msci | merrill sheriff constructionmscibuild.com/wp-content/uploads/2020/01/20kp16... · 1/20/2020...
TRANSCRIPT
![Page 1: MSCI | Merrill Sheriff Constructionmscibuild.com/wp-content/uploads/2020/01/20KP16... · 1/20/2020 · psecurity system pop-it mount as per. man cclock outlet +7'-6"8. dp flat panel](https://reader034.vdocuments.us/reader034/viewer/2022050602/5fa98617471635744231287d/html5/thumbnails/1.jpg)
![Page 2: MSCI | Merrill Sheriff Constructionmscibuild.com/wp-content/uploads/2020/01/20KP16... · 1/20/2020 · psecurity system pop-it mount as per. man cclock outlet +7'-6"8. dp flat panel](https://reader034.vdocuments.us/reader034/viewer/2022050602/5fa98617471635744231287d/html5/thumbnails/2.jpg)
![Page 3: MSCI | Merrill Sheriff Constructionmscibuild.com/wp-content/uploads/2020/01/20KP16... · 1/20/2020 · psecurity system pop-it mount as per. man cclock outlet +7'-6"8. dp flat panel](https://reader034.vdocuments.us/reader034/viewer/2022050602/5fa98617471635744231287d/html5/thumbnails/3.jpg)
![Page 4: MSCI | Merrill Sheriff Constructionmscibuild.com/wp-content/uploads/2020/01/20KP16... · 1/20/2020 · psecurity system pop-it mount as per. man cclock outlet +7'-6"8. dp flat panel](https://reader034.vdocuments.us/reader034/viewer/2022050602/5fa98617471635744231287d/html5/thumbnails/4.jpg)
![Page 5: MSCI | Merrill Sheriff Constructionmscibuild.com/wp-content/uploads/2020/01/20KP16... · 1/20/2020 · psecurity system pop-it mount as per. man cclock outlet +7'-6"8. dp flat panel](https://reader034.vdocuments.us/reader034/viewer/2022050602/5fa98617471635744231287d/html5/thumbnails/5.jpg)
![Page 6: MSCI | Merrill Sheriff Constructionmscibuild.com/wp-content/uploads/2020/01/20KP16... · 1/20/2020 · psecurity system pop-it mount as per. man cclock outlet +7'-6"8. dp flat panel](https://reader034.vdocuments.us/reader034/viewer/2022050602/5fa98617471635744231287d/html5/thumbnails/6.jpg)
Project For
Jordan School District
7905 South Redwood Road
West Jordan, Utah 84088
The
Jordan School
District
Board of
Education
Secure Entries
N a y l o rW e n t w o r t hL u n dA r c h i t e c t s
Sheet Title
NWL Project
Number
Stamp
Project Issue Date
Project Phase
Revision Schedule
136.014
No. Description Date
Bid Documents
January 21, 2020
Sheet
Number
5445 New Bingham Hwy
West Jordan, Utah 84081
Copper Hills
High School
ã 2020 BNACONSULTING
635 South State StreetSalt Lake City, Utah 84111
P:801.532.2196F:801.532.2305
www.bnaconsulting.comBNACONSULTINGSALT LAKE ST.GEORGE
11917 S. Mustang Trail Way
Herriman, Utah 84096
Herriman
High School
E001
SYMBOLS,
SCHEDULES,
AND NOTES
ONE CIRCUIT, HOME RUN TO PANEL
TWO CIRCUIT, HOME RUN TO PANEL
THREE CIRCUIT, HOME RUN TO PANEL
CONDUIT RUN CONCEALED IN WALL OR CEILING
CONDUIT RUN CONCEALED IN FLOOR OR GROUND
CONDUIT UP
CONDUIT DOWN
CONDUIT STUB LOCATION
CONDUIT
CAP
CONDUIT/CIRCUIT CONTINUATION
CABLE TRAY AS NOTED
CEILING LIGHT FIXTURE
CEILING 1.
WALL LIGHT FIXTURE AS NOTED 1.
RECESSED DOWNLIGHT FIXTURE CEILING 1.
RECESSED WALL-WASH FIXTURE CEILING 1.
BASE
AREA LIGHT POLE AND FIXTURE
CONCRETE
SEE DIAGRAM
FLOOD OR TRACK FIXTURE AS NOTED
CEILING/WALL MOUNTED EXIT LIGHT 1. 3. 8.
