motor fundamentals

Upload: dev-swain

Post on 13-Apr-2018

226 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/24/2019 Motor Fundamentals

    1/27

    ComprehensiveGuide to

    UnderstandingMotorFundamentalsInstruction ManualII. INTRODUCTION. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 - 1II. MOTOR BASICS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 - 1Stator Construction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1Rotor Construction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2Simplified Motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3Rotor Current and Slip . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4Te !or"in# Motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-$Tor%ue &s. Stator 'oles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-$Rotatin# Ma#netic (ields . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-)Stator 'oles &s. Speed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-*Speed of Rotatin# (ield . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1+Motor Acceleration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1+Te Rotor ,nder oad . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-12i# (re%uenc/ Rotor Currents . . . . . . . . . . . . . . . . . . . . . . . . . 2-13Tor%ue Caracteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-140MA esi#n Classes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1

    Te Motor as a Transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2+Motor osses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-21ffects of &olta#e &ariations . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-22Reduced &olta#e Startin# . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2Motor Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2$&olta#e ,n5alance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2)ffects of (re%uenc/ &ariations . . . . . . . . . . . . . . . . . . . . . . . . . 2-2*

    Ill. MOTORS AND ADJUSTABLE FREQUENCY DRIVES . 3 - 1'erformance Ad6anta#es . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-Operation A5o6e Base Speed . . . . . . . . . . . . . . . . . . . . . . . . . . 3-$Constant &olta#e Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-$Constant Tor%ue Ran#e . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1+7enerator Action . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-13

    IV. ENERGY EFFICIENT MOTORS . . . . . . . . . . . . . . . . . 4-1

    V. SPECIAL MOTORS . . . . . . . . . . . . . . . . . . . . . . . . . 5. - 1

    II. MOTOR BASICSThe stator electromagnets are comprised of enameled wire

  • 7/24/2019 Motor Fundamentals

    2/27

    wound over a permeable iron core. A typical motor may have 6,128

    or 18 individual windings placed on a common core. The core is a

    collection of stamped disks with slots for mounting the wire

    windings (seeFigure 2-l).Stamped Steel is"s

    STATORCOR!indin#sCannels (illedROTOR CORnum

    Figure 2 - 1

    Figure 2-2shows a simplified stator with only one set of

    windings, labeled Al and A2. They are wound identically. If direct

    current flows through Al and A2, they will be polarized north and

    south as shown inFigure2-3(see page2-2). Notice that flux

    crosses the gap between Al and A2, where the rotor is normally

    mounted.Figure 2-2

    2-1

    AlFigure 2-3

    The rotor itself has no wire windings, but does consist of

    steel disks (or laminations), similar to the stator. The laminations

    are perforated near the circumference (refer toFigure2-1, page

    2-l).These disks are stacked together so that the perforations

    align to form channels near the surface of the core assembly.

    Through a careful die-casting process, the channels are then filledwith aluminum and a ring is formed on each end of the rotor. The

    result is a row of conductive bars embedded into the rotor surface.

    All of the bars are connected at each end of the rotor to form a

    closed circuit for current flow (seeFigure 2-4).Rotor Barsnd Rin#s

    Figure 2-4

    Although the rotor bars are in direct contact with the steel

    laminations, their resistance is much lower. Practically all rotor

    current therefore flows in the bars, not in the laminations. Some

    rotor designs employ a copper-brass alloy instead of aluminum.

    This creates a lower resistance rotor circuit and thereby changes

    motor performance. Sin-ce there are no wire windings, the squirrel

    cage rotor is very rugged.2-2

    To establish current flow in the rotor, there must first be a

    voltage present on the rotor bars. This voltage is supplied by the

  • 7/24/2019 Motor Fundamentals

    3/27

    magnetic field created by stator poles Al and A2. Simply

    mounting the rotor in the gap between Al and A2 will not provide

    voltage for the rotor circuit. However, if there was relative motion

    between the rotor conductors and the stator field, a voltage would

    be induced in the rotor bars (hence the name induction motor).

    ie rFigure2-5 is a simplified view of an induction motor. It

    details only two pairs of rotor bars (with end rings) and one set of

    stator poles, labeled Al and A2. For clarity, Al and A2 are

    permanent magnets instead of electromagnets. The motors shaft

    is represented by the rotors centerline. In a squirrel cage motor,

    the rotor voltage is induced by moving the stator's magnetic field

    past the rotor bars. The rollers and hand crank inFigure 2-5

    merely illustrate a means of rotating the magnetic field.

    Figure 2-5

    If the crank is turned while the rotor is at rest, the relative

    motion between field and conductor will induce a voltage in the

    rotor bars. Current will flow, producing a magnetic field around

    each rotor bar as shown inFigure2-6a(see page2-4). The rotor

    is attracted to the stator and begins to follow along in the same

    direction. As the stator turns farther; the rotor bars pass out of

    the magnetic field and the induced rotor voltage drops to zero (see

    Figure2-6b, page2-4).Rotor current decays, as does the

    resultant rotor field.

    Continued rotation of the stator field produces the

    conditions shown inFigure2-6c(see page2-4). Notice that the

    stator has turned about 180 and now its magnetic field is cutting

    the rotor bars again.2-3

    Te !or"in# MotorThe model of the squirrel cage motor shown inFigure l-l

    (see page l-l) is for illustration only. It is far from a practical

    motor. An actual rotor has many bars, which are normally skewedat a slight anglelike Figure 2-8a.ComparingFigure 2-8aand

    Figure 2-8bdepicts the difference between a skewed and

    unskewed rotor.Figure 2-8a

    Rotor 9it s"e9Figure 2-8b

    Rotor 9itout s"e9Figure 2-8

  • 7/24/2019 Motor Fundamentals

    4/27

    This prevents cogging (torque pulsations), which occurs if

    the rotor bars are parallel to the stator poles. A normal squirrel

    cage induction motor does not employ a crank to rotate the field,

    either. The stator field rotates when 3~ alternating current is

    applied to the stator.

    If alternating current is applied to the single winding

    shown inFigure2-2(see page2-1), the magnetic polarity will

    reverse as the current reverses. This results in each pole swinging

    north-south at the same frequency as the applied voltage. The

    stator field can be considered to be rotating. A single phase

    induction motor operates in this manner. However, this single

    phase circuit has no starting torque. An extra starting circuit is

    required to initially set the rotor in motion. If there is a 30

    circuit, no extra starting circuit is required with the squirrel cage

    motor.

