modular ahu manual

Upload: wolfzemun

Post on 14-Apr-2018

270 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/30/2019 Modular AHU Manual

    1/17

  • 7/30/2019 Modular AHU Manual

    2/17

    Instruction The Installation Part of this manual is intended for professional installers.

    Read the Operation Part carefully before you install the unit to prevent

    unit damage or accidents caused by your mishandling.

    The contents of this manual may change with the update of certain models,

    and no further notice will be given for such change.

    Product standard: GB/T 14294-93

  • 7/30/2019 Modular AHU Manual

    3/17

    Contents1. General ....................................................................................................... 1

    1.1 Introduction ......................................................................................... 1

    1.2 Nomenclature and Structure ............................................................... 1

    1.3 Unit Model List .................................................................................... 1

    2. Installation of Units ...................................................................................... 32.1 Preparation Before Installation ............................................................ 3

    2.2 Check-and-acceptRiggingPortage ............................................... 3

    2.3 Installation ........................................................................................... 4

    2.4 Unit Connection................................................................................... 5

    2.5 Other Instructions ................................................................................ 6

    3. Operation and Commisioning ...................................................................... 7

    3.1 Wiring Connection Check .................................................................... 7

    3.2 Operation ............................................................................................ 8

    4. Unit Maintenance ........................................................................................ 9

    4.1 Regular Maintenance .......................................................................... 9

    4.2 Precautions ....................................................................................... 10

    5. Troubleshooting .......................................................................................... 11

  • 7/30/2019 Modular AHU Manual

    4/17

    1. General

    1.1 Introduction

    The MKZII modular air handling unit is an air handling device which cools, heats,

    humidifies, purifies and conveys air. The unit does not carry cool or heat source, and the

    refrigerant is water or vapor. The unit provides the functional sections such as fresh return

    air hybrid section, cooling coil section, heating section, low/mid/high-efficiency filter

    section, electric heating section, humidifier section, resistance muffler section, heat

    recovery, secondary air return section, fan section, and flow equalization section. The

    user can select any combination of the functional sections to meet the requirements. The

    air handling unit is widely applied to the central air conditioning systems in medium and

    big buildings for electronics, textile and chemical fibers, precision instruments, metallurgy,chemical industry, pharmaceutics, food, tobacco, shopping malls and stadium.

    1.2 Nomenclature and Structure

    MKZ II 2124 A Z 1

    MKZ :Midea Modu lar AHU

    II :Designing Serial Code;

    2124 :The width and length module is 24 21 respectively.Each module is

    equal to 100mm;

    A :No. of Coi l Rows,A = 4B = 6C = Other;

    Z :Direction of Pipe Connection,Z Left-handedY Right-handed ,See

    Note 1;

    1 :Direction of Air Discharge,1 Vertical Discharge 2 Horizotal

    Discharge;

    Note 1:It is LEFT-HANDED pipe connection if the header pipe is on the

    left-hand side when viewing from the air inlet.

    1.3 Unit Model List

    Note:The Detail Specification Please Kindly Check In The Catalogue.

    Unit Model MKZ 0710 MKZ 0712 MKZ 08 12 MKZ 0814 MKZ 0915 MKZ 1118

    Air Volume

    m3/h

    5000 6000 7000 8000 10000 15000

    1

  • 7/30/2019 Modular AHU Manual

    5/17

    Modular Air Handling Unit Installation & Operation & Maintenance Manual

    2

    Unit Model MKZ 1418 MKZ 1620 MKZ 1623 MKZ 1826 MKZ 2127 MKZ 2131

    Air Volume

    m3/h

    20000 25000 30000 40000 50000 60000

    Unit Model MKZ 2631 MKZ 2635 MKZ 3136

    Air Volume

    m3/h

    70000 80000 100000

  • 7/30/2019 Modular AHU Manual

    6/17

    Modular Air Handling Unit Installation & Operation & Maintenance Manual

    3

    2. Installation of Units

    The unit must be installed and implemented under GB50243-2002 Specifications for

    Quality Acceptance of Ventilation and Air Conditioning Projects.

    2.1 Preparation Before Installation(1) Get familiar with the relevant drawings and documents, and check whether the

    installation site is readily available.

    (2) Check whether the devices (or parts) and relevant accessories are complete.

