monitoreo en linea de transformadores

59
Copyright © Siemens Austral Andina 2009. All rights reserved. MONITOREO EN LINEA MONITOREO EN LINEA TM TM D D S S TRANSFORMER MONITORING AND TRANSFORMER MONITORING AND DIAGNOSTIC DIAGNOSTIC SYSTEM SYSTEM

Upload: larry-flowers

Post on 06-Sep-2015

248 views

Category:

Documents


6 download

TRANSCRIPT

  • Copyright Siemens Austral Andina 2009. All rights reserved.

    MONITOREO EN LINEAMONITOREO EN LINEA

    TMTMDDSSTRANSFORMER MONITORING ANDTRANSFORMER MONITORING AND DIAGNOSTICDIAGNOSTIC SYSTEMSYSTEM

  • Page 1 2009-05Copyright Siemens Austral Andina 2009. All rights reserved.

    ED SE PTICabrera L.

    0,5-800 TONS

    0,5-200 M3

    Cu

    Fe

    Madera

    Papel

    Aceite

    CONSTRUCCIN DEL TRANSFORMADOR

    [email protected]

  • Page 2 2009-05Copyright Siemens Austral Andina 2009. All rights reserved.

    ED SE PTICabrera L.

    Interconexin de sistemas

    GEAFOL

    HVDC

    Reguladoresde tensin

    GSU - Generacin

    ReactoresShunt

    Sistemas dedistribucin

    Conversores / rectificadores Hornoselctricos

    TMDSTransformerMonitoring and DiagnosticsSystem

    TLMTransformerLifeManagement

    Traccin elctricaDistribucin inmersosen aceite mineral

    800 kV900 MVA

    RANGO DE APLICACION

    [email protected]

  • Page 3 2009-05Copyright Siemens Austral Andina 2009. All rights reserved.

    ED SE PTICabrera L.

    ANSI/IEEE Std C57.91-1995, IEEE Guide for loading Mineral-Oil Immersed Transformers Part 5 Life Expectations.IEEE Std C57.91TM-1995/Corrigendum 1

    ANSI/IEEE C57.92 1981, Guide for loading mineral oil-immersed power transformers up to 100 MVA, With 55C or 65C Average Winding Rise.

    EXPECTATIVA DE VIDA TIL

    [email protected]

  • Page 4 2009-05Copyright Siemens Austral Andina 2009. All rights reserved.

    ED SE PTICabrera L.

    EXPECTATIVA DE VIDA?

    20.55180 000

    Interpretacin de la vida funcional en Transformadores. (Former IEEE C57.91-1981 criterion)

    15.41135 00025% Permanencia de la resistencia a la tensin mecnica

    17.12150 000200 Permanencia del grado de polimerizacin en el aislamiento.

    ANSI C57.91.1995 CORR. 2001 IEEE Guide for loading mineral Oil immersed Transformers. Considera el criterio

    bastante conservador, a la luz de los clculos que se pueden efectuar utilizando criterios de Montsinger

    7.4265 00050% Permanencia de la resistencia a la tensin mecnica (Former IEEE Std C57.92-1981 criterion)

    AosHoras

    Vida normal del aislamiento

    Bases

    [email protected]

  • Page 5 2009-05Copyright Siemens Austral Andina 2009. All rights reserved.

    ED SE PTICabrera L.

    180.000 horas/(24 horas/da) = 7500 das

    Perdida de vida por da Promedio esperado = 1/7500* 100% = 0.0133%

    PROMEDIO ESPERADO

    [email protected]

  • Page 6 2009-05Copyright Siemens Austral Andina 2009. All rights reserved.

    ED SE PTICabrera L.

    Aging Model CIGRE WG A2.18 Life Management Techniques for Power Transformers

    Bobinas EvolucinDe burbujas

    Agua Partculas

    FibrasLibre Vapor Metal

    Aislamiento Principal

    Productos que envejecen el

    aceite

    Incremento del porcentaje de saturacin

    Decrecimiento de la rigidez dielctrica

    Aceleracin de la tasa de

    envejecimiento

    Burbujas causadas por: SobresaturacinCavitacin

    Sobrecalentamiento.

    MODELO DE ENVEJECIMIENTO DEL AISLAMIENTO

    [email protected]

  • Page 7 2009-05Copyright Siemens Austral Andina 2009. All rights reserved.