    Tor%ue &s. Stator 'olesFigure2-9ashows the stator poles of a 30 2 pole motor.

    Two poles are energized by each of the three incoming phases. A 4

    pole, 30 motor has twice as many stator poles per phase and is

    illustrated inFigure2-9b.A motor may be constructed with any

    even number of stator poles. The 4 pole motor is the most

    commonly used. The 2, 6, and 8 pole motors are also popular.

    Notice that the 4 pole stator has a flux pattern that contacts the

    rotor in four places instead of only two(see Figure2-9c).Thisresults in twice the magnetic interaction between rotor and stator,

    producing twice the amount of turning force (torque) at the motor

    shaft.2-6

    often operated from square waves generated by adjustable

    frequency drives instead of sine waves of current. At low

    frequencies (below 20 Hertz), a square waves magnetic field does

    not shift smoothly from one position to the next, and cogging may

    be noticeable.

    Follow diagrams ofFigure2-10through times 3, 4, 5, 6

    and 7 to verify that the magnetic field does, in fact, rotate. The

    field at time 7 is identical to the field at time 1 in the cycle. The

    magnetic field of a 2 pole motor makes one complete rotation

    during one electrical cycle. If a rotor is placed inside the stator, it

  • 7/24/2019 Motor Fundamentals

    5/27

    will make almost one rotation in one electrical cycle (depending on

    the amount of slip between rotor and stator). The direction of

    motor rotation may be reversed by switching any two of the stator

    leads. This causes the stator field to reverse direction.

    If the stator is wound with 4 poles per phase instead of two,

    it might be compared to two separate 2 pole stators together.

    Figure 2-11is a means to visualize this. Simply slide all six of the

    stator poles onto one side of the core. When one cycle of 3 0 AC is

    applied, the magnetic field rotates around only one-half of the

    stator. The addition of six more poles on the right half of the stator

    would allow a complete rotation to be made. However, it would

    also require one more cycle of 3 0 power. A 4 pole stator field

    rotates only once for each 2 cycle of applied current. Slide all 12 of

    these stator poles onto one half of the core to create one half of an 8

    pole motor. Logically, this motor demands 4 cycles of alternating

    current to complete one rotation of its magnetic field. Also, an 8

    pole stator is physically larger and draws more current than the 4

    and 2 pole motors for the same HP or kW rating.

    Concept of a 4 'ole StatorFigure 2-11

    If the current that excites the 2, 4 and 8 pole motor is the

    same frequency, then the 4 pole motor will run at one half the

    speed of a 2 pole motor. The 8 pole motor will run at one-half the

    speed of a 4 pole machine or one-fourth the speed of the 2 pole

    motor.2-9

    Speed of Rotatin# (ieldSince the stator field speed is exactly dependent on the

    frequency of the applied current, it is said to be in synchronism

    with the applied current.

    The speed at which the stator field rotates is therefore

    calledSynchronous Speed.The speed of the rotor is called

    Running Speed.It differs only by the amount of slip as shown in

    the equation below:

    Where:

    Ns=Synchronous speed of motor in RPMF = applied freuency in hert!P = num"er of poles per phase12# = con$ersion factor

    (Equation 2-1)

    Synchronous speed may be altered by changing either the

    frequency applied or the number of poles. Multi-speed motors

  • 7/24/2019 Motor Fundamentals

    6/27

    have external connections that allow an operator to switch the

    stator from 2 poles to 4 poles or 4 poles to 6 poles, etc. This

    provides only a limited number of definite speeds, such as those

    shown inTable2-A(page2-7). This table lists the synchronous

    speeds of various motors excited by the same frequency. If speeds

    other than those listed are desired, it is necessary to change the

    motors applied frequency.

    This is commonly done by powering the motor from an

    adjustable frequency drive. Using a drive to generate the applied

    frequency produces an infinitely variable speed range from 0 RPM

    to as high as 100,000 RPM (if required).

    otor AccelerationLet us assume that the stator field is rotated at 1800 RPM

    by 60 Hertz AC applied to the windings. Before the rotor begins to

    turn, there is a slip of 1800 RPM. Relative motion between fieldand conductors is maximum, inducing a very high voltage in the

    rotor. Rotor current is maximum and a strong magnetic field

    results.Figure2-12plots the motor current in relation to rotor

    speed.

    The rotor accelerates from rest (point A), following the

    stator. Slip decreases as the rotor accelerates. A rotor speed of

    500 RPM (point B) means a slip of 1300 RPM. It also means less

    relative motion between field and conductor and therefore a lower

    induced voltage with less rotor current and a weaker rotor field.The rotor continues to accelerate, drawn by the stator field. When

    the rotor reaches 1795 RPM (point E), its field is very weak. The

    rotor bars are cutting very few lines of flux in a given time period.

    If the rotor continued to accelerate, its current (and magnetic field)2-1#

    otor ,nder oadIf no work is required at the motor shaft (no load applied),

    the rotor will turn at approximately 1795 RPM (point E). Slip is

    minimal and the resulting rotor field is very weak. Yet, rotorstator

    attraction is just strong enough to produce enough torque to

    keep the rotor turning at 1795 RPM. If a load is now applied to

    the motor shaft, it immediately slows down, since the torque being

    produced was just enough to keep the rotor at 1795 RPM. If the

    stator speed remains constant (1800 RPM), then as the rotor slows

    down, its bars automatically begin to cut more lines of stator flux

  • 7/24/2019 Motor Fundamentals

    7/27

    per unit of time. The rotor field strengthens and more torque is

    produced. The rotor will continue to slow down (or slip back) until

    adequate torque is produced to power the load and maintain

    rotation. This might correspond to point D inFigure2-12(see

    page2-11). where slip has increased to 50 RPM, and current has

    increased to 100%. If the load is removed, the torque being

    produced will cause the rotor to accelerate back to its no load speed

    of 1795 RPM (point E).

    If the load is increased, again the motor will slow down to

    produce greater torque by the rotor bars cutting more lines of flux.

    Speed stabilizes when the motor torque matches the load torque,

    this time perhaps at point C. The motor will maintain this speed

    as long as the load is constant. Further load increases cause

    greater current flow; beyond the safe limits of motor operation. An

    overpowering load may cause the motor to stall completely, causing

    extremely high currents to flow (point A). Overcurrent protection

    must be installed to protect the motor in such an event. Under

    normal circumstances this magnitude of current occurs only

    during starting, (which lasts less than one second) while the rotor

    attains its running speed.

