model pkfy-wl-vlm-e

16
AIR CONDITIONING SYSTEMS PKFY-WL-VLM-E MODEL

Upload: others

Post on 04-Oct-2021

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: MODEL PKFY-WL-VLM-E

AIR CONDITIONING SYSTEMS

PKFY-WL-VLM-EMODEL

Page 2: MODEL PKFY-WL-VLM-E

PKFY-WL-VLM-E

MEES19K102 1

CONTENTS Wall mounted

I.Wall mounted

1. SPECIFICATIONS.................................................................................................................................... 2

2. EXTERNAL DIMENSIONS ....................................................................................................................... 4

3. CENTER OF GRAVITY ............................................................................................................................ 6

4. ELECTRICAL WIRING DIAGRAMS ......................................................................................................... 7

5. SOUND LEVELS ...................................................................................................................................... 8

5-1. Sound levels .................................................................................................................................... 85-2. NC curves ........................................................................................................................................ 8

6. TEMPERATURE/AIRFLOW DISTRIBUTIONS......................................................................................... 9

6-1. Temperature distributions ................................................................................................................ 96-2. Airflow distributions.......................................................................................................................... 11

7. ELECTRICAL CHARACTERISTICS......................................................................................................... 13

8. OPTIONAL PARTS................................................................................................................................... 14

8-1. Optional parts line up for the Indoor unit.......................................................................................... 148-2. Drain pump ...................................................................................................................................... 148-3. Valve kit ........................................................................................................................................... 14

0000005527.BOOK 1 ページ 2020年1月24日 金曜日 午後2時47分

Page 3: MODEL PKFY-WL-VLM-E

MEES19K102

PK

FY

-WL

-VL

M-E

2

1. SPECIFICATIONS Wall mounted

I.Wall mounted1. SPECIFICATIONS

Model PKFY-WL10VLM-E PKFY-WL15VLM-E PKFY-WL20VLM-E

Power source1-phase 220-240V 50Hz,

1-phase 220V 60Hz1-phase 220-240V 50Hz,

1-phase 220V 60Hz1-phase 220-240V 50Hz,

1-phase 220V 60Hz

Cooling capacity *1 kW 1.2 1.7 2.2

(Nominal) *1 kcal / h 1,000 1,500 1,900

*1 BTU / h 4,100 5,800 7,500

Power input kW 0.02 0.02 0.03

(220V) Current input A 0.20 0.20 0.25

Heating capacity *2 kW 1.4 1.9 2.5

(Nominal) *2 kcal / h 1,200 1,600 2,200

*2 BTU / h 4,800 6,500 8,500

Power input kW 0.01 0.01 0.02

(220V) Current input A 0.15 0.15 0.20

External finish Plastic, MUNSELL (0.7PB 9.2/0.4) Plastic, MUNSELL (0.7PB 9.2/0.4) Plastic, MUNSELL (0.7PB 9.2/0.4)

External dimension HxWxD mm 299x773x237 299x773x237 299x773x237

in. 11-25/32 x 30-7/16 x 9-11/32 11-25/32 x 30-7/16 x 9-11/32 11-25/32 x 30-7/16 x 9-11/32

Net weight kg(lbs) 11 (25) 11 (25) 11 (25)

Heat exchangerCross fin

(Aluminum fin and copper tube)Cross fin

(Aluminum fin and copper tube)Cross fin

(Aluminum fin and copper tube)

Water Volume L 0.6 0.6 0.7

FAN Type x Quantity Line flow fan x 1 Line flow fan x 1 Line flow fan x 1

External static press. Pa 0 0 0

mmH2O 0 0 0

Motor Type DC motor DC motor DC motor

Motor output kW 0.030 0.030 0.030

Driving mechanism Direct-driven Direct-driven Direct-driven

Airflow rate m3 / min 3.3-3.8-4.1-4.5 3.3-3.8-4.3-4.9 4.0-5.0-6.0-7.0

(Low-Mid2-Mid-High) L/s 55-63-68-75 55-63-72-82 67-83-100-117

cfm 117-134-145-159 117-134-152-173 141-177-212-247

Sound pressure level (measured in anechoic room) dB <A> 22-26-28-30 22-26-29-32 22-28-33-36

