model emissions standby rating prime rating 60 hertz mqp20cs...
TRANSCRIPT
MULTI-PAK TM
Diesel Powered Generator
Heavy Duty EngineHeavy duty, 4-cycle, diesel engine; naturally aspirated, oil cooled.Electronic speed control governor.Meets EPA emissions standards for mobile off-highway.
AlternatorBrushless, 4-pole, synchronous, 4 lead design.Class H insulation system conforms to NEMA MG1-22, BS5000,CSA-C22-2, IEC-34-1 standards for temperature rise.Sustained short-circuit capability allowing downstream coordinationbreakers to trip without collapsing the generator field.
Drip-proof, self-venting, amortisseur windings.
Epoxy impregnated windings with tropical insulation for increasedenvironmental protection and long life.
Exceptional waveshape and voltage balance; 2/3 pitch winding tominimize harmonic distortion.
Electronic Voltage Regulator
■ Encapsulated electronic voltage regulator precisely regulates thecurrent into the exciter field.Voltage regulation of +1.0% no load to full load.
Full Load AcceptanceAccepts 100% of standby nameplate rating in one step, in compliancewith NFPA, para 5-13.2.6.
Cooling SystemClosed circuit, external oil cooling with ambient temperature rating of40°C (104°F).
Generator Control PanelBasler 2020 microprocessor-based, digital control panel; vibrationisolated and NFPA 110 compliant.Liquid crystal display screen with alphanumeric readout for displayand programming.Self-diagnostic feature continuously verifies processing, memorycircuits and input/output.
Skid and Housing120 mph wind rated, weather-protective, sound-attenuated housing(1/8 in. aluminum - 5052H32).54 gallon, double-wall, sub base fuel cell, UL142 listed.Integral vibration isolatorsSteel battery rack and battery cables.
WarrantyEngine-generator sets are covered by an express written 2-year/2000 hour (whichever occurs first) limited warranty.Optional extended warranties available.
Agency ApprovalUL 2200 - Approved
Model Emissions Standby Rating Prime Rating
MQP20CS EPA Certified60 Hertz
20kW (25kVA) TBD
Standard Features
20kW Full Rated Single PhaseOutput Single Side Service
Smallest Footprint in the Industry
MULTI-PAK TM
Diesel Powered Generator
Rating Guidelines
STANDBY POWER: Rating corresponds to ISO Standard Fuel Stop Power. It isapplicable for supplying standby electrical power at variable load in areas with wellestablished electrical networks in the event of normal utility power failure. Nooverload capability is available for this rating.
PRIME POWER: Rating corresponds to ISO Standard Power for continuousoperation. It is applicable for supplying electrical power at variable load for anunlimited number of hours instead of commercially purchased power. A 10%overload capability is available for this rating.
SINGLE PHASE OUTPUT: Broad range alternators can supply single phase out-put up to 2/3 set rated 3-phase kW at 1.0 P.F. Refer to Amperage chart.
Alternator SpecificationsManufacturer/Model Marathon MagnaPlus 283PSL1516Type 4-Pole Rotating FieldExciter Type Brushless, Shunt Excitation Design
Number of Leads 4 leads
Voltage Regulator SE350Insulation NEMA MG1-1.66Material Class HTemperature Rise 125°C, Standby RatingBearing, Type Single, SealedCoupling Flexible Disk typeCooling Air Volume 250 cfmAmortisseur Windings FullVoltage Regulation (no load to full load) ± 1%Single Step Load Acceptance per NFPA 110 100% of Rating
Engine SpecificationsManufacturer/Model Deutz / F3M2011
Type 4-cycle, natually aspirated, oilcooled / liquid cooled
Cylinder Arrangement 3 In-LineDisplacement 142 in3 (2.3 liter)Bore 3.7 in. (94 mm)Stroke 4.4 in. (112 mm)Compression Ratio 19 : 1Cylinder Block Cast ironCylinder Head Block type, cast ironCrankshaft Modular cast ironBrake Mean Effective Pressure (BMEP) 97.3 psi (671 kPa)Rated RPM 1800 RPM
Max. Power @ Rated RPM (w/o fan) Standby: 30.1 hp (22.1 kW)
Governor Type ElectricalFrequency Regulation:no load to full load
8% under varying loads from noload to 100% rated load.
Frequency Regulation: Steady State ±0.5% of mean value for constantloads from no load to full load.
