motor modutrol honeywell.pdf
TRANSCRIPT
-
385
Motors and ActuatorsFoot-MountedB
uild
ing
Co
ntro
ls a
nd
Sy
stem
s
Modutrol IV Family of Motors Contractor-Friendly design for service and retrofit
Modutrol IV Motors replace all present generation Modutrol motors and set a new, certifiable standard for the industry. Modutrol IV Motors retain all the features that made Honeywell Modutrol motors the most reliable produced, and go even further with 20 quality improvements.
TRADELINE models provide these features and benefits:1. Dual shafts. Both drive and auxiliary shafts have equal torque rat-
ings, allowing auxiliary shaft to drive full torque loads. This provides a more flexible motor. For example, a spring-return, normally closed motor will provide normally open operation simply by using the auxil-iary shaft.
2. NEMA 3 housing. Modutrol IV motor housings protect the motor from driving rain if motor is mounted in the upright position (as shown in above photo). May be mounted outdoors without a weatherproof-ing kit.
3. Higher holding torques. Holding torques have been increased by 35-100%. More reliable performance on the job. Greatly reduced likelihood of dithering once motor has stabilized in position.
4. Improved spring return drive torque. Rating increased from 50 lb-in. to 60 lb-in. for the high torque M9185 style motor (oldM945/955 motor).
5. Reduced power consumption. Motor power needs can always be satisfied with a 40 VA transformer.
6. Internal quality improvements. Result in improved performance and longer life. These significant quality improvements include:
Common Bore Motor precisely aligns bearings, end caps, stator and rotor for increased performance and reliability.
One Piece Stator provides greater durability plus improved efficiency. Stronger Gear Train, the most reliable in the industry. Die-Cast Housing with tongue and groove seal design provides
superior oil-seal integrity. Plus significant improvements in the drive shaft, terminal block, and
more.
A total of more than 20 improvements have gone into the design and manufacture of Modutrol IV MotorsThe Performers.
Fourteen TRADELINE motors and appropriate accessories can be configured to replace all previous Honeywell Modutrol motors, as well as most OEM modutrol motors. The TRADELINE motors are:
The appropriate accessories are listed in Parts and Accessories, a table near the end of this section of the catalog.
ResistorBoard
CrankArm
ControllerInterfaceModule
InternalField-AddableAuxiliarySwitches
InternalField-AddableTransformer
M16727
M6184D1035 M9174D1007 M6285A1005
M6194D1017 M9184D1013 M6285A1013
M6284D1000 M9184D1021 M9175D1014
M6294D1008 M9194D1003 M9185D1004
M9164D1009 M8185D1006
-
Motors and ActuatorsFoot-Mounted
386
Modutrol IV Family of MotorsThe following Modutrol IV motors can replace the old style Modutrol motors as shown below.
New Mod IV Replacement Old Motors Replaced
Non-Spring Return
M6184M6194M6284M6294M7164M7274M7284M7294M7364
M7384M7964M7984M9164M9174M9184M9194M9484M9494
M644M744M941M944M954
M734M934
High Torque Spring Return
M4185M4186M6285M6286M7185M7186M7285
M7286M7385M7685M8185M9185M9186
M445M745M845M945M955
MediumTorqueSpringReturn
M7975M9175
M765M865M965M975
-
387
Motors and ActuatorsFoot-Mounted
continued next page
Bu
ildin
g C
on
trols
an
d S
ys
tems
The Honeywell Family of Modutrol IV Foot-Mounted Actuators*TRADELINE models.
Actuator
Voltage Vac
Stroke Timing
Control Input Torque (lb-in.)Spring Return
Recommended Controller24a 120 208 220 240
On/Off
Spdt Floating Modulating Thermistor 25 35 50 60 75 150 300
M4185A1001 ! 160 60 ! ! ! T775; T4031
M4185B1009 ! 160 60 ! ! ! T775; T4031
M4185B1017 ! ! ! 160 60 ! ! ! T775; W7080
M4185B1058 ! ! ! 90 30 ! ! ! T775; T4031
M6184A1015 ! 90 30 ! ! T775; T7075; T675; T678; T6031
M6184A1023 ! 160 30 ! ! T775; T7075; T675; T678; T6031
M6184D1001 ! 90-160 15-30 ! ! T775; T7075; T675; T678; T6031
*M6184D1035 ! 90-160 30-60 ! ! T775; T7075; T675; T678; T6031
M6184D1068 ! 90-160 120-240 ! ! T775; T7075; T675; T678; T6031
M6184F1014 ! 90-160 30-60 ! ! T775; T7075; T675; T678; T6031
*M6194B1011 ! 90 60 ! ! T775; T7075; T675; T678; T6031
*M6194D1017 ! 90-160 120-240 ! ! T775; T7075; T675; T678; T6031
M6194E1006 ! 90-160 120-240 ! ! T775; T7075; T675; T678; T6031
M6284A1048 ! 160 60 ! ! T775; T7075; T675; T678; T6031
M6284A1055 ! 90 30 ! ! T775; T7075; T675; T678; T6031
M6284A1063 ! 160 160 ! ! T775; T7075; T675; T678; T6031
*M6284D1000 ! 90-160 30-60 ! ! T775; T7075; T675; T678; T6031
M6284F1013 ! 90-160 30-60 ! ! T775; T7075; T675; T678; T6031
*M6285A1005 ! 160 60 ! ! ! T775; T7075; T675; T678; T6031
*M6285A1013 ! 90 30 ! ! ! T775; T7075; T675; T678; T6031
M6285C1001 ! 160 60 ! ! ! T775; T7075; T675; T678; T6031
M6286G1001 ! 160 60 ! ! ! T775; T7075; T675; T678; T6031
*M6294D1008 ! 90-160 120-240 ! ! T775; T7075; T675; T678; T6031
M7164A1017b ! 90 30 10.5-13.5 Vdc ! T775; W7080
M7164G1030b ! 90 30 10.5-13.5 Vdc ! T775; W7080
M7185A1004b ! 160 60 4-7 Vdc ! ! T775; W7080
M7284A1004b ! 90 30 4-20 mA ! T775, EXCEL 5000
M7284A1012b ! 160 60 4-20 mA ! T775, EXCEL 5000
M7284A1038b ! 90 15 4-20 mA ! T775, EXCEL 5000
M7284A1046b ! 90 30 4-20 mA ! T775, EXCEL 5000
M7284A1079b ! 160 60 2-10 Vdc ! T775, EXCEL 5000
M7284C1000b ! 90 30 4-20 mA ! T775, EXCEL 5000
M7284C1018b ! 160 60 4-20 mA ! T775, EXCEL 5000
M7284C1059 ! 90 30 ! 4-20 mA ! DDC
-
Motors and ActuatorsFoot-Mounted
388
The Honeywell Family of Modutrol IV Foot-Mounted Actuators continued
continued next page
M7284C1067 ! 160 60 ! 4-20 mA ! DDC
M7284G1001b ! 160 60 2-10 Vdc ! T775, EXCEL 5000
M7284Q1009b ! 90 30 4-20 mA ! T775, EXCEL 5000
M7284Q1017b ! 160 60 4-20 mA ! T775, EXCEL 5000
M7284Q1033 ! 90 30 ! 4-20 mA ! DDC
M7284Q1041 ! 160 60 ! 4-20 mA ! DDC
M7285A1003b ! 90 30 4-20 mA ! ! T775, EXCEL 5000
M7285A1011b ! 160 60 4-20 mA ! ! T775, EXCEL 5000
M7285A1045b ! 160 60 2-10 Vdc ! ! T775, EXCEL 5000
M7285C1009b ! 90 30 4-20 mA ! ! T775, EXCEL 5000
M7285C1017b ! 160 60 4-20 mA ! ! T775, EXCEL 5000
M7285Q1008b ! 90 30 4-20 mA ! ! T775, EXCEL 5000
M7285Q1016b ! 160 60 4-20 mA ! ! T775, EXCEL 5000
M7286G1009b ! 160 60 2-10 Vdc ! ! T775, EXCEL 5000
M7294A1010b ! 160 120 2-10 Vdc ! T775, EXCEL 5000
M7294G1009b ! 160 120 2-10 Vdc ! T775, EXCEL 5000
M7294Q1007b ! 90 60 4-20 mA ! T775, EXCEL 5000
M7685A1025b,c ! 90 30 14-17 Vdc ! ! T775; W7080
M7964A1001b ! 90 30 ! ! T7047
M7964B1009b ! 90 30 ! ! T7047
M7964B1017b ! 160 60 ! ! T7047
M7964C1007b ! 90 30 ! ! T7047
M7964C1015b ! 90 30 ! ! T7047
M8185A1002 ! 160 60 ! ! ! T775
*M8185D1006 ! 90-160 30-60 ! ! ! T775
M9164A1005 ! 90 30 135 ohm ! T775; T915; T991
M9164A1013 ! 160 60 135 ohm ! T775; T915; T991
M9164A1021 ! 160 60 135 ohm ! T775; T915; T991
M9164A1070 ! 160 60 135 ohm ! T775; T915; T991
M9164A1088 ! 160 60 135 ohm ! T775; T915; T991
M9164A1120 ! 90 30 135 ohm ! T775; T915; T991
M9164C1001 ! 160 60 135 ohm ! T775; T915; T991
M9164C1050 ! 160 60 135 ohm ! T775; T915; T991
M9164C1068 ! 90 30 135 ohm ! T775; T915; T991
*M9164D1009 ! 90-160 30-60 135 ohm ! T775; T915; T991
M9174B1027 ! 90 30 135 ohm ! T775; T915; T991
M9174B1043 ! 160 60 135 ohm ! T775; T915; T991
M9174C1025 ! 90 30 135 ohm ! T775; T915; T991
M9174C1033 ! 160 60 135 ohm ! T775; T915; T991
*M9174D1007 ! 90-160 30-60 135 ohm ! T775; T915; T991
M9175D1006 ! 90-160 30-60 135 ohm ! ! T775; T915; T991
*M9175D1014 ! 90-160 30-60 135 ohm ! ! T775; T915; T991
M9184A1019 ! 160 60 135 ohm ! T775; T915; T991
M9184A1035 ! 90 30 135 ohm ! T775; T915; T991
M9184C1031 ! 90 30 135 ohm ! T775; T915; T991
M9184D1005 ! 90-160 15-30 135 ohm ! T775; T915; T991
*M9184D1013 ! 90-160 30-60 135 ohm ! T775; T915; T991
*TRADELINE models.
