COnTACTORS MOTOR PROTeCTiOn SwiTCHeS
��
• Versions: -MS25–withthermalandmagneticreleases -MST25–withathermalrelease -MS20-withthermalandmagneticreleasesforsingle-phaseconsumers -MST20–withathermaloverloadreleaseforsinglephaseconsumers• Manualcontrol: -START,STOP,push-buttons -Testofreleasefunction(TEST)• Automaticswitch-offwiththermalormagneticrelease• Controlwithunder-voltagereleaseorshuntrelease• Anauxiliaryswitchforsidemountingorflushmountingusedfor indicatingtheswitchingstate• ON/OFF,push-buttonspositionunequivocallyindicatestheswitching positionofmaincircuitcontacts
• Contactmaterial: -Resistanttocontactweld -Enableslowcontactheating• Isolatingdistancebetweencontacts:4.5mmpercontactplace• Connectionofarigidorflexibleconductor• Assemblyto35mmwidemountingrailinaccordancewithEN60715orfixingwithtwoscrews• Verticalorhorizontaloperationposition
GE
NE
RA
L
Standards IEC/EN60947-2,IEC/EN60947-4-1,IEC/EN60947-5-1,IEC/EN60204,UL508,CSA22.2No.14
Approvals UL,SEMKO
Climaticclass constantdampheatacc.toIEC60068-2-78cyclicdampheatacc.toIEC60068-2-30
Degreeofprotection IP20,afterterminalscoveringIP20
Ambienttemperature °C -25…+60
Storagetemperature °C -25…+70
Temperaturerangeofthermalcompensationforoverloadrelease
°C -5…+40
Mechanicalandelectricalendurance op.c. 100,000
Shockresistanceacc.toIEC68-2-27 g 20
Vibrationresistanceacc.toIEC68-2-6 5gatf=5…150Hz
Overvoltagecategory/pollutiondegree III/3
Ratedinsulationvoltage Ui V 690
Ratedimpulsewithstandvoltage Uimp kV 6
Weight kg 0.252
MS25, MST25, MS20, MST20
TECHNICALDATA
MOTOR PROTeCTiOn SwiTCHeS
�0
MOTOR PROTeCTiOn SwiTCHeS
Standardmotorpower Settingrange
Single-phase Three-phase
220V230V240V
220V230V240V
380V400V415V
440V 500V 660V690V
kW A
0.02 0.06 0.1…0.16
0.06 0.06 0.06 0.09 0.16…0.25
0.06 0.09 0.12 0.12 0.18 0.25…0.4
0.09 0.12 0.18 0.25 0.25 0.4…0.63
0.06…0.09 0.09…0.12 0.18…0.25 0.25 0.37 0.37…0.55 0.63…1
0.12 0.18…0.25 0.37…0.55 0.37…0.55 0.55…0.8 0.75…1.1 1…1.6
0.18…0.25 0.37 0.75…1.1 0.75…1.1 1.1 1.5 1.6…2.5
0.37 0.55…0.8 1.1…1.5 1.5 1.5…2.2 2.2…3 2.5…4
0.55…0.75 1.1…1.5 2.2…2.5 2.2…3 3 4 4…6.3
1.1…1.5 1.5…2.5 3…4 4…5 4…5.5 5.5…7.5 6.3…10
2.2 3…4 5…7.5 5.5…9 7.5…9 11 10…16
3 5.5 9 11 11…12.5 15 16…20
5.5…7.5 11…12.5 12.5 15 18.5 20…25
MA
INC
IRC
UIT
Designationofconnectionterminals
1−L1;3−L2;5−L3;2−T1;4−T2;6−T3
Terminalcapacity rigidS mm2
0.75…6
flexible 0.75…4
Screwwithself-liftingclamp,
protectedagainstfallingout
Screwhead PZ2
Tighteningtorque Nm 1.8
Max.operationalvoltage Ue V 690
Settingrange
A
0.1−0.16(onlyMS25);0.16−0.25(onlyMS25);0.25−0.4;0.4−0.63;0.63−1;1−1.6;1.6−2.5;2.5−4;
4−6.3;6.3−10;10−16;16−20;20-25
No.ofpoles 3
Operatingcurrentofthermaloverloadrelease
I1.05Ir<I≤1.20Ir
Ir….setvalue
Sensitivitytophasefailure yes
Operatingcurrentofmagneticoverloadrelease
I11In<I≤13In±20%In…uppersettinglimit
PowerdissipationonpoleatloadwithIn
P W2−2.5
Utilizationcategory acc.toIEC/EN60947-4-1 AC-3
acc.toIEC/EN60947-2 A
Tripclassacc.toIEC/EN60947-4-1 10A
MS25, MST25, MS20, MST20
TECHNICALDATA
SWITCHSELECTIONFORMOTORPROTECTION
MOTOR PROTeCTiOn SwiTCHeS MOTOR PROTeCTiOn SwiTCHeS
��
Type Operatingcurrentof
short-circuitrelease
(A)
Ratedultimateshort-circuitbreakingcapacityIcu(kA) Max.back-upfuse,ifIcp>Icu
(gL) (A)
230V 400V 500V 690V 230V 400V 500V 690V
Icu Icu Icu Icu
MS25−0.16 2 50 50 50 50
Noback-upfuserequired
MS25−0.25 3 50 50 50 50
MS25−0.4 5 50 50 50 50
MS25−0.63 8 50 50 50 50
MS25−1 12 50 50 50 50
MS25−1.6 20 50 50 50 50
MS25−2.5 33 50 50 3 2.5 25 20
MS25−4 44 50 50 3 2.5 35 25
MS25−6.3 75 50 50 3 2.5 50 35
MS25−10 120 50 6 3 2.5 80 50 35
MS25−16 160 6 4 2.5 2 80 80 63 35
MS25−20 230 6 4 2.5 2 80 80 63 50
MS25−25 270 6 4 2.5 2 80 80 63 50
Type Max.back-upfuse
Ue<400VgL(A)
MS25−0.4 1
MS25−0.63 2
MS25−1 2
MS25−1.6 4
MS25−2.5 6
MS25−4 16
MS25−6.3 20
MS25−10 25
MS25−16 35
MS25−20 50
MS25−25 50
MS25motorprotectionswitches,ratedultimateshort-circuitbreakingcapacityIcuandmax.back-upfusesifprospectiveshort-circuitcurrentIcpexceedsIcu:
MST25motorprotectionswitchesandmax.back-upfusesforshort-circuitprotection:
MS25, MST25, MS20, MST20
MOTOR PROTeCTiOn SwiTCHeS
��
MOTOR PROTeCTiOn SwiTCHeS
AuxiliaryswitchforlateralmountingPS
PS11–withonemakeandonebreakcontactPS10–withonemakecontactPS01–withonebreakcontactPS20–withtwomakecontacts
Under-voltagereleaseUShuntreleaseA
EnclosureIP41/55O-41/55
FrontplateIP41/55CP-41/55
MS25orMST25withallaccessoriescanbebuiltintoanenclosureorafrontplate.
O-41/55CP-41/55
Emergencystoppush-buttonNAT.Itisalsoavailablewithakey-lock.
Ratedinsulationvoltage Ui V 500
Thermalcurrent Ith A 6
RatedoperationalcurrentatAC-15
230V
Ie A
3.5
400V 2
500V 1.5
Terminalcapacity S mm2 0.75…2.5
Tighteningtorque Nm 1
Controlvoltages Uc V 24…600
Ratedfrequency f Hz 50or60
Trip-indieatingauxiliaryswitchRSand
auxiliaryflush-typeswitchPSRS10–withonemakecontactRS01–withonebreakcontactPSV11–withonemakeandonebreakcontact
Ratedinsulationvoltage Ui V 500
Thermalcurrent Ith A 6
RS Ratedoperational
currentatAC-15
230V
Ie A
3.5
400V 2
500V 1.5
RS
V
RatedoperationalcurrentatAC-15
230V
Ie A
3.5
400V 2
500V 1.5
Terminalcapacity S mm2 0.75…2.5
Tighteningtorque Nm 1
MS25, MST25, MS20, MST20
ACCESSORIES
ENCLOSURES
MOTOR PROTeCTiOn SwiTCHeS MOTOR PROTeCTiOn SwiTCHeS
��
PadlockingfeatureZ
Push-buttondiaphragmM
ThemanufactureralsosuppliesanenclosureandafrontplatewithdegreeofprotectionIP55(O-55,CP-55);inthiscasethediaphragmisalreadymounted.However,itshouldberemovedifapadlockingfeatureoranemergencystopbush-buttonisbuilt-in.
NeutrallinkNLOneN/PEneutrallinkisusuallybuilt intheenclosure0-41/55orCP-41/55.Aplaceforanadditional neutral link is alsoavailable.