CEILING/
AS NOTED
A AUTOMATIC RELAY PACK
CEILING
SEE DIAGRAM. SPEC.
ABOVE
LOW VOLTAGE TRANSFORMER
T
PHOTO-ELECTRIC CONTROL
PTORK 2000AAS NOTED
DIGITAL DAYLIGHT SENSORCEILING
SEE DIAGRAM
SPECIFICATION
TIME CLOCK +5'-0" 2.
TC
UPPER OUTLET
SWITCH CONTROLLED
DUPLEX RECEPTACLE 9. 11.
AS NOTED
+16" OR
SIMPLEX RECEPTACLE 9. 11.
AS NOTED
+16" OR
SIMPLEX RECEPTACLE WITH USB OUTLET 9. 11.
AS NOTED
+16" OR
U
DUPLEX RECEPTACLE 9. 11.
AS NOTED
+16" OR
U
DUPLEX RECEPTACLE WITH USB OUTLET 9. 11.
AS NOTED
+16" OR
DUPLEX RECEPTACLE WITH CONTROL 9. 11.
AS NOTED
+16" OR
A
DUPLEX RECEPTACLE9.
ELECTRIC WATER COOLER RECEPTACLE
W
SEE DIAGRAM
WEATHERPROOF RECEPTACLE
WP
2. 9.
AS NOTED
+24" OR
ISOLATED GROUND RECEPTACLE
IG
9. 11.
AS NOTED
+16" OR
GROUND FAULT INTERRUPTER DUPLEX RECEPTACLE9. 11.
AS NOTED
+16" OR
DUPLEX RECEPTACLE EMERGENCY POWER (RED) 9. 11.
AS NOTED
+16" OR
FOURPLEX RECEPTACLE 9. 11.
AS NOTED
+16" OR
9. 11.
AS NOTED
+16" OR
GROUND FAULT INTERRUPTER FOURPLEX RECEPTACLE
FOURPLEX RECEPTACLE EMERGENCY POWER (RED) 9. 11.
AS NOTED
+16" OR
TVSS PROTECTED RECEPTACLE 9. 11.
AS NOTED
+16" OR
SPECIAL PURPOSE OUTLET10. WITH CAP. 11.
AS NOTED
+16" OR
CORD DROP SEE DIAGRAM
TOMBSTONE RECEPTACLE
PLUGMOLD
+46" OR
AS NOTED
TELEVISION OUTLET 11.
AS NOTED
+16" OR
POWER POLE
FTFLIP-TOP BOX 9.
JUNCTION BOX ('F' IN FLOOR)J
AS NOTED
MOTOR OUTLET
EQUIP.
TO SUIT
NON-FUSED DISCONNECT SWITCH
+5'-0"
5.
FUSED DISCONNECT SWITCH
F
+5'-0"
5.
MAGNETIC STARTER+5'-0"
7.
MAGNETIC STARTER / DISCONNECT COMBINATION +5'-0"
VARIABLE FREQUENCY DRIVEVFD
+6'-6"
PANEL BOARD
TOP AT
+6'-0"
MAIN DISTRIBUTION PANEL
TELEPHONE TERMINAL BOARD
GROUND BUS BAR
EQUIPMENT CABINET/RACK CIRCUIT TO 120V
BELL
+7'-6"
CHIME +7'-6"
ASPIRATING SMOKE DETECTION SYSTEM
V
MOUNT AS PER. MANCEILING
SMOKE DETECTOR
S
CEILING
SMOKE/CARBON MONOXIDE DETECTOR
SC
CEILING
CARBON MONOXIDE DETECTOR
C
CEILING
H
HEAT DETECTORCEILING
DUCT SMOKE DETECTOR
D
MTD. IN DUCT
DFIRE/SMOKE DAMPER
DOOR HOLDER
AS NOTED
S
F
FLOW SWITCH
S
T
TAMPER SWITCH
F
W
WATER FLOOD INDICATOR
O.S. & Y. VALVE
SEE DIAGRAM
RFIRE ALARM RELAY OR SECURITY RELAY
CMFIRE ALARM CONTROL MODULE
MMFIRE ALARM MONITOR MODULE
1
DSECURITY SYSTEM DOOR SWITCH
DOOR
JAMB
MOUNT AS PER. MAN
2
D SECURITY SYSTEM OVERHEAD DOOR SWITCHCEILING
ML
MAGNETIC SHEAR LOCK
I INFRARED SENSORAS NOTED
MOUNT AS PER. MAN
MSECURITY MOTION DETECTOR
GGLASS BREAK DETECTOR
CEILING
ES
ELECTRIC DOOR STRIKE 12.