    When the rotor is stationary, either when stalled by a load

    or during starting, rotor frequency is equal to stator frequency. If

    the stator is excited by 60 Hz, then rotor frequency is also 60 Hz or

    if the stator is excited by 50 Hz the rotor frequency is also 50 Hz.This is true regardless of the number of stator poles a motor has.

    A 2 pole stator turns at 3600 RPM (@ 60 Hz) or 3000 RPM (@ 50

    Hz) and induces 1 cycle of rotor voltage as each pole pair passes a

    rotor bar. A 4 pole sator turns at half the speed but has twice the

    pole pairs cutting each rotor bar. It induces 2 cycles of rotor

    voltage per revolution, matching the rotor frequency of a 2 pole

    machine.2-12

    When the rotor field shifts (during high slip) it not only

    affects motor current, but torque as well. Recall that torque

    results from the magnetic attraction between rotor and stator.

    Increased inductive reactance causes the rotor current (and

    resultant field) to lag rotor voltage. Since the rotor voltage is

    in-phase with the stator field, the rotor field must be out of phase

    with the stator field.Figure2-13ashows the rotor field lagging

  • 7/24/2019 Motor Fundamentals

    8/27

    the stator field and rotor voltage by the angle m (the cosine of x is

    a measure of power factor). Notice that positive motor torque is

    produced only during the periods when stator and rotor fields are

    in-phase. Compare this withFigure2-13b,where voltage and

    current are both in-phase. The out-of-phase rotor field(in

    Figure2-13a)actually produces negative torque, or a retarding

    force. As power factor decreases further, torque suffers more.

    Figure2-13cshows a condition of maximum current lag ( m - 90>

    resulting in negative torque completely cancelling positive torque.

    Although maximum voltage and current flow in such a circuit, no

    power is produced.

    The torque equation of a squirrel cage induction motor is

    similar to that for a DC shunt motor as shown in the following

    equations. The major difference is the term cos m ". This

    stipulates that only the in-phase rotor current produces positive

    torque. Inductive reactance causes this phase shift, so it would be

    expected that motor torque would be worst when inductive

    reactance is greatest.%& Shunt Motor 'orue = ()# 1)

    Where:(' = Motor 'orue &onstant# = *ield *lu+, = rmature &urrent

    (Equation 2-2)

    ,nduction Motor 'orue = () ,)cos m

    Where:KT = Motor 'orue &onstant/ = *ield *lu+,0 = Rotor &urrentcos c-c = Phase %isplacement of Rotor &urrent

    (Equation2-3) 2-3)

    2-1

    As acceleration continues, rotor frequency and inductive

    reactance decreases. The rotor flux moves more in-phase with

    stator flux and torque increases. Maximum Torque (or

    Break-down Torque) is developed at point C inFigure2-14,where

    inductive reactance becomes equal to the rotor resistance. Beyond

    point C, (points D, E and F) the inductive reactance continues to

    drop off, but rotor current also decreases at the same rate,

    reducing torque.

    stator

    Point G is synchromous speed and proves that if rotor and

  • 7/24/2019 Motor Fundamentals

    9/27

    are at the same speed, rotor current and torque are zero.

    At running speed, the motor will operate between points F

    and D, depending on load. However, temporary load surges may

    cause it to slip all the way back near point C on the knee of the

    curve.

    Beyond point C, the power factor decreases faster than

    current increases, causing torque to drop-off. On the linear part of

    the motor curve (points C to G), rotor frequency is only 1 to 3 Hertz

    - almost DC. Inductive reactance is essentially zero and rotor

    power factor approaches unity. Torque and current now become

    directly proportional - 100% current produces 100% torque. If a

    motor has a nameplate current of 3.6 amps, then when it draws 3.6

    amps (at proper voltage and frequency) it must be producing 100%

    of its nameplate torque. Torque and current remain directly

    proportional up to approximately 10% slip. This relationship isvery useful when troubleshooting the motor and driven machine.

    Notice that as motor load increases from zero (point F) to

    100%, (point E) the speed drops only 45-55 RPM, about 3% of

    synchronous speed. This makes the squirrel cage induction motor

    very suitable for most constant speed applications (such as

    conveyors) where, in some cases, 3% speed regulation might be

    acceptable. This compares favorably with shunt wound DC

    motors. If better speed regulation is required, the squirrel cage

    motor may be operated from a closed loop regulator. As an

    alternative, a reluctance synchronous induction motor (see pages

    2-12 and 2-13) may be used instead of a squirrel cage induction

    motor.

    0MA esi#n ClassesIn the U.S., the National Electrical Manufacturers

    Association (NEMA) has a standard on motors and generators;

    NEMA Standards Publication No. MG 1. This standard has

    classified squirrel cage motors according to their locked rotor

    torque and current, breakdown torque, pull-up torque, and percent

    slip. The four major classifications are A, B, C and D. They differ

    primarily in the amount of rotor resistance and inductance each

    possesses. Increasing a rotors resistance increases Starting

    Torque but also decreases Breakdown Torque, overall efficiency,

    and speed regulation (slip increases).

    2-17

  • 7/24/2019 Motor Fundamentals

    10/27

    The NEMA design D motor has the highest resistance rotor

    for maximum starting torque(Figure2-18, seepage2-19). It has

    no Pull-up or Breakdown Torque and is used where high starting

    torque is critical. Acceleration of the flywheel on a punch press is

    an excellent application for NEMA D motors.

    These motors have the lowest efficiency of the 4 types

    mentioned. They are available in two ranges of slip: 5% to 8% and

    8% to 13%. The higher slip motors produce greater Starting

    Torque, but lower slip motors possess a greater instantaneous

    overload capability.

    Figure 2-19shows the phase to phase wiring of a standard

    squirrel cage motor. Note the resemblance to a 3 phase

    transformer. The stator is the primary and the rotor acts as the

    secondary. This comparison helps to emphasize the minimalmaintenance required on squirrel cage motors, Its just a

    transformer that rotates. How much maintenance do you perform

    on transformers?

    1''ase A

    $ STATORROTORTe Motor is 6er/ similar to a Transformer

    Figure 2-19

    2-2#

    A transformers magnetic coupling is fixed, but the motors

    coupling between stator and rotor changes. When slip is 1, the

    coupling is optimum. This occurs at locked rotor, when the

    induced rotor voltage is highest and rotor current is maximum,

    Figure2-12, point A(page2-11). This may be compared to the

    transformer with a shorted secondary circuit. As the rotor

    accelerates, slip decreases from 1 to as little as 0.1 (no load speed).