    ED SE PTICabrera L.

    Un modelo de riesgo para fallas futuras en transformadores, basado en el envejecimiento. Desarrollado por HSB, y publicado en el ao 2000. El modelo se basa en los modelos de mortalidad, propuestos por primera vez en el siglo 19.

    f(t) = e t[] = es una constante[] = tiempo constante[t ] = tiempo en aos

    Comportamiento de mortalidad en seres humanos. Por Benjamin Gompertz en 1825

    Para una tasa de falla instantnea

    MODELO DE RIESGO PARA FALLAS FUTURAS EN TRANSFORMADORES

    [email protected]

  • Page 8 2009-05Copyright Siemens Austral Andina 2009. All rights reserved.

    ED SE PTICabrera L.

    En 1860 W.M Makeham, modific la ecuacin de Gompertzadicionando un termino constante con el fin de corregir

    la muerte accidental.

    f(t) = A + e t

    A + e tf(t) =

    1 + e t

    [] = Modificador para permitir una curva ms aproximada al incremento de la mortalidad

    en edades avanzadas (1932) W, PERKS, R.E. Berhards and Others

    RIESGO PARA FALLAS FUTURAS EN [email protected]

  • Page 9 2009-05Copyright Siemens Austral Andina 2009. All rights reserved.

    ED SE PTICabrera L.

    + e tf(t) =A+

    K + e t

    Willam Bartley, Hartford Steam Boiler, Inspection & Insurance Co, (2006) Publicadoen Transformer committe tutorial 2007

    RIESGO PARA FALLAS FUTURAS EN TRANSFORMADORES

    [email protected]

  • Page 10 2009-05Copyright Siemens Austral Andina 2009. All rights reserved.

    ED SE PTICabrera L.

    Numero de fallas = [Tasa de falla] x [PoblaciNumero de fallas = [Tasa de falla] x [Poblacin que sobrevive]n que sobrevive]

    La tasa instantnea de falla para transformadores, en un ao dado es la probabilidad de falla por unidad de tiempo, por la poblacin de transformadores que han sobrevivido hasta el tiempo t.

    TASA DE FALLAS EN LOS [email protected]

  • Page 11 2009-05Copyright Siemens Austral Andina 2009. All rights reserved.

    ED SE PTICabrera L.

    TRANSFORMER BATHTUB CURVE

    0

    0.02

    0.04

    0.06

    0.08

    0.1

    0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40

    F

    a

    i

    l

    u

    r

    e

    R

    a

    t

    e

    Despus de 25 aos la tasa de fallasse incrementa exponencialmente

    CURVA BATHTUB DE FALLA [email protected]

  • Page 12 2009-05Copyright Siemens Austral Andina 2009. All rights reserved.

    ED SE PTICabrera L.

    TASA HIPOTETICA DE FALLA

    Tomando 1000 transformadores fabricados en 1964, hay un nmero alto de transformadores que fallan antes de 2008 posteriormente el nmerodecrece, debido a que los sobrevivientes igual disminuyen

    [email protected]

  • Page 13 2009-05Copyright Siemens Austral Andina 2009. All rights reserved.

    ED SE PTICabrera L.

    DISTRIBUCION DE FALLA

    (50%) (Se asume no reemplazos)10GVA ; 250 Unidades de 40 MVA

    Incrementos

    10 GVA

    [email protected]

  • Page 14 2009-05Copyright Siemens Austral Andina 2009. All rights reserved.

    ED SE PTICabrera L.

    4,03%Moisture

    5,91%Maintenance Issues

    7,38%Electrical connection loose or high resistance

    9,80%Insulation Issues

    17,32%Lightning

    29,43%Electrical disturbances

    1,24%Others

    2,01%Sabotage

    2,01%Overload

    (%)Causa de la falla

    CAUSA DE FALLAS

    Bartley William H: International Technical Conference, Methven, New Zealand (April 19-21 2005) Twentyyears period for utilities class transformers

    [email protected]

  • Page 15 2009-05Copyright Siemens Austral Andina 2009. All rights reserved.

    ED SE PTICabrera L.

    Incluye aquellos transformadores en los cuales se evidencia una carga sostenida que excede la capacidad nominal de la placa de caracteristicas

    Overloading

    Inundaciones, tuberias con fugas, agua entrando al tanque por los bushings, y presencia confirmada de agua en el aceite

    Moisture

    Controles desconectados o modificados en forma errnea, prdida de refrigerante, acumulacin de suciedad y de aceite, problemas de corrosin.

