n jessup st
TRANSCRIPT
N JESSUP ST.
N M
INN
ES
OTA
AV
E.
NORTH COURTYARD
SOUTH COURTYARD
100.00 ft
NEW RESIDENTIAL DEVELOPMENTFLOOR AREA (TITLE 33): 51,455 SF (49,403 SF FAR)
GROSS FLOOR AREA (OSSC): 54,011 SF TOTAL (49,488 SF W/ 4,523 SF BASEMENT)
R226160, R226159(NEW BUILDINGS SHALL HAVE APPROVED ADDRESS NUMBERS, SEE G2)
LAND USE REVIEW: 20-224618-DZREQUIRED: NO FIELD CHANGES ALLOWED
ADJACENT DEVELOPMENT(UNAFFILIATED PROJECT)
5630 N. MONTANA AVE.20-196209-CO
100.03 ft
GENERAL SITE PLAN NOTES:
A. REQUIRED: NO FIELD CHANGES ALLOWED.
B. ATTENTION EXCAVATORS: OREGON LAW REQUIRES YOU TO FOLLOW RULES ADOPTED BY THE OREGON UTILITY NOTIFICATION CENTER. THOSE RULES ARE SET FORTH IN OAR 952-001-0010 THROUGH OAR 952-001-0090. YOU MAY OBTAIN COPIES OF THESE RULES FROM
THE CENTER BY CALLING 811 OR 1-800-332-2344. YOU MUST NOTIFY THE CENTER AT LEAST 2 BUSINESS DAYS, BUT NOT MORE THAN 10 BUSINESS DAYS, BEFORE COMMENCING AN EXCAVATION. CALL 811 OR 1-800-332-2344 FOR QUESTIONS AND INQUIRIES.
C. THE WORKING DRAWINGS ARE GENERALLY DIAGRAMMATIC. THEY DO NOT SHOW EVERY OFFSET, BEND, OR ELBOW REQUIRED FOR INSTALLATION OF THE UTILITIES SHOWN. THE DRAWINGS DO NOT DEPICT EVERY DIMENSION, COMPONENT PIECE, SECTION, JOINT, OR FITTING REQUIRED TO COMPLETE THE PROJECT. ALL LOCATIONS FOR
WORK SHALL BE CHECKED AND COORDINATED WITH EXISTING CONDITIONS IN THE FIELD BEFORE BEGINNING CONSTRUCTION. EXISTING UNDERGROUND UTILITIES LAYING WITHIN THE LIMITS OF EXCAVATION SHALL BE VERIFIED AS TO CONDITION, SIZE, AND LOCATION BY UNCOVERING, PROVIDING SUCH IS PERMITTED BY LOCAL PUBLIC AUTHORITIES WITH JURISDICTION, BEFORE BEGINNING
CONSTRUCTION. CONTRACTOR TO NOTIFY ARCHITECT AND ENGINEER IMMEDIATELY IF THERE ARE ANY DISCREPANCIES.
D. ALL BEDDING AND BACKFILLING MATERIAL AND INSTALLATION SHALL MEET CITY OF PORTLAND AND PIPING MANUFACTURER'S
SPECIFICATION REQUIREMENTS, ALONG WITH A MINIMUM DEPTH OF BURIAL.
E. LANDSCAPING IS TO BE IRRIGATED BY AN IN-GROUND IRRAGATION SYSTEM PER SEPARATE PERMIT.
F. PROVIDE WOVEN-FABRIC LANDSCAPING FABRIC AND 3" MIN. DARK BROWN FIR MULCH THROUGHOUT ALL LANDSCAPED AREAS (TAPER GRADE TO PLANTS).
GENERATOR
10'-2 1/2"
11 '-1 "
SEE CIVIL FOR ALL PUBLIC WORKS, C2.1 FOR UTILITIES
AND C2.2 FOR GRADING PLANS
10'-6"
10'-10" 17'-2 1/2"
SUMP TRANSF.
__________________________
A1.1
3
__________________________
A1.1
2
TREES1.5" CALIPER MIN. AT TIME OF PLANTING
HERITAGE RIVER BIRCH
MAPLE MATSUMURAE
WHITE STAR MAGNOLIA
SHRUBS3 GAL. POT MIN. AT TIME OF PLANTING
CAMELLIA SASANQUA
CUTLEAF LILAC
NORTHWIND SWITCH GRASS
NATIVE SNOWBERRY
TUFTED HAIRGRASS
GROUNDCOVERS4" POT MIN. AT TIME OF PLANTING @ 18" O.C.
BLACK MONDO GRASS
GREEN MONDO GRASS
NATIVE BUNCHBERRY
SWORD FERN
FOUNTAIN GRASS
HARDSCAPESEE CIVIL FOR GRADINGAND STORMWATER PLANS
RIVER ROCK
STAMPED CONCRETE
SITE PLAN LANDSCAPING KEY:
FDC
INSTALL DCDA AND DCVA AT PROPERTY LINE IN BASEMENT, PER PWB REQUIREMENTS UNDER
SEPARATE PERMIT, SEE CIVIL C2.1 UTILITY PLAN
EXISTING GARAGE ON ADJACENT
PROPERTY
DOWNSPOUT (ABOVE)
STORMWATER COLLECTOR (ABOVE)
TUBE STEEL COLONNADE
CANOPY (ABOVE)
PROPERTY LINE
ELEVATED STAMPED
CONCRETE WALK
ROUND RIVER ROCK THROUGHOUT RAINGARDEN
AREA, UNDER TREES AND BENCHES
CUSTOM CONCRETE
BENCH
2A5.2
__________________________
24"
24"
VAULT ACCESSDOORS
LINE OF VAULT BELOW
LINE OF BUILDING ABOVE
SUMP PUMP ACCESS DOOR
PROPERTY LINE
EMERGENCY GENERATOR, ENCLOSE IN 8 FT TALL FULLY
SIGHT-OBSCURING SCREENING
9'-9"
14'-11"
36" MIN.