Actuator
Voltage Vac
Stroke Timing
Control Input Torque (lb-in.)Spring Return
Recommended Controller24a 120 208 220 240
On/Off
Spdt Floating Modulating Thermistor 25 35 50 60 75 150 300
-
389
Motors and ActuatorsFoot-MountedThe Honeywell Family of Modutrol IV Foot-Mounted Actuators continued
Bu
ildin
g C
on
trols
an
d S
ys
tems
a All 24 Vac Modutrol motors have CE approval.b Available only through Honeywell Authorized Distributors.c Includes minimum position potentiometer.
Modutrol IV Motor Order Number Guide
*M9184D1021 ! 90-160 30-60 135 ohm ! T775; T915; T991
M9184F1000 ! 90-160 30-60 135 ohm ! T775; T915; T991
M9184F1034 ! 90-160 30-60 135 ohm ! T775; T915; T991
M9185A1018 ! 160 60 135 ohm ! ! T775; T915; T991
M9185A1026 ! 90 30 135 ohm ! ! T775; T915; T991
M9185C1006 ! 160 60 135 ohm ! ! T775; T915; T991
*M9185D1004 ! 90-160 30-60 135 ohm ! ! T775; T915; T991
M9185E1019 ! 90-160 30-60 135 ohm ! ! T775; T915; T991
M9186G1006 ! 160 60 135 ohm ! ! T775; T915; T991
*M9194D1003 ! 90-160 120-240 135 ohm ! T775; T915; T991
M9194E1000 ! 90-160 120-240 135 ohm ! T775; T915; T991
*TRADELINE models.
Actuator
Voltage Vac
Stroke Timing
Control Input Torque (lb-in.)Spring Return
Recommended Controller24a 120 208 220 240
On/Off
Spdt Floating Modulating Thermistor 25 35 50 60 75 150 300
SERIES 40, TWO-POSITION, LINE VOLTAGESERIES 60, FLOATING CONTROLSERIES 60, FLOATING WITH FEEDBACKPOTENTIOMETER4-7, 6-9, 10.5-13.5 VDC CONTROL4-20 mA OR 2-10 VDC CONTROLW936 CONTROL14-17 VDC WITH MINIMUM POSITIONSPECIALSSERIES 80, TWO-POSITION, LOW VOLTAGESERIES 90, PROPORTIONING CONTROLPROPORTIONAL FLAME SAFEGUARDFIRING RATE MOTOR
35 LB-IN.75 LB-IN.
150 LB-IN.300 LB-IN.
25 LB-IN.60 LB-IN.
SPRING RETURN
NON-SPRINGRETURN
TORQUETORQUE DESIGNATION
6789
N.C.N.O.
N.C.N.O.
SPRING RETURN
SPRING RETURN
NON-SPRING RETURN
NON-SPRING RETURNROTATION ACTION
OUTPUT DRIVE
456123
416162
7172737679819194
CONTROL SERIES (FIRST TWO DIGITS)
SHAFT
DUAL-ENDEDSHAFT
SINGLE-ENDEDSHAFT
NUMBER OFAUX. SWITCHES
SUFFIX LETTERAPPLIES TO ALL MODELS EXCEPT SERIES 79
A
SPECIALFUNCTION
B C
QN
YV W
G HL
0 1 2STANDARD
MINIMUMPOSTITION
STANDARDSTANDARD
ADJ. ZEROAND SPAN
STROKE ELECTRICALROTATION
N.C.
N.O.
FIXED
FIXEDFD E STANDARD ADJUSTABLE
ADJUSTABLE
SPECIFICATIONNUMBER
FURTHERIDENTIFIESMOTORM9184D1021
M17507
2
2
MODEL NUMBERS IN SHADED AREAS ARE AVAILABLE SPECIAL ORDER ONLY. CONTACT YOUR HONEYWELL SALES REPRESENTATIVE.
SUFFIX LETTERS IN BOLD ARE OBSOLETE.
1
1
1
1
1
-
Motors and ActuatorsFoot-Mounted
390
continued next page
M4185; M4186; M8185 Modutrol IV Motors
Two-position, spring return motors used to operate dampers and valves.
Used to operate dampers and valves in applications where it is necessary or desirable to have the controlled element return to the starting position in the event of power failure or interruption.
Replace M445A,D; M845A,C,E; and M865B motors. Available with factory-installed transformers, or an internal transformer
can be added in the field. Oil-immersed motor and gear train provide reliable performance and
long life. Provide NEMA 3 weather protection with wiring box, when mounted
upright. Electrically normally closed (at closed position when control signal is at
minimum level) and rotate clockwise to open with a signal increase.
Integral helical spring that returns the motor shaft to the normal position (fully closed for M4185 and M8185; fully open for M4186) on power interruption.
Internal actuator motor and circuitry operate from 24 Vac Line voltage models shipped with internal transformers.
Double-ended, 3/8 in. (10 mm) square crankshaft.
APPROVALS:Underwriters Laboratories Inc. Listed: File E4436, Guide XAPX.Canadian Standards Association Certified: File LR1620,
Guide 400-E.
TEMPERATURE RATINGS:Ambient: -40 F to +150 F (-40 C to +66 C) at 25% duty cycle.
ELECTRICAL RATINGS:Auxiliary Switch Ratings (A):
a 40 VA pilot duty, 120/240 Vac on opposite contact.ELECTRICAL CONNECTIONS: Quick-connect terminals are standard;
screw terminal adapter available.
*TRADELINE model.
a Torque given is normal running torque. Breakaway torque rating is 2X normal running torque and is the maximum torque available to overcome occasional large loads such as a seized damper or valve. MOTOR NOT TO BE USED CONTINUOUSLY AT BREAKAWAY TORQUE RATING.
M6184; M6194 Modutrol IV Motors
Reversing, three-wire spdt or floating control motors used to operate dampers and valves.
Replace M644-A-E motors. Available with fixed or adjustable stroke. Internal actuator motor and circuitry operate from 24 Vac. Line voltage
models shipped with internal transformers. Double-ended, 3/8 in. (10 mm) square crankshaft.
APPROVALS:Underwriters Laboratories Inc. Listed: File E4436, Guide XAPX.Canadian Standards Association Certified: File LR1620,
Guide 400-E.
TEMPERATURE RATINGS:Ambient: -40 F to +150 F (-40 C to +66 C) at 25% duty cycle.
ELECTRICAL RATINGS:Auxiliary Switch Ratings (A):
a 40 VA pilot duty, 120/240 Vac on opposite contact.
One Contacta 120V 240V
Full Load 7.2 3.6
Locked Rotor 43.2 21.6
ORDER NUMBER
Electrical Ratings
Torquea
TimingStroke (degrees) Includes CommentsPower Supply
Power
W VA lb-in. Nm
M4185A1001 120 Vac at 50/60 Hz 25 30 60 6.8 60 sec 160
M4185B1009 1 spdt auxiliary switch
M4185B1017 120/208/240 Vac at 50/60 HzM4185B1058 30 sec 90
M8185A1002 24 Vac at 50/60 Hz 20 21 60 sec 160
*M8185D1006 30 to 60 sec
90 to 160 220738A adapter bracket to match height of Mod III motors
Shorter timing applies to 90 degree stroke.
