multilin™ b30 - belmetdesigned to interface with the ge multilin hardfiber system, allowing...
TRANSCRIPT
269
Bus
Prot
ectio
n
g Digital Energy
• HighspeeddifferentialprotectionalgorithmforenhancedwithSubcycletriptimesof0.75powercycle
• CompleteIEC61850ProcessBussolutionprovidingresourceoptimizationandminimizingtotalP&Clifecyclecosts
• SuperiorCTsaturationdetectorcapableofdetectingCTsaturationevenwithonly2msecofsaturationfreecurrentforenhancedthroughfaultstability.
• Ambienttemperaturemonitoringwithalarmingwhenoutsidetemperatureexceedsupperthresholds
• Costeffectivealternativetohighimpedanceschemes• Advancedautomationcapabilitiesforprovidingcustomized
protectionandcontrolsolutions
• High-endfaultanddisturbancerecording,includinginternalrelayoperatingsignalsprovidedthuseliminatingtheneedforredundantrecordingdevices
• ApplicationflexibilitywithmultipleI/Ooptionsandprogrammablelogic(FlexLogic™)
• RobustnetworksecurityenablingCriticalInfrastructureProtectionthroughusercommandlogging,anddualpermissionaccesscontrol
• SimplifiedsystemintegrationwithcommunicationssupportingserialandEthernetinterfacesandmultipleprotocols
• EmbeddedIEC61850Protocolwithnoexternalcommunicationshardwarerequired
• Re-configurablesimplebusapplications,upto6feedersand2differentialzoneswithbreakerfailure
• IntegratedbusprotectionandmeteringforHVandEHVsubstations
• Isolatormonitoring• CTtroublemonitoring,VTsupervision• Metering-current,voltage,frequency• Oscillography-64samples/cycle,upto64records• EventRecorder-1024timetaggedevents,with0.5msscan
ofdigitalinputs
Monitoring and Metering
Protection and Control• Differentialprotectionwithrestrainedand
unrestrainedfunction• FastandreliableCTsaturationdetection• Breakerfailureprotection• ExternalCheck-zone• CTratiomismatchcompensation• DynamicBusReplica• ThermaloverloadandBack-upphase,ground
andneutraltimeandinstantaneousovercurrentprotection
• Undervoltagefunctionforsupervisionpurposes
Communications• Networkingoptions-Ethernet-fiber(optionalredundancy),
RS422,RS485,G.703,C37.94• Multipleprotocols-IEC61850,DNP3.0Level2,ModbusRTU,
ModbusTCP/IP,IEC60870-5-104• DirectI/O-securehigh-speedexchangeofbinarydata
betweenURs
FEATURESFEATURES
APPLICATIONS
KEY BENEFITS
EnerVistaTM Software• GraphicalLogicDesignerandLogicMonitortosimplify
designingandtestingprocedures• Documentandsoftwarearchivingtoolsettoensure
referencematerialanddeviceutilitiesareup-to-date• EnerVistaTMIntegratorprovidingeasyintegrationofdatain
theB30intoneworexistingmonitoringandcontrolsystems
• Robustcommunicationswithupto8HardFiberBricks• SeamlessintegrationwithexistingB30functions• Redundantarchitecturefordependabilityandsecurity
IEC 61850 Process Bus Interface
B30Multilin™
BUS DIFFERENTIAL SYSTEM
Costeffectivelowimpedancebiasedbusdifferentialprotectionforuptosixfeeders
270270
B30Bus Differential SystemBu
s Pr
otec
tion
www.GEDigitalEnergy.com
Protection and ControlTheB30BusDifferentialSystemprovides,secure, subcycle low impedance busprotection for a single busbar with upto six feeders. The B30 is ideally suitedin applications where high impedanceschemes were typically used. Overallsystem costs can be reduced with theB30,sincethereisnoneedfordedicated,or interposing, CTs. TheB30 comeswithadvanced features, such as breakerfailure, CT trouble detection, under-voltage supervision, and dynamic busreplica.With itsextremeflexibility,whichincludesaCTratiomismatchofupto32:1between terminals, the B30 is the idealsolutioninawidevarietyofbusdifferentialapplications.