EL
ELECTRIC DOOR LOCK 12.
R
ACCESS CONTROL SYSTEM, REQUEST TO EXIT
DOOR POSITION INDICATING SWITCH
LIGHT FIXTURE (LETTER DESIGNATES TYPE)
A
34
EQ
EQUIPMENT NUMBER
842 ARCHITECTURAL ROOM NUMBER
EPEMERGENCY LIGHTING CONTROL UNIT SEE DIAGRAM, SPEC.
CEILING
ABOVE
R RECEPTACLE SWITCH PACK
CEILING
SPEC.
ABOVE
LIGHT FIXTURE AS NOTED 1
EGRESS LIGHT FIXTURE AS NOTED UNSWITCHED
ELECTRICAL SYMBOL SCHEDULE
1. SEE FIXTURE SCHEDULE FOR TYPE, MOUNTING AND WATTAGE. 7. PROVIDE H.O.A. AND S.S. PUSHBUTTONS AS REQUIRED.
4. SUBSCRIPT KEYS SWITCH TO FIXTURES CONTROLLED.
8. DOUBLE ARROWS DENOTE A DOUBLE FACE UNIT.
3. REFER TO DRAWINGS FOR DIRECTIONAL ARROWS.
STANDARD MOUNTING HEIGHT UNLESS OTHERWISE NOTED ON PLANS
11. HEIGHT MEASURED TO BOTTOM OF THE BOX FROM FINISH FLOOR.
6. HEIGHT MEASURED TO TOP OF THE BOX FROM FINISHED FLOOR.
5. NEMA TYPE 'ND' NON-FUSED UNLESS NOTED 'F' (FUSED). USE 'HD' 480 V.
2. HEIGHT MEASURED TO CENTER LINE OF THE BOX FROM THE FINISH FLOOR.
9. COORDINATE WITH MILLWORK SHOP DRAWINGS AND ELEVATIONS FOR HEIGHT.
10. SUBSCRIPT DENOTES NEMA CONFIGURATION.
SYMBOL
DESCRIPTION
MOUNTING
HEIGHT
NOTESSYMBOL
DESCRIPTION
MOUNTING
HEIGHT
NOTES
* TYPICAL SYMBOL SCHEDULE. SOME SYMBOLS MAY NOT BE USED IN
THIS SET OF DRAWINGS.
12. COORDINATE WITH DOOR HARDWARE SUPPLIER.
FIRE ALARM SIGNAL HORN/STROBEH
+8'-0"
6.
FIRE ALARM SIGNAL SPEAKER/STROBE
E+8'-0"
6.
SFIRE ALARM STROBE
+8'-0"
6.
KFIRE ALARM SPEAKER ONLY
+8'-0"
6.
B
FIRE ALARM SIGNAL STROBE WITH
CEILING
MOUNT AS PER. MAN
BLUE COLORED LENS (CO VISUAL ALARM)
+8'-0"/
CONCEALED FIRE ALARM SIGNAL HORN/STROBE WALL
+8'-0"
H
6.
CONCEALED FIRE ALARM SIGNAL SPEAKER/STROBE WALL
+8'-0"
E
6.
CONCEALED FIRE ALARM SIGNAL STROBE WALLS
+8'-0" 6.
CONCEALED FIRE ALARM SIGNAL HORN/STROBE
HCEILING
CLG
CONCEALED FIRE ALARM SIGNAL SPEAKER/STROBEE
CEILINGCLG
CONCEALED FIRE ALARM SIGNAL STROBE
SCEILING
CLG
DUAL TECHNOLOGY CEILING MOUNTED OCCUPANCY
SENSOR (PROVIDE WITH ALL ROOM CONTROLLERS)
CEILING SEE DIAGRAM, SPEC.
DUAL TECHNOLOGY WALL MOUNTED OCCUPANCY SENSOR
(SUBSCIPT D=DIMMING AND DAY-LIGHT CONTROL)
+4'-0" SEE DIAGRAM, SPEC.
