1.3.6.1.4.1.4555.1.1.1.1.5.3.1.2.2]
upsBypassVoltage [1.3.6.1.4.1.4555.1.1.1.1.5.3.1.2.3]
upsBypassCurrent [1.3.6.1.4.1.4555.1.1.1.1.5.3.1.3.1]
upsBypassCurrent [1.3.6.1.4.1.4555.1.1.1.1.5.3.1.3.2]
upsBypassCurrent [1.3.6.1.4.1.4555.1.1.1.1.5.3.1.3.3]
upsAlarm [1.3.6.1.4.1.4555.1.1.1.1.6]
upsAlarmPresent [1.3.6.1.4.1.4555.1.1.1.1.6.1]
upsAlarmTable [1.3.6.1.4.1.4555.1.1.1.1.6.2.]
upsAlarmEntry [1.3.6.1.4.1.4555.1.1.1.1.6.2.1]
upsAlarmId [1.3.6.1.4.1.4555.1.1.1.1.6.2.1.1]
upsAlarmDescr [1.3.6.1.4.1.4555.1.1.1.1.6.2.1.2]
upsAlarmTime [1.3.6.1.4.1.4555.1.1.1.1.6.2.1.3]
upsAlarmExtDes [1.3.6.1.4.1.4555.1.1.1.1.6.2.1.4]
upsWellKnownAlarms [1.3.6.1.4.1.4555.1.1.1.1.6.3]
upsAlarmBatteryBad 1.3.6.1.4.1.4555.1.1.1.1.6.3.1
upsAlarmOnBattery 1.3.6.1.4.1.4555.1.1.1.1.6.3.2
upsAlarmLowBattery 1.3.6.1.4.1.4555.1.1.1.1.6.3.3
upsAlarmDepletedBattery 1.3.6.1.4.1.4555.1.1.1.1.6.3.4
upsAlarmTempBad 1.3.6.1.4.1.4555.1.1.1.1.6.3.5
upsAlarmInputBad 1.3.6.1.4.1.4555.1.1.1.1.6.3.6
upsAlarmOutputBad 1.3.6.1.4.1.4555.1.1.1.1.6.3.7
upsAlarmOutputOverload 1.3.6.1.4.1.4555.1.1.1.1.6.3.8
upsAlarmOnBypass 1.3.6.1.4.1.4555.1.1.1.1.6.3.9
upsAlarmBypassBad 1.3.6.1.4.1.4555.1.1.1.1.6.3.10
upsAlarmOutputOffAsRequested 1.3.6.1.4.1.4555.1.1.1.1.6.3.11
upsAlarmUpsOffAsRequested 1.3.6.1.4.1.4555.1.1.1.1.6.3.12
upsAlarmChargerFailed 1.3.6.1.4.1.4555.1.1.1.1.6.3.13
upsAlarmUpsOutputOff 1.3.6.1.4.1.4555.1.1.1.1.6.3.14
upsAlarmUpsSystemOff 1.3.6.1.4.1.4555.1.1.1.1.6.3.15
upsAlarmFanFailure 1.3.6.1.4.1.4555.1.1.1.1.6.3.16
upsAlarmFuseFailure 1.3.6.1.4.1.4555.1.1.1.1.6.3.17
upsAlarmGeneralFault 1.3.6.1.4.1.4555.1.1.1.1.6.3.18
upsAlarmDiagnosticTestFailed 1.3.6.1.4.1.4555.1.1.1.1.6.3.19
upsAlarmCommunicationLost 1.3.6.1.4.1.4555.1.1.1.1.6.3.20
upsAlarmAwaitingPower 1.3.6.1.4.1.4555.1.1.1.1.6.3.21
upsAlarmShutdownPending 1.3.6.1.4.1.4555.1.1.1.1.6.3.22
upsAlarmShutdownImminent 1.3.6.1.4.1.4555.1.1.1.1.6.3.23
upsAlarmTestInProgress 1.3.6.1.4.1.4555.1.1.1.1.6.3.24
upsAlarmPowerSupplyFault 1.3.6.1.4.1.4555.1.1.1.1.6.3.25
upsAlarmAuxMainFail 1.3.6.1.4.1.4555.1.1.1.1.6.3.26
upsAlarmManualBypassClose 1.3.6.1.4.1.4555.1.1.1.1.6.3.27
upsAlarmShortCircuit 1.3.6.1.4.1.4555.1.1.1.1.6.3.28
upsAlarmBatteryChargerFailure 1.3.6.1.4.1.4555.1.1.1.1.6.3.29
upsAlarmInverterOverCurrent 1.3.6.1.4.1.4555.1.1.1.1.6.3.30