One Contacta 120V 240V
Full Load 7.2 3.6
Locked Rotor 43.2 21.6
-
391
Motors and ActuatorsFoot-MountedM6184; M6194 continued
Bu
ildin
g C
on
trols
an
d S
ys
tems
*TRADELINE models.
a Torque given is normal running torque. Breakaway torque rating is 2X normal running torque and is the maximum torque available to overcome occasional large loads such as a seized damper or valve. MOTOR NOT TO BE USED CONTINUOUSLY AT BREAKAWAY TORQUE RATING.
M6284; M6294 Modutrol IV Motors
Reversing, three-wire floating-control motors with feedback potentiometer. Used with controllers that provide a spdt output to operate dampers and valves.
Replace M944B,E,G,S motors. Internal actuator motor and circuitry operate from 24 Vac. Line voltage
models shipped with internal transformers. Double-ended, 3/8 in. (10 mm) square crankshaft.
APPROVALS:Underwriters Laboratories Inc. Listed: File E4436, Guide XAPX.Canadian Standards Association Certified: File LR1620,
Guide 400-E.
TEMPERATURE RATINGS:Ambient: -40 F to +150 F (-40 C to +66 C) at 25% duty cycle.
ELECTRICAL RATINGS:Auxiliary Switch Ratings (A):
a 40 VA pilot duty, 120/240 Vac on opposite contact.
*TRADELINE models.
a Torque given is normal running torque. Breakaway torque rating is 2X normal running torque and is the maximum torque available to overcome occasional large loads such as a seized damper or valve. MOTOR NOT TO BE USED CONTINUOUSLY AT BREAKAWAY TORQUE RATING.
ORDER NUMBER
Electrical Ratings
Torquea
TimingStroke (degrees) Includes CommentsPower Supply
Power
W VA lb-in. Nm
M6184A1015 24 Vac at 50/60 Hz 15 17 150 17.0 30 sec 90
M6184A1023 120 Vac at 50/60 Hz 20 25 75 8.5 30 sec 160
M6184D1001 24 Vac at 50/60 Hz 15 17 15 to 30 sec
90 to 160 Shorter timing applies to 90 degree stroke.
*M6184D1035 150 17.0 30 to 60 sec
90 to 160 220738A adapter bracket to match height of Mod III motors.
M6184D1068 120 to 240 sec
M6184F1014 30 to 60 sec
M6194B1011 300 34.0 60 sec 90
*M6194D1017 120 to 240 sec
90 to 160 220738A adapter bracket to match height of Mod III motors.
Shorter timing applies to 90 degree stroke.
M6194E1006
One Contacta 120V 240V
Full Load 7.2 3.6
Locked Rotor 43.2 21.6
ORDER NUMBER
Electrical Ratings
Torquea
TimingStroke (degrees) Includes CommentsPower Supply
Power
W VA lb-in. Nm
M6284A1048 120 Vac at 50/60 Hz 20 25 150 17 60 sec 160
M6284A1055 30 sec 90
M6284A1063 15 17 60 sec 160 Auxiliary cams, MOVs and screw terminal adapter.
*M6284D1000 24 Vac at 50/60 Hz 30 to 60 sec
90 to 160 220738A adapter bracket to match height of Mod III motors.
Shorter timing applies to 90 degree stroke.
M6284F1013 2 spdt auxiliary switches.
*M6294D1008 300 34 120 to 240 sec
220738A adapter bracket to match height of Mod III motors.
-
Motors and ActuatorsFoot-Mounted
392
continued next page
M6285; M6286 Modutrol IV Motors
Spring return motors with isolated feedback potentiometer, used with spdt or floating controls to operate dampers and valves.
Replace M945B,C,G motors. Contain integral springs that return motor shafts to normal position (full
open for M6286, full closed for M6285) when power is interrupted. Include electrically isolated feedback potentiometers to provide
indication of shaft position. Oil-immersed motor and gear train provide reliable performance and
long life. Includes adapter brackets to match shaft height of older motors. Provide NEMA 3 weather protection with wiring box, when mounted
upright.
Factory-installed transformer models available, or an internal transformer can be added in the field.
Double-ended, 3/8 in. (10 mm) square crankshaft.
APPROVALS:Underwriters Laboratories Inc. Listed: File E4436, Guide XAPX.Canadian Standards Association Certified: File LR1620,
Guide 400-E.
TEMPERATURE RATINGS:Ambient: -40 F to +150 F (-40 C to +66 C) at 25% duty cycle.
ELECTRICAL RATINGS:Auxiliary Switch Ratings (A):
a 40 VA pilot duty, 120/240 Vac on opposite contact.ELECTRICAL CONNECTIONS: Quick-connect terminals are standard;
screw terminal adapter available.
*TRADELINE models.
a Torque given is normal running torque. Breakaway torque rating is 200 lb.-in. and is the maximum torque available to overcome occasional large loads such as a seized damper or valve. MOTOR NOT TO BE USED CONTINUOUSLY AT BREAKAWAY TORQUE RATING.
M7164; M7185 Modutrol IV Motors
Proportional motors used to operate dampers and valves when used with a modulating dc voltage source such as W7080 panel.
M7164 replaces M734H,J motors; M7185 replaces M745P motors. Oil-immersed motor and gear train provide reliable performance and
long life. Provide NEMA 3 weather protection with wiring box when mounted
upright.
M7164A and M7185A are normally closed (at closed position when control signal is at a minimum) and rotate clockwise to open with a signal increase.
M7164G is electrically normally open (at open position when control signal is at a minimum) and rotate counterclockwise to close with a signal increase.
M7185 motor has a helical spring that returns the motor to the normal position on power interruption.
Internal actuator motor and circuitry operate from 24 Vac. Line voltage models shipped with internal transformers. Separate transformer may be required for 24 Vac models of M7164 motors for proper system operation.
Double-ended, 3/8 in. (10 mm) square crankshaft.
APPROVALS:Underwriters Laboratories Inc. Listed: File E4436, Guide XAPX.Canadian Standards Association Certified: File LR1620;
Guide 400-E.TEMPERATURE RATINGS:
Ambient: -40 F to +150 F (-40 C to +66 C) at 25% duty cycle.
ELECTRICAL CONNECTIONS: Quick-connect terminals are standard; screw terminal adapter available.
One Contacta 120V 240V
Full Load 7.2 3.6
Locked Rotor 43.2 21.6
ORDER NUMBER
Electrical Ratings
Torquea
TimingStroke (degrees) Includes Power Supply
Power
W VA lb-in. Nm
*M6285A1005 24 Vac at 50/60 Hz 20 21 60 6.8 60 sec 160 220738A adapter bracket to match height of Mod III motors.
*M6285A1013 30 sec 90
M6285C1001 60 sec 160 2 spdt auxiliary switches.
M6286G1001
M7164 M7185, M7186
-
393
Motors and ActuatorsFoot-MountedM7164; M7185 continued
Bu
ildin
g C
on
trols
an
d S
ys
tems
Available only through Honeywell Authorized Commercial Wholesalers and Honeywell Authorized Distributors.
a Torque given is normal running torque. Breakaway torque rating is 2X normal running torque and is the maximum torque available to overcome occasional large loads such as a seized damper or valve. MOTOR NOT TO BE USED CONTINUOUSLY AT BREAKAWAY TORQUE RATING.
b CW means motor is electrically normally closed and rotates clockwise with an increase in signal. Motor is in closed position when input signal is at minimum value.
c CCW means motor is electrically normally open and rotates counterclockwise with an increase in signal. Motor is in open position when input signal is at minimum value.
M7284A,G; M7285A; M7286G; M7294A,G,Q Modutrol IV Motors
Proportional motors operate valves when used with a modulating 2-10 Vdc or 4-20 mA input signal, such as EXCEL 5000 system.
Oil-immersed motor and gear train provide reliable performance and long life.
Provide NEMA 3 weather protection with wiring box, when mounted upright.
M7285 motors have helical springs that return motor shaft to closed position on power interruption.
Internal actuator motor and circuitry operate from 24 Vac. Line voltage models shipped with internal transformers.
Double-ended, 3/8 in. (10 mm) square crankshaft.
APPROVALS:Underwriters Laboratories Inc. Listed: File E4436; Guide XAPX.Canadian Standards Association Certified: File No. LR1620;
Guide 400-E.TEMPERATURE RATINGS:
Ambient: -40 F to +150 F (-40 C to +66 C) at 25% duty cycle.
ELECTRICAL RATINGS:Auxiliary Switch Ratings (A):
a 40 VA pilot duty, 120/240 Vac on opposite contact.
ELECTRICAL CONNECTIONS: Quick-connect terminals are standard; screw terminal adapter available.
Available only through Honeywell Authorized Commercial Wholesalers and Honeywell Authorized Distributors.
a Torque given is normal running torque. Breakaway torque rating is 2X normal running torque and is the maximum torque available to overcome occasional large loads such as a seized damper or valve. MOTOR NOT TO BE USED CONTINUOUSLY AT BREAKAWAY TORQUE RATING.
b VA figures listed are for 60 Hz. Values will be higher by 5 VA at 50 Hz.