    Inadequate Mainten.

    Descargas electricas externas confirmadasLightning

    Unin no apropiada entre metales diferentes, problemas con el torque de conexiones roscadasLoose Connections

    Fallas en la que no se evidencian problemas de sobretensin, se incluyen oxidacin, acidez y humedad (La humedad en el aceite se reporta separadamente) la edad promedio de los transformadores que fallaron debido a problemas del aislamiento fue de 17,8 aos

    Insulation Issues

    Sobretensiones de maniobra, picos de voltaje, disrupciones en las lneas, y otras anormalidades de T&DElectrical Disturbances

    OBSERVACIONES

    CAUSA DE FALLAS

  • Page 16 2009-05Copyright Siemens Austral Andina 2009. All rights reserved.

    ED SE PTICabrera L.

    William H. William H. BartleyBartley, HSB,, HSB, Analysis of Transformer Failures, ProceedingsProceedings of the of the sixtysixty SeventhSeventh AnnualAnnual International Doble International Doble ClientClient ConferenceConference , Boston MA, 2000., Boston MA, 2000.

    William H. William H. BartleyBartley, HSB,, HSB, Failure History of Transformers Theoretical Projections for Random Failures, , ProceedingsProceedings of the TJH2B of the TJH2B TechConTechCon Mesa AZ, 2001.Mesa AZ, 2001.

    Tim HigginsTim Higgins, , Mathematical Models of Mortality, , presentedpresented at the Workshop at the Workshop onon MortalityMortalityModelingModeling and and ForecastingForecasting, , AustralianAustralian NationalNational UniversityUniversity, , FebruaryFebruary 2003.2003.

    William H. William H. BartleyBartley, HSB, HSB, , International Technical Conference, Methven, New Zealand(April 19-21 2005) Twenty years period for utilities class transformers

    IEEE C57.140 IEEE C57.140 DraftDraft 9 9 MarchMarch, 2003,, 2003, IEEE IEEE GuideGuide for the for the EvaluationEvaluation and and ReconditioningReconditioning of of LiquidLiquid ImmersedImmersed Power Power TransformersTransformers , , RowlandRowland James & William James & William BartleyBartley CoCo--ChairChair

    ANSI/IEEE Std C57.91-1995, IEEE Guide for loading Mineral-Oil Immersed TransformersPart 5 Life Expectations.IEEE Std C57.91TM-1995/Corrigendum 1

    ANSI/IEEE C57.92 1981, Guide for loading mineral oil-immersed power transformers up to100 MVA, With 55C or 65C Average Winding Rise.

    CIGRE 12CIGRE 12--2020 GuideGuide onon EconomicsEconomics of Transformer Management ( of Transformer Management ( draftdraft 23.7.02)23.7.02)

    CIGRE A2CIGRE A2--1818 LifeLife Management Management TechniquesTechniques for Power for Power TransformersTransformers

    [email protected]

  • Copyright Siemens Austral Andina 2009. All rights reserved. Siemens AG 2009Energy Sector - Power Transformers

    Siemens TLM Transformer Lifecycle Management

  • Page 18 2009-05Copyright Siemens Austral Andina 2009. All rights reserved.

    ED SE PTICabrera L.

    Transport Installation & Commissioning Desensamble, preparacin para transporte, embarque & pdministracin del transporte, instalacin ensamble y puesta en servicio

    Condition Analysis & On-Site Diagnostics Servicios de laboratorio de aceite, valoracin de condicin,anlisis de equipoexistente,valoracin del ciclo de vida, mediciones elctricas avanzadas, pruebas de alta tensin en sitio.

    Lifecycle Maintenance Preventivo, curativo, correctivo, a largo plazo, secado en lnea, desgasif icado , secado de la parte activa, regeneracin de aceite, manejo de unidades para disposicin final.