Insulation material Polyethylene sheet Polyethylene sheet Polyethylene sheet

Air filter PP honeycomb PP honeycomb PP honeycomb

Protection device Fuse Fuse Fuse

Refrigerant control device - - -

Connectable outdoor unit/HBC controllerHYBRID CITY MULTI/

CMB-WM-V-AA, CMB-WM-V-ABHYBRID CITY MULTI/

CMB-WM-V-AA, CMB-WM-V-ABHYBRID CITY MULTI/

CMB-WM-V-AA, CMB-WM-V-AB

Water pipingConnection size

Inlet in. RC 3/4 screw RC 3/4 screw RC 3/4 screw

diameter Outlet in. RC 3/4 screw RC 3/4 screw RC 3/4 screw

*3 *4Field pipe size

Inlet mm I.D 20 20 20

Outlet mm I.D 20 20 20

Field drain pipe size mm(in.) I.D. 16(5/8) I.D. 16(5/8) I.D. 16(5/8)

Drawing External BT01B059 BT01B059 BT01B059

Wiring RH79C061 RH79C061 RH79C061

Refrigerant cycle - - -

Standard attachment Document Installation Manual, Instruction Book Installation Manual, Instruction Book Installation Manual, Instruction Book

Accessory

Mount board, Screw, Felt tape, Compression joint, L-shape connection pipe A/B, Compression joint ring (ø15),

Insulation, Tie band

Mount board, Screw, Felt tape, Compression joint, L-shape connection pipe A/B, Compression joint ring (ø15),

Insulation, Tie band

Mount board, Screw, Felt tape, Compression joint, L-shape connection pipe A/B, Compression joint ring (ø15),

Insulation, Tie band

Optional parts Drain pump PAC-SK01DM-E PAC-SK01DM-E PAC-SK01DM-E

Valve kit *5 PAC-SK04VK-E PAC-SK04VK-E PAC-SK04VK-E

Remarks * Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual.* Due to continuing improvement, above specification may be subject to change without notice.

Notes: Unit converter

1.Nominal cooling conditions Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B. (95°FD.B.) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.) 2.Nominal heating conditions Indoor: 20°CD.B. (68°FD.B.), Outdoor: 7°CD.B./6°CW.B. (45°FD.B./43°FW.B.) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.) 3.Be sure to install a valve on the water outlet. 4.Install a strainer (40 mesh or more) on the pipe next to the valve to remove the foreign matters. 5.Certain restrictions apply to indoor unit combinations. Refer to the section on the valve kit in the chapter "OPTIONAL PARTS" in the DATA BOOK for the restrictions. When the valve kit is installed farther away from the HBC than the distance between the HBC and the WL-model indoor unit, the maximum allowable height difference between the HBC and the valve kit is 15 meters. The maximum allowable piping length between the indoor unit and the valve kit is 5 meters. *Please group units that operate on 1 branch.

kcal/h =kW x 860

BTU/h =kW x 3,412

cfm =m3/min x 35.31

lbs =kg/0.4536

*Above specification data is subject to rounding variation.

0000005527.BOOK 2 ページ 2020年1月24日 金曜日 午後2時47分

Page 4: MODEL PKFY-WL-VLM-E

MEES19K102

PK

FY

-WL

-VL

M-E

3

1. SPECIFICATIONS Wall mounted

Model PKFY-WL25VLM-E PKFY-WL32VLM-E PKFY-WL40VLM-E

Power source1-phase 220-240V 50Hz,

1-phase 220V 60Hz1-phase 220-240V 50Hz,

1-phase 220V 60Hz1-phase 220-240V 50Hz,

1-phase 220V 60Hz

Cooling capacity *1 kW 2.8 3.6 4.5

(Nominal) *1 kcal / h 2,400 3,100 3,900

*1 BTU / h 9,600 12,300 15,400

Power input kW 0.04 0.04 0.05

(220V) Current input A 0.35 0.35 0.45

Heating capacity *2 kW 3.2 4.0 5.0

(Nominal) *2 kcal / h 2,800 3,400 4,300

*2 BTU / h 10,900 13,600 17,100

Power input kW 0.03 0.03 0.04

(220V) Current input A 0.30 0.30 0.40

External finish Plastic, MUNSELL (0.7PB 9.2/0.4) Plastic, MUNSELL (0.7PB 9.2/0.4) Plastic, MUNSELL (0.7PB 9.2/0.4)