ORDER NUMBER
Electrical Ratings
Torquea
TimingStroke (degrees) Signal, Input Rotation Direction Power Supply
Power
W VA lb-in. Nm
M7164A1017 24 Vac at 50/60 Hz 14 15 35 4 30 sec 90 10.5 to 13.5 Vdc CWb
M7164G1030 120 Vac at 50/60 Hz 19 24 CCWc
M7185A1004 24 Vac at 50/60 Hz 23 60 6.8 60 sec 160 4 to 7 Vdc CWb
M7284, M7294 M7285, M7286
One Contacta 120V 240V
Full Load 7.2 3.6
Locked Rotor 43.2 21.6
ORDER NUMBER
Electrical Ratings
Torquea
TimingbStroke (degrees) Comments
Signal, Input Power Supply
Power
W VAb lb-in. Nm
M7284A1079 24 Vac at 50/60 Hz 19 20 150 17 60 sec 160 2-10 Vdc
M7284G1001 Normally Open
M7285A1045 23 24 60 6.8
M7286G1009 Normally Open
M7294A1010 19 20 300 34 120 sec
M7294G1009 Normally Open
M7294Q1007 120 Vac at 50/60 Hz 23 29 60 sec 90 4-20 mA
-
Motors and ActuatorsFoot-Mounted
394
M7284A,C,Q; M7285A,C,Q Modutrol IV Motors
Proportional motors used to operate dampers and valves when used with a modulating 4-20 mA current source.
Replace M744S,T,Y and M745S,T,Y motors. Oil-immersed motor and gear train provide reliable performance and
long life. Provide NEMA 3 weather protection with wiring box when mounted
upright. M7285 motors have helical springs that return motor shaft to closed
position on power interruption.
Internal actuator motor and circuitry operate from 24 Vac. Line voltage models shipped with internal transformers.
Double-ended, 3/8 in. (10 mm) square crankshaft.
APPROVALS:Underwriters Laboratories Inc. Listed: File E4436, Guide XAPX.Canadian Standards Association Certified: File LR1620,
Guide 400-E.TEMPERATURE RATINGS:
Ambient: -40 F to +150 F (-40 C to +66 C) at 25% duty cycle.
ELECTRICAL RATINGS:Auxiliary Switch Ratings (A):
a 40 VA pilot duty, 120/240 Vac on opposite contact.
ELECTRICAL CONNECTIONS: Quick-connect terminals are standard; screw terminal adapter available.
Available only through Honeywell Authorized Commercial Wholesalers and Honeywell Authorized Distributors.
a Torque given is normal running torque. Breakaway torque rating is 2X normal running torque and is the maximum torque available to overcome occasional large loads such as a seized damper or valve. MOTOR NOT TO BE USED CONTINUOUSLY AT BREAKAWAY TORQUE RATING.
b VA figures listed are for 60 Hz. Values will be higher by 5 VA at 50 Hz.
M7284 M7285
One Contacta 120V 240V
Full Load 7.2 3.6
Locked Rotor 43.2 21.6
ORDER NUMBER
Electrical Ratings
Torquea
TimingStroke (degrees)
Signal, Input Includes Comments
Power Supply
Power
W VAb lb-in. Nm
M7284A1004 120 Vac at 50/60 Hz
23 29 150 17 30 sec 90 4-20 mA
M7284A1012 60 sec 160
M7284A1038 75 8.5 15 sec 90
M7284A1046 150 17 30 sec
M7284C1000 2 auxiliary switchesM7284C1018 60 sec 160
M7284C1059 24 Vac at 50/60 Hz
30 sec 90 4-20 mA, spdt floating
Enhanced Series 72 Modutrol MotorsMore repositions, direct/reverse acting user selectable, reversal adjustments, and include 220738A adapter plate.
M7284C1067 60 sec 160
M7284Q1009 120 Vac at 50/60 Hz
30 sec 90 4-20 mA Inputs have adjustable zero and span for split range applications.M7284Q1017 60 sec 160
M7284Q1033 24 Vac at 50/60 Hz
30 sec 90 4-20 mA, spdt floating
Inputs have adjustable zero and span for split range applications. Enhanced Series 72 Modutrol Motors More repositions, direct/reverse acting user selectable, reversal adjustments, and include 220738A adapter plate. Zero offset adjustment.
M7284Q1041 60 sec 160
M7285A1003 120 Vac at 50/60 Hz
28 34 60 6.8 30 sec 90 4-20 mA
M7285A1011 60 sec 160
M7285C1009 30 sec 90 2 auxiliary switchesM7285C1017 60 sec 160
M7285Q1008 30 sec 90
M7285Q1016 60 sec 160 Inputs have adjustable zero and span for split range applications.
-
395
Motors and ActuatorsFoot-MountedB
uild
ing
Co
ntro
ls a
nd
Sy
stem
s
M7685 Modutrol IV Motor
Proportional, spring-return motors for use with Honeywell W7080 panel 14-17 Vdc output; with minimum position adjustment.
Replaces M745L motors. Oil-immersed motor and gear train provide reliable performance and
long life.
Provides NEMA 3 weather protection with wiring box, when mounted upright.
Normally closed (at closed position when control signal is at a minimum) and rotate clockwise to open with a signal increase.
Includes a helical spring that returns the motor to the normal position on power interruption.
Double-ended, 3/8 in. (10 mm) square crankshaft.
APPROVALS:Underwriters Laboratories Inc. Listed: File E4436, Guide XAPX.Canadian Standards Association Certified: File LR1620,
Guide 400-E.TEMPERATURE RATINGS:
Ambient: -40 F to +150 F (-40 C to +66 C) at 25% duty cycle.
ELECTRICAL CONNECTIONS: Quick-connect terminals are standard; screw terminal adapter available.
M7964 Modutrol IV Motor
Proportional motors specially designed for specific controllers.
M7964A,B,C replaces M734A,B,C Motors (for ITT Nesbitt multizone systems), and are used with T7047 thermistor-type thermostats.
M7984N replaces M744J motors (for Despatch Industries), and has a voltage input that can be adjusted from -0.9 to 2.6 Vdc to 1.0 to 2.4 Vdc and is designed to be controlled by a voltage source with series resistance of 2740 ohms.
Internal actuator motor and circuitry operate from 24 Vac. Line voltage models shipped with internal transformers.
Double-ended, 3/8 in. (10 mm) square crankshaft. Includes 220738A Adapter Bracket to match height of Mod III motors.APPROVALS:
Underwriters Laboratories Inc. Listed: File E4436, Guide XAPX.Canadian Standards Association Certified: File LR1620,
Guide 400-E.
TEMPERATURE RATINGS:Ambient: -40 F to +150 F (-40 C to +66 C) at 25% duty cycle.
Available only through Honeywell Authorized Commercial Wholesalers and Honeywell Authorized Distributors.
a Torque given is normal running torque. Breakaway torque rating is 2X normal running torque and is the maximum torque available to overcome occasional large loads such as a seized damper or valve. MOTOR NOT TO BE USED CONTINUOUSLY AT BREAKAWAY TORQUE RATING.
ORDER NUMBER
Electrical Ratings
Torque
TimingStroke (degrees) Includes Power Supply
Power
W VA lb-in. Nm
M7685A1025 24 Vac at 50/60 Hz 23 24 60 6.8 30 sec 90 Minimum position potentiometer.
ORDER NUMBER
Electrical Ratings
Torquea
TimingStroke (degrees)
Signal, Input Rotation Direction Comments
Power Supply
Power
W VA lb-in. Nm
M7964A1001 120 Vac at 50/60 Hz
19 24 35 4.0 30 sec 90 T7047 CW; motor is electrically normally closed and rotates clockwise with an increase in signal. Motor is in closed position when input signal is at minimum value.
Motor equipped with Molex plugs required in ITT Nesbitt multizone applications.
M7964B1009 T7047 with ramp. Motor outputs a voltage ramp signal when shaft rotates to a limit.
CCW; motor is electrically normally open and rotates counterclockwise with an increase in signal. Motor is in open position when input signal is at minimum value.
Separate motor transformer may be required for proper system operation. Motor equipped with Molex plugs required in ITT Nesbitt multizone applications.
M7964B1017 60 sec 160 Motor equipped with Molex plugs required in ITT Nesbitt multizone applications.
M7964C1007 30 sec 90 CW; motor is electrically normally closed and rotates clockwise with an increase in signal. Motor is in closed position when input signal is at minimum value.
M7964C1015
-
Motors and ActuatorsFoot-Mounted
396
M9164; M9174 Modutrol IV Motors
Reversing, proportional motors used to operate dampers and valves.
Replace M934 Motors. Electronic drive circuit. Can drive up to six Modutrol motors using 4074BYK Resistor Bag
Assembly or 221508A Resistor Board Kit (see Accessories section). Interface modules available for series 70 (electronic) control.