    On-line Monitoring Sensores de medida, Gasguard, Tapguard, Monitoreo coherente de unidades, Integracin a subestaciones & monitoreo con servidor central

    Troubleshooting Repair & Retrofit Diagnstico de falla, reparacin en sitio, reparaciones y modif icaciones en fbrica, modernizacin, Repotenciacin

    Spare Parts Accessories Bushings, OLTCs NOLTCs Motor Drives & Contactos, Coolers, Ventiladores & Bombas , Dispositivos de proteccin & Reles, componentes metalmecnicos

    Consulting Expertise Training Servicios de ingeniera, Prevencin & Recommendaciones asesorias para acciones preventivas, correctivas y curativas, Seminarios educativos y Workshops

    [email protected] para transformadores de Potencia

  • Page 19 2009-05Copyright Siemens Austral Andina 2009. All rights reserved.

    ED SE PTICabrera L.

    Origen del Producto

    Introduccin al TMDS

    Arquitectura del sistema

    Visin tcnica

    Informacin adicional

    Agenda

  • Page 20 2009-05Copyright Siemens Austral Andina 2009. All rights reserved.

    ED SE PTICabrera L.

    Principios2005

    Feb 2007 Lanzamiento del TMDS L

    Med 2003

    Med 2004

    Inicios

    Inicio del desarrollo del TMDS

    Se introduce el TMDS

    Se introduce el TMDS 3000

    Siemens Introduce el primer sistema de monitoreo

    Basado en los requerimientos de los clientes Siemens empieza a investigar y evoluciona del data logger al sistema de monitoreo.

    Se hace la adaptacin del producto basados en los requerimientosparticulares de cada cliente.

    Desarrollo de la herramienta

  • Page 21 2009-05Copyright Siemens Austral Andina 2009. All rights reserved.

    ED SE PTICabrera L.

    Lista de experiencia

    Rev. Feb/07

    2007* Furnas Viana Brazil 3 75 345 TMDS 20002007* CESP Jupi Brazil 4 134 440 TMDS 20002007* Entergy Amite USA 1 400 230 TMDS 30002007* ENAP Chile 2 80 110 TMDS 20002007* Enelven Colombia 4 83 138 TMDS 30002007* Enelven Colombia 6 42 138 TMDS 30002007* Enelco Colombia 8 40 115 TMDS 30002007* UHE Lajeado Brazil 4 320 230 TMDS 20002007 Braskem Brazil 1 50 69 TMDS 20002006 Entergy Sterlington USA 1 616 525 TMDS 30002006 Entergy Indian Point USA 2 629 345 TMDS 30002006 Entergy Dell USA 1 672 525 TMDS 30002006 Furnas Rio Verde Brazil 4 15 230 TMDS 20002006 UHE Tucuru Brazil 12 405 550 TMDS 20002006 Furnas Serra da Mesa Brazil 7 80 525 TMDS 20002006 Eletronuclear Angra dos Reis Brazil 4 490 525 TMDS 20002005 Cemig Vespasiano Brazil 2 300 525 TDMS 20002005 Furnas Vitria Brazil 4 75 345 TMDS 20002005 Itaip Brazil 6 275 525 SITRAM2005 Furnas So Jos Brazil 7 200 525 SITRAM

    * On-going project

    QUANTITY

    Reference List for Transformer Monitoring and Diagnostic System

    TYPEYEAR CUSTOMER COUNTRY RATINGS(MVA) RATED

    VOLTAGE (kV)

  • Page 22 2009-05Copyright Siemens Austral Andina 2009. All rights reserved.

    ED SE PTICabrera L.

    TMDS es una herramienta de ingeniera querecolecta datos y los analiza usando los metodosdesarrollados en las normas internacionales, creando una informacin detallada, la cual permitehacer un manejo integral de todos los factoresrelevantes para el correcto funcionamiento de un transformador de potencia.

    Definicin del producto

  • Page 23 2009-05Copyright Siemens Austral Andina 2009. All rights reserved.

    ED SE PTICabrera L.

    Temp ambiente

    Bushings

    OLTC

    Temp. Top Oil

    Temp Inferior Aceite

    Gas en aceiteHumedad

    Nivel Aceite

    Flujo de aceite o agua

    Control Refrigeracin

    Sala Comando Subestacin

    Intranet ClienteCorriente de carga

    Sensores TMDS

  • Page 24 2009-05Copyright Siemens Austral Andina 2009. All rights reserved.

    ED SE PTICabrera L.

    Configuraciones del sistema

  • Page 25 2009-05Copyright Siemens Austral Andina 2009. All rights reserved.

    ED SE PTICabrera L.

