mri-v...characteristics in accordance with bs142 and iec 255-4. furthermore, the mri-v has an...
TRANSCRIPT
2/5/96 0 MRI-V 01/96H
MRI-V Digital Multifunctional Relay for Voltage
Controlled Overcurrent Protection
P&B Engineering
Belle Vue Works
Boundary Street
Manchester
M12 5NG
Tel: 0161 230 6363
Fax: 0161 230 6464
2/5/96 i MRI-V 01/96H
Contents
1. INTRODUCTION ........................................................................................................................................................ 1
2. APPLICATION ............................................................................................................................................................ 2
3. FEATURES AND CHARACTERISTICS.................................................................................................................. 2
4. DESIGN......................................................................................................................................................................... 3
4.1 CONNECTIONS ........................................................................................................................................................... 3
4.1.1 Analogue input circuits...................................................................................................................................... 3
4.1.2 Output relays ..................................................................................................................................................... 3
4.1.3 Remote data communication.............................................................................................................................. 4
4.1.4 Blocking Input ................................................................................................................................................... 4
4.2 FRONT PANEL............................................................................................................................................................. 4
4.2.1 Display............................................................................................................................................................... 4
4.2.2 LED indicators .................................................................................................................................................. 6
4.2.3 Push buttons ...................................................................................................................................................... 6
4.3 CODE JUMPERS .......................................................................................................................................................... 6
4.3.1 Password programming..................................................................................................................................... 7
4.3.2 Alarm and Trip relay function ........................................................................................................................... 7
5. WORKING PRINCIPLES........................................................................................................................................... 8
5.1 ANALOGUE CIRCUITS ................................................................................................................................................. 8
5.2 DIGITAL CIRCUITS ...................................................................................................................................................... 8
5.3 POWER SUPPLY .......................................................................................................................................................... 8
5.4 VOLTAGE DEPENDENT TRIPPING CHARACTERISTIC ................................................................................................... 9
5.5 REQUIREMENTS FOR THE MAIN CURRENT TRANSFORMERS...................................................................................... 10
5.6. RESET DELAY & DWELL TIME.................................................................................................................................. 10
6. OPERATION AND SETTING.................................................................................................................................. 10
6.1 LAYOUT OF THE CONTROL ELEMENTS ...................................................................................................................... 10
6.2 RELAY SETTING PRINCIPLES ..................................................................................................................................... 11
6.2.1 Password protected parameter adjustment ..................................................................................................... 11
6.3 SETTING PROCEDURE ............................................................................................................................................... 12
6.3.1 Starting current for phase overcurrent relay (Isn and Isl) .............................................................................. 12
6.3.2 Time current Characteristic (CHAR I>).......................................................................................................... 12
6.3.3 Tripping time delay or time multiplier for overcurrent (tI>)........................................................................... 12
6.3.4 Current setting for high set overcurrent stage (I>>)....................................................................................... 13
6.3.5 Tripping time delay for high set overcurrent stage (tI>>) .............................................................................. 13
6.3.6 Setting of the Undervoltage Switching Point ................................................................................................... 13
6.3.7. Reset & Dwell ................................................................................................................................................. 13
6.3.8 Nominal frequency........................................................................................................................................... 13
6.4 INDICATION OF MEASURED VALUES AND FAULT DATA ............................................................................................. 13
6.4.1 Indication of measured values ......................................................................................................................... 13
6.4.2 Indication of fault data .................................................................................................................................... 14
6.5 TEST TRIP ................................................................................................................................................................ 14
6.6 RESET ...................................................................................................................................................................... 14
6.6.1 Hand reset........................................................................................................................................................ 14
6.6.2 Auto-reset at Power Up ................................................................................................................................... 14
6.7 SETTING VALUE CALCULATION ................................................................................................................................ 14
2/5/96 ii MRI-V 01/96H
7. RELAY CASE............................................................................................................................................................. 15
7.1 INDIVIDUAL CASE..................................................................................................................................................... 15
7.2 RACK MOUNTING ..................................................................................................................................................... 15
7.3 TERMINAL CONNECTIONS ........................................................................................................................................ 15
8. TEST AND MAINTENANCE ................................................................................................................................... 15
9. TECHNICAL DATA.................................................................................................................................................. 16
9.1 MEASURING INPUT CIRCUITS ................................................................................................................................... 16
9.2 AUXILIARY POWER SUPPLY ...................................................................................................................................... 16
9.3 COMMON DATA........................................................................................................................................................ 16
9.4 SETTING RANGES AND STEPS.................................................................................................................................... 17
9.4.1 Definite time phase overcurrent relay ............................................................................................................. 17
9.4.2 Inverse time phase overcurrent relay .............................................................................................................. 17
9.5. INVERSE TIME CHARACTERISTICS............................................................................................................................ 18
9.6 OUTPUT CONTACT RATINGS ..................................................................................................................................... 19
9.7 SYSTEM DATA.......................................................................................................................................................... 19
9.8 HOUSING.................................................................................................................................................................. 20
9.9 TERMINAL CONNECTION DETAILS ........................................................................................................................... 21
10. ORDER FORM......................................................................................................................................................... 22
2/5/96 1 MRI-V 01/96H
1. Introduction
The application of powerful microprocessors opens a new chapter for power system
protective relaying. The digital processing of measured values and the ability to perform
complex arithmetic and logic operations, give digital protection relays significant
performance and flexibility improvements over their traditional analogue counterparts.
