Modeling of three-phase autotransformer for short-circuit studies Dalibor Filipovic ´ -Grc ˇic ´ a , Boz ˇidar Filipovic ´ -Grc ˇic ´ b,, Kosjenka Capuder c a Konc ˇar Electrical Engineering Institute, Fallerovo šetalište 22, 10000 Zagreb, Croatia b University of Zagreb, Faculty of Electrical Engineering and Computing, Unska 3, 10000 Zagreb, Croatia c Konc ˇar Power Transformers, Josipa Mokrovic ´a 6, 10090 Zagreb, Croatia article info Article history: Received 11 August 2013 Received in revised form 28 October 2013 Accepted 6 November 2013 Keywords: Autotransformer Inductance matrix model Short-circuit Symmetrical components Tertiary winding abstract In this paper a three-phase autotransformer is represented by inductance matrix for short-circuit studies. The inductance matrix consists of winding self-inductances and corresponding mutual inductances between windings. For single phase-to-ground fault the inductance matrix model results are compared to symmetrical components results, commonly used to analyze unsymmetrical faults in three-phase power systems. The influence of a delta connected tertiary winding on un-faulted phase voltages and asymmetrical fault current distribution is analyzed. Ó 2013 Elsevier Ltd. All rights reserved. 1. Introduction The autotransformer is a power transformer in which one wind- ing, known as the common or parallel winding, is shared between the high voltage (HV) and the low voltage (LV) circuit. As a part of the power transmission system, in service the autotransformer is exposed to various voltage and current stresses. Short-circuit currents cause thermal and mechanical stresses of transformer windings, while the ground fault occurrence in network with an isolated neutral point may result in un-faulted phase voltages sig- nificantly higher than operating voltages [1]. As a consequence, an internal winding fault can occur and eventually lead to insulation failure [2,3]. The autotransformer zero sequence impedance highly depends on delta winding presence. For this reason, delta winding is com- monly used to provide a low impedance path for third harmonic currents and to reduce current and voltage imbalances caused by asymmetrical loading, but also for other purposes such as to con- nect compensation. Delta connected tertiary winding is usually sized for at least one third of the rated power and having the low- est rated voltage. The tertiary must withstand the effects of a short-circuit fault across its external terminals, as well as those due to earth faults on the main windings. An embedded delta ter- tiary winding, sometimes referred to as a stabilization winding, improves the availability of the transformer by eliminating the occurrence of tertiary lead faults since only two connections from the phases, forming one corner of the delta that is grounded, are brought out of the transformer. In Ref. [4] three winding transformer model for short-circuit studies is presented. The model takes into account off-nominal tap positions and the phase shifts among the windings. A systematic approach to solving power system faults using the three terminal Thevenin’s equivalent circuit is presented in [5] and demonstrated in case of symmetrical and unsymmetrical faults. Papers [6,7] describe the autotransformer models for load-flow, short-circuit [8] and transient recovery voltage analysis [9]. High- frequency autotransformer model derived from the results of a lightning electromagnetic pulse test is presented in [10]. Ref. [11] describes the influence of a delta connected tertiary winding on voltages and currents during fault conditions. The contribution of this paper is the development of autotrans- former inductance matrix model for short-circuit studies. Model was developed and verified in Matlab/M-file [12]. The application of this model could be useful when performing short-circuit system studies needed for autotransformer dimensioning and protection relay setting [13,14]. The influence of a delta connected tertiary winding on un-faulted phase voltages and fault currents was analyzed. 2. Three-phase autotransformer model based on inductance matrix In autotransformer the HV circuit is composed of the common winding and the series winding while the LV circuit is composed only of the common winding [15]. 0142-0615/$ - see front matter Ó 2013 Elsevier Ltd. All rights reserved. http://dx.doi.org/10.1016/j.ijepes.2013.11.005 Corresponding author. Tel.: +385 1 6129 714; fax: +385 1 6129 890. E-mail addresses: dfi[email protected] (D. Filipovic ´ -Grc ˇic ´), bozidar. [email protected] (B. Filipovic ´ -Grc ˇic ´), [email protected] (K. Capuder). Electrical Power and Energy Systems 56 (2014) 228–234 Contents lists available at ScienceDirect Electrical Power and Energy Systems journal homepage: www.elsevier.com/locate/ijepes

Upload: kosjenka

Post on 30-Dec-2016

225 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Modeling of three-phase autotransformer for short-circuit studies

Electrical Power and Energy Systems 56 (2014) 228–234

Contents lists available at ScienceDirect

Electrical Power and Energy Systems

journal homepage: www.elsevier .com/locate / i jepes

Modeling of three-phase autotransformer for short-circuit studies

0142-0615/$ - see front matter � 2013 Elsevier Ltd. All rights reserved.http://dx.doi.org/10.1016/j.ijepes.2013.11.005

⇑ Corresponding author. Tel.: +385 1 6129 714; fax: +385 1 6129 890.E-mail addresses: [email protected] (D. Filipovic-Grcic), bozidar.

