more than simple voltage regulation.in3430220/00 en – tapcon ® 240 – tapcon 260 – f0305500...
TRANSCRIPT
TRANSFORMER CONTROL
TAPCON® 240TAPCON® 260
MORE THAN SIMPLE VOLTAGE REGULATION.
TAPCON® 240 ANd TAPCON® 260 – VOLTAGE REGULATORS FOR EVERY APPLICATION.
TAPCON® 240, TAPCON® 260
3
The modular system used in our TAPCON® 240 and TAPCON® 260 voltage regulators provides maximum fl exibility and a comprehensive scope of function. TAPCON® 240 and TAPCON® 260 allow you to run up to 16 transformers in parallel and support the current control system protocols for station automation – ideal for fl exible and convenient voltage regulation. Commissioning on site is done quickly and, above all, in a user-friendly manner thanks to the TAPCON®-trol confi guration software.
TAPCON® 260 – the all-rounder
Our all-rounder, TAPCON® 260, is the right choice for challenging regulation work extending beyond the standard scope of the TAPCON® 240. On request, it can be individually adapted to your requirements.
Maximum operational reliability through integration in redundant networks
With immediate effect, the TAPCON® 260 can also support integration in redundant network systems with the RSTP and PRP protocols. Even if a connec-tion to the control system fails, interrupt-free com-munication is ensured.
Maschinenfabrik Reinhausen (MR) has been developing and manufacturing voltage regulators for over 40 years. All this time, our goal has been to provide our customers with the best possible solutions. The voltage regula-tors of the TAPCON® series provide the right device for all scenarios.
Modular and flexible design
I The ideal solution for both simple regulation tasks and very complex applications such as regulating three-winding transformers or banks of transformers
I Parallel operation of up to 16 transformersI Optional: integrated on-load tap-changer monitoring
Graphic display
I Contrast-rich graphics display with clearly arranged indicators and freely programmable LEds
I Line voltage and on-load tap-changer position are shown in the display, rendering additional displays in the switch cabinet unnecessary
I Illustration of time sequences for measured values and/or analog signals
Quick and reliable
Insulation displacement connectors and diverse assembly variants enable rapid installation
Communication
I Support for all common control system protocolsI TAPCON® 260 can also be integrated into redundant
network systems with the RSTP and PRP protocols
BETTER VOLTAGE REGULATION.
4
We place great emphasis on operator comfort in devices from the TAPCON® range. This includes a contrast-rich graphics display with clearly arranged indicators and freely programmable LEds.
FUNCTIONAL ANd COMFORTABLE VOLTAGE REGULATORS.
TAPGUARd® 240 and TAPGUARd® 260 can be installed quickly due to insulation displacement connectors and diverse assembly variants. The standard control system protocols for station automation are supported – including IEC 61850 Edition 2 with immediate effect. TAPCON® 240 and TAPCON® 260 are therefore ideal for fl exible and convenient voltage regulation.
TAPCON® 240, TAPCON® 260
STATION LEVEL
GRId CONTROL LEVEL
PROCESS LEVEL
SCAdA
RSP20/25
TAPCON®-trol
Line control system
TAPCON®-trol
TAPCON® 240
TAPCON® 240
TAPCON® 260
Overvoltage limit V >
Undervoltage limit V <
Bandwidth+ B
V actual
V desired
– BBandwidth
2nd TAPCON® 240 or TAPCON® 260
TAPCON® 260 – PROVEN TECHNOLOGY, MAXIMUM INdIVIdUALITY.
With the TAPCON® 260, there are no limits to your individual voltage regulation requirements.
5
Extending beyond the function of the TAPCON® 240, our professional TAPCON® 260 device offers virtually unlimited possibilities. The firmware of the TAPCON® 260 is adapted specifically to your needs. This produces a voltage regulator which can handle simple regulation tasks as well as complex challenges and thereby satisfy your every requirement including the regulation of three-winding transformers, parallel transformer bank operations, or individual programming for the phase-shift oscillator regulation.