PartoftheUniversalRelayfamily,theB30comeswithavarietyofversatilefeaturestruly integrating protection, monitoring,metering, communicationand control inoneeasy-to-usedevice.TheUniversalRelayfamilyoffershigherdegreeofmodularityin its design and functionality providingsuperior performance in protection andcontrolmeetingthetoughestrequirementsofthemarketplace.
Bus Differential Protection
TheB30isbasedonacentralizedphase-segregatedarchitecturethatdoesnotrelyon extensive communications betweenIEDs,anapproach that increasesoverallreliability.
The B30 provides fast and secure lowimpedancebusprotectionwithsub-cycletrippingtimesaveraging0.75cycles.The
primaryprotectionisbasedondifferentialand directional protection principles,and uses a dedicated CT saturationmechanism for additional through-faultstability. This mechanism is capable ofdetectingsaturationofCTsasquicklyastwo milliseconds into an external fault .Theoverallsystemcostscanbereducedwith the B30 since there is no need fordedicated,orinterposing,externalCTs.Thetwodifferentialzonescanhandletwosmall buses, split bus, or single bus barwithsupervisionzone.
Dynamic Bus Replica
TheB30providesadynamicbus replicafor each zone of differential protection.Built-inprogrammablelogicremovestheneed for external auxiliary relays, andprovidestheabilityto includeorexclude
currentsdynamicallyfromthedifferentialzones. This allows the B30 to follow theactual busbar configuration with noexternalswitchingofCTcircuitsrequired.TheB30alsoavoidsblindandovertrippingspots in simple bus configurations.Reliabilityisincreasedandcostsreducedbyeliminatingauxiliaryrelaysthatwouldotherwisebeusedforswitchingphysicalcurrents. Theability tomonitorauxiliaryswitchesandacontactdiscrepancyalarmalsoprovidesincreasedsecurity.
Breaker Failure Protection
Three-polebreakerfailure(BF)protectionisavailable.TheB30systemprovidesforupto6BFelementsthatcanrespondtocurrents and/or auxiliary contacts. Thecurrent supervision provides fast reset
B30
Bus
Di�
eren
tial S
yste
m
Zone 1 Zone 2
27P
49
59X
59N51N50N 50G 51G51P
50/87
Rest
rain
t Cur
rent
Metering FlexElements
VT in
put
(opt
iona
l)
TM
Curr
ent D
irec
tiona
l Com
pari
son
CT S
atur
atio
n D
etec
tion
CT T
roub
le (5
0/74
)
87B
51N50N 50G 51G51P
51N50N 50G 51G51P
51N50N 50G 51G51P
51N50N 50G 51G51P
51N50N 50G 51G51P
50P
50P
50P
50P
50P
50P
Functional Block DiagramDeviceNumber Function27P PhaseUndervoltage49 Thermaloverload50G GroundInstantaneousOvercurrent50N NeutralInstantaneousOvercurrent50P PhaseInstantaneousOvercurrent50/74 CTTrouble50/87 UnrestrainedBusDifferential51G GroundTimeOvercurrent51N NeutralTimeOvercurrent51P PhaseTimeOvercurrent59N NeutralOvervoltage59X AuxiliaryOvervoltage87B RestrainedBusDifferential
ANSIDeviceNumbers&Functions
B30 - Protection, Metering, Monitoring and Control
The B30 is the single point for protection, control, metering, and monitoring in one integrated device that can easily be connected directly into DCS or SCADA monitoring and control systems like Viewpoint Monitoring.
271271
B30Bus Differential System
Bus
Prot
ectio
n
www.GEDigitalEnergy.com
time and separate settings for low-setandhi-setare implemented. TheBF canbe initiated internally from the busbarprotectionorexternallyviainputcontactsorcommunications.
Backup Protection
Backup protection is available withinstantaneous and time overcurrentfunctions for each current input of theB30system.Forsupervisionpurposes,anundervoltagefunctionisalsoprovidedforeachvoltageinputoftheB30system.