    El sistema base es un Paquete Consolidado de Monitoreo (PCM), el cualincluye el sensor Gas-Guard, sensores de las diferentesvariables en lnea y acceso a los ingenieros expertos de Siemens en transformadores, para la asistencia con los anlisis, resolucin y mantenimiento.

    SISTEMA BASE

  • Page 26 2009-05Copyright Siemens Austral Andina 2009. All rights reserved.

    ED SE PTICabrera L.

    Top Oil Temperature: RTD PT100

    Bottom Oil Temperature: RTD PT100

    Ambient Air Temperature: RTD PT100

    Moisture in Oil: Invasive Current Load (Single Phase): Transducer

    Skin Temperature (1): RTD PT100

    Tank Oil Level : Analogue Output

    Gas in Oil Monitoring: GAS-Guard 3

    Fan Motor Current (Bank A): Transducer

    Oi l Pump Motor Current (Bank A): Transducer

    Fan Motor Current (Bank B): Transducer

    Oil Pump Motor Current (Bank B): Transducer

    Standard Data Analysis ModelsStatistical Significance Analysis ModuleLimit Adaption (Learning System)Oil Level ModelCooling System Effectiveness ModelThermal Model 2

    Advanced Winding Hot Spot Thermal ModelLoad Factor Model

    DGA Model (3 Gas)Oil Moisture Content Model

    SISTEMA AVANZADO

  • Page 27 2009-05Copyright Siemens Austral Andina 2009. All rights reserved.

    ED SE PTICabrera L.

    Top Oil Temperature: RTD PT100

    Bottom Oil Temperature: RTD PT100

    Ambient Air Temperature: RTD PT100

    Moisture in Oil: Invasive Current Load (Single & Three Phase): Transducer

    Skin Temperature (1): RTD PT100

    Tank Oil Level: Analogue Output

    Gas in Oil Monitoring: GAS -Gu ard 8 , Kelman

    Fan Motor Current (Bank A): Transducer

    Oil Pump Motor Current (Bank A): Transducer

    Fan Motor Current (Bank B): Transducer

    Oil Pump Motor Current (Bank B): Transducer

    Bushing Monitor: Doble, HSP

    Skin Temperature (2): RTD PT100

    Standard Data Analysis ModelsStatistical Significance Analysis ModuleLimit Adaption (Learning System)Oil Level ModelCooling System Effectiveness ModelThermal Model 2

    Advanced Winding Hot Spot Thermal ModelLoad Factor ModelThermal Limit Prediction ModelLoad-ability Recommendation ModelOil Vapour Pressure ModelRelative Aging Factor

    DGA Model (8 Gas)Oil Moisture Content ModelLoad Shedding Recommendation ModelBushing Monitoring Model

    SISTEMA PREMIUM

  • Page 28 2009-05Copyright Siemens Austral Andina 2009. All rights reserved.

    ED SE PTICabrera L.

    SENSORES Y MODELOS

    Desviacin relativa de la capacitancia de los bushings

    Evaluacin de la integridad del aislamiento en los bushings, basado en aprendizaje estadstico on-line.

  • Page 29 2009-05Copyright Siemens Austral Andina 2009. All rights reserved.

    ED SE PTICabrera L.

    Modelos de Ingeniera

    Humedad en el aislamiento

    Evaluacin de la humedad del aceite aislante y clculo estimado de la humedad en el papel, incluyendo anlisis de tendencia.

    Gua de Cargabilidad

    Con base en un mtodo propiedad de Siemens, el sistema calcula el hot spot que sera alcanzado a partir de valores suministrados por el usuario y tambin de las condiciones actuales de operacin, para la administracin de la carga del transformador.

  • Page 30 2009-05Copyright Siemens Austral Andina 2009. All rights reserved.

    ED SE PTICabrera L.

    Modelos de Ingeniera

    TrmicoClculo del hot spot del transformador por los mtodos normalizados IEEE/ANSI, IEC y mtodo desarrollado por Siemens.

    Prdida de vida y envejecimiento relativosClculo de prdida de vida relativa del transformador y tasa de envejecimiento relativo por los mtodos IEEE/ANSI, IEC.

    Sistema de refrigeracinVerifica el funcionamiento adecuado del sistema de refrigeracin a travs del monitoreo de la corriente de carga de los ventiladores y del flujo de aceite o agua (dependiendo del sistema de refrigeracin).

