    © ABB GroupMarch 26, 2014 | Slide 2

    Definition of Hybrid Switchgear as per IEC 62271-205

    Compact switchgear assemblies consist either of

    components of air-insulated switchgear (AIS) or of a

    combination of air-insulated switchgear and gas-

    insulated switchgear (GIS), so called mixed

    technology switchgear (MTS)

    HV ComponentsELK HybridConventional AIS Busbar 

  • 8/18/2019 Mr.shahabb Elk 3

    3/29

    © ABB GroupMarch 26, 2014 | Slide 3

    Product Positioning

    Breaker and

    Modules

     AIS

    Conventional

    LTB, DCB   P  r  o   d  u  c   t   L   i  n  e

       P  r  o   d

      u  c   t

       F  a  m

       i   l  y HV Components

    Capacitors,

    Instrument

    Transformers,

    Surge Arrestors

    HV Components

    GIS or Breaker

    and Modules

    Capacitors,Instrument

    Transformers,

    Surge Arrestors

    ELK Hybrid

    GIS

    GIS

    ELK System

    Surge Arrestors

    HV Components

    MTS

  • 8/18/2019 Mr.shahabb Elk 3

    4/29

    © ABB GroupMarch 26, 2014 | Slide 4

    ELK Hybrid Switchgear 

    Gas insulated switching module

    with more than one integrated high voltage devices

    circuit breaker 

    earthing switch

    current transformer 

    bushing

    disconnector 

    voltage transformer 

    high speed earthing

    switch

    surge arrestor 

    cable end box

    transformer direct

    connection

    busduct

    ELK Hybrid customized ELK Hybrid standard

    Product M mt

  • 8/18/2019 Mr.shahabb Elk 3

    5/29

    © ABB GroupMarch 26, 2014 | Slide 5

    ELK Hybrid differentiation

    ELK Hybrid customized ELK Hybrid standard

    Product M mt

  • 8/18/2019 Mr.shahabb Elk 3

    6/29

    © ABB GroupMarch 26, 2014 | Slide 6

    Proven technologySame components in GIS and ELK Hybrid

    Product M mt

    circuit breaker 

    earthing switch

    current transformer 

    bushing

    disconnector 

  • 8/18/2019 Mr.shahabb Elk 3

    7/29

    ELK Hybrid Switchgear Standard Module

    © ABB GroupMarch 26, 2014 | Slide 7

    Product M mt

    circuit breaker 

    earthing switch

    current transformer 

    bushing

    disconnector 

  • 8/18/2019 Mr.shahabb Elk 3

    8/29

    ELK Hybrid Switchgear Diameter in 1 1/2, 6 Bays

    © ABB GroupMarch 26, 2014 | Slide 8

    Product M mt

    ELK Hybrid Standard

    Module

    Conventional equipment

  • 8/18/2019 Mr.shahabb Elk 3

    9/29

    ELK Hybrid Switchgear Diameter in 1 1/2, 6 Bays

    © ABB GroupMarch 26, 2014 | Slide 9

    Product M mt

    ELK Hybrid Standard

    Module

    Conventional equipment

    Fast, simple to integrate

  • 8/18/2019 Mr.shahabb Elk 3

    10/29

    ELK Hybrid Switchgear Diameter in 1 1/2, 6 Bays

    © ABB GroupMarch 26, 2014 | Slide 10

    Product M mt

    ELK Hybrid Standard

    Module

    Conventional equipment

    Compact footprint

  • 8/18/2019 Mr.shahabb Elk 3

    11/29

    ELK Hybrid Switchgear Customized Module, double busbar 

    © ABB GroupMarch 26, 2014 | Slide 11

    circuit breaker 

    earthing switch

    current transformer 

    bushing

    disconnector 

    Fast acting earthing

    switch

    Connection elements

  • 8/18/2019 Mr.shahabb Elk 3

    12/29

    ELK Hybrid Switchgear Customized Module, double busbar 

    © ABB GroupMarch 26, 2014 | Slide 12

    ELK Hybrid Customized

    Modul

    Conventional equipment

  • 8/18/2019 Mr.shahabb Elk 3

    13/29

    ELK Hybrid Switchgear Customized Module, double busbar 

    © ABB GroupMarch 26, 2014 | Slide 13

    ELK Hybrid Customized

    ModulFull flexibility to adapt to customer

    needs, i.e. busbar configuration

    Conventional equipment

  • 8/18/2019 Mr.shahabb Elk 3

    14/29

    Proven technology

    © ABB GroupMarch 26, 2014 | Slide 14

    ELK components reliability

    Outdoor experience since 1974

    i.e. Live tank SF6 circuit breakers

    three times higher major failure

    frequency than GIS or metal

    enclosed units;

    CIGRE VALUES

    Product M mt

    5 year warranty

  • 8/18/2019 Mr.shahabb Elk 3

    15/29

    © ABB GroupMarch 26, 2014 | Slide 15

    Reduced execution time

    Engineering

    Installation

    Delivery

    Site Preparation

    Depending on configuration and voltage level

    Time savings can be achieved by

    Engineering Standardization 20%

    Site Preparation 50%

    Delivery 30%

    Installation 20%

    Engineering

    Installation

    DeliverySite Preparation

       H  y   b  r   i   d

       A   I   S

    Product M mt

  • 8/18/2019 Mr.shahabb Elk 3

    16/29

    © ABB GroupMarch 26, 2014 | Slide 16

    Reduced execution time

    Product M mt

  • 8/18/2019 Mr.shahabb Elk 3

    17/29

    © ABB GroupMarch 26, 2014 | Slide 17

    Small footprint

    ConventionalAIS

    13’104m2

    100%

     