External dimension HxWxD mm 299x773x237 299x898x237 299x898x237

in. 11-25/32 x 30-7/16 x 9-11/32 11-25/32 x 35-3/8 x 9-11/32 11-25/32 x 35-3/8 x 9-11/32

Net weight kg(lbs) 11 (25) 13(29) 13(29)

Heat exchangerCross fin

(Aluminum fin and copper tube)Cross fin

(Aluminum fin and copper tube)Cross fin

(Aluminum fin and copper tube)

Water Volume L 0.7 1.0 1.1

FAN Type x Quantity Line flow fan x 1 Line flow fan x 1 Line flow fan x 1

External static press. Pa 0 0 0

mmH2O 0 0 0

Motor Type DC motor DC motor DC motor

Motor output kW 0.030 0.030 0.030

Driving mechanism Direct-driven Direct-driven Direct-driven

Airflow rate m3 / min 4.0-5.4-7.0-8.4 6.3-7.6-9.0-10.4 6.4-8.2-10.0-11.9

(Low-Mid2-Mid-High) L/s 67-90-117-140 105-127-150-173 107-137-167-198

cfm 141-191-247-297 222-268-318-367 226-290-353-420

Sound pressure level (measured in anechoic room) dB <A> 22-30-36-41 29-34-38-41 30-36-41-45

Insulation material Polyethylene sheet Polyethylene sheet Polyethylene sheet

Air filter PP honeycomb PP honeycomb PP honeycomb

Protection device Fuse Fuse Fuse

Refrigerant control device - - -

Connectable outdoor unit/HBC controllerHYBRID CITY MULTI/

CMB-WM-V-AA, CMB-WM-V-ABHYBRID CITY MULTI/

CMB-WM-V-AA, CMB-WM-V-ABHYBRID CITY MULTI/

CMB-WM-V-AA, CMB-WM-V-AB

Water pipingConnection size

Inlet in. RC 3/4 screw RC 3/4 screw RC 3/4 screw

diameter Outlet in. RC 3/4 screw RC 3/4 screw RC 3/4 screw

*3 *4Field pipe size

Inlet mm I.D 20 20 20

Outlet mm I.D 20 20 20

Field drain pipe size mm(in.) I.D. 16(5/8) I.D. 16(5/8) I.D. 16(5/8)

Drawing External BT01B059 BT01B060 BT01B060

Wiring RH79C061 RH79C061 RH79C061

Refrigerant cycle - - -

Standard attachment Document Installation Manual, Instruction Book Installation Manual, Instruction Book Installation Manual, Instruction Book

Accessory

Mount board, Screw, Felt tape, Compression joint, L-shape connection pipe A/B, Compression joint ring (ø15),

Insulation, Tie band

Mount board, Screw, Felt tape, Compression joint, L-shape connection pipe A/B, Compression joint ring (ø15),

Insulation, Tie band

Mount board, Screw, Felt tape, Compression joint, L-shape connection pipe A/B, Compression joint ring (ø15),

Insulation, Tie band

Optional parts Drain pump PAC-SK01DM-E PAC-SK01DM-E PAC-SK01DM-E

Valve kit *5 PAC-SK04VK-E PAC-SK04VK-E PAC-SK04VK-E

Remarks * Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual.* Due to continuing improvement, above specification may be subject to change without notice.