  • Page 31 2009-05Copyright Siemens Austral Andina 2009. All rights reserved.

    ED SE PTICabrera L.

    Modelos de Ingeniera

    Volumen de aceite en el conservador

    Indica un defecto incipiente, antes de llegar al nivel mnimo admisible, comparando el volumen estimado de aceite aislante en el conservador con el volumen calculado en la indicacin del sensor de nivel.

    Control de refrigeracinCon la indicacin de la temperatura deseada para operacin del transformador, este modelo efecta el control del sistema de refrigeracin a travs del clculo del hot spot futuro en funcin del cargamento actual. Esta operacin tambin considera el nmero de horas de uso de ventiladores y bombas, equilibrando el desgaste de cada grupo (rotacin). Adicionalmente, efecta el ejercicio peridico de los grupos de refrigeracin.

  • Page 32 2009-05Copyright Siemens Austral Andina 2009. All rights reserved.

    ED SE PTICabrera L.

    Modelos de Ingeniera

    Cambiador de tomas bajo carga (OLTC)Indicacin de posicin del OLTC y clculo de desgaste de contactos.

    Gases combinados disueltos en aceiteEvaluacin de tasas, tendencias y valores limites de generacin de gases en aceite, basado en aprendizaje estadstico on-line.

    Cromatografa on-line para ocho (8) gasesEvaluacin y indicacin de fallas incipientes a travs de mtodos normalizados incluyendo el triangulo de Duval. Realiza anlisis de tasas, tendencias y valores limites, basado en aprendizaje estadstico on-line. Incluye evaluacin de relacin CO2/CO, para mejor evaluacin de un defecto eventual.

  • Page 33 2009-05Copyright Siemens Austral Andina 2009. All rights reserved.

    ED SE PTICabrera L.

    TABLERO LOCAL

    Recibe la informacin adquirida por los sensores situados en los transformadores. Cada tablero es proyectado y construido para soportar las condiciones de operacin junto al transformador, sin interferencias en el funcionamiento de los componentes electrnicos.

  • Page 34 2009-05Copyright Siemens Austral Andina 2009. All rights reserved.

    ED SE PTICabrera L.

    Unidad de adquisicinRemota ET200s Fuente Universal

    24 Vcc

    Monitoreode bushing

    Transductores de corriente

    Termostato e higrostato

    OLM - conversorelctrico / ptico

    Proteccin contra sobretensiones

    Transductores de posicin OLTC

    Transductor deFlujo Aire / Aceite

    PANEL LOCAL EN EL TRANSFORMADOR

  • Page 35 2009-05Copyright Siemens Austral Andina 2009. All rights reserved.

    ED SE PTICabrera L.

    PANEL REMOTO EN LA SE

    Evaluacin y indicacin de fallas incipientes a travs de mtodos normalizados incluyendo el triangulo de Duval. Realiza anlisis de tasas, tendencias y valores limites, basado en aprendizaje estadstico on-line.

    Cromatografa on-line para tres

    Verif ica el funcionamiento adecuado del sistema de refrigeracin a travs del monitoreo de la corriente de carga de los ventiladores y del f lujo de aceite o agua (dependiendo del sistema de refrigeracin).

    Sistema de refrigeracin.

    Clculo de prdida de vida relativa del transformador y tasa de envejecimiento relativo por los mtodos IEEE/ANSI, IEC.

    Prdida de vida y envejecimiento

    relativos.

    Clculo del hot spot del transformador por los mtodos normalizados IEEE/ANSI, IEC y mtodo desarrollado por Siemens.

    Trmico.

    Con base en un mtodo desarrollado por Siemens, el sistema calcula el Hot spot que sera cargado por valores f inales y tambin de las condiciones actuales de operacin, ayudando en la administracin de la cargabilidad del equipo.

    Gua de Cargabilidad.

    Evaluacin de la humedad del aceite aislante y clculo estimado de la humedad en el papel, incluyendo anlisis de tendencia.

    Humedad en el aislamiento.

    Evaluacin de la integr idad del aislamiento en los bushing, basado en aprendizaje estadstico on-line.Desvo relativo de

    las capacitancias de los bushing.

    Funciones PrincipalesModelo

  • Page 36 2009-05Copyright Siemens Austral Andina 2009. All rights reserved.