• IOCFunctions:TwoseparateIOCfunctionsareavailablefortripsupervisionorotheruser-configurableapplications
• TOC:OneTOCfunctionisincorporatedforeachCTinputoftherelay.Upto6TOCsareavailableforbackupprotection.TheTOCfunctioncanusestandardoruser-programmablecurves
• VoltageSupervision:uptotwoundervoltageelementsareavailablepereachVTinputoftherelay.Thisfunctionmaybeusedtosupervisethecurrent-basedprotectionfunctionsforextrasecurity
External Check-Zone
An optional external check-zone canbe used to prevent operation of thedifferentialprotectionduetoCTtroubles.IfoneB30currentinputisleftunusedandanalternativesetofcurrentsignalsisavailablefrom independent CTs, the currents canbe combined externally and connectedto the relay. Two phase overcurrentelementsareavailabletocheckthelevelof this independently formeddifferentialcurrenttosupervisethemaindifferentialprotection.
IEC 61850 Process BusThe IEC 61850 Process Bus module isdesignedtointerfacewiththeGEMultilinHardFiberSystem,allowingbi-directionalIEC 61850 fiber optic communications.The HardFiber System is designed tointegrate seamlessly with the existingUniversal Relay applications, includingprotection functions,FlexLogic,meteringandcommunications.TheGEMultilin HardFiber System offersthefollowingbenefits:
• CommunicatesusingopenstandardIEC61850messaging
• DrasticallyreducesP&Cdesign,installationandtestinglaborbyeliminatingindividualcopperterminations
• IntegrateswithexistingB30’sbyreplacingtraditionalCT/VTinputswithIEC61850ProcessBusmodule
• NonewCyberSecurityconcerns
Built-in Advanced Disturbance Recording
The bus differential element picks up due to heavy CT saturation
The CT Saturation flag is set safely before the pickup flag
The directional flag is not set
The element does not maloperate
Despite heavy CT saturation the external fault is seen in the opposite direction
The bus differential element picks up
The CT Saturation flag is not set - no directional decision required
The directional flag is set
The element operates in 10 ms
All the fault currents are seen in one direction
The built-in advanced disturbance recording function allows users to view the COMTRADE files and trouble shoot bus fault . The internal operation of the B30 elements, logic, and outputs can be monitored in real time to simplify commissioning and troubleshooting procedures. Two cases are shown here:
External Fault: Even with heavy CT saturation and with only 1 msec of saturation free current B30 is stable for through faults. See the Directional Comparison element output, which adds additional security to the bus differential functionInternal Fault: For internal fault the CT saturation flag is not set and the directional element output is safely ignored resulting in an operating time of less than 10 msec.
272272
B30Bus Differential SystemBu
s Pr
otec
tion
www.GEDigitalEnergy.com
VisittheHardFiberSystemproductpageontheGEMultilinwebsiteformoredetails.
Advanced AutomationTheB30incorporatesadvancedautomationfeatures including powerful FlexLogic™programmablelogic,communication,andSCADAcapabilitiesthatfarsurpasswhatisfoundintheaveragebusrelay.TheB30integratesseamlesslywithotherURrelaysforcompletesystemprotection.
FlexLogic™
FlexLogic™ is the powerful UR-platformprogramming logic engine thatprovidesthe ability of creating customizedprotectionandcontrol schemes therebyminimizing theneed,andtheassociatedcosts,ofauxiliarycomponentsandwiring.Using FlexLogic™, the B30 can beprogrammedtoproviderequiredtrippinglogicalongwithcustomschemelogicforbreakercontrol,transfertrippingschemesforremotebreakersanddynamicsettinggroupchanges.
Scalable HardwareTheB30isavailablewithamultitudeofI/Oconfigurationstosuitthemostdemanding
applicationneeds.Theexpandablemodulardesignallowsforeasyconfigurationandfutureupgrades.