Additional advantages - very small power consumption, adaptability, self-supervision, fault
diagnosis through fault data recording, smaller physical construction and selectable relay
characteristics - all combine to allow the implementation of accurate and highly reliable
protection schemes at a significantly reduced financial burden.
The development of microprocessor based protective relays and their introduction into the
market has been stimulated by the recent trend to replace analogue with digital equipment.
This modern trend has prompted the development of a new P&B protective relay family - the
MR relay series. This comprehensive family of protection relays can satisfy the demands of
even the most complex protection schemes:
MRI - Overcurrent Relay (Independent time/I.D.M.T + earth + directional facilities)
MRI-V - Voltage Dependent Overcurrent Relay
MREF - Restricted Earth Fault Relay
MRAR - Auto-Reclosing Relay
MRMF - Mains Failure Relay
MRVT - Voltage Protection
MRFT - Frequency Protection
MROS - Vector Surge or Rate of Change of Frequency
MRNS - Negative Sequence Relay
MRRP - Power Relay
MRCS - Check Synchronising Relay
MRFF - Field Failure Relay
MRDG - Differential Relay
The superiority of digital protective relaying over traditional analogue devices, as embodied
by the MR relay family, is summarized by the following features:
•••• Integration of many protective functions in a single compact case
•••• High accuracy owing to digital processing
•••• Digital relay setting with very wide setting ranges and fine setting steps
•••• Comfortable setting procedure through extensive human - relay dialogue
•••• Measured values and fault data indication by means of alpha-numeric display
•••• Data exchange with DCS/SCADA by means of RS485
•••• Operational reliability through self-supervision
A similar but simplified range, with reduced functions and without display, is also available.
The MIRI - overcurrent and earth fault relays, and the MIRV - undervoltage, overvoltage
and neutral voltage displacement relays. To complement the MR series, a range of Auxiliary,
Timing and Tripping devices are also available.
2/5/96 2 MRI-V 01/96H
2. Application
The MRI-V digital voltage dependent overcurrent relay is a universal multifunctional
protection device for medium voltage networks. It offers both Definite Time and Inverse
Definite Minimum Time (IDMT) overcurrent protection in a single compact unit. IDMT
protection is also selectable between Normal Inverse, Very Inverse and Extremely Inverse
characteristics in accordance with BS142 and IEC 255-4. Furthermore, the MRI-V has an
adjustable undervoltage switching point and may be employed as protection for voltage loss
during short circuit of the generator where the decreasing current supplied may be lower than
the full load conditions prior to the fault. The protective functions of the MRI-V are
summarized as follows:
• Selectable protective functions between :
- Definite time overcurrent relay
- Inverse time overcurrent relay
• Inverse definite minimum time (IDMT) overcurrent relay with the following
selectable characteristics in accordance with BS 142 and IEC 255-4:
- Normal Inverse
- Very Inverse
- Extremely Inverse
• Two stage overcurrent relay
• High set overcurrent unit with instantaneous or definite time function
• Voltage controlled tripping characteristic
3. Features and characteristics
• Complete digital processing of the sampled measured values
• Digital filtering of measured values using discrete fourier analysis to
suppress high frequency harmonics and d.c component induced by faults or
system operations
• Extremely wide setting ranges with fine setting steps
• Unauthorized user access control through password protection
• User defined password
• Continuous self-supervision of software and hardware
• Outstanding design flexibility for easy selection of appropriate operational
scheme for numerous applications
• Numerical display of setting values, actual measured values and
memorized fault data etc.
• Serial data communication facilities via RS485
• Wide voltage range for DC or AC power supply
• Withdrawable modules with automatic short circuit of C.T. inputs
2/5/96 3 MRI-V 01/96H
4. Design
4.1 Connections
Application Diagram;
POWER
SUPPLY
1 2 CASE
Supply
MRI-VTypical Earthing Shown
54 5553External Reset Blocking Input
L N L
TRIP SIGNAL
ALARM
INDICATION
33
31
29
32
3034
4852
50
45
43
41
44
4246
40
38
36
37
3539
+
7 9 10
Gnd-
SELF SUPERVISION
I>>
I>
RS485
19
15
17
21
22
23
24
25
26
L1
L2
L3
I1
I2
I3
S2P2
P1
S1
AlternativeEarthing
L 1-2
L1-3
4.1.1 Analogue input circuits
The constantly detected measuring values are galvanically decoupled, filtered and finally fed
to the analogue/digital converter. The protection unit receives these analogue input signals
for the phase currents I1, I2 & I3, and phase to phase voltages V12, V23 & V31.