SignallampSS…230,240,400VB-white,R-red,Z-green
Connectiondiagram
1-pole 2-pole 3-pole
DIMENSIONS
MS25,MST25,MS20,MST20
O-41/55 CP-41/55
ORDERINGDATAMS25withthesettingrange2.5–4.0A:MS25-4Thesameswitchwithunder-voltagereleaseforcontrolvoltage380VwithanauxiliaryswitchwithtwoNOcontacts,builtintheenclosure,withanemergencystoppush-buttonandagreensignallampfor230V:MS25–4/U380/PS20/0-41/NAT/SSz230
MS25, MST25, MS20, MST20
MOTOR PROTeCTiOn SwiTCHeS
��
MOTOR PROTeCTiOn SwiTCHeS
• Versions: -MS32–withthermalandmagneticreleases -MSB32–withathermalrelease• Manualcontrol: -START,STOP,push-buttons–withareleasestateindication -Testofreleasefunction(TEST)• Automaticswitch-offatover-currentwiththermalormagneticrelease• Controlwithunder-voltagereleaseorshuntrelease• Anauxiliaryswitchforsidemountingorflushmountingusedforindicatingthe switchingstate• Indicationofreleasewithtripindicatingauxiliaryswitch• ON/OFFbuttonspositionunequivocallyindicatesswitchingpositionofmain circuitcontacts• Contactmaterial -Resistanttocontactweld -Enableslowcontactheating
• Isolatingdistancebetweencontacts:4.5mmpercontactplace• Connectionofarigidorflexibleconductor• Assemblyto35mmwidemountingrailincompliancewithEN60715• Verticalorhorizontaloperationposition
GE
NE
RA
L
Standards IEC/EN60947-2,IEC/EN60947-4-1,IEC/EN60947-5-1,IEC/EN60204,UL508,CSA22.2No.14
Approvals UL
Climaticclass constantdampheatacc.toIEC60068-2-78cyclicdampheatacc.toIEC60068-2-30
Degreeofprotection IP20,afterterminalscoveringIP40
Ambienttemperature °C -25…+60
Storagetemperature °C -25…+70
Temperaturerangeofthermalcompensationforoverloadrelease
°C -5…+40
Mechanicalandelectricalendurance op.c. 100,000
Shockresistanceacc.toIEC68-2-27 g 20
Vibrationresistanceacc.toIEC68-2-6 5gatf=5…150Hz
Overvoltagecategory/pollutiondegree III/3
Ratedinsulationvoltage Ui V 690
Ratedimpulsewithstandvoltage Uimp kV 6
Weight kg 0.279
MA
INC
IRC
UIT
Designationofconnectionterminals 1−L1;3−L2;5−L3;2−T1;4−T2;6−T3
Terminalcapacity rigidS mm2
0.75…10
flexible 0.75…6
Screwwithself-liftingclamp,
protectedagainstdropout
Screwhead PZ2
Tighteningtorque Nm 2.0
MS32, MSB32
TECHNICALDATA
MOTOR PROTeCTiOn SwiTCHeS MOTOR PROTeCTiOn SwiTCHeS
��
MA
INC
IRC
UIT
Max.operationalvoltage Ue V MS32:690;MSB32:400
Settingrange
A
0.1−0.16(onlyMS32);0.16−0.25(onlyMS32);0.25−0.4;0.4−0.63;0.63−1;1−1.6;
1.6−2.5;2.5−4;4−6.3;6.3−10;9−14;13−18;17−23;20−27;25-32
No.ofpoles 3
Operatingcurrentofthermaloverloadrelease
I1.05Ir<I≤1.20Ir
Ir….setvalue
Sensitivitytophasefailure yes
Operatingcurrentofmagneticoverloadrelease
I11In<I≤13In±20%In…uppersettinglimit
Powerdissipationonpoleatuppersettinglimit
P W 2−2.5
Utilizationcategory acc.toIEC/EN60947-4-1 AC-3
acc.toIEC/EN60947-2 A
Tripclassacc.toIEC/EN60947-4-1 10
Standardmotorpowers Settingrange
Single-phase Three-phase
220V230V240V
220V230V240V
380V400V415V
440V 500V 660V690V
kW A
0.06 0.1…0.16
0.06 0.06 0.06...0.9 0.06...0.12 0.16…0.25
0.06 0.09 0.12 0.09...0.12 0.18 0.25…0.4
0.09 0.12...0.18 0.18 0.18 0.25 0.4…0.63
0.06…0.09 0.09…0.12 0.18…0.25 0.25...0.37 0.25...0.37 0.37…0.55 0.63…1
0.12 0.18…0.25 0.37…0.55 0.37…0.55 0.55…0.75 0.75…1.1 1…1.6
0.18…0.25 0.37 0.75 0.75…1.1 1.1 1.5 1.6…2.5
0.37 0.55…0.75 1.1…1.5 1.5 1.5…2.2 2.2…3 2.5…4
0.55…0.75 1.1…1.5 2.2 2.2…3 2.2...3 4 4…6.3
1.1…1.5 1.5…2.2 3…4 4 4…5.5 5.5…7.5 6.3…10
2.2 2.2…3 5.5 5.5…7.5 5.5…7.5 9...11 9…14
3 4 7.5 7.5...9 9...11 15 13…18
5.5 9...11 11 11 15...18.5 17…23
5.5...7.5 11 11 15 18.5...22 20...27
7.5 15 15 18.5 22 25...32
MS32, MSB32
TECHNICALDATA
SWITCHSELECTIONFORMOTORPROTECTION
MOTOR PROTeCTiOn SwiTCHeS
��
MOTOR PROTeCTiOn SwiTCHeS
Type Operatingcurrentof
short-circuitrelease
(A)
Ratedultimateshort-circuitbreakingcapacityIcu ,Ics(kA)
Max.back-upfuse,ifIcp>Icu(gL)(A)
230V 400V 500V 690V 230V 400V 500V 690V
Icu Ics Icu Ics Icu Ics Icu Ics
MS32−0.16 2 100 100 100 100 100 100 100 100
Noback-upfuserequired
MS32−0.25 3 100 100 100 100 100 100 100 100
MS32−0.4 5 100 100 100 100 100 100 100 100
MS32−0.63 8 100 100 100 100 100 100 100 100
MS32−1 12 100 100 100 100 100 100 100 100
MS32−1.6 20 100 100 100 100 100 100 100 100
MS32−2.5 33 100 100 100 100 100 100 5 5 16
MS32−4 44 100 100 100 100 100 100 3 3 25
MS32−6.3 75 100 100 100 100 6 4.5 3 2 35 35
MS32−10 120 100 100 100 100 6 4.5 3 2 50 35
MS32−14 160 25 12.5 25 12.5 6 4.5 3 2 80 63 50 50
MS32−18 230 25 12.5 25 12.5 6 4.5 3 2 80 63 50 50
MS32−23 270 25 12.5 25 12.5 4 3 3 2 80 80 50 50
MS32−27 360 25 12.5 25 12.5 4 3 3 2 80 80 50 50
MS32−32 400 25 12.5 25 12.5 4 3 3 2 80 80 50 50
Type Max.back-upfuse
Ue<400VgL(A)
MSB32−0.4 2
MSB32−0.63 2
MSB32−1 4
MSB32−1.6 6
MSB32−2.5 6
MSB32−4 10
MSB32−6.3 16
MSB32−10 25
MSB32−14 25
MSB32−18 35
MSB32−23 35
MSB32−27 50
MSB32−32 50
MS32motorprotectionswitches,ratedultimateandserviceshort-circuitbreakingcapacityIcuandIcs,andmax.back-upfusesifshortcircuitcurrentIcpexceedsIcu:
MSB32motorprotectionswitchesandmax.back-upfusesforshort-circuitprotection:
MS32, MSB32
MOTOR PROTeCTiOn SwiTCHeS MOTOR PROTeCTiOn SwiTCHeS
��
EnclosureIP41/55HO-41/55 FrameIP41/55FP-41/55 FrontplateIP41/55P-41/55
Emergencystoppush-buttonEavailablealsowithakey-lock.
PadlockingfeatureHZ
Push-buttondiaphragmMThemanufactureralsosuppliesanenclosure,aframeandafrontplatewith degreeofprotectionIP55(HO-55,FP-55,P-55)wherethediaphragmisalreadyinserted.However,itshouldbe removedifapadlockingfeatureoranemergencystopbush-buttonisbuilt-in.
NeutrallinkNLOneN/PEneutrallinkisalreadymountedintheenclosuresHO-41/55orframesFP-41/55.Aplaceforanadditionalneutrallinkisalsoprovided.
SignallampSS(B-white,R-red,Z-green)
AuxiliaryswitchHS
HS11–with1makeand1breakcontactHS10–with1makecontactHS20–with2makecontacts
AuxiliarycontactblockHSVTripindicatingcontact
blockHRSHSV10–with1makecontactHSV01–with1breakcontactHRS10–with1makecontactHRS01–with1breakcontact
PRIBOR
Ratedinsulationvoltage Ui V 500
Thermalcurrent Ith A 5
Electricalratingacc.toIEC/EN60947-5-1
B300
R300
Terminalcapacity S mm2 0.75…2.5
Tighteningtorque Nm 1
Ratedinsulationvoltage Ui V 300
Thermalcurrent Ith A 1
Electricalratingacc.toIEC/EN60947-5-1
B300
R150
Terminalcapacity S mm2 0.75…2.5
Tighteningtorque Nm 1
TheMS32orMSB32motorprotectivecircuitbreakerwithallaccessoriescanbebuiltinanenclosureorunderaframeandafrontplate
MS32, MSB32
ACCESSORIES
ACCESSORIESUSEDFORALLENCLOSURES
AUXILIARYSWITCHFORSIDEMOUNTINGHS,AUXILIARYCONTACTBLOCKHSV,TRIPINDICATINGCONTACTBLOCKHRS
MOTOR PROTeCTiOn SwiTCHeS
��
MOTOR PROTeCTiOn SwiTCHeS
1-pole 2-pole 3-pole
HO-41/55
MS32,MSB31Motorprotectionswitch
AuxiliaryswitchHS Under-voltagereleaseURShuntreleaseAR
SealingplatePP
Under-voltagereleaseUR ShuntreleaseAR
Controlvoltages Uc V 24…600
Ratedfrequency f Hz 50or60
Terminalcapacity S mm2 0.75…2.5
Tighteningtorque Nm 1
FP-41/55
MS32, MSB32
UNDER-VOLTAGERELEASEURANDSHUNTRELEASEAR
CONNECTIONDIAGRAM
DIMENSIONS
MOTOR PROTeCTiOn SwiTCHeS MOTOR PROTeCTiOn SwiTCHeS
��
MSK07,MSKNL9andMSKNL22adaptersareusedforconnectingamotorprotectionswitchwithacontactorformingasingle-unitstarterforquickassemblytoa35mmwidemountingrail(EN60715).
AdapterforconnectingMS32motorprotectionswitchwith
K07minicontactor
AdapterforconnectingMS32motorprotectionswitchwith
KNL9-KNL16contactor
AdapterforconnectingMS32motorprotectionswitchwith
KNL22,KNL30contactor
MS32...
MSK07
K07...
MS32...
MSKNL9
KNL9-KNL18...
MS32...
MSKNL22
KNL22KNL30...
COnneCTiOn BLOCKS
MiniATURe CiRCUiT BReAKeRS
�0
MiniATURe CiRCUiT BReAKeRS
•RI60isusedforover-current(overloadandshort-circuit)protectionofinstallationsanddevices,andasadisconnectorincaseof electricshock•RI60miniaturecircuitbreakersareprovidedwithtwospringsfor assemblytoa35mmwidemountingrail(EN60715).Thesprings enablesimpletakingoffirrespectiveofwhetherabusbaris positionedbeloworabove•Specialspringsareavailableforfixingminiaturecircuitbreakerswith twoM5screws•AhandlecanbesealedinONorOFFposition•Optionaloperationposition•DegreeofprotectionIP20;degreeofprotectionIP40after installationinadistributionbox•Additionalcolourindicationofthepositionofmaincontacts(red:contactclosed;green:contactsopen)Types
RI61 single-poleRI61N single-pole+neutralpoleRI61J single-pole(forDCcircuits)RI62 two-poleRI62J two-pole(forDCcircuits)RI63 three-poleRI63N three-pole+neutralpoleRI64 three-pole+neutralpole
AC DC
Standards IEC/EN60898,IEC/EN60947-2
Approvals VDE
No.ofpoles 1,2,3,4,1+N,3+N 1.2
Trippingcharacteristic(IEC/EN60898) B,C,D C
Ratedvoltage Un V 230,230/400 -
RatedDCvoltageUn V
max.40–1polefort=15ms
440–2-pole220–1-pole
Ratedfrequency Hz 50/60 -
Ratedcurrent In A 0.5to631)
Short-circuitcapacity Icn kA 102) 4.5
Selectivityclass 3
Terminalcapacity CuS mm2
1.5…25
Al 2.5...25
Ambienttemperature °C −25…+55
Vibrationresistance 3g(8-10Hz)
1) Characteristics B, C, D: 0.5, 1, 2, 3, 4, 6, 8, 10, 13, 16, 20, 25, 32, 40, 50, 63 A2) Characteristic D: I
n = 63 A, short-circuit capacity I
cn = 6 kA
Ri 60
TECHNICALDATA
MiniATURe CiRCUiT BReAKeRS MiniATURe CiRCUiT BReAKeRS
��
•TheyareusedwithRI60miniaturecircuitbreakersandRV60disconnectionswitches(0.5modulewidth).•DeliveredasasingleunitorwithRI60orRV60;fixedtotheleftsidewithaspringorascrew.•Types: - PKJ,2PKJ–withoneortwochangeovercontacts - PKJ+SKJ–withausualchangeovercontactandachangeovercontactforindicationoftripping(trip indicatingauxiliarycontacts)
In>10AIn<10A
*Connectionoftwoauxiliarycontactsinseriesat220V
ratedcurrent In ratedcurrent In
itrip
pin
gti
me
t(s)
trip
pin
gti
me
t(s)
Ri 60
AUXILIARYANDSIGNALCONTACTS
Standards IEC/EN60947-5-1 Ratedinsulationvoltage Ui V 400 Ratedoperationalvoltage Ue V 230 Ratedthermalcurrent Ith A 16 Ratedoperationalcurrent AC-15 Ie A 3(Ue=230V) DC-13 0.5(Ue=110V)* Terminalcapacity S mm2 0.5...2.5
TRIPPINGCHARACTERISTICB,C,D(EN60898)
TECHNICALDATA
MiniATURe CiRCUiT BReAKeRS
��
MiniATURe CiRCUiT BReAKeRS
•UsedwithRI60miniaturecircuitbreakersandRV60disconnectionswitches.•Enablesremoteswitch-off.•AvailableasasingleunitortogetherwithRI60orRV60;itisfixedtotherightsidewithaspringorascrew.
