MTTF* prediction for Anybus X-gateway Modbus-TCP Simulation method: Telcordia Issue 2, Method 1 Case 3 Simulation environment: Ground, Fixed, Controlled Simulation temperature: 30° C Simulation duty cycle: 100 % Simulation software: ReliaSoft Lambda Predict 3, 3.1.1 Remarks:
Only electrical components included in the calculation.
Discrete components estimated to quality level 1, connectors to level 0.
Predicted failure intensity only valid after running-in period.
Components normally not mounted are included in the calculation.
FIT rates from manufacturers used where available.
Part number Description; Modbus-TCP to… MTTF* value; hours
AB9000-B EtherCAT 544 000h
AB9001-B PROFIBUS 1 034 000h
AB9002-B DeviceNet 655 000h
AB9003-B ControlNet 742 000h
AB9004-B CANopen 755 000h
AB9005-B Modbus-RTU [missing]
AB9006-B EtherNet/IP 811 000h
AB9007-B PROFINET IO 811 000h
AB9008-B Modbus-TCP 811 000h
AB9009-B CC-Link 609 000h
* Note: MTTF = Mean Time To Failure Definition: Estimation of average time to failures with the modeling assumption that the failed system is not repaired (infinite repair rate).