4.1.2 Output relays
The MRI-V has four output relays, with single or dual pole change-over contacts as detailed
in the previous diagrams and summarized below:
• Tripping relay (2)
• Self-supervision alarm relay (1)
• High set overcurrent relay (2)
• Low set overcurrent relay (2)
2/5/96 4 MRI-V 01/96H
4.1.3 Remote data communication
As an option, the MRI-V may have an RS485 interface for remote data communication with
a control centre. The unit provides the following information:
• Measured phase fault current values
• Status signals
• Self supervision alarm signal
• Actual measured current values
• Relay settings
• Phase fault signalling
4.1.4 Blocking Input
When required to inhibit the high set function I>>, the auxiliary supply is connected to the
blocking input terminals, 54-55.
4.2 Front panel
The front panel of the MRI-V comprises the following operation and indication elements:
• Alphanumeric display (4 Digits)
• 5 push buttons for setting and other operations
• 10 LEDs for measured value indication and setting
4.2.1 Display
The measured and set values, and recorded fault data, are shown alphanumerically on the
display. The meaning of the displayed values is easily interpreted from the LED indicators on
the front panel.
2/5/96 5 MRI-V 01/96H
Table: Adjustment possibilities by means of the display
Function Display Shows Pressed push button
and system reply
Illuminated LED
Measured operating
values (phase current)
Actual measured current
value, related to In
<SELECT> L1, L2, L3
Measured operating
values (line voltages)
Actual measured voltage
value, related to Vn
<SELECT> L1, L2, L3,V
Recorded fault data Tripping current in L1,
L2, L3
<SELECT> L1, L2, L3, I>,
I>>,V
Setting value current settings I>, I>>
related to In
voltage switch value
related to Vn
trip time delay in second
time multiplier
Characteristics:
- DEFT
- NINV
- VINV
- EINV
function Inhibited -
EXIT
<SELECT>
<UP>
<DOWN>
I>, CHARI>, tI>,
I>>, tI>>, V
Reset delay Os or 60s <SELECT>
<UP>
<DOWN
I> CHAR I
tI.>
Dwell time 200 or auto < SELECT>
<UP>
<DOWN.
Nominal frequency f = 50, f = 60 <SELECT>
<UP>
<DOWN>
Normal operation P&B <SELECT> long -
system reset
Inquire password PSW? <ENTER> / <TRIP>
Save parameter? SAV? <ENTER>
Save parameter SAV! <ENTER>
Manual trip TRI? <TRIP>
Relay is tripped TRIP <TRIP> / or system
reply
L1, L2, L3, I> or
I>>
Secret password XXXX Push-button
combination S,∨,∧,E
Maximum measuring
range reached
max. System reply L1, L2, L3
2/5/96 6 MRI-V 01/96H
4.2.2 LED indicators
The LEDs to the left of the display indicate measuring or tripping values. The purpose of the
corresponding LED is identified by the adjacent inscription, (e.g. L2 for current in phase 2).
The first row of three LEDs to the left of the display are bi-coloured - green indicates
measuring and red indicates fault condition.
The LED marked RS indicates active serial data communication.
Five LEDs support the setting menu selection. They are arranged at the characteristic points
on the setting curve and indicate the corresponding menu point selected.
4.2.3 Push buttons
The front panel contains five push buttons used for setting, measuring and other user
functions.
The individual setting and measuring values can be selected in turn by pressing the
<SELECT> / <RESET> push button. This button also resets the relay if pressed for
approximately 3 seconds.
The <UP> and <DOWN> push buttons are for incrementing and decrementing any selected
parameter. Continuous pressing of these push buttons will cause the parameter to change at
an increased rate.
The <ENTER> push button is used to transfer the indicated value to the internal parameter
memory. An unintended or unauthorized change of the selected parameter can be avoided
through the password protection facility.
The <TRIP> push button is used to test the output relay circuits, both for tripping and
signalling. This operation is also password protected.
4.3 Code jumpers
Behind the front panel of the MRI-V are three code jumpers used to preset the following
functions:
•••• Password programming
•••• Alarm and Trip relay functions
The following figure shows the position and designation of the code jumpers
J3 J2 J1
Code Jumper ON
Code Jumper OFF
Front Board
Code Jumper
2/5/96 7 MRI-V 01/96H
4.3.1 Password programming
The MRI-V relay is normally delivered with the preset password "∧∧∧∧". It can be
reprogrammed using the removable code jumper J1. After power on and the pressing of any
push button, the MRI-V relay enquires for a new password with the text <PSW?> appearing
on the display. A new password is then entered by pressing a combination of <SELECT>,
<UP>, <DOWN> or <ENTER>, as chosen by the user. After the new password has been
given, the relay module is extracted from its case and code jumper J1 removed.
4.3.2 Alarm and Trip relay function
The following functions of the MRI-V alarm relays may be preset using jumpers J1 & J2:
•••• Alarm relay activation upon initiation or after a trip
•••• Manual or Automatic reset of the output relays
Code jumper J2 - OFF
The alarm relays respond directly upon the initiation of the corresponding measuring
circuit. Thus, an alarm signal, e.g. for overcurrent, will be given before the relay trips.