    The primary to secondary coupling deteriorates and induced rotor

    voltage is very low. Rotor current is as low as the secondary

    current in an unloaded transformer.

    Although an unloaded transformer may draw only 2% of

    rated primary current,Figure2-12, point E(page2-11) shows

    that the unloaded squirrel cage stator draws about 40% current.

    One reason for this is because the motors magnetic coupling is not

    as efficient as a transformer coupling. This is due to the air gap

  • 7/24/2019 Motor Fundamentals

    11/27

    between stator and rotorFigure2-9(page2-7). The stator must

    draw extra current to increase the flux density of its magnetic field

    and bridge the air gap. A narrow air gap requires less no-load

    current than a wide air gap, so motor designs incorporate the

    narrowest air gaps possible. This improves efficiency and power

    factor.

    However, if the air gap is too small there is a danger that

    the rotor may actually contact the stator, short circuiting it.

    Maintaining a precise air gap requires precision rotor bearings and

    careful machining.

    There are other no-load losses besides the air gap. The

    rotor must produce enough torque to spin the shaft-mounted fan to

    cool itself. This loss is known as Windage. The rotor must also

    overcome friction from the bearings which support it. There are

    also iron (Hysteresis and Eddy Current) and copper (12R> losses to

    consider. The sum of these losses result in the unloaded motor

    drawing as much as 40% of rated current. It is more important,

    therefore, to carefully size induction motors. An oversized motor

    might never operate at rated horsepower, resulting in poor

    efficiency and power factor.

    Figure2-20(see page2-22) shows the relationship

    between efficiency, power factor and load for an average squirrel

    cage motor. A fully loaded motor is more efficient than the same

    motor running at quarter load. Also, a large HP motor is moreefficient than a small motor. High speed motors are more efficient

    than low speed motors. Medium and low voltage motors (230 to

    460V) are more efficient than high voltage (2300V) motors and

    normal slip motors (NEMA A, B, C) are more efficient than high

    slip (NEMA D) motors.

    2-21

    100

    85

    ((ICI0C:0 25

    'o9er (actorIllI IIll III1

    75 100 125

    OA ;Figure 2-20

    ffects of &olta#e &ariationsRecall fromEquation2-3that torque is determined by

    stator flux and rotor current, which result from rotor voltage. For

    a given slip, rotor voltage is directly proportional to the density of

  • 7/24/2019 Motor Fundamentals

    12/27

    the stator flux being cut. Stator flux is directly proportional to

    stator current (until the saturation level is reached). Therefore, if

    the motors applied frequency is held constant, stator current and

    flux will rise and fall in direct relation to the applied voltage.

    Increased voltage yields higher flux density, which means

    that higher rotor voltages are induced at a given slip.

    It follows then that less slip is required to produce rated

    torque at the motor shaft. The slip from no-load to 150% full load

    becomes more vertical as shown inFigure 2-21,where stator

    applied voltage has been increased by 10%. Notice that the entire

    torque curve is affected by this increase.;O(

    9,?1221++)12S'

    Figure 2-21

    2-22

    If applied voltage is decreased, flux is decreased, flux and

    the rotor must slip back more in order to produce rated torque.

    This is clear from the 90% and 50% curves inFigure2-21.Also

    observe that 90% rated voltage, does not produce 90% of the rated

    torque, but rather only 81%. 50% voltage only produces 25% rated

    torque. This is because both stator flux and rotor current are

    affected by voltage variations. As such, torque varies not directly,

    but rather by the square of the applied voltage. With some

    manipulation (not elaborated here),Equation2-3may be restated

    from the voltage standpoint:

    Where:T = torue at any slipKt = a ne torue constant = $olta4e applied to the stator indin4s

    (Equation 2-4)

    The relationship between voltage and torque is especially

    important during troubleshooting. Low voltage can cause any of

    the following problems:

    Inadequate Starting Torque- If a motor and load are

    closely matched, then a 10% drop in line voltage (even momentary)

    during starting could result in load torque demand exceeding

  • 7/24/2019 Motor Fundamentals

    13/27

    motor torque.

    Speed Fluctuations- A momentary drop in line voltage

    will cause a proportional dip in speed. Compare the 100% curve

    and 90% curve ofFigure2-21.Notice that at rated load the 90%

    curve requires more slip. The resulting drop in speed may causeproblems in the driven machine or process.

    Reduced Speed -A prolonged drop in voltage may result

    in the motor never reaching its nameplate rated base speed. Also,

    speed regulation would be poor; since greater slip is required for

    normal load changes.

    Reduced Peak Torque- A 10% voltage decrease will

    reduce Peak Torque (Breakdown Torque) by 19%. If the

    application involves momentary load surges, there may not be

    adequate Peak Torque to ride through the surge. Severe speed

    fluctuations or even a complete stall may result.2-23

    For example, consider a motor nameplate rated at 230

    voltage (ENP) and 20A (INP). If line is increased to 245V (ELI&

    the full load current (I& would be only 18.8 amps.IFL 5 27 = 2# + 4 = 1/./ mps

    If line voltage is reduced to 208, then the full load current

    will increase to a value of 22 amps. When determining expected

    motor current, the following values are accurate within 20%. A

    30 squirrel cage motor operating at 230V draws 3 amps/HP. A460V motor draws 1.5 amps/HP and a 575V motor draws 1 amp/HP

    In contrast, a single (21 motor at 115V draws 10A/HP and at 230V

    draws 5A/HP.

    Using the effects of voltage variations on a motor can be

    used as an advantage. By limiting the voltage to the motor during

    starting, the current drawn and the torque produced by the motor

    can be regulated. There are four different common methods for

    reduced voltage starting: Autotransformer, Wye-Delta

    (Star-Delta), Part Winding and Solid State.

    Autotransformer reduced voltage starting is the most

    commonly used method in North America. This method has three

    adjustments which can be set to provide different torque and

    current settings.Table2-Bshows a comparison of the different

    types of starting and the corresponding reduced current and torque

    of the motor.