[email protected] (B. Filipovic-Grcic), [email protected](K. Capuder).

Dalibor Filipovic-Grcic a, Bozidar Filipovic-Grcic b,⇑, Kosjenka Capuder c

a Koncar Electrical Engineering Institute, Fallerovo šetalište 22, 10000 Zagreb, Croatiab University of Zagreb, Faculty of Electrical Engineering and Computing, Unska 3, 10000 Zagreb, Croatiac Koncar Power Transformers, Josipa Mokrovica 6, 10090 Zagreb, Croatia

a r t i c l e i n f o a b s t r a c t

Article history:Received 11 August 2013Received in revised form 28 October 2013Accepted 6 November 2013

Keywords:AutotransformerInductance matrix modelShort-circuitSymmetrical componentsTertiary winding

In this paper a three-phase autotransformer is represented by inductance matrix for short-circuit studies.The inductance matrix consists of winding self-inductances and corresponding mutual inductancesbetween windings. For single phase-to-ground fault the inductance matrix model results are comparedto symmetrical components results, commonly used to analyze unsymmetrical faults in three-phasepower systems. The influence of a delta connected tertiary winding on un-faulted phase voltages andasymmetrical fault current distribution is analyzed.

� 2013 Elsevier Ltd. All rights reserved.

1. Introduction occurrence of tertiary lead faults since only two connections from

The autotransformer is a power transformer in which one wind-ing, known as the common or parallel winding, is shared betweenthe high voltage (HV) and the low voltage (LV) circuit. As a part ofthe power transmission system, in service the autotransformer isexposed to various voltage and current stresses. Short-circuitcurrents cause thermal and mechanical stresses of transformerwindings, while the ground fault occurrence in network with anisolated neutral point may result in un-faulted phase voltages sig-nificantly higher than operating voltages [1]. As a consequence, aninternal winding fault can occur and eventually lead to insulationfailure [2,3].

The autotransformer zero sequence impedance highly dependson delta winding presence. For this reason, delta winding is com-monly used to provide a low impedance path for third harmoniccurrents and to reduce current and voltage imbalances caused byasymmetrical loading, but also for other purposes such as to con-nect compensation. Delta connected tertiary winding is usuallysized for at least one third of the rated power and having the low-est rated voltage. The tertiary must withstand the effects of ashort-circuit fault across its external terminals, as well as thosedue to earth faults on the main windings. An embedded delta ter-tiary winding, sometimes referred to as a stabilization winding,improves the availability of the transformer by eliminating the

the phases, forming one corner of the delta that is grounded, arebrought out of the transformer.

In Ref. [4] three winding transformer model for short-circuitstudies is presented. The model takes into account off-nominaltap positions and the phase shifts among the windings.

A systematic approach to solving power system faults using thethree terminal Thevenin’s equivalent circuit is presented in [5] anddemonstrated in case of symmetrical and unsymmetrical faults.

Papers [6,7] describe the autotransformer models for load-flow,short-circuit [8] and transient recovery voltage analysis [9]. High-frequency autotransformer model derived from the results of alightning electromagnetic pulse test is presented in [10]. Ref. [11]describes the influence of a delta connected tertiary winding onvoltages and currents during fault conditions.

The contribution of this paper is the development of autotrans-former inductance matrix model for short-circuit studies. Modelwas developed and verified in Matlab/M-file [12]. The applicationof this model could be useful when performing short-circuitsystem studies needed for autotransformer dimensioning andprotection relay setting [13,14]. The influence of a delta connectedtertiary winding on un-faulted phase voltages and fault currentswas analyzed.

2. Three-phase autotransformer model based on inductancematrix

In autotransformer the HV circuit is composed of the commonwinding and the series winding while the LV circuit is composedonly of the common winding [15].