Code jumper J2 - ON
The alarm relay responds only after the relay has tripped. Thus, the alarm relay and the
trip relay respond at the same time.
Code jumper J3 - OFF
All output relays will be reset automatically after tripping, once the fault has been
cleared.
Code jumper J3 - ON
All output relays remain activated and must be reset manually by pressing the
<RESET> push button, after the fault has been cleared.
Summarizing the coding possibilities
Code jumper Function Code jumper Position Operation Mode
J1 Password OFF
ON
Normal position
Password programming
J2 Alarm Relays OFF
ON
Alarm relays will be
activated on energizing.
Alarm relays will be
activated upon tripping.
J3 Reset OFF
ON
Output relays will be reset
automatically.
Output relays will be reset
manually.
2/5/96 8 MRI-V 01/96H
5. Working principles
5.1 Analogue circuits
The incoming currents from the external current transformers are converted to internal signals in
proportion to the currents, via the internal input transducers and shunt resistors. The noise signals
caused by inductive and capacitive coupling are suppressed by an analogue RC filter circuit. The
analogue signals are fed to the A/D converter of the micro-processor and transformed to digital
signals through sample-hold circuits. The analogue signals are sampled with a sampling frequency
of 800 Hz, namely a sampling rate of 1.25 mS for every measured quantity.
The incoming voltages from the external voltage transformers are fed to operational amplifiers
through the input transducers and RC filters.
5.2 Digital circuits
The essential component of the MRI-V relay is a powerful micro-controller. All of the operations,
from the analogue digital conversion to the relay trip decision, are carried out by the micro-
controller digitally. The relay program, located in EPROM, allows the CPU of the micro-
controller to calculate the three phase currents to detect a possible fault.
For the calculation of the current value, an efficient digital filter, based on the Fourier Analysis
(DFFT - Discrete Fast Fourier Transformation), is applied to suppress high frequency harmonics
and DC components caused by fault induced transients or other system disturbances. The actual
calculated current values are compared with the relay settings. When a current exceeds the starting
value the unit starts the corresponding time delay calculation. When the set time delay has elapsed,
a trip signal is given.
The relay setting values for all parameters are stored in EEPROM, so that the actual relay settings
cannot be lost, even in the event of auxiliary supply interruption. The micro-processor is
supervised through a built in "Watch-dog" timer. Should a failure occur the watch-dog timer resets
the micro-processor and gives an alarm signal via the self supervision output relay.
5.3 Power supply
Two auxiliary power supply versions are available:
Vaux = 24V in a range from 16V to 60V AC
or in a range from 16V to 80V DC
Vaux = 110V in a range from 50V to 270V AC
or in a range from 70V to 360V DC
2/5/96 9 MRI-V 01/96H
5.4 Voltage Dependent Tripping Characteristic
The MRI-V is the combination of an overcurrent time relay (MRI basic unit) and an additional
undervoltage supervision unit.
The undervoltage unit has an influence on the tripping time of the overcurrent and short circuit
steps by switching in two tripping characteristics. In normal operation, at nominal voltage, the
MRI-V operates like a normal overcurrent time relay with preselected tripping characteristics
(IDMT, DMT) and an adjusted response value, Is. The following diagram shows the switching
over to another value of Is. Isn is the response value during normal operation and IsL is the value
during low voltage.
I>>L I>>NISNISL
→←
→←
Tripping characteristic as
selected in 6.3.2 & 6.3.3
Movement of trip level
upon switchover due
to undervoltage
In the case of failure, a short circuit of the alternator, the alternator voltage decreases. The MRIV
will recognize this and then switch over without delay to a lower response value of Is. The value
of IsL can be adjusted and as a result shorter tripping periods of the overcurrent and short circuit
step can be achieved. The adjusted tripping characteristics; normal inverse, very inverse,
extremely inverse or IDMT; is maintained. The undervoltage switching point can be adjusted from
10% to 100% of Vn. The reduced level of Is may be independently changed for both I> & I>>.
Other adjustable ranges are given in the technical data section.
2/5/96 10 MRI-V 01/96H
5.5 Requirements for the main Current Transformers
In order to ensure the correct operation of the MRI-V range of relays, protection class CT's must
be utilized. Instrument CT's are NOT a suitable alternative.
CT's should be chosen such that saturation, or loss of accuracy does not occur within the settings
and operation ranges of the relays. In the absence of known settings the following may be regarded
as an approximate guide.
For 1A secondary
CT class 5P20 or 10P20 2.5VA (Allowing for up to 1Ω of secondary lead resistance)
For 5A secondary
CT class 5P20 or 10P20 5VA (Allowing for up to 0.5Ω of secondary lead resistance)
with due regard to a suitable CT ratio and fault level capacity.
5.6. Reset delay & dwell time
In order to provide better discrimination with Electromechanical relays two additional settings are
provided. The reset delay delays the reset of the relay following a Flashing Fault which simulates
the time an electromechanical relay takes in order to “wind back” a partially rotated Disk (IDMT).