• MultipleCT/VTconfigurationsallowforimplementationofmanydifferentschemes
• Flexible,modularI/Ocoveringabroadrangeofinputsignalsandtrippingschemes
• Typesofdigitaloutputsincludetrip-ratedForm-AandSolidStateRelay(SSR)mechanicallylatching,andForm-Coutputs
• Form-AandSSRoutputsavailablewithoptionalcircuitcontinuitymonitoringandcurrentdetectiontoverifycontinuityandhealthoftheassociatedcircuitry
• Mechanicallylatchingoutputscanbeusedtodevelopsecureinterlockingapplicationsandreplaceelectromechanicallockoutrelays
• RTDsandDCmAinputsareavailabletomonitorequipmentparameterssuchastemperature&pressure
Monitoring and MeteringTheB30includeshighaccuracymeteringandrecording forallACsignals.Voltage,current,andpowermeteringarebuiltintothe relayasa standard feature.Currentandvoltageparameters are availableas total RMS magnitude, and asfundamental frequency magnitude andangle.
Fault and Disturbance Recording
The advanced disturbance and eventrecording features within the B30 cansignificantly reduce the timeneeded forpostmortem analysis of power systemeventsandcreationofregulatoryreports.Recordingfunctionsinclude:
• SequenceofEvent(SOE)-1024timestampedevents
• Oscillography,
-64digital&upto40Analogchannels
• DataLogger,disturbancerecording–16channelsupto1sample/cycle/channel
• FaultReports-Powerfulsummaryreportofpre-faultandfaultvalues
The very high sampling rate and largeamount of storage space available fordata recording in theB30 can eliminatetheneed for installingcostlystandalonerecordingequipment.
Advanced Device Health Diagnostics
The B30 performs comprehensivedevice health diagnostic tests duringstartup and continuously at runtime totest its ownmajor functions and criticalhardware.Thesediagnostictestsmonitorforconditionsthatcould impactsecurityandavailabilityofprotection,andpresentdevicestatusviaSCADAcommunicationsand front panel display. Providingcontinuousmonitoringandearlydetectionof possible issueshelps improve systemuptime.
• Comprehensivedevicehealthdiagnosticperformedduringstartup
• MonitorstheCT/VTinputcircuitrytovalidatetheintegrityofallsignals
Custom Programmable Logic Designer
The internal operation of the B30 elements, logic, and outputs can be monitored in real time to simplify commissioning and troubleshooting procedures
273273
B30Bus Differential System
Bus
Prot
ectio
n
www.GEDigitalEnergy.com
CommunicationsTheB30providesforsecureremotedataand engineering access,making it easyand flexible to use and integrate intonew and existing infrastructures. Fiberoptic Ethernet provides high-bandwidthcommunicationsallowingforlow-latencycontrolsandhigh-speed file transfersofrelayfaultandeventrecord information.Theavailable redundantEthernetoptionprovides the means of creating faulttolerant communicationarchitectures inaneasy,cost-effectivemanner.TheB30supportsthemostpopularindustrystandardprotocolsenablingeasy,directintegrationintoDCSandSCADAsystems.
• IEC61850
• DNP3.0
• IEC60870-5-104
• ModbusRTU,ModbusTCP/IP
Interoperability with Embedded IEC61850
The B30 with integrated IEC61850 canbe used to lower costs associated withbusprotection, control, andautomation.GE Multilin’s leadership in IEC61850comes from thousands of installeddevices and follows on Multilin’sextensive development experience withUCA2.0.
• ReplaceexpensivecopperwiringbetweendeviceswithdirecttransferofdatausingGOOSEmessaging
• ConfiguresystemsbasedonIEC61850andalsomonitorandtroubleshoottheminreal-timewithEnerVistaTM
ViewpointEngineer
• IntegrateGEMultilinIEDsandgenericIEC61850-compliantdevicesseamlesslyinEnerVistaTMViewpointMonitoring
Direct I/O Messaging
DirectI/Oallowsforsharingofhigh-speeddigital information betweenmultiple URrelaysviadirectback-to-backconnectionsor multiplexed through a standard DS0multiplexerchannelbank. Regardlessoftheconnectionmethod,DirectI/Oprovidescontinuousreal-timechannelmonitoringthat suppliesdiagnostics informationonchannelhealth.DirectI/Oprovidessuperiorrelay-to-relaycommunications that can be used inadvancedinterlocking,generationrejectionandotherspecialprotectionschemes.