Notes: Unit converter

1.Nominal cooling conditions Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B. (95°FD.B.) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.) 2.Nominal heating conditions Indoor: 20°CD.B. (68°FD.B.), Outdoor: 7°CD.B./6°CW.B. (45°FD.B./43°FW.B.) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.) 3.Be sure to install a valve on the water outlet. 4.Install a strainer (40 mesh or more) on the pipe next to the valve to remove the foreign matters. 5.Certain restrictions apply to indoor unit combinations. Refer to the section on the valve kit in the chapter "OPTIONAL PARTS" in the DATA BOOK for the restrictions. When the valve kit is installed farther away from the HBC than the distance between the HBC and the WL-model indoor unit, the maximum allowable height difference between the HBC and the valve kit is 15 meters. The maximum allowable piping length between the indoor unit and the valve kit is 5 meters. *Please group units that operate on 1 branch.

kcal/h =kW x 860

BTU/h =kW x 3,412

cfm =m3/min x 35.31

lbs =kg/0.4536

*Above specification data is subject to rounding variation.

0000005527.BOOK 3 ページ 2020年1月24日 金曜日 午後2時47分

Page 5: MODEL PKFY-WL-VLM-E

MEES19K102

PK

FY

-WL

-VL

M-E

4

2. EXTERNAL DIMENSIONS Wall mounted

2. EXTERNAL DIMENSIONS

PKFY-WL10, 15, 20, 25VLM-E Unit: mm

0000005527.BOOK 4 ページ 2020年1月24日 金曜日 午後2時47分

Page 6: MODEL PKFY-WL-VLM-E

MEES19K102

PK

FY

-WL

-VL

M-E

5

2. EXTERNAL DIMENSIONS Wall mounted

PKFY-WL32, 40VLM-E Unit: mm

0000005527.BOOK 5 ページ 2020年1月24日 金曜日 午後2時47分

Page 7: MODEL PKFY-WL-VLM-E

MEES19K102

PK

FY

-WL

-VL

M-E

6

3. CENTER OF GRAVITY Wall mounted

3. CENTER OF GRAVITY

PKFY-WL-VLM-E

Model W D H

PKFY-WL20VLM-EPKFY-WL15VLM-EPKFY-WL10VLM-E 773 237

237237

299299299

773773

X130130130

Y340340340

Z(mm)

150150150

PKFY-WL25VLM-EPKFY-WL32VLM-E

773 237 299 130 340 150898 237 299 120 390 150

PKFY-WL40VLM-E 898 237 299 120 390 150

X

D

YW

Z

H

0000005527.BOOK 6 ページ 2020年1月24日 金曜日 午後2時47分

Page 8: MODEL PKFY-WL-VLM-E

MEES19K102

PK

FY

-WL

-VL

M-E

7

4. ELECTRICAL WIRING DIAGRAMS Wall mounted

4. ELECTRICAL WIRING DIAGRAMS

PKFY-WL10, 15, 20, 25, 32, 40VLM-E

0000005527.BOOK 7 ページ 2020年1月24日 金曜日 午後2時47分

Page 9: MODEL PKFY-WL-VLM-E

MEES19K102

PK

FY

-WL

-VL

M-E

8

5. SOUND LEVELS Wall mounted

5. SOUND LEVELS5-1. Sound levels

5-2. NC curves

* Measured in anechoic room.

PKFY-WL10VLM-E

Sound level at anechoic room: Low-(Middle2-Middle)-High

22-26-28-30PKFY-WL15VLM-E 22-26-29-32

Sound level dB (A)ModelWall mounted

1m

Measurementlocation 1m

PKFY-WL20VLM-EPKFY-WL25VLM-EPKFY-WL32VLM-E

22-28-33-3622-30-36-4129-34-38-41

PKFY-WL40VLM-E 30-36-41-45

50

Power Source: 220-230-240V 50Hz/220V 60HzExternal Static Pressure: 0Pa [0.00in.WG]PKFY-WL10VLM-E

50/60Hz

50/60HzLow50/60HzMiddle250/60HzMiddle

High

Octave band center frequencies (Hz)