Page 2: Modeling of three-phase autotransformer for short-circuit studies

1003232 krr uU ⋅

Fig. 2. Test circuit used for determination of Mp3.

1003131 krr uU

Fig. 3. Test circuit used for determination of MS3.

D. Filipovic-Grcic et al. / Electrical Power and Energy Systems 56 (2014) 228–234 229

The proposed autotransformer model consists of winding self-inductances and corresponding mutual inductances betweenwindings. In power transformers the resistance component of theimpedance is negligible in comparison with the inductance compo-nent, thus only the inductive component is considered in thefollowing calculations. This approximation slightly overestimatesshort-circuits currents.

All model parameters can be obtained from factory measure-ments and manufacturer data. First, the total self-inductance L1

of series and parallel winding is determined from open-circuit testdata (1):

L1 ¼U2

r1

x � I0 � Sr� 100; ð1Þ

where I0 is the magnetizing current in percent of the rated current,Ur1 is the rated voltage of HV winding, Sr is the rated power and x isthe angular frequency.

Afterwards, the self-inductances LS of the series winding, LP ofthe parallel winding and L3 of the tertiary winding are determinedfrom the following expressions:

LS ¼ L1 �Ur1 � Ur2

Ur1

� �2

; ð2Þ

LP ¼ L1 �Ur2

Ur1

� �2

; ð3Þ

L3 ¼U2

r3

x � I0 � Sr1� 100 � 3; ð4Þ

where Ur2 is the rated voltage of the parallel winding and Ur3 is therated voltage of tertiary winding.

Mutual inductance MSPbetween series and parallel winding canbe determined from the test circuit shown in Fig. 1. LV winding isshort-circuited and voltage is increased on HV side until rated cur-rent Ir1 is reached.

The phase angle of the applied voltage is assumed to be 0� andcurrent Ir1 lags by 90� since the load is purely inductive. Value ofthe current through parallel winding I2 is unknown but the direc-tion is opposite to Ir1. The Eqs. (5) and (6) are derived from the testcircuit shown in Fig. 1.

Ur1ffiffiffi3p � ukr12

100¼ Ir1xðLS þMSPÞ � I2xðLP þMSPÞ ð5Þ

I2 ¼ Ir1MSP

LPð6Þ

ukr12 is the rated short-circuit voltage of a transformer referred torated apparent power Sr12 between HV and LV winding. Ur1 is therated voltage of HV winding. MSP is determined by substituting I2

in (5) with expression (6).

1003121 krr uU ⋅

Fig. 1. Test circuit used for determination of MSP.

MSP ¼

ffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiIr1xLS �

Ur1ffiffiffi3p � ukr12

100

� �� LP

xIr1

sð7Þ

Mutual inductance MP3 between parallel and tertiary winding canbe determined from the test circuit shown in Fig. 2. Voltage is ap-plied on LV winding, while the tertiary winding is short-circuited.

The Eqs. (8) and (9) are derived from the test circuit shown inFig. 2.

Ur2ffiffiffi3p � ukr23

100¼ Ir2xLP � I3xMP3 ð8Þ

I3 ¼ Ir2MP3

L3ð9Þ

ukr23 is the rated short-circuit voltage of a transformer referred torated apparent power Sr23 between LV and tertiary winding. Ur2 isthe rated voltage of LV winding. From Eqs. (8) and (9) MP3 is deter-mined (10).

MP3 ¼

ffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiIr2xLP �

Ur2ffiffiffi3p � ukr23

100

� �� L3

xIr2

sð10Þ

Mutual inductance MS3 between series and tertiary winding can bedetermined from the test circuit shown in Fig. 3 and from theresults of previous tests. Voltage is applied on HV side, while thetertiary winding is short-circuited.

Page 3: Modeling of three-phase autotransformer for short-circuit studies

Fig. 4. Autotransformer three-phase representation for short-circuit studies.

ZHVN

ZLVN X11

X12

X13

Positive sequence network

„1”-system

ZHVN

ZLVN X21

X22Negative sequence

U=1 p.u.

230 D. Filipovic-Grcic et al. / Electrical Power and Energy Systems 56 (2014) 228–234

The Eqs. (11) and (12) are derived from the test circuit shown inFig. 3.