    Name Quantity Remarks

    Installation and operationmanual of modular air

    conditioning unit1 (Must be delivered to the user)

    Customer service guide 1 (Must be delivered to the user)

    (3) Prepare the conveyance devices (or components) and installation tools.

    (4) Coordinate the installation progress of all parties to the project.

    2.2 Check-and-acceptRiggingPortage

    (1) If the integrated equipment is delivered to the destination, open the outer packageafter the unit, and Check the appearance quality of the product in the box and the

    completeness of accessories. If any damage occurs, contact the logistics company

    of Midea or claim against the carrier.

    (2) If disassembled components are delivered to the destination, decide whether to

    unpack first or convey the package to the site first.

    (3) Convey the equipment according to the following figure in order not to damage the

    unit in the conveyance and installation process.

  • 7/30/2019 Modular AHU Manual

    7/17

    Modular Air Handling Unit Installation & Operation & Maintenance Manual

    4

    (4) If rollers are used for conveying the unit, use at least three materials longer than the

    width of the unit.

    (5) Handle with care and be cautious during the conveyance.

    2.3 Installation

    (1) The schematic diagram of installing the unit serves as a reference for the user.

    (2) Enough maintenance space shall be reserved around the unit to facilitate daily

    maintenance and upkeep of the unit. Note that at least 1m width shall be reserved in

    the direction of setting up the overhauling door. The air system installer shall provide

    the location dimensions of the direction for connecting the air duct.

    (3) To install the unit, put the sections onto the foundation sequentially against the

    drawing. For application sensitive to vibration, a damping cushion made of natural

    rubber 10mm thick shall be applied between the unit and the foundation.

    (4) If the unit is a small unit of the Company and needs to be installed in a suspended

    way, the user shall allow for a maintenance space and a suspending weight.

    (5) When connecting all sections of the unit, rubber plastic shall be used for sealing

    between the sections.

    (6) In the installation process, the installers shall pay attention to the weight-bearingcapacity of the unit and the panel.

    (7) The procedure of installing the dry vapor humidifier is as follows: (The vapour spray

    direction of the humidifier is opposite to air flow, and a drainage controller shall be set

    at the vapour outlet).

    (8) For any questions about installation, consult our technical department.

  • 7/30/2019 Modular AHU Manual

    8/17

    Modular Air Handling Unit Installation & Operation & Maintenance Manual

    5

    2.4 Unit Connection

    (1) According to the air volume and air pressure of this unit, select the proper ducts. The

    ducts shall undergo heat insulation treatment. A straight pipe as long as at least

    double length of the air outlet shall be reserved before the outtake duct is connected

    from the air outlet to the elbow pipe.

    (2) An air volume regulating valve shall be set at the intake duct and outtake duct for

    ease of regulating the air volume of the system. flexible connection shall be set

    between the unit and the outside.

    (3) The top operating pressure of the cooling coil and the heating water unit shall not

    exceed 1.6 MPa. Screws or flanges shall be applied for connection between the

    lead-in water pipe and the lead-out water pipe. Thread seal tape shall be applied

    around the pipe screws. The water pipes shall be led in from the top and led out from

    the bottom, as shown in the following figure.

    (4) When the maximum operating pressure in vapor heating is not greater than 1.4 MPa,

    screws or flanges shall be applied for connection between lead-out water pipes. The

    vapor is led in from the top and led out from the bottom. A drainage controller shall be

    set at the vapor outlet. See the following figure.

    (5) Regulating valves shall be installed for both lead-in water pipes and lead-out water

    pipes of the unit (except the condensate pipe) for purpose of air volume regulation

    and maintenance. The lead-in and lead-out water pipes of the unit shall insulate heat.

    Necessary water seals shall be set on the condensate pipe. See the pipe diagram.

    (6) Set a manometer and a thermometer on the lead-in water pipe and lead-out waterpipe of the unit for monitoring whether the water system is normal.

    (7) All wire installation must adhere to the local power regulations. Before distributing the

    wires, check whether the power supply and wires meet requirements against the

    parameters on the nameplate of the unit.

    (8) The power supply lead-in is located at the overhauling door side of the fan section

    (unless otherwise required by the user). Connect the power wire to the motor junction

    box of the unit.