    3’786m2

    29%

    HybridAIS

    up to 70% reduction

    Product M mt

  • 8/18/2019 Mr.shahabb Elk 3

    18/29

    © ABB GroupMarch 26, 2014 | Slide 18

    Operational safety

    Drives are accessible from

    ground level

    Inspection from ground level

    to view ports

    Product M mt

  • 8/18/2019 Mr.shahabb Elk 3

    19/29

    Simple integration

    © ABB GroupMarch 26, 2014 | Slide 19

    Product M mt

    Mount bushings

    LCC, SC and wiringGas filling

    Commissioning of entire MTS

    installation

    Placing modules

    HV-Test

    for quality insurance(transport damages)

    Product supplier Substation Integrator  

    LCC SC

    Civil work, S/S earthing

    module earthing

  • 8/18/2019 Mr.shahabb Elk 3

    20/29

    © ABB GroupMarch 26, 2014 | Slide 20

    Multi purposes

    AIS Extensions

    Retrofit of AIS

    New Installation

    Product M mt

  • 8/18/2019 Mr.shahabb Elk 3

    21/29

    © ABB GroupMarch 26, 2014 | Slide 21

    Technical RatingsELK Hybrid

    Technical Data ELK-3 420 Hybrid

    Rated voltage kV 420

    Rated power-frequency withstand voltage kV 650

    Rated power-frequency withstand voltage across open

    contacts

    kV 800

    Rated lightning impulse withstand voltage kV 1425

    Rated lightning impulse withstand voltage across open

    contacts

    kV 1425+345

    Rated switching impulse withstand voltage kV 1050

    Rated switching impulse withstand voltage across open

    contacts

    kV 1050+345

    Rated frequency Hz 50 / 60

    Rated continuous current A 4000

    Rated short-time withstand current kA 63

    Rated peak withstand current kA 170

    Bus Transfer switching current A/V 1600 / 300

    3200 / 300

     Ambient temperature °C standard -30 / +55

    mixed gas or

    heating mats -50 / +55

    Creepage distance of bushing mm/kV 31

  • 8/18/2019 Mr.shahabb Elk 3

    22/29

    Fast acting disconnector ELK-TK3S

    Bus-transfer switching

    ABB Power Products High Voltage, Gas-Insulated Switchgear 

  • 8/18/2019 Mr.shahabb Elk 3

    23/29

    ELK-TK3S

    Disconnectors can be used for bustransfer switching, e. g. in double or 

    multiple busbar arrangements of 

    SF6 gas insulated substations (GIS).

    Switching sequence for the current

    transfer in a GIS with double busbar:

    Closing of disconnector No. 2 yields

    distribution of the load current “I” onto

    the two parallel paths “I1” and “I2” ac-

    cording to the relation of the impe-

    dances of both sections. Opening of 

    disconnector No. 1 in the third scheme

    leads to the transfer of the load current

    part “I1” from bus A to bus B.

    Bus-transfer switching

    © ABB Group

  • 8/18/2019 Mr.shahabb Elk 3

    24/29

    Rated voltage Ur kVA

    Air-insulated

    disconnectors

    V r.m.s.

    Gas-insulated disconnectors

    V r.m.s.

    52

    72.5

    100

    123

    145170

    110 10

    245

    300

    362

    20020

    420

    300550800

    40

    IEC: The value of the rated bus-transfer current for both air- and gas-insulated

    disconnectors shall be 80 % of the rated normal current. It will normally not

    exceed 1600 A, irrespective of the rated normal current of the disconnector.

    Rated bus-transfer voltages for disconnectorsIEC 62271-102

    © ABB Group

    IEC 1600 A / ABB 3200 A

  • 8/18/2019 Mr.shahabb Elk 3

    25/29

    ELK-TK3S

     All disconnectors of ABB type ELK are tested according to

    IEC 62271-102 and they fulfilled completely the IEC

    requirements.

    References: IEC 62271-102, Alternative current

    disconnectors and earthing switches; Annex B, Bus-

    transfer current switching by disconnectors

    Conclusion

    © ABB Group

  • 8/18/2019 Mr.shahabb Elk 3

    26/29

    © ABB GroupMarch 26, 2014 | Slide 26

    ELK-TK3SType test at PHELA performed successfully

    3200 A

    300 V

    100 CO, DIT

  • 8/18/2019 Mr.shahabb Elk 3

    27/29

    ELK-TK3SType tests archived

    Type test archived

    Mechanical endurance 10000 CO 3-ph

    Bus charging current switching TD1, TD2, TD3

    Operation at limit temperature -30 °C / +55 °C

    Bus transfer current switching 3200 A / 300 V

    © ABB GroupMarch 26, 2014 | Slide 27

  • 8/18/2019 Mr.shahabb Elk 3

    28/29

    ELK-TK3SExample ELK-3 Hybrid Switchgear, 420 kV

    © ABB Group