upsAlarmInverterDistorsion 1.3.6.1.4.1.4555.1.1.1.1.6.3.31
upsAlarmPrechargeVoltageFail 1.3.6.1.4.1.4555.1.1.1.1.6.3.32
upsAlarmBoostTooLow 1.3.6.1.4.1.4555.1.1.1.1.6.3.33
37Net Vision Version 6.20 - Ref.: IOMNETVIXX01-GB 02
EN
GL
ISH
17. APPENDIX 5: SNMP OID TABLE
upsAlarmBoostTooHigh 1.3.6.1.4.1.4555.1.1.1.1.6.3.34
upsAlarmBatteryTooHigh 1.3.6.1.4.1.4555.1.1.1.1.6.3.35
upsAlarmImproperCondition 1.3.6.1.4.1.4555.1.1.1.1.6.3.36
upsAlarmOverloadTimeout 1.3.6.1.4.1.4555.1.1.1.1.6.3.37
upsAlarmControlSystemFailure 1.3.6.1.4.1.4555.1.1.1.1.6.3.38
upsAlarmDataCorrupted 1.3.6.1.4.1.4555.1.1.1.1.6.3.39
upsAlarmPllFault 1.3.6.1.4.1.4555.1.1.1.1.6.3.40
upsAlarmInputGeneralAlarm 1.3.6.1.4.1.4555.1.1.1.1.6.3.41
upsAlarmRectifierGeneralAlarm 1.3.6.1.4.1.4555.1.1.1.1.6.3.42
upsAlarmBoostGeneralAlarm 1.3.6.1.4.1.4555.1.1.1.1.6.3.43
upsAlarmInverterGeneralAlarm 1.3.6.1.4.1.4555.1.1.1.1.6.3.44
upsAlarmBatteryGeneralAlarm 1.3.6.1.4.1.4555.1.1.1.1.6.3.45
upsAlarmOutputOver 1.3.6.1.4.1.4555.1.1.1.1.6.3.46
upsAlarmOutputUnder 1.3.6.1.4.1.4555.1.1.1.1.6.3.47
upsAlarmBypassGeneralAlarm 1.3.6.1.4.1.4555.1.1.1.1.6.3.48
upsAlarmStopForOverload 1.3.6.1.4.1.4555.1.1.1.1.6.3.49
upsAlarmImminentStop 1.3.6.1.4.1.4555.1.1.1.1.6.3.50
upsAlarmModule1Alarm 1.3.6.1.4.1.4555.1.1.1.1.6.3.51
upsAlarmModule2Alarm 1.3.6.1.4.1.4555.1.1.1.1.6.3.52
upsAlarmModule3Alarm 1.3.6.1.4.1.4555.1.1.1.1.6.3.53
upsAlarmModule4Alarm 1.3.6.1.4.1.4555.1.1.1.1.6.3.54
upsAlarmModule5Alarm 1.3.6.1.4.1.4555.1.1.1.1.6.3.55
upsAlarmModule6Alarm 1.3.6.1.4.1.4555.1.1.1.1.6.3.56
upsAlarmExternalAlarm1 1.3.6.1.4.1.4555.1.1.1.1.6.3.57
upsAlarmExternalAlarm2 1.3.6.1.4.1.4555.1.1.1.1.6.3.58
upsAlarmExternalAlarm3 1.3.6.1.4.1.4555.1.1.1.1.6.3.59
upsAlarmExternalAlarm4 1.3.6.1.4.1.4555.1.1.1.1.6.3.60
upsAlarmEService 1.3.6.1.4.1.4555.1.1.1.1.6.3.61
upsAlarmRedundancyLost 1.3.6.1.4.1.4555.1.1.1.1.6.3.62
upsAlarmPeriodicServiceCheck 1.3.6.1.4.1.4555.1.1.1.1.6.3.63
upsAlarmAllTransferDisabled 1.3.6.1.4.1.4555.1.1.1.1.6.3.64
upsAlarmAutoTransferDisabled 1.3.6.1.4.1.4555.1.1.1.1.6.3.65
upsAlarmBatteryRoom 1.3.6.1.4.1.4555.1.1.1.1.6.3.66
upsAlarmManualBypass 1.3.6.1.4.1.4555.1.1.1.1.6.3.67
upsAlarmBatteryDischarged 1.3.6.1.4.1.4555.1.1.1.1.6.3.68
upsAlarmInsufficientResources 1.3.6.1.4.1.4555.1.1.1.1.6.3.69
upsAlarmOptionalBoards 1.3.6.1.4.1.4555.1.1.1.1.6.3.70