4
A1.1__________________________
ROUND RIVER ROCK
THROUGHOUT RAINGARDEN
AREA, UNDER TREES AND BENCHES
24" SQUARE STAMPED CONCRETE, SEE
CIVIL STORMWATER MANAGEMENT
CUSTOM CONCRETE
BENCH
STRUCTURAL COLUMN
CUSTOM CONCRETE BENCH
BIKE STAPLE
STORMWATER COLLECTOR (ABOVE) TUBE STEEL COLUMNS
1A5.2
__________________________
RETAINING WALL
TUBE STEEL COLONNADE
8'-0"
METAL PANEL SYSTEM PER
ELEVATION
GALVANIZED STEEL FRAME
PER STRUCTURAL
FOOTING PER STRUCTURAL
ORIGINAL SHEET SIZE: 24" x 36"
HALF SIZE: 12" x 18"
503.206.8380
2222 NE Oregon Street, Suite
Portland, Oregon
www.wright-
john@wright-
Job #:
Drawing Number
Issued:
Project Owner:
Project Name:
PERMIT SUBMITTAL 8.16.2021
1 RESP. TO COMMENTS 9.9.2021
2 C.O.P. REVISIONS 11.15.2021
A1.1
SITE PLAN
SMART PDX PROPERTIES, LLC
MINNESOTAPLACES
2020
PERMITDOCUMENTS
1220 N. JESSUP ST.
1" = 10'-0"1
SITE PLANN
1/4" = 1'-0"2
ENLARGED NORTH COURTYARD PLAN
1/4" = 1'-0"3
ENLARGED SOUTH COURTYARD PLAN
3/4" = 1'-0"4
MECHANICAL SCREEN SECTION DETAIL
N
N
2
UP
DN
UP
DN
1
A
N JESSUP ST.
N M
INN
ES
OT
A A
VE
.
NORTH
COURTYARD
SOUTH
COURTYARD
234567
B
C
D
E
F
18'-3"
13'-7"
24'-4"
13'-7"
18'-3"
2'-11"
15'-4"
0'-10"
12'-9"
5'-5 1/2"
13'-5 1/4"
5'-5 1/2"
12'-9"
0'-10"
17'-4"
0'-11"
14'-3" 14'-6" 31'-0" 14'-6" 14'-3"
COVERED COLONNADE
PROPERTY LINE
BUILDING LINE (ABOVE)
COLONNADE FENCE
9'-0"
18'-0"
__________________________1
A3.2
__________________________1
A3.1
__________________________1
A3.3
__________________________1
A3.4
72"
26"
72"
24"
__________________________
A6.7
2
__________________________
A6.5
2
__________________________
A6.3
1
__________________________
A6.1
3
__________________________
A6.9
2
W-1
TRASH
CANOPY (ABOVE)
CANOPY (ABOVE)
1.252.75
A.25
5.256.75
B.25
C.25
C.75
D.75
E.75
0'-11" 13'-4" 13'-7" 0'-11" 15'-6" 15'-6" 0'-11" 13'-7" 11'-4" 2'-11"
1A4.3
__________________________
GENERAL PLAN NOTES:
A. ALL WALL DIMENSIONS ARE TO FACE OF FRAMING (STUD
AND SHEATHING, CONCRETE, OR CMU BLOCK), ALL POSTS, PLUMBING FIXTURES, AND OPENINGS (WINDOW, DOOR, AND VENT) DIMENSIONS ARE TO CENTERLINE, OTHER DIMENSIONS SUCH AS CLEARANCES, STAIRS, OR CASEWORK ARE TO FACE OF FINISH UNLESS OTHERWISE NOTED.
B. ALL DIMENSIONS ARE TO BE VERIFIED IN THE FIELD BEFORE CONSTRUCTION BEGINS. NOTIFY ARCHITECT AND ENGINEER OF ANY DISCREPANCIES ON DRAWINGS.
C. AN ENGINEERS SPECIFICATION SHALL SUPERSEDE ARCHITECTURAL SPECIFICATION.
D. INTERIOR CORRIDOR FINISH FLOOR LEVEL SAME AS UNIT INTERIOR FINISH FLOOR LEVEL WITH 1/2" THRESHOLD MAX.
ALL EXTERIOR LANDINGS 2% SLOPE MAX.
E. ALL EXPOSED CONCRETE FLOORS ON FOUNDATION, FIRST AND SECOND LEVELS SEE PROJECT MANUAL FOR FINISH.
F. ALL EXPOSED CONCRETE CORE WALLS SEE PROJECT
MANUAL FOR FINISH.
G. ALL FLOORS ON LEVELS 3-8 SHALL BE LVL PER PROJECT MANUAL.
H. CEILING FINISH:ALL BASEMENT, FIRST, AND SECOND LEVEL CEILINGS ARE EXPOSED CONCRETE, FINISH PER PROJECT MANUAL. ALL HALLWAY CEILINGS ON THIRD-8TH FLOORS ARE DROP CIELINGS LOCATED 8'-0" A.F.F. ALL OTHER CEILINGS ARE
GYPSUM WALL BOARD TIGHT AGAINST STRUCTURAL MPP PER ASSEMBLY. ALL EXPOSED PIPING, DUCTWORK, AND CONDUIT TO BE PAINTED TO MATCH ADJACENT SURFACE.
1A4.1
__________________________
STAIR 1
STAIR 2
ELEV.
CORRIDOR114
MAIN LOBBY100
MINNESOTA AVE
LOBBY116
TYPE B UNIT107
TYPE B UNIT108
TYPE B UNIT109
TYPE B UNIT110
COMMUNITY ROOM105
COMMUNITY ROOM106
REST. RM118
REST. RM119
BIKE PARKING A115
COMMUNITY ROOM102
OFFICE104
102
103
111
119
118
104
1A4.2
__________________________
1A4.4
__________________________
LOADING & TRASH103
101
120
115
LARGE PARCEL
PARCEL BOXES
117
100
MAINT.111
88'-6"
88'-0"
24"
DUMPSTER STORAGE
116
MAIL117
W5W5
W4
W5
W4
W4
W5
W5
W12
W12
3'-10 1/2"
12'-0"
2'-4 1/2"
10'-7 1/2"
2'-11 1/2"
2'-0 1/2"
3'-5"
2'-8 3/4"
4'-0"
6'-8 3/4"
3'-5"
5'-0"
10'-7 1/2"
4'-4 1/2"
10'-0"
3'-10 1/2"
4'-10 1/2" 6'-0"
3'-4 1/2" 3'-7 1/2"
6'-0" 4'-10 1/2"
6'-4 1/2"
5'-0"
6'-10 1/2"
6'-6" 4'-0" 5'-0" 12'-0" 3'-6" 2'-9"
102B
96"
120"
48"
FDC
1
2
34
5
5
6 67
8
9
9
10
11
EDGE OF VAULT BELOW
BUILDING LINE ABOVE
12
12
12
12
113
121
1
FLOOR PLAN KEYNOTES:
MAILBOXES PER USPS REQUIREMENTS
ELECTRONIC PARCEL STORAGE SYSTEM SUMP PUMP ACCESS HATCH
TRANSFORMER VAULT ACCESS HATCH PER PGE
REQUIREMENTS
STORMWATER COLLECTOR (ABOVE)
LOADING DOCK CORNER BUMPER
PARKING BOLLARD
WHEEL STOP
STAND PIPE, SEE FIRE PROTECTION
SHORT-TERM BICYCLE PARKING, SEE SHEET G9FOR BICYCLE PARKING STANDARDS
TRASH COMPACTOR, INSTALL PER MANUF. SPECS.