PPPOWER PACK SEE DIAGRAM, SPEC.
CEILING
ABOVE
CEILING
ABOVE
RC
NUMBER OF RELAYS, #E INDICATES EM ENABLED RC)
DIGITAL ROOM CONTROLLER (SUBSCRIPT INDICATES
X
SEE DIAGRAM. SPEC.
CORD REEL SEE DIAGRAM
PTPOKE THRU - SEE SCHEDULE SEE DIAGRAM, SPEC.
FLOOR
CAMERA - SEE SCHEDULE AS NOTED SEE DIAGRAM, SPEC.
DEVICE/EQUIPMENT (TEXT DESIGNATES TYPE) SEE SCHEDULE
X
S
x
SINGLE POLE SWITCH+4'-0"
4. 6.
3
S
THREE-WAY SWITCH+4'-0" 6.
S
4
FOUR-WAY SWITCH+4'-0" 6.
S
K
KEY OPERATED SWITCH+4'-0" 6.
S
P
SWITCH WITH PILOT LIGHT +4'-0" 6.
VARIABLE INTENSITY SWITCH
+4'-0" 6.
S
D
TIMER SWITCH +4'-0" 6.
S
TM
MOMENTARY CONTACT SWITCH, CENTER POSITION OFF
S
+4'-0" 6.
LOW VOLTAGE WALL STATION (SUBSCRIPT INDICATES
+4'-0" 6.
CONFIGURATION & CONTROL SEQUENCE) SEE DIAGRAMX
CALL SWITCH
+4'-0"
6.
FBFLOOR BOX - SEE SCHEDULE SEE DIAGRAM, SPEC.
FLOOR
PUSHBUTTON +4'-0" 6.
MANUAL STARTER THERMAL OVERLOAD SWITCH WITH PILOT LIGHT
S
T
+4'-0" 6.
FIRE ALARM MANUAL STATION
F
+4'-0" 6.
TWZTWO-WAY COMMUNICATION SYSTEM ANNUNCIATOR PANEL +4'-0" 6.
TWTWO-WAY COMMUNICATION CALL STATION +4'-0" 6.
D
DURESS PUSHBUTTON
+4'-0" 6.
CRACCESS CONTROL CARD READER +4'-0" 6.
BRACCESS CONTROL BIOMETRIC READER +4'-0" 6.
A
SECURITY SYSTEM KEYED ACCESS SWITCH +4'-0" 6.
K
SECURITY SYSTEM KEYED PAD +4'-0" 6.
MOUNT AS PER. MAN
PSECURITY SYSTEM POP-IT
CLOCK OUTLETC
+7'-6" 8.
DP
FLAT PANEL DISPLAY WALL BOX, TVSS RECEPT.,
AS NOTED
SPEC. 26 2726
SEE DIAGRAM &
DATA AND OTHER DEVICES, REFER TO DIAGRAMS
CPCEILING PROJECTION SYSTEM CEILING BOX
AND SPEC.
SEE DIAGRAM
CEILING
ABOVE
9. 11. 13.
AS NOTED
+16" OR
AV DATA OUTLET (SEE SPECIFICATION)
9. 11.
AS NOTED
+16" OR
DATA OUTLET W/MORE THAN (3) CABLES (SEE SPEC)X
9. 11.
AS NOTED
+16" OR
DATA OUTLET W/(3) CABLES (SEE SPECIFICATION)
9. 11.
AS NOTED
+16" OR
DATA OUTLET W/(2) CABLES (SEE SPECIFICATION)
DATA OUTLET W/(1) CABLE (SEE SPECIFICATION)
9. 11.
AS NOTED
+16" OR
WIRELESS ACCESS POINT, W/(2) CABLES (SEE SPEC)
CEILING
GENERAL NOTES
MAXIMUM LENGTH
<70 MIN. #12 AWG
70 - 115
115 - 170
170 - 270
20 AMP MINIMUM BRANCH CIRCUIT CONDUCTOR SIZING
BRANCH CIRCUIT VOLTAGE
CONDUCTOR LENGTH (FT) 120 VOLT 277 VOLT
271 - 380
>380
MIN. #12 AWG
MIN. #10 AWG MIN. #12 AWG
MIN. #8 AWG MIN. #10 AWG
MIN. #6 AWG MIN. #8 AWG
NOTE B MIN. #8 AWG
NOTE B NOTE B
THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR CONTACTING THE SENSOR MANUFACTURER
FOR PROPER PLACEMENT AND ADJUSTMENT OF OCCUPANCY SENSORS.