Ur1ffiffiffi3p � ukr13

100¼ Ir1xðLS þ LP þ 2MSPÞ � I3xðMS3 þMP3Þ ð11Þ

I3 ¼ Ir1MS3 þMP3

L3ð12Þ

ukr13 is the rated short-circuit voltage of a transformer referred torated apparent power Sr13 between HV and tertiary winding. Byincluding Eq. (12) into (11) MS3 is determined (13).

MS3 ¼ffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiL3 � ðLS þ LP þ 2MSPÞ �

Ur1ffiffiffi3p � ukr13

100� L3

xIr1

s�MP3 ð13Þ

Active networks connected to HV and LV side are represented withvoltage sources and impedances ZAN1 and ZAN2:

ZAN1 ¼ jU2

r1

Ssc1ð14Þ

ZAN2 ¼ jU2

r2

Ssc2ð15Þ

where Ssc1 and Ssc2 are short-circuit powers of active networks onHV and LV side, respectively. The autotransformer model is pre-sented in Fig. 4.

Impedances ZAL1 and ZAL2 from Fig. 4 are used to simulate short-circuits on HV and LV side, while ZN represents the impedance ofthe autotransformer ground impedance.

Fig. 5. Equivalent scheme of single phase-to-ground fault on HV side of three-phaseautotransformer.

Kirchhoff’s voltage law equations for HV side phase A are givenin (16) and (17).

UA1 ¼ ðIAL1 þ IASÞ � ZAN1 þ IASjxLS � IAPjxLP þ INZN � IAPjxMSP

þ IASjxMSP þ I3jxMS3 þ I3jxMP3 ð16Þ

UA1 ¼ ðIAL1 þ IASÞ � ZAN1 þ IAL1ZAL1 þ INZN ð17Þ

Analogous to (16) and (17) the equations are derived for phases Band C at HV. Kirchhoff’s voltage law equations for LV side phase Aare given in (18) and (19).

UA2 ¼ ðIAL2 � IAS � IAPÞ � ZAN2 � IAPjxLP þ INZN þ IASjxMSP þ I3jxMP3

ð18Þ

X23

ZHVN

ZLVN X01

X02

X03

network„2”-system

Zero sequence network

„0”-system

I

Fig. 6. Single phase-to-ground fault on HV side modeled using symmetricalcomponents.

Page 4: Modeling of three-phase autotransformer for short-circuit studies

D. Filipovic-Grcic et al. / Electrical Power and Energy Systems 56 (2014) 228–234 231

UA2 ¼ ðIAL2 � IAS � IAPÞ � ZAN2 þ IAL2ZAL2 þ INZN ð19Þ

Analogous to (18) and (19) the equations are derived for phases Band C at LV side.

Two more equations are derived from Kirchhoff’s current law:

ðIAP þ IBP þ ICPÞ � jxMP3 ¼ ðIAS þ IBS þ ICSÞ � jxMS3 þ 3I3 � jxL3 ð20Þ

IAP þ IBP þ ICP þ IN ¼ IAL1 þ IBL1 þ ICL1 þ IAL2 þ IBL2 þ ICL2 ð21Þ

UA1

UB1

UC1

UA2

UB2

UC2

UA1

UB1

UC1

UA2

UB2

UC2

00

2666666666666666666666666666664

3777777777777777777777777777775

¼

ZAN1 0 0 0 0 0 ZAN1þXSþXSP 0 0 �ðXPþXSPÞ 0 0 ZN XS3þXP3

0 ZBN1 0 0 0 0 0 ZBN1þXSþXSP 0 0 �ðXP þXSPÞ 0 ZN XS3þXP3

0 0 ZCN1 0 0 0 0 0 ZCN1þXSþXSP 0 0 �ðXP þXSPÞ ZN XS3þXP3

0 0 0 ZAN2 0 0 XSP �ZAN2 0 0 �ðZAN2þXPÞ 0 0 ZN XP3

0 0 0 0 ZBN2 0 0 XSP �ZBN2 0 0 �ðZBN2þXPÞ 0 ZN XP3

0 0 0 0 0 ZCN2 0 0 XSP �ZCN2 0 0 �ðZCN2þXPÞ ZN XP3

ZAN1þZAL1 0 0 0 0 0 ZAN1 0 0 0 0 0 ZN 00 ZBN1þZBL1 0 0 0 0 0 ZBN1 0 0 0 0 ZN 00 0 ZCN1þZCL1 0 0 0 0 0 ZCN1 0 0 0 ZN 00 0 0 ZAN2þZAL2 0 0 �ZAN2 0 0 �ZAN2 0 0 ZN 00 0 0 0 ZBN2þZBL2 0 0 �ZBN2 0 0 �ZBN2 0 ZN 00 0 0 0 0 ZCN2þZCL2 0 0 �ZCN2 0 0 �ZCN2 ZN 00 0 0 0 0 0 XS3 XS3 XS3 �XP3 �XP3 �XP3 0 3X3