STEEL POST PER STRUCTURAL, CUSTOM COLOR
2
3
4
5
6
7
8
9
10
11
12
ORIGINAL SHEET SIZE: 24" x 36"
HALF SIZE: 12" x 18"
503.206.8380
2222 NE Oregon Street, Suite
Portland, Oregon
www.wright-
john@wright-
Job #:
Drawing Number
Issued:
Project Owner:
Project Name:
PERMIT SUBMITTAL 8.16.2021
1 RESP. TO COMMENTS 9.9.2021
2 C.O.P. REVISIONS 11.15.2021
A2.1
FLOOR PLANLEVEL 1
SMART PDX PROPERTIES, LLC
MINNESOTAPLACES
2020
PERMITDOCUMENTS
1220 N. JESSUP ST.
3/16" = 1'-0"1
FLOOR PLAN LEVEL 1N
2
2
FINISH FLOOR LEVEL 10'-0"
FINISH FLOOR LEVEL 213'-0"
FINISH FLOOR LEVEL 323'-0"
FINISH FLOOR LEVEL 433'-0"
FINISH FLOOR LEVEL 543'-0"
FINISH FLOOR LEVEL 653'-0"
FINISH FLOOR LEVEL 763'-0"
FINISH FLOOR LEVEL 873'-0"
T.O. PARAPET85'-9"
ABCDEF C.5
T.O. ROOF84'-3"
A.25B.25C.25C.75D.75E.75
METAL SYSTEM LOUVERED VENT CAP, TYP.
G I F F I F A A A A B F F G I F F F G
B
B B B B
F F F F
A E
A
E F G I J G F A D E A BB B G G G F F
E A D A C B I J G I J F J F D A E A A A A J
F
I F
D B B A E
J FFB D B A
F G G F G F A A D E A A A B F F G I F F FA
D A A D
G F F F J F D A E A A A A J GIJ F F
D A D B A A A
J F
G
F F B E A D B A A A A J G F F G F F G D A A
F D E A B D A B G G GD
E
A E F F G I J G
F F F J
D E AB AGF E A
B
A A A A E
AAAAAGJFF
JIA
AD
EADAE
B B B B B I J G F F F J F D A E A A A A B G
F
F I J F
D E A A A A A
G G H GG
G E A D B A A A A J G F F G F F G D A A A E A A DBB
F F F G J F I G A A E B A A A B F F G I F F F A A A AEE A
F F F F I J F
A D E
A
E A E F F G I J G F A D E A B A A D J F I G F F J F
G H G G J
G G H G G A
A D E A E A E
A A A J G F F G G D A A A E
1A4.1
__________________________
F F
A
L M NM N L M N M
F
G
A
A
B
A
F
A
F
B
A
G
A
F
J
A
G
ELEVATOR OVERRUN
ENTRY CANOPY
ALUM. SSG STOREFRONT SYSTEM, SEE SCHEDULE
AND PROJECT MANUAL
CONCRETE COLUMN PER STRUCTURAL
TUBE STEEL COLONNADE, SEE SCHEDULE AND
PROJECT MANUAL
ALUM. SSG WINDOW WALL SYSTEM, SEE SCHEDULE AND PROJECT
MANUAL
METAL PANEL SYSTEM, SEE SCHEDULE AND
PROJECT MANUAL
ENTRY CANOPY
1A4.2
__________________________
5
A8.3__________________________
6
A8.2__________________________
4
A8.3__________________________
ROOF HATCH GUARDRAIL
F
__________________________
A9.3
3__________________________
A9.3
2 __________________________
A9.3
1
A
TYP.
A
TYP.
A
TYP.
A
TYP.
A
TYP.
A
TYP.
A
TYP.
A
TYP.
C
TYP.
C
TYP.
__________________________
A9.4
1
D
D D
__________________________
A9.4
3
DED D
DE E D D D
FDC
FIRE DEPARTMENT CONNECTION (FDC)
W/ REQUIRED SIGNAGE
1'-6"
11'-3"
10'-0"
10'-0"
10'-0"
10'-0"
10'-0"
10'-0"
13'-0"
F
TUBE STEEL COLONNADE, SEE SCHEDULE AND
PROJECT MANUAL
15'-0"
15'-0"
EXISTING ADJACENT GARAGE
ORIGINAL SHEET SIZE: 24" x 36"
HALF SIZE: 12" x 18"
503.206.8380
2222 NE Oregon Street, Suite
Portland, Oregon
www.wright-
john@wright-
Job #:
Drawing Number
Issued:
Project Owner:
Project Name:
PERMIT SUBMITTAL 8.16.2021
1 RESP. TO COMMENTS 9.9.2021
2 C.O.P. REVISIONS 11.15.2021
A3.2
EAST ELEVATION
SMART PDX PROPERTIES, LLC
MINNESOTAPLACES
2020
PERMITDOCUMENTS
1220 N. JESSUP ST.
3/16" = 1'-0"1
EAST ELEVATION
2
FINISH FLOOR LEVEL 10'-0"
FINISH FLOOR LEVEL 213'-0"
FINISH FLOOR LEVEL 323'-0"
FINISH FLOOR LEVEL 433'-0"
FINISH FLOOR LEVEL 543'-0"
FINISH FLOOR LEVEL 653'-0"
FINISH FLOOR LEVEL 763'-0"
FINISH FLOOR LEVEL 873'-0"
T.O. PARAPET85'-9"
1234567
T.O. ROOF84'-3"
1.252.755.256.75
1A4.3
__________________________
F F F F A B D A DFG IF
D A A D A FA F F G F BG D D A A B
G G
D A E A A D A A
G G H G G G D A D E A F F F F F F F F F F D B
F G F F G F F D A A B A EA
A A D F F F I F F F AD
A B A A D A A E B F G G F B B C B B B B B
GG F I G F F F F D A A E A F F G I F G F FF
F F F F F D B FF FFFAADDABDFFFFFJFFFIF
FAAAAA
A
E
A
A F F F I G F A
D
A B A A D A A F F G G F F F D A A A A EA
E A F F G I F F FF
F F FF F D AAA A A FFF F F F F F F F D B D A F JF F A
EAAAADFFFG
B D D E A A F F F F F GFFFFJFFFI
F
FABEBA
GFFBEDAABAA
D
AAEFGGFG IGE
G F E A F F G I F F F
F
F F E B A A A A B
A A D A F G G
GFFFFFABAF DFJI FFF
F
FE
A
A
GF
B
F A B D AI A
BB
F
F
N L N M M M L N M L M M L M L N M L M M N
N
N M L N M M L M L L N M L L
M N M N
M L
N
MM N L M N M L N N
METAL PANEL SYSTEM, SEE SCHEDULE AND
PROJECT MANUAL
ENTRY CANOPY
ALUM. SSG STOREFRONT SYSTEM, SEE SCHEDULE
AND PROJECT MANUAL
CONCRETE COLUMN PER STRUCTURAL
COLUMN
1A4.4
__________________________
L
M N
N M N M
ELEVATOR OVERRUN ROOF HATCH GUARDRAIL
__________________________
A9.4
6 __________________________
A9.4
4
G F G G F F
__________________________
A9.3
9
TYP.
A
TYP. TYP. TYP. TYP. TYP. TYP. TYP.
A A A A A AC C C C C C
TYP.TYP.TYP.TYP.TYP.TYP.
DD D D
E
DD D
DD
D B D D
1'-6"
11'-3"
10'-0"
10'-0"
10'-0"
10'-0"
10'-0"
10'-0"
13'-0"
STORMWATER COLLECTOR
G
C
AREA AFFECTED BY OSSC 705.8.6.2, VERTICAL
EXPOSURE FOR BUILDINGS ON SEPARATE LOTS
NO OPERABLE WINDOWS OR
MECHANCIAL OPENINGS
ORIGINAL SHEET SIZE: 24" x 36"
HALF SIZE: 12" x 18"
503.206.8380
2222 NE Oregon Street, Suite
Portland, Oregon
www.wright-
john@wright-
Job #:
Drawing Number
Issued:
Project Owner:
Project Name:
PERMIT SUBMITTAL 8.16.2021
1 RESP. TO COMMENTS 9.9.2021
2 C.O.P. REVISIONS 11.15.2021
A3.3
SOUTHELEVATION
SMART PDX PROPERTIES, LLC
MINNESOTAPLACES
2020
PERMITDOCUMENTS
1220 N. JESSUP ST.
3/16" = 1'-0"1
SOUTH ELEVATION
2
FINISH FLOOR LEVEL 10'-0"
FINISH FLOOR LEVEL 213'-0"
FINISH FLOOR LEVEL 323'-0"
FINISH FLOOR LEVEL 433'-0"
FINISH FLOOR LEVEL 543'-0"
FINISH FLOOR LEVEL 653'-0"
FINISH FLOOR LEVEL 763'-0"
FINISH FLOOR LEVEL 873'-0"
T.O. PARAPET85'-9"
FINISH FLOOR BASEMENT-10'-0"
ABCDEF C.5
T.O. ROOF84'-3"
A.25B.25C.25C.75D.75E.751
A4.1__________________________
1A4.2
__________________________
ELECTRICALTRANSFORMER
CLASS A VAULT002
ELECTRICAL
ROOM003
FIRE / WATER
UTILITY ROOM004
MINNESOTA AVE
LOBBY116
COMMUNITY ROOM102
TYPE B UNIT202
TYPE B UNIT203
TYPE B UNIT204
OFFICE104
LOADING & TRASH103
TYPE B UNIT304
TYPE B UNIT303
TYPE B UNIT302
TYPE A UNIT402
TYPE B UNIT403
TYPE B UNIT404
TYPE B UNIT504
TYPE B UNIT503
TYPE B UNIT502
TYPE B UNIT602
TYPE B UNIT603
COMMUNITY ROOM604
TYPE B UNIT704
TYPE B UNIT703
TYPE B UNIT702
TYPE B UNIT802
TYPE B UNIT803
TYPE B UNIT804
__________________________
A5.1
2__________________________
A5.1
5
__________________________
A8.6
5
VAULT ACESS DOORS
CONCRETE COLUMNS
(BEYOND)
11'-2"
F4
W11 W10
F4
F3
F1
F1
F1
F1
F1
F1
R1
W7W4W4W2W8
W5 W10
W5W4 W5
9'-4"
1'-6"
11'-3"
10'-0"
10'-0"
10'-0"
10'-0"
10'-0"
10'-0"
13'-0"
10'-0"
ORIGINAL SHEET SIZE: 24" x 36"
HALF SIZE: 12" x 18"
503.206.8380
2222 NE Oregon Street, Suite
Portland, Oregon
www.wright-
john@wright-
Job #:
Drawing Number
Issued:
Project Owner:
Project Name:
PERMIT SUBMITTAL 8.16.2021
1 RESP. TO COMMENTS 9.9.2021
2 C.O.P. REVISIONS 11.15.2021
A4.4
BUILDINGSECTION
SMART PDX PROPERTIES, LLC
MINNESOTAPLACES
2020
PERMITDOCUMENTS
1220 N. JESSUP ST.
3/16" = 1'-0"1
NORTH-SOUTH BUILDING SECTION
GFI
D
SURFACE MOUNT FIXTURE
WALL MOUNT FIXTURE
PENDANT FIXTURE
EXHAUST FAN W/ LIGHT FIXTURE
EXHAUST HOOD W/ LIGHT
4' LED PENDANT LIGHT FIXTURE
VERTICLE LED LINEAR FIXTURE
4' STRIP LIGHT ABOVE /BELOW CABINENTS
WALL MOUNTED LIGHT FIXTURE
CEILING MOUNTED FIXTURE
RECESSED LED LIGHT FIXTURE
SINGLE SWITCH
DIMMER SWITCH
DUPLEX RECEPTICLE
DUPLEX RECEPTICLE W/ GFI
CARBON MONOXIDE ALARM
110 V SMOKE DETECTOR
DIGITAL THERMOSTAT, 48" A.F.F.