upsAlarmRectifierFault 1.3.6.1.4.1.4555.1.1.1.1.6.3.71
upsAlarmBoostFault 1.3.6.1.4.1.4555.1.1.1.1.6.3.72
upsAlarmInverterFault 1.3.6.1.4.1.4555.1.1.1.1.6.3.73
upsAlarmParallelModuleFault 1.3.6.1.4.1.4555.1.1.1.1.6.3.74
upsAlarmGenSetGeneral 1.3.6.1.4.1.4555.1.1.1.1.6.3.75
upsAlarmGenSetFault 1.3.6.1.4.1.4555.1.1.1.1.6.3.76
upsAlarmEmergencyStopActive 1.3.6.1.4.1.4555.1.1.1.1.6.3.77
upsAlarmBatteryCircuitOpen 1.3.6.1.4.1.4555.1.1.1.1.6.3.78
upsAlarmFansFailure 1.3.6.1.4.1.4555.1.1.1.1.6.3.79
upsAlarmPhaseRotationFault 1.3.6.1.4.1.4555.1.1.1.1.6.3.80
upsAlarmBypassFault 1.3.6.1.4.1.4555.1.1.1.1.6.3.81
upsAlarmA63 1.3.6.1.4.1.4555.1.1.1.1.6.3.82
upsAlarmModule7Alarm 1.3.6.1.4.1.4555.1.1.1.1.6.3.83
upsAlarmModule8Alarm 1.3.6.1.4.1.4555.1.1.1.1.6.3.84
upsAlarmBatteryTemperature 1.3.6.1.4.1.4555.1.1.1.1.6.3.85
upsAlarmRecRedundancy 1.3.6.1.4.1.4555.1.1.1.1.6.3.86
upsAlarmInvRedundancy 1.3.6.1.4.1.4555.1.1.1.1.6.3.87
38 Net Vision Version 6.20 - Ref.: IOMNETVIXX01-GB 02
17. APPENDIX 5: SNMP OID TABLE
17.2. RFC1628 UPS MIB
NOTE: RFC1628 is only available with NetVision firmware version 6.2.
upsIdentManufacturer [1.3.6.1.2.1.33.1.1.1.0]
upsIdentModel [1.3.6.1.2.1.33.1.1.2.0]
upsIdentUPSSoftwareVersion [1.3.6.1.2.1.33.1.1.3.0]
upsIdentAgentSoftwareVersion [1.3.6.1.2.1.33.1.1.4.0]
upsIdentName [1.3.6.1.2.1.33.1.1.5.0]
upsIdentAttachedDevices [1.3.6.1.2.1.33.1.1.6.0]
upsBatteryStatus [1.3.6.1.2.1.33.1.2.1.0]
upsSecondsOnBattery [1.3.6.1.2.1.33.1.2.2.0]
upsEstimatedMinutesRemaining [1.3.6.1.2.1.33.1.2.3.0]
upsEstimatedChargeRemaining [1.3.6.1.2.1.33.1.2.4.0]
upsBatteryVoltage [1.3.6.1.2.1.33.1.2.5.0]
upsBatteryCurrent [1.3.6.1.2.1.33.1.2.6.0]
upsBatteryTemperature [1.3.6.1.2.1.33.1.2.7.0]
upsInputLineBads [1.3.6.1.2.1.33.1.3.1.0]
upsInputNumLines [1.3.6.1.2.1.33.1.3.2.0]
upsInputLineIndex [1.3.6.1.2.1.33.1.3.3.1.1.1]
upsInputLineIndex [1.3.6.1.2.1.33.1.3.3.1.1.2]
upsInputLineIndex [1.3.6.1.2.1.33.1.3.3.1.1.3]
upsInputFrequency [1.3.6.1.2.1.33.1.3.3.1.2.1]
upsInputFrequency [1.3.6.1.2.1.33.1.3.3.1.2.2]
upsInputFrequency [1.3.6.1.2.1.33.1.3.3.1.2.3]
upsInputVoltage [1.3.6.1.2.1.33.1.3.3.1.3.1]
upsInputVoltage [1.3.6.1.2.1.33.1.3.3.1.3.2]
upsInputVoltage [1.3.6.1.2.1.33.1.3.3.1.3.3]
upsInputCurrent [1.3.6.1.2.1.33.1.3.3.1.4.1]