Internal actuator motor and circuitry operate from 24 Vac. Line voltage models shipped with internal transformers. Separate transformer may be required for 24V models for proper system operation.
Double-ended, 3/8 in. (10 mm) square crankshaft.
APPROVALS:Underwriters Laboratories Inc. Listed: File E4436, Guide XAPX.Canadian Standards Association Certified: File LR1620,
Guide 400-E.
TEMPERATURE RATINGS:Ambient: -40 F to +150 F (-40 C to +66 C) at 25% duty cycle.
ELECTRICAL RATINGS:Auxiliary Switch Ratings (A):
a 40 VA pilot duty, 120/240 Vac on opposite contact.
*TRADELINE models.
a Torque given is normal running torque. Breakaway torque rating is 2X normal running torque and is the maximum torque available to overcome occasional large loads such as a seized damper or valve. MOTOR NOT TO BE USED CONTINUOUSLY AT BREAKAWAY TORQUE RATING.
One Contacta 120V 240V
Full Load 7.2 3.6
Locked Rotor 43.2 21.6
ORDER NUMBER
Electrical Ratings
Torquea
TimingStroke (degrees) Includes Comments
Power Supply
Power
W VA lb-in. Nm
M9164A1005 120 Vac at 50/60 Hz
19 24 35 4.0 30 sec 90
M9164A1013 240 Vac at 50/60 Hz
60 sec 160
M9164A1021 120 Vac at 50/60 Hz
M9164A1070 24 Vac at 50/60 Hz
14 15
M9164A1088 220 Vac at 50/60 Hz
19 24
M9164A1120 24 Vac at 50/60 Hz
14 15 30 sec 90
M9164C1001 60 sec 160 2 spdt auxiliary switches
M9164C1050 120 Vac at 50/60 Hz
19 24
M9164C1068 30 sec 90
*M9164D1009 24 Vac at 50/60 Hz
14 15 30 to 60 sec
90 to 160 220738A adapter bracket to match height of Mod III motors.
Shorter timing applies to 90 degree stroke.
M9174B1027 120 Vac at 50/60 Hz
21 27 75 8.5 30 sec 90 1 spdt auxiliary switch
M9174B1043 60 sec 160
M9174C1025 30 sec 90 2 spdt auxiliary switches
M9174C1033 60 sec 160
*M9174D1007 24 Vac at 50/60 Hz
16 17 30 to 60 sec
90 to 160 220738A adapter bracket to match height of Mod III motors.
Shorter timing applies to 90 degree stroke.
-
397
Motors and ActuatorsFoot-MountedB
uild
ing
Co
ntro
ls a
nd
Sy
stem
s
M9175; M9185; M9186 Modutrol IV Motors
Reversing, proportional, spring-return motors used to operate dampers and valves when used in a series 90 control circuit.
M9185; M9186 replace M945A,D,F and M955 motors; M9175 replaces M965 and M975 motors.
Can be adapted to series 70 control with interface modules. Contain integral helical springs to return motor shafts to normal
position (full closed for M9175 and M9185, full open for M9186) on power interruption.
Oil-immersed motor and gear train provide reliable performance and long life.
Provide NEMA 3 weather protection with wiring box, when mounted upright.
Up to six Modutrol motors can be driven by one series 90 controller using 4074BYK Resistor Bag Assembly or 221508A Resistor Board (see Accessories).
Internal actuator motor and circuitry operate from 24 Vac. Line voltage model shipped with internal transformer.
Double-ended, 3/8 in. (10 mm) square crankshaft.
APPROVALS:Underwriters Laboratories Inc. Listed: File E4436, Guide XAPX.Canadian Standards Association Certified: File LR1620,
Guide 400-E.
TEMPERATURE RATINGS:Ambient: -40 F to +150 F (-40 C to +66 C) at 25% duty cycle.
ELECTRICAL RATINGS:Auxiliary Switch Ratings (A):
a 40 VA pilot duty, 120/240 Vac on opposite contact.ELECTRICAL CONNECTIONS: Quick-connect terminals are standard;
screw terminal adapter available.
*TRADELINE models.
M9175 M9185, M9186
One Contacta 120V 240V
Full Load 7.2 3.6
Locked Rotor 43.2 21.6
ORDER NUMBER
Electrical Ratings
Torque
TimingStroke (degrees) Includes Comments
Power Supply
Power
W VA lb-in. Nm
M9175D1006 120 Vac at 50/60 Hz
26 31 25 2.8 30 to 60 sec
90 to 160 Shorter timing applies to 90 degree stroke.
*M9175D1014 24 Vac at 50/60 Hz
21 22 220738A Adapter Bracket to match height of Mod III motors.
M9185A1018 23 24 60 6.8 60 sec 160
M9185A1026 30 sec 90
M9185C1006 60 sec 160 2 spdt auxiliary switches
*M9185D1004 30 to 60 sec
90 to 160 220738A Adapter Bracket to match height of Mod III motors.
Shorter timing applies to 90 degree stroke.
M9185E1019 1 spdt auxiliary switch
M9186G1006 60 sec 160 M9186G drives to full open position when powered with control wiring not connected.
-
Motors and ActuatorsFoot-Mounted
398
M9184; M9194 Modutrol IV Motors
Reversing, proportional motors used to operate dampers and valves.
Replace M944A,C,D and M954 motors. Electronic drive circuit. Available with fixed or adjustable stroke. Can drive up to six Modutrol motors using 4074BYK Resistor Bag
Assembly or 221508A Resistor Board Kit (see Accessories section). Interface modules available for series 70 (electronic) control.
Internal actuator motor and circuitry operate from 24 Vac. Double-ended, 3/8 in. (10 mm) square crankshaft. Available with tapped (8-32) shafts for Flame Safeguard applications.
APPROVALS:Underwriters Laboratories Inc. Listed: File E4436, Guide XAPX.Canadian Standards Association Certified: File LR1620,
Guide 400-E.
TEMPERATURE RATINGS:Ambient: -40 F to +150 F (-40 C to +66 C) at 25% duty cycle.
ELECTRICAL RATINGS:Auxiliary Switch Ratings (A):
a40 VA pilot duty, 120/240 Vac on opposite contact.
*TRADELINE models.
a Torque given is normal running torque. Breakaway torque rating is 2X normal running torque and is the maximum torque available to overcome occasional large loads such as a seized damper or valve. MOTOR NOT TO BE USED CONTINUOUSLY AT BREAKAWAY TORQUE RATING.
One Contacta 120V 240V
Full Load 7.2 3.6
Locked Rotor 43.2 21.6
ORDER NUMBER
Electrical Ratings
Torquea
TimingStroke (degrees) Includes Comments Power Supply
Power
W VA lb-in. Nm
M9184A1019 24 Vac at 50/60 Hz 18 19 150 17.0 60 160
M9184A1035 30 90
M9184C1031 2 spdt auxiliary switches, tapped shaft.
M9184D1005 75 8.5 15 to 30
90 to 160 Shorter timing applies to 90 degree stroke.*M9184D1013 150 17.0 30 to
60220738A adapter bracket to match height of Mod III motors.
*M9184D1021 Tapped shaft; 220738A adapter bracket to match height of Mod III motors.
M9184F1000 2 spdt auxiliary switches.
M9184F1034 2 spdt auxiliary switches, tapped shaft.
*M9194D1003 300 34.0 120 to 240
220738A adapter bracket to match height of Mod III motors.
M9194E1000 1 spdt auxiliary switch.
-
399
Motors and ActuatorsFoot-Mounted
continued next page
Bu
ildin
g C
on
trols
an
d S
ys
tems
Modutrol IV Cross ReferenceUSE DIRECT REPLACEMENTS OR CONFIGURE MODELS TO MINIMIZE YOUR INVENTORY.(See notes at the end of this cross reference table.)
Motor To Be Replaced
TRADELINE Replacement
Functional Replacemente
TRADELINEMotor
Set Stroke Tob
Add Internal Transformer
Add Switch Comments
M445A1000 M8185D1006 160 198162EA 220736A M4185B1009
M445A1042 M8185D1006 160 198162AA 220736A M4185B1017
M445A1067 M8185D1006 160 198162GA 220736A
M445D1007 M8185D1006 160 198162EA M4185A1001
M644A1016 M6184D1035 160 M6184D1035
M644A1024 M6184D1035 90 M6184A1015
M644B1049 M6184D1035 160 198162EA Replaced motor has 30 second timing. M6184A1023
M644C1006 M6184D1035 Adjustable Replaced motor has 15/30 second timing. M6184D1001
M644C1014 M6194D1017 Adjustable M6194D1017
M644D1005 M6184D1035 Adjustable 220736B M6184F1014
M644E1012 M6194D1017 90 220736A Replaced motor has 60 second timing. M6194B1011
M644E1053 M6194D1017 Adjustable 220736A M6194E1006
M734D1004 M9164D1009 160 198162EA Add Q7330Ac.