  • 7/24/2019 Motor Fundamentals

    14/27

    Outside North America, Wye-Delta or Star-Delta starting is

    used most often. However, throughout the world Solid State

    starting is very popular and in some areas has replaced traditional

    electro-mechanical starters as the preferred method of reduced

    voltage starting. The ability to make a wide range of adjustments

    so that the motor and load can be matched more closely is one of

    the reasons for its popularity.Table2-Bshows these adjustments.2-2

    III. MOTORS A0 A@,STAB (R>,0C: RI&SIn the curves ofFigure2-24(see page2-29) the voltage (E)

    remained constant while frequency varied. Since frequency (F)

    appears in the denominator of the right hand term, stator currentmust vary as inverse of frequency (I/F).Figure2-24(see page

    2-29) bears this out: 105% frequency produces only 95% current

    and 95% frequency results in 105% current. They are inversely

    proportional if applied voltage is held constant. This poses a

    problem for motors operated from adjustable frequency drives.

    Drives are capable of generating a broad range of output

    frequencies to change a motors synchronous speed when required.

    If a drives output voltage is fixed while its frequency is changed,

    motor problems can quickly develop. For example, if the output

    frequency is reduced from 60 Hz to 30 Hz (50%) the stator current

    would double, overheating the motor. If frequency is increased

    from 60 Hz to 120 Hz, current is halved and torque would suffer.

    To prevent overheating at 30 Hz, the current must be reduced. To

    provide adequate torque at 120 Hz the current must be increased.

    RecallingEquation2-9, the only value left to manipulate is E, the

    applied voltage.

    If the stator applied voltage were to be reduced 50% while

    the frequency is being decreased 50%, the ratio of voltage to

    frequency would remain constant.

    Stator current would not increase and assuming cooling is

    not affected by speed, the motor would not overheat. Torque would

    be unaffected, and the motor would perform properly at the

    reduced speed. In reality, this is the method adjustable frequency

    drives use: change the voltage with the frequency to maintain

    proper current and torque.

  • 7/24/2019 Motor Fundamentals

    15/27

    Every AC motor has a ratio of voltage to frequency, known

    as itsVolts per Hertz Ratio.As long as voltage and frequency

    are held in this relationship, the motor will function properly. A

    motors Volts per Hertz Ratio can be determined by its nameplate

    data. For example, a motor nameplate for 460 Volts and 60 Hz has

    a Volts per Hertz ratio of 460/60 or 7.6V/Hz. A motor rated for 380

    Volts at 50 Hertz also has a 7.6V/Hz ratio.

    These ratios indicate that for each 1 Hertz increase of

    frequency, the voltage must be raised by 7.6 Volts to offset the

    effects of inductive reactance. If the frequency is decreased by 1

    Hertz, then the voltage must be lowered by 7.6 Volts for the same

    reason.

    3-l

    At very low frequencies, the stator winding resistancebecomes a large portion of the overall impedance. As a result,

    most of the applied voltage drops across the resistance. This

    leaves very little voltage to excite the stator electromagnetic circuit

    to produce torque. Recall that the stator impedance is really:

    not just F, as used for illustration.

    It is the R2 term that dominates below 15 Hertz of motor

    operation. The logical solution to this problem is to boost the

    applied voltage at very low frequencies to offset R2.

    This is precisely what the adjustable frequency drive does

    (see Figure 3-3).Some manufacturers call it Low Speed Boost,

    Low Volts/Hertz Boost, or simply IR Compensation. Its effect is

    shown in the torque curve ofFigure3-4(seepage3-4). The

    torque curve is very flat, matching that of the DC shunt motor.

    Some of the newest microprocessor controlled AC drives can match

    this torque curve when coupled to a high efficiency squirrel cage

    motor. The limiting factor becomes motor cooling at low speeds.

    4$+&olta#e Boostedat o9 (re%uencies

    34AC &OTA7&OTS?23+1 3+ 4(R>,0C: ?$+

    Figure 3-3

    3-3

  • 7/24/2019 Motor Fundamentals

    16/27

    When replacing line starter with an AC drive, the same

    motor, wiring and conduits may be used. The drive may be

    remotely mounted as far as one mile from the motor for

    convenience or safety. Sometimes the customer may retain the line

    starter as a back-up system. In the event of a system malfunction,

    the line starter can bypass the drive to operate the motor

    temporarily. Bypass capability is a requirement in some

    applications such as water treatment pumps or boiler pumps.

    Other drive methods (i.e. DC drives, eddy current clutches and

    hydraulic drives) are much more expensive to bypass. (Always

    check NEMA specifications and local codes to assure safe wiring

    practices.)

    Improved speed regulation is available with AC drives. A

    line started squirrel cage motor will drop approximately 3% inspeed when fully loaded. By installing a tachometer on the motor,

    the AC drive can actively monitor motor speed and improve speed

    regulation to as high as 0.1%.

    Operation A5o6eA motor rated for 60 Hz operation may be run at higher

    frequencies when powered by an AC drive. The top speed depends

    upon the voltage limits of the motor and its mechanical balancing.

    230V and 460V motors normally employ insulation rated for 600V,

    so the voltage limit is not usually a problem. An average 2 pole

    industrial motor can safely exceed base speed by 25%. Many

    manufacturers balance their 3 pole and 4 pole rotors to the same

    speed - 25% over the 2 pole base speed. A 4 pole motor may

    therefore operate up to 125% over base speed before reaching its

    balance limit. A 60 Hz 4 pole motor might run up to 135 Hz,

    whereas a 60 Hz 2 pole motor would reach its balance limit at 75

    Hz. Both motors would run at the same RPM. Naturally, it is

    sound advice to consult the motor manufacturer before exceeding

    any motors base speed by more than 25%.

    Constant &olta#e OperationFigure3-3 shows that at 60 Hz the AC drives output is

    460 Volts, its maximum value. What happens if the output

    frequency is increased above 60 Hz while the voltage remains at

    460V? The drives Volts per Hertz ratio no longer remains constant

    and available torque decreases.

    If output frequency is increased to 120 Hz with 100%

  • 7/24/2019 Motor Fundamentals

    17/27

    voltage applied to the motor, the Volts per Hertz of the drive is no

    longer 7.6 but rather 3.83. The same Volts per Hertz ratio results

    when a line started motor is operated at 60 Hz with only 50%

    voltage applied (for reduced voltage starting). As might be

    expected, the effect on torque is the same. Recall that torque

    varies as the square of the applied voltage(Equation2-4).As

    such, maximum motor torque at 120 Hz is only 25% of the

    maximum torque at 60 Hz.3-6

    If AC drive output frequency is reduced from 120 Hz to 90

    Hz at constant voltage, the Volts per Hertz ratio improves from

    3.83 to 5.1 V/Hz. This is the same as providing 66% voltage at 60

    Hz to a line-started motor. Torque will be 0.662 or 44% of the full

    voltage torque at 60 Hz.Figure 3-5illustrates the peak torque

    curve for constant voltage operation from base speed to 4 timesbase. On a 60 Hz rated motor this would cover 60 Hz to 240 Hz.