SD
CM
t
LIGHTING & MECHANICAL KEY:
ABBREVIATION KEY:C-1: COOKTOPM-1: MICROWAVE
MC-1: MEDICINE CABINETTP-1: TOILET PAPER HOLDERR-1: REFRIGERATORWD-1: WASHER/DRYERLVL-1: VINYL TILE**SEE SPECIFICATION SECTION
10.28.00 TOILET,BATH, AND LAUNDRY ACCESSORIES AND 11.30.13
NOTES:
* SEE ENLARGED UNIT PLANS FOR REFLECTED CEILING PLANS**ALL BASEMENT,FIRST, AND SECOND LEVEL CEILINGS ARE CONCRETE*** ALL HALLWAY CEILINGS ON THIRD-8TH FLOORS ARE DROP CIELINGS LOCATED 8'-0" A.F.F. ****ALL OTHER CEILINGS ARE GYPSUM WALL BOARD TIGHT AGAINST STRUCTURAL MPP.****ALL EXPOSED PIPING, DUCTWORK, AND CONDUIT TO BE PAINTED TO MATCH ADJACENT SURFACE.
1
A
234567
B
C
D
E
F
C.5
1.252.75
A.25
5.256.75
B.25
C.25
C.75
D.75
E.75
__________________________
A6.3
2
__________________________
A6.1
4
__________________________
A6.5
1
TRASHCHUTE
9"
1'-2".
1'-2"
3'-0"3'-0"
7 1/4"
7 3/4"
72°
0'-9" 1'-3 1/2"
1'-9"
0'-9"
3'-10"
2'-0"
52.79°
10'-4 1/4"
2'-2 1/4"
41°
2'-4"
0'-9"
1'-5 1/2"
0'-9"
108°
0'-9"
3'-6 1/4"
0'-9"
2'-1 3/4"
1'-3 1/2"
0'-9"
0'-9"
108°
2'-2"
SD
SD
SD
SD
SD
SD
CMSD
SD
TYPE 13 WATER CURTAIN SPRINKLER HEADS @ 6 FT O.C.,
MAX. 12" BELOW SOFFIT
TYPE 13 WATER CURTAIN SPRINKLER HEADS @ 6 FT O.C., 6" MIN. & 12" MAX.
FROM WINDOW, 12" MAX. BELOW CEILING
R 3'-
0"
ORIGINAL SHEET SIZE: 24" x 36"
HALF SIZE: 12" x 18"
503.206.8380
2222 NE Oregon Street, Suite
Portland, Oregon
www.wright-
john@wright-
Job #:
Drawing Number
Issued:
Project Owner:
Project Name:
PERMIT SUBMITTAL 8.16.2021
1 RESP. TO COMMENTS 9.9.2021
2 C.O.P. REVISIONS 11.15.2021
A7.1
REFLECTEDCEILING PLAN
LEVEL 1
SMART PDX PROPERTIES, LLC
MINNESOTAPLACES
2020
PERMITDOCUMENTS
1220 N. JESSUP ST.
3/16" = 1'-0"1
REFLECTED CEILING PLAN LEVEL 1N
2
2
D
D
D
D
D
D
DD
DD
D
D
D
D
D
D
D
D
D
D
DD
D D
DD
D
DD
D
GFI
D
1
A
234567
B
C
D
E
F
C.5
1.252.75
A.25
5.256.75
B.25
C.25
C.75
D.75
E.75
__________________________
A6.2
2
__________________________
A6.1
2
__________________________
A6.4
2
8'-0"
8'-0"8'-0"
9"
0'-9"
0'-9"
TYPE 13 WATER CURTAIN SPRINKLER HEADS @ 6 FT O.C., 6" MIN. & 12" MAX.
FROM WINDOW, 12" MAX. BELOW CEILING
SURFACE MOUNT FIXTURE
WALL MOUNT FIXTURE
PENDANT FIXTURE
EXHAUST FAN W/ LIGHT FIXTURE
EXHAUST HOOD W/ LIGHT
4' LED PENDANT LIGHT FIXTURE
VERTICLE LED LINEAR FIXTURE
4' STRIP LIGHT ABOVE /BELOW CABINENTS
WALL MOUNTED LIGHT FIXTURE
CEILING MOUNTED FIXTURE
RECESSED LED LIGHT FIXTURE
SINGLE SWITCH
DIMMER SWITCH
DUPLEX RECEPTICLE
DUPLEX RECEPTICLE W/ GFI
CARBON MONOXIDE ALARM
110 V SMOKE DETECTOR
DIGITAL THERMOSTAT, 48" A.F.F.
SD
CM
t
LIGHTING & MECHANICAL KEY:
ABBREVIATION KEY:C-1: COOKTOPM-1: MICROWAVE
MC-1: MEDICINE CABINETTP-1: TOILET PAPER HOLDERR-1: REFRIGERATORWD-1: WASHER/DRYERLVL-1: VINYL TILE**SEE SPECIFICATION SECTION
10.28.00 TOILET,BATH, AND LAUNDRY ACCESSORIES AND 11.30.13
NOTES:
* SEE ENLARGED UNIT PLANS FOR REFLECTED CEILING PLANS**ALL BASEMENT,FIRST, AND SECOND LEVEL CEILINGS ARE CONCRETE*** ALL HALLWAY CEILINGS ON THIRD-8TH FLOORS ARE DROP CIELINGS LOCATED 8'-0" A.F.F. ****ALL OTHER CEILINGS ARE GYPSUM WALL BOARD TIGHT AGAINST STRUCTURAL MPP.****ALL EXPOSED PIPING, DUCTWORK, AND CONDUIT TO BE PAINTED TO MATCH ADJACENT SURFACE.