upsInputCurrent [1.3.6.1.2.1.33.1.3.3.1.4.2]
upsInputCurrent [1.3.6.1.2.1.33.1.3.3.1.4.3]
upsInputTruePower [1.3.6.1.2.1.33.1.3.3.1.5.1]
upsInputTruePower [1.3.6.1.2.1.33.1.3.3.1.5.2]
upsInputTruePower [1.3.6.1.2.1.33.1.3.3.1.5.3]
upsOutputSource [1.3.6.1.2.1.33.1.4.1.0]
upsOutputFrequency [1.3.6.1.2.1.33.1.4.2.0]
upsOutputNumLines [1.3.6.1.2.1.33.1.4.3.0]
upsOutputLineIndex [1.3.6.1.2.1.33.1.4.4.1.1.1]
upsOutputLineIndex [1.3.6.1.2.1.33.1.4.4.1.1.2]
upsOutputLineIndex [1.3.6.1.2.1.33.1.4.4.1.1.3]
upsOutputVoltage [1.3.6.1.2.1.33.1.4.4.1.2.1]
upsOutputVoltage [1.3.6.1.2.1.33.1.4.4.1.2.2]
upsOutputVoltage [1.3.6.1.2.1.33.1.4.4.1.2.3]
upsOutputCurrent [1.3.6.1.2.1.33.1.4.4.1.3.1]
upsOutputCurrent [1.3.6.1.2.1.33.1.4.4.1.3.2]
upsOutputCurrent [1.3.6.1.2.1.33.1.4.4.1.3.3]
upsOutputPower [1.3.6.1.2.1.33.1.4.4.1.4.1]
upsOutputPower [1.3.6.1.2.1.33.1.4.4.1.4.2]
upsOutputPower [1.3.6.1.2.1.33.1.4.4.1.4.3]
upsOutputPercentLoad [1.3.6.1.2.1.33.1.4.4.1.5.1]
upsOutputPercentLoad [1.3.6.1.2.1.33.1.4.4.1.5.2]
upsOutputPercentLoad [1.3.6.1.2.1.33.1.4.4.1.5.3]
upsBypassFrequency [1.3.6.1.2.1.33.1.5.1.0]
upsBypassNumLines [1.3.6.1.2.1.33.1.5.2.0]
upsBypassLineIndex [1.3.6.1.2.1.33.1.5.3.1.1.1]
upsBypassLineIndex [1.3.6.1.2.1.33.1.5.3.1.1.2]
upsBypassLineIndex [1.3.6.1.2.1.33.1.5.3.1.1.3]
upsBypassVoltage [1.3.6.1.2.1.33.1.5.3.1.2.1]
upsBypassVoltage [1.3.6.1.2.1.33.1.5.3.1.2.2]
upsBypassVoltage [1.3.6.1.2.1.33.1.5.3.1.2.3]
upsBypassCurrent [1.3.6.1.2.1.33.1.5.3.1.3.1]
upsBypassCurrent [1.3.6.1.2.1.33.1.5.3.1.3.2]
upsBypassCurrent [1.3.6.1.2.1.33.1.5.3.1.3.3]
upsBypassPower [1.3.6.1.2.1.33.1.5.3.1.4.1]
upsBypassPower [1.3.6.1.2.1.33.1.5.3.1.4.2]
upsBypassPower [1.3.6.1.2.1.33.1.5.3.1.4.3]
upsAlarmsPresent [1.3.6.1.2.1.33.1.6.1.0]
upsAlarmEntry [1.3.6.1.2.1.33.1.6.2.1.0]
upsAlarmId [1.3.6.1.2.1.33.1.6.2.1.1.0]
upsAlarmDescr [1.3.6.1.2.1.33.1.6.2.1.2.0]
upsAlarmTime [1.3.6.1.2.1.33.1.6.2.1.3.0]
upsAlarmBatteryBad [1.3.6.1.2.1.33.1.6.3.1.0]
upsAlarmOnBattery [1.3.6.1.2.1.33.1.6.3.2.0]
upsAlarmLowBattery [1.3.6.1.2.1.33.1.6.3.3.0]
upsAlarmDepletedBattery [1.3.6.1.2.1.33.1.6.3.4.0]
upsAlarmTempBad [1.3.6.1.2.1.33.1.6.3.5.0]
upsAlarmInputBad [1.3.6.1.2.1.33.1.6.3.6.0]
upsAlarmOutputBad [1.3.6.1.2.1.33.1.6.3.7.0]
upsAlarmOutputOverload [1.3.6.1.2.1.33.1.6.3.8.0]
upsAlarmOnBypass [1.3.6.1.2.1.33.1.6.3.9.0]