20-NC

30-NC

40-NC

continuous noiseaudible limit onApproximate minimum

Oct

ave

band

pre

ssur

e le

vel (

dB) 0

dB=2

0μP

a

-NC

60-NC

8k4k2k1k50025012563

70.0

65.0

60.0

55.0

50.0

45.0

40.0

35.0

30.0

25.0

20.0

15.0

10.0

5.0

50

Power Source: 220-230-240V 50Hz/220V 60HzExternal Static Pressure: 0Pa [0.00in.WG]PKFY-WL15VLM-E

50/60Hz

50/60HzLow50/60HzMiddle250/60HzMiddle

High

Octave band center frequencies (Hz)

20-NC

30-NC

40-NC

continuous noiseaudible limit onApproximate minimum

Oct

ave

band

pre

ssur

e le

vel (

dB) 0

dB=2

0μP

a

-NC

60-NC

8k4k2k1k50025012563

70.0

65.0

60.0

55.0

50.0

45.0

40.0

35.0

30.0

25.0

20.0

15.0

10.0

5.0

50

Power Source: 220-230-240V 50Hz/220V 60HzExternal Static Pressure: 0Pa [0.00in.WG]PKFY-WL20VLM-E

50/60Hz

50/60HzLow50/60HzMiddle250/60HzMiddle

High

Octave band center frequencies (Hz)

20-NC

30-NC

40-NC

continuous noiseaudible limit onApproximate minimum

Oct

ave

band

pre

ssur

e le

vel (

dB) 0

dB=2

0μP

a

-NC

60-NC

8k4k2k1k50025012563

70.0

65.0

60.0

55.0

50.0

45.0

40.0

35.0

30.0

25.0

20.0

15.0

10.0

5.0

50

Power Source: 220-230-240V 50Hz/220V 60HzExternal Static Pressure: 0Pa [0.00in.WG]PKFY-WL25VLM-E

50/60Hz

50/60HzLow50/60HzMiddle250/60HzMiddle

High

Octave band center frequencies (Hz)

20-NC

30-NC

40-NC

continuous noiseaudible limit onApproximate minimum

Oct

ave

band

pre

ssur

e le

vel (

dB) 0

dB=2

0μP

a

-NC

60-NC

8k4k2k1k50025012563

70.0

65.0

60.0

55.0

50.0

45.0

40.0

35.0

30.0

25.0

20.0

15.0

10.0

5.0

50

Power Source: 220-230-240V 50Hz/220V 60HzExternal Static Pressure: 0Pa [0.00in.WG]PKFY-WL32VLM-E

50/60Hz

50/60HzLow50/60HzMiddle250/60HzMiddle

High

Octave band center frequencies (Hz)

20-NC

30-NC

40-NC

continuous noiseaudible limit onApproximate minimum

Oct

ave

band

pre

ssur

e le

vel (

dB) 0

dB=2

0μP

a

-NC

60-NC

8k4k2k1k50025012563

70.0

65.0

60.0

55.0

50.0

45.0

40.0

35.0

30.0

25.0

20.0

15.0

10.0

5.0

50

Power Source: 220-230-240V 50Hz/220V 60HzExternal Static Pressure: 0Pa [0.00in.WG]PKFY-WL40VLM-E

50/60Hz

50/60HzLow50/60HzMiddle250/60HzMiddle

High

Octave band center frequencies (Hz)

20-NC

30-NC

40-NC

continuous noiseaudible limit onApproximate minimum

Oct

ave

band

pre

ssur

e le

vel (

dB) 0

dB=2

0μP

a

-NC

60-NC

8k4k2k1k50025012563

70.0

65.0

60.0

55.0

50.0

45.0

40.0

35.0

30.0

25.0

20.0

15.0

10.0

5.0

0000005527.BOOK 8 ページ 2020年1月24日 金曜日 午後2時47分

Page 10: MODEL PKFY-WL-VLM-E

MEES19K102

PK

FY

-WL

-VL

M-E

9

6. TEMPERATURE/AIRFLOW DISTRIBUTIONS Wall mounted

6. TEMPERATURE/AIRFLOW DISTRIBUTIONS6-1. Temperature distributions

<Heating mode>Downward air flow

<Cooling mode>Horizontal air flow

Floor distance (m)