ORIGINAL SHEET SIZE: 24" x 36"
HALF SIZE: 12" x 18"
503.206.8380
2222 NE Oregon Street, Suite
Portland, Oregon
www.wright-
john@wright-
Job #:
Drawing Number
Issued:
Project Owner:
Project Name:
PERMIT SUBMITTAL 8.16.2021
1 RESP. TO COMMENTS 9.9.2021
2 C.O.P. REVISIONS 11.15.2021
A7.2
REFLECTEDCEILING PLAN
LEVEL 2
SMART PDX PROPERTIES, LLC
MINNESOTAPLACES
2020
PERMITDOCUMENTS
1220 N. JESSUP ST.
3/16" = 1'-0"1
REFLECTED CEILING PLAN LEVEL 2N
2
2
W6
METAL STUD PER STRUCTURAL
(2) LAYERS 3/4" TYPE "X" GWB
1/2" RESILIENT CHANNEL @ 24" O.C.
(2) LAYERS 3/4" TYPE "X" GWB
GLASS FIBER OR MINERAL WOOL INSULATION, FILL ENTIRE CAVITY FILL ALL PLUMBING CAVITIES W/
MINERAL WOOL INSULATION
(1) LAYER 5/8" GWB
6
C.25
W4
W1
METAL FURRING AS NEEDED
METAL STUD PER STRUCTURAL
(1) LAYER 5/8" TYPE "X" GWB
1/2" RESILIENT CHANNEL @ 24" O.C.
GLASS FIBER OR MINERAL WOOL INSULATION, FILL ENTIRE CAVITY
CONCRETE COLUMN PER STRUCTURAL
8"
4 1/2"
6"
1 3/4"
C.25
W15 W13
W15
W13
W4
1'-5" 2'-9 1/2"
W2
2'-0"
2'-2"
METAL STUD PER STRUCTURAL
(2) LAYERS 1/2" TYPE "X" GWB
MINERAL WOOL INSULATION, FILL
ENTIRE CAVITY
(S) LAYERS 1/2" TYPE "X" GWB
(2) LAYERS 5/8" TYPE "X" GWB
(1) LAYER 1" GYPSUM LINER
PANELS
3/4"
6"
18"
18"
45 MIN. FIRE-RATED DOOR ON 30 SECOND
DELAY SELF-CLOSER
SPRINKLER HEAD DIRECTLY ABOVE
CHUTE DOOR
TRASH CHUTE DOOR TO FULLY LATCH IF
CHUTE IS FULLY OPEN
90 MIN. FIRE-RATED CHUTE DOOR, SEE
PROJECT MANUAL
W13 W15
ORIGINAL SHEET SIZE: 24" x 36"
HALF SIZE: 12" x 18"
503.206.8380
2222 NE Oregon Street, Suite
Portland, Oregon
www.wright-
john@wright-
Job #:
Drawing Number
Issued:
Project Owner:
Project Name:
PERMIT SUBMITTAL 8.16.2021
1 RESP. TO COMMENTS 9.9.2021
2 C.O.P. REVISIONS 11.15.2021
A8.7
INTERIOR WALLDETAILS
SMART PDX PROPERTIES, LLC
MINNESOTAPLACES
2020
PERMITDOCUMENTS
1220 N. JESSUP ST.
1 1/2" = 1'-0"1
BEARING WALL TO NON-BEARING PARTITION PLAN DETAIL
1 1/2" = 1'-0"2
NON-BEARING PARTITIONS @ COLUMN PLAN DETAIL
1 1/2" = 1'-0"3
TRASH CHUTE PLAN DETAIL2
MARK NAME DESCRIPTION FIRE RATING SOUND RATING
WALL ASSEMBLIES (cont.)
W10
3-HR FIRE RATED EXTERIOR
FOUNDATION WALLN/A
R-7.5 MIN. CONTINUOUS INSULATIONWEATHER RESISTANT BARRIERCAST-IN-PLACE CONCRETE WALL, REINFORCEMENT PER STRUCTURAL
W11
3-HR FIRE RATED INTERIOR BEARING
SHEAR WALL
VAR
IES,
SEE
STR
UCT
UR
AL
CAST-IN-PLACE CONCRETE WALL, REINFORCEMENT PER STRUCTURAL
MARK NAME DESCRIPTION FIRE RATING SOUND RATING
FLOOR/CEILING ASSEMBLIES
F1
F3
2-HR FIRE RATEDINTERIOR
REINFORCED CONCRETE
FLOOR-CEILINGASSEMBLY
F4
F2 INTERIOR
SLAB ON GRADE
MARK NAME DESCRIPTION FIRE RATING SOUND RATING
ROOF/CEILING ASSEMBLIES
FINISH FLOOR PER PLANACOUSTICAL UNDERLAYMENT1.5" GYPCRETE SLAB5" MPP PANEL(1) LAYER 5/8 TYPE 'X' GWB1/2" RESILIENT CHANNEL @ 12" O.C. PERP. TO JOISTS, CHANNELS ORIENTED OPPOSITE AT GWB JOINTS(1) LAYER 5/8 TYPE 'X' GWB, JOINTS FINISHED, PANELS INSTALLED WITH LONG DIMENSION PERPENDICULAR TO RESILIENT CHANNELS, PANELS SECURED WITH 1 IN. LONG TYPE S BUGLE-HEAD SCREWS SPACED 8 IN. OC IN BOTH THE FIELD AND THE PERIMETER, AND 1-1/2 IN. FROM SIDE EDGES OF THE BOARD
R1 1-HR FIRE RATED
ROOF ASSEMBLY
STC & ICC 45 MIN.FIELD TEST
2-HR FIRE RATEDINTERIOR
FLOOR-CEILINGASSEMBLY
0'-9
1/2
"
1'-0
3/8
"0'
-7"
0'-4
"
FINISH FLOOR PER PLAN4" MIN. CONCRETE SLAB PER STRUCTURALVAPOR BARRIER 8" MIN. 3/4" COMPACTED FREE DRAIN ROCKUNDISTURBED OR COMPACTED SOIL PER STRUCTURAL