upsAlarmBypassBad [1.3.6.1.2.1.33.1.6.3.10.0]
upsAlarmOutputOffAsRequested [1.3.6.1.2.1.33.1.6.3.11.0]
upsAlarmUpsOffAsRequested [1.3.6.1.2.1.33.1.6.3.12.0]
upsAlarmChargerFailed [1.3.6.1.2.1.33.1.6.3.13.0]
upsAlarmUpsOutputOff [1.3.6.1.2.1.33.1.6.3.14.0]
upsAlarmUpsSystemOff [1.3.6.1.2.1.33.1.6.3.15.0]
upsAlarmFanFailure [1.3.6.1.2.1.33.1.6.3.16.0]
upsAlarmFuseFailure [1.3.6.1.2.1.33.1.6.3.17.0]
upsAlarmGeneralFault [1.3.6.1.2.1.33.1.6.3.18.0]
upsAlarmDiagnosticTestFailed [1.3.6.1.2.1.33.1.6.3.19.0]
upsAlarmCommunicationsLost [1.3.6.1.2.1.33.1.6.3.20.0]
upsAlarmAwaitingPower [1.3.6.1.2.1.33.1.6.3.21.0]
upsAlarmShutdownPending [1.3.6.1.2.1.33.1.6.3.22.0]
upsAlarmShutdownImminent [1.3.6.1.2.1.33.1.6.3.23.0]
upsAlarmTestInProgress [1.3.6.1.2.1.33.1.6.3.24.0]
39
EN
GL
ISH
EN
GL
ISH
Net Vision Version 6.20 - Ref.: IOMNETVIXX01-GB 02
18. TRAP LIST
TRAP
number
TRAP Management Remarks
1 upsTrapOnBattery Send remaining backup battery running
time each minute.
TRAP enabled i f TRAP FILTER =
Disabled on Net Vision Control web page
2 upsTrapTestCompleted NOT MANAGED
3 upsTrapAlarmEntryAdded TRAP sent each time a new active
alert is added to the list. Includes the
upsWellKnownAlarms OID.
TRAP enabled i f TRAP FILTER =
Disabled on Net Vision Control web page
4 upsTrapAlarmEntryRemoved TRAP sent each time an active alert is
removed from the list.
TRAP enabled i f TRAP FILTER =
Disabled on Net Vision Control web page
5 upsTrapUpsNormal
6 upsTrapUpsBattTestFailed
7 upsTrapOnBatteryPower
8 upsTrapBatteryLow
9 upsTrapPowerRestored
10 upsTrapImminentStop
11 upsTrapTurned Off
12 upsTrapOverTemperature
13 upsTrapOverload
14 upsTrapOnMains
15 upsTrapRedoundancyLost
16 upsTrapOnBattery
17 upsTrapTestCompleted
18 upsTrapAlarmEntryAdded
19 upsTrapAlarmEntryRemoved
20 upsTrapUpsNormal
21 upsTrapUpsBattTestFailed
22 upsTrapOnBatteryPower
23 upsTrapBatteryLow
24 upsTrapPowerRestored
25 upsTrapImminentStop
26 upsTrapTurnedOff
27 upsTrapOverTemperature
28 upsTrapOverload
29 upsTrapOnMains
30 upsTrapRedoundancyLost
31 upsTrapEmdTempLow
32 upsTrapEmdTempNotLow
33 upsTrapEmdTempHigh
34 upsTrapEmdTempNotHigh
35 upsTrapEmdHumidityLow
36 upsTrapEmdHumidityNotLow
37 upsTrapEmdHumidityHigh
40 Net Vision Version 6.20 - Ref.: IOMNETVIXX01-GB 02
NOTE: RFC1628 only manages trap 1 to 4.