Busbar–universal (forone-polecircuitbreakersandone-polecircuitbreakerswithanauxiliaryswitch)
DesignationLength(m)Cross-section(mm2)G-1L-210/12iso0.21 12G-1L-1000/12iso1 12G-2L-1000/10 1 12
Busbar–fork-type,3-phase (forthree-polecircuitbreakersandone-polecircuitbreakersinthree-phasecircuits)
DesignationLength(m)Cross-section(mm2)G-3L-1000/10C1 10G-3L-1000/16C1 16G-4L-1000/16 1 16
Endcaps(forthree-phasebusbars)
DesignationCross-section(mm2)EK-C-3/1010EK-C-2+3/1616
TECHNICALDATAStandards IEC/EN60947-1
Controlvoltages ACUn V
12,24,48,60,110,230,400
DC 24,48,110
Limitsofoperationalvoltage
% 70…110
Max.trippingcurrent(atcoilvoltage)
ACA(V)
6(12);2.8(24);0.8(48);0.9(60);0.5(110);0.6(230);0.5(400)
DC 3(24);2(48);0.6(110)
Ratedfrequency Hz 50
Trippingtime ms <50
Terminalcapacity S mm2 1.5…6
TECHNICALDATAStandards IEC/EN60947
Modulewidth 1
Controlvoltage Uc V 230,400
Mechanicalendurance op.c. 10,000
Terminalcapacity S mm2 0.5…6
Ri 60
SHUNTTRIPRELEASEVC
UNDERVOLTAGERELEASEPC60
ACCESSORIES
MiniATURe CiRCUiT BReAKeRS MiniATURe CiRCUiT BReAKeRS
��
Ri 60
CONNECTIONDIAGRAMANDDIMENSIONS
4-pole+N-conductor
1-pole+N-conductor
2-pole
4-pole
3-pole
2-pole
1-pole
AC DC AUXILIARYCONTACTS
RI60
9052.23517.5 6.5 44
60
71
45
12 14 1
211 11 2
1
95
96 98 12 14
PKJ 2PKJ,PKJ+SKJ
PC6059
59
4317.5
84 45
MiniATURe CiRCUiT BReAKeRS
��
MiniATURe CiRCUiT BReAKeRS
• Theyareusedforprotectinghouseandindustrial installations.• RI120miniaturecircuitbreakersareprovidedwithtwo springsforassemblytoa35mmwidemountingrail inaccordancewithEN60715.Thespringsenable simpletakingoffirrespectiveofwhetherabusbar ispositionedbeloworabove.• AhandlecanbesealedinONorOFFposition.• Optionaloperationposition.• DegreeofprotectionIP20;degreeofprotection IP40afterinstallationinadistributionbox.
Ri120
TECHNICALDATA
Standards IEC/EN60898
No.ofpoles 1,2,3,4,1+N;3+N
Trippingcharacteristic B,C
Ratedvoltage Un V 230/400
Ratedfrequency f Hz 50-60
Ratedcurrent In A 80,100,125
Short-circuitbreakingcapacity kA 10
Selectivityclass 3
Ambienttemperature °C -5...+40
Terminalcapacity S mm2 2.5...50
Accessories ShunttripreleaseVC
MiniATURe CiRCUiT BReAKeRS MiniATURe CiRCUiT BReAKeRS
��
trip
pin
gti
me
ratedcurrent xIn
t(s)
Ri120
DIMENSIONS
TRIPPINGCHARACTERISTICB,C(EN60898)
2727
100
100
100
100
2727
7878 7878 100
45 94
27
44
60
68
��
inSTALLATiOn BUiLT-in deViCe MiniATURe CiRCUiT BReAKeRS
TECHNICALDATA Standards IEC/EN60947-3 No.ofpoles 1,2,3,4,1+N,3+N Ratedvoltage UnV 230/400 Ratedfrequency fHz 50/60 Ratedcurrent InA 25,63 Utilizationcategory AC-22A Ratedconditionalshort-circuitcurrent 3(RV6063Awith63AgGback-upfuse) kA 6(RV6063Awith35AgGback-upfuse) 10(RV6025Awith25AgGback-upfuse) Terminalcapacity Smm2 seepage70 Ambienttemperature °C -25…+55 Vibrationresistance 4g(from8to10Hz) Accessories SeeaccessoriesforRI60miniaturecircuitbreaker
•Theyareusedasmainswitchesinhousedistributionboxesoras switchesforindividualelectriccircuits.•AhandlecanbesealedinONorOFFposition.•Assemblyto35mmwidemountingrailinaccordancewithEN60715.•Optionaloperationposition.•DegreeofprotectionIP20;degreeofprotectionIP40afterinstallationin adistributionbox.•Additionalcolourindicationsofthepositionofmaincontacts(red:contactsclosed,green:contactsopen).•ExternaldimensionsofRV60andRV120disconnectionswitches. matchwithdimensionsofRI60orRI120miniaturecircuitbreakers.
TECHNICALDATA Standards IEC/EN60947-3 No.ofpoles 1,2,3,4,1+N,3+N Ratedvoltage Un V 230 Ratedfrequency f Hz 50/60 Ratedcurrent In A 125 Utilizationcategory AC-22 OperationalcurrentatAC-23 Ie A 40 Ratedconditionalshort-circuitcurrent kA 3(with100AgGback-upfuses) Terminalcapacity Smm2 50 Ambienttemperature °C -25…+55
•Assemblytoa35mmwidemountingrailinaccordancewithEN60715•Optionaloperationposition•DegreeofprotectionIP20,degreeofprotectionIP40afterinstallation inadistributionbox
RV 60, RV 120, RS
DISCONNECTIONSWITCHRV120
SIGNALLAMPRS
TECHNICALDATA Standards EN60947-5-1 Modulewidth 1 Ratedvoltage Un V 24,48,110,230 Lightsource HighcapacityLEDs Lightsourcecapacity W 0.8 Colours green–G,red–R;transparent–T;yellow-Y Terminalcapacity S mm2 0.75…6
DISCONNECTIONSWITCHRV60
inSTALLATiOn BUiLT-in deViCe MiniATURe CiRCUiT BReAKeRS
��
Numberofpoles 1+NTrippingcharacteristic B,C,DRatedcurrent A 2,6,10,16,20,25,32Ratedvoltage V 230Ratedfrequency Hz 50Ratedshort-circuitcapacitykA 4,5Terminalcapacity mm2 1-10Mountingto35mmwidemountingrailAssemblyaccordancewithEN60715Ambienttemperature °C -5...+40
TRIPPINGCHARACTERISTICS
Trip
pin
gti
me
Ratedcurrent xIn
t(s)
CdB3x
TECHNICALDATA
Changedratedvaluesregardingambienttemperature Ratedcurrent Ambienttemperature (A) -10°C 0°C 10°C 20°C 30°C 40°C 50°C 60°C 6 1.17 1.13 1.09 1.04 1 0.96 0.91 0.84 10 1.21 1.16 1.10 1.06 1 0.94 0.88 0.82 16 1.18 1.13 1.09 1.04 1 0.94 0.91 0.84 20 1.17 1.13 1.09 1.04 1 0.96 0.91 0.84 25 1.18 1.13 1.09 1.04 1 0.96 0.91 0.84 32 1.17 1.13 1.09 1.04 1 0.96 0.91 0.84
DIMENSIONSCONNECTION
DIAGRAM
ACCeSSORieS
��
ReSidUAL CURRenT CiRCUiT BReAKeRS
• Transparentorwhitedoor• AdditionalterminalsforPE-andN-conductors• No.ofmodulesfrom4to36• ProtectionclassII• DegreeofprotectionIP40
Type INO-4 INO-12 INO-18 INO-24 INO-36
IPO-4 IPO-12 IPO-24 IPO-36
Standards IEC60670-24
Ratedvoltage Un V 400
Max.powerdissipation INOW
12 22 22 24 26
IPO 14 22 24 26
No.ofmodules 4(+4) 12 18 24 36
PE-andN-conductorterminals 2x8 2x10 2x13 2x13 2x15
Ambienttemperature °C −20…+70
Dimensions INOmm
215x263x112 287x236x112 396x236x112 287x361x112 287x482x112
IPO 211x232x70 283x232x70 283x357x70 283x482x70
SURFACe MOUnTed (inO) And FLUSH MOUnTed (iPO) COMPACT diSTRiBUTiOn BOARdS
TECHNICALDATA
ACCeSSORieS ReSidUAL CURRenT CiRCUiT BReAKeRS
��
• Residualcurrentcircuitbreakersareusedforprotection againstindirectcontact,fireprotectionandadditional protectionagainstdirectcontact.• Theyaresuitableforisolation.• Nooverloadprotectionorshort-circuitprotectionisbuiltinRCCB.• RCCBsaremanufacturedintwoversions: -TypeA(markedNFI)–sensitivetoalternatingandpulsating dcresidualcurrents. -TypeAC(markedFI)–sensitivetoalternatingresidual currentsofsineform.• Assemblytoa35mmwidemountingrailinaccordancewith EN60715.• Optionaloperationposition.• DegreeofprotectionIP20,degreeofprotectionIP40after installationinadistributionbox.
• Additionalcolourdisplayofthepositionofmaincontacts(red:contactsclosed,green:contactsopen).• Aterminalshapepreventsconnectionofaconductoroutsidetheconnectionarea.• Specialversions:
- Type S:Aswitchwithdelayedbreakenablingselectivityregardingageneraltypeandashort-timedelayedtype(typeG)connectedontheloadside.Breaktimeislongerthan40ms.Theswitchesexcelinhighresistancetosurgecurrents(upto3kA),whichpreventsunwantedtrippings.Theirratedcurrentsarefrom25to100A,andratedresidualoperatingcurrentsare0.1Aand0.3A.ThisistypeA,andacustomercanchoosebetweenNFI2Stwo-poleandNFI4Sfour-poleswitches.