M734D1012 M9164D1009 90 198162EA Add Q7330Ac.
M734D1038 M9164D1009 160 Add Q7330Ac.
M734H1000 M9164D1009 90 198162EA Add Q7130Ac, set at 10.5-13.5 Vdc, select CCW. M7164G1030
M734H1018 M9164D1009 90 198162EA Add Q7130Ac, set to 4-7 Vdc, select CCW.
M734H1026 M9164D1009 160 Add Q7130Ac, set to 4-7 Vdc, select CCW.
M734J1015 M9164D1009 160 Add Q7130Ac, set to 4-7 Vdc.
M734J1056 M9164D1009 90 Add Q7130Ac, set to 10.5-13.5 Vdc. M7164A1017c
M734J1072 M9164D1009 160 198162EA 220736A Add Q7130Ac, set to 4-7 Vdc.
M744A1006 M9184D1021a 160 Add Q7330Ac.
M744A1014 M9184D1021a 90 Add Q7330Ac.
M744D1003 M9184D1021a 160 Add Q7130Ac, set to 4-7 Vdc.
M744S1005 M9184D1021a 90 198162EA Add Q7230Ac, set to 4-20 mA. M7284A1004c
M744S1013 M9184D1021a 160 198162EA Add Q7230Ac, set to 4-20 mA. M7284A1012c
M744T1004 M9184D1021a 90 198162EA 220736B Add Q7230Ac, set to 4-20 mA. M7284C1000c
M744T1012 M9184D1021a 160 198162EA 220736B Add Q7230Ac, set to 4-20 mA. M7284C1018c
M744Y1009 M9184D1021a 90 198162EA 220736B Add Q7230Ac, set to desired range. M7284Q1009c
M744Y1017 M9184D1021a 160 198162EA 220736B Add Q7230Ac, set to desired range. M7284Q1017c
M745A1003 M9185D1004 90 Add Q7330Ac.
M745A1011 M9185D1004 160 Add Q7330Ac.
M745G1007 M9185D1004 160 Add Q7130Ac, set to 4-7 Vdc, select CCW.
M745L1027 M9185D1004 160 Add Q7630Ac.
M745L1043 M9185D1004 90 Add Q7630Ac. M7685A1025c
M745P1007 M9185D1004 160 Add Q7130Ac, set to 4-7 Vdc. M7185A1004c
M745S1002 M9185D1004 90 198162EA Add Q7230Ac, set to 4-20 mA. M7285A1003c
M745S1010 M9185D1004 160 198162EA Add Q7230Ac, set to 4-20 mA. M7285A1011c
M745T1001 M9185D1004 90 198162EA 220736B Add Q7230Ac, set to 4-20 mA. M7285C1009c
M745T1019 M9185D1004 160 198162EA 220736B Add Q7230Ac, set to 4-20 mA. M7285C1017c
-
Motors and ActuatorsFoot-Mounted
400
Modutrol IV Cross Reference continued
continued next page
M745Y1006 M9185D1004 90 198162EA 220736B Add Q7230Ac, set to desired range. M7285Q1008c
M745Y1014 M9185D1004 160 198162EA 220736B Add Q7230Ac, set to desired range. M7285Q1016c
M845A1001 M8185D1006 160 220736A
M845A1027 M8185D1006 160 198162AA 220736A
M845A1035 M8185D1006 90 198162AA 220736A M4185B1058
M845C1009 M8185D1006 160 M8185A1002
M845E1007 M8185D1006 160 198162EA 220736A Replaced motor is Normally Opend. M4185B1009
M934A1201 M9164D1009 160 198162AA M9164A1013
M934A1219 M9164D1009 160 198162EA M9164A1021
M934A1227 M9164D1009 160 M9164D1009
M934A1235 M9164D1009 160 198162GA M9164A1088
M934A1243 M9164D1009 160 220736B M9164C1050
M934A1250 M9164D1009 160 198162EA 220736B M9164C1050
M934A1268 M9164D1009 160 198162AA 220736B
M934A1284 M9164D1009 160 198162EA M9164A1021
M934A1292 M9164D1009 160 198162EA 220736B M9164C1050
M934A1318 M9164D1009 90 198162EA 220736B M9164C1068
M934A1326 M9164D1009 90 198162EA M9164A1005
M934A1334 M9164D1009 90
M934A1342 M9164D1009 160 M9164A1021
M934D1000 M9174D1007 160 198162EA 220736A M9174B1043
M934D1018 M9174D1007 160 198162EA 220736B M9174C1033
M934D1026 M9174D1007 90 198162EA 220736A M9174B1027
M934D1034 M9174D1007 90 198162EA 220736B M9174C1025
M941A1008 M9484D1002c
M941A1016 M9484D1010c
M941A1024 M9484D1002
M941A1032 M9484D1020c
M941A1057 M9484D1002c
M941C1006 M9484E1009c
M941C1014 M9484E1017c
M941C1022 M9484E1033c
M941C1030 M9484E1033c
M941C1063 M9484E1033c
M941D1005 M9484F1007c
M941D1021 M9484F1023c
M941D1039 M9484F1031c
M941D1047 M9484F1049c
M944A1010 M9184D1021a 160 M9184A1019c
M944A1028 M9184D1021a 90 M9184A1035c
M944B1175 M6284D1000 160 M6284D1000
M944B1191 M6294D1008 160
M944B1241 M6294D1008 160 220736A
M944C1000 M9184D1021a Adjustable Replaced motor has 15/30 second timing. M9184D1005
Motor To Be Replaced
TRADELINE Replacement
Functional Replacemente
TRADELINEMotor
Set Stroke Tob
Add Internal Transformer
Add Switch Comments
-
401
Motors and ActuatorsFoot-MountedModutrol IV Cross Reference continued
Bu
ildin
g C
on
trols
an
d S
ys
tems
a The M9184D1013 and M9184D1021 have the same features and functions, except the M9184D1021 has a tapped shaft.b Adjustable indicates original motor has adjustable stroke.c Available only through Authorized Honeywell Distributors.d Can use auxiliary end of TRADELINE model, which is N.C. motor.e Functionally equivalent motor, may require 220738A adapter bracket (order separately) to match shaft height of Mod III motor being replaced. All
Mod IV TRADELINE motors include 220738A adapter bracket.
M944C1018 M9194D1003 Adjustable M9194D1003
M944C1042 M9184D1013a Adjustable M9184D1013
M944C1059 M9194D1003 Adjustable 220736A M9194E1000
M944D1017 M9184D1021a Adjustable 220736B M9184F1000
M944E1040 M6284D1000 Adjustable 220736B M6284F1013
M944G1089 M6284D1000 160 198162EA M6284A1048
M944G1097 M6284D1000 90 198162EA M6284A1055
M944S1027 M6284D1000 Adjustable 198162EA 220736B M6284F1013
M945A1017 M9185D1004 160 M9185A1018
M945A1082 M9185D1004 90 M9185A1026
M945A1157 M9185D1004 Adjustable M9185D1004
M945B1057 M6285A1005 M6285A1005
M945B1065 M6285A1013 M6285A1013
M945C1015 M6285A1005 220736B M6285C1001
M945D1006 M9185D1004 160 220736B M9185C1006
M945F1004 M9185D1004 160 Replaced motor is Normally Opend. M9186G1006
M945G1037 M6285A1005 Replaced motor is Normally Opend.
M954A1035 M9184D1021a Adjustable M9184D1021
M954B1034 M9184D1021a 90 220736B M9184C1031
M954D1016 M9184D1021a Adjustable 220736B M9184F1034
M955A1024 M9185D1004 Adjustable M9185D1004
M955C1014 M9185D1004 Adjustable 220736A M9185E1019
M975A1089 M9175D1014 160 M9175D1014
M975A1097 M9175D1014 160 198162EA M9175D1014
Motor To Be Replaced
TRADELINE Replacement
Functional Replacemente
TRADELINEMotor
Set Stroke Tob
Add Internal Transformer
Add Switch Comments
-
Motors and ActuatorsFoot-Mounted
402
Q7130; Q7230; Q7330; Q7630 Interface Modules
For converting series 90 Modutrol IV motors to series 70 (electronic) control.
Mounts and works inside wiring box of any series 90 Modutrol IV Motor.
Protected from weather by motor's NEMA 3 wiring box. Mates to motor's quick-connect terminals and provides screw
terminals for control wiring connections. Features solid-state circuitry with surface mount components. Plastic enclosure provides easy handling and protection for circuitry. Includes (except Q7330A) reversing switch to allow replacement of
electrically normally open or electrically normally closed motors.
DIMENSIONS, APPROXIMATE:Circuit Module: 3-1/2 in. (89 mm) wide, 2 in. (51 mm) deep, 1 in.
(25 mm) high.Terminal Block: 3-1/2 in. (89 mm) wide, 1 in. (25 mm) deep, 1/2 in.
(13 mm) high.Ribbon Connector: 4 in. (102 mm).