TRAP
number
TRAP Management Remarks
38 upsTrapEmdHumidityNotHigh
39 upsTrapEmdFirstInputActive
40 upsTrapEmdFirstInputRestored
41 upsTrapEmdSecondInputActive
42 upsTrapEmdSecondInputRestored
18. TRAP LIST
18.1. SNMP V3 CONFIGURATION
When SNMP V3 has been enabled by NET VISION the 'SNMPv3 USM Table' item is added to the NET VISION configuration menu.
This table manages up to 4 users. For each user it is necessary to select the encryption security level, (without, only authentication/
no private, or authentication and private), and the authentication coding key: HMAC-MD5 or HMAC-SHA.
Those configurations have to be set in the same manner by the NMS software. Once the NET VISION has established the connection
with NMS, the status of the user switches to "Ready" in the USM table.
See HTML help page for more details.
41
EN
GL
ISH
EN
GL
ISH
Net Vision Version 6.20 - Ref.: IOMNETVIXX01-GB 02
19. APPENDIX 6: RADIUS CONFIGURATION
19.1. AUTHENTIFICATION CONFIGURATION
19.1-1
1. UDP Port: This parameter dsiplays the RADIUS protocol port.
2. Primary Server: Primary radius server IP or domain name.
3. Secondary Server: Backup radius server IP or domain name. If the radius server is not backed up the parameter can remain blank.
4. Share Secret of Primary Server: This parameter is used to transmit an encryption password between Net Vision and primary radius
server. This value must be the same as primary radius server setting.
5. Share Secret of Secondary Server: This parameter is used to transmit an encryption password between Net Vision and secondary
radius server. This value must be the same as secondary radius server setting. If the radius server is not backed up the parameter
can remain blank.
6. Packet Timeout Interval: When radius server does not respond within time interval authentication packet will be re-sent. This
parameter range is 1 to 3.
7. Packet Retry Times: When radius server does not respond authentication request re-sent according to packet retry times. This
parameter range is 1 to 4.
If you do not have a secondary radius server, you can only set “Primary Server” and “Share Secret of Primary Server”.
42 Net Vision Version 6.20 - Ref.: IOMNETVIXX01-GB 02
HTTP(S) AUTHENTIFICATION
Refer to Net Vision Control page.
1. Local User: Only supports local user login.
2. RADIUS: Only supports radius user login.
3. Both: Local user and radius user can both log in.
19.3. LOGIN
Enter username and password in RADIUS Table
If HTTP(s) Authentifi cation type is RADIUS or Both, you can use radius user to log in.
19. APPENDIX 6: RADIUS CONFIGURATION
19.2. DOMAIN USER TABLE
1. User Name: this parameter is used to set the user's name. User Name must be defined in the radius server.
2. Access Type: Defines user's level of acess. The user can be allowed to modify the system configuration, by setting Access Type
to 'Read/Write'.
19.2-2
43
EN
GL
ISH
EN
GL
ISH
Net Vision Version 6.20 - Ref.: IOMNETVIXX01-GB 02
20. NET VISION TECHNICAL SPECIFICATIONS
20.1. TECHNICAL SPECIFICATIONS
CPU 16-bits AC1107 Fast Ethernet RISC Processor Phoenix Kernel
Memory 2 MB (1Mbit x 16) TFBGA Flash ROM
2 MB (1Mbit x 16) SDRAM
Serial Communication Two UART Channels, one RJ-45, one Gold finger.