�1 �1 �1 �1 �1 �1 0 0 0 1 1 1 1 0

2666666666666666666666666666664

3777777777777777777777777777775

IAL1

IBL1

ICL1

IAL2

IBL2

ICL2

IAS

IBS

ICS

IAP

IBP

ICP

IN

I3

2666666666666666666666666666664

3777777777777777777777777777775ð22

Kirchhoff’s law equations can be written in matrix form (22) whichcan be simplified as:

½I� ¼ ½Z��1 � ½U� ð23Þ

The unknown current vector [I] is calculated as a product of the in-verted matrix [Z] and the vector [U] with known nodal voltages.

3. Symmetrical components model for single phase-to-groundfault

The autotransformer model for short-circuit studies was verifiedwith symmetrical components [16]. Symmetrical components arecommonly used to analyze unsymmetrical faults in three-phasepower systems since in many cases the unbalanced part of the phys-ical system can be isolated for a study, while the rest of the system isbeing considered to be in balance. In such cases, the aim is to find thesymmetrical components of the voltages and the currents at thepoint of unbalance and connect the sequence networks.

Fig. 5 shows equivalent scheme for the analysis of single phase-to-ground fault on HV side of three-phase autotransformer.

Per unit impedances of active networks can be calculated byEqs. (24) and (25).

ZHVN ¼Sb

SscHVð24Þ

ZLVN ¼Sb

SscLVð25Þ

Sb is base power and SscHV and SscLV are short-circuit powers of activenetworks.

Currents relevant to the base power are given by Eqs. (26)–(28).

Ir1 ¼Sbffiffiffi

3p� Ur1

ð26Þ

Ir2 ¼Sbffiffiffi

3p� Ur2

ð27Þ

Ir3 ¼Sb

3 � Ur3ð28Þ

The per unit short-circuit impedances are calculated by Eqs. (29)–(31).

XHV=LV ¼ukr12

100ð29Þ

XHV=TV ¼ukr13

100ð30Þ

XLV=TV ¼ukr23

100ð31Þ

Þ

Short-circuit reactances of the primary X1, secondary X2 and tertiarywinding X3, referring to Fig. 5, can be calculated by Eqs. (32)–(34).

X1 ¼12� ðXHV=LV þ XHV=TV � XLV=TV Þ ð32Þ

X2 ¼12� ðXHV=LV þ XLV=TV � XHV=TV Þ ð33Þ

X3 ¼12� ðXHV=TV þ XLV=TV � XHV=LV Þ ð34Þ

Reactances of the transformer windings in positive (X11,X12,X13),negative (X21,X22,X23) and zero (X01,X02,X03) sequence systems aredetermined by the Eqs. (35)–(37).

X11 ¼ X21 ¼ X01 ¼ X1 ð35ÞX12 ¼ X22 ¼ X02 ¼ X2 ð36ÞX13 ¼ X23 ¼ X03 ¼ X3 ð37Þ

Equivalent scheme of single phase-to-ground fault on HV side mod-eled using symmetrical components is shown in Fig. 6.

Total impedances of the positive, negative and zero sequencenetworks are determined using the Eqs. (38)–(41).

Z1 ¼Z1HVN � ðZ1LVN þ X11 þ X12ÞZ1LVN þ Z1HVN þ X11 þ X12

ð38Þ

Z2 ¼Z2HVN � ðZ2LVN þ X21 þ X22ÞZ2LVN þ Z2HVN þ X21 þ X22

ð39Þ

Zp ¼X03 � ðZ0LVN þ X02ÞX03 þ Z0LVN þ X02

ð40Þ

Z0 ¼Z0HVN � ðZp þ X01ÞZ0HVN þ Zp þ X01

ð41Þ

Total currents of positive, negative and zero-sequence networks aredetermined by Eq. (42).