This may be selected as 0 or 60 seconds.
The dwell time, is an additional delay introduced on the output contacts used to prevent the
contacts opening during a tripping action. This may be selected as 0 or 200 mS.
6. Operation and setting
6.1 Layout of the control elements
All control elements required for the operation and adjustment of the MRI-V are located on the
front panel. They are divided according to function into the three following groups:
• Alphanumeric Display: Indication of parameter set values, actual measured values and
recorded fault data.
• LED's: Indication of selected parameters and measured quantities.
• Push Buttons: Selection of parameter to be adjusted, quantity to be measured and
adjustment of parameter values. Where;
<SELECT / RESET> Selection of the parameter to be set and the relay quantities
to be measured. Continuous pressing as the reset function.
<UP> Increment of the setting values for the parameter selected.
<DOWN> Decrement of the setting values for the parameter selected.
<ENTER> Storage of the setting values for the selected parameter.
<TRIP> Testing of the output relay circuits.
2/5/96 11 MRI-V 01/96H
6.2 Relay setting principles
There are eight relay parameters that can be set in the MRIV:
Isn - Value of the overcurrent step during normal operation
IsL - Value of the overcurrent step during undervoltage.
CHAR I> - Current time characteristic for the overcurrent relay.
tI> - Tripping time delay for definite time overcurrent relay or the time multiplier
for the inverse time overcurrent relay.
I>>N - Current setting for the high set stage of the phase overcurrent relay.
I>>L - Value for the fast short circuit tripping during undervoltage.
tI>> - Tripping time delay for high set stage.
V - Tripping value for undervoltage supervision.
By pressing the <SELECT/RESET> push button, the parameter to be modified is reached. The
corresponding LED illuminates on the curve and the present set value of the selected parameter is
indicated on the display. This set value may then be increased or decreased by pressing the <UP>
or <DOWN> buttons respectively. The selected set value is only stored after pressing the
<ENTER> push button and inputting the correct password. This means that adjustment of the unit
is only possible by authorized users.
6.2.1 Password protected parameter adjustment
The adjustment of all relay settings are password protected, however, to enable ease of adjustment,
for authorized users, application of the password is usually only required once for multiple
parameter adjustment. The following step by step sequence is given to illustrate the
implementation of the password protection facility, where a new relay setting is to be applied:
• After the present setting value has been selected and changed using the <UP>,
<DOWN> push buttons, the <ENTER> push button should be pressed.
• The message <SAV?> appears on the display, to confirm that the new setting value
is to be saved.
• After pressing <ENTER> again, the password will be requested. The message
<PSW?> is displayed.
• After the password has been given correctly, as indicated by the message <SAV!>,
the new setting value may be stored by pressing the <ENTER> push button for at
least 3 seconds. The new setting parameter then reappears on the display.
A password consists of four push button operations. The pressed push buttons and their sequence
define the password. If the four push buttons are defined by the following symbols:
<SELECT> = S
<DOWN> = ∨∨∨∨
<UP> = ∧∧∧∧
<ENTER> = E
Then a password "∨∨∨∨E∧∧∧∧S" is achieved by the following sequence:
<DOWN> <ENTER> <UP> <SELECT>.
2/5/96 12 MRI-V 01/96H
After a password is given correctly, parameter setting is permitted for five minutes. Subsequent
parameter setting made within the five minute period after the password was inputted, does not
require renewed password entry. Furthermore, the valid period for parameter setting is
automatically extended for a further 5 minutes after each push button operation.
If no push button is pressed within the 5 minute period then the validity of the password will be
suspended. To enter further parameters after this period re-application of the password is required.
During the 5 minute period when changes may be made, a new set value, acknowledged by
<SAV?> then <SAV!> , may be stored by pressing <ENTER> for approximately 3 seconds.
6.3 Setting procedure
The following sections describe in detail the setting of all relay parameters.
6.3.1 Starting current for phase overcurrent relay (Isn and Isl)
The displayed setting value for these parameters are related to the nominal rated current (IN) of
the relay. Thus;
Starting current (Isn) = Displayed Value x Rated Current (IN)
e.g. If Displayed Value = 1.25, then Isn = 1.25 x IN
The setting of the Isl value is indicated by the I> LED flashing.
6.3.2 Time current Characteristic (CHAR I>)
By setting this parameter, one of the following four options is displayed:
DEFT - Definite Time
NINV - Normal Inverse
VINV - Very Inverse
EINV - Extremely Inverse
Any one of these four characteristics can be chosen by using the <UP> <DOWN> keys and can be
stored by pressing <ENTER>.
6.3.3 Tripping time delay or time multiplier for overcurrent (tI>)
After the time/current characteristic has been selected, the time delay (or time multiplier) should
be changed accordingly. In order to avoid an unsuitable arrangement of relay modes the following
precautions are taken:
Adjustment of the time delay setting is automatically prompted for after a change in the set
time/current characteristic. LED tI> flashes yellow to remind the operator to change the time
delay setting accordingly. After pressing the <SELECT> push button, the present time delay
setting value is shown on the display. A new setting value may then be entered.