LAN Controller 10/100 Mbits Ethernet controller
Network Connection 10/100 TX RJ-45 jack connector
RTC Real time clock
Network Protocol SNMP over UDP/IP
HTTP over TCP/IP
ARP, TFTP, SSH, SSL , NTP and ICMP
Supported MIB SOCOMEC UPS MIB
Operating Temperature 0 ~ 40 °C
Operating Humidity 10 ~ 80 %
Power Input 8-15 V DC
Power Consumption 3.0 Watts Maximum
Dimensions 130 x 60 x 18,2 mm (L x W x H)
Weight 70 g
Regulatory compliance FCC class B
CE class B
20.2. PIN ASSIGNMENT
Bottom Side Component Side
Pin 1 GND Pin 2 DC (8-15V)
Pin 3 Txd > UPS Pin 4 Rxd > UPS
Pin 5 NC Pin 6 NC
Pin 7 NC Pin 8 Short to pin 10
Pin 9 GND Pin 10 Short to pin 8
Pin 11~25 NC Pin 12~26 NC
*IOMNETVIXX01-GB 02*IOMNETVIXX01-GB 02 02.2015
www.socomec.com
HEAD OFFICE
SOCOMEC GROUPS.A. SOCOMEC capital 10 816 800€ R.C.S. Strasbourg B 548 500 149 B.P. 60010 - 1, rue de Westhouse F-67235 Benfeld Cedex - FRANCE Tel. +33 3 88 57 41 41 Fax +33 3 88 74 08 00 [email protected]
Socomec worldwide
BELGIUM
SolarTel. +32 2 340 02 30 Fax +32 2 346 28 99 [email protected]
FRANCE
SolarTel. +33 1 45 14 63 00 Fax +33 1 48 67 31 12 [email protected]
GERMANYPower Control & Energy EfficiencyTel. +49 7243 65292 0 Fax +49 7243 65292 13 [email protected]
UPSTel. +49 621 71 68 40 Fax +49 621 71 68 444 [email protected]
ITALYPower Control & Energy EfficiencyTel.+39 02 98 49 821 Fax +39 02 98 24 33 10 [email protected]
SolarTel. +39 0444 598611 Fax +39 0444 598627 [email protected]
UPS Tel.+39 02 98 242 942 Fax +39 02 98 240 723 [email protected]
NETHERLANDS
SolarTel. +31 30 760 0900 Fax +31 30 637 2166 [email protected]
POLANDPower Control & Energy EfficiencyTel. +48 91 442 64 11 Fax +48 91 442 64 19 [email protected]
UPSTel. +48 22 825 73 60 Fax. +48 22 825 73 60 [email protected]
PORTUGALUPS / SolarTel.+351 261 812 599 Fax +351 261 812 570 [email protected]
ROMANIA
SolarTel. +40 21 319 36 88 Fax +40 21 319 36 89 [email protected]
RUSSIA
SolarTel. +7 495 775 19 85 Fax +7 495 775 19 85 [email protected]
SLOVENIA
SolarTel. +386 1 5807 860 Fax +386 1 561 11 73 [email protected]
SPAIN
SolarTel. +34 93 540 75 75 Fax +34 93 540 75 76 [email protected]
UNITED KINGDOMPower Control & Energy EfficiencyTel. +44 1462 440 033 Fax +44 1462 431 143 [email protected]
UPSTel.+44 1285 863 300 Fax+44 1285 862 304 [email protected]
TURKEY
SolarTel. +90 216 540 71 20-21-22 Fax +90 216 540 71 27 [email protected]
YOUR DISTRIBUTOR
IN ASIA PACIFIC
AUSTRALIAUPSTel. +61 2 9325 3900 Fax +61 2 9888 9544 [email protected]
CHINAUPS / Power Control & Energy EfficiencyTel. +86 21 52 98 95 55 Fax +86 21 62 28 34 68 [email protected]
INDIAPower Control & Energy EfficiencyTel. +91 124 4027210 Fax +91 124 4562738 [email protected]
Tel. +91 44 39215400 Fax +91 44 39215450 & 51 [email protected] [email protected]
SINGAPORE UPS / Power Control & Energy EfficiencyTel.+65 6506 7600 Fax +65 64 58 7377 [email protected]
THAILANDUPSTel. +66 2 941 1644 7 Fax +66 2 941 1650 [email protected]
VIETNAMUPSTel. +84 8 3559 1220 Fax +84 8 3559 1221 [email protected]
IN MIDDLE EAST
UNITED ARAB EMIRATES
SolarTel.+971 4 29 98 441 Fax +971 4 29 98 449 [email protected]
IN AMERICA
USA, CANADA & MEXICOPower Control & Energy EfficiencyTel. +1 617 245 0447 Fax +1 617 245 0437 [email protected]
OTHER COUNTRIES
NORTH AFRICAAlgeria / Morocco / [email protected]
AFRICAOther [email protected]
SOUTH EUROPECyprus / Greece / Israel / [email protected]
SOUTH AMERICATel. +34 93 540 75 75 [email protected]
MORE DETAILSwww.socomec.com/worldwide
IN EUROPE