I1 ¼ I2 ¼ I0 ¼ I ¼ UZ1 þ Z2 þ Z0

ð42Þ

Page 5: Modeling of three-phase autotransformer for short-circuit studies

232 D. Filipovic-Grcic et al. / Electrical Power and Energy Systems 56 (2014) 228–234

Positive-sequence currents of HV and LV side are determined by Eq.(43).

I11 ¼ I12 ¼ I � Z1HVN

Z1LVN þ Z1HVN þ X11 þ X12ð43Þ

Negative-sequence currents of HV and LV side are determined byEq. (44).

I21 ¼ I22 ¼ I11 ð44Þ

Zero-sequence currents are determined by Eqs. (45)–(47).

I01 ¼ I � Z1HVN

Z0HVN þ Zp þ X01ð45Þ

I02 ¼ I01 �X03

Z0LVN þ X02 þ X03ð46Þ

I03 ¼ I01 � I02 ð47Þ

Finally, currents through HV, LV and tertiary winding are deter-mined by Eqs. (48)–(50).

I1 ¼ ðI11 þ I21 þ I01Þ � Ir1 ð48ÞI2 ¼ ðI12 þ I22 þ I02Þ � Ir2 � I1 ð49ÞI3 ¼ I03 � Ir ð50Þ

Fig. 7. Phasor diagram in case of isolated neutral ZN ?1.

4. Calculation examples

Calculations were performed on autotransformer with datagiven in Table 1.

Rated autotransformer powers are Sr1 = Sr2 = 400 MVA,Sr3 = 80 MVA. Short-circuit powers of active networks areSscLV = 3.43 GVA and SscHV = 11.9 GVA.

4.1. Single phase-to-ground fault on HV side

Inductance matrix model was compared to symmetrical com-ponents for single phase-to-ground fault on HV side of three-phaseautotransformer with solidly grounded neutral. Calculation resultsare shown in Table 2 and the percentage difference between faultcurrents is calculated. Calculation results with both autotrans-former models show excellent agreement for different tappositions.

Table 2Calculation results.

Tap position Current Current values for inductance matrix model (A)

High tap I3 24308.1585IAS 3406.4256IAP 710.6559

Principal tap I3 23137.1589IAS 3194.4801IAP 515.5074

Low tap I3 22225.8374IAS 2980.4587IAP 356.1546

Table 1Autotransformer data.

Tap Ur1 (kV) Ur2 (kV) Ur3 (kV) ukr12(%) ukr13 (%) ukr23 (%)

+ 439.87 231 13.0 9.47 10.94 9.460 400 231 10.5 11.63 13.92 10.66� 371.75 231 8.76 14.14 17.02 12.14

4.2. Influence of tertiary winding on un-faulted phase voltages fordifferent grounding impedances

Autotransformer neutral is sometimes isolated in order toreduce the short circuit currents in power system. In case ofground fault in solidly grounded network the un-faulted phasevoltages remain unchanged, but in isolated network un-faultedphase voltages will reach the phase-to-phase values. This wouldalmost certainly result in over excitation of the core, with greatlyincreased magnetizing currents and core losses.

Current values for symmetrical components model (A) Difference (ppm)

24308.1909 1.333406.4283 0.80

710.6554 0.76

23137.2034 1.923194.4835 1.06

515.5073 0.13

22225.8968 2.672980.4629 1.39

356.1552 1.68

Fig. 8. Phasor diagram in case of neutral grounding impedance ZN = 10 X.

Page 6: Modeling of three-phase autotransformer for short-circuit studies

D. Filipovic-Grcic et al. / Electrical Power and Energy Systems 56 (2014) 228–234 233

Delta connected tertiary winding acts as short-circuit in zero se-quence network and therefore reduces zero sequence impedance.As a consequence, the un-faulted phase voltages will be reduced.

The following example illustrates the effect of tertiary windingon un-faulted phase voltages for different grounding impedances.The single phase-to-ground fault was analyzed and the autotrans-former was represented with inductance matrix.

Fig. 7 shows the voltage phasor diagram in case of isolated auto-transformer neutral. Black dotted line indicates the half-circularpath of neutral point potential with respect to ground impedance.

The results show that tertiary winding reduces overvoltages inun-faulted phases by 28.6% in case of isolated neutral. Fig. 8 showsthe voltage phasor diagram when ZN = 10 X, to illustrate the condi-tion when neutral point is neither directly grounded nor isolated.