    ED SE PTICabrera L.

    SMART MONITOR

    Este monitor mide y almacena los parmetrosindicativos del estado operativo del transformador, procesando estos datosemitiendo diagnsticos accesibles a travs de interfase local tipo touch screen de 12 pulgadas, permitiendo acceso fcil a los datos y diagnsticos del transformador en campo, o a travs de su servidor web nativo.

  • Page 37 2009-05Copyright Siemens Austral Andina 2009. All rights reserved.

    ED SE PTICabrera L.

    ARQUITECTURA EN UNA SUBESTACION

    Panel Local

    Servidor Ingeniera

    Servidor WebPLC

    Anillo fibra ptica

    Panel Central

    Panel Local

    Panel Local

    LAN WAN

  • Page 38 2009-05Copyright Siemens Austral Andina 2009. All rights reserved.

    ED SE PTICabrera L.Localidad Central, Centro de Control, etc.

    Subestacin 1 Subestacin 2 . Subestacin n

    WAN

    ARQUITECTURA VARIAS SUBESTACIONES

  • Page 39 2009-05Copyright Siemens Austral Andina 2009. All rights reserved.

    ED SE PTICabrera L.

    Efficient Data Handling for Base DataCaptures 3 Values Vs 24

    T

    e

    m

    p

    Unicamente captura los datos significativos

    T

    V1

    V3

    V2

    Estrategia de almacenamiento de datos

  • Page 40 2009-05Copyright Siemens Austral Andina 2009. All rights reserved.

    ED SE PTICabrera L.

    +1, +2-1, -2

    Se crea una definicinestadstica en un tiempode aprendizaje. Lo que significa , Estado del devanado con un intervalo de certesa del 95%.

    +1, +2-1, -2

    Los cambios estadsticos son monitoreados con el fin de evitarerrores potenciales, esto se hace por medio del anlisis de toda la gama de las desviaciones estandard.

    Sistema de aprendizaje basado en los datos de operacin con el fin de evitar, disparos o alarmas. Adems puede detectarestadsticamente posibles fallasantes de alcanzar los limitespermitidos.

    Definicin estadstica: Usada para deducir los modelosque se deben aplicar

  • Page 41 2009-05Copyright Siemens Austral Andina 2009. All rights reserved.

    ED SE PTICabrera L.

    A

    T

    Estos parametros pueden ser establecidos usando:1. Directrices aceptadas por la industria tales como los

    estandares IEEE/ ANSI.2. Clculos hechos en base a la condicin off-line ,histricos

    y anlisis pasados de DGA.3. NIveles definidos de uso.

    Absolute & Rate of Change Metrics: Usada para deducirlos modelos que se deben aplicar

  • Page 42 2009-05Copyright Siemens Austral Andina 2009. All rights reserved.

    ED SE PTICabrera L.

    Arquitectura Estndar

  • Page 43 2009-05Copyright Siemens Austral Andina 2009. All rights reserved.

    ED SE PTICabrera L.

    TMDS Message

    Siemens Transformer Monitoring and Diagnostics System(TMDS) at S Substation has detected an event which demands action. Please check the web address:www.siemens-tmdsl-subs.com

    [email protected]

    Mensaje enviado al usuario

  • Page 44 2009-05Copyright Siemens Austral Andina 2009. All rights reserved.

    ED SE PTICabrera L.

    Diagnstico

  • Page 45 2009-05Copyright Siemens Austral Andina 2009. All rights reserved.

    ED SE PTICabrera L.

    DiansticoTringulo de Duval (IEC 60599-1999 Annex B.3)

  • Page 46 2009-05Copyright Siemens Austral Andina 2009. All rights reserved.

    ED SE PTICabrera L.

    Modelo de Ingeniera Modelo trmico 1

    LV Winding Hot Spot Calculation

  • Page 47 2009-05Copyright Siemens Austral Andina 2009. All rights reserved.

    ED SE PTICabrera L.

    LV Winding Hot Spot Calculation

    New Hot Spot Temp RiseCalculation @ Time = T2

    Old Temp Rise Calculation @ Time = T1

    Incremental Calculation Based on Load @ Time = T2-T1; H, m based on design parameters

    Thermal Time Constant of HV Winding based on design parameters

    Modelo de Ingeniera Modelo trmico 1

    HV Clculo de puntos calientes del devanado (Temp Rise)

  • Page 48 2009-05Copyright Siemens Austral Andina 2009. All rights reserved.