The parallel bank operation solution
Parallel bank operation is the regulation of a bank of transformers comprising three single-phase trans-formers with three separate motor-drive units and
on-load tap-changers. In this application, one single TAPCON® 260 voltage regulator is enough to control the three motor-drive units. The load voltage of a bank of transformers is regulated as per the voltage regula-tion description.
V
V
V
TAPCON® 260
TAPCON® 240
Solution for phase-shifter regulation
Customized regulation functions are available to meet virtually all customer requirements. For example, a phase-shifter regulation project has already been implemented where a TAPCON® 260 regulates the desired power splitting.
100 MW
TAPCON® 260
TAPCON® 240
Z
100 MW generator
~
TAPCON® 240 ANd TAPCON® 260SCOPE OF FUNCTION.
6
Scope of function TA TAPCON® 240 TAPCON® 260
Basic functions Voltage regulation, including line drop compensation x x
Parallel mode up to number of transformers 16 16
Optional functions Customer-specific topology x x
Cross-monitoring x x
Limit volt x x
On-load tap-changer monitoring (TAPGUARD® 240 function)
x x
Regulation of three-winding transformers – x
Parallel transformer bank operation of single-phase transformers – x
Phase-shifter application – x
Order-specific programming – x
Communication IEC60870-5-101/103 x x
DNP3 x x
MODBUS ASCII/RTU x x
IEC 61850 Edition 2 – x
Tap position capture BCD x x
Current signal x x
Voltage signal x x
Resistor contact series x x
Housing design 19" (1/2 19") 19" (1/2 19")
TAPCON® 240, TAPCON® 260
TAPCON® 260 APPLICATION EXAMPLE: 3 PHYSICALLY SEPARATE SINGLE-PHASE TRANSFORMERSUSED AS PHASE SHIFTERS We were contacted by an Austrian energy provider with a very challenging job: one phase shifter comprising three single-phase transformers. MR's solution: three sets, each comprising three VACUTAP® VR® on-load tap-changers combined with two COMTAP® ARS off-circuit tap-changers. This complex regulation challenge was solved with special programming on four TAPCON® 260 voltage regulators. One TAPCON® 260 was fitted into each of the tap-changer drives of the individual phases (3 x slave) and one master TAPCON® 260 was placed in the control room.
Setting ranges
Desired value 1 ... 3 60 … 160 V
Sensitivity ± 0.5 … ± 9 %
Delay time 1 1 … 600 s
Delay time 2 1 … 10 s
Switching pulse duration 1.5 s
LDC Ur = 0 … ± 25 V
Ux = 0 … ± 25 V
Z compensation Voltage rise 0…15 % of desired value
Limitation: 0 … 15 % of desired value
Undervoltage blocking 60 … 100 % of desired value
Overvoltage recording with high-speed return (can be deactivated) 100 … 140 % of desired value
Cycle 1.5 / 1.5 s
Overcurrent blocking 50 … 210 %
Voltage transformer 0.1 … 999 kV / 100 V
Current transformer 100 … 10,000 A / 5 / 1 / 0.2 A
TAPCON® 240 ANd TAPCON® 260 TECHNICAL dATA.
Operating controls, display
Function keys Manual / automatic
Raise / Lower
Menu keys
Display Monochromatic display with graphics capabilities, 128 x 128 dot
1 LED (green), operating indicator
1 LED (yellow), parallel operation message
1 LED (red) each, message for U<, U>, I>
1 LED (green), NORMset on message
3 LEDs (yellow) for random assignment
1 LED (yellow / green / red) for random assignment
Power supply DC 36 … 72 V, 18 … 32 V
AC, DC 88 … 265 V
Power consumption approx. 25 VA
Protective housing 19" housing
483 x 133 x 178 mm (W x H x D)
Degree of protection IP00 in accordance with IEC 60529
Weight approx. 5 kg
Operating temperature -25 … +70°C
Storage temperature -35 … +80°C
7
Maschinenfabrik Reinhausen GmbHFalkensteinstrasse 893059 Regensburg, Germany
Phone: +49 941 4090-0Fax: +49 941 4090-7001Email: [email protected]
www.reinhausen.com
Please note:
The data in our publications may differ from
the data of the devices delivered. We reserve
the right to make changes without notice.