IAS·NS

IBS·NS

ICS·NS

IBP·NP

IAP·NP

ICP·NP

I3·N3

IAP·NP=IAS·NS

IBP·NP=IBS·NS

ICS≈ICP≈0

IAS·NS

IBS

ICS=0

IBP·NP

IAP·NP

ICP·NP

I3·N3

IAP·NP=IAS·NS

IB

ICP≈ICS=0

(a) (b)

Fig. 9. Ampere-turns phasor diagrams for double phase-to-ground fault (phases A and B)Blue markings refer to case without tertiary winding. (For interpretation of the references

ICS·NSIBP·NP=IBS·NS

IAP·NP=IAS·NS

IAS·NS

IBS·NS

IAP·NP

IBP·NP

I3·N3

ICP·NPICS≈ICP≈0

I3·N3 IAP·NP=IB

(a)

Fig. 10. Ampere-turns phasor diagrams for double phase-to-ground fault (phases A and BBlue markings refer to case without tertiary winding. (For interpretation of the references

IAP·NP IBS·NS=ICS·NS

IAS·NS

I3·N3

IBP·NP=ICP·NP

IAP·NP=IAS·NS

IBS≈ICS≈IBP≈ICP≈0

IASIAP·NP

IB

IBPI3·N3

IAP·NP=IAS·NS

(a) (b)

Fig. 11. Ampere-turns phasor diagrams for single phase-to-ground fault (phase A) on HVmarkings refer to case without tertiary winding. (For interpretation of the references to

4.3. Influence of tertiary winding on asymmetrical fault currentdistribution

In case of an asymmetrical fault current flows through tertiarywinding. The following examples, calculated with inductance ma-trix model, show the influence of tertiary winding presence on HVand LV side currents.

Figs. 9–12 show ampere-turns diagrams for asymmetrical faultson autotransformer with and without tertiary winding. Black dot-ted line represents translated ampere-turns phasor I3N3 which isequal to difference between parallel and serial winding ampere-turns. It can be seen that tertiary winding presence reduces thecurrents in un-faulted windings, but increases currents in faultyones.

·NS

P·NP=IBS·NS

IAS·NS=IBS·NS=ICS·NS

IAP·NP=IBP·NP=ICP·NP

I3·N3IAS≈IBS≈ICS≈IAP≈IBP≈ICP≈0

(c)

on HV side supplied from: (a) HV and LV side; (b) LV side only; and (c) HV side only.to color in this figure legend, the reader is referred to the web version of this article.)

IAS=IBS=ICS=0

P·NP=ICP·NPIAP·NP

IAS·NS

IBS·NS

IBP·NP

I3·N3

ICP·NP

ICS·NS

ICS≈ICP≈0

IBP·NP=IBS·NS

IAP·NP=IAS·NS

(b) (c)

) on LV side supplied from: (a) HV and LV side; (b) LV side only; and (c) HV side only.to color in this figure legend, the reader is referred to the web version of this article.)

·NS

S=ICS=0

·NP=ICP·NP

IAS·NS=IBS·NS=ICS·NS

IAP·NP=IBP·NP=ICP·NP

I3·N3

IAS≈IBS≈ICS≈0 IAP≈IBP≈ICP≈0

(c)

side supplied from: (a) HV and LV side; (b) LV side only; and (c) HV side only. Bluecolor in this figure legend, the reader is referred to the web version of this article.)

Page 7: Modeling of three-phase autotransformer for short-circuit studies

IAP·NP

IAS·NS

I3·N3

IBP·NP=ICP·NP

IBS·NS=ICS·NSIBS≈ICS≈IBP≈ICP≈0

IAP·NP=IAS·NS

IAS=IBS=ICS=0

IAP·NP=IBP·NP=ICP·NP

I3·N3

IAP≈IBP≈ICP≈0IAS=IBS=ICS=0

IAP·NP

IAS·NS

I3·N3

IBP·NP=ICP·NP

IBS·NS=ICS·NS

IBS≈ICS≈IBP≈ICP≈0

IAP·NP=IAS·NS

(a) (b) (c)

Fig. 12. Ampere-turns phasor diagrams for single phase-to-ground fault (phase A) on LV side supplied from: (a) HV and LV side; (b) LV side only; and (c) HV side only. Bluemarkings refer to case without tertiary winding. (For interpretation of the references to color in this figure legend, the reader is referred to the web version of this article.)