TPO ROOF MEMBRANE(1) LAYER 1/2" BARRIER BOARD6" MIN. TAPERED RIGID INSULATION, STAGGERED JOINTSMOISTURE BARRIER5" MPP PANEL(1) LAYER 5/8 TYPE "X" GWB1/2" RESILIENT CHANNEL @ 12" O.C.(1) LAYER 5/8 TYPE "X" GWB, JOINTS FINISHED, PANELS INSTALLED WITH LONG DIMENSION PERPENDICULAR TO RESILIENT/FURRING CHANNELS, PANELS SECURED TO RESILIENT CHANNELS WITH 1 IN. LONG TYPE S BUGLE-HEAD SCREWS SPACED 8 IN. OC, WITH SCREWS LOCATED 4 IN. FROM AND ON EACH SIDE OF THE GYPSUM PANEL MID-SPAN, AND 1-1/2 IN. FROM SIDE EDGES OF THE BOARD
FINISH FLOOR PER PLANACOUSTICAL UNDERLAYMENTCONCRETE SLAB AND REINFORCEMENT PER STRUCTURAL
FINISH FLOOR PER PLANACOUSTICAL UNDERLAYMENTCONCRETE SLAB AND REINFORCEMENT PER STRUCTURAL
MARK NAME DESCRIPTION FIRE RATING SOUND RATING
WALL ASSEMBLIES
W1 NON-RATED
INTERIORNON-BEARING
PARTITION
0'-4
7/8
"
N/A
W2
NON-RATEDINTERIOR
NON-BEARINGPLUMBINGPARTITION
(1) LAYER 5/8" GWB, JOINTS FINISHEDFILL ALL PLUMBING CAVITIES W/ MINERAL WOOL INSULATION6" METAL FRAMING STUDS @ 24" O.C. (1) LAYER 5/8" GWB, JOINTS FINISHED
0'-7
1/4
"
W3
NON-RATEDINTERIOR
NON-BEARINGPLUMBING PARTITION
(1) LAYER 5/8" GWB, JOINTS FINISHED3-5/8" METAL FRAMING STUDS @ 24" O.C.FILL ALL PLUMBING CAVITIES W/ MINERAL WOOL INSULATION3-5/8" METAL FRAMING STUDS @ 24" O.C.(1) LAYER 5/8" GWB, JOINTS FINISHED
1'-1
1/2
"
(1) LAYER 5/8" GWB, JOINTS FINISHED3-5/8" METAL FRAMING STUDS @ 24" O.C.(1) LAYER 5/8" GWB, JOINTS FINISHED
W6 2-HR FIRE RATED
INTERIORBEARING
WALL
0'-9
1/2
"
2-HOUR
TEST SOURCE:
BXUV-ANSI/ UL 263DESIGN NO. U425
W5 2-HR FIRE RATED
INTERIORNON-BEARING FIRE BARRIER
(2) LAYER 5/8" TYPE "X" GWB, JOINTS FINISHED AND STAGGEREDGLASS FIBER OR MINERAL WOOL INSULATION, FILL ENTIRE CAVITY1/2" RESILIENT CHANNEL @ 24" O.C3-5/8" METAL FRAMING STUDS @ 24" O.C.(2) LAYER 5/8" TYPE "X" GWB,JOINTS FINISHED AND STAGGERED FROM OPPOSITE SIDE
0'-6
5/8
"
W4 1-HR FIRE RATED
INTERIORNON-BEARING
FIRE PARTITION
0'-5
3/8
"
2-HOURFIELD TEST
1-HOURFIELD TEST
N/AN/A
2-HOUR
TEST SOURCE:
BXUV-ANSI/ UL 263DESIGN NO. U425
(2) LAYER 3/4" TYPE "X" GWB, JOINTS FINISHED AND STAGGEREDGLASS FIBER OR MINERAL WOOL INSULATION, FILL ENTIRE CAVITY1/2" RESILIENT CHANNEL @ 24" O.C.6" METAL FRAMING STUDS, SEE STRUCTURAL (2) LAYER 3/4" TYPE "X" GWB,JOINTS FINISHED AND STAGGERED FROM OPPOSITE SIDE
N/A
(1) LAYER 5/8" TYPE "X" GWB, JOINTS FINISHEDGLASS FIBER OR MINERAL WOOL INSULATION, FILL ENTIRE CAVITY1/2" RESILIENT CHANNEL @ 24" O.C MAX.3-5/8" METAL FRAMING STUDS @ 24" O.C. MAXIMUM, SEE STRUCTURAL(1) LAYER 5/8" TYPE "X" GWB, JOINTS FINISHED
1-HOUR
TEST SOURCE:
BXUV-ANSI/ UL 263DESIGN NO. U419
N/AN/A
N/AN/A
4-HOUR
TEST SOURCE:
TABLE 721.1(2)
4-HOUR
TEST SOURCE:
TABLE 721.1(2)
4-HOUR
TEST SOURCE:
TABLE 721.1(2)
4-HOUR
TEST SOURCE:
TABLE 721.1(2)
STC & ICC 45 MIN.FIELD TEST
STC & ICC 45 MIN.FIELD TEST
STC & ICC 45 MIN.FIELD TEST
STC & ICC 45 MIN.FIELD TEST
STC & ICC 45 MIN.FIELD TEST
2-HR FIRE RATEDINTERIOR
REINFORCED CONCRETE
FLOOR-CEILINGASSEMBLY
STC & ICC 45 MIN.FIELD TEST
2-HR FIRE RATED EXTERIOR
BEARING WALLW9
1-HR FIRE RATED EXTERIOR
NON-BEARINGWALL
W8
NON-RATED EXTERIOR
NON-BEARINGWALL
W7
0'-1
1"1'
-0 1
/4"
METAL WALL PANEL PER ELEVATIONS1-1/2" RIGID INSULATIONZ-GIRT SUB-FRAMING @ 24" O.C.WEATHER RESISTANT BARRIER(2) LAYERS 3/4" TYPE "X" GYPSHEATHING, JOINTS TAPED AND STAGGERED6" METAL FRAMING STUDS, SEE STRUCTURAL GLASS FIBER OR MINERAL WOOL INSULATION, FILL ENTIRE CAVITY(2) LAYERS 3/4" TYPE "X" GWB,JOINTS FINISHED AND STAGGERED FROM OPPOSITE SIDE