• Communicationwithupto16URrelaysinsingleorredundantringsratherthanstrictlylimitedtosimplisticpoint-to-pointconfigurationsbetweentwodevices
• ConnecttostandardDS0channelbanksthroughstandardRS422,G.703orIEEEC37.94interfacesorviadirectfiberopticconnections
• Noexternalorhandheldtesterrequiredtoprovidechanneldiagnosticinformation
Multi-Language
TheB30supportsEnglish,French,Russian,andChineselanguagesonthefrontpanel,EnerVista setup software, and productmanual. Easily switch between Englishandanadditional languageon the localdisplayswithoutuploadingnewfirmware.
EnerVistaTM SoftwareTheEnerVista™Suiteisanindustry-leadingset of software programs that simplifieseveryaspectofusingtheB30relay.TheEnerVistaTM suite provides all the toolsto monitor the status of the protectedasset ,maintain the relay, and integrateinformation measured by the B30 intoDCS or SCADA monitoring systems.Convenient COMTRADE and Sequenceof Events viewers are an integral partof the UR Setup software included witheveryURrelay,tocarryoutpostmortemeventanalysistoensureproperprotectionsystemoperation.
EnerVista™ Launchpad
EnerVista™ Launchpad is a powerfulsoftwarepackagethatprovidesuserswithallofthesetupandsupporttoolsneededforconfiguringandmaintainingGEMultilinproducts. The setup software withinLaunchpad allows configuring devicesin real-time by communicating usingserial,Ethernet,ormodemconnections,orofflinebycreatingsettingfilestobesenttodevicesatalatertime.
Included in Launchpad is a documentarchiving and management systemthat ensures critical documentation isup-to-date and available when needed.Documentsmadeavailableinclude:
• Manuals
• ApplicationNotes
• GuideformSpecifications
• Brochures
• WiringDiagrams
• FAQ’s
• ServiceBulletins
Monitor the status of your substation using the easy to use Viewpoint Monitoring HMI
Substation Monitoring
274274
B30Bus Differential SystemBu
s Pr
otec
tion
www.GEDigitalEnergy.com
Viewpoint Monitoring
Viewpoint Monitoring is a simple-to-useand full-featured monitoring and datarecording software package for smallsystems.ViewpointMonitoringprovidesacompleteHMIpackagewiththefollowingfunctionality:
• Plug-&-PlayDeviceMonitoring
• SystemSingle-LineMonitoring&Control
• AnnunciatorAlarmScreens
• TrendingReports
• AutomaticEventRetrieval
• AutomaticWaveformRetrieval
Viewpoint Engineer
Viewpoint Engineer is a set of powerfultools that will allow the configurationandtestingofURrelaysatasystemlevelin an easy-to-use graphical drag-and-drop environment . Viewpoint Engineerprovides the followingconfigurationandcommissioningutilities:
• GraphicalLogicDesigner
• GraphicalSystemDesigner
• GraphicalLogicMonitor
• GraphicalSystemMonitor
Record the operation of the internal B30 elements and external connected devices with 1ms time-stamped accuracy
Simplifying Commissioning and Testing
Create B30 Setting File Templates to ensure critical settings are not altered
LEDIndicators
Multi-LanguageDisplay• English• Russian• French• Chinese
UserProgrammablePushbuttons
Viewpoint Maintenance
ViewpointMaintenanceprovidestoolsthatwillcreatereportsontheoperatingstatusoftherelay,simplifythestepstodownloadfaultandeventdata,andreducetheworkrequired for cyber-security complianceaudits. Tools available in ViewpointMaintenanceinclude:
• SettingsSecurityAuditReport
• DeviceHealthReport
• SingleClickFaultDataRetrieval
EnerVista™ Integrator
EnerVistaTM Integrator is a toolkit thatallowsseamlessintegrationofGEMultilin
devices intonewor existingautomationsystems.IncludedinEnerVistaIntegratoris:
• OPC/DDEServer
• GEMultilinDrivers
• AutomaticEventRetrieval
• AutomaticWaveformRetrieval
User InterfaceThe B30 front panel provides extensivelocalHMI capabilities. The local displayisusedformonitoring,statusmessaging,faultdiagnosis,anddeviceconfiguration.Userconfigurablemessagesthatcombinetextwithlivedata,canbedisplayedwhenuser-definedconditionsaremet.