If the relay characteristic has been changed (e.g. from DEFT to NINV), but the time delay
setting has not, the relay will, after 5 minutes, automatically set itself to the most sensitive time
setting value available for that selected characteristic. The most sensitive time setting value
implies the fastest tripping for the selected relay characteristic. If the time delay or the time
multiplier is set out of range, "EXIT" appears on the display, and the low set stage of the relay
is blocked.
2/5/96 13 MRI-V 01/96H
6.3.4 Current setting for high set overcurrent stage (I>>)
The current setting value of this parameter is related to the nominal rated current of the relay.
Thus;
I>> = Displayed Value x Rated Current (IN)
e.g. If Displayed Value = 20, then I>> = 20 x IN
The high set stage of the overcurrent relay is blocked if the setting value is set to "EXIT".
6.3.5 Tripping time delay for high set overcurrent stage (tI>>)
Independent from the chosen tripping characteristic for I>, the high set stage I>> always has a
definite time tripping characteristic. An indication value in seconds appears on the display.
6.3.6 Setting of the Undervoltage Switching Point
The voltage setting value of this parameter is related to the nominal rated voltage of the relay, Vn.
Thus;
Undervoltage Switching Point, V = Displayed Value x Vn
e.g. If Displayed Value = 0.5, then V = 0.5 x Vn
The setting of the undervoltage switching point value is indicated by the LED flashing.
6.3.7. Reset & Dwell
If co-ordination with electromechanical relays is required tRST should be set to 60s, tTrip to Auto.
Otherwise tRST should be set to 0, tTrip to 20mS.
6.3.8 Nominal frequency
The FFT Algorithm employed requires the nominal frequency as a parameter for correct digital
filtering of the input currents.
By pressing <SELECT> the display shows "f=50" or "f=60". The desired nominal frequency may
then be selected and stored.
6.4 Indication of measured values and fault data 6.4.1 Indication of measured values
Any one of the following measured quantities may be indicated on the display during normal
service by pressing the <SELECT> button:
• Current in Phase 1 (LED L1 green)
• Current in Phase 2 (LED L2 green)
• Current in Phase 3 (LED L3 green)
• Phase to Phase Voltage, V12 (L1, L2 and V LED's Green)
• Phase to Phase Voltage, V23 (L2, L3 and V LED's Green)
• Phase to Phase Voltage, V31 (L3, L1 and V LED's Green)
The relevant operating values of the individual measured quantities are indicated on the display
and are referred to the rated current and voltage.
2/5/96 14 MRI-V 01/96H
6.4.2 Indication of fault data
Visual indication of faults detected by the relay is given on the front panel. The three phase LEDs
L1, L2, L3, the undervoltage LED, as well as the function LEDs I>, and I>> are used to
indicate/specify fault events.
When a fault initiates a relay function, the corresponding function LED illuminates yellow. At the
same time, the phase LED(s) flash(es) red to indicate the faulty phase or phases.
After the set time delay has elapsed, the relay trips and the LED(s) for the faulty phase(s) become
a constant red. The function LED remains illuminated. The fault currents measured at the instant
of trip are recorded in registers for fault indication.
After the occurrence of a trip, fault data for all three phase currents may be displayed in turn by
repeatedly pressing the <SELECT> key. After all phases have been indicated, the LEDs return to
red indicating the fault event. By pressing the <SELECT/RESET> button for approximately 3
seconds the relay is reset to its original status. If however, the relay was initiated by the occurrence
of a fault, which then fell below a detectable level, a slowly flashing LED corresponding to the
detected fault is displayed. This can also be reset using the <SELECT/RESET> button.
6.5 Test Trip
The whole tripping circuit of the protection system may be tested by simulating a fault with the
<TRIP> push button. This button is also used to interrogate the relay for its software version
number. A single press reveals the first half of the software version number and a second press
reveals the second half. A third press will be responded to by <PSW?>. Entering the correct
password will be responded to by <TRI?> . Pressing <TRIP> again energizes all output relays in
turn with a delay time of 1 second. All relays will stay energized until manually reset.
6.6 Reset
There are two ways in which to reset the MRI-V relay:
6.6.1 Hand reset
By pressing the <SELECT/RESET> for approximately 3 seconds the relay is reset.
6.6.2 Auto-reset at Power Up
After loss of supply voltage and upon its reconnection the unit resets itself and displays P&B.
This resetting of the unit does not effect the set parameters which are stored in an EEPROM.
6.7 Setting value calculation
In order to ensure that protection relays form an integral part of any system, a full protection co-
ordination study should normally be undertaken which considers both upstream and downstream
equipment. Further details may be obtained by contacting P&B Engineering.
2/5/96 15 MRI-V 01/96H
7. Relay case
The MRI-V is delivered in an individual case for flush mounting.
7.1 Individual case
The MRI-V is supplied in a UK manufactured industry standard drawout case suitable for flush
mounting. For case dimension and cut-out, refer to Technical Data.