    The motors rated torque (at 100% current) and intermittent

    torque (at 150% current) both decay at the same rate.8'ATOR>,100

    75

    50

    25

    1.0

    .06

    $

    Base 1.25 1.5 1.75 2 2.25 2.5 2.75 3.0 3.25 3.5 3.75 4.0

    For 60Hz Motor: 60 75 90 105 120 135 150 165 180 195210 225 240

    M,TI'S O( BAS S'Figure 3-5

    Since the voltage, in reality, is not changing above base

    speed, it is more appropriate to define torque in terms of frequency

    change instead of voltage change. It can be stated then that

    torque above base speed drops as the square of the frequency -

    doubling the frequency, quarters the available torque. Applied

    frequency and synchronous speed are equivalent, so going one step

    further, torque may be defined in terms of speed. In the constant

    voltage range then, motor torque drops off as the inverse of

    synchronous speed squared, or 1/N2. This is shown by the curve in

    Figure 3-5.

    Many machine applications are constant horsepower in

    their load characteristics. As speed increases, the torque required

    decreases as the inverse of speed, or l/N. This torque drop-off is

  • 7/24/2019 Motor Fundamentals

    18/27

    not as severe as the motors l/N2 torque drop-off.Figure3-6(see

    page3-8) displays the motor maximum torque and a nameplate

    rated constant horsepower load.3-, O6ersie Motor

    MotorBase 1.25 1.5 1.75 260 75 90 105 120 Hz

    Figure 3-6

    Notice that motor available torque exceeds load torque up

    to approximately twice base speed. Beyond this point the load

    exceeds the motor capability and would cause a stall condition.

    If frequency is reduced so that the motor runs between

    points A and B on the curve, a small load surge could still stall the

    motor. Beyond point A there is not enough overload cushion

    between the load demand and the motors peak capability. The

    motor is not capable of safely powering a constant horsepower loadbeyond point A on the curve.

    In the constant voltage mode of operation the range of

    constant horsepower extends only to 1.5xbase speed. This does

    not compare favorably with DC drives that provide constant

    horsepower up to 3 or 4xbase speed. However, Voltage Source

    AC Drives can achieve constant horsepower without modification

    to the drive or motor - its a standard feature.

    In order to exceed point A on the curve ofFigure 3-6,a

    safety margin must be added to handle temporary load surges. If

    the existing motor is replaced by one of greater horsepower, the

    motors peak curve will increase, providing a safety margin as

    shown in the insert ofFigure 3-6.However, with the existing

    motor, the curve cannot be raised. Instead, the load must be

    reduced to provide a margin for overloads.

    By lowering the load curve to 2/3 of the motors peak curve,

    an acceptable overload cushion is established.Figure3-7shows

    the derated curve for operation above 1.5xbase speed. Derating

    assures an adequate cushion for momentary overloads.

    3-)The method of motor cooling will affect available torque in

    speed ranges above1.5to 1. Shaft mounted cooling fans present a

    variable torque load to the motor, which becomes appreciable at

    high speeds. Other factors, such as the exact load profile, the

    motors actual peak torque, service factor, and environment act to

    complicate matters. Often times it will be necessary to consult the

  • 7/24/2019 Motor Fundamentals

    19/27

    motor manufacturer and AC drive application engineer before

    exceeding the 1.5 to 1 speed range.Motor'ea"1.2 1.4 1. 1. 2.+ 2.2M,TI'S O( BAS S'

    Figure 3- 7

    Some motor applications, such as conveyors, require 100%

    (nameplate) torque throughout the speed range. To increase

    production it may be desired to operate the conveyor motor above

    its base speed. An AC drive in the constant voltage mode can

    provide 100% torque for a limited speed range.Figure3-8(see

    page3-10) illustrates that 100% torque is available up to 1.25x

    base speed while maintaining a 25% overload cushion.3-9

    'ea"

    TOR>,Tor%ue at Rated Current1.2 1. 2S'

    Figure 3-8

    Notice that the motor torque at rated (nameplate) current

    drops off just as the peak torque does. In order to produce rated

    torque, the motor must draw greater than rated current. The

    additional heat generated is normally offset by increased airflow

    from the motors fan. However, totally enclosed motors may

    overheat if rated torque is demanded continuously above base

    speed. Consult the motor manufacturer when employing totallyenclosed motors above rated speed. Oversize motors (higher

    horsepower) may be recommended to assure adequate cooling and

    torque.

    Constant Tor%ue Ran#eAn AC drive in the Constant Voltage mode cannot provide

    continuous constant torque beyond the 1.25 to 1 speed range

    (oversizing the motor may extend this range to 1.5 to 1). To

    develop Constant Torque beyond this limit, the drive must operate

    in a true Constant Torque mode, not the Constant Voltage mode.

    The drives Volts per Hertz must again match the motors Volts per

    Hertz ratio. There are 3 ways to achieve this.

    1. Rewind the Motor -Most stators are wound such that

    base speed is achieved at 60 Hz or 50 Hz. Higher base speeds

    (such as 90 Hz or 120 Hz) can be obtained by special request to the

    manufacturer. The curves of a pole motor wound for 90 Hz base

  • 7/24/2019 Motor Fundamentals

    20/27

    speed are shown inFigure3-9.

    3-10

    AC drives do not produce sinuosidal voltages, but rather

    generate square wave or pulses of voltage, which would saturate

    and destroy a standard transformer. Special purpose customdesigned transformers are therefore essential for proper operation.

    These transformers become quite expensive, approaching or

    exceeding the price of a small AC drive. It may not be economical

    to install such a transformer on small drive applications.

    On larger applications output transformers are sometimes

    used to match low voltage drive to a high voltage motor. This is

    done in the petrochemical industry where the output voltage of a

    460V AC drive may be stepped up to operate a 2300 Volt pump

    motor from zero to its base speed. The price of such a transformer

    was motivation for the development of high voltage semiconductors

    for the output stages of AC drives.