Hei

ght (

m)

Floor distance (m)

Hei

ght (

m)

<Heating mode>Downward air flow

<Cooling mode>Horizontal air flow

Floor distance (m)

Hei

ght (

m)

Floor distance (m)

Hei

ght (

m)

<Heating mode>Downward air flow

<Cooling mode>Horizontal air flow

Floor distance (m)

Hei

ght (

m)

Floor distance (m)

Hei

ght (

m)

PKFY-WL10VLM-E

PKFY-WL15VLM-E

PKFY-WL20VLM-E

Note : These figures show typical temperature distributions in the conditions above. In the actual installation, they may differ from these figures under the influence of air temperature conditions, ceiling height, cooling/heating load,obstacles,etc.

00

1

2

2.4

21

27.027.027.0

25.025.025.0

25.025.025.0

00

1

2

2.4

321

[°C]

29.029.029.0

27.027.027.0

23.023.023.0

25.025.025.0

31.031.031.0

3

[°C]

23.023.023.0

00

1

2

2.4

210

1

2

2.4 [°C]

3 4

[°C]

27.027.027.0

25.025.025.0

25.025.025.0

23.023.023.0

0 21 3 4

23.023.023.027.027.027.0

23.023.023.0

25.025.025.0

29.029.029.0

31.031.031.0

00

1

2

2.4

21 3 54

[°C]

27.027.027.0

25.025.025.0

25.025.025.0

23.023.023.0

00

1

2

2.4

21 3 54

[°C]

31.031.031.0

29.029.029.0

23.023.023.0

25.025.025.0

27.027.027.0

25.025.025.0

23.023.023.0

0000005527.BOOK 9 ページ 2020年1月24日 金曜日 午後2時47分

Page 11: MODEL PKFY-WL-VLM-E

MEES19K102

PK

FY

-WL

-VL

M-E

10

6. TEMPERATURE/AIRFLOW DISTRIBUTIONS Wall mounted

<Heating mode>Downward air flow

<Cooling mode>Horizontal air flow

Floor distance (m)

Hei

ght (

m)

Floor distance (m)

Hei

ght (

m)

<Heating mode>Downward air flow

<Cooling mode>Horizontal air flow

Floor distance (m)

Hei

ght (

m)

Floor distance (m)

Hei

ght (

m)

<Heating mode>Downward air flow

<Cooling mode>Horizontal air flow

Floor distance (m)

Hei

ght (

m)

Floor distance (m)

Hei

ght (

m)

PKFY-WL25VLM-E

PKFY-WL32VLM-E

PKFY-WL40VLM-E

Note : These figures show typical temperature distributions in the conditions above. In the actual installation, they may differ from these figures under the influence of air temperature conditions, ceiling height, cooling/heating load,obstacles,etc.

00

1

2

2.4

21 3 4 5 6

[°C]

00

1

2

2.4

21 3 4 5 6 7

[°C]

27.027.027.0

25.025.025.025.025.025.0 23.023.023.0

00

1

2

2.4

21 3 4 5 6

[°C]

27.027.027.027.027.027.025.025.025.0 25.025.025.0 23.023.023.0

33.033.033.0

31.031.031.0

29.029.029.029.029.029.023.023.023.0

27.027.027.0

25.025.025.0

25.025.025.0 23.023.023.0

00

1

2

2.4

21 3 4 5 6 7

[°C]

.0

2

31.031.031.0

33.033.033.0

29.029.029.029.029.029.027.027.027.0

25.025.025.023.023.023.0

27.027.027.025.025.025.0 23.023.023.0

00

1

2

2.4

21 3 4 5 6 7

[°C]

00

1

2

2.4

21 3 4 5 6 7

[°C]

.