- Type G:ashort-timedelayedbreakingcharacteristic(min.non-actuatingperiodis10ms).Theswitchesareresistanttounwantedtrippingsatcurrentimpulsesorwhenbuilt-ininspecialcriticalconditions.Theyexcelinhighresistancetosurgecurrents(upto3kA)andareliableoperationincaseofhighmakingcurrents.Ratedcurrentsarefrom25to100A,andratedresidualoperatingcurrentsare0.03A,0.1A,0.3Aand0.5A.ThisistypeA,andacustomercanchoosebetweenaNFI2Ktwo-poleandNFI4Kfour-poleswitches.VersionsSandGcomplywiththeEN61008standard.Regardingtrippingtimes,typeGalsocomplieswithÖVE/ÖNORME8601(supplementtoÖVEEN61008).BothtypesareVDEapproved.
- FIR – FIT combination:Itisusedfortheprotectionincircuitswhereoperationalcurrentsarehigherthatratedcurrentsofresidualcurrentcircuitbreakers.AnactuatingrelayFIRisseparatedfromaFItransformer(FIT).Thefunctionofloadswitchingisperformedbythecontactororacircuit-breakerwithanundervoltagerelease.Acombinationratedcurrentthereforedependsonselectedswitchingdevices.Itislimitedwithcablecross-sectionswhichcanbeinsertedthroughtheholeoftheFItransformer.Rateddifferentialcurrentsare0.3A,0.5A,1Aand2A.
Fi, nFi
ReSidUAL CURRenT CiRCUiT BReAKeRS
�0
ReSidUAL CURRenT CiRCUiT BReAKeRS
DIMENSIONS
Asealingcoverfortwo-pole(SCNF12)andfour-pole(SCNF14)switches
Type AC FI2-16 FI2-25 FI2-40 FI2-63 FI2-80 FI2-100 FI4-25 FI4-40 FI4-63 FI4-80 FI4-100
ANFI2-16 NFI2-25 NFI2-40 NFI2-63 NFI2-80 NFI2-100 NFI4-25 NFI4-40 NFI4-63
NFI4-80
NFI4-100
Standards IEC/EN61008
Approvals VDE
No.ofpoles 2 4
Ratedvoltage Un V 230 230/400
Ratedimpulsevoltage Uimp kV 4
Ratedfrequency f Hz 50/60
Ratedcurrent In A 16 25 40 63 80 100 25 40 63 80 100
Ratedresidualoperatingcurrent
IΔn A
0.01 0.01
0.03 0.03 0.03 0.03 0.03 0.03 0.03 0.03 0.03 0.03 0.03
0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1
0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3
0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
Ratedmakingandbreakingcapacity=Ratedresidualmakingandbreakingcapacity
Im=IΔm A 800 1000 800 1000
Max.back-upfuseforshort-circuitprotectiongL
Iv A 63 63 63 80 80 100 63 63 80 80 100
Ratedconditionalshort-circuitcurrent
Icn kA 10
Terminalcapacity S mm2 1…35
Trippingtimes s at1xIΔn<0.2;at5xIΔn<0.04
Ambienttemperature °C −25…+40
Weight kg 0.23 0.39
FI2,NFI2 FI4,NFI4,FIR FIT
ORDERINGDATA FI2 - 25 /0.03 NFI4 - 40 /0.3
RatedresidualoperatingcurrentIΔn(A)RatedcurrentIn(A)Type
Fi, nFi
TECHNICALDATA
ACCESSORIES
ReSidUAL CURRenT CiRCUiT BReAKeRS ReSidUAL CURRenT CiRCUiT BReAKeRS
��
•RFI2isacombinationofaresidualcurrentcircuitbreakerandaminiaturecircuitbreaker•Abuilt-inprotectionagainstoverloadandshort-circuit•Thefollowingprotectionmeasuresareavailable:-faultprotection(protectionagainstindirectcontact)-protectionagainstfire-additionalprotectionagainstdirectcontact•Protectionagainstover-currents•TheswitchistypeAwhichmeansthatitissensitivetoalternatingandpulsatingdcresidualcurrents•SealinginONorOFFposition•Assemblytoa35mmwidemountingrailinaccordancewithEN60715•Optionaloperationposition•DegreeofprotectionIP20,degreeofprotectionIP40afterinstallationinadistributionbox•Additionalcolourindicationofthepositionofmaincontacts(red:contactsclosed,green:contactsopen)
Type A RFI2-6 RFI2-10 RFI2-16 RFI2-20 RFI2-25 RFI2-32 RFI2-40
Standards IEC/EN61009
No.ofpoles 2
Trippingcharacteristic B,C
Ratedvoltage Un V 230
Ratedimpulsevoltage Uimp kV 4
Ratedcurrent In A 6 10 16 20 25 32 40
Ratedresidualoperatingcurrent
IΔn A
0.01 0.01 0.01 0.01 0.01 − −
0.03 0.03 0.03 0.03 0.03 0.03 0.03
0.1 0.1 0.1 0.1 0.1 0.1 0.1
0.3 0.3 0.3 0.3 0.3 0.3 0.3
0.5 0.5 0.5 0.5 0.5 0.5 0.5
Ratedshort-circuitcapacity kA 10
Selectivityclass 3
Ambienttemperature °C −25…+40
Terminalcapacity S mm2 1.5...25
Accessories Auxiliaryandsignalchangeovercontacts
RFi2
ACCESSORIES
ReSidUAL CURRenT CiRCUiT BReAKeRS
��
COnTACTOR COMBinATiOnS
Connectiondiagram
ORDERINGDATA
RFI2 - B - 16 /0,03
RatedresidualoperatingcurrentIΔn(A)RatedcurrentIn(A)Trippingcharacteristic(BorC)Type
DIMENSIONS
Trip
pin
gti
me
Ratedcurrent xIn
t(s)
In=6-40A
RFi2
TRIPPINGCHARACTERISTICB,C(EN60898)
ReSidUAL CURRenT CiRCUiT BReAKeRS COnTACTOR COMBinATiOnS
��
Theyaremainlyusedforstart-up,overloadprotectionandswitch-offofelectricmotorsandalsoforotherloads.AcontactorandacorrespondingbimetalrelayarebuiltintheenclosureofdegreeofprotectionIP55.TheyareswitchedonwiththeONpushbuttonandswitchedoffwiththeOFFpushbutton.Themushroompushbuttonfunctionsasanemergencystoppushbutton.Correspondingback-upfusesshouldbebuiltinacircuitinfrontofanautomaticcontactorfortheprotectionagainstshort-circuit.TheKPLstartersarenotpro-videdwithoverloadprotection,whileKMPLstartersare.
KPL9,KPL12,KPL16,KPL22,KMPL9,KMPL12,KMPL16,KMPL22
KMPL And KPL diReCT On-Line STARTeRSKMPL9,KMPL12,KMPL16,KMPL22,KPL9,KPL12,KPL16,KPL22
TECHNICALDATA
Typeofdirectstarterwithoutoverloadprotection KPL9 KPL12 KPL16 KPL22
Typeofdirectstarterwithoverloadprotection KMPL9 KMPL12 KMPL16 KMPL22
Correspondingthermaloverloadrelay TRB14/KNL
Standards IEC/EN60947-4-1
Ratedinsulationvoltage Ui V 690 Max.permittedpowersof 230V 2.2/3 3/4 4/5.5 5.5/7.5
three-phasemotorsatAC-3 400V 4/5.5 5.5/7.5 7.5/10 11/15
500V 5.5/7.5 5.5/7.5 7.5/10 11/15
690V 5.5/7.5 7.5/10 7.5/10 11/15
Max.back-upfuseforshort-circuitprotectiongL A 25 25 35 50
Coordinationtype2
Rangeatcontrolvoltage Uc % 85…110
Max.operatingfrequency op.c./h 15
Degreeofprotection IP55
Ambienttemperature °C -20…+40
Terminalcapacity rigid 0.75...6 2.5...10
flexible 0.5...6 1.5...10
Pm kW/HP
S mm2
DIMENSIONS
COnTACTOR COMBinATiOnS
��
COnTACTOR COMBinATiOnS
Allrequiredelementsforstart-up,overloadprotectionandswitch-offofasynchronouselectricmotorsarebuiltintheenclosureofdegreeofprotectionIP55.
Type AC-3Ratedoperationalpower(kW) 230V 400V 500V 690VK0-LD7 3 5.5 5.5 5.5KNL-LD9 2.2 4 5.5 5.5KNL-LD12 3 5.5 5.5 7.5KNL-LD16 4 7.5 7.5 7.5KNL-LD18 4 9 9 9KNL-LD22 5.5 11 11 11KNL-LD30 7.5 15 15 15
KMSPL COMBinATiOn STARTeRSTheyaremainlyusedforstart-upandswitch-offofelectricmotorsupto11kWpower.MS25motorprotectionswitchwithundervoltagereleaseandacorrespondingcontactorarebuilt intheenclosureofdegreeofprotectionIP55.Theadvantagesofcombinationstartersoverdirectstartersare:•itisnotnecessarytobuildinback-upfusesforprotectionagainstshort-circuituptorated motorpower1.5kWat400V•aftereachoverloadandpowerlinefailuretheautomaticswitch-onisnotpossible
Typeofcombinationstarter KMSPL3 KMSPL9 KMSPL12 KMSPL16 KMSPL22Typeofmotorprotectionswitch MS25-6.3 MS25-10 MS25-16 MS25-16 MS25-25Settingrangeofbimetalrelease 4…6.3 6.3…10 10…16 10…16 20…25AC-3,max.permittedpowers 230V 1.5 2.2 3 4 5.5ofthree-phasemotors 400V 2.2 4 5.5 7.5 11 500V 3 5.5 5.5 7.5 11 690V 4 5.5 7.5 7.5 11
Pm kW
ZK STAR–deLTA MOTOR STARTeR
TECHNICALDATA
Permittedmotorpower Startertype Relaytype 230V 400V 500V kW HP kW HP kW HP
ZK12 TRB14-KNL16/6-10 4 5.5 7.5 10 7.5 10
ZK16 TRB14-KNL16/9,6-16 5.5 7.5 11 15 11 15
ZK22 TRB14-KNL30/15-25 8 11 18.5 25 18,5 25
ZK30 TRB14-KNL30/24-40 12.5 17 25 34 25 34
ZK40 BR43/30-43 20 27 37 50 45 60
ZK65 BR43/40-63 25 34 55 75 65 88
ZK95 BRA180/75-125 40 54 75 100 100 136
ZK115 BRA180/90-150 63 86 110 150 147 200
ZK145 BRA180/120-200 80 108 132 180 185 252
ZK180 BRA180/120-200 92 125 160 220 210 272
KO-Ld, KnL-Ld COMBinATiOnS FOR ReVeRSinG
COnTACTOR COMBinATiOnS COnTACTOR COMBinATiOnS
��
Todefinethestarter,thefollowingdatahavetobeknown:•motorpower,operationalcurrent•coilcontrolvoltage•requiredpushbuttons(none,start,stop,reset)•mainswitch(yesorno)Basedonthesedata,aconvenientcontactorandanoverloadrelayaswellascorrespondinglyequippedenclosureareselected.