    ED SE PTICabrera L.

    HV Clculo de puntos calientes del devanado (Temp Rise)

    New Hot Spot HV Winding Calculation @ Time = T2 is calculated addingTop Oil Temperature

    El clculo del punto caliente es un proceso contnuo, actualizado interactivamente, disponible para el uso de otros modelos de correlacin.

    El anlisis proporciona informacin contextual asociada a una alarma.

    Modelo de Ingeniera Modelo trmico 1

  • Page 49 2009-05Copyright Siemens Austral Andina 2009. All rights reserved.

    ED SE PTICabrera L.

    HV Temperaturade punto caliente

    LV Temperaturade punto caliente

    Modelo de Ingeniera Modelo trmico 1

    HV Clculo de puntos calientes del devanado (Temp Rise)

    LV Clculo de puntos calientes del devanado (Temp Rise)

  • Page 50 2009-05Copyright Siemens Austral Andina 2009. All rights reserved.

    ED SE PTICabrera L.

    Modelo de Ingeniera Modelo Trmico 1 Usa como soporteAlarma Predictiva y Cargabilidad

  • Page 51 2009-05Copyright Siemens Austral Andina 2009. All rights reserved.

    ED SE PTICabrera L.

    BackgroundModels

    Modelo de Ingeniera Modelo Trmico 1 Usa como soporteAlarma Predictiva y Cargabilidad

  • Page 52 2009-05Copyright Siemens Austral Andina 2009. All rights reserved.

    ED SE PTICabrera L.

    Estrategia usadacomo soporte de lasAlarmas de Prediccin; Direcciones;Si sigo en mi cargaactual, corro el riesgode exceder el lmitede temperaturaCuanto es el margende que tengo en mi punto de cargaactual

    Modelo de Ingeniera Modelo Trmico 1 Usa como soporteAlarma Predictiva y Cargabilidad

  • Page 53 2009-05Copyright Siemens Austral Andina 2009. All rights reserved.

    ED SE PTICabrera L.

    Estrategia de soporteusada para el movimiento del transformadoe en el nuevo punto de carga; Direcciones;

    Podemosincrementar esacarga del transformador por X% sin exceder los lmitesde temperatura.

    Modelo de Ingeniera Modelo Trmico 1 Usa como soporteAlarma Predictiva y Cargabilidad

  • Page 54 2009-05Copyright Siemens Austral Andina 2009. All rights reserved.

    ED SE PTICabrera L.

    LL to 90,95%LL to 90,95%LL to 90,95%LL to 90,95%LL to 90,95%LL to 90,95%LL to 90,95%

    LL 90,95%

    Modelos de Ingeniera Modelo DGA & Anlisis usandorecomendaciones de soporte de alarmas y cargas

    Inicio

    Toma de muestrade Gas

    Analisiscomparativo

    del gas de referencia

    ANSI Lmite del Cliente Statistical

    GasH2CH4COC2H2C2H4C2H6TDCG

    100120350355065720

    G1G2G3G4G5G6B1,B2, B3

    Se limitar elalcance en

    15 das

    Se limitar elalcance en

    15 das

    TieneTDCG escedela proporcin

    Alcana el lmiteespecfico de Gas

    Alcanza la rata

    mnima de GasHas

    Requiere DGA completo (Hydran)Presenta reporte individual de Monitoreo de GasPresenta anlisis de gases Duval/Rogers Ratio

    Da alarma Desencadena anlisis

    Duval/RR

    No

    Si

    No NoNo

    No

    Si Si Si Si

  • Page 55 2009-05Copyright Siemens Austral Andina 2009. All rights reserved.

    ED SE PTICabrera L.

    Diagrama de flujo

  • Page 56 2009-05Copyright Siemens Austral Andina 2009. All rights reserved.

    ED SE PTICabrera L.

    Condicin de monitoreo Informacin de operacin

  • Page 57 2009-05Copyright Siemens Austral Andina 2009. All rights reserved.

    ED SE PTICabrera L.

    Condicin de monitoreo Informacin de operacinTreeing (Anlisis de Tendencias

  • Page 58 2009-05Copyright Siemens Austral Andina 2009. All rights reserved.

    ED SE PTICabrera L.

    Gracias!