    (9) Configure the electric devices and wires according to the electric heating wire

    diagram and the schematic diagram of the unit, and connect the wires correctly. Themetal enclosure of the electric heating coil pipe shall be well grounded. The

    temperature relay signals in the electric heating coil pipe must be connected to the

    electric heating controller center. This ensures that the electric heating power supply

    will be cut off in case too high temperature of air in the unit. The electric heating

    controller shall perform interlocked control for the fan and the electric heater, and

    ensure that the electric heating power supply is disconnected when the fan stops.

  • 7/30/2019 Modular AHU Manual

    9/17

    Modular Air Handling Unit Installation & Operation & Maintenance Manual

    6

    2.5 Other InstructionsAdopt flexible connection when connecting the external intake duct and outtake duct.

    This prevents the vibration and duct weight from being borne by the unit.

    In case of connecting external lead-in and lead-out water pipes, use flexible adapters.

    Apply force equally when connecting the pipes. For piping of the vapor coil pipe, connect

    the pipes according to the heating specifications in order to prevent the coil pipe from

    being damaged by the heat stress. The intake and outtake pipes of various coil pipes

    shall be connected as opposite to the air flow direction (the air flow direction shall be

    inverse to flow direction of the refrigerant).

    If a drain pipe is connected externally, connect the U-shape drain elbow first to

    prevent difficulty of draining the condensate water caused by negative pressure in the unit.

    The height difference of the water seal of the drain elbow may be twice as much as thenegative pressure in the unit. For the configuration of the foundation and the water seal,

    see the following figure.

    Both cooling and heating water shall be clean demineralized water. Before

    supplying water, clean the water pipelines of the system and use the exhaust valve to

    expel the air in the coil pipe completely.If the unit needs to stop operation in winter, be sure to keep continuous flow of the

    water in the coil pipe, fill anti-freeze liquid, and close the fresh air valve to prevent freezing

    of the coil pipe. If the unit needs to stop operation in winter for a long period, empty the

    water in the coil pipe.

  • 7/30/2019 Modular AHU Manual

    10/17

    Modular Air Handling Unit Installation & Operation & Maintenance Manual

    7

    3.Operation and Commisioning

    3.1 Wiring Connection Check(1) The system should be correct and smooth without leak.

    (2) The power wires shall be correctly connected, safe and tight. The motor of the unit

    shall be connected to the power supply with phase loss protection and overload

    protection. The startup of motors of over 11 kw shall be implemented through

    potential fall. The motors of the unit shall under a one-to-one protection mechanism.

    It is not allowed to connect two or more motors in parallel with the same protection

    switch. Before connecting the power supply, check whether the voltage meets the

    requirements, whether phase loss occurs, and whether the three phases are

    balanced. After connecting the power supply, start the motor first to check whetherthe fan rotation direction is correct. If not correct, adjust the phase sequence.

    W1V1U1

    W1V1

    U1

    ~M1

    FR1

    KM1

    QF

    L1 L2 L3 N

    SB1SB2

    KM1

    FR1KM1

  • 7/30/2019 Modular AHU Manual

    11/17

    Modular Air Handling Unit Installation & Operation & Maintenance Manual

    8

    (3) The air system is safe, reliable and correct. It is clean inside the pipe.

    (4) No foreign matters exist in the fan, the fan VANE does not scratch the enclosure, and

    the fan rotation direction is correct.

    (5) If the integrated equipment is delivered out of the factory, remove the fixing block

    beside the vibration absorber.

    3.2 Operation

    (1) This unit is designed according to the pressure and air volume required by the user.

    Adjust the location of the damper as required, AND prevent a high pressure

    difference between the inside and the outside of the unit because this will lead to

    deformation of the unit.

    (2) When supplying water to the unit, open the gas valve to expel air.

    (3) In winter (especially in areas characterized by cold weather), the outdoor

    temperature is low. Evacuate the water in the coil pipe or take proper protection

    measures to prevent frost crack.

    (4) For the unit with a humidifier, turn on the fan before giving out water (vapor); to shut

    down the unit, stop the water (vapor) before turning off the fan.

    (5) For the unit with an electric heater, the heater should be interlocked with the fan.

    (6) To start the unit, turn on the fan before supplying water (vapor) to the coil pipe. To

    shut down the unit, stop the water (vapor) before turning off the fan.