D120
D121
arrangement data
Thermaloverloadrelay Direct-on Enclosure
TR
B14/K
NL16
0.06 0.08 0.15-0.25 0.12 0.16 0.24-0.4 0.18 0.25 0.38-0.63 0.25 0.33 0.6-1 0.55 0.75 0.96-1.6 1.1 1.5 1.5-2.5 1.5 2 2.4-4 2.2 3 3.8-6.3 4 5.5 6-10 4 5.5 6-10 5.5 7.5 6-10 7.5 10 9.6-16 11 15 15-25
15 20 24-40
KNL9
KNL12
KNL16
KNL22
KNL30
start&stop
reset
none
start&stop
reset
none
start&stopresetnone
start&stopresetnone
withmain
switch
−
withmain
switch
ORDERINGDATA
S–forKNL9–KNL16,M–forKNL22,KNL30Mainswitch(0–none,1–25A,2–32A)Pushbuttons(0–none,1–resetpushbutton,2–start&stop)Enclosuresize
TR
B14/K
NL30
D1 ...0,1,2... ...0,1,2 ...S,M
Enclosures:IP66,ametalbasewithapolycarbonatecover
*Standardcontrolvoltages(50/60Hz)B7 24VF7 110/125VM7 220/240VQ7 380/400VOthercontrolvoltagesonrequest.
**NDL6-11snap-onauxiliaryswitchblockincluded.
D120S**
D110
D100
D121**
D111
D101
D122**
D112D102
diReCT On-Line STARTeRS UP TO 30 A
COMPONENTSELECTION
−
min.–maxHPkW
D110D120M**
D120M**
Type PermittedmotorpowerOperationalcurrent(A)contactor*
400/415,three-phase Push-button Orderingcode Kode
COnTACTOR COMBinATiOnS
��
COnTACTOR COMBinATiOnS
Connectionforthree-phasethree-wiresystem-asshownabove
Connectionforfour-wiresystem:1.Removeconnection1(L1)–A12.ConnectaneutralconductortoA1terminal
Connectiondiagram
Connectionforremotestart-inch-stopcontrol
Connectionforremotepush-buttoncontrol:
1.Removeconnection96–642.Connectasillustrated
KNL9-KNL30direct-on-linestarters
Connectionforremotepilotswitchcontrol
Connectionforremotecontrolwithselectionswitch,
manual–0-automatic
Connectionforsingle-phasemotors
pomik
KnL9-KnL30 diReCT-On-Line STARTeRS
WIRINGDIAGRAMS
COnTACTOR COMBinATiOnS COnTACTOR COMBinATiOnS
��
Anenclosureforcontactorsanddirect-on-linestarters(sizeD)
diReCT On-Line STARTeRS UP TO 30 A
DIMENSIONS
IP66 A B C D E F G H J K L
KNL9–KNL30(enclosureD1) 212 124 156 164 76 117 132.5 - 29.5 3x20 5.5
KNL9–KNL30+mainswitch(enclosureD1)
212 124 156 164 76 117 132 146 29.5
3x20 3x5.5
HolesforcableinletswithKdiameter,topandbottom
FixingholeswithLdiameter
COnTACTOR COMBinATiOnS
��
COnTACTOR COMBinATiOnS
Todefinethestarter,thefollowingdatahavetobeknown:•motorpower,operationalcurrent•coilcontrolvoltage•requiredpushbuttons(none,I,II,0,reset)•mainswitch(yesorno)Based on these data, a convenient contactorandanoverload relayaswellascorrespondinglyequippedenclosureareselected.
R420
ORDERINGDATA
Settingrangeforthermaloverloadrelay.S–forKNL9–KNL16,M–forKNL22,KNL30Mainswitch(0–none,1–25A,2–32A)Pushbuttons(0–none,1–resetpushbutton,2–I,IIand0)Enclosuresize
Enclosure:I,IIand0pushbuttonscanbemarked:FOR/REV,UP/DOWN,OPEN/CLOSED,LEFT/RIGHTDegreeofprotectionIP66,ametalbaseandapolycarbonatecover
*Standardcontrolvoltages(50/60Hz)B7 24VF7 110/125VM7 220/240VQ7 380/400V
Othercontrolvoltagesalsoavaiable
R221
RS9
R2,R4 ...0,1,2... ...0,1,2 ...S,M -....
ReVeRSinG STARTeRS UP TO 30 A
Type Motorpowerat Opertionalcurrent(A)Reversingstarter*
400/415,three-phase
kW HP min.-maks. Pushbuttons Orderingcode
R420S
R410
R400
R221
R211
R201
R420MR410R400
R221R211R201
R420MR410R400
R222R212R202
Thermaloverloadrelay Enclosure
RS9
RS12
RS16
RS22
RS22
I,IIand0
reset
none
I,IIand0
reset
none
I,IIand0resetnone
I,IIand0resetnone
−
withmainswitch
−
withmainswitch
TR
B14/K
NL
0.06 0.08 0.15-0.25 0.12 0.16 0.24-0.4 0.18 0.25 0.38-0.63 0.25 0.33 0.6-1 0.55 0.75 0.96-1.6 1.1 1.5 1.5-2.5 1.5 2 2.4-4 2.2 3 3.8-6.3 4 5.5 6-10 4 5.5 6-10 5.5 7.5 6-10 7.5 10 9.6-16 11 15 15-25
11 15 15-25
15 20 24-40
15 20 24-40
RS30
RS30
I,IIand0resetnone
I,IIand0resetnone
−
withmainswitch
COnTACTOR COMBinATiOnS COnTACTOR COMBinATiOnS
��
Wiringifapositionswitchisrequired:1.Removeconnections52–632.Connectasillustrated
NOTE:Auxiliarycontact13-14belongstoaKNL9-KNL16contactorstandardequipment
CONTROLCIRCUITSUPPLYARRANGEMENTS
KNL9-KNL30reversingstarters
SUPPLY WIRINGPhasetophase SeeafigurePhasetoneutral RemoveconnectionDconnect neutraltoterminal96Separatesupply RemoveconnectionsDandE. Connectseparatecoilsupplyto terminal96onoverloadrelayand terminal64onK2contactor
ReVeRSinG STARTeRS UP TO 30 A
CONNECTIONDIAGRAM
ConnectionD
ConnectionE
Pushtorun
Asimplepush-to-runarrangementcanbeachivedinoneorbothdirectionsbychangingthetopstartswitches.
ConnectionD
ConnectionE
Wiringifremotecontrolwithpushbuttons:1.RemoveconnectionsD
2.Connectasillustrated
COnTACTOR COMBinATiOnS
�0
COnTACTOR COMBinATiOnS
Enclosuresforreversingstarters(enclosuresizesR2andR4)
EnclosureR2
FixingholeswithLdiameterTopandbottomholesforcableinletswithK
diameter
EnclosureR4FixingholeswithLdiameter
HolesforcableinletswithKdiameter,topandbottom
ReVeRSinG STARTeRS UP TO 30 A
DIMENSIONS
IP66 A B C D E F G H J K L
KNL9–KNL30(enclosureR4) 260 158 160 210 108 132 147 - 27.52x201x25
3x5.5
KNL9–KNL30+mainswitch(enclosureR2)
260 230 171 210 180 133 148 161 28.5 2x20
1x254x5.5
COnTACTOR COMBinATiOnS COnTACTOR COMBinATiOnS
��
Todefinethestarter,thefollowingdatahavetobeknown:•motorpower,operationalcurrent•coilcontrolvoltage•requiredpushbuttons(none,start,stop,reset)•mainswitch(yesorno)Basedonthesedata,aconvenientcontactorandanoverload relayaswellascorrespondinglyequippedenclosureare selected.
Thermaloverloadrelay Operationalcurrent Star-delta
Type Motorpowerat (A) starter*Enclosure
400/415V3ph Ordering
kW HP min.-max.. Push-buttons code
TR
B14/K
NL16
SD16
SD22
start&stopresetnone
S320SS310S300S321S311S301S320S310S300
S321S311S301
*Standardcontrolvoltages(50/60Hz)B724VF7110/125VM7220/240VQ7380/400V
Othercontrolvoltagesalsoavailable
S320
S321
SD16
SD22
start&stopresetnone
start&stopresetnone
start&stopresetnone
−
withmainswitch
STAR-DELTA STARTERS APPLICATIONForastar-deltaunit,theoverloadrelayisconnectedtoadeltaloopandthereforeprotectsthemotoronlyatthisconnection.Foreasierselectionoftherelay,motorcurrentsarestatedinatable.Astar-deltastarterisequippedwithanelectronictimerelaywithaminimumrangefrom3to45seconds.Thetimerelayassuresrequireddelaybetweena“star”contactoropeninganda“delta”contactorclosing.
SettingrangeforthermaloverloadrelayS–forKNL9–KNL16,M–forKNL22,KNL30Mainswitch(0–noswitch,1–25A,2–32A)Pushbuttons(0–noswitch,1–resetpushbutton,2–startandstop)Enclosuresize
S3 ...0,1,2... ...0,1,2,3 ...S,M -....
ORDERINGDATA
S322S312S302
TR
B14/K
NL30
2.2 3 2.4-4 4 5.5 3.8-6.3 7.5 10 6-10 11 15 9.6-16 18.5 25 15-25
18.5 25 15-25
22 30 15-25 25 34 24-40
22 30 15-25 25 34 24-40
SD30
SD30start&stop
resetnone
start&stopresetnone
−
withmainswitch
S320S310S300
STAR-deLTA STARTeRS UP TO 25 kw
COMPONENTSELECTION
withmainswitch
−
COnTACTOR COMBinATiOnS
��
COnTACTOR COMBinATiOnS
Connectiondiagram
CONTROL CIRCUIT SUPPLY ARRANGEMENTS
SUPPLY WIRINGPhasetophase SeeafigurePhasetoneutral RemoveconnectionD Connectterminal96toaneutralconductorSeparatesupply RemoveconnectionsDandE Connectseparatecoilsupplytoterminal96onoverloadrelayandterminal64onK2contactor
NOTE:AUXILIARYCONTACT13-14BELONGSTOAKNL9-KNL16CONTACTORSTANDARDEQUIPMENT
Wiringforremotecontrolwithpushbuttons 1.RemoveconnectionD 2.Connectasillustrated
MotorwindingsConnecttoappropriateterminals
onthestarter
ConnectionE
ConnectionD
ConnectionD ConnectionE
STAR-deLTA STARTeRS UP TO 25 Kw
CONNECTIONDIAGRAM
KNL9-KNL30stardeltastartercontactors
Connectiondiagram(RemotePilotSwitchControl)1.Removeconnection63to52ontheK2contactor2.Connectbetween52and64ontheK1contactorandfromterminal51ontheK1contactortoterminal52ontheK2contactor3.ConnectthepilotswitchinplaceofconnectionE4.Setoverloadrelaytomanualresetposition.