27.027.027.027.027.027.0

25.025.025.0

25.025.025.0

23.023.023.0

.0

31.031.031.0

33.033.033.0

29.029.029.0 29.029.029.027.027.027.0

25.025.025.023.023.023.0

27.027.027.0

25.025.025.0 23.023.023.0

0000005527.BOOK 10 ページ 2020年1月24日 金曜日 午後2時47分

Page 12: MODEL PKFY-WL-VLM-E

MEES19K102

PK

FY

-WL

-VL

M-E

11

6. TEMPERATURE/AIRFLOW DISTRIBUTIONS Wall mounted

6-2. Airflow distributions

PKFY-WL10VLM-E

Note : These figures show typical airflow distributions in the conditions above. In the actual installation, they may differ from these figures under the influence of air temperature conditions, ceiling height, cooling/heating load,obstacles,etc.

<Heating mode>Downward air flow

<Cooling mode>Horizontal air flow

Floor distance (m)

Hei

ght (

m)

Floor distance (m)

Hei

ght (

m)

<Heating mode>Downward air flow

<Cooling mode>Horizontal air flow

Floor distance (m)

Hei

ght (

m)

Floor distance (m)

Hei

ght (

m)

<Heating mode>Downward air flow

<Cooling mode>Horizontal air flow

Floor distance (m)

Hei

ght (

m)

Floor distance (m)

Hei

ght (

m)

PKFY-WL15VLM-E

PKFY-WL20VLM-E

[m/s] [m/s]

[m/s] [m/s]

[m/s] [m/s]

00

1

2

2.4

21 00

1

2

2.4

3213

00

1

2

2.4

210

1

2

2.4

3 4 0 21 3 4

00

1

2

2.4

21 3 54 00

1

2

2.4

21 3 54

1.01.01.0

0.50.50.5

0.50.50.5

1.01.01.0

1.01.01.01.51.51.5

0.50.50.5

0.50.50.5

1.01.01.0

1.51.51.5

1.01.01.01.51.51.5

2.02.02.0

0.50.50.5

1.01.01.0

1.51.51.5

2.02.02.0

0.50.50.50.50.50.5

0000005527.BOOK 11 ページ 2020年1月24日 金曜日 午後2時47分

Page 13: MODEL PKFY-WL-VLM-E

MEES19K102

PK

FY

-WL

-VL

M-E

12

6. TEMPERATURE/AIRFLOW DISTRIBUTIONS Wall mounted

PKFY-WL25VLM-E

Note : These figures show typical airflow distributions in the conditions above. In the actual installation, they may differ from these figures under the influence of air temperature conditions, ceiling height, cooling/heating load,obstacles,etc.

<Heating mode>Downward air flow

<Cooling mode>Horizontal air flow

Floor distance (m)

Hei

ght (

m)

Floor distance (m)

Hei

ght (

m)

<Heating mode>Downward air flow

<Cooling mode>Horizontal air flow

Floor distance (m)

Hei

ght (

m)

Floor distance (m)

Hei

ght (

m)

<Heating mode>Downward air flow

<Cooling mode>Horizontal air flow

Floor distance (m)

Hei

ght (

m)

Floor distance (m)

Hei

ght (

m)

PKFY-WL32VLM-E

PKFY-WL40VLM-E

[m/s]

[m/s]

00

1

2

2.4

4 531 2 6

00

1

2

2.4

21 3 4 5 6 7 0 21 3 4 5 6 7

7

2.52.52.52.02.02.0

0.50.50.5

0.50.50.5

1.51.51.5

1.01.01.0

[m/s]

00

1

2

2.4

4 531 2 6

2.52.52.5

2.02.02.0

3.03.03.0

0.50.50.5

0.50.50.51.51.51.5

1.01.01.0

1.01.01.0

1.51.51.52.02.02.02.52.52.5

0.50.50.5

0.50.50.5

[m/s]

0

1

2

2.4

01.01.01.0

1.51.51.5

2.02.02.0

2.52.52.5

0.50.50.5

0.50.50.5

[m/s]

00

1

2

2.4

21 3 4 5 6 7 0 21 3 4 5 6

[m/s]