Air Cleaner Type DryEngine Electrical SystemBattery Charging Alternator - Make MitsubishiGround Type Negative
Volts (DC) 12 VDCAmpere Rating 55AStarter Motor Make/Model Nippon DensoStarter Motor Rated Voltage 12 VDCStarter Motor Battery Capacity 950A
Lubrication SystemType Forced-feed lubrication
Oil Capacity-With Filter 2 gal (7.5 L)
Oil Filter Disposable, spin-on
Oil Pressure At Rated Speed 35 psi
Maximum Oil Temperature 266oF (130oC)
AmperageVoltage Phase Power Factor Amperage
120/240 Volt 1 1.0 83
MULTI-PAK TM
Diesel Powered Generator
GENERATOR CONTROLLER
Basler DGC-2020 microprocessor-based digital genset controller.12 or 24 Volt DC compatible.Meets all NFPA 110 Level I requirements.Backlit LCD display screen with alphanumeric readout.16 Programmable inputs.SAEJ1939 engine ECU communications.Wide ambient temperature range.Integrated RS485.Automatic transfer control switch.Certified to UL508 and CSA 22.2 #14, CE approved
AC Metering Display:Voltage/Amperage/FrequencyGenerator Phase Voltage / CurrentGenerator Frequency
Engine Information Display:Engine Temperature /Oil Pressure (psi)Battery Voltage (DC) / TachometerHourmeter
Timer Countdown Display:Engine Start DelayOil BypassOvercrankCycle CrankRest PeriodStarter Re-engage DelayBypass Delay
Minor Fault Warning Display:Switch Not In AutoLow Fuel LevelLow Oil Pressure AlarmLow Engine TemperatureHigh Engine Temperature AlarmLow Battery VoltageHigh Battery VoltageWeak Battery ConditionBattery Charger Input FailUndervoltageUnderfrequencyOverfrequencyOvercurrent
Major Fault Shutdown Display:OvervoltageEmergency StopLoss Of SpeedOvercrankOverspeedLow Oil PressureHigh Engine TemperatureLow Coolant LevelSpare Programmable Digital Faults
Switches And Operating Controls:Run / Off / Auto / Load Test ButtonsDecrement / Increment / Previous(Exit) /Next (Enter) Program ButtonsEmergency Stop ButtonAudible Alarm HornAlarm Horn Silence ButtonLamp Test ButtonFault Reset FunctionRJ45 Remote Communications,External Expansion Module Ports
Control LED Indicators:Switch Position (Run, Off, Auto,Load Test)Common Alarm (Minor Fault)Common Shutdown (Major Fault)Generator Ready (When in Auto)Speed SignalEmergency Stop
Standard Controller Features
Derating FactorsFor non-standard site conditions, derate according to ISO 3046.Under the terms of the guarantee, the rating selected must beappropraite to the operational condtions of the engine.
Cooling SystemType External oil cooling
Ambient Temperature Rating 40°C (104°F)
Coolant (Oil) Capacity 2.1 gal (8.0 L)Coolant Flow 2100 L/h (9.2 g/min)
Radiator Cooling Air 21 ft3/sec
Heat Rejection To Coolant 784.9 Btu/min (13.8 kW)
Fan Horsepower 0.7 kW
Max. Coolant Temperature 275°F (135°C)
Fuel SystemFuel Injection Pump Type Single injectionRecommended Fuel ASTM-D975 No.1 and No. 2 DieselFeed Pump Maximum Suction Head 3 m (118 in)Fuel Filter Replaceable cartridge
Max. Fuel Flow 8.1 gal/h (30.7 L/h)Fuel Consumption
Diesel Fuel At % of Load gal/hr (L/hr)100% 1.5 (5.7)75% 1.2 (4.5)50% 0.8 (3.0)
25% 0.7 (2.6)
Exhaust SystemExhaust Flow at Rated kW 450 m3/h (264.8 cfm)Exhaust Temperature at Rated kW 1274°F (690°C)
Maximum Allowable Backpressure 65 mbar (26 in/H2O)Heat Rejection To Exhaust TBD
MULTI-PAK TM
Diesel Powered Generator
Alternator❑ 3 Phase Alternator❑ Generator Strip Heater❑ Permanent Magnet Generator (PMG)Control Panel❑ Remote Monitoring and Generator
Network Communications Link❑ Voltage Adjusting Rheostat❑ Frequency Adjusting PotentiometerCooling System❑ Coolant Heater❑ Low Coolant Shutdown Safety
Engine❑ Engine Crankcase Ventilation FilterOpen Unit❑ Critical Exhaust Silencer❑ Exhaust Mounting PackageElectrical System❑ Battery❑ Environmental Plastic Battery Box with Lid❑ Battery Charger, Equalize/Float Type
3.5 Amperes / 20 VAC❑ Battery Charger w/Alarms, Equalize/Float
Type, 10 Amperes / 20 VAC
Generator Set Options
Backfeed to a utility system can cause electrocution and/or propertydamage. Do not connect to any building’s electrical system except throughan approved device. Specifications are subject to change without notice.
Your MQ Power dealer is:
© COPYRIGHT 2007, MQ POWERRev. 0 (04-07) MQP20CS_Multi-Pak
MQ POWERPOST OFFICE BOX 6254CARSON, CA 90749310-537-3700 • 800-883-2551FAX: 310-632-2656E-MAIL: [email protected]: www.mqpower.com
Automatic Transfer Switch❑ Amperage ______________________❑ No. Poles _______________________❑ Type Enclosure __________________❑ OptionsMiscellaneous❑ Main Line Circuit Breaker❑ Main Line Circuit Breaker Options
❑ Auxiliary Contacts❑ DC Shunt Trip
❑ Remote Annunciator Panel❑ Remote Emergency Stop Kit❑ Wall-PAKTM Mounting Kit❑ Vibration Isolators, Spring Type
WeightDry Weight Wet Weight
1496 lbs. 1866 lbs.