EACH ZONE SHALL HAVE COVERAGE BY OCCUPANCY SENSOR SUCH THAT NO BLIND SPOT EXIST.
UPON COMPLETION OF THE INSTALLATION, THE SYSTEM SHALL BE COMPLETELY COMMISSIONED BY THE
MANUFACTURER'S FACTORY AUTHORIZED TECHNICIAN WHO WILL VERIFY ALL ADJUSTMENTS AND SENSOR
PLACEMENT TO ENSURE A TROUBLE FREE INSTALLATION.
THE LOCATION AND QUANTITIES OF SENSORS SHOWN ON THE DRAWINGS ARE DIAGRAMMATIC AND INDICATE
ONLY THE ROOMS WHICH ARE TO BE PROVIDED WITH SENSORS. THE ELECTRICAL CONTRACTOR SHALL
PROVIDE ADDITIONAL SENSORS IF REQUIRED TO PROPERLY COVER THE RESPECTIVE ROOM.
PROVIDE OCCUPANCY SENSOR WITH AN ADDITIONAL SET OF DRY CONTACTS FOR HVAC CONTROL AT EACH
VAV BOX LOCATION. COORDINATE WITH MECHANICAL DRAWINGS AND THE MECHANICAL CONTRACTOR FOR
EXACT LOCATIONS.
1.
2.
3.
4.
5.
SENSOR GENERAL NOTES
ABBREV.
# NUMBER
AC ALTERNATING CURRENT
A.F.F. ABOVE FINISH FLOOR
AIC AMPS INTERRUPTING CAPACITY
AM AMPS METER
AMP AMPERE
ANN ANNUNCIATOR
ATS AUTOMATIC TRANSFER SWITCH
AUX AUXILIARY
AWG AMERICAN WIRE GAUGE
BC BARE COPPER
BFG BELOW FINISH GRADE
C CONDUIT
CAB CABINET
CATB COMMUNITY ANTENNA TELEVISION
CATV CABLE TELEVISION
CKT CIRCUIT
CLG CEILING
CNTR CONTRACTOR
C.O. CONDUIT ONLY
CRT COMPUTER TERMINAL
CT CURRENT TRANSFORMER
CU COPPER
C/W COMPLETE WITH
DB DECIBEL
DC DIRECT CURRENT
DWG DRAWING
(E) EXISTING
EC EMPTY CONDUIT
EG EMERGENCY GENERATOR
EMT ELECTRICAL METALLIC TUBING
EX EXPLOSION PROOF
FACP FIRE ALARM CONTROL PANEL
FC FOOT CANDLE
FT FOOT
GFI GROUND FAULT INTERRUPTER
GND GROUND
GRC GALVANIZED RIGID CONDUIT
HP HORSE POWER
HZ HERTZ
IG ISOLATED GROUND
IMC INTERMEDIATE METALLIC CONDUIT
IN INCH
J-BOX JUNCTION BOX
KV KILOVOLT
KVA KILOVOLT AMPERES
KVAR KILOVARS
KW KILOWATT
LRA LOCKED ROTOR AMPS
LTG LIGHTING
MNF MANUFACTURER
MATV MASTER ANTENNA TELEVISION
MAX MAXIMUM
MB MAIN BUS
MCC MOTOR CONTROL CENTER
MCM 1000 CIRCULAR MILLS
MH MANHOLE
MIC MICROPHONE
MIN MINIMUM
MTG MOUNTING
MTR MOTOR
N/A NOT APPLICABLE
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECT. MANUFAC. ASSOC.
NFC NATIONAL FIRE CODE
NFPA NATIONAL FIRE PROTECTION ASSOC.