0

1

2

2.4

0

1.01.01.0

1.51.51.52.02.02.0

2.52.52.53.03.03.0

0.50.50.5

0.50.50.5

1.01.01.0

1.01.01.0

1.51.51.5

2.52.52.5

2.02.02.0

3.03.03.0

0.50.50.5 0.50.50.5

0000005527.BOOK 12 ページ 2020年1月24日 金曜日 午後2時47分

Page 14: MODEL PKFY-WL-VLM-E

MEES19K102

PK

FY

-WL

-VL

M-E

13

7. ELECTRICAL CHARACTERISTICS Wall mounted

7. ELECTRICAL CHARACTERISTICS

Symbols: MCA (Max.Circuit Amps =1.25xFLA), FLA (Full Load Amps)

IFM (Indoor Fan Motor), Output (Fan motor rated output)

PKFY-WL-VLM-EPower supply IFM

Volts/Hz Range +-10% MCA(A) Output (kW) FLA(A)

PKFY-WL10VLM-E

220-240V/50Hz220V/60Hz

Max.: 264VMin.: 198V

0.25 0.030 0.20

PKFY-WL15VLM-E 0.25 0.030 0.20

PKFY-WL20VLM-E 0.32 0.030 0.25

PKFY-WL25VLM-E 0.44 0.030 0.35

PKFY-WL32VLM-E 0.44 0.030 0.35

PKFY-WL40VLM-E 0.57 0.030 0.45

0000005527.BOOK 13 ページ 2020年1月24日 金曜日 午後2時47分

Page 15: MODEL PKFY-WL-VLM-E

MEES19K102

PK

FY

-WL

-VL

M-E

14

8. OPTIONAL PARTS Wall mounted

8. OPTIONAL PARTS8-1. Optional parts line up for the Indoor unit

8-2. Drain pump

8-3. Valve kit

WLV = WL-Type (With an optional valve kit)WL = WL-Type (Without an optional valve kit)WP = WP-Type (Without a built-in valve and not compatible with the optional valve kit)W = W-Type (With a built-in valve)

PKFY-WL10, 15, 20, 25, 32, 40VLM-E

Drain pump

PAC-SK01DM-E

Valve kit

PAC-SK04VK-E

PAC-SK01DM-E

Detailed installation information should be referred to its Installation Manual.

If drain water can not flow out the Indoor unit by gravity and gradient, a Drain-pump for draining is needed.Drain pump PAC-SK01DM-E can pump water up to 850mm [33-1/2 in.] high from the drain pan.

ItemQuantity

Shape

ItemQuantity

Shape

1 Drain pump 2 Screw 3 Drain hose 4 Flexible hose cover1 (M4×16)×1, (M4×35)×6 1 1 2

16 Paper gauge

5 Band

Valve kit is necessary for using HVRF-Y systemIn an HVRF-R2 system, if a valve kit is connected to any of the WL indoor units, all other indoor units must also have a valve.The table below summarizes the connectability of different combinations of indoor units.

Item

Quantity

Shape

Leadwire

Cap

VALVE KIT

1 1 1 1 1 8

Attachment-1 Attachment-2 Band (large) Band (small) Screw

Outdoor UnitIndoor Unit

ConnectionA B C

HVRF-R2System

WLV WLV - ConnectableWLV W - ConnectableWLV WL - Not connectableWLV WP - Not connectableWLV WL W Not connectableWLV WL WP Not connectableWLV W WP Not connectableWL WL - ConnectableWL WP - ConnectableWL W - Not connectableWL WP W Not connectableW WP - Not connectable

0000005527.BOOK 14 ページ 2020年1月24日 金曜日 午後2時47分

Page 16: MODEL PKFY-WL-VLM-E

MEES19K102New publication effective Jan. 2020

Specifications subject to change without notice

WarningDo not use refrigerant other than the type indicated in the manuals provided with the unit and on the nameplate.- Doing so may cause the unit or pipes to burst, or result in explosion or fire during use, repair, or at the time of disposal of the unit.- It may also be in violation of applicable laws.- MITSUBISHI ELECTRIC CORPORATION cannot be held responsible for malfunctions or accidents resulting from the use of the wrong

type of refrigerant.Our air conditioning equipment and heat pumps contain a fluorinated greenhouse gas, R410A/R32.