COnTACTOR COMBinATiOnS COnTACTOR COMBinATiOnS
��
Enclosuresforstar-deltastarters(sizesS2andS3)
EnclosuresS2andS3
fixingholeswithLdiameterHolesforcableinletswithKdiameter,topandbottom
STAR-deLTA STARTeRS UP TO 25 Kw
DIMENSIONS
IP66 A B C D E F G H J K L
KNL16–KNL30(enclosureS2) 260 230 161 210 180 133 148 - 28.52x201x25
3x5.5
KNL16–KNL30+mainswitch(enclosureS3)
260 332 171 210 282 133 148 161 28.5 3x20
1x254x5.5
SOFT STARTeRS
��
SOFT STARTeRS
Ifyouneedarobust,fullyfeaturedSoftStarterorasophisticatedcontrollerwithCommunicationslinks,MSCistherightchoiceforyou.Itoffersuser-friendlyautosetupwithasimpleselectionoftheapplicationrequiredfromthefirstmenu.Analphanumericdisplayenableseasymonitoringofmessagesduringnormaloperationandincaseofemergency.MSCexcelsinhighqualityandsimpleconnection.Itisadaptableandadvanced.
FEATURES:• Forallrequirements:9-900A,230-460,400-575 and500-690V• Automaticapplicationsetup:Fan,Pump,Conveyor, etc.• ManualadjustmentofStartandStoptimesupto 255seconds,StartandStoppedestalsfrom10% to60%,currentlimitation1to8xFLC,kickstart forhighbreakawaytorqueapplications• Six-buttonkeypadincludingStart/Stopwith 2-line32-characterLCD• Menudesignedforeasyparametersetup• Continuousdisplayofmotorphasecurrentand controlstatus:starting,stopping,fullvolts, optimising,currentlimitation,overloadandfault indication
• Modbus&RemoteKeypodoptioneliminatingmanycontrolitemscanbeusedontheone-to-onebasisor onekeypodcancontrolupto10SoftStarters•Loads-StandardW3Ccontrolofmotors,staticloads,resistive(heaters)andinductive(transformers)•In-deltaoperation:allowsforalowercurrentratingthanthemotor•Recordhistoryoflast5trips–overload,shearpin,undercurrent,currentlimittimeout;inputandmotorside phaseloss;thyristorshortcircuit,signal,firingandsensing;external;phaserotation;communicationfailure; thermalswitch;thermistorandexcessivestartsperhourtrips•Automaticenergyoptimizingwithadjustableoptimisingresponserate•Controlsupplyselectable115or230V•Fullyprogrammableinputs12VDC–230VAC,outputsAC1230V3A•IP20•MSC,MSS+optionadds:twoanalogueoutputs0-10VDC,twoanalogueinputs4-20mAand0-10VDC, thermistortripinput,twoextrarelaysandtwoextra12VDC–230VACinputs.Allarefullyprogrammable.
DESIGN STANDARDS AND APPROVALS
IEC60947-4-2-:StandardsforACSemiconductorMotorControllerandStartersEN60947-4-2:EuropeanStandardsforACSemiconductorMotorControllersandStarters
BENEFITS• Reductionofhighstartingcurrents• Eliminationofinrushcurrents• Smooth,steplessaccelerationtofullspeed• Snatchfreestartingremovingmechanicalstress• Extendedcontactorlife• Reducedwearonmechanicaltransportcomponents• Automaticenergyoptimising• Improvedpowerfactoratlightloads,reducedkVAdemand• Suitableforalltypesofinductionmotors
MSS And MSC diGiTAL SOFT STARTeRS
SOFT STARTeRS SOFT STARTeRS
��
SIZE2
Allunitsareforcecooled.Clearanceof75mmisrequiredaboveandbelow,15mmsideand25mmfront,forcoolingairflow.Cableentryextensionsareoptionalextrasforsize2unit.Theyaredesignedtobedrilledforpowerandcontrolcableglands.Whenused,theoverallheightisincreasedto740mm.
MSS And MSC diGiTAL SOFT STARTeRS
MCSTYPESANDSPECIFICATION
SIZE1Type MSC9 MSC16 MSC23 MSC30 MSC44 MSC59 MSC72 MSC85 MSC105 MSC146
Max. continuous current:
9A 16A 23A 30A 44A 59A 72A 85A 105A 146A
Appropriate equivalent motor ratings at voltage – kW:
230V 2.2 3.7 6.3 7.5 11 16 20 22 30 45
400V 4 7.5 11 15 22 30 37 45 55 75
460V 4 7.5 11 15 22 32 40 45 55 80
Model G/E MSC9 MSC16 MSC23 MSC30 MSC44 MSC59 MSC72 MSC85 MSC105 MSC146
Max. continuous current:
9A 16A 23A 30A 44A 59A 72A 85A 105A 146A
Appropriate equivalent motor ratings at voltage – kW:
575V(G) 5.5 11 15 22 30 37 45 55 75 110
690V(E) 7.5 15 22 30 37 55 60 75 90 132
Heat output at FLC – W:
30 45 60 80 110 155 180 220 275 440
Weight – kg:
7 7 7 7 8 8 8 8 8
Cable size – mm2:
4 4 4 6 10 10 16 25 35 70
Type MSC174 MSC202 MSC242 MSC300 MSC370
Max. continuous current:
174A 202A 242A 300A 370A
Appropriate equivalent motor ratings at voltage – kW:
230V 55 63 75 90 110
400V 90 110 132 160 200
460V 110 132 150 185 220
Model G/E MSC174 MSC202 MSC242 MSC300 MSC370
Max. continuous current:
174A 202A 242A 300A 370A
Appropriate equivalent motor ratings at voltage – kW:
575V(G) 132 150 185 220 250
690V(E) 160 200 220 300 375
Heat output at FLC – W:
520 610 650 850 970
Weight – kg:
15,7 15,7 22 22 22
Cable size – mm2:
95 120 120 150 150
SIZE3Type MSC500 MSC600MSC750MSC900
Max. continuous current:
500A 600A 750A 900A
Appropriate equivalent motor ratings at voltage – kW:
230V 160 185 250 300
400V 250 320 400 500
460V 300 375 450 560
Model G/E MSC500 MSC600 MSC750 MSC900
Max. continuous current:
500A 600A 750A 900A
Appropriate equivalent motor ratings at voltage – kW:
575V(G) 375 450 560 670
690V(E) 500 600 750 900
Heat output at FLC – W:
1600 2000 2500 3000
Weight – kg:
65 65 72 72
Busbar (conns.) 2xM10
95
Allunitsareforcecooled.Clearanceof200mmisrequiredaboveandbelow,90mmsideand25mmfront,forcoolingairflow.
SOFT STARTeRS
��
SOFT STARTeRS
TheAmpsvaluesforthesoftstarterarethemaximumcontinuouscurrentforthemodelatthestatedduty.TherearemanyMSStypesavailableinordertoofferthebestcosteffectivesolutionforyourapplication.TohelpourcustomersselecttherightproductwepreparedaspecialApplicationselectortableavailablefromourinternetsite.
MSS 100 series current ratings
MSS And MSC diGiTAL SOFT STARTeRS
Continuous/Optimising ExternallyBypassed
Cla
ss10
BA
C53
a3.
5-12
:75-
5
Cla
ss10
BA
C53
a3.
5-12
:75-
5
Cla
ss20
AC
53a
4-19
:75-
5
Cla
ss30
AC
53a
4-29
:75-
5
Cla
ss10
BA
C53
b3
.5-1
2:70
8
Cla
ss10
AC
53b
3-2
3:69
7
Cla
ss20
AC
53b
4-1
9:70
1
Cla
ss30
AC
53b
4-2
9:69
1
MSS102 3A 3A 3A 3A 5A 4A 3A 3A
MSS104 6A 6A 6A 6A 9A 9A 7A 6A
MSS106 8A 8A 8A 7A 12A 12A 9A 8A
MSS108 13A 13A 10A 9A 18A 19A 12A 11A
MSS110 19A 19A 18A 17A 23A 28A 21A 20A
MSS112 23A 23A 22A 21A 31A 34A 26A 24A
MSS114 27A 27A 25A 24A 35A 40A 30A 29A
MSS116 33A 33A 31A 30A 45A 49A 37A 35A
MSS118 35A 35A 30A 28A 46A 43A 33A 31A
MSS120 41A 44A 35A 33A 47A 51A 39A 37A
MSS122 44A 46A 44A 43A 56A 72A 55A 51A
MSS124 55A 55A 55A 54A 85A 89A 69A 64A
MSS126 70A 70A 59A 58A 85A 84A 63A 61A
MSS128 77A 85A 66A 64A 86A 92A 70A 67A
MSS130 88A 98A 75A 73A 94A 105A 80A 77A
MSS132 98A 108A 83A 81A 107A 117A 89A 85A
MSS134 116A 128A 99A 96A 126A 139A 106A 101A
MSS136 132A 135A 112A 106A 146A 159A 122A 115A
MSS138 154A 166A 131A 124A 171A 186A 143A 134A
MSS140 179A 190A 151A 142A 203A 215A 167A 156A
MSS TYPES AND MOTOR CURRENTS AT RATED VOLTAGES
SOFT STARTeRS SOFT STARTeRS
��
Continuous/Optimising ExternallyBypassed
Cla
ss10
BA
C53
a3.
5-12
:60-
3
Cla
ss10
AC
53a
3-23
:60-
3
Cla
ss20
AC
53a
4-19
:60-
3
Cla
ss30
AC
53a
4-29
:60-
3
Cla
ss10
BA
C53
b3
.5-1
2:11
88
Cla
ss10
AC
53b
3-2
3:11
77
Cla
ss20
AC
53b
4-1
9:11
81
Cla
ss30
AC
53b
4-2
9:11
71
MSS202 209A 225A 174A 164A 218A 232A 178A 167A
MSS204 243A 261A 202A 190A 253A 270A 208A 195A
MSS206 314A 314A 242A 222A 330A 322A 250A 230A
MSS208 350A 320A 258A 235A 360A 344A 272A 242A
MSS210 370A 350A 274A 248A 390A 364A 288A 256A
MSS212 440A 412A 325A 295A 460A 433A 342A 305A
Continuous/Optimising ExternallyBypassed
Cla
ss10
BA
C53
a3.
5-12
:60-
3
Cla
ss10
AC
53a
3-23
:60-
3
Cla
ss20
AC
53a
4-19
:60-
3
Cla
ss30
AC
53a
4-29
:60-
3
Cla
ss10
BA
C53
b3
.5-1
2:11
88
Cla
ss10
AC
53b
3-2
3:11
77
Cla
ss20
AC
53b
4-1
9:11
81
Cla
ss30
AC
53b
4-2
9:11
71
MSS306 630A 630A 480A 430A 662A 655A 500A 442A
MSS308 780A 750A 600A 530A 817A 780A 628A 543A
MSS310 795A 780A 615A 545A 825A 800A 640A 560A
MSS312 850A 850A 724A 650A 875A 895A 754A 665A
MSS314 950A 950A 810A 727A 1000A 1000A 842A 744A
MSS316 1060A 1060A 904A 812A 1100A 1115A 940A 830A
MSS318 1150A 1150A 980A 880A 1209A 1210A 1020A 900A
MSS319 1150A 1150A 980A 880A 1209A 1210A 1020A 900A
MSS320 1320A 1320A 1050A 930A 1360A 1360A 1080A 950A
MSS322 1400A 1400A 1110A 950A 1400A 1430A 1160A 970A
MSS324 1550A 1520A 1230A 1050A 1560A 1580A 1280A 1075A
MSS326 1850A 1750A 1460A 1190A 1998A 1810A 1520A 1225A
MSS 300 series current ratings
Thischassissizeisalwaysbuilttoorderandcanthereforebemadeforaspecificdutyotherthanthestandardratings.Pleasecontactyoursupplierfordetailsregardingthischassissize.