275275
B30Bus Differential System
Bus
Prot
ectio
n
www.GEDigitalEnergy.com
Typical Wiring
B30-H00-HCL-F8H-H6H-L8H-N6A-S8H-U6H
F3
F5
F4
F6
DC
Dry
B30
1
PowerSupply
9
CPU
JU MX LW KV BHT DN G FPS R8
CT
6
Inputs/outputs
8
CT*
6
Inputs/outputs
*
8
CT*
6
Inputs/outputs
*
F1
F2
A B C
Digital EnergyMultilin
B30-H00-HCL-F8H-L8H-N6A-S8H-U6H
(Rear View)
CRITICALFAILURE
OUTPUT
CONTROLPOWER
HILO
1
FILTERSURGE
B3a
B1b
B8a
B6b
B8b
B6a
B3b
B1aB2b
B5b
SURGE
N6a
N8a
N5b
N7b
N8b
N5a
N7a
N6c
N8c
N5c
N7c
6A
N1
N2
N3
N4
N1a
N2b
N1cN1b
N2c
N2a
N4a
N4c
N3bN3a
N4b
N3c
I
V
I
V
6H
H8a
H7b
H7a
H8c
H7c
H1b
H2b
H3b
H4b
H5b
H6b
H1a
H2a
H3a
H4a
H5a
H6a
H1c
H2c
H3c
H4c
H5c
H6c
SURGEH8b
H1
H5
H2
H6
H3
H4
I
V
I
V
I
V
I
V
I
V
I
V
Wet
6H
U8a
U7b
U7a
U8c
U7c
U1b
U2b
U3b
U4b
U5b
U6b
U1a
U2a
U3a
U4a
U5a
U6a
U1c
U2c
U3c
U4c
U5c
U6c
SURGEU8b
U1
U5
U2
U6
U3
U4
I
V
I
V
I
V
I
V
I
V
I
V
Minimum
PROVIDED
com
10BaseFL
10BaseFL
10BaseT
D1aD2a
D4bD3a
D4a IRIG-BInput
IRIG-BOutput
COM1
RS485
ALTERNATE
NORMAL
Tx2Rx2
Tx1Rx1
BNC
BNC
FibreOptic
*
RemoteDevice
Shielded
Co-axial
Co-axial
F7c
F5c
F5a
F5b
F7b
F3c
F1c
F6a
F2b
F7a
F2a
F6b
F6c
F2c
F1a
F1b
F3a
F3b
IA
IA
IC
IC
IB
IB
IA5
IA5
IC5
IC5
IB5
IB5
IA1
IA1
IC1
IC1
IB1
IB1
7c
5c
5a
5b
7b
3c
1c
6a
2b
7a
2a
6b
6c
2c
1aS
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
1b
3a
3b
IA
IA
IC
IC
IB
IB
IA5
IA5
IC5
IC5
IB5
IB5
IA1
IA1
IC1
IC1
IB1
IB1
L7c
L5c
L5a
L5b
L7b
L3c
L1c
L6a
L2b
L7a
L2a
L6b
L6c
L2c
L1a
L1b
L3a
L3b
IA
IA
IC
IC
IB
IB
IA5
IA5
IC5
IC5
IB5
IB5
IA1
IA1
IC1
IC1
IB1
IB1
276276
B30Bus Differential SystemBu
s Pr
otec
tion
www.GEDigitalEnergy.com
Ordering Note: 1-Forverticalmountingordercodes,pleasevisitouronlinestoreorreviewtheB30instructionmanual2-ToviewthelatestoptionsavailablefortheB30,ortoordertheURClassicFrontPanel,pleasevisitouronlinestoreformoredetails.