7.2 Rack mounting
MRI-V relays may be supplied mounted in 19" racks if specified by the user.
7.3 Terminal connections
The MRI-V plug in module is supplied in a case which has a very compact plug and socket
connector. The current terminals are equipped with self closing short circuit contacts. Thus the
MRI-V module can be unplugged even with current flowing without endangering personnel.
8. Test and maintenance
Currents may be supplied to the input transformers to test the behaviour of the relay. By switching
on test currents and measuring the tripping time, the whole system can be accurately tested. A
portable overcurrent test case can be supplied which is suitable for testing the MRI-V.
All measuring input circuits of the MRI-V are of static design and the relay functions are fully
digitized. Thus, the MRI-V has no particular demand on maintenance.
2/5/96 16 MRI-V 01/96H
9. Technical Data
9.1 Measuring Input Circuits
Rated Data
Rated current, IN 1A or 5A
Rated voltage, VN 110V, 230V or 400V
Rated frequency, fN 50Hz, 60Hz
Power consumption
@ IN = 1A 0.2 VA
@ IN = 5A 0.1 VA
In voltage circuit < 1 VA
Thermal withstand
Half wave 250 x IN
for 1 second 100 x IN
for 10 seconds 30 x IN
Continuously 4 x IN
In voltage circuit 1.2 x VN
9.2 Auxiliary power supply
Supply Voltage
Vaux = 24V in a range from 16V to 60V AC
or in a range from 16V to 80V DC
Vaux = 110V in a range from 50V to 270V AC
or in a range from 70V to 360V DC
Power Consumption
Quiescent Approx. 3W
Operating Approx. 6W
9.3 Common data
Drop Off/Pick Up ratio >97%
Drop Off time 30mS
Time Lag error ± 10mS
Minimum operating time 30mS
Transient over-reach £ 5%
Factors effecting current measurement:
Auxiliary voltage No changes measured
Frequency harmonics in the range 0.9 < f/fN < 1.1 = < 0.02% /Hz
Up to 20% of the third harmonic = < 0.08% /Hz
Up to 20% of the fifth harmonic = < 0.07% /Hz
Factors effecting delay times:- No influences could be measured.
2/5/96 17 MRI-V 01/96H
9.4 Setting ranges and steps
9.4.1 Definite time phase overcurrent relay
Setting range / step Tolerance
I> Isn; IsL
tI>
0.5...2 x In / 0.05; 0.1 x In
0.03...165s / 0.01; 0.02; 0.05; 0.1;
0.2; 0.5; 1.0; 2.0; 5.0 seconds
± 5% from set value
± 3% or ± 10mS
I>> I>>N; I>>L
tI>>
2...40 x In / 0.1; 0.2; 0.5; 1.0 x In
0.03...2s / 0.01; 0.02; 0.05s
± 5% from set value
± 3% or ± 10mS
V V 10...100% Vn / 5% x Vn ± 5% from set value
9.4.2 Inverse time phase overcurrent relay
Characteristics according to IEC 255-4 or BS 142
Normal Inverse t = 0.14 tI> [s]
(I/IS)0.02 - 1
Very Inverse t = 13.5 tI> [s]
(I/Is) - 1
Extremely Inverse t = 80 tI> [s]
(I/Is)2 - 1
Where: t = Tripping Time
tI> = Time Multiplier
I = Fault Current
Is = Starting Current
Inverse time phase overcurrent relay setting ranges and steps
Setting range / step Tolerance
I> Isn; IsL
tI>
0.5...2 x In / 0.05; 0.1 x In
0.05...1.6 / 0.01; 0.02;
± 5% from set value
± 3% or ± 10mS
I>> I>>N; I>>L
tI>>
2...40 x In / 0.1; 0.2; 0.5; 1.0 x In
0.03...2s / 0.01; 0.02; 0.05s
± 5% from set value
± 3% or ± 10mS
V V 10...100% Vn / 5% x Vn ± 5% from set value
2/5/96 18 MRI-V 01/96H
9.5. Inverse time characteristics
Normal Inverse
Extremely Inverse
Very Inverse
Definite Time
I/I s
2/5/96 19 MRI-V 01/96H
9.6 Output contact ratings
Number of relays = 4
Contacts = 2 change over contacts for trip signal, I> alarm, & I>> alarm.
1 change over contact for self supervision.
Maximum breaking capacity
250V AC / 1500VA / continuous current 6A
for DC voltage:
ohmic L/R = 4ms L/R = 7ms
300 V DC 0.3 A / 90 W 0.2 A / 63 W 0.18 A / 54 W
250 V DC 0.4 A / 100 W 0.3 A / 70 W 0.15 A / 40 W
110 V DC 0.5 A / 55 W 0.4 A / 40 W 0.2 A / 22 W
60 V DC 0.7 A / 42 W 0.5 A / 30 W 0.3 A / 17 W
24 V DC 6 A / 144 W 4.2 A / 100 W 2.5 A / 60 W
Max. rated making current: 64A(IEC65)
mechanical life span: 3 × 106 operating cycles
electrical life span: 2 × 105 operating cycles at 220 V AC / 6A
Contact material Silver Cadmium Oxide (AgCdO)
9.7 System data
Design standard = IEC 255-4, BS 142
Operating temperature range = -20°C to 70°C
Storage temperature range = -40°C to 85°C
Relative humidity = 93% @ 40°C for 56 days
Test Voltages to EN50081-1, EN50082-2
Isolation Test = 2.5kV / 50Hz / 1 min.