234 D. Filipovic-Grcic et al. / Electrical Power and Energy Systems 56 (2014) 228–234

5. Conclusion

The inductance matrix autotransformer model for short-circuitstudies is presented. The proposed model consists of winding self-inductances and corresponding mutual inductances betweenwindings which are calculated from factory measurements andmanufacturer data.

The model was verified with symmetrical components for sin-gle phase-to-ground fault and the results showed excellentagreement.

Additionally, the influence of tertiary winding on un-faultedphase voltages and on asymmetrical fault current distributionwas analyzed. From the conducted analysis the following conclu-sions can be emphasized.

� The presence of tertiary winding significantly reduces tempo-rary overvoltages in networks with isolated neutral. Neutralpoint potential moves along the half-circular path with respectto ground impedance.� Asymmetrical fault currents in autotransformer HV and LV

windings highly depend on delta winding presence. Tertiarywinding presence increases currents in faulty windings, butreduces the currents in un-faulted ones.Some benefits of the inductance matrix model compared tosymmetrical components model are:� It is suitable for analyzing specific problems, i.e. the influence of

tertiary winding on un-faulted phase voltages and fault currentdistribution, as described in chapter 4.� It could be easily used in any standard transient simulation

environment, including EMTP-like tools.� It is possible to study easily different simultaneous faults on HV

and LV side. Though relatively infrequent, simultaneous faultsare important because relay systems, operating satisfactorilyfor single faults, may fail to isolate simultaneous faults. Theanalysis of simultaneous faults is considerably more compli-cated when using symmetrical components.

References

[1] Winders Jr JJ. Power transformers principles and applications. PPL electricutilities. Allentown, Pennsylvania: Marcel Dekker; 2002.

[2] Behjat V, Vahedi A, Setayeshmehr A, Borsi H, Gockenbach E. Sweep frequencyresponse analysis for diagnosis of low level short circuit faults on the windingsof power transformers: an experimental study. Int J Elect Power Energy Syst2012;42(1):78–90.

[3] Rahmatian M, Vahidi B, Ghanizadeh AJ, Gharehpetian GB, Alehosseini HA.Insulation failure detection in transformer winding using cross-correlationtechnique with ANN and k-NN regression method during impulse test. Int JElect Power Energy Syst 2013;53:209–18.

[4] Varricchio SL, Gomes Jr S, Diniz Rangel R. Three winding transformer s-domainmodel for modal analysis of electrical networks. Int J Elect Power Energy Syst2011;33(3):420–9.

[5] Talaq J. Fault calculations using three terminal Thevenin’s equivalent circuit.Int J Elect Power Energy Syst 2011;33(8):1462–9.

[6] Vlachogiannis JG. An accurate autotransformer model for load flow studieseffect on the steady-state analysis of the Hellenic transmission system. ElectPower Syst Res 1999;50(2):147–53.

[7] Andrei RG, Rahman ME, Koeppel C, Arthaud JP. A novel autotransformer designimproving power system operation. IEEE Trans Power Delivery2002;17(2):523–7.

[8] Mork BA, Gonzalez F, Ishchenko D. Leakage inductance model forautotransformer transient simulation. In: International conference on powersystems transients. Montreal, Canada, June 2005.

[9] Horton R, Dugan RC, Wallace K, Hallmark D. Improved autotransformer modelfor transient recovery voltage (TRV) Studies. IEEE Trans Power Delivery2012;27(2):895–901.

[10] Delfino F, Procopio R, Rossi M. High-frequency EHV/HV autotransformer modelidentification from LEMP test data. IEEE Trans Power Delivery2011;26(2):714–24.

[11] Kelemen T. Transformer tertiary and how to handle it. J Energy1994;43:111–7.

[12] McMahon D. MATLAB demystified. McGraw-Hill Professional; 2007.[13] Gajic Z, Holst S. Application of unit protection schemes for auto-transformers.

In: 2nd International scientific and technical conference: actual trends indevelopment of power system protection and automation. Moscow,September 2009.

[14] Gajic Z, Ivankovic I, Filipovic-Grcic B. Differential protection issues forcombined autotransformer-phase shifting transformer. Int Conf DevelopPower Syst Protect 2004;1:364–7.

[15] Dolenc A. Transformers 1 and 2, book, Faculty of electrical engineering andcomputing, 3rd ed. Zagreb; 1991.

[16] Sluis Lou van der. Transients in power systems. Chichester, England: JohnWiley & Sons Ltd; 2001.