NOTE: Q7330A consists only of terminal block.
TEMPERATURE RATINGS: Ambient: -40 F to +150 F (-40 C to +66 C).
ELECTRICAL RATINGS:Power Supply: 24 Vac, 50/60 Hz.Power Consumption: 2 VA.Input Impedance:
Q7130A: >100K ohms.Q7230A: Voltage input >100K ohms;
Current input = 67 ohms.Q7630A: >50K ohms.
Available only through Authorized Honeywell Distributors.*TRADELINE models.
ORDER NUMBER Application Replaces Replaces Use With
*Q7130A1006 Provides selectable voltage ranges: 4 to 7, 6 to 9 or 10.5 to 13.5 Vdc. Adapts M91XX Modutrol IV motor to function as M71XX model for M734H,J; M744D; M745G,P replacements.
M734H1034, M734H1000 M7164G1006 M9164D1009
M734H1018 M7164G1014
M734H1026 M7164G1022
M734J1015 M7164A1009
M734J1031, M734J1023, M734J1056
M7164A1017
M734J1007, M734J1072 M7164B1007
M744D1011, M744D1003 M7184A1005 M9184D1013
M745G1007 M7186G1000 M9186G1006
M745P1007 M7185A1004 M9185D1004
*Q7230A1005 Provides adjustable zero and span, voltage or current control (includes 4 to 20 mA and 2 to 10 Vdc). Adapts M91XX Modutrol IV motors to function as M72XX model for M744S,T,Y; M745S,T,Y replacements.
M744S1005 M7284A1004 M9184D1013
M744S1013 M7284A1012
M744T1004 M7284C1000
M744T1012 M7284C1018
M744Y1009 M7284Q1009
M744Y1017 M7284Q1017
M745S1002 M7285A1003 M9185D1004
M745S1010 M7285A1011
M745T1001 M7285C1009
M745T1019 M7285C1017
M745Y1006 M7285Q1008
M745Y1014 M7285Q1016
*Q7330A1004 Provides interface to W936 Control. Adapts M91XX Modutrol IV motor to function as M73XX model for M734D; M744A; M745A replacements.
M734D1004 M7364A1007 M9164D1009
M734D1012 M7364A1015
M734D1038 M7364A1023
M744A1006 M7384A1003 M9184D1013
M744A1014 M7384A1011
M745A1003 M7385A1002 M9185D1004
M745A1011 M7385A1010
*Q7630A1001 Provides 3-wire 14 to 17 Vdc control with minimum position capability. Adapts M91XX Modutrol IV motors to function as M76XX model for M745 replacements.
M745L1027 M7685A1009 M9185D1004
M745L1035, M745L1043 M7685A1017
M745H1006 M7685A1009
M745L1001 M7685A1041
M745L1019 M7685A1033
-
403
Motors and ActuatorsFoot-MountedB
uild
ing
Co
ntro
ls a
nd
Sy
stem
s
Parts and AccessoriesThe following pages contain replacement parts and accessories for use with foot-mounted motors and actuators.
198162 Internal TransformersConvert Modutrol IV motors from low voltage to line voltage.
Single- or multi-tap available to match 24 Vac power supply.
ELECTRICAL RATINGS:Power Consumption: 40 VA.
220736 Internal Auxiliary Switch Kits
Control auxiliary equipment as a function of motor shaft position.
For installation in any TRADELINE Modutrol IV Motor. Cams can be set to actuate switches at any angle within stroke of
motor.
Selectable switch differentials of one or ten degrees of rotation. Switch adjustment procedures same as for factory-installed switches in
certain motor models.
ELECTRICAL RATINGS:Auxiliary Switch Ratings (A):
a 40 VA pilot duty, 120/240 Vac on opposite contact.
221508 Modutrol IV Motor Resistor Board
Mounts inside wiring box of any M91XX Modutrol IV motor; can be used in place of 4074BYK, 4074EAU, 4074EDC or 4074EED resistor kits.
Board can be configured for any application listed by setting dip switch:In 4074BYK application, board allows single series 90 controller to
operate up to six motors in unison.In 4074EDC, EED application, board permits operation of one to four
motors from 4-20 mA controller.In 4074EAU application, board allows W973 Single-zone Logic
Panel to drive two or three motors. Board snaps on easily to any M91XX Modutrol IV motor.
ORDER NUMBER Primary Voltage Includes
198162JA 24 (for electrical isolation) Transformer, screws, instructions for mounting internally in Modutrol IV motors.
198162EA 120 Vac at 50/60 Hz
198162GA 220 Vac at 50/60 Hz
198162AA 120/208/240 Vac at 50/60 Hz
One Contacta 120V 240V
Full Load 7.2 3.6
Locked Rotor 43.2 21.6
ORDER NUMBER Switches Applicable Motors Includes
220736A 1 spdt TRADELINE Modutrol IV motors One Micro Switch V3 precision switch, which is actuated by adjustable cams inside the motor.
220736B 2 spdt Two Micro Switch V3 precision switches, which are actuated by adjustable cams inside the motor.
ORDER NUMBER Description
221508A Resistor board for use with Modutrol IV motors. One board can be configured for any application listed above.
-
Motors and ActuatorsFoot-Mounted
404
Parts and Accessories
Description Use WithOrder Number
Hardware
Housing, explosion-proof. Modutrol IV motors, requires 7617DM coupling. For ordering information, contact: O-Z/Gedney, Nelson Enclosures & Controls, (918) 641-7381 or (918) 641-7374 and ask for E & C Customer Service; or write to: O-Z/Gedney, Nelson Enclosures & Controls, P.O. Box 471650, Tulsa, OK 74147-1650.
ES-650-117
Motor crank arm. Modutrol IV motors. 221455A
Screw terminal adapters. Modutrol IV motors. 220741A
Economizer adapter assembly Mounts W859 Economizer on any Modutrol IV motor. 203977A
Mod III Adapter Bracket Used with Mod IV Actuator to match shaft height of Mod III Actuator. 220738A
Switch Kits
External auxiliary switch kits. Auxiliary equipment for Modutrol III and Modutrol IV motors. Q607A,B
Internal auxiliary switch kits: Auxiliary equipment (for TRADELINE Modutrol IV motors only).
One switch 220736A
Two switches 220736B
Linkages
Bracket and linkage assembly. Water or steam valves. Q5001D
Damper linkage. Dampers with Modutrol IV motors. Q605F,G,H,J
Linkage. Butterfly valves. Q100
Potentiometers
Auxiliary potentiometer. 1 to 4 additional motors. Q181
Dual control potentiometer. 1 to 5 additional motors. Q68B
Potentiometer. Series 90 Modutrol IV motors (M91XX models). Q209E,F
Interface Modules
Interface modules: M71XX functionM72XX functionM73XX functionM76XX function
M91XX motors. Available only through Authorized Honeywell Distributors. Q7130A1006 Q7230A1005 Q7330A1004 Q7630A1001
Resistor kits. Up to six M91XX motors in unison. 4074BYK
Up to three M91XX motors from one W973 Single zone Logic Panel or T775. 4074EAU
One M91XX motor from a 4-20 mA controller. 4074EDC
Up to six M91XX motors from a 4-20 mA controller. 4074EED
Resistor board M91XX motors. May be used in place of 4074BYK, EAU, EDC, EED resistor kits. 221508A
Replacement Oil
Replacement Oil; 4 oz. container
All Modutrol motors. 17947A
Transformers
Transformers. 24 Vac 120 Vac220 Vac 120/208/240 Vac
Modutrol IV motors. 198162JA 198162EA 198162GA 198162AA
Weatherproofing Kit
NEMA 3 Weatherproofing kit Fits all Modutrol IV motors. Protects motor from driving rain when mounted in any position. Not needed if motor is mounted upright.
4074ERU
-
405
Motors and ActuatorsFoot-MountedB
uild
ing
Co
ntro
ls a
nd
Sy
stem
s
Q181 Auxiliary Potentiometer
Controls one to four Modutrol (series 90) motors from one master motor.
Compatible with Modutrol III and Modutrol IV motors.
Mounts on master motor and operates controlled motors in unison or in sequence.
Controls motors with mechanical balance relay and solid state drive circuit.
Use with 24V motors.
THROTTLING RANGE: Adjustable, 40 to 160 degrees on each 135 ohm potentiometer.
DIMENSIONS, APPROXIMATE: 3-3/16 in. (81 mm) high, 3-1/4 in. (83 mm) wide, 3-3/8 in. (86 mm) deep.
ACCESSORIES: 7640JK Adapter Plate for mounting Q181 on early motors without
bosses on gear end or for mounting over an external return spring.
Q209 Manual Potentiometers
Used to limit minimum position of a proportioning Modutrol motor.
Mount directly in motor. All wiring is accomplished within motor wiring compartment. Color-coded leadwires.
DIMENSIONS, APPROXIMATE:
Typical hookup diagram for Q209 and a Modutrol motor (cooling hookup shown).