Impulse Test = 5kV, 1.2 / 50mS, 0.5J
High frequency interference Test = 2.5kV / 1MHz
Burst transient Test = 4kV / 2.5KHz, 15mS
ESD Test = 8kV
RFI Suppression Test = 10V/m, 27 - 500MHz, 1 Octave/ 3 min.
EMI Suppression Test = 10V/m
Mechanical Tests:
Shock = IEC 41B (CO) 38, Class 1
Vibration = IEC 41B (CO) 35, Class 1
Degree of Protection = Front - IP52
Rear - IP00
Weight = Approx. 2kg.
2/5/96 20 MRI-V 01/96H
9.8 Housing
Throughout the MR series range a modular housing system has been employed, utilizing the latest
high quality UK manufactured industry standard case components. This approach affords
maximum flexibility for both the relay scheme designer and the maintenance engineer. The relay
modules are fully withdrawable for ease of maintenance and where applicable incorporate
automatic short-circuiting CT connections to avoid dangerous open circuit CT overvoltages. A
clear plastic front cover is provided for inspection purposes.
MRI-V units are supplied in standard height (179mm≅7in.) cases, complying with IEC 297 size 4U.
The rigid case wall is manufactured from a single sheet of hot dipped galvanized steel coated
externally with Plastisol PVC and internally with a low gloss alkyd paint finish. This construction
technique provides improved thermal transfer characteristics over plastic walled cases and
combines exceptional corrosion and flame resilience with good electromagnetic and electrostatic
screening properties allowing many relays to be freely situated in close proximity and hazardous
environments. When the relay is inserted a leaf spring along the top edge of the module makes
contact with a solidly bonded nickel plated steel strip on the interior of the case, providing
excellent earth continuity. This strip is brought out at the rear of the case, above the terminal
block, where it forms a separate earthing terminal. A rigid front mounting flange is provided
allowing the entire range of standard cases to be flush mounted without alteration. These flanges
are also used to mount the relay inspection cover which is secured by thumbscrews. Securely
bonded channels can be provided on the top and bottom surfaces toward the rear of the case
allowing large rigid assemblies to be created by the use of joining strips located in these channels.
This uniform but highly flexible housing system integrates excellent mechanical strength with
good electrical practice in industry standard sizes.
PANEL CUT OUT FLUSH
MOUNTING FIXING DETAILS
4 HOLES 4.4mm DIAMETER
99
168 159
52 23.5
10
97
45
PUSH BUTTON
PROJECTION 10mm
NOT SHOWN TO SCALE
103
177
212
Clearance
25 min
157
32
OPTIONAL
OPTIONAL
OPTIONAL
Min28
NOTE Minimum gap between vertical
spacing is required in order to
withdraw relay from the case above.
178
Required to open case SIZE 100 CASE
2/5/96 21 MRI-V 01/96H
9.9 Terminal Connection Details
The rear terminal block accepts both pre-insulated screw and push-on blade type connectors which
may be used singly or in combination. Each terminal has 1 screw type and 2 blade type
connectors.
Screw: Each connection uses a 4mm (M4) screw outlet and accepts standard
L-shaped ring type connectors designed for 4mm screws.
Blade: Each connection facilitates 2 pre-insulated push-on blades 4.8mm
wide 0.8mm thick complying with BS5057.
Combinations: Each terminal will accept either;
2 ring type connectors
or 2 push-on blade type connectors
or 1 ring type connector & 1 push-on blade type connector
1
3
5
7
9
11
13
15
17
19
21
23
25
27
2
4
6
8
10
12
14
16
18
20
22
24
26
28
Earth
Rear terminal block connections.
Each terminal
1 screw &
2 spade29
31
33
35
37
39
41
43
45
47
49
51
53
55
30
32
34
36
38
40
42
44
46
48
50
52
54
56
All information subject to change without notice
Publication number MRIV-02/96H
2/5/96 22 MRI-V 01/96H
10. Order Form
Digital Multifunctional Relay for Voltage Controlled Overcurrent Protection MRI-V
MRI-V
Rated Current, 1A 1
5A 5
Rated Voltage, 100 V (110V) 1
230 V (240V) 2
400 V (415V) 4
Power Supply, 24V (16-60Vac, 16-80Vdc) L
110V (50-270Vac, 70-360Vdc) H
Data Communications, RS485 R
Housing, 19" Rack A
Flush Mounting D
PBSI Ltd Trading as
P&B ENGINEERING
Bell Vue Works,
Boundary Street,
Manchester.
M12 5NG.
Tel: 0161-230-6363
Fax: 0161-230-6464