modele ge - kohler · pdf fileengine type l3e-sdh alternator type ... for the generator sets...

5
KM12H Engine type L3E-SDH Alternator type AT00361T Performance class G2 GENERAL CHARACTERISTICS Frequency (Hz) 50 Voltage (V) 400/230 Standard control panel APM303 Optional control panel DEC4000 POWER ESP PRP Voltage kWe kVA kWe kVA Standby Amps 230 TRI 9.6 12 - - 30 400/230 9.6 12 - - 17 DIMENSIONS COMPACT VERSION Length (mm) 1220 Width (mm) 700 Height (mm) 922 Dry weight (kg) 260 Tank capacity (L) 50 DIMENSIONS SOUNDPROOFED VERSION Commercial reference of the enclosure M125 1482 760 1030 380 50 80 Length (mm) Width (mm) Height (mm) Dry weight (kg) Tank capacity (L) Acoustic pressure level @1m in dB(A) Sound power level guaranteed (Lwa) Acoustic pressure level @7m in dB(A) 95 POWER DEFINITION PRP : Prime Power is available for an unlimited number of annual operating hours in variable load applications, in accordance with ISO 8528-1. ESP : The standby power rating is applicable for supplying emergency power in variable load applications in accordance with ISO 8528-1. Overload is not allowed TERMS OF USE According to the standard, the nominal power assigned by the genset is given for 25°C Air Intlet Temperature, of a barometric pressure of 100 kPA (100 m A.S.L), and 30 % relative humidity. For particular conditions in your installation, refer to the derating table. ASSOCIATED UNCERTAINTY For the generator sets used indoor, where the acoustic pressure levels depend on the installation conditions, it is not possible to specify the ambient noise level in the operating and maintenance instructions. You will also find in our operating and maintenance instructions a warning concerning the air noise dangers and the need to implement appropriate preventive measures. This document is not contractual - Kohler Co. reserves the right to modify any of the characteristics without notice, in a constant effort to improve the quality of its products. GBD5-02008 (KM12H) 02/16 DESCRIPTIVE Kohler Co. Provides one-source responsibility for the generating system and accessories The generator set and its components are prototype- tested, factory-built, and production-tested A one-year limited warranty covers all systems and components Mechanic governor Mechanically welded chassis with antivibration suspension Main line circuit breaker Radiator for core temperature of 48/50°C max with mechanical fan Protective grille for fan and rotating parts (CE option) 9 dB(A) silencer supplied separately Charger DC starting battery with electrolyte 12 V charge alternator and starter Delivered with oil and coolant -30°C Manual for use and installation 66

Upload: nguyenliem

Post on 18-Mar-2018

220 views

Category:

Documents


2 download

TRANSCRIPT

KM12H Engine type L3E-SDHAlternator type AT00361TPerformance class G2

GENERAL CHARACTERISTICS Frequency (Hz) 50Voltage (V) 400/230Standard control panel APM303Optional control panel DEC4000

POWERESP PRP

VoltagekWe kVA kWe kVA

Standby Amps

230 TRI 9.6 12 - - 30400/230 9.6 12 - - 17

DIMENSIONS COMPACT VERSIONLength (mm) 1220Width (mm) 700Height (mm) 922Dry weight (kg) 260Tank capacity (L) 50

DIMENSIONS SOUNDPROOFED VERSIONCommercial reference of the enclosure M125

148276010303805080

Length (mm)Width (mm)Height (mm)Dry weight (kg)Tank capacity (L)Acoustic pressure level @1m in dB(A) Sound power level guaranteed (Lwa)Acoustic pressure level @7m in dB(A)

95POWER DEFINITIONPRP : Prime Power is available for an unlimited number of annual operating hours in variable load applications, in accordance with ISO 8528-1. ESP : The standby power rating is applicable for supplying emergency power in variable load applications in accordance with ISO 8528-1. Overload is not allowed

TERMS OF USEAccording to the standard, the nominal power assigned by the genset is given for 25°C Air Intlet Temperature, of a barometric pressure of 100 kPA (100 m A.S.L), and 30 % relative humidity. For particular conditions in your installation, refer to the derating table.ASSOCIATED UNCERTAINTYFor the generator sets used indoor, where the acoustic pressure levels depend on the installation conditions, it is not possible to specify the ambient noise level in the operating and maintenance instructions. You will also find in our operating and maintenance instructions a warning concerning the air noise dangers and the need to implement appropriate preventive measures.