    L1 L2 L3

    QF1

    QF2

    N

    M

    KM1

    FR

    KM2

    U1V1

    W1

    V2 W2U2

    KM3

    KM3

    KT

    KM3 KM2KT

    KM1

    FR

    KM1

    SB1

    SB2 KM1

    KM2

    KM2KT

  • 7/30/2019 Modular AHU Manual

    12/17

    Modular Air Handling Unit Installation & Operation & Maintenance Manual

    9

    4.Unit Maintenance

    4.1 Regular Maintenance(1) During operation of the unit, observe the operation status of the fan regularly, and

    check the belt tightness and the bearing conditions periodically.(2) The Rotation Power Momentum (RPM) of the fan depends on the required air volume

    and the resistance caused by the accessories, the supply air and return air pipelinesystem of the unit. Such data can be used to determine the RPM of the fan accordingto the characteristic curve of the fan. The sheave and the belt specifications can bedetermined according to the required RPM and motor power. After the motor isstarted, adjust the resistance of the supply air and return air pipeline system toensure that the air is supplied evenly in the air conditioner room.

    (3) By adjusting the location of the motor sheave and the fan sheave, let the belt beproperly tense (Figure 3). Press the belt with a finger, and the deformation size shall

    be about 20 mm). Stop the fan during full-speed running. After stop of running, thestop time interval of the fan should be over 7 seconds.

    (4) After the unit has run for a week, adjust the belt to the proper tenseness again.Afterward, perform a routine inspection every another month or every another two

    months, and ensure that the results fall within the value range shown in the figure.Otherwise, adjust or replace the belt.

    Note: Too loose and too tense belts will damage the system and increase noise.

    (5) Rinse the filter (a) before the unit is started for the first time; (b) after the unit has runfor 3 months (in an average environment); or (c) an alarm is raised by the monitoringsystem. The procedure of rinsing the filter is: If the filter is cleanable, put the filter intoa neutral solution and scrub it gently, and reinstall it after sunning it dry. If the filter isnot cleanable, replace it. The non-woven fabric filter cannot be cleaned for more thanthree times, and the metal filter can be cleaned repeatedly.

    (6) For the High Efficiency Particulate Air Filter (HEPA), install the filter in a clean indoorenvironment which must be airtight.

    (7) Clean the surface of the coil pipe periodically. After the unit has run for 2-3 years,

    Fig 3: Adjusting the tighteness of the V belt

  • 7/30/2019 Modular AHU Manual

    13/17

    Modular Air Handling Unit Installation & Operation & Maintenance Manual

    10

    cleanse the pipe chemically to remove the incrustation scale in the pipe.(8) Check the electric devices periodically.

    4.2 Precautions

    (1) The supply air temperature of the unit cannot be greater than 80C.(2) The supplied water shall be dmineralized water. Generally, the lead-in cool water

    temperature is about 7C and the lead-in hot water temperature is about 60C.(3) The unit shall work under rated air volume or rated current.(4) In case of low temperature, pay special attention to frost prevention.

  • 7/30/2019 Modular AHU Manual

    14/17

    Modular Air Handling Unit Installation & Operation & Maintenance Manual

    11

    5. TroubleshootingCommon

    faultLocation Possible cause Solution

    Abnormalsound

    1. Impeller

    The impeller deviates from the

    spindle.

    The bearings become loose due to

    too big spacing between them

    The impeller becomes loose.

    The spindle and the bearing sleeve

    become loose.

    The impeller is damaged.

    The fan fastener becomes loose.

    Foreign matter exists in the fan.

    Contact the seller.

    Contact the seller.

    Contact the seller.

    Contact the seller.

    Contact the seller.

    Tighten the screws.

    Eliminate foreign

    matters.

    2. Conveyance part

    The sheave is fastened on the

    spindle.

    The V belt becomes loose. Adjust it48 hours after the first operation.

    The V belt is too tight.

    The model of the V belt in use is

    improper.

    Multiple V belts in a unit have different

    lengths.

    The V sheave of the fan is not aligned

    with the V sheave of the motor

    properly.

    The V belt is damaged.

    The motor and the screws for

    fastening the motor seat becomeloose.

    Tighten the sheave.

    Adjust the V belt

    Adjust the V beltReplace the V belt.

    Replace the V belt and

    make the length

    consistent.

    Align the V sheave.

    Replace the V belt.

    Tighten the screws.

    3. Bearing

    Lube has run out.

    The bearing sleeve becomes loose.

    The unit is not installed in a level and

    straight way.

    Foreign matter exists in the bearing.

    The bearing is damaged.

    The bearing becomes rusted.