1-HOUR
TEST SOURCE:
BXUV-ANSI/ UL 263DESIGN NO. U425
2-HOUR
TEST SOURCE:
BXUV-ANSI/ UL 263DESIGN NO. U425
N/A
METAL WALL PANEL PER ELEVATIONS1-1/2" RIGID INSULATIONZ-GIRT SUB-FRAMING @ 24" O.C.WEATHER RESISTANT BARRIER(1) LAYER 5/8" TYPE "X" GYPSHEATHING, JOINTS TAPED6" METAL FRAMING STUDS, SEE STRUCTURAL GLASS FIBER OR MINERAL WOOL INSULATION, FILL ENTIRE CAVITY1/2" RESILIENT CHANNEL @ 24" O.C.(1) LAYER 5/8" TYPE "X" GWB,JOINTS FINISHED AND STAGGERED FROM OPPOSITE SIDE
METAL WALL PANEL PER ELEVATIONS1-1/2" RIGID INSULATIONZ-GIRT SUB-FRAMING @ 24" O.C.WEATHER RESISTANT BARRIER(1) LAYER 5/8" TYPE "X" GYPSHEATHING, JOINTS TAPED6" METAL FRAMING STUDS, SEE STRUCTURAL GLASS FIBER OR MINERAL WOOL INSULATION, FILL ENTIRE CAVITY1/2" RESILIENT CHANNEL @ 24" O.C.(1) LAYER 5/8" TYPE "X" GWB,JOINTS FINISHED AND STAGGERED FROM OPPOSITE SIDE
0'-1
1"
STC & ICC 45 MIN.FIELD TEST
STC & ICC 45 MIN.FIELD TEST
STC & ICC 45 MIN.FIELD TEST
W13
2-HR FIRE RATED INTERIOR
NON-BEARINGSHAFT ENCLOSURE
FIRE BARRIER
2-1/2" MIN. GALV. "J" RUNNER PERIMETER2-1/2" MIN. GALV. "C-H" STUDS @ 24" O.C.(1) LAYER 1" GYPSUM LINER PANELS, PANELS CUT 1 IN. LESS IN LENGTH THAN FLOOR TO CEILING HEIGHT, VERTICAL EDGES INSERTED IN "H" PORTION OF "C-H" STUDS, FREE EDGE OF END PANELS ATTACHED TO LONG LEG OF VERTICAL "J" - RUNNERS WITH 1-5/8 IN. LONG TYPE S STEEL SCREWS SPACED NOT GREATER THAN 12 IN. OC.(2) LAYERS 5/8" TYPE "X" GWB, BASE LAYER ATTACHED TO STUDS WITH 1 IN. LONG TYPE S STEEL SCREWS SPACED 24 IN. OC VERTICALLY, FACE LAYER ATTACHED TO STUDS WITH 1-5/8 IN. LONG TYPE S STEEL SCREWS SPACED 12 IN. OC VERTICALLY AND STAGGERED 12 IN. FROM BASE LAYER SCREWS
2-HOUR
TEST SOURCE:
BXUV-ANSI/ UL 263DESIGN NO. U415B
0'-3
3/4
"
W12
2-HR FIRE RATED INTERIORBEARING
WALL
0'-9
"
2-HOUR
TEST SOURCE:
BXUV-ANSI/ UL 263DESIGN NO. U425
(2) LAYER 3/4" TYPE "X" GWB, JOINTS FINISHED AND STAGGERED6" METAL FRAMING STUDS, SEE STRUCTURAL (2) LAYER 3/4" TYPE "X" GWB,JOINTS FINISHED AND STAGGERED FROM OPPOSITE SIDE
N/A
STC & ICC 45 MIN.FIELD TEST
0'-8
1/2
"
1-HR FIRE RATED EXTERIOR
NON-BEARINGWALLW
141-HOUR
TEST SOURCE:
BXUV-ANSI/ UL 263DESIGN NO. U425
METAL WALL PANEL PER ELEVATIONS1-1/2" RIGID INSULATIONZ-GIRT SUB-FRAMING @ 24" O.C.WEATHER RESISTANT BARRIER(2) LAYER 3/4" TYPE "X" GYPSHEATHING, JOINTS TAPED6" METAL FRAMING STUDS, SEE STRUCTURAL GLASS FIBER OR MINERAL WOOL INSULATION, FILL ENTIRE CAVITY1/2" RESILIENT CHANNEL @ 24" O.C.(1) LAYER 5/8" TYPE "X" GWB,JOINTS FINISHED AND STAGGERED FROM OPPOSITE SIDE
0'-1
1 7/
8"
STC & ICC 45 MIN.FIELD TEST
STC & ICC 52 MIN.FIELD TEST
W15
2-HR FIRE RATED INTERIOR
NON-BEARINGFIRE PARTITION
0'-3
5/8
"(2) LAYERS 1/2" TYPE "X" GWB, JOINTS FINISHEDMINERAL WOOL INSULATION, FILL ENTIRE CAVITY1-5/8" METAL FRAMING STUDS @ 16" O.C. MAXIMUM, SEE STRUCTURAL(2) LAYERS 1/2" TYPE "X" GWB, JOINTS FINISHED AND STAGGERED FROM OPPOSITE SIDE
2-HOUR
TEST SOURCE:
BXUV-ANSI/ UL 263DESIGN NO. U419
STC & ICC 45 MIN.FIELD TEST
0'-8
3/8
"
2
ORIGINAL SHEET SIZE: 24" x 36"
HALF SIZE: 12" x 18"
503.206.8380
2222 NE Oregon Street, Suite
Portland, Oregon
www.wright-
john@wright-
Job #:
Drawing Number
Issued:
Project Owner:
Project Name:
PERMIT SUBMITTAL 8.16.2021
1 RESP. TO COMMENTS 9.9.2021
2 C.O.P. REVISIONS 11.15.2021
G6
ASSEMBLIES
SMART PDX PROPERTIES, LLC
MINNESOTAPLACES
2020
PERMITDOCUMENTS
1220 N. JESSUP ST.