MSS 200 series current ratings
MSS And MSC diGiTAL SOFT STARTeRS
SOFT STARTeRS
��
SwiTCH diSCOnneCTORS
BENEFITS• 22-500A• Replacesstar-deltaStarters• Fitsinthesamefootprintasstar-delta• Noneedtochangelayoutdrawings• Simplifiedinstallation• Offerssoftstopping• RemovalofhightransientcurrentsFEATURES• Adjustablestarttimebetween0.5sand12s (uptomodelMDS195) 0.5and30s(frommodelMDS195toMDS500)• Adjustablestoptimebetween0sand12s
(uptomodelMDS195) 0.5and30s(frommodelMDS195toMDS500)•Runrelay•Faultrelay•Adjustablemotorrating• Internalby-pass•Eliminationofinrushcurrents•Smoothsteplessacceleration• Improvedreliability
STANDARDS:IEC60947-5-2StandardsforACSemiconductorMotorControllersandStartersEN60947-5-2EuropeanStandardsforACSemiconductorMotorcontrollersandStarters
Type MDS22MDS29MDS41 MDS55MDS66MDS80MDS97 MDS132MDS160MDS195MDS230MDS280MDS350MDS430MDS500
Max.continuouscurrent:
22A 29A 41A 55A 66A 80A 97A 132A 160A 195A 230A 280A 350A 430A 500A
Approximateequivalentmotorratingsatvoltage–kW:
400V 11 15 22 30 37 45 55 75 90 110 132 160 200 250 280
Operationalvoltage 230-460VACrms3-phase(-15%+10%)
Ratedfrequency 50-60Hz+/-2Hz
Indexrating AC53b:3-5:355;Class10AAC53b:3-12:348 Class10AAC53b:3-12:1188
Controlsupply 24VDCexternal
Start/softstopcontrol 24VDC/110VACelectricallyisolatedterminals
Auxiliarycircuits(relays) Run,ready:230VAC3A,AC11
Indication MiltifunctionLEDsonfrontpanel
Starttime 0,5to12sek. 0.5to30sec.
Stoptime 0to12sek. 0.5to30sec.
Startduty 3xFLCfor5secondsatstandard (12s−class10A;23s−class10)
Starts/hour 10startsperhouror5starts+5softstopsperhour 3softstartsorsoftstopsperhour
Internalby-pass MDS97–IP20
IPratingMDS132+MDS500–IP00
MdS diGiTAL SOFT STARTeRS
Fixedspeedinductionmotorsarestartedwithastar-deltastarterinatraditionalway.Thestar-deltastartercannowbereplacedwithanewISKRAMDSdigitalsoftstarter.Itisspeciallydesignedtofitintothesamefootprint.
SOFT STARTeRS
��
SwiTCH diSCOnneCTORS
GENERAL• ComplieswithIEC/EN60947-3standard• Usedasmainandemergencystopswitches,maintenanceswitchesorsafety switches• From16to125Aratings• Availableversions:doorinterlock,directoperationandfrontdoormounting• Compactandmodularsize• Fixing:withscrewsorassemblytoa35mmwidemountingrailinaccordancewith EN60715• Padlockableat0positionwithoutextraaccessories
Three-poleswitch BSA16 BSA25 BSA32 BSA40 BSAM63 BSAM80 BSAM100BSAM125
withouthandle
Three-poleswitch BSC16 BSC25 BSC32 BSC40 BSCM63 BSCM80 BSCM100BSCM125
withdirecthandle
Three-poleswitch BSD16 BSD25 BSD32 BSD40 BSD63
directdoormounting
Ith A 16 25 32 40 63 80 100 125
Ui V 800 800 800 800 800 800 800 800
Uimp kV 8 8 8 8 8 8 8 8
16 25 32 40 63 80 100 125
16 25 32 40 63 80 100 125
16 25 32 40 63 80 100 125
Ie A 16 25 32 40 63 80 100 125
16 25 32 40 63 80 100 125
16 25 32 40 63 80 100 100
16 25 32 40 63 80 80 80
16 25 32 40 63 63 63 63
16 25 25 25 50 50 50 50
7,5 9 11 11 18,5 22 37 40
P kW 7,5 9 11 15 22 30 37 37
11 11 11 18,5 25 30 30 30
Icw Arms 1260 1260 1260 1260 1500 1500 1500 1500
Icc kArms 50 50 50 50 25 40 25 11
A 16 25 32 40 63 80 100 125
A 160 250 320 400 630 800 800 800
A 128 200 256 320 504 640 640 640
op.c. 100,000 100,000 100,000 100,000 30,000 30,000 30,000 30,000
op.c. 3,000 3,000 3,000 3,000 1,500 1,500 1,00 1,500
mm2 16 16 16 16 50 50 50 50
Nm 2 2 2 2 3.5 3.5 3.5 3.5
Type
Thermalcurrent
Ratedinsulationvoltage
Ratedimpulsewithstandvoltage
RatedoperationalcurrentAC-21A 415V
500V
690V
AC-22A415V
500V
690V
AC-23A415V
500V
690V
RatedoperationalpowerAC-23A415V
500V
690VRatedshort-circuitwithstandcurrent(1s)
Ratedconditionalshort-circuitcurrent
withfuseclassgG
BS
TECHNICALDATA
Makingcapacity
Breakingcapacity
Electricalendurance
Mechanicalendurance
Terminals
Tighteningtorque
�00
SwiTCH diSCOnneCTORS SwiTCH diSCOnneCTORS
BS
ACCESSORIES
1NO+1NC
Type Description Version
BSX11 Auxiliarycontact16Afor16-125Aswitch
Auxiliarycontact16Afor16-63Afor
BSX11D directdoormounting
AUXILIARYCONTACTS
ThermalcurrentIth(A) 16 25 32 40 63 80 100 125
forBSAandBSCswitchesBSF16AC BSF25AC BSF32AC BSF40AC BSFM63AC BSFM80ACBSFM100AC BSFM125
forBSDswitches BSF16D BSF25D BSF32D BSF40D BSFM63D
FOURTHPOLE
Type
BSH16 DirectblackhandleforBSC16–BSC40
BSHM63 DirectblackhandleforBSCM125
BSH48RA Externalred/yellow,IP65,3timespadlockable,0/OFFand1/ONmarkings
BSH48BA ExternalblackhandleIP65,3timespadlockable,0/OFFand1/ONmarkings
HANDLES
Type
BSS70 70mmshaftforhandleBSH48RAandBSH48BA
BSS90 90mmshaftforhandleBSH48RAandBSH48BA
BSS150 150mmshaftforhandleBSH48RAandBSH48BA
BSS300 300mmshaftforhandleBSH48RAandBSH48BA
EXTENSIONSHAFTS
SwiTCH diSCOnneCTORS
�0�
SwiTCH diSCOnneCTORS
Doormounting
Mountingofexternalhandle
Howtomeasureandcuttheshaft1.Measurethedistancebetweenthefrontsideofthedoorandtheupperpartofthemountingrail.2.CalculatetheshaftlengthL=H–30.3.Cuttheshaft.
BS
ASSEMBLY
DIMENSIONS
Time Relays
102
Time Relays
TRE 701 is a multifunction multitime time relay with build-in microprocessor technology. It covers most of the user needs. It comprehends simple and more sophisticated time functions with very wide time ranges. It can be delivered in many varieties according to operating voltages and the number of output contacts.
A: A pulse after power-on or after the rising edge of trigger pulse S. B: Delay after power-on or after the rising edge of trigger pulse S. C: A pulse after power-on or after the rising edge of trigger pulse S. Retriggerable. D: Delay after power-on or after the rising edge of trigger pulse S. Retriggerable. E: The first edge of trigger pulse S turns relay on while the second edge starts counting down till relay off. Additional trigger S before the process is finished prolongs the on-state. F: Each rising edge of trigger S appends additional period T to the time of on-state. G: Pulsating operating with a starting pulse or pause which depends on the state of trigger S at power-on. H: Bistable operating. Each rising edge of trigger S swaps the relay into the opposite state. I: Prolonged pulse after power-on. The presence of trigger S temporarily stops counting. J: Prolonged pause after power-on. The presence of trigger S temporarily stops counting.
Notes Functions A - D: If triggering at power-on is required, then the control signal S must be active. When changing function, the relay must be powered OFF and ON again. It is possible to upgrade the relay with some user-defined functions with one or two independent output relays (for larger quantities).
Orderind data:
TRE 701 2 24 - 240 VTRE 701 - relay type2 - number of contacts (1,2,3)24 - 240 V - operating voltage (12 V AC/DC, 230 V AC, 24-240 V AC/DC)
NOTE: Combination with 3 output contacts and 230 VAC operating voltage cannot be delivered. For technical data see page 105.
TRe 701
Connection diagram:
Function description:
Basic technical data Time ranges (time ranges selected with seconds: 1, 10 a microswitch) minutes: 1, 10 hours: 1, 10, 100, 500 ON, OFFOperating voltage ranges (select one range) 24 - 240 V AC/DC 12 V AC/DC 230 V AC Output contacts 1 - 3 x 8 A/250 V
Time Relays Time Relays
103
TRE 702 is a multifunction T1-T2 time relay with built-in microprocessor technology. It covers most of the user needs. The time relay comprehends simple and more sophisticated time functions with very wide time ranges. It can be delivered in many varieties according to operating voltages and the number of output contacts. It excels in the possibility of setting extremely asymmetrical T1-T2 time functions.
Basic technical data Time ranges (time ranges selected with seconds: 1, 10 a microswitch) minutes: 1, 10 hours: 1, 10, 100, T1,T2: 1h - 1 min; 10 h - 10 min;100 h - 1hOperating voltage ranges (select one range) 24 - 240 V AC/DC 2 V AC/DC 230 V AC Output contacts 1 - 3 x 8 A/250 V
Connection diagram:
Ordering data:
TRE 702 2 24 - 240 VTRE 702 − relay type2 – a number of contacts (1, 2, 3)24 - 240 V – operating voltage (12 V AC/DC, 230 V AC, 24-240 V AC/DC)
TRe 702
A: A pulse after power-on or after the rising edge of trigger pulse S.Eventual signals S occurring before time T expiry have no influence. B: Delay after power-on or after the rising edge of trigger pulse S. Eventual signals S occurring before time T expiry have no influence. C: A pulse after power-on or after the rising edge of trigger pulse S. Retriggerable. D: Delay after power-on or after rising edge of trigger pulse S. Retriggerable. E: The first edge of trigger pulse S turns relay on while the second edge starts counting down till relay off. Additional trigger S prolongs the on-state before the process is finished. F: Prolonged pulse after power-on. The presence of trigger S temporarily stops counting. G: Pulsating operating with a non-equal pulse-pause rate. A starting pulse or a pause which depends on the state of trigger S at power-on. H: After the rising edge of trigger S, the device waits for period T1 and the relay is activated (if trigger S is still present). After period T2, it is deactivated. If the trigger signal is shorter than period T1, the relay does not activate at all. If trigger S reappears during period T2, it has no influence. I: After the rising edge of trigger S, the device waits for period T1 and the relay is activated (if the trigger S is still present). At the falling edge of trigger S the second counting starts and when it reaches T2 , the relay is deactivated. If the trigger signal is shorter than period T1, the relay does not activate at all. If trigger S reappears during period T2, it has no influence. J: The rising edge of trigger S activates the relay for period T1. The falling edge of trigger S activates the relay for period T2. If trigger S falls down during period T1, period will be cancelled. If trigger S reappears during period T2, it has no influence.