N.I.C. NOT IN CONTRACT
NO NORMALLY OPENED
NTS NOT TO SCALE
OS & Y OUTSIDE SCREW & YOKE
PB PUSHBUTTON
PF POWER FACTOR
PFR PHASE FAILURE RELAY
PNL PANEL
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE CONDUIT
(R) RELOCATE
RECEP RECEPTACLE
REQ REQUIREMENT
RLA RATED LOAD AMPS
RMS ROOT MEAN SQUARE
SE SERVICE ENTRANCE
SPEC SPECIFICATIONS
SPKR SPEAKER
SS SELECTOR SWITCH
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
TTB TELEPHONE TERMINAL BOARD
TTC TELEPHONE TERMINAL CABINET
TV TELEVISION
TYP TYPICAL
UG UNDERGROUND
UPS UNINTERRUPTED POWER SUPPLY
V VOLT (KV-KILOVOLT)
VA/R VOLT-AMPS/REACTIVE
VM VOLT METER
W WATTS
W/ WITH
WH WATTHOUR METER
W/O WITHOUT
WP WEATHERPROOF
XFMR TRANSFORMER
XFMR SW TRANSFER SWITCH
XP EXPLOSION PROOF
1P SINGLE-PHASE
2P TWO-POLE
3P THREE-POLE
4P FOUR-POLE
Ø PHASE
DESCRIPTION ABBREV. DESCRIPTION
ABBREVIATIONS INDEX
E001 - SYMBOLS, SCHEDULES AND NOTES
E101 - ELECTRICAL PLAN
INDEX OF ELECTRICAL DRAWINGS
![Page 7: MSCI | Merrill Sheriff Constructionmscibuild.com/wp-content/uploads/2020/01/20KP16... · 1/20/2020 · psecurity system pop-it mount as per. man cclock outlet +7'-6"8. dp flat panel](https://reader034.vdocuments.us/reader034/viewer/2022050602/5fa98617471635744231287d/html5/thumbnails/7.jpg)
UP
COPPER HILLS HIGH SCHOOL NEW
EXISTINGLOBBYCH101A
SECUREVESTIBLECH101
EXISTINGVESTIBLECH100A
EXISTINGVESTIBLECH100B
EXISTINGADMINISTRATION
CH102
EXISTINGCOMMONSCH103
CR
T5
T2
T3
T1
T4
UP
HERRIMAN HIGH SCHOOL NEW
EXISTINGLOBBYH101A
SECUREVESTIBLE
H101
EXISTINGADMINISTRATION
H102
EXISTINGVESTIBLEH100A
EXISTINGVESTIBLEH100B
CR
T5
T2
T3
T1
T4
Project For
Jordan School District
7905 South Redwood Road
West Jordan, Utah 84088
The
Jordan School
District
Board of
Education
Secure Entries
N a y l o rW e n t w o r t hL u n dA r c h i t e c t s
Sheet Title
NWL Project
Number
Stamp
Project Issue Date
Project Phase
Revision Schedule
136.014
No. Description Date
Bid Documents
January 21, 2020
Sheet
Number
5445 New Bingham Hwy
West Jordan, Utah 84081
Copper Hills
High School
ã 2020 BNACONSULTING
635 South State StreetSalt Lake City, Utah 84111
P:801.532.2196F:801.532.2305
www.bnaconsulting.comBNACONSULTINGSALT LAKE ST.GEORGE
11917 S. Mustang Trail Way
Herriman, Utah 84096
Herriman
High School
SHEET KEYNOTES
T1 PROVIDE AN LNL RK-AL400 ULX (OR DISTRICT STANDARD) POWER SUPPLY.
T2 PROVIDE CABLING TO ELECTRIFIED HARDWARE, DEVICES AND ACCESS CONTROL PANEL. INSTALL
CONDUIT IN STRUCTURE OF THE WINDOW FRAMING. ACCESS CONTROL PANEL IS LOCATED
APPROXIMATELY 150' TO THE LEFT.
T3 PROVIDE PROXIMITY CARD READER.
T4 CHECK PANEL 'BL18' FOR AN AVAILABLE CIRCUIT BREAKER. PROVIDE 2 #12 THWN AND 1 #12 GROUND
AND TERMINATE.
T5 PROVIDE A NEW EXIT LIGHT FIXTURE. PROVIDE A DIE-CAST ALUMINUM SLIM PROFILE LED EXIT SIGN.
MATTE BLACK WITH BRUSHED ALUMINUM FACE, AC, UNIVERSAL MOUNT FIXTURE (BEGHELLI
FME-HT-LG1-M, OR EQUAL).
E101
ELECTRICAL
PLAN