    Apply lube

    Tighten the bearing

    sleeve.

    Perform a reinstallation.

    Eliminate foreign

    matters.

    Replace the bearing.

    Remove rust or replace

    the bearing.

    4. Fan scroll case

    Foreign matter exists in the scroll

    case.

    The scroll case becomes loose.

    The air inlet scroll case is damaged.

    Eliminate foreign

    matters.

    Contact the seller.

    Contact the seller.

    5. Electric partThe lead-in wire becomes loose.

    The motor raises a resonant sound.

    Phase is lost.

    Tighten the lead-in wires.

    Contact the seller.

    Supply 3-phase power

    6. Spindle

    It becomes bent and deformed.

    The counterbalance becomes loose.

    The spindle becomes loose.

    Replace the spindle

    Tighten the

    counterbalance.

    Tighten the spindle.

    7. Too high air speed

    The duct is too small.

    The practical static pressure does not

    reach the designed static pressure

    value.

    Redesign the duct.

    Change the V sheaves,

    and reduce the fan

    rotation speed.

  • 7/30/2019 Modular AHU Manual

    15/17

    Modular Air Handling Unit Installation & Operation & Maintenance Manual

    12

    8. Periodical vibration

    The duct is too small.

    The system is not stable.

    The duct vibrates with the pulsation of

    the fan.

    Redesign the duct.

    Adjust the system.

    Adjust the fan rotation

    speed.9. Noise caused by

    high-speed air running

    through gaps and holesThe duct leaks air Apply gasket cement.

    10. Clucks or squeaks

    caused by obstructed

    high-speed air

    The duct has too sharp bends.

    The duct flares sharply.

    The duct tapers sharply.

    The air speed in the duct is too high.

    The damping adapter is too tight.

    Redesign the duct.

    Redesign the duct.

    Redesign the duct.

    Redesign the duct.

    Adjust the damping

    adapter.

    The fan runs

    normally but

    the supplied

    air volume is

    deficient

    1. Fan

    The impeller is installed incorrectly.

    The fan runs inversely.Contact the seller.

    Adjust the phase

    sequence of the power

    supply.

    2. Duct system

    The actual duct system resistanceexceeds the designed resistance.

    The duct is not hermetic.

    The fire valve is closed.

    Redesign the system.Apply gasket cement.

    Open the fire valve.

    3. FilterThe assembly is too dirty or even

    blocked.Cleanse or replace the

    filter.

    4. Coil pipeThe assembly is too dirty or even

    blocked.Rinse the coil pipe.

    5. Short air

    The outlet area is not sharply

    separated from the inlet of the fan,

    and the air runs through the partition

    plate which provides poor partition to

    the inlet area.

    Apply a partition plate.

    6.Blocked fan inlet

    The elbow at the air return place is

    too close to the unit.

    The fan inlet is too close to the fan

    panel.

    Obstacles exist at the fan outlet.

    Redesign the location of

    the elbow.

    Move the fan.

    Remove the obstacles.

    7. No straight pipe at the

    fan outlet

    A segment of straight pipe is set at

    the fan outlet at the time of fan test.

    If the straight pipe lacks in practical

    use, the fan performance will be

    deteriorated, and the fan rotation

    speed may increase to overcome the

    resistance caused by it.

    Install a straight pipe.

    8. Obstacles in the air

    systemObstacles exist at the fan outlet.

    A bend exists at the fan outlet.Remove the obstacles.

    Redesign the duct.

  • 7/30/2019 Modular AHU Manual

    16/17

    Modular Air Handling Unit Installation & Operation & Maintenance Manual

    13

    The fan runs

    normally but

    the supplied

    air volume is

    excessive

    1. System

    The fan size is improper.

    The overhauling door is open.

    The system is out of balance, and the

    actual resistance is less than the

    designed resistance.

    No damper or damper vane is

    installed.

    The filter is detached.

    Redesign the duct.

    Close the overhauling

    door

    Redesign the system.

    Install damper or damper

    vane.

    Reinstall the filter.

    2. Duct The return duct leaks air. Apply gasket cement.The air in

    the air

    conditioner

    room is not

    fresh.

    1. FilterThe filter is too dirty. Rinse or replace the

    filter.

    2. Fresh airThe fresh air volume is deficient. Increase fresh air.

  • 7/30/2019 Modular AHU Manual

    17/17