    Notice inFigure3-10(see page3-11) that the step-up

    transformer halves the current while doubling voltage. To supply

    100% (nameplate) current to the motor, the drive must produce

    200% current at its output. The AC drive must be doubled in size:

    a 10 HP drive is needed to power the 5 HP motor for constant

    torque up to 120 Hz. If the range is reduced to 90 Hz, a 7l/2 HP

    drive would provide rated current at the motor. This is because

    the transformers winding ratio would be changed from 2 to 1 to

    1.5 to 1.

    Figure 3-11displays the voltage and torque curve of a 5

    HP 230 volt motor when operated from an AC drive with an output

    transformer.

    T9ice Rated '2++TOR>,A0&OTA7;? 1 ++

    'ea" Tor%ue(re%uenc/ ? $+ D 12+ Speed 2.+

    Figure 3-11

    The motor is rated for 60 Hz and has a V/Hz ratio of 230/60

    or 3.83. The drives V/Hz ratio has been adjusted to 1.92 V/Hz

    because its output voltage will be doubled by a transformer,

    providing the motor with 3.83 V/Hz for constant torque operation.

  • 7/24/2019 Motor Fundamentals

    21/27

    3-12

    At 60 Hz the motor receives 230 Volts and produces 5 HP

    when fully loaded. At 120 Hz the motor voltage is 460 Volts. Since

    both voltages and frequency are doubled, the V/Hz ratio remains at

    3.83 and rated torque may be obtained. Increased motor losses at

    the high speed and frequency will cause the motor to draw greater

    than rated current to produce rated torque. However, the motor is

    not over or under voltaged and will perform properly, producing 10

    HP at 120 Hz. This justifies the 10 HP drive required to assure

    adequate current. Still, the oversize drive and transformer

    increase the price of a system significantly, normally making it

    uneconomical. In addition, the step-up transformer limits the

    available torque at low frequencies, limiting the range of constant

    torque. This occurs because the transformer may saturate and

    overheat at low frequencies, demanding that the current (andtorque) be reduced. The third method of producing constant torque

    above rated speed is more practical.

    3. Use a 460V Drive for a 230 Volt Motor -The curves

    ofFigure 3-11may be obtained without placing a transformer

    between the drive and motor if the drive can produce 460 Volts

    directly at its output. The drives V/Hz ratio must be set at 3.83 to

    accommodate a 230 volt motor. Also, since a 230 volt motor draws

    twice the current of a 460 volt motor of equal horsepower, the AC

    drive must double in size.

    As current flows through the stator and rotor a counter

    voltage is generated, just as in a transformer. The counter voltage

    opposes the applied voltage and acts to limit motor current.

    Normally the applied voltage exceeds the counter voltage and

    power is supplied to the motor. However, if the counter voltage

    exceeds the applied voltage, the motor will effectively become a

    generator and feed power back onto the supply lines. The

    generated power will be at the same voltage and frequency as the

    supply and the motors power factor will be leading instead of

    lagging. The magnitude of generated power is dependent on thedifference between applied voltage and the counter voltage.

    During normal operation, motor synchronous speed exceeds

    the running speed by the amount of slip as shown by point A in

    Figure3-12(see page3-14). If the load overhauls the motor (pulls

    the rotor faster than synchronous speed), slip reverses. The rotor

    bars begin to cut the stator field from the opposite direction, which

  • 7/24/2019 Motor Fundamentals

    22/27

    reverses the polarity of rotor voltage. Rotor counter voltage then

    exceeds the rotor induced voltage and produces a larger voltage of

    mutual inductance in the stator windings. This voltage is the

    same polarity as stator counter voltage and results in a net voltage

    polarity reversal, feeding power back to the supply lines.3-13

    TOR>,E3++;, , , :, , , , S'.25 .5 1.75

    -1++; --2++; -

    Figure 3-12

    Point B inFigure 3-12illustrates that an overhauling load

    has occurred; the rotor is moving faster than the stator field speed

    dictates. Notice that 100% current flows but that torque is

    negative and produces a retarding force that opposes theoverhauling load. It is an effective means of braking the load

    while retrieving power that has been put into the mechanical load

    by the motor originally. Braking of this type is called Regenerative

    Braking and occurs frequently in many applications, such as

    motor-generator sets and wind-powered AC generators.

    Regeneration occurs in AC drives during the deceleration

    process as well as during overhauling loads. If the motor is

    running at 60 Hz and the frequency is quickly decreased to 50 Hz,

    the rotor will suddenly be turning faster than synchronous speed

    and begin regenerating. Negative torque rapidly decreases motor

    speed to match the 50 Hz applied frequency. If frequency is

    reduced further, regeneration will again occur. By ramping down

    the applied frequency at a steady rate, an AC drive can effectively

    and economically brake its load down to almost zero speed. No

    mechanical brakes are required and much of the loads kinetic

    energy can be retrieved.

    This is especially desirable on high inertia loads, where

    much energy is expanded during acceleration.

    Quadrant 1 ofFigure3-13shows the motoring torqueduring forward operation when a squirrel cage motor is powered

    from a variable frequency supply (AC Drive). Quadrant IV is the

    generator torque for the same frequencies. Note that the

    magnitude of peak generator torque equals peak motoring torque

    and that regenerative torque is possible throughout the entire

    speed range.

  • 7/24/2019 Motor Fundamentals

    23/27

    3-1

    The energy efficient motor differs from a standard motor in

    both design and manufacturing techniques. It is not, as some

    suppose, a return to the old U frame motors of the past.

    First of all, the energy efficient motor employs larger stator

    conductors with higher conductivity. The rotor bars are larger as

    well, to reduce the overall copper (or aluminum) loss which

    comprises 55-60% of total motor losses. The motor flux density

    and air gap are reduced to minimize the magnetizing current

    required. Stator and rotor laminations are thinner to increase

    resistance to the flow of eddy currents. More laminations are

    added to the core stacks as well, producing a longer stator and

    rotor for increased torque. Hysteresis losses, which are normally

    20-25% of the total motor losses, are reduced by utilizing siliconsteel, instead of low carbon steel for the laminations. As a result,

    the motor uses less current, has better power factor, and runs

    cooler.

    Since the energy efficient motor runs cooler, ventilation

    requirements are reduced, allowing a smaller fan to be installed.

    Windage loss (typically 5-9% of total losses) decreases and the

    smaller fan runs quieter. These motors are less susceptible to

    damage from impaired ventilation and operate well at higher

    altitudes also. Cooler operation also increases motor life.