110503-v6
Ordering
• URApplicationsILearningCD TRCD-URA1-C-S-1
• MultilinkEthernetSwitch ML2400-F-HI-HI-A2-A2-A6-G1
• ViewpointEngineer VPE-1
• ViewpointMaintenance VPM-1
• ViewpointMonitoringIEC61850 VP-1-61850
Accessories for the B30 • ViewGuideformspecifications
• Downloadtheinstructionmanual
• Reviewapplicationsnotesandsupportdocuments
• BuyaB30online
• ViewtheURFamilybrochure
Visit www.GEMultilin.com/B30 to:
B30 - * ** - H * * - F ** - H ** - L ** - N ** - S ** - U ** - W ** For Full Sized Horizontal MountBaseUnit B30 BaseUnitCPU E RS485+RS485(IEC61850optionnotavailable) G RS485+10BaseF H RS485+Redundant10BaseF J RS485+Multi-modeST100BaseFX K RS485+Multi-modeSTRedundant100BaseFX N RS485+10/100BaseTSoftwareOptions 00 NoSoftwareOptions 03 IEC61850Mount/Coating H Horizontal(19"rack) A Horizontal(19"rack)-HarshChemicalEnvironmentOptionUserInterface K EnhancedEnglishFrontPanel L EnhancedEnglishFrontPanelwithUser-ProgrammablePushbuttons M EnhancedFrenchFrontPanel N EnhancedFrenchFrontPanelwithUser-ProgrammablePushbuttons Q EnhancedRussianFrontPanel T EnhancedRussianFrontPanelwithUser-ProgrammablePushbuttons U EnhancedChineseFrontPanel V EnhancedChineseFrontPanelwithUser-ProgrammablePushbuttons C BasicFrontPanelwithEnglishdisplayPowerSupply H 125/250VAC/DC H RH 125/250VAC/DCwithredundant125/250VAC/DCpowersupply L 24-48V(DConly)CT/VTDSP 8L 8L 8L Standard4CT/4VTw/enhanceddiagnostics 8M 8M 8M SensitiveGround4CT/4VTw/enhanceddiagnostics 8N 8N 8N Standard8CTw/enhanceddiagnostics 8R 8R 8R SensitiveGround8CTw/enhanceddiagnosticsIEC61850ProcessBus 81 8PortIEC61850ProcessBusModuleDigitalI/O XX XX XX Nomodule 4A 4A 4A 4SolidState(NoMonitoring)MOSFETOutputs 4C 4C 4C 4SolidState(Currentw/optVoltage)MOSFETOutputs 4D 4D 4D 16DigitalInputswithAuto-Burnish 4L 4L 4L 14Form-A(NoMonitoring)LatchableOutputs 67 67 67 8Form-A(NoMonitoring)Outputs 6C 6C 6C 8Form-COutputs 6D 6D 6D 16DigitalInputs 6E 6E 6E 4Form-COutputs,8DigitalInputs 6F 6F 6F 8FastForm-COutputs 6K 6K 6K 4Form-C&4FastForm-COutputs 6L 6L 6L 2Form-A(Currentw/optVoltage)&2Form-COutputs,8DigitalInputs 6M 6M 6M 2Form-A(Currentw/optVoltage)&4Form-COutputs,4DigitalInputs 6N 6N 6N 4Form-A(Currentw/optVoltage)Outputs,8DigitalInputs 6P 6P 6P 6Form-A(Currentw/optVoltage)Outputs,4DigitalInputs 6R 6R 6R 2Form-A(NoMonitoring)&2Form-COutputs,8DigitalInputs 6S 6S 6S 2Form-A(NoMonitoring)&4Form-COutputs,4DigitalInputs 6T 6T 6T 4Form-A(NoMonitoring)Outputs,8DigitalInputs 6U 6U 6U 6Form-A(NoMonitoring)Outputs,4Digital 6V 6V 6V 2Form-A(Curw/optVolt)1Form-COutput,2LatchingOutputs,8DigitalInputsTransducerI/O 5A 5A 5A 4dcmAInputs,4dcmAOutputs 5F 5F 5F 8dcmAInputsInter-RelayCommunications 2B C37.94SM,1300nmsingle-mode,ELED,2channelsingle-mode 7A 820nm,multi-mode,LED,1Channel 7B 1300nm,multi-mode,LED,1Channel 7C 1300nm,single-mode,ELED,1Channel 7H 820nm,multi-mode,LED,2Channels 7I 1300nm,multi-mode,LED,2Channels 7J 1300nm,single-mode,ELED,2Channels 7S G.703,2Channels 7W RS422,2Channels 77 IEEEC37.94,820nm,multimode,LED,2Channel