Note: Functions A – D: triggering power-on, is required the control signal S must be active. When changing function, the relay must be powered OFF and ON again.
For larger quantities, it is possible to upgrade the relay with some user-defined functions by means of one or two independent output relays.
NOTE: A combination with three contacts and 230 V AC operating voltage cannot be delivered.For technical data see page 105.
Function description:
Time Relays
104
Time Relays
TRE 703 is a one-function one-time time relay used for more sensitive applications. It can be delivered in many varieties according to function, time range, operating voltage and the number of output contacts.
Basic technical data Time ranges (select one range) seconds: 3,15 minutes: 1, 3, 15 hours: 1, 3Operating voltage ranges (select one range) 24-240 V AC/DC 12 V AC/DC 230 V ACOutput contacts 1 - 3 x 8 A/250 V
Connection diagram
Ordering data
TRE 703 2 24-240 V A 1 hTRE 703 – relay type2 – number of contacts (1, 2, 3)24-240 V – operating voltage (12 V AC/DC, 230 V AC, 24-240 V AC/DC)A – time function (A, B, C, D)1 h – time range (3 s, 15 s, 1 min, 3 min, 15 min, 1 h, 3 h)
NOTE: A combination with three contacts and 230 V AC operating voltage can not be delivered.
For technical data see page 105.
TRe 703
A: Pulse at power-on or at falling edge of control signal S B: Pause at power-on or at falling edge of control signal S C: Pulsating with starting pulse D: Pulsating with starting pause
Function description
Time Relays Time Relays
105
TRE 704 is a star-delta switch. Time T1 can be adjusted within the selected time range. It can be delivered in many varieties according to time range and operating voltage.
Function description
Basic technical data
Time ranges (select one range) seconds: 10, 30, 60, 100, 600
Operating voltage ranges (select one range) 24-240 V AC/DC 12 V AC/DC 230 V AC
Output contacts 2 x 8 A/250 V
Connection diagram
Ordering data
TRE 704 24-240 V 100 sTRE 704 – relay type24-240 V – operating voltage (12 V AC/DC, 230 V AC, 24-240 V AC/DC) 100 s – time range (10, 30, 60, 100, 600)
For technical data see page 105.
TRe 704
After power-on, the relay Y is activated for time T. After the pause. T2 = 100 ms, the relay ∆ is activated.
Time Relays
106
Time Relays
TRE 705 is a bistable time relay with hold-on after power off. Time T1 can be adjusted within the selected time range. It can be delivered in many varieties according to time range and operating voltage.
Basic technical data
Time ranges (select one range) seconds: 3, 10, 30, 60, 100, 300
Operating voltage ranges (select one range) 24-240 V AC/DC 12 V AC/DC
Output contacts 6 A/250 V
Connection diagram
Ordering data
TRE 705 – 24-240 V A 100 sTRE 705 – relay type24-240 V – operating voltage (12 V AC/DC, 24-240 V AC/DC)A - time function100 s – time range (3, 10, 30, 60, 100, 300 seconds)
For technical data see page 105.
TRe 705
A: The relay is activated after power-on. After power-off, it remains activated for the period T. B: The relay is activated at power-off and remains activated for the period T.
Function description
Time Relays Time Relays
107
TRE 706 is a staircase switch. Time can be adjusted in the range from 0.5 to 10 minutes. It is edge triggered, which means that it is broken-switch proof. Enhanced version B has the possibility of multiplying ON time by factor 8. This fast-on function is activated by holding the switch for prolonged time (6- to 8 - second). This is very useful at cleaning, repairs etc.
Ordering data
TRE 706 A
TRE 706 – relay typeA – option (A, B): A is a basic version, B has the possibility of time
prolonged operation
TRe 706
Option B
Basic technical data Time ranges 0.5 - 10 minutes ON, OFF Option B: extra 4-80 minutes ON, OFF Operating voltage 230 V AC Output contact 16 A/250 V Number of bulb lamps (<1mA) 10
Technical data for time relays TRE 701 to TRE 706
Operating voltage range: -15%, +10%Input resistance of control input S: (TRE 701, 702, 703, 706): 100 kOhmMin. duration of trigger pulse S: 50 msTime setting repeatability:TRE 703/704/705/706/CRT < 2%TRE 701/702 < 1%Nominal time range toleranceTRE 703, 704, 705, 706: 5%TRE 701/702: 1%Operating temperature: 0°C to 55°C (-20°C to +65°C available on order)Storage temperature: -25°C to +70°CDegree of protection: IP20Diameter of connection cable: 2.2 mm max.Mechanical endurance: >107 cyclesStandards: EN 60669, EN 60256; EN 61000, EN 61010, EN 61812
DIMENSIONS
Connection diagram
Function description
The signal S activates the relay for period T. If the duration of the signal S is longer than 6 seconds, the period T is prolonged by factor 8 (version B). This is indicated by changing the brightness of the control red LED.
If the signal S reappears before the period T expires, the counting time starts again from the beginning.
accessoRies
108
accessoRies
Type OS1/ 2P+Pe / IP55OS1/ 3P+Pe / IP55
Type OS3/ 2P+Pe / IP55OS3/ 3P+Pe / IP55
Type OS4/ 2P+Pe / IP55OS4/ 3P+Pe / IP55
Type OS5/ 2P+Pe / IP55OS5/ 3P+Pe / IP55
Type OS6/ 2P+Pe / IP55OS6/ 3P+Pe / IP55
Type OS2/ 2P+Pe / IP55OS2/ 3P+Pe / IP55OS2/ 4P+Pe / IP55
coNNecTioN caBiNeTs os1, os2, os3, os4, os5, os6 (WiTH eXTeNsioN FoR mecHaNical iNTeRlocK)
ACCeSSORieS ACCeSSORieS
�0�
Type WidthUMP4545mm UMP90 90mm UMP90E 90mm
wK wiRinG SYSTeM Type Description
WK1.1 Forreversingswitch,suitableforcontactors:2.2-5.5kW (forminicontactorsK03,K07)(max.current16A) 5terminalinline,(3mainterminals,1auxiliaryterminal,1coilterminal)
WK2.1 Forreversingswitch,suitableforcontactors:4:5.5:7.5or9kW (forKNL9-KNL18)(max.current25A),4terminalsinline(3mainterminals,1auxiliary terminal)WK4.1 Forreversingswitch,suitableforcontactors:11and15kW (forKNL22-KNL30)(max.current40A),3terminalsinline(3mainterminals)
WK5.1Forreversingswitchwithmechanicalinterlock(suitableforcontactors:4:5.5: 7.5or9(kWforKNL9-KNL18)(max.current25A),4terminalsinline(3mainterminals,1auxiliaryterminal)
WK1.2 Forstar-deltastarters,suitableforcontactors:2.2-5.5kW(forminicontactorsK03, K07)(max.current16A),5terminalsinline(3mainterminals,1auxiliaryterminal,1coilterminal)
WK2.2 Forstar-deltastarters,suitableforcontactors:4:5.5;7.5or9kW (forKNL18)(max.current25A),4terminalsinline(3mainterminals,1auxiliaryterminal)
WK4.2 Forstar-deltastarters,suitableforcontactors:11and15kW(forKNL22-KNL30) (max.current40A),3terminalsinline(3mainterminals)
dST-U COnneCTiOn BLOCK BeTween MOTOR-PROTeCTiOn SwiTCH And COnTACTOR
Type CablelengthCross-section WidthDST-U-2,5(20A)40mm 2.5mm2 45mmDST-U-4(35A)40mm 4mm2 45mmDST-U-2,5L(20A)70mm 2.5mm2 45mm
UMP90E
UMP90
MULTi - FUnCTiOnAL AdAPTeRS
UMP45
Forreversingstarterupto30A
1 2
3
1 Fordirect-starterupto30A
2
3 Forstar-deltastarterupto30A
ACCeSSORieS
��0
APPROVALS
MSS-3L COnneCTiOn BLOCK FOR MOTOR PROTeCTiOn SwiTCH Type Module/length MSS-3L-M2-45 2x3/80 MSS-3L-M3-45 3x3/125 MSS-3L-M4-45 4x3/170 MSS-3L-M5-45 5x3/215 MSS-3L-M2+Hi-45+9 2x3/90 MSS-3L-M3+Hi-45+9 3x3/145 MSS-3L-M4+Hi-45+9 4x3/200 MSS-3L-M5+Hi-45+9 5x3/250
eSB-S/V-MS SUPPLY BLOCK (25 MM2) FOR MOTOR PROTeCTiOn SwiTCH
BS-MS 0 PROTeCTiOn FOR COnneCTiOn CABLe
M 25 x 1.5 CABLe inLeT
ACCeSSORieS
���
APPROVALS
eSB-S/V-MS SUPPLY BLOCK (25 MM2) FOR MOTOR PROTeCTiOn SwiTCH
Typeofproduct Certificates
MS25,MS20 UL/CSA,Semko,GOSTMST25,MST20 UL/CSA,SemkoMS20 MST20 PS UL/CSA,GOSTU,Arelease UL/CSA,GOSTRS,PSV UL/CSA,GOSTMS32 UL/CSAMSB32 UL/CSAHS,HSV,HRS UL/CSAUR,ARrelease UL/CSAFI2,FI4,NFI2,NFI4,NFIS,NFIK VDE,GOSTK03C,K07C,K07CG,K07CF UL/CSA,GOSTK03M,K07M,K07MG,K07MF,K07MX UL/CSA,GOSTND2,ND4 UL/CSA,GOSTBR6 GOSTKNL6 UL/CSA,GOSTKNL9,KNL12,KNL16 UL/CSA,GOSTKNL18 GOSTKNL22,KNL30 UL/CSA,GOSTKNL6G UL/CSA,GOSTKNL9G,KNL12G,KNL16G UL/CSA,GOSTKNL22G,KNL30G UL/CSA,GOSTNDL1,NDL2,NDL3,NDL4 UL/CSA,GOSTNPL1,NPL2 UL,GOSTTRB14/KNL GOSTKNL40,KNL65 GOSTBR43 GOSTKNL80,KNL90,KNL110 UL,GOSTG480,G484 BR90 GOSTKNL95-KNL1000 UL,GOSTBRA180,BRA400 GOSTG350KC12-KC60IKA20,IKA25,IKD20,IKD25,IK40,IK63 NF,Semko,GOSTIKA20-R,IKA25-R NFIKN NF,SemkoRI60 VDECDB3X NFZK12-ZK180 K0-LD7 KNL-LD7,…,KNL-LD30 KMSPL3-KMSPL22 BS