ORDER NUMBER Motors Controlled Cover
Q181A1007 1 Yes
Q181A1015 2 Yes
Q181A1064 3 No
Q181A1072 4 No
Q209E 3-1/4 in. (83 mm) x 3-3/8 in (86 mm) x 3-7/8 in. (98 mm)
Q209F 1 in. (25 mm) x 1-3/8 in. (35 mm) x 2-5/8 in. (67 mm)
SERIES 90 CONTROLLER
SERIES 90 MOTOR
Q209
M3280
BLUERED
WHITEB
W
R R
B
W
ORDER NUMBER Application Resistance Includes
Q209E1002 External mount onto Modutrol IV motors. 150 ohms Quick-connect terminals with leadwires.
Q209E1010 300 ohms
Q209F1001 Internal mount to Modutrol IV motors. 150 ohms Terminal board.
Q209F1019 300 ohms
-
Motors and ActuatorsFoot-Mounted
406
continued next page
S443 Manual Potentiometer
Used for remote manual control of proportioning (series 90) motors and relays.
Compatible with Modutrol III and Modutrol IV motors. Select automatic or manual control with dpst toggle switch. Suitable for series 90, M7385; M7186; M7685; M7185; and M7285
motors controlled by 135 ohm slidewire inputs. Surface mounted, with conduit outlet on each side of case. Screw terminals. Scale marked OPEN-CLOSE.
DIMENSIONS, APPROXIMATE: 3-3/4 in. (95 mm) high, 3-3/8 in. (86 mm) wide, 3-1/4 in. (83 mm) deep (including knob).
REPLACEMENT PART:30112A Potentiometer, 135 ohm.
Internal schematic of S443A.
Q100 LinkageContains necessary hardware to link Modutrol motors to a V51B Butterfly Valve.
Compatible with Modutrol III and Modutrol IV motors. (Requires adapter bracket, which is standard on all Modutrol IV motors included in this catalog.)
Adaptable for all sizes of V51B Valves. Strain release and stop bracket are provided with V51B.
Q5001 Valve Linkage for Modutrol IV Motors
The Q5001 Valve Linkage connects a Modutrol Motor to a 2- or3-Way valve. It is used primarily on V5011 or V5013 steam and water valves.
Q5001 Valve Linkage is applicable to 2-Way or 3-Way valves in modulating or two-position service.
Linkage requires no adjustment when used with Honeywell valves and Modutrol IV Motors.
Q5001 Valve Linkage replaces Q601 and Q618 Valve Linkages. Linkage mounts directly to the valve bonnet; motor mounts to linkage
bracket.
Easy-to-read position indicator. Valve stem lift height cam selectable. Overtravel permits tight closeoff without excessive motor strain. Available brackets make linkages adaptable to many valve bodies. Models available with 80 lb, 160 lb, and 320 lb stem force. Reversible cams on the Q5001 allow field selection of normally open
or normally closed valve operation. All models have anti-spin.
TEMPERATURE RATINGS:Ambient: -40 F to +150 F (-40 C to +66 C) air temperature;
-40 F to +337 F (-40 C to +169 C) valve bonnet temperature.
STROKE: 160 degrees rotation for motor.BONNET CONNECTION: Setscrew.
CONNECTIONS:Stem: Button and Clip.
DIMENSIONS, APPROXIMATE: 5-13/16 in. (148 mm) wide, 10-1/4 to 10-1/2 in. (260 to 267 mm) high, 8-13/64 in. (212 mm) deep. Note: motor will add up to 2-1/8 in. (54 mm) to depth.
M17510
BWR
BWR
POTENTIOMETER
AUTO
MAN
UAL
DPDT SWITCH
TERMINALBLOCK
ORDER NUMBER Resistance Use with
S443A1007 135 ohm M9164; M9484; M9184; M9185 and motors replaced by these models.
ORDER NUMBER V51 Valve Size (NPT)
Dimensions, Linkage Rod
Commentsin. mm
Q100A1015 2-1/2 and 3 in. 6-5/8 168 Connecting holes for pins are 5/16 in. (8 mm) in diameter and 1/4 in. (6 mm) from each end of rod.Q100A1023 4 in. 7-1/4 184
-
407
Motors and ActuatorsFoot-MountedQ5001 continued
Bu
ildin
g C
on
trols
an
d S
ys
tems
ACCESSORIES:Valve Adapter Kits (order separately):
220829BCQ1Barber-Colman Valves.220829JCQ1Johnson Control Valves.
220829LGQ1Landis & Gyr Powers Valves (bonnet nut1-3/32 in., bonnet bracket 1-3/32 in.).
220829LGQ2Landis & Gyr Powers Valves (bonnet nut 1-3/8 in., bonnet bracket 1-3/8 in.).
220829LGQ3Landis & Gyr Powers Valves (bonnet nut 1 in., bonnet bracket 1-3/8 in.).
220845 Retainer clip for stem button.CAMS:
a Select a Modutrol IV Motor with equal or greater torque.b Use the 320 lb stem force linkage with a 300 lb-in. torque motor.
HONEYWELL VALVE/LINKAGE SELECTION GUIDE
a Merchandise cam required (see cam table).
*TRADELINE models.
a If valve lift is not 3/4 in., order a merchandise cam (see Cam table).b If valve lift is not 1-1/2 in., order a merchandise cam (see Cam table).
Cam Number Type Lift in in.
Required Torquea in lb-in.
Application80 lb Stem Force
160 lb Stem Force
320 lb Stem Forceb
220855A Custom 1/4 25 50 100
220858A 9/16 V5047A, 1 in. to 1-1/2 in.
220861A Standard 3/4 V5011/V5013, 1/2 in. to 3 in.; V5047, 2 in.
220862A 60 degrees overtravel for Auxiliary Switch
60 120 240
220863A Custom 1 30 60 120
220864A 1-1/8
220865A 1-1/4 50 100 200
220866A 1-3/8
220867A Standard 1-1/2 V5011/V5013, 4 in. to 6 in.
Valve Type Valve Body Dimensions, Approximate, Pipe Size Linkage Bonnet Size Lift (in.)
V5011A 2-Way Flanged 2-1/2, 3 in. Q5001D 1-3/8 3/4
V5011A,B 4, 5, 6 in. 1-7/8 1-1/2
V5011F Threaded 1/2, 3/4, 1, 1-1/4, 1-1/2, 2, 2-1/2, 3 in. 1-3/8 3/4
V5011G
V5013N 3-Way
V5047A 2-Way Threaded 1, 1-1/4, 1-1/2 in. 1-3/8 9/16a
2 in. 3/4
V5051A Flanged 2-1/2, 3, 4, 5, 6 in. 1-1/2
ORDER NUMBER
Stem ForceLift Adjustment
Bonnet Size Linkage Replacedlb N
*Q5001D1000 80, 160 356, 712 3/4 fixed 1-3/8 in. Q601J,K,L,Ma; Q618A.
*Q5001D1018 160, 320 712, 1355 Q601J,K,Q; Q618A1008a; Q618A1024.
*Q5001D1026 1-1/2 fixed 1-7/8 in. Q601E,Pb
-
Motors and ActuatorsFoot-Mounted
408
Q607 Auxiliary Switches
For control of auxiliary equipment as a function of motor shaft position.
Compatible with Modutrol III and Modutrol IV motors. (Requires 220738A adapter bracket for use with Modutrol IV motors).
Micro Switch precision switches, adjustable. Indicate motor position by use of a scale plate anchored to a common
shaft, which allows Q607 to be adjusted for operational sequence before mounting.
Adjustable plate allows universal mounting on either end of motor.
Wrap-around cover for easy access to switch adjustments and wiring. Maintenance-free protection of the switches and cams.
APPROVALS:Underwriters Laboratories Inc. Listed.Canadian Standards Association Component Recognized.
DIMENSIONS, APPROXIMATE:Mounting: 6-7/16 in. (164 mm) high, 5-3/16 in. (132 mm) wide,
2-1/8 in. (54 mm) deep (3-7/16 in. (87 mm) required for cover removal).
ELECTRICAL RATINGS:Current Draw:
Pilot Duty: 75 VA at 24V and 277V.Resistive Load: 22A at 24V, 120V, 240V, 277V; 15A at 480V.
*TRADELINE models.
a With adapter plate for mounting over the spring-return assembly on cover end of motor. Adapter plate to be used to mount Q607 gear end of older motors without bosses or for mounting over spring-return assembly on cover end of motor.
120V 240V 480V
Full Load 9.8A 4.9A 2.45A
Locked Rotor 58.8A 29.4A 14.7A
ORDER NUMBER Switches Applicable Motors
Q607A1050 1 spdt Post 1969 Honeywell Modutrol motors.
*Q607A1076a Pre/Post 1969 Honeywell Modutrol motors.
Q607B1067 2 spdt Post 1969 Honeywell Modutrol motors.
*Q607B1083a Pre/Post 1969 Honeywell Modutrol motors.