    Insulation life is up to 4 times longer, an important fact, since

    insulation break-down is the number 1 cause of motor failures.

    Bearing lubrication lasts longer too, doubling the interval between

    required lubrication. Cooler operation means that less burden is

    placed on air conditioning equipment, (The Textile Industry uses

    many squirrel cage motors in air conditioned factories.) Energy

    efficient motors can also operate in higher ambient temperatures

    without requiring extra cooling. A standard motor may need

    additional cooling to survive in the same environment. This could

    add substantially to the purchase price of the motor.Energy efficient motors are also more rugged than standard

    motors, tolerating greater fluctuations in applied voltage, voltage

    unbalance, and overload.

    Some manufacturers line of energy efficient motors all

    possess 1.15 service factors. Some can even tolerate 30-40%

    overloads for prolonged periods. They are also capable of starting

  • 7/24/2019 Motor Fundamentals

    24/27

    higher inertia loads than standard motors because of their

    increased thermal capacity. For example, manufacturers standard

    50 HP motor can accelerate a maximum inertia of 597 lb ft while

    an ener

    57

    efficient model can accelerate an inertia load as high as

    764 lb ft .

    Energy efficient motors tolerate non-sinusoidal waveforms

    better than standard motors. This is important when the motor is

    powered by an AC drive.Figure4-1shows the speed-torque

    curves for an energy efficient and standard motor powered by a 6

    step AC drive.-2

    8OA

    --w---- $!$"ResistantFCurrent

    1G Ho + 1$+(R>,0C: D?

    Figure 4-l

    Notice that the standard motor has been derated to 85%.

    This is due to the heating caused by the waveform shown in the

    right corner. To provide the same performance as the energy

    efficient motor, a larger standard motor is required. No derating is

    required on the energy efficient motor, since it can tolerate the

    disturbances caused by the 6 step waveform. Other types of AC

    drives produce smoother waveforms that would not require

    derating of the standard motor. One such type is the PWM (Pulse

    Width Modulated) AC drive.

    Energy efficient motors prove most cost effective in

    applications where:

    The cost of electricity is high. The higher the power rate, the

    greater potential for savings.

    The customer is concerned about power factor penalties and

    peak demand charges.

    Loads are constant, allowing accurate projection of potential

    savings.

    Excessive heating is expected, either from high ambient

    conditions or severe duty cycle.

  • 7/24/2019 Motor Fundamentals

    25/27

    Running time exceeds idle time, again increasing savings.

    Larger horsepower motors are involved, since they consume

    more power and represent greater savings potentials.4-3

    &. S'CIA MOTORS

    The Wound Rotor Motor is an induction motor that permits

    variable speed operation without the use of an AC drive. The

    motors stator is identical to that of the standard polyphase

    squirrel cage motor, but its rotor differs considerably. The rotor is

    not of cast aluminum or copper bars, but rather consists of

    insulated coils of wire connected in regular succession to form

    definite poles (the same number as the stator poles). The ends of

    these rotor windings are brouht out to slip rings mounted on the

    motor shaft. Carbon brushes ride the slip rings to connect the

    rotor windings to an external resistor network.Figure 5-lshows the controller, which allows adjustment

    of the rotor resistance. By varying rotor resistance, the torque and

    current characteristics can be changed. For example, high

    resistance would produce high starting torque at low current,

    similar to a NEMA D motor. As the motor accelerates, resistance

    can be reduced to simulate a NEMA A motor. The result is

    high starting torque, smooth acceleration, and optimum efficiency

    at running speeds.JternalT1 T2 T3

    on RotorFigure 5-l

    Figure5-2(see page5-2) is the speed/torque curve of a

    Wound Rotor Motor. It portrays the speed regulation obtained by

    inserting various amounts of resistance in the rotor circuit. Notice

    that with 100% resistance the rotor will slip 50% in speed when a

    50% load is applied (Point A). Reducing resistance to 30%

    improves speed regulation considerably (Point B).5-l

    260

    250

    240230

    220

    210

    200

    190

    180

    170

    160

    8 150(, 140

  • 7/24/2019 Motor Fundamentals

    26/27

    130

    OA 120TOR>, 110100

    90

    80

    70

    60

    50

    40

    30

    20

    10

    010 20 30 40 50 60 70 80 90 100

    S' ; O( S:0CRO0O,SFigure 5-2

    A means of variable speed operation is achieved with the

    Wound Rotor Motor. Unfortunately, the motors efficiency

    decreases in direct proportion to the speed reduction desired.

    Because of this, the wound rotor motor is most often used on

    cranes, hoists and elevators, where exact speed regulation andefficiency are not important. Efficiency may be improved by the

    installation of a slip recovery system in the rotor circuit. Basically,

    the external resistances are replaced by a solid state converter

    which feeds the excess rotor power back to the supply lines.

    Another type of special motor is the Reluctance

    Synchronous Motor. It again uses the same stator assembly as a

    standard squirrel cage motor and differs only in rotor construction.

    Figure5-3shows a rotor punching used in a typical Reluctance

    Synchronous Motor.-2

    (luJBarriersAluminum

    Figure 5-3

    The rotor bars permit the motor to start as an induction

    motor, with similar torque and current characteristics. Notice the

    flux barriers inFigure 5-3,which guide the rotor flux to form

    definite magnetic poles. At approximately 90% sync speed, the

    rotor and stator fields begin to closely align, causing the rotor to

    quickly accelerate to synchronous speed. Motor current increases

    sharply during the transition to synchronous speed. However,

    once in synchronism with the stator, the motor draws rated

    current to produce rated torque without slip as shown in

    Figure5-4. Speed regulation becomes dependent on the stability

    of the applied frequency, which is normally excellent.TOR>,;S:0CRO0O,SS'

  • 7/24/2019 Motor Fundamentals

    27/27

    Figure 5-4

    Reluctance Synchronous Motors are specified when speed

    regulation is a primary factor, such as in the machine tool and

    textile industries. Normal sizes range from fractional to 15 HP,

    although higher horsepowers are available. Efficiencies are low

    (3575%) and power factor is also poor (.45-.63). They are not

    recommended for high inertia loads or heavy cyclical loads. This is

    because the rotor must accelerate into its synchronous position

    rapidly, making the jump from 95% speed to 100% speed very

    quickly. High load inertia or a pulsating load makes this difficult.-3

    Publication 150-2.7 December 1998 Copyright 1998 Rockell !nternational Printe" in #$%