This document is not contractual - Kohler Co. reserves the right to modify any of the characteristics without notice, in a constant effort to improve the quality of its products. GBD5-02008 (KM12H) 02/16

DESCRIPTIVEKohler Co. Provides one-source responsibility for the generating system and accessoriesThe generator set and its components are prototype- tested, factory-built, and production-tested A one-year limited warranty covers all systems and

components Mechanic governor Mechanically welded chassis with antivibration

suspension Main line circuit breaker Radiator for core temperature of 48/50°C max with

mechanical fan Protective grille for fan and rotating parts (CE option) 9 dB(A) silencer supplied separately Charger DC starting battery with electrolyte 12 V charge alternator and starter Delivered with oil and coolant -30°C Manual for use and installation

66

koca691
Typewritten Text
koca691
Typewritten Text

KM12H ENGINE CHARACTERISTICS

MITSUBISHI

L3E-SDH

Athmo L

3 0.95 N/A

76 x 70

23 : 1 3000

7

16.4

+/- 2.5%

6.00

GENERAL ENGINE DATA Engine model

Engine type

Air inlet

Cylinders arrangement

Number of cylinders

Displacement (L)

Charge Air coolant

Bore (mm) x Stroke (mm)

Compression ratio

Speed (RPM)

Pistons speed (m/s)

Maximum stand-by power at rated

RPM (kW)

Frequency regulation, steady state (%)

BMEP (bar)

Governor type Mechanical

COOLING SYSTEMRadiator & Engine capacity (L) 3.7

Max water temperature (°C) 111

Outlet water temperature (°C) 93

Fan power (kW) 1.8

0.9

10

Fan air flow w/o restriction (m3/s) Available restriction on air flow (mm H2O)Type of coolant Glycol-Ethylene

Thermostat modulating range HT (°C) 76.5-90

100

250

N/A

EMISSIONS Emission PM (mg/Nm3) 5% O2

Emission CO (mg/Nm3) 5% O2

Emission HC+NOx (g/kWh)

Emission HC (mg/Nm3) 5% O2 20

590

54.3

EXHAUSTExhaust gas temperature @ ESP 50Hz (°C)

Exhaust gas flow @ ESP 50Hz (L/s)

Max. exhaust back pressure (mm H2O) 800

FUELConsumption @ 110% load (L/h) N/A

Consumption @ 100% load (L/h) 5.1

Consumption @ 75% load (L/h) 4.2

Consumption @ 50% load (L/h) 3.2

Maximum fuel pump flow (L/h) 18

4.1

0.5

4

0.014

OILOil capacity (L)

Min. oil pressure (bar)

Max. oil pressure (bar)

Oil consumption 100% load (L/h)

Oil sump capacity (L) 3.6

15

2

HEAT BALANCEHeat rejection to exhaust (kW)

Radiated heat to ambient (kW)

Heat rejection to coolant (kW) 18.6

310

AIR INTAKEMax. intake restriction (mm H2O) Intake air flow (L/s) 19.7

This document is not contractual - Kohler Co. reserves the right to modify any of the characteristics without notice, in a constant effort to improve the quality of its products. GBD5-02008 (KM12H) 02/16

KM12HALTERNATOR CHARACTERISTICS

GENERAL DATA Alternator type AT00361TNumber of Phase Three phasePower factor (Cos Phi) 0.8Altitude (m) 0 to 1000Overspeed (rpm) N/ANumber of pole 2Capacity for maintaining short circuit at 3 ln for 10 s N/A

Insulation class H T° class (H/125°), continuous 40°C H / 125°K T° class, standby 27°C H / 163°KAVR Regulation NoTotal Harmonic Distortion in no-load DHT (%) N/A

Total Harmonic Distortion, on load DHT (%) N/A

Wave form : NEMA=TIF N/AWave form : CEI=FHT N/ANumber of bearing 1Coupling Direct

N/A

N/A

Voltage regulation at established rating (+/- %)Recovery time (Delta U = 20% transient) (ms)Protection class IP 23Technology Collar and brush

OTHER DATA Continuous Nominal Rating 40°C (kVA) 16Standby Rating 27°C (kVA) N/AEfficiencies 100% of load (%) 84.5Air flow (m3/s) N/A

Short circuit ratio (Kcc) N/ADirect axis synchro reactance unsaturated (Xd) (%) N/AQuadrature-axis synchro reactance unsaturated (Xq) (%)Open circuit time constant (T'do) (ms) N/ADirect axis transient reactance saturated (X'd) (%) N/A

N/AN/AN/A

N/A

Short circuit transient time constant (T''d) (ms) Direct axis subtransient reactance saturated (X''d) (%)Subtransient time constant (T"d) (ms)Quadrature-axis subtransient reactance saturated (X"q) (%)Subtranscient time constant (T"q) (ms) N/AZero sequence reactance unsaturated (Xo) (%) N/ANegative sequence reactance saturated (X2) (%) N/AArmature time constant (Ta) (ms) N/ANo load excitation current (io) (A) 0.9Full load excitation current (ic) (A) N/A

90

N/A

Full load excitation voltage (uc) (V)Engine start (Delta U = 20% perm. or 50% trans.) (kVA)Transient dip (4/4 load) - PF : 0,8 AR (%) N/ANo load losses (W) N/AHeat rejection (W) N/A

This document is not contractual - Kohler Co. reserves the right to modify any of the characteristics without notice, in a constant effort to improve the quality of its products. GBD5-02008 (KM12H) 02/16

N/A

Unbalanced load acceptance ratio (%) N/A

KM12HCONTROL PANEL

APM303, comprehensive and simple DEC4000, ergonomic and user-friendly

This document is not contractual - Kohler Co. reserves the right to modify any of the characteristics without notice, in a constant effort to improve the quality of its products. GBD5-02008 (KM12H) 02/16

The APM303 is a versatile unit which can be operated in manual or automatic mode. It offers the following features:Measurements:phase-to-neutral and phase-to-phase voltages, fuel level(In option : active power currents, effective power, power factors, Kw/h energy meter, oil pressure and coolant temperature levels)Supervision:Modbus RTU communication on RS485Reports:(In option : 2 configurable reports)Safety features:Overspeed, oil pressure,coolant temperatures, minimum and maximum voltage, minimum and maximum frequency (Maximum active power P<66kVA)Traceability:Stack of 12 stored eventsFor further information, please refer to the data sheet for the APM303.

The highly versatile DEC4000 control unit is complex yet accessible, thanks to the particular attention paid to optimising its ergonomics and ease of use. With its large display screen, buttons and scroll wheel, it places the accent on simplicity and communication.

The DEC4000 offers the following functions:

Electrical measurements: voltmeter, frequency meter, ammeter.

Engine parameters: working hours counter, oil pressure, coolant temperature, fuel level, engine speed, battery voltage.

Alarms and faults: oil pressure, coolant temperature, failure to start, overspeed, alternator min./max., battery voltage min./max., emergency stop, fuel level.

Ergonomics: wheel for navigating around the various menus.

Communication: remote control and operation software, USB connections, PC connection.

For more information on the product and its options, please refer to the sales documentation.

The control unit can be used as a basic terminal block for connecting a control box.

Offers the following functions:

emergency stop button, customer connection terminal block, CE.

Basic terminal block

KM12HCONTROL PANEL

This document is not contractual - Kohler Co. reserves the right to modify any of the characteristics without notice, in a constant effort to improve the quality of its products. GBD